Contents

Toshiba BMS-SM1280HTLE Smart Manager Owner's Manual PDF

1 of 12
1 of 12

Summary of Content for Toshiba BMS-SM1280HTLE Smart Manager Owner's Manual PDF

SMART MANAGER

Model name:

BMS-SM1280HTLE

Owners Manual

Save These Instructions!

ENGLISH

+00DE93919001_01EN.book Page 1 Wednesday, January 5, 2011 3:09 PM

2-EN

Smart Manager Owners Manual

Contents 1 Precautions for Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2 Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

4 Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5 Group Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

6 Zone Operation and Simultaneous Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Thank you very much for purchasing TOSHIBA Smart Manager. This manual explains how to use the main unit of the Smart Manager. For the usage of the WEB TYPE Smart Manager, refer to its specific Owner's Manual.

+00DE93919001_01EN.book Page 2 Wednesday, January 5, 2011 3:09 PM

Smart Manager Owners Manual

EN

+00DE93919001_01EN.book Page 3 Wednesday, January 5, 2011 3:09 PM

1 Precautions for Safety Important information is described in the product itself and the manuals to prevent injury to the user and other

persons, and damage to property, and for safe and correct use.Make sure to thoroughly understand the following details (descriptions and graphic symbols) before reading the text, and make sure to observe the precautions.

Keep this Manual at accessible place for future reference.

Indication Meaning of Indication

Text set off in this manner indicates that failure to adhere to the directions in the warning could result in serious bodily harm (*1) or loss of life if the product is handled improperly.

Text set off in this manner indicates that failure to adhere to the directions in the caution could result in serious bodily injury (*2) or damage (*3) to property if the product is handled improperly.

*1: Serious bodily harm indicates loss of eyesight, injury, burns, electric shock, bone fracture, poisoning, and other injuries which leave aftereffect and require hospitalization or long-term treatment as an outpatient.

*2: Bodily injury indicates injury, burns, electric shock, and other injuries which do not require hospitalization or long- term treatment as an outpatient.

*3: Damage to property indicates damage extending to buildings, household effects, domestic livestock, and pets.

Symbols Meaning of Symbols

" Indicates prohibited items. The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol.

" Indicates compulsory (mandatory) items. The actual contents of the obligation indicated by a picture or text placed inside or next to the graphic symbol.

Only a qualified installer or qualified service person is allowed to do installation work. Installation requires specialized knowledge and skills. If installation is carried out by an unqualified individual, fire or electric shock may result.

If an abnormality occurs (burning odour), stop operations, and turn off the circuit breaker. Otherwise, fire or electric shock may result. Consult your dealer to repair the product.

Do not disassemble, modify, repair or move the product yourself. Doing so may cause fire, electric shock or injury. Ask a qualified installer or qualified service person to do any repairs or to move the product.

Do not operate the buttons with wet hands. Doing so may cause electric shock.

WARNING

CAUTION

WARNING

CAUTION

3-EN

Smart Manager Owners Manual

4-EN

+00DE93919001_01EN.book Page 4 Wednesday, January 5, 2011 3:09 PM

2 Specification Using the Smart Manager, you can control up to 128 groups of air conditioners by line, zone or group; you can run/ stop them and change their settings centrally. The Smart Manager also displays the status and settings of the air conditioners.

External Dimensions Central Controller

Power Unit

Line Two lines, line 1 and line 2, can be connected to the Smart Manager to communicate with air conditioners. The Smart Manager can manage all air conditioners connected to the same line at once.

Zone In the zone setting mode, you can make zones by grouping air conditioners. You can make up to 64 zones (zone 1 - zone 64). The Smart Manager can manage all air conditioners in a zone at once. (For setting zones, refer to the Installation Manual.)

Part name Central Controller Power Unit

Model name BMS-SM1280HTLE

Power supply Use bundled power unit.

220 - 240 VAC, 50/60 Hz

Power consumption 7W

Connectable unit number

Indoor unit Up to 128 units (Line1: Up to 64 units, Line2: Up to 64 units)

Energy monitoring interface Up to 4 units.

Digital input/output interface Up to 4 units

Operating temperature / humidity 0 oC to 40 oC, 10 to 90 %RH (no condensation)

Dimention 120(H) x 180(W) x 64(D) mm 114(H) x 177(W) x 50(D) mm

Mass 0.8 kg 0.9 kg

180

1 2 0

19

140

45

9 0

9 0

1 1

4

1 0 2

12

153

12

177

6 - 5.5

12 153 50

52.4

12

182.7

Smart Manager Owners Manual

EN

+00DE93919001_01EN.book Page 5 Wednesday, January 5, 2011 3:09 PM

3 System Configuration

* Up to 64 zones and 64 groups per line can be managed. (This Smart Manager controls 2 lines, 128 zones, and 128 groups in total.)

* Groups that can be registered in each zone must meet the following conditions. 1. Groups are connected to the same line. 2. Groups are in the same group number range when the control group selection is used.

* In the control group selection, the Smart Manager displays only for air conditioners in the set group number range. (For details, refer to the Installation Manual.)

ZONE 17

LINE1 ALL

LINE2 ALL

ZONE 32ZONE 42ZONE 33

ZONE 1 ZONE 2 ZONE 3 ZONE 9 ZONE 13

Gr55 Gr58Gr50 Gr59 Gr64

ZONE 17

ZONE 49

ZONE 22

ZONE 48ZONE 39

ZONE 45 ZONE 59

ZONE 1

Gr1

Gr17

Gr33 Gr39 Gr42 Gr48Gr35 Gr43

Gr49 Gr55 Gr58 Gr64Gr50 Gr60

Gr23 Gr28 Gr32Gr19 Gr30

Gr5 Gr8 Gr16Gr2 Gr10

Gr1 Gr5 Gr10 Gr16Gr2 Gr11

Gr17 Gr22 Gr25 Gr32Gr19 Gr27

Gr33 Gr39 Gr40 Gr48Gr35 Gr45

Gr49 r r

LINE 1

Smart Manager

LINE 2

Gr=Group

5-EN

Smart Manager Owners Manual

6-EN

+00DE93919001_01EN.book Page 6 Wednesday, January 5, 2011 3:09 PM

4 Operating Instructions

Button operation

A: LINE button

Switches line 1 (display 1), line 2 (display 2)

B: ALL/ ZONE/ GROUP button

Switches ALL, ZONE, and GROUP.

: Selects all groups on the selected line simultaneously.

: Selects all groups in the specified zone.

: Selects a group.

Group 1 to 64 connected to the same line can configure zones. Groups connected to different lines cannot be specified for the same zone. This remote controller can control up to 2 lines, 128 zones, and 128 groups.

C: ZONE button

: Increments the zone number. : Decrements the zone number.

* There are up to 64 zones per line. (128 groups in total).

D: GROUP button

: Increments the group number. : Decrements the group number.

* There are up to 64 groups per line. (128 groups in total).

E: MODE button

Switches operation mode. (* Selectable operation modes vary depending on models.) AUTO: Automatically switches heating operation and cooling operation alternately. HEAT: Performs heating operation. DRY : Performs dehumidifying operation. COOL: Performs cooling operation. FAN : Performs FAN operation. * When lights, operation mode is fixed to COOL or HEAT by the remote control

system.

F: FAN button

Switches air volume. (* Selectable air volume levels vary depending on models.) AUTO: Air volume is automatically switched by the indoor unit. HEAT: Large air volume (Fan speed: High) MED.: Medium air volume (Fan speed: Medium) LOW : Small air volume (Fan speed: Low) * While is displayed, air volume is fixed and cannot be selected.

A B

C D

E

F

G H I

J

K

LMNOPQRT S

Smart Manager Owners Manual

EN

+00DE93919001_01EN.book Page 7 Wednesday, January 5, 2011 3:09 PM

* [Return-back operation] The return-back operation is a function to return the temperature automatically to the set temperature in a predetermined time period if a temperature lower than the specified temperature (for cooling) or higher than the specified temperature (for heating) is set on the remote controller. (For details, refer to the Installation Manual.)

* For the details of power saving mode, refer to the Owners Manual of the air conditioner.

G: Run lamp Indicates the operating status of the selected group. OFF: The selected group is not operating. ON: The selected group is operating. Flashing: When an error occurs or the protective device is activated

H: ON button Starts operation.

I: OFF button

Stops operation.

J: SET TEMP. button

Increases the set temperature. Decreases the set temperature.

K: RESET button Used to reset settings. (Do not usually use this button.)

L: SWING/FIX button

Switches the auto-swing mode and louver direction when no remote controller is used. * This button is disabled in the ALL or ZONE mode.

M: VENT button

Used when a commercially available ventilation fan is connected. Pressing this button runs or stops the connected ventilation fan. When operation of air conditioners is started or stopped, the ventilation fan is also started or stopped at the same time. (While the ventilation fan is running, is displayed on the display.) * When appears on the display when the VENT button is pressed, no ventilation fan is

connected. * This button is used to operate and stop the damper when a heat exchange ventilators is connected.

N: SAVE button

Drives the air conditioner into the power saving mode. * When appears on the display, the power saving mode is not available for the air

conditioner.

O: CENTRAL button

Switches CENTRAL 1 to CENTRAL 4 in the central control mode. No indication: Central control is cleared (individual operation) * This button is disabled in the remote controller mode. Individual: Controls with the remote controller are possible. CENTRAL 1:Disables operation start/stop using the remote controller. CENTRAL 2:Disables operation start/stop, operation mode switching, and temperature setting using the

remote controller. CENTRAL 3:Disables operation mode switching and temperature setting using the remote controller. CENTRAL 4:Disables operation mode switching using the remote controller.

P: CL button Erases the filter mark on the display. This button is also used for the initial settings.

Q: SET button Used for service or special operations. (Do not usually use these buttons.)

R: CHECK button

S: ITEM button

Used for enable/disable settings for return-back operation* and timer operation. : Selects an item to be set sequentially. (The selected item and the mark light.) : Enables or disables the selected item.

* Selectable items may vary depending on models. T:

SELEC T button

7-EN

Smart Manager Owners Manual

8-EN

+00DE93919001_01EN.book Page 8 Wednesday, January 5, 2011 3:09 PM

Indications on the LCD panel

A: ALL/ZONE/GROUP , , or is displayed.

B: Line number

C: Zone number The selected line number, zone number or group number is displayed.

1.2

1~64

1~64

D: Group number Connected groups are automatically recognized and displayed. When a group is specified with the GROUP button, it is displayed like .

E: Operation mode The current operation mode is displayed. AUTO: HEAT: DRY: COOL: FAN:

* When lights when the button is pressed, switching of HEAT and COOL operation mode is disabled.

F: Temperature The set temperature is displayed.

G: Air volume One of AUTO , HEAT , MED. , LOW , or FIXED is displayed.

B C D E

GHIJK LM

A

Q P O N

F

When a line is selected, the ( ) mark of the selected line number flashes.

The number lights up when any controllable unit is detected on the line.

When both line 1 and line 2 are selected, the line of the flashing ( ) mark is displayed.

The underline lights when there is at least one operating air conditioner on the line.

The underline flashes when an alarm occurs.

Flashing: Shows the group whose settings are displayed on the panel.

Lighting: Shows selected groups.

Underline: Shows that the group is operating.

The underline flashes when an alarm occurs.

Smart Manager Owners Manual

EN

+00DE93919001_01EN.book Page 9 Wednesday, January 5, 2011 3:09 PM

H: Check code When the selected air conditioner is abnormal, its unit number and the check code are displayed.

I: Louver position/swing Louver position or louver swinging is displayed. (When no remote controller is used.)

J: Functions (1) : Lights when the power saving mode is activated.

: Lights when a ventilation fan is running.

: Lights when the or button is pressed though the function is not provided.

K: Functions (2) : Displayed when functions of schedule (*) and return-back operation enabled activated. * (A separately sold weekly timer is required.)

L: Functions (3) : Indicates that filters should be replaced.

: Indicates that a test run is being executed.

: Displayed when the air conditioner cannot operate with the selected operation mode (when heating and cooling modes are mixed in the multi- indoor unit control system).

: Displayed at the beginning of heating operation or during defrosting operation. While this mark is displayed, the indoor fan stops.

M: Central control : The selected operation prohibited setting (CENTRAL 1, 2, 3, or 4) is displayed in the central control mode.

: Displayed when the central control system is controlling. When the , , , or SET TEMP. button is pressed

with remote controller operation disabled by the central control system, flashes and no setting change is accepted.

N: Flashes for several minutes when the power switch is turned on. While this mark is flashing, no setting is enabled because the Smart Manager is recognizing connected groups.

O:

(Controller Prohibition mark)

Lights while the controller prohibition function is activated. (While this mark is lighting, no operation is enabled.) * Pressing the , , and buttons simultaneously switches controller prohibition ON/

OFF.

P: Lights in the emergency stop state due to an alarm signal input. (Ex. fire alarm)

Q:

(Operating mark)

Lights when at least one controlled air conditioner is operating. Flashes when at least one air conditioner is abnormal or the protective device is activated.

9-EN

Smart Manager Owners Manual

10-EN

+00DE93919001_01EN.book Page 10 Wednesday, January 5, 2011 3:09 PM

5 Group Operation

* Indications on the LCD of the Smart Manager remain unchanged even when operation is stopped.

Power on Turn on the power of the remote controller. (Buttons on the remote controller are disabled while is displayed, but this is not a fault.)

1 Line switching Select line 1 with the button.

2 ALL/ZONE/GROUP Select with the button.

3 Group switching Select group number 4 with the GROUP and buttons. (Group number 4 blinks like .)

4 ON Press the ON button to start operation.

5 Operation mode switching Select COOL mode with the button.

6 Air volume switching Select AUTO air volume with the button.

7 Temperature setting Set temperature to 24C with the SET TEMP. and buttons.

8 Swing/wind direction setting (When no remote controller is used)

Select a louver position or up/down swinging with the button.

9 Central/individual (Only in the central control mode)

Change the setting with the button. Individual: Controls with the remote controller are possible. CENTRAL 1:Disables operation start/stop using the remote controller. CENTRAL 2:Disables operation start/stop, operation mode switching, and temperature

setting using the remote controller. CENTRAL 3:Disables operation mode switching and temperature setting using the remote

controller. CENTRAL 4:Disables operation mode switching using the remote controller.

CENTRAL is displayed for central or individual control other than above.

STOP Press the OFF button to stop operation.

(Example) Operating LINE 1, GROUP 4 (Cooling at 24C, air volume: AUTO)

2 1

3

4

65

7

8

STOP

9

24C

Smart Manager Owners Manual

EN

+00DE93919001_01EN.book Page 11 Wednesday, January 5, 2011 3:09 PM

6 Zone Operation and Simultaneous Operation

(Example) Performing zone operation (LINE 1, ZONE 8, GROUP 34~42 cooling at 24C, air volume: AUTO) and simultaneous operation (LINE 1, cooling at 24C, air volume: AUTO)

* When or is displayed, the button is disabled. * Settings when ALL or ZONE is selected: Only the contents that are set in the ALL or ZONE mode are set in each

air conditioner. (Example) When the button is pressed in the ALL or ZONE mode, only the operation mode is set in each air conditioner.

* Indications on the LCD of the Smart Manager remain unchanged even when operation is stopped.

2 1

3

4

6

5 7

STOP

8

Zone operation (LINE 1, ZONE 8, cooling at 24C, air volume: AUTO)

Simultaneous operation (LINE 1, cooling at 24C, air volume: AUTO)

Power on Turn on the power of the remote controller (Buttons on the remote controller are disabled while is displayed, but this is not a fault.)

1 Line switching Select line 1 with the button.

2 ALL/ZONE/GROUP Select with the button. Select with the button.

3 Zone switching Select 8 ZONE with the ZONE and buttons. (8 is displayed.)

(Not necessary) (1 is displayed.)

4 ON Press the button to start operation. (Operation starts one group after another at about one- second interval.)

5 Operation mode switching Select COOL mode with the button.

6 Air volume switching Select AUTO air volume with the button.

7 Temperature setting Set temperature to 24C with the SET TEMP. and buttons.

8 Central/individual (Only in the central control mode)

Change the setting with the button. Individual: Controls with the remote controller are possible. CENTRAL 1:Disables operation start/stop using the remote controller. CENTRAL 2:Disables operation start/stop, operation mode switching, and temperature setting

using the remote controller. CENTRAL 3:Disables operation mode switching and temperature setting using the remote

controller. CENTRAL 4:Disables operation mode switching using the remote controller.

CENTRAL is displayed for central or individual control other than above.

Manualsnet FAQs

If you want to find out how the BMS-SM1280HTLE Toshiba works, you can view and download the Toshiba BMS-SM1280HTLE Smart Manager Owner's Manual on the Manualsnet website.

Yes, we have the Owner's Manual for Toshiba BMS-SM1280HTLE as well as other Toshiba manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Owner's Manual should include all the details that are needed to use a Toshiba BMS-SM1280HTLE. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Toshiba BMS-SM1280HTLE Smart Manager Owner's Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Toshiba BMS-SM1280HTLE Smart Manager Owner's Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Toshiba BMS-SM1280HTLE Smart Manager Owner's Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Toshiba BMS-SM1280HTLE Smart Manager Owner's Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Toshiba BMS-SM1280HTLE Smart Manager Owner's Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.