SMC PF2A20 Monitor Operation Manual PDF

1 of 44
1 of 44

Summary of Content for SMC PF2A20 Monitor Operation Manual PDF

No.PF-OMH0003-F

PRODUCT NAME

4-channel Flow Monitor

(Remote type monitor unit)

MODEL / Series / Product Number

PF2A20# PF2W20# PF2D20#

-1-

No.PF-OMH0003-F

Table of Contents

Safety Instructions 2

Model Indication and How to Order 9

Summary of Product parts 12

Definition and terminology 13

Mounting and Installation 15

Installation 15

Wiring 16

Outline of setting 19

List of outputs 20

Initialize mode 21

Default settings 21

Setting procedure of Initialize mode 22

Function selection mode 26

Default settings 26

F_1 Input procedure of the Set value of instantaneous output 27

F_2 Input procedure of the Set value of accumulated output 28

F_3 Copy function 30

Other functions 31

Channel scan function 31

Peak/Bottom value display 31

Key-lock function 32

Maintenance 33

Troubleshooting 34

Cross-reference for troubleshooting 34

Error indication 36

Specification 37

Specifications 37

Dimensions 41

-2-

No.PF-OMH0003-F

Safety Instructions

These safety instructions are intended to prevent hazardous situations and/or equipment damage. These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or "Danger". They are all important notes for safety and must be followed in addition to International Standards (ISO/IEC)*1), and other safety regulations. *1) ISO 4414: Pneumatic fluid power -- General rules relating to systems.

ISO 4413: Hydraulic fluid power -- General rules relating to systems. IEC 60204-1: Safety of machinery -- Electrical equipment of machines. (Part 1: General requirements) ISO 10218: Manipulating industrial robots -Safety. etc.

Caution Caution indicates a hazard with a low level of risk which, if not avoided, could

result in minor or moderate injury.

Warning Warning indicates a hazard with a medium level of risk which, if not avoided,

could result in death or serious injury.

Danger Danger indicates a hazard with a high level of risk which, if not avoided, will

result in death or serious injury.

Warning 1. The compatibility of the product is the responsibility of the person who designs the

equipment or decides its specifications. Since the product specified here is used under various operating conditions, its compatibility with specific equipment must be decided by the person who designs the equipment or decides its specifications based on necessary analysis and test results. The expected performance and safety assurance of the equipment will be the responsibility of the person who has determined its compatibility with the product. This person should also continuously review all specifications of the product referring to its latest catalog information, with a view to giving due consideration to any possibility of equipment failure when configuring the equipment.

2. Only personnel with appropriate training should operate machinery and equipment. The product specified here may become unsafe if handled incorrectly. The assembly, operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced.

3. Do not service or attempt to remove product and machinery/equipment until safety is confirmed. 1. The inspection and maintenance of machinery/equipment should only be performed after measures to

prevent falling or runaway of the driven objects have been confirmed. 2. When the product is to be removed, confirm that the safety measures as mentioned above are

implemented and the power from any appropriate source is cut, and read and understand the specific product precautions of all relevant products carefully.

3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and malfunction. 4. Contact SMC beforehand and take special consideration of safety measures if the

product is to be used in any of the following conditions. 1. Conditions and environments outside of the given specifications, or use outdoors or in a place

exposed to direct sunlight. 2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping,

vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and beverages, emergency stop circuits, clutch and brake circuits in press applications, safety equipment or other applications unsuitable for the standard specifications described in the product catalog.

3. An application which could have negative effects on people, property, or animals requiring special safety analysis.

4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by using a mechanical protective function, and periodical checks to confirm proper operation.

-3-

No.PF-OMH0003-F

Safety Instructions

Caution 1.The product is provided for use in manufacturing industries.

The product herein described is basically provided for peaceful use in manufacturing industries. If considering using the product in other industries, consult SMC beforehand and exchange specifications or a contract if necessary. If anything is unclear, contact your nearest sales branch.

Limited warranty and Disclaimer/Compliance Requirements The product used is subject to the following "Limited warranty and Disclaimer" and "Compliance Requirements". Read and accept them before using the product.

Limited warranty and Disclaimer 1. The warranty period of the product is 1 year in service or 1.5 years after the product is

delivered, whichever is first.2) Also, the product may have specified durability, running distance or replacement parts. Please consult your nearest sales branch.

2. For any failure or damage reported within the warranty period which is clearly our responsibility, a replacement product or necessary parts will be provided. This limited warranty applies only to our product independently, and not to any other damage incurred due to the failure of the product.

3. Prior to using SMC products, please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products. 2) Vacuum pads are excluded from this 1 year warranty.

A vacuum pad is a consumable part, so it is warranted for a year after it is delivered. Also, even within the warranty period, the wear of a product due to the use of the vacuum pad or failure due to the deterioration of rubber material are not covered by the limited warranty.

Compliance Requirements 1. The use of SMC products with production equipment for the manufacture of weapons of

mass destruction (WMD) or any other weapon is strictly prohibited. 2. The exports of SMC products or technology from one country to another are governed

by the relevant security laws and regulation of the countries involved in the transaction. Prior to the shipment of a SMC product to another country, assure that all local rules governing that export are known and followed.

Caution SMC products are not intended for use as instruments for legal metrology. Products that SMC manufactures or sells are not measurement instruments that are qualified by pattern approval tests relating to the measurement laws of each country. Therefore, SMC products cannot be used for business or certification ordained by the measurement laws of each country.

-4-

No.PF-OMH0003-F

Operator

This operation manual is intended for those who have knowledge of machinery using pneumatic equipment, and have sufficient knowledge of assembly, operation and maintenance of such equipment. Only those persons are allowed to perform assembly, operation and maintenance.

Read and understand this operation manual carefully before assembling, operating or providing maintenance to the product.

Safety Instructions

Warning Do not disassemble, modify (including changing the printed circuit board) or repair.

An injury or failure can result.

Do not operate the product outside of the specifications.

Do not use for flammable or harmful fluids.

Fire, malfunction, or damage to the product can result.

Verify the specifications before use.

Do not operate in an atmosphere containing flammable, explosive or corrosive gas.

Fire, explosion or corrosion can result.

This product is not designed to be explosion proof.

Do not use the product in a place where static electricity is a problem.

Otherwise it can cause failure or malfunction of the system.

If using the product in an interlocking circuit:

Provide a double interlocking system, for example a mechanical system

Check the product regularly for proper operation

Otherwise malfunction can result, causing an accident.

The following instructions must be followed during maintenance:

Turn off the power supply

Ensure the flow is shut off before performing maintenance

Otherwise an injury can result.

-5-

No.PF-OMH0003-F

Caution Do not touch the terminals and connectors while the power is on.

Otherwise electric shock, malfunction or damage to the product can result.

Do not touch the piping or its connected parts when the fluid is at high temperature.

It may lead to burnt.

Ensure the piping cools sufficiently before touching.

After maintenance is complete, perform appropriate functional inspections and leak tests. Stop operation if the equipment does not function properly or there is a leakage of fluid.

When leakage occurs from parts other than the piping, the product might be faulty.

Disconnect the power supply and stop the fluid supply.

Do not apply fluid under leaking conditions.

Safety cannot be assured in the case of unexpected malfunction.

NOTE

Follow the instructions given below when designing, selecting and handling the product.

The instructions on design and selection (installation, wiring, environment, adjustment, operation,

maintenance, etc.) described below must also be followed. Product specifications

Use the specified voltage.

Otherwise failure or malfunction can result.

Insufficient supply voltage may not drive a load due to a voltage drop inside the product.

Verify the operating voltage of the load before use.

Do not exceed the specified maximum allowable load.

Otherwise it can cause damage or shorten the lifetime of the product.

Data stored by the product is not deleted, even if the power supply is cut off.

(writing time: 1000000 cycles)

Reserve a space for maintenance.

Allow sufficient space for maintenance when designing the system.

-6-

No.PF-OMH0003-F

Product handling Installation

Do not apply excessive stress to the product when it is panel mounted.

Otherwise damage to the product and disconnection from the panel mount can result. Ensure that the FG terminal is connected to ground when using a commercially available switch-mode

power supply.

Do not drop, hit or apply excessive shock to the product.

Otherwise damage to the internal parts can result, causing malfunction.

Do not pull the lead wire forcefully, not lift the product by pulling the lead wire. (Tensile force 49 N or less)

Hold the product body when handling, to prevent damage, failure or malfunction.

Limit of the power and output cable tensile force is 50 N, and limit of the sensor lead wire tensile force is

25 N.

Never mount the product in a location that will be used as a foothold.

The product may be damaged if excessive force is applied by stepping or climbing onto it.

Wiring

Do not pull the lead wires.

In particular, never lift a product equipped with fitting and piping by holding the lead wires.

Otherwise damage to the internal parts can result, causing malfunction or disconnection of the connector.

Avoid repeatedly bending or stretching the lead wire, or placing heavy load on it.

Repeated bending stress or tensile stress can cause damage to the sheath, or breakage of the wires.

If the lead wire can move, fix it near the body of the product.

The recommended bend radius of the lead wire is 6 times the outside diameter of the sheath, or 33 times the

outside diameter of the wire insulation material, whichever is larger.

Replace any damaged lead wire with a new one.

Wire correctly.

Incorrect wiring can damage the product.

Do not perform wiring while the power is on.

Otherwise damage to the internal parts can result, causing malfunction.

Do not route wires and cables together with power or high voltage cables.

Otherwise the product can malfunction due to interference or noise and surge voltage from power and high voltage

cables.

Confirm proper insulation of wiring.

Poor insulation (interference from another circuit, poor insulation between terminals, etc.) can lead to excess

voltage or current being applied to the product, causing damage.

Keep wiring as short as possible to prevent interference from electromagnetic noise and surge voltage.

Do not use a cable longer than 30 m.

Wire the DC(-) line (blue) as close as possible to the power supply.

When analogue output is used, install a noise filter (line noise filter, ferrite element, etc.) between the

switch-mode power supply and this product.

-7-

No.PF-OMH0003-F

Environment

Do not use the product in an environment that is constantly exposed to the splash of water.

Otherwise failure or malfunction can result. Take measures such as using a cover.

Do not use the product in an environment where corrosive gases or fluids could be splashed.

Otherwise damage to the product and malfunction can result.

Do not use in a place where the product could be splashed by oil or chemicals.

If the product is to be used in an environment containing oils or chemicals such as coolant or cleaning solvent,

even for a short time, it may be adversely affected (damage, malfunction, or hardening of the lead wires).

Do not use in an area where electrical surges are generated.

If there is equipment generates a large electrical surge (solenoid type lifter, high frequency induction furnace, motor,

etc.) close to the product, damage or failure of the internal circuit may occur. Take measures against the surge

sources, and prevent the wires from coming into close contact.

Do not use a load which generates surge voltage.

When a surge-generating load such as a relay or solenoid is driven directly, use a product with a built-in surge

absorbing element.

The product is CE marked, but not immune to lightning strikes. Take measures against lightning strikes

in the system.

Do not use the product in areas that are exposed to vibration or impact.

Otherwise failure or malfunction can result.

Do not use the product in the presence of a magnetic field.

This may lead to the malfunction of the product.

Prevent foreign matter such as remnant of wires from entering the product.

Otherwise failure or malfunction can result.

Do not use the product in areas subject to large temperature cycle.

Heating/cooling cycles other than ordinary changes in temperature can adversely affect the internal structure of the

product Do not expose the product to direct sunlight.

If using in a location directly exposed to sunlight, use a suitable protective cover.

Otherwise failure or malfunction can result. Keep within the operating temperatures range.

The operating temperature range is 0 to 50 oC. Operation below the minimum temperature limit may cause damage or operation failure due to frozen moisture in

the fluid or air. Avoid sudden temperature changes even within the specified temperature range.

Do not operate close to a heat source, or in a location exposed to radiant heat.

Otherwise malfunction can result.

-8-

No.PF-OMH0003-F

Adjustment and Operation

Connect load before turning on the power.

Do not short-circuit the load.

Although an error is displayed when the product load is short circuited, excess current may cause damage to the

product.

Do not press the setting buttons with a sharp pointed object.

This may damage the setting buttons.

Supply the power when there is no flow.

Check regulators and flow adjustment valves before introducing the fluid.

If pressure or flow rate beyond the specified range are applied to the sensor, the sensor unit may be damaged.

Do not attempt to insert or pull the flow rate sensor or its connector when the power is on.

The output is off for 3 seconds after power is supplied.

Use settings suitable for the operating conditions.

Incorrect settings can cause operational failure.

(Refer to page 19 "Outline of setting")

During the initial setting and any subsequent flow rate setting, the product will switch the output

according to the existing settings until the changes are complete.

Confirm the output has no adverse effect on machinery and equipment before setting.

Stop the control system before setting if necessary.

Do not touch the LCD during operation.

The display can vary due to static electricity.

Maintenance

Perform regular maintenance and inspections.

There is a risk of unexpected malfunction of components due to the malfunction of equipment and machinery.

Turn off the power supply, stop the fluid and check the safety before performing any maintenance.

There is a risk of unexpected malfunction.

Do not use solvents such as benzene, thinner etc. to clean the product.

They could damage the surface of the body and erase the markings on the body.

Use a soft cloth to remove stains.

For heavy stains, use a cloth lightly dampened with diluted neutral detergent, then wipe up any residue with a dry

cloth.

-9-

No.PF-OMH0003-F

Model indication and How to Order

-10-

No.PF-OMH0003-F

Option 1

Nil A

without panel mount adapter

with panel mount adapter

B

with panel mount adapter + front protective cover

: Each accessory is not assembled with the product, but shipped together.

Option 2

Nil 4C

without sensor connector

with sensor connector (4 pcs.)

: Each accessory is not assembled with the product, but shipped together.

-11-

No.PF-OMH0003-F

Accessories/Part number

If an accessory is required separately, order using the following part numbers.

Part number Description Remarks Weight

ZS-26-A Power and output cable Length: 2 m 65 g

ZS-26-B Panel mount adapter with waterproof seal, with Mounting screw (3.0 x 8 L) 2 pcs. 10 g

ZS-26-C Panel mount adapter +

front protective cover with waterproof seal, with Mounting screw (3.0 x 8 L) 2 pcs. 15 g

ZS-26-01 Front protective cover

only 5 g

ZS-26-D 48 mm conversion

adapter

The panel which hold is 48 can be mounted to 36 by using the

adapter.

5 g

ZS-28-CA-4

Sensor connector for

PF2A5, PF2W5,

PF3W5

(e-con)

1 pc, Finished O.D.: 1.15 to 1.35, Cover colour: Blue 2 g

ZS-28-CA-2

Sensor connector

for PF2D5

(e-con)

1 pc, Finished O.D.: 0.9 to 1.0, Cover colour: Red 2 g

-12-

No.PF-OMH0003-F

Summary of Product parts

Front

Item Description

Unit display Indicates the unit currently selected, and automatically displays instantaneous

flow or accumulated flow units according to the display mode.

LCD display Displays the flow value, setting mode, and error indication.

Indicator LED (output) Indicates the switch output status. LED is ON when the output is ON.

Indicator LED Indicates the reference condition selected. LED is ON (Red) when normal

condition is selected. (Only the PF2A)

Channel display Indicates the channel selected (CH1 to CH4).

button (UP) Selects the mode or increases the ON/OFF Set value.

button (SET) Press this button to change the mode and to set a value.

button (DOWN) Selects the mode or decreases the ON/OFF Set value.

: Operate only the PF2A2 series.

Back

Sensor connector pin numbers (on the product)

1 DC(+) Brown

2 N.C.

3 DC(-) Blue

4 Sensor input

(1 to 5 V)

White (PF25)

Black (PF3W5)

Power and output connector pin numbers (on the product)

1 DC(+)

2 DC(-)

3 CH1_OUT1

4 N.C.

5 CH2_OUT1

6 CH3_OUT1

7 CH4_OUT1

8 N.C.

Item Description

Sensor connector socket Socket for the sensor connection.

Power and output socket Socket for the power and output connection.

Sensor connector Connector for attaching (crimping) to the sensor lead wire.

Power and output cable Cable to supply power to the product and transmit outputs.

-13-

No.PF-OMH0003-F

Definition and terminology

Terms Meaning

A Accumulated flow

The total amount of fluid that has passed through the device. If an instantaneous flow of

10 L/min continues for 5 minutes, the accumulated flow will be 510 = 50 L.

Accumulated pulse

output

A type of output where a pulse is generated every time a predefined accumulated flow

passes. It is possible to calculate the total accumulated flow by counting the pulses.

Analogue output

Outputs a value proportional to the flow rate. When the analogue output is in the range

1 to 5 V, it will vary between 1 to 5 V according to the rate of flow. The same for

analogue output of 4 to 20 mA.

C Chattering

The problem of the switch output turning ON and OFF repeatedly around the Set value

at high frequency due to the effect of pulsation.

D Digit

Minimum unit for setting/display is 1 digit. When the minimum unit for setting/display is

5 L/min, 3 digits will be 3 x 5 = 15 L/min

Display flow range The range that which can be displayed by the product with a digital display.

F F.S.

(Full span, Full scale)

Stands for "full span" or "full scale", and indicates varied analogue output range at rated

value. For example, when analogue output is 1 to 5 V, F.S. = 5[V] - 1[V] = 4[V], (ref.

1%F.S. = 4[V] x 1% = 0.04[V])

H Hysteresis

The difference between ON and OFF points used to prevent chattering. Hysteresis can

be effective in avoiding the effects of pulsation.

Hysteresis mode Mode where the switch output will turn ON when the flow is greater than the Set value,

and will turn OFF when the flow falls below the Set value hysteresis value.

I Instantaneous flow

The flow passing per unit of time. If it is 10 L/min, there is a flow of 10 L passing through

the device in 1 minute.

Internal voltage drop

The voltage drop across the product (and therefore not applied to the load), when the

switch output is ON. The voltage drop will vary with load current, and ideally should be

0 V.

M Minimum

setting/display unit

The resolution of set and display values. If the minimum setting unit is 1 L/min, the

display will change in 1 L/min steps, e.g. 10..11..12 L/min.

O Operating humidity

range

The ambient humidity range within which the product will meet all published

specifications.

Operating

temperature range

The ambient temperature range within which the product will meet all published

specifications.

R Rated flow range The flow range within which the product will meet all published specifications.

Rated pressure range The pressure range within which the product will meet all published specifications.

Repeatability Reproducibility of the display or analogue output value, when the measured quantity is

repeatedly increased and decreased.

Response time Time from when the target flow is applied until the flow reaches 90% of the Set value.

-14-

No.PF-OMH0003-F

Terms Meaning

S Setting flow range

The range of ON/OFF threshold values that can be set for those products with a switch

output.

Switch output

Output type that has only 2 conditions, ON or OFF. In the ON condition, an indicator

light (output) will show, and any connected load will be powered. In the OFF condition,

there will be no indicator (output) and no power supplied to the load.

T Temperature

characteristics

The amount of variation in the analogue output or display value when ambient

temperature is changed.

U Unit selection function

A function to select display units other than the international unit (SI unit) specified in

the new Japanese measurement law. Flow can only be displayed by SI units in Japan.

W Window comparator

mode

An operating mode in which the switch output is turned on and off depending on

whether the flow is inside or outside the range of two Set values.

-15-

No.PF-OMH0003-F

Mounting and Installation

Installation Never mount the product in a location that will be used as a foothold.

Installing Mounting with the panel mount adapter

Install the product as shown below. The 48 mm conversion adapter is available if required.

The panel mount adapter and the front cover can be rotated 90o for mounting.

Fix the panel mount adapter to the product with the mounting screws (nominal size: 3 x 8 L, 2 pcs.)

supplied.

The front protective cover for panel mounting satisfies IP65 (when 48 mm conversion adapter is used, it

satisfies IP40). However, if the panel mount adapter is not fixed securely or the instrument is not seated

correctly, water might enter. After the product makes contact with the panel, the screws should be further

tightened 1/4 to 1/2 turn.

The self tapping screws cannot be re-used. The product can be mounted on a panel with a thickness of 0.5 to 8 mm.

Refer to the dimension drawing (page 42) for panel cut-out dimensions.

Removing the panel mount adapter

The product with panel mount adapter can be removed from the installation by removing 2 screws and

releasing the hooks at the sides. The hooks can be released by inserting a suitable thin card. Pull the panel mount adapter to the front, and remove the product. If the panel mount adapter is pulled with the hook engaged, the product or the panel mount adapter will be

damaged.

-16-

No.PF-OMH0003-F

Wiring Connections should only be made with the power supply turned off. Use separate routes for the product wiring and any power or high voltage wiring. Otherwise, malfunction

may result due to noise.

Ensure that the FG terminal is connected to ground when using a commercially available switch-mode

power supply. When a switch-mode power supply is connected to the product, switching noise will be

superimposed and the product specification can no longer be met. This can be prevented by inserting a

noise filter, such as a line noise filter and ferrite core, between the switch-mode power supply and the

product, or by using a series power supply instead of a switch-mode power supply.

Connecting the wiring Attaching the sensor connector to the sensor wire

Strip the sensor wire as shown. Do not cut the insulator.

Insert the corresponding wire colour shown in the table into the pin number printed on the sensor

connector, to the bottom.

Pin number on connector Wire colour (PF25) Wire colour (PF3W5)

1 Brown Brown

2 (N.C.) (N.C.)

3 Blue Blue

4 White Black

Check that the above preparation has been performed correctly, then part A shown should be pressed in

by hand to make temporary connection.

Part A should then be pressed in using a suitable tool, such as pliers.

The sensor connector cannot be re-used once it has been fully crimped.

In cases of connection failure such as incorrect order of wires or incomplete insertion, please use the new

connector.

If the sensor is not connected correctly, [---] will be displayed.

-17-

No.PF-OMH0003-F

Connecting/Disconnecting

When connecting, insert the connectors straight into the body until it clicks.

When removing the connector, press down the lever to release the hook from the housing and pull the

connector straight out.

Power and output connector pin numbers (on the cable)

Sensor connector pin numbers (on the cable)

Pin

no. Description

Wire

cable

1 DC(+) Brown

2 DC(-) Blue

3 CH1_OUT1 Black

4 N.C. White

5 CH2_OUT1 Grey

6 CH3_OUT1 Red

7 CH4_OUT1 Green

8 N.C. Yellow

with PF25

Pin

no. Description

Wire

cable

1 DC(+) Brown

2 N.C.

3 DC(-) Blue

4 Sensor input

(1 to 5 V) White

with PF3W5

Pin

no. Description

Wire

cable

1 DC(+) Brown

2 N.C.

3 DC(-) Blue

4 Sensor input

(1 to 5 V) Black

-18-

No.PF-OMH0003-F

Internal circuit and wiring example When the Power and output cable (ZS-26-A) is used, the wire colours will apply as shown in the diagram.

NPN (4 outputs) type PF2A200-

Max. 30 V, 80 mA

Internal voltage drop: 1 V or less

PNP (4 outputs) type PF2A201-

Max. 80 mA

Internal voltage drop: 1.5 V or less

-19-

No.PF-OMH0003-F

Outline of setting

Power is supplied

The output will not operate for 3 seconds after supplying power. The identification code of the product is displayed.

Measurement mode

The mode in which the flow is detected and displayed, and the switch output is operating. This is the basic operating mode; and other modes should be selected for setting changes and other function settings.

Each time the button is pressed, a channel is selected "1 2 3 4 1 ".

The flow value will be displayed for each channel selected.

Press the button to select either instantaneous flow or accumulated flow.

The display of instantaneous flow and accumulated flow can be changed

while the button is pressed.

While pressing the button during the display of accumulated flow,

the accumulation can be started/stopped by pressing the button.

button

press

for 2 sec.

button

press.

Initialize mode (Refer to page 21)

Items below can be set.

Connected sensor Display mode Unit selection function 1

Output mode Switch operation Reference condition 2

Function selection mode

(Refer to page 26)

Items below can be set.

[F_1] Input the Set value of instantaneous output

[F_2] Input the Set value of accumulated output

[F_3] Copy function

Other functions (Refer to page 31)

Items below can be set.

Channel scan function

Peak/Bottom value display

Key-lock function

1: Operate only the product with unit selection function.

2: Operate only the PF2A2 series.

-20-

No.PF-OMH0003-F

List of outputs Find the diagram of the output required in the table below. Perform settings following the Set value column

on the right.

Switch output diagram Output mode Switch

operation Set value

In s

ta n

ta n

e o

u s

f lo

w

Instantaneous

output mode

Non-Reverse

output

Set point 2 Set point 1

2

Hysteresis mode

Set point 1 Set point 2

Window comparator mode

Reverse output

Set point 2 Set point 1

2

Hysteresis mode

Set point 1 Set point 2

Window comparator mode

A c c

u m

u la

te d

f lo

w

Accumulated

output mode

Non-Reverse

output

Upper 3 digits Lower 3 digits

+

Reverse output

Upper 3 digits Lower 3 digits

+

A c

c u

m u

la te

d p

u ls

e

Accumulated

pulse output

mode

Non-Reverse

output

No Set value input

Reverse output

No Set value input

1: In window comparator mode, the hysteresis is fixed at 3 digits. When setting, allow 7 digits or more between Set point 1 and Set point 2.

2: When Set point 1 = Set point 2, chattering may occur.

-21-

No.PF-OMH0003-F

Initialize mode

Default settings

PF2A20 series

Item Default settings Page

Selection of the connected sensor [10L] 1 to 10 L/min type (PF2A510) Page 22

Selection of display mode [d_1] Display instantaneous flow

Page 23 Unit selection function [U_1] L/min

Selection of output mode [o10] Instantaneous output mode

Selection of switch operation [1_n] Reverse output Page 24

Selection of reference condition [Anr] Standard condition

: Operate only the product with unit selection function.

PF2W20 series

Item Default settings Page

Selection of the connected sensor [04L] 0.5 to 4 L/min type (PF2W504) (PF3W504) Page 22

Selection of display mode [d_1] Display instantaneous flow

Page 23 Unit selection function [U_1] L/min

Selection of output mode [o10] Instantaneous output mode

Selection of switch operation [1_n] Reverse output Page 24

: Operate only the product with unit selection function.

PF2D20 series

Item Default settings Page

Selection of the connected sensor [04d] 0.4 to 4 L/min type (PF2D504) Page 22

Selection of display mode [d_1] Display instantaneous flow

Page 23 Unit selection function [U_1] L/min

Selection of output mode [o10] Instantaneous output mode

Selection of switch operation [1_n] Reverse output Page 24

: Operate only the product with unit selection function.

-22-

No.PF-OMH0003-F

Setting procedure of Initialize mode

Press the button in measurement mode to select the channel to be set.

Press the button for 2 seconds or longer.

Selection of the connected sensor The sensor to be connected is selectable before using the product.

If the select connected sensor is changed, the accumulated value and the peak (bottom) value

display are return to default setting.

Press the button to select.

PF2A20 series

[10L]:

[50L]:

[11L]:

[21L]:

[51L]:

1 to

5 to

10 to

20 to

50 to

10 L/min type (PF2A510)

50 L/min type (PF2A550)

100 L/min type (PF2A511)

200 L/min type (PF2A521)

500 L/min type (PF2A551)

PF2W20 series

[04L]:

[20L]:

[40L]:

[11L]:

0.5 to

2 to

5 to

10 to

4 L/min type (PF2W504) (PF3W504)

16 L/min type (PF2W520) (PF3W520)

40 L/min type (PF2W540) (PF3W540)

100 L/min type (PF2W511) (PF3W511)

: Flow display is available for PF3W5 series. Temperature display (Model indication: with T) is not available.

PF2D20 series

[04d]:

[20d]:

[40d]:

0.4 to

1.8 to

4 to

4 L/min type (PF2D504)

20 L/min type (PF2D520)

40 L/min type (PF2D540)

Press the button. (continued)

-23-

No.PF-OMH0003-F

Press the button. SI unit only The product with unit selection function

Selection of display mode Select the display of instantaneous flow or accumulated flow.

Press the button to select.

[d_1]: display instantaneous flow

[d_2]: display accumulated flow

Selection of unit selection function The display unit can only be selected for products with unit selection unction.

Press the button to select.

PF2A20 series Display Instantaneous flow Accumulated flow

[U_1] L/min L

[U_2] CFM x 10-2, CFM x 10-1 ft3 x 10-1, ft3 x 10-2

PF2W20 series Display Instantaneous flow Accumulated flow

[U_1] L/min L

[U_2] gal(US)/min gal(US)

PF2D20 series Display Instantaneous flow Accumulated flow

[U_1] L/min L

[U_2] gal(US)/min gal(US)

: Refer to page 25 for the flow rate when [U_2] is selected.

: Use the unit label included in the product, if necessary.

Press the button.

Selection of output mode Select the switch output mode required referring to the list of outputs (page 20).

Press the button to select.

[o10]: Instantaneous output mode

[o11]: Accumulated output mode

[o12]: Accumulated pulse output

mode

Press the button. (continued)

-24-

No.PF-OMH0003-F

Selection of switch operation Select the switch operation required referring to the list of outputs (page 20).

Press the button to select.

[1_n]: Reverse output

[1_P]: Non-Reverse output

Press the button.

Reference condition selection Operate only the PF2A2 series. Select standard condition or normal condition for the display units.

Press the button to select.

[ Anr]: Standard condition.

Flow display which is converted in

atmospheric pressure at 20 C, 65%R.H.

[ nor]: Normal condition.

Flow display which is converted in

atmospheric pressure at 0 C.

: Flow rate in the specification is the value at standard condition.

If the display unit standard is changed from standard to normal, use the conversion formula.

Flow rate at standard condition x 0.927 = Flow rate at normal condition

: When [nor] is selected, an Indicator light (reference condition) appears.

Press the button.

Setting of initialize mode is completed. Return to measurement mode.

-25-

No.PF-OMH0003-F

Flow specification when [U_2] is selected by the unit selection function

PF2A20 series

Model PF2A20

Applicable sensor PF2A510 PF2A550 PF2A511 PF2A521 PF2A551

F lo

w

Rated flow range 3.5 to 35.5

CFM x 10-2

18 to 176

CFM x 10-2

3.5 to 35.5

CFM x 10-1

7 to 71

CFM x 10-1

18 to 176

CFM x 10-1

In s ta

n ta

n e o u s

fl o

w

Setting/display flow

range

1.0 to 38.5

CFM x 10-2

8 to 186

CFM x 10-2

1.0 to 38.0

CFM x 10-1

2 to 76

CFM x 10-1

8 to 186

CFM x 10-1

Min. setting/display unit 0.5

CFM x 10-2

2.0

CFM x 10-2

0.5

CFM x 10-1

1.0

CFM x 10-1

2.0

CFM x 10-1

A c c u m

u la

te d

fl o

w

Setting/display flow

range 0 to 999999 ft3 x 10-2 0 to 999999 ft3 x 10-1

Min. setting/display unit 1 ft3 x 10-3 1 ft3 x 10-1

Conversion of accumulated pulse 0.5

ft3 x 10-2/pulse

2.0

ft3 x 10-2/pulse

0.5

ft3 x 10-1/pulse

1.0

ft3 x 10-1/pulse

2.0

ft3 x 10-1/pulse

: Flow rate in the specification is the value at standard condition.

If the display unit standard is changed from standard to normal, use the conversion formula.

Flow rate at standard condition x 0.927 = Flow rate at normal condition

PF2W20 series

Model PF2W20

Applicable sensor PF2W504 PF2W520 PF2W540 PF2W511

PF3W504 PF3W520 PF3W540 PF3W511

F lo

w

Rated flow range 0.13 to 1.06

gal(US)/min

0.55 to 4.25

gal(US)/min

1.3 to 10.6

gal(US)/min

2.6 to 26.4

gal(US)/min

In s ta

n ta

n e o u s

fl o

w

Setting/display flow

range

0.10 to 1.16

gal(US)/min

0.40 to 4.75

gal(US)/min

1.0 to 11.6

gal(US)/min

7 to 110

gal(US)/min

Min. setting/display unit 0.01

gal(US)/min

0.05

gal(US)/min

0.1

gal(US)/min

0.2

gal(US)/min

A c c u m

u la

te d

fl o

w

Setting/display flow

range 0 to 999999 gal(US)

Min. setting/display unit 1 gal(US)

Conversion of accumulated pulse 0.01

gal(US)/pulse

0.05

gal(US)/pulse

0.1

gal(US)/pulse

0.2

gal(US)/pulse

PF2D20 series

Model PF2D20

Applicable sensor PF2D504 PF2D520 PF2D540

F lo

w

Rated flow range 0.11 to 1.06

gal(US)/min

0.40 to 5.30

gal(US)/min

1.1 to 10.6

gal(US)/min

In s ta

n ta

n e o u s

fl o

w

Setting/display flow

range

0.9 to 1.16

gal(US)/min

0.25 to 5.80

gal(US)/min

0.9 to 11.6

gal(US)/min

Min. setting/display unit 0.01

gal(US)/min

0.05

gal(US)/min

0.1

gal(US)/min

A c c u m

u la

te d

fl o

w

Setting/display flow

range 0 to 999999 gal(US)

Min. setting/display unit 1 gal(US)

Conversion of accumulated pulse 0.01

gal(US)/pulse

0.05

gal(US)/pulse

0.1

gal(US)/pulse

-26-

No.PF-OMH0003-F

Function selection mode Function selection mode

In measurement mode, press the button, to display [F_].

This [F_] indicates the mode for changing each functional setting.

: When the output mode is set to instantaneous output mode, [F_1] is displayed. When the output mode is set to accumulated output

mode, [F_2] is displayed. When the output mode is set to accumulated pulse output mode, [F_3] is displayed.

Default settings

Item Default Setting Page

[F_1]

Input the Set value of

instantaneous output

[n_1] Input of the Set point 1 50% of max. rated flow

PF2A20 : [ 5.0] L/min (PF2A510)

PF2W20: [2.00] L/min (PF2W504, PF3W504)

PF2D20 : [2.00] L/min (PF2D504)

Page 27

[n_2] Input of the Set point 2

[F_2]

Input the Set value of

accumulated output

[1nL] Input of the Set value for

the lower 3 digits [ 0]

Page 28 [1nH] Input of the Set value for

the upper 3 digits [ 0]

[F_3]

Copy function - - Page 30

: When Non-Reverse output is selected as the switching operation, n becomes P.

-27-

No.PF-OMH0003-F

[F_1] Input procedure of the Set value of instantaneous output The Set point of the switch output can be set manually.

Press the button in function selection mode to display [F_1]. (When output mode is assigned to be

instantaneous output mode, [F_1] is displayed. When the output mode is set to accumulated output mode,

[F_2] is displayed. When output mode is assigned to be accumulated pulse output mode, [F_3] is

displayed.)

Press the button.

Input of the Set point 1

[n_1] and the current Set value are displayed in turn.

Press the and button to change the value

referring to the list of outputs (page 20).

: When Non-Reverse output is selected as the switch operation,

[P_1] is displayed.

Press the button.

Input of the Set point 2

[n_2] and the current Set value are displayed in turn.

Press the and button to change the value

referring to the list of outputs (page 20).

: When Non-Reverse output is selected as the switch operation,

[P_2] is displayed.

Press the button.

[F_1] Input procedure of the Set value of instantaneous output is completed.

Return to measurement mode.

-28-

No.PF-OMH0003-F

[F_2] Input procedure of the Set value of accumulated output Press the button in measurement mode to select the channel to be set.

The Set point of the switch output can be manually set. Accumulated flow rate is displayed by the lower 3

digits and upper 3 digits separately. Setting is performed separately.

Press the button in function selection mode to display [F_2]. (When output mode is assigned to be

instantaneous output mode, [F_1] is displayed. When the output mode is set to accumulated output mode,

[F_2] is displayed. When output mode is assigned to be accumulated pulse output mode, [F_3] is

displayed.)

Press the button.

Input of the Set value for the lower 3 digits

[1nL] and the current Set value are displayed in turn.

Press the and button to change the value

referring the list of outputs (page 20).

: When Non-Reverse output is selected as the switch operation,

[1PL] is displayed.

Press the button.

Input of the Set value for the upper 3 digits

[1nH] and the current Set value are displayed in turn.

Press the and button to change the value

referring the list of outputs (page 20).

: When Non-Reverse output is selected as the switch operation,

[1PH] is displayed.

Press the button.

[F_2] Input procedure of the Set value of accumulated output is completed.

Return to measurement mode.

(continued)

-29-

No.PF-OMH0003-F

Starting of accumulation Check that the display of accumulated flow rate is selected as the display mode.

Press the and buttons simultaneously in measurement mode.

[-] flashes and accumulation starts.

Stop and restart of accumulation are performed the same way.

Pressing the button displays the instantaneous flow rate while displaying

the accumulated flow.

The accumulated flow rate can be displayed up to 999,999 L, but the display

normally shows the lower 3 digits.

To display upper three digits, press the button while the button is

pressed

The display flashes when the value reaches 999,999 L. To reset the

accumulated flow value, press the button while the button is

pressed for 4 seconds or longer.

The accumulated value will be reset if the power supply is turned off.

-30-

No.PF-OMH0003-F

[F_3] Copy function

The following set items can be copied to another channel

Connected sensor Display mode

Unit selection function (Operate only the product with unit selection function.) Output mode

Reference condition (Operate only the PF2A2 series.) Switch operation

Set value

Press the button in function selection mode to display [F_3].

(Instantaneous output mode: [F_1], Accumulated output mode: [F_2], Accumulated pulse output mode: [F_3]). : Press the

button to return to measurement mode.

Press the button.

[ CPY] will be displayed.

The channel display number will flash.

Press the button to select the channel to be copied.

Press the button.

The channel display number will stop flashing.

[ CPY] and [ C_1] will be displayed in turn.

Press the button to select the channel to which the setting is to be copied.

Press the button.

Copying will begin.

[F_3] is displayed when copying is completed.

Continue copying

Copying is completed

Press the button. Press the button.

Return to measurement mode.

-31-

No.PF-OMH0003-F

Other functions

Channel scan function The instantaneous flow and accumulate flow value will be displayed in turn for 2 seconds each repeatedly.

Press the button for 2 seconds or longer in measurement mode.

Press the button again for 2 seconds or longer to release the function.

Peak/Bottom value display This function can be only used when the display mode is set to instantaneous flow rate display.

The maximum (minimum) instantaneous flow from when the function was started to this moment is

displayed and updated.

1. Check that the display mode is set to instantaneous flow rate.

2. Press the button in measurement mode to select the channel to be set.

3. Press the and buttons simultaneously for 2 seconds or longer in measurement mode.

4. Press the button to select peak or bottom value.

.

5. Press the button to return to measurement mode.

[ ] will appear in the display to indicate peak value display.

[ ] will appear in the display to indicate bottom value display.

To release, follow the above procedure again from the first step and select [ n_n]

: Disconnecting the power supply will reset the peak (bottom) value display.

-32-

No.PF-OMH0003-F

Key-lock function This function is used to prevent errors occurring due to unintentional changes of the Set values.

1. Press the button for 4 seconds or longer in measurement mode. The display will change from

[F_] to [L]([d]) to [unL]. When [unL] is displayed, release the button.

2. Press the button to select [Loc], to lock the keys.

3. Key operation is locked by pressing the button, and returns to measurement mode.

: The channels can be selected and the channel scan will function by pressing the button, even when the keys are locked.

1. Press the button for 4 seconds or longer in measurement mode.

2. Press the button to select [unL], to unlock the keys.

3. Key operation is unlocked by pressing the button, and returns to measurement mode.

-33-

No.PF-OMH0003-F

Maintenance

How to reset the product after a power cut or forcible de-energizing

The setting of the product will be retained as it was before a power cut or de-energizing.

The output condition is also basically recovered to that before a power cut or de-energizing, but may change

depending on the operating environment.

Therefore, check the safety of the whole installation before operating the product.

-34-

No.PF-OMH0003-F

Troubleshooting

Troubleshooting

If an operation failure of the product occurs, please confirm the cause of the failure from the following table.

If the cause of the failure cannot be identified and normal operation can be recovered by replacement with a

new product, this indicates that the product itself is faulty. Product damage can be caused by the operating

environment (system construction, etc.), therefore contact SMC.

Cross-reference for troubleshooting

Fault Probable cause Countermeasures

D is

p la

y

Display is OFF. Incorrect wiring Correct the wiring.

Connector loose. Check the connector.

Display does not

change.

Peak (bottom) value display has

been selected. Turn off the peak (bottom) value display (page 31).

The display is

unstable.

Foreign matter inside. Refer to the operation manual of the sensor.

The piping is connected in the

wrong direction.

Connect the product so that the fluid direction is the

same as the arrow indicated on the sensor.

Flow passage inside the sensor

is not filled with fluid. 1

Arrange piping so that the flow passage inside the

sensor is filled with fluid.

Pulsation in the flow.

It is possible that pulsation is generated due to the

fluctuation of the supply pressure or the

characteristics of the compressor or pump used as

the pressure source.

Change to a pressure source with less fluctuation or

install a tank which reduces the pressure fluctuation.

Fluid leakage Refer to the operation manual of the sensor.

The display is not

correct.

Foreign matter inside. Refer to the operation manual of the sensor.

Piping is connected in the wrong

direction.

Connect the product so that the fluid direction is the

same as the arrow indicated on the sensor.

Flow passage inside the sensor

is not filled with fluid. 1

Arrange piping so that the flow passage inside the

sensor is filled with fluid.

Incorrect unit selection. 2 Select the correct unit using the unit selection

function.

Fluid leakage Refer to the operation manual of the sensor.

1: Operate only the PF2W2 and PF2D2 series.

2: Operate only the product with unit selection function.

-35-

No.PF-OMH0003-F

Fault Type Troubleshooting

O u

tp u

t

There is no output. Incorrect wiring Correct the wiring.

Connector loose. Check the connector.

Output is unstable.

Foreign matter inside. Refer to the operation manual of the sensor.

The piping is connected in the

wrong direction.

Connect the product so that the fluid direction is the

same as the arrow indicated on the sensor.

Flow passage inside the sensor

is not filled with fluid. 1

Arrange piping so that the flow passage inside the

sensor is filled with fluid.

Pulsation in the flow.

It is possible that pulsation is generated due to the

fluctuation of the supply pressure or the

characteristics of the compressor or pump used as

the pressure source.

Change to a pressure source with less fluctuation or

install a tank which reduces the pressure fluctuation.

Fluid leakage Refer to the operation manual of the sensor.

Hysteresis is narrow. Increase the hysteresis.

B u

tt o

n

The buttons cannot be

operated.

Key-lock function is activated. Cancel the key-lock function (page 32).

Channel scan function is valid. Disable channel scan function (page 29).

1: Operate only the PF2W2 and PF2D2 series.

-36-

No.PF-OMH0003-F

Error indication

Error Name Error Display Error Type Troubleshooting Method

Excessive

instantaneous flow

Flow has exceeded the upper limit of the

display flow range. Reduce the flow.

Over current error

The switch output load current is more

than 80 mA (OUT1).

Turn the power off and remove

the cause of the over current.

Then turn the power on again.

System error

Internal data error. Contact SMC to repair.

Excessive

accumulated flow

Accumulated

flow displayed

(flashing)

The display flow range of accumulated

flow has been exceeded.

To reset the accumulated flow

value, press the button

while the button is pressed

for 4 seconds or longer

(page 31).

: If the error cannot be reset after the above measures are taken, then please contact SMC.

-37-

No.PF-OMH0003-F

Specification

Specifications PF2A20

Model PF2A20

Applicable sensor PF2A510 PF2A550 PF2A511 PF2A521 PF2A551

F lo

w

Rated flow range 1 to 10

L/min

5 to 50

L/min

10 to 100

L/min

20 to 200

L/min

50 to 500

L/min

In s ta

n ta

n e o u s

flo w

Setting/display flow

range 1 2

0.5 to 10.5

L/min

2.5 to 52.5

L/min

5 to 105

L/min

10 to 210

L/min

25 to 255

L/min

Min. setting/display unit 0.1

L/min

0.5

L/min

1

L/min

2

L/min

5

L/min

A c c u m

u la

te d

F lo

w

Setting/display flow

range 0 to 999999 L

Min. setting/display unit 1 L

Reference condition 3 Standard condition, Normal condition 4

S w

it c h

o u

tp u

t

NPN open collector output, PNP open collector output

Output mode 3 Instantaneous flow output mode (hysteresis mode, window comparator mode)

Accumulated flow output mode, Accumulated pulse output mode

Switch operation 3 Non-Reversed output, Reversed output

Max. load current 80 mA

Max. applied voltage 30 VDC (NPN output)

Internal voltage drop 1 V or less (at 80 mA)

Response time 1 s or less

Repeatability 5 1%F.S. max.

Accuracy 5 5%F.S. max.

Hysteresis Hysteresis mode: Variable 3

Window comparator mode: Fixed (3 digits)

Output protection Short circuit protection

A c c u m

u la

te d

p u

ls e Pulse width 50 ms

Conversion of

accumulated pulse 0.1 L/pulse 0.5 L/pulse 1 L/pulse 2 L/pulse 5 L/pulse

1: Display flow rage in the specification is the value at standard condition.

If the display unit standard is changed from standard to normal, use the conversion formula. Flow rate at standard condition x 0.927 = Flow rate at normal condition

2: If the flow rate is smaller than the minimum flow of the display range, "0 L/min" is displayed.

3: Selectable by setting.

4: Standard condition: Flow display which is converted in atmospheric pressure at 20 C, 65%R.H.

Normal condition: Flow display which is converted in atmospheric pressure at 0 C.

5: Total accuracy when used with applicable sensor.

-38-

No.PF-OMH0003-F

PF2W20

Model PF2W20

Applicable sensor PF2W504(T) PF2W520(T) PF2W540(T) PF2W511(T)

PF3W504 PF3W520 PF3W540 PF3W511

F lo

w

Rated flow range 0.5 to 4.0

L/min

2 to 16

L/min

5 to 40

L/min

10 to 100

L/min

In s ta

n ta

n e o u s

flo w

Setting/display flow

range 1

0.35 to 4.50

L/min

1.7 to 17.0

L/min

3.5 to 45.0

L/min

7 to 110

L/min

Min. setting/display unit 0.05

L/min

0.1

L/min

0.5

L/min

1

L/min

A c c u m

u la

te d

F lo

w

Setting/display flow

range 0 to 999999 L

Min. setting/display unit 1 L

S w

it c h

o u

tp u

t

NPN open collector output, PNP open collector output

Output mode 2 Instantaneous flow output mode (hysteresis mode, window comparator mode)

Accumulated flow output mode, Accumulated pulse output mode

Switch operation 2 Non-Reversed output, Reversed output

Max. load current 80 mA

Max. applied voltage 30 VDC (NPN output)

Internal voltage drop 1 V or less (at 80 mA)

Response time 1 s or less

Repeatability 3 1%F.S. max.

Accuracy 3 5%F.S. max.

Hysteresis Hysteresis mode: Variable 2

Window comparator mode: Fixed (3 digits)

Output protection Short circuit protection

A c c u m

u la

te d

p u

ls e Pulse width 50 ms

Conversion of

accumulated pulse 0.05 L/pulse 0.1 L/pulse 0.5 L/pulse 1 L/pulse

1: If the flow rate is smaller than the minimum flow of the display range, "0 L/min" is displayed.

2: Selectable by setting.

3: Total accuracy when used with applicable sensor.

-39-

No.PF-OMH0003-F

PF2D20

Model PF2D20

Applicable sensor PF2D504 PF2D520 PF2D540

F lo

w

Rated flow range 0.4 to 4.0

L/min

1.8 to 20.0

L/min

4 to 20

L/min

In s ta

n ta

n e o u s

flo w

Setting/display flow

range 1

0.25 to 4.50

L/min

1.3 to 21.0

L/min

2.5 to 45.0

L/min

Min. setting/display unit 0.05

L/min

0.1

L/min

0.5

L/min

A c c u m

u la

te d

F lo

w

Setting/display flow

range 0 to 999999 L

Min. setting/display unit 1 L

S w

it c h

o u

tp u

t

NPN open collector output, PNP open collector output

Output mode 2 Instantaneous flow output mode (hysteresis mode, window comparator mode)

Accumulated flow output mode, Accumulated pulse output mode

Switch operation 2 Non-Reversed output, Reversed output

Max. load current 80 mA

Max. applied voltage 30 VDC (NPN output)

Internal voltage drop 1 V or less (at 80 mA)

Response time 1 s or less

Repeatability 3 1%F.S. max.

Accuracy 3 5%F.S. max.

Hysteresis Hysteresis mode: Variable 2

Window comparator mode: Fixed (3 digits)

Output protection Short circuit protection

A c c u m

u la

te d

p u

ls e Pulse width 50 ms

Conversion of

accumulated pulse 0.05 L/pulse 0.1 L/pulse 0.5 L/pulse

1: If the flow rate is smaller than the minimum flow of the display range, "0 L/min" is displayed.

2: Selectable by setting.

3: Total accuracy when used with applicable sensor.

-40-

No.PF-OMH0003-F

Common Specifications

Model PF220

D is

p la

y Display part Displayed digit: 4 digits 7 segments, Colour: Orange

Channel display Displayed digit: 1 digit 7 segments, Colour: Red

Indicator light (output) When ON, Red light is ON

Supply voltage 24 VDC10%

Power consumption (no load) 55 mA or less

E n

v ir

o n

m e n

t

Enclosure Front part: IP65 (at panel mounting), Other: IP40

Operating temperature range Operation: 0 to 50 C, Storage: -10 to 60 C (No freezing or condensation)

Operating humidity range Operation, Storage: 35 to 85%R.H. (No condensation)

Temperature characteristics 2%F.S. max. (0 to 50 oC, 25 oC reference)

Withstand voltage 1000 VAC, for 1minute between the external terminals and case

Insulation resistance 50 M or more (with 500 VDC mega meter)

between the external terminals and case

Standards and regulations CE marked (EMC directive, RoHS directive)

Materials Body: PBT, Display: PET, Rubber cover for the back: CR

W e

ig h

t

Weight of the body 60 g

Cable weight 65 g

Lead wire Specifications

Sheath Finished outside diameter approx. 4.8 mm

Material Heat resistant polyethylene

Insulator Colour Brown, Black, Grey, Red, Green, Blue, White, Yellow

Outside diameter approx. 0.9 mm

Conductor Nominal cross section area approx. 0.15 mm2

Outside diameter approx. 0.5 mm

-41-

No.PF-OMH0003-F

Dimensions (in mm)

PF220

PF220 + panel mount adapter (ZS-26-B) + front protective cover (ZS-26-01)

PF220 + panel mount adapter (ZS-26-B) + front protective cover (ZS-26-01) +

48 mm conversion adapter (ZS-26-D)

-42-

No.PF-OMH0003-F

Panel cut-out dimensions

: Suitable for panel thickness of 0.5 to 8 mm. (When the waterproof seal is used, Suitable for panel thickness of 0.5 to 6 mm.)

Power and output cable (ZS-26-A)

Sensor connector

ZS-28-C ZS-28-CA-

No.PF-OMH0003-F

Revision history

A: Full scale revision due to the change of the

format and addition of items.

B: Content is changed due to the change of the

format.

C: Contents revised in several places.

D: Contents are added.

E: Contents revised in several places. [July 2018]

F: Contents revised in several places.

[August 2019]

Manualsnet FAQs

If you want to find out how the PF2A20 SMC works, you can view and download the SMC PF2A20 Monitor Operation Manual on the Manualsnet website.

Yes, we have the Operation Manual for SMC PF2A20 as well as other SMC manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Operation Manual should include all the details that are needed to use a SMC PF2A20. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the SMC PF2A20 Monitor Operation Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This SMC PF2A20 Monitor Operation Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download SMC PF2A20 Monitor Operation Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print SMC PF2A20 Monitor Operation Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the SMC PF2A20 Monitor Operation Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.