NO.ZK2-OM00501-B
PRODUCT NAME
Digital pressure switch for energy-saving
control ejector
MODEL / Series / Product Number
ZK2-ZSV####-A
-1-
NO.ZK2-OM00501-B
Table of Contents
Safety Instructions 2
Model indication and How to order 9
Summary of Product parts 10
Definition and terminology 11
Wiring 15
Wiring 15
Internal circuit and wiring example 16
Mounting and Installation 17
Installation 17
Easy Setting 18
Measurement mode 18
Function Setting 22
Function selection mode 22
Default setting 22
F0 Unit selection function 24
F1 OUT1 25
F2 OUT2 27
F3 Response time 29
F4 Auto-preset 30
F6 Fine adjustment of display value 32
F11 Display resolution 33
F80 Power saving mode 34
F81 Security code 35
F90 Setting of all functions 36
F96 Check of suction command signal 38
F98 Check of output 39
F99 Reset to the default setting 41
Other Settings 42
How to stop energy-saving control function 45
Maintenance 46
Troubleshooting 47
Error indication 54
Specification 55
A
B
-2-
NO.ZK2-OM00501-B
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage. These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or "Danger". They are all important notes for safety and must be followed in addition to International
standards (ISO/IEC) 1) and other safety regulations.
1) ISO 4414: Pneumatic fluid power -- General rules relating to systems ISO 4413: Hydraulic fluid power -- General rules relating to systems IEC 60204-1: Safety of machinery -- Electrical equipment of machines (Part 1: General requirements) ISO 10218-1992: Manipulating industrial robots -Safety. etc.
Caution : CAUTION indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury.
Warning : WARNING indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury.
Danger : DANGER indicates a hazard with a high level of risk which, if not avoided, will result in death or serious injury.
Warning
1. The compatibility of the product is the responsibility of the person who designs the equipment or decides its specifications.
Since the product specified here is used under various operating conditions, its compatibility with specific equipment must be decided by the person who designs the equipment or decides its specifications based on necessary analysis and test results. The expected performance and safety assurance of the equipment will be the responsibility of the person who has determined its compatibility with the product. This person should also continuously review all specifications of the product referring to its latest catalog information, with a view to giving due consideration to any possibility of equipment failure when configuring the equipment.
2. Only personnel with appropriate training should operate machinery and equipment.
The product specified here may become unsafe if handled incorrectly. The assembly, operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced.
3. Do not service or attempt to remove product and machinery/equipment until safety is confirmed.
1. The inspection and maintenance of machinery/equipment should only be performed after measures to prevent falling or runaway of the driven objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures as mentioned above are implemented and the power from any appropriate source is cut, and read and understand the specific product precautions of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and malfunction.
4. Contact SMC beforehand and take special consideration of safety measures if the product is to be used in any of the following conditions.
1. Conditions and environments outside of the given specifications, or use outdoors or in a place exposed to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping, vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and beverages, emergency stop circuits, clutch and brake circuits in press applications, safety equipment or other applications unsuitable for the standard specifications described in the product catalog.
3. An application which could have negative effects on people, property, or animals requiring special safety analysis.
4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by using a mechanical protective function, and periodical checks to confirm proper operation.
-3-
NO.ZK2-OM00501-B
Caution
The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in manufacturing industries. If considering using the product in other industries, consult SMC beforehand and exchange specifications or a contract if necessary. If anything is unclear, contact your nearest sales branch.
Limited warranty and Disclaimer/Compliance Requirements The product used is subject to the following "Limited warranty and Disclaimer" and "Compliance Requirements". Read and accept them before using the product.
Limited warranty and Disclaimer
1. The warranty period of the product is 1 year in service or 1.5 years after the product is delivered,
whichever is first. 2) Also, the product may have specified durability, running distance or replacement parts. Please consult your nearest sales branch.
2. For any failure or damage reported within the warranty period which is clearly our responsibility, a replacement product or necessary parts will be provided. This limited warranty applies only to our product independently, and not to any other damage incurred due to the failure of the product.
3. Prior to using SMC products, please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products.
2) Vacuum pads are excluded from this 1 year warranty.
A vacuum pad is a consumable part, so it is warranted for a year after it is delivered.
Also, even within the warranty period, the wear of a product due to the use of the vacuum pad or failure due to
the deterioration of rubber material are not covered by the limited warranty.
Compliance Requirements
1. The use of SMC products with production equipment for the manufacture of weapons of mass destruction (WMD) or any other weapon is strictly prohibited.
2. The exports of SMC products or technology from one country to another are governed by the relevant security laws and regulation of the countries involved in the transaction. Prior to the shipment of a SMC product to another country, assure that all local rules governing that export are known and followed.
-4-
NO.ZK2-OM00501-B
Operator
This operation manual is intended for those who have knowledge of machinery using pneumatic equipment, and have sufficient knowledge of assembly, operation and maintenance of such equipment. Only those persons are allowed to perform assembly, operation and maintenance.
Read and understand this operation manual carefully before assembling, operating or providing maintenance to the product.
Safety Instructions
Warning Do not disassemble, modify (including changing the printed circuit board) or repair.
An injury or failure can result.
Do not use the product except for energy-saving control ejector
Fire, malfunction, or damage to the product or the system can result.
Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.
Do not operate in an atmosphere containing flammable or explosive gases.
Fire or an explosion can result.
This product is not designed to be explosion proof.
Do not use the product in a place where static electricity is a problem.
Otherwise it can cause failure or malfunction of the system.
If using the product in an interlocking circuit.
Provide a double interlocking system, for example a mechanical system
Check the product regularly for proper operation
Otherwise malfunction can result, causing an accident.
The following instructions must be followed during maintenance.
Turn off the power supply
Stop the air supply, exhaust the residual pressure and verify that the air is released before performing
maintenance.
Otherwise an injury can result.
Verify the system sufficiently before judging the applicability when a permeable workpiece is to be sucked.
Rapid decrease in vacuum pressure during suction of the workpiece may cause the ejector to fail to restart
in time, causing injury or damage to the system because of the suction failure.
-5-
NO.ZK2-OM00501-B
Caution Do not touch the terminals and connectors while the power is on.
Otherwise electric shock, malfunction or damage to the product can result.
Perform sufficient trial run.
Otherwise, injury or damage to the system can result due to suction failure depending on the conditions of
the suction of the workpiece or the pressure switch settings.
Perform sufficient verification before using this product.
After maintenance is complete, perform appropriate functional inspections and leak test.
Stop operation if the equipment does not function properly or there is leakage of fluid.
If there is leakage from parts other than the piping, the product might be broken.
Cut off power supply and stop supplying fluid.
Do not supply fluid if there is leakage.
Safety cannot be assured in the case of unexpected malfunction.
NOTE Follow the instructions given below when designing, selecting and handling the product. The instructions on design and selection (installation, wiring, environment, adjustment,
operation, maintenance, etc.) described below must also be followed. Product specifications
Use the specified voltage.
Otherwise failure or malfunction can result.
Do not exceed the specified maximum allowable load.
Otherwise it can cause damage or shorten the lifetime of the Pressure switch.
Design the product to prevent reverse current when the circuit is opened or the product is forced to operate for
operational check.
Reverse current can cause malfunction or damage to the product.
Input data to the Pressure switch is not deleted, even if the power supply is cut off.
(Writing time: 1,000,000 times)
For the details of compressed air quality, refer to ISO 8573-1, 1.1.2 to 1.6.2: 2001.
This can cause operating failure.
If compressed air containing condensate is used, install an air dryer or drain catch before the filter and perform
drainage regularly.
If drainage is not performed regularly and condensate enters the secondary side, it can cause operating failure of
pneumatic equipment.
If regular drainage is difficult, the use of a filter with an auto drain is recommended.
Applicable fluid is air, inert gases and incombustible gases. Do not use a fluid containing chemicals, synthetic oils including organic solvent, salt and corrosive gases. Otherwise, damage to the product and malfunction can result.
Check the details of the specifications before using.
Use the specified measurement flow rate and operating pressure.
Otherwise it can cause damage to the pressure switch or inability to measure correctly.
Reserve a space for maintenance.
Allow sufficient space for maintenance when designing the system.
-6-
NO.ZK2-OM00501-B
Product handling Installation
Tighten to the specified tightening torque.
If the tightening torque is exceeded the mounting screws and brackets may be broken.
If the tightening torque is insufficient, the product can be displaced and loosen the mounting screws.
(Refer to page 17)
Be sure to ground terminal FG when using a commercially available switch-mode power supply.
Do not drop, hit or apply excessive shock (over 100 m/s2) to the Pressure switch.
Otherwise damage to the internal parts can result, causing malfunction.
Do not pull the lead wire forcefully, not lift the product by pulling the lead wire. (Tensile force 20 N or
less)
Hold the body when handling to avoid the damage of the Pressure switch which lead to cause the failure and
malfunction.
Eliminate any dust left in the piping by air blow before connecting the piping to the product.
Otherwise it can cause damage or malfunction.
Do not insert metal wires or other foreign matter into the pressure measurement port.
It can damage the pressure sensor causing failure or malfunction.
Never mount a Pressure switch in a location that will be used as a foothold.
The product may be damaged if excessive force is applied by stepping or climbing onto it.
If the entering of foreign material to the fluid is possible, install and pipe the filter or the mist separator to
the inlet to avoid failure and malfunction.
-7-
NO.ZK2-OM00501-B
Wiring
Do not pull the lead wires.
In particular, never lift a Pressure switch equipped with fitting and piping by holding the lead wires.
Otherwise damage to the internal parts can result, causing malfunction or to be off the connector.
Avoid repeatedly bending or stretching the lead wire, or placing heavy load on them.
Repetitive bending stress or tensile stress can cause the sheath of the wire to peel off, or breakage of the wire.
If the lead wire can move, fix it near the body of the product.
The recommended bend radius of the lead wire is 6 times the outside diameter of the sheath, or 33 times the
outside diameter of the insulation material, whichever is larger.
Replace the damaged lead wire with a new one.
Wire correctly.
Incorrect wiring can break the Pressure switch.
Do not perform wiring while the power is on.
Otherwise damage to the internal parts can result, causing malfunction.
Do not route wires and cables together with power or high voltage cables.
Otherwise the product can malfunction due to interference of noise and surge voltage from power and high voltage
cables to the signal line. Route the wires (piping) of the product separately from power or high voltage cables.
Confirm proper insulation of wiring.
Poor insulation (interference from another circuit, poor insulation between terminals, etc.) can lead to excess
voltage or current being applied to the product, causing damage.
Design the system to prevent reverse current when the product is forced to operate for operational
check.
Depending on the circuit used, insulation may not be maintained when operation is forced, allowing reverse current
to flow, which can cause malfunction and damage the product.
Keep wiring as short as possible to prevent interference from electromagnetic noise and surge voltage.
Do not use a cable longer than 10 m.
Wire the DC(-) line(blue) as close as possible to the power supply.
Environment
Do not use the product in area that is exposed to corrosive gases, chemicals, sea water, water or steam.
Otherwise failure or malfunction can result.
Do not use in a place where the product could be splashed by oil or chemicals.
If the product is to be used in an environment containing oils or chemicals such as coolant or cleaning solvent,
even for a short time, it may be adversely affected (damage, malfunction, or hardening of the lead wires).
Do not use in an area where surges are generated.
If there is equipment which generates a large amount of surge (solenoid type lifter, high frequency induction
furnace, motor, etc.) close to the Pressure switch, this may cause deterioration or breakage of the internal circuit of
the Pressure switch. Avoid sources of surge generation and crossed lines.
Do not use a load which generates surge voltage.
When a surge-generating load such as a relay or solenoid is driven directly, use a Pressure switch with a built-in
surge absorbing element.
The product is CE marked, but not immune to lightning strikes. Take measures against lightning strikes
in the system.
This product is CE marked, it may happen that the set value of product is changed by the noise impressed in
excess.
Mount the product in a place that is not exposed to vibration or impact.
Otherwise failure or malfunction can result.
-8-
NO.ZK2-OM00501-B
Prevent foreign matter such as remnant of wires from entering the Pressure switch.
Take proper measures for the remnant not to enter the Pressure switch in order to prevent failure or malfunction.
Do not use the product in an environment that is exposed to temperature cycle.
Heat cycles other than ordinary changes in temperature can adversely affect the inside of the product.
Do not expose the product to direct sunlight.
If using in a location directly exposed to sunlight, shade the product from the sunlight.
Otherwise failure or malfunction can result.
Keep within the specified fluid and ambient temperatures range.
The fluid and ambient temperatures should be 5 to 50 oC. Operation under low temperature leads to cause damage
or operation failure due to frozen moist in the fluid or air.
Protection against freezing is necessary. Air dryer is recommended for elimination of drain and water.
Avoid sudden temperature change even within specified temperature.
Do not operate close to a heat source, or in a location exposed to radiant heat.
Otherwise malfunction can result.
Adjustment and Operation
Turn the power on after connecting a load.
Otherwise it can cause excess current causing instantaneous breakage of the Pressure switch.
Do not short-circuit the load.
Although error is displayed when the Pressure switch load is short circuit, generated excess current lead to cause
the damage of the Pressure switch.
Do not press the setting buttons with a sharp pointed object.
It may damage the setting buttons.
If using the product to detect very small pressure rates, warm up the product for 10 to 15 minutes first.
There will be a drift on the display of approximate 1% immediately after the power supply is turned on.
Perform settings suitable for the operating conditions.
Incorrect setting can cause operation failure.
For details of each setting, refer to page 21 to 45 of this manual.
The Pressure switch is compulsory turned off for 1 second after power supplied.
For 4 seconds after supplying power, the measurement output is turned off.
Maintenance
Turn off the power supply, stop the supplied air, exhaust the residual pressure and verify the release of
air before performing maintenance.
There is a risk of unexpected malfunction.
Perform regular maintenance and inspections.
There is a risk of unexpected malfunction.
Perform drainage regularly.
If condensate enters the secondary side, it can cause operating failure of pneumatic equipment.
Do not use solvents such as benzene, thinner etc. to clean the Pressure switch.
They could damage the surface of the body and erase the markings on the body.
Use a soft cloth to remove stains. For heavy stains, use a cloth soaked with diluted neutral detergent and fully
squeezed, then wipe up the stains again with a dry cloth.
A
-9-
NO.ZK2-OM00501-B
Model Indication and How to order
How to order
Integrated cable assembly for the solenoid valve/pressure switch
A
-10-
NO.ZK2-OM00501-B
Summary of Product parts
Output (OUT1) LED (green): LED is ON when the switch output (OUT1) is ON.
Output (OUT2) LED (Red): LED is ON when the supply pilot valve is ON.
LED display: Displays the current status of pressure, setting mode and error code.
button (UP): Selects a mode and increases ON/OFF set value.
Press this button to change to the peak display mode.
button (DOWN): Selects a mode and decreases ON/OFF set value.
Press this button to change to the bottom display mode.
button (SET): Press this button to change to another mode and to set a value.
-11-
NO.ZK2-OM00501-B
Definition and terminology
No. Terms Meaning
7
7-segment indication
Display type where each individual display character consists of up to 7 separate
sections (called segments)
(The figure 8 uses all 7 segments)
A Adsorption directive signal
Indicate the command signal which generate vacuum.
(It is necessary to input the pressure switch)
Auto preset
A function of the Pressure switch to automatically setup pressure just by having
equipment hold and release a workpiece via vacuum adsorption. This function is
used in an application where vacuum adsorption of a workpiece needs to be
confirmed with a Pressure switch.
B Bottom value display (mode) Indicates the minimum vacuum pressure reached up to that moment.
C Chattering
The problem of the switch output turning ON and OFF repeatedly around the set
value at high frequency due to the effect of pulsation.
Chattering-preventing function A function to delay the response time of switch output in order to prevent
chattering.
D
Digit (Min. setting unit)
Shows how precisely the pressure can be indicated or set by the digital
Pressure switch. When 1 digit = 1 kPa, the pressure is given with an increment of
1 kPa, e.g., 1, 2, 3,, 99, 100.
E Energy saving automatic
control
Indicate that the vacuum pressure during adsorption is monitored and ON and
OFF of the ejector is automatically controlled.
Error indication (Error code) With the self-diagnosis function given to the Pressure switch, it indicates that
there is a failure which could cause a switch failure.
F Fine adjustment mode Refer to "Fine adjustment of display value".
Fine adjustment of display
value
An indicated pressure value can be adjusted within the range of 5% R.D.
(5% of the indicated value). It is used if a true pressure value is known or to
correct the difference of an indicated value of the measurement equipment
nearby that measures the same pressure as the Pressure switch.
F.S. (full span/full scale) Abbreviation for full span and full scale; means the maximum fluctuation range
of the Pressure switch rated value.
Function selection mode
A mode in which setting of functions is performed. It is a separate menu from the
pressure setting.
If any function settings needs to be changed from the factory default, each setting
can be selected with F .
The setting items are: display color, operation mode, output type, response time,
display resolution, display value fine adjustment, use of auto preset, use of power
saving mode, and use of PIN number. Refer to page 25 for a list of output
modes that can be selected.
H Hysteresis Difference between the points at which the Pressure switch is turned on and off.
Hysteresis mode Refer to "List of output modes" on page 25
A
-12-
NO.ZK2-OM00501-B
No. Terms Meaning
I Indication accuracy Shows the deviation between displayed pressure value and the true pressure.
Insulation resistance Insulation resistance of the product.
The resistance between the electrical circuit and the case.
Indication resolution
How fine the rated pressure range can be segmented. (Example: If a product
for 0 to 1 MPa can indicate pressure by 0.001 MPa, the indication resolution is
1/1000.)
Indication LED The LED that turns on when the switch output is ON.
Indication unit The unit of pressure used in the display.
K Key lock function
Function that prevents changes to the settings of the Pressure switch (disables
button operation).
M
Manual set up
Manual pressure setup without using auto preset.
This term is used to distinguish between manual and auto preset pressure
setup.
Max. applied voltage The maximum value of applied voltage available to the output line of the NPN
output.
Max. (Min) load impedance The maximum (minimum) load (resistance value and impedance) which can be
connected to the output (output line) of the analog current output.
Measurement mode The condition in which the pressure is being detected and indicated and switch
operation is enabled.
Min. setting unit Refer to "digit".
N
Normal output
One of the switch output types. In hysteresis mode the switch output is turned
ON when pressure equal to or greater than the switch output set value is
detected.
Refer to "List of output modes" on page 25)
NPN (open collector) (output) The switch that uses the NPN transistor for output.
O Output configuration
The operation principle of the switch output.
Refer to "List of output modes" on page 25 for the operation status.
Output mode Either hysteresis mode can be selected.
A
-13-
NO.ZK2-OM00501-B
No. Terms Meaning
P Peak value display Displays the maximum vacuum pressure reached up to that moment.
Pilot valve for air supply The solenoid valve which turns on and off the ejector.
(This pressure switch outputs signal to the supply pilot valve)
PNP (open collector) (output) The switch that uses the PNP transistor for output.
Power saving mode The condition in which the indicated value turns off and current consumption is
reduced.
Pressure setting The setting of pressure to determine the point at which the Pressure switch
turns on and off.
Proof pressure Pressure limit that if exceeded will result in mechanical and/or electrical damage
to the product.
R
Rated pressure range
The pressure range in which the Pressure switch satisfies the specifications.
Values over this range can be set if they are within the set pressure range, but
cannot assured the specifications to be satisfied.
Repeatability Reproducibility of the displayed value for pressure and ON-OFF output
operating point when the pressure changes at a temperature of 25 oC.
Residual voltage
The difference between the ideal ON voltage and the actual voltage when the
switch output is on. It depends on present load current and ideally should be
"0".
Resolution See "Indication resolution".
Response time
The time from when the pressure applied to the pressure switch reaches the set
value, to when the ON-OFF output actually begins working. Generally, the
shorter the response time, the better the performance.
Reversed output(OUT1)
One of the switch output types. In hysteresis mode the switch output is turned
ON when pressure less than or equal to the switch output set value is detected.
(Refer to "List of output modes" on page 25)
A
-14-
NO.ZK2-OM00501-B
No. Terms Meaning
S Setting of function Refer to "Function selection mode".
Setting pressure range. The pressure range within which switch output can be set.
Switch output Output type that only has 2 possible states, ON or OFF. Sometimes referred to
as "ON-OFF output".
U
Unit selection function
Function to change the unit in which the value of pressure is indicated. Only a
product with this function can change the unit. A product with unit-changing
function cannot be purchased if it is used within Japan. Pressure is indicated
only by SI units in Japan.
W
Withstand voltage
A measure of the products resistance to a voltage applied between the
electrical circuit and case.
The product may be damaged if a voltage over this value is applied.
(The withstand voltage is not the supply voltage used to power the product.)
Z Zero clear (function) Adjusts the displayed pressure value to "0".
A
-15-
NO.ZK2-OM00501-B
Wiring
Wiring
Connection Connections should only be made with the power supply turned off.
Use separate routes for the Pressure switch wiring and any power or high voltage wiring. Otherwise,
malfunction may result due to noise.
Ensure that the FG terminal is connected to ground when using a commercially available switch-mode
power supply. When a switch-mode power supply is connected to the product, switching noise will be
superimposed and the product specification can no longer be met. This can be prevented by inserting a
noise filter, such as a line noise filter and ferrite core, between the switch-mode power supply and the
product, or by using a series power supply instead of a switch-mode power supply.
Connector use for pressure switch
Connecting/Disconnecting When mounting the connector, insert it straight into the socket holding the lever and connector body, and
push the connector until the lever hooks into the housing, and locks.
When removing the connector, press down the lever to release the hook from housing and pull the
connector straight out.
Pin No. of the Connector (Power supply and output cable for the digital pressure switch and pilot
valve)
-16-
NO.ZK2-OM00501-B
Internal circuit and wiring example NPN output type
NPN open collector 2 outputs, Max. applied voltage 26.4VDC, Max. load current 80mA
Residual voltage 2 V or less
PNP output type PNP open collector 2 outputs, Max. load current 80mA, Residual voltage 2 V or less
-17-
NO.ZK2-OM00501-B
Mounting and Installation
Installation Mount the O-ring provided into the O-ring groove of the pressure switch, and mount the pressure switch to
the ejector body with the two mounting screws provided. (The required tightening torque is 0.08 to 0.10 Nm)
If the tightening torque is exceeded, the mounting part can be deformed and broken.
-18-
NO.ZK2-OM00501-B
Easy Setting
Measurement mode
The measurement mode is the condition where the pressure is detected and indicated, and the switch
function is operating.
This is the basic mode, and other modes should be selected for setting changes and other function settings.
A
-19-
NO.ZK2-OM00501-B
See below for the energy saving control operation and the set values which are preset to the switch.
If the operation shown below is acceptable, then keep these settings.
Function that enables the easy setting of the ON and OFF points of the switch output, and the operation of the
supply pilot valve.
Operation of OUT1
When the pressure exceeds the set value (P_1), the pressure switch will be turned ON.
When the pressure falls below the set value (P_1) by the amount of hysteresis value (H_1), the switch will be
turned OFF.
The default settings are P_1: -70.0 kPa and H_1:10.0 kPa.
Operation of OUT2
Supply pilot valve: OUT2 is turned on by the signal for suction. Suction starts by the generation of vacuum
pressure.
When the vacuum pressure reaches the set value (P_1), the supply pilot valve turns OFF.
After the supply pilot valve is turned off, the vacuum pressure will decrease, when the vacuum pressure drops
below (P_1) by the amount set in (P_2) the supply pilot valve will turn on again and increase the vacuum
pressure.
After that, supply pilot valve will turn ON and OFF repeatability.
Default setting is H_2: 5.0 kPa.
-20-
NO.ZK2-OM00501-B
Normal output (OUT1)
(1) Press the button once in measurement mode. (Refer to page 18)
(2) P_1" and the set value are displayed in turn.
(3) Press the or button to change the set value.
The button is to increase vacuum pressure and the button is to decrease.
Press the button once to increase by one digit, and press it continuously to keep increasing the set
value.
Press the button once to decrease by one digit, press it continuously to keep decreasing the set
value.
(4) Press the button to complete the setting of P_1. The display shows [H_1] and the set value in turn.
The button is to increase and the button is to decrease the set value.
(5) Press the button to complete the setting of H_1. The display shows [H_2] and the set value in
turn.
The button is to increase and the button is to decrease the set value.
(6) Press the button to complete the setting.
When the reversed output is changed, the following parameters are displayed, and each set value can be
changed, using the method shown above.
For details of how to change the reversed output, refer to the setting of each function.
A
-21-
NO.ZK2-OM00501-B
Reversed output (out1)
A
-22-
NO.ZK2-OM00501-B
Function Setting
Function selection mode
In measurement mode, press the button for 2 seconds or longer to display [F 0]. Select to display the
function setting to be changed, [F ].
Press the button for 2 seconds or longer in function selection mode to return to measurement mode.
Default setting
The default settings are as follows
[F 0] Unit selection function See page 24
Item Default setting
SI unit fixed Unit conversion
function kPa
[F 1] Setting of OUT1 See page 25
Item Description Default setting
Output mode Select the hysteresis mode. Hysteresis mode
Reversed output Selects which type of switch output is used, normal or reversed. Normal output
Pressure setting Sets the ON or OFF point of the switch output. -70 kPa(P_1)
Hysteresis Set the hysteresis to prevent chattering. 10 kPa(H_1)
[F 2] Setting of OUT2 See page 27
Same setting as [F 1] OUT1.
Item Description Default setting
Supply pilot valve
at signal ON Sets the ON point of the supply pilot valve signal 5 kPa(H_2)
Supply pilot valve
at signal OFF Sets the OFF point of the supply pilot valve signal 0 kPa(H_3)
Set the range in which
the supply pilot valve
input is prohibited
Sets the range where the ON point of the supply pilot valve signal
is not allowed to be input. 1 kPa(H_4)
A
A
-23-
NO.ZK2-OM00501-B
Item Page Default setting
[F 3] Response time See page 29 2.5 ms
[F 4] Auto-preset See page 30 Manual
[F 6] Fine adjustment of display value See page 32 0
[F11] Display resolution See page 33 1000-split
[F80] Power saving mode See page 34 OFF
[F81] Security code See page 35 OFF
[F90] Setting of all functions See page 36 OFF
[F96] Check of suction command condition See page 38 OFF
[F98] Check of output See page 39 Normal
[F99] Reset to the default setting See page 41 OFF
A
-24-
NO.ZK2-OM00501-B
[F 0] Unit selection function
Setting is only possible when using a product with the unit selection function.
(kPa/MPa can still be selected if the product does not have the unit selection function.)
Press the or button in function selection mode to display [F 0].
Press the button. Move on to select the display unit.
Press the button to set. Return to function selection mode.
Setting of [F 0] Unit selection function completed.
Display unit and minimum setting unit.
Unit
MPa kPa kgf/cm2 bar psi InHg mmHg
0.001 0.1 0.001 0.001 0.02 0.1 1
Selection of the display unit
Press the or button to select the display unit.
-25-
NO.ZK2-OM00501-B
[F 1] Setting of OUT1
The output mode of OUT1 can be set.
Reversed output, pressure value and hysteresis can be set.
List of output modes
-26-
NO.ZK2-OM00501-B
Press the or button in function selection mode to display [F 1].
Press the button. Move on to the check of output mode.
Press the button to set. Move on to setting of reversed output.
Press the button to set. Move on to setting of pressure.
Press the button to set. Move on to setting of hysteresis.
Press the button to set. Return to function selection mode.
[F 1] Setting of OUT1 complete.
Check of output mode
Check the set value same as the display shown to the
right, then move on to next setting.
Setting of reversed output
Press the or button to select reversed
output.
Setting of pressure
Press the or button to
adjust pressure setting.
Setting of hysteresis
Press the or button to
select hysteresis.
-27-
NO.ZK2-OM00501-B
[F 2] Setting of OUT2
Set OUT2.
Set ON and OFF points of the supply pilot valve, and the range in which an input is not allowed.
Operation of OUT2
Supply pilot valve: OUT2 is turned on by the signal for suction. Suction starts by the generation of vacuum
pressure.
When the vacuum pressure reaches the set value (P_1 H_3: OFF point of supply pilot valve signal),
the supply pilot valve is turned off.
After that, when the vacuum level decreases and reaches the suction switch ON point (P_1 + H_2: Supply
pilot valve signal ON point), the supply pilot turns on again to maintain the vacuum.
After the supply pilot valve is turned off, the vacuum pressure will decrease.
When the vacuum pressure reaches the suction switch ON point (P_1 + H_2: ON point of supply pilot
valve signal), the solenoid valve for supply will turn ON again and increase the vacuum pressure.
Afterwards, The supply pilot valve repeats this ON and OFF cycle.
Area in which setting of H_2 is prohibited can be set by the range in which H_4: supply pilot valve signal is
prohibited to input.
The default settings are P_1-70.0 kPa, H_1:10.0 kPa, H_2:5.0 kPa, H_3:0.0 kPa, H_4:1.0 kPa
A
-28-
NO.ZK2-OM00501-B
Press the or button in function selection mode to display [F 2].
Press the button to set. Move on to setting of pressure.
Setting ON point of the supply pilot valve
Press the button to set. Move on to the next parameter.
Setting OFF point of the supply pilot valve
Press the button to set. Move on to the next parameter.
Set the range in which ON point of the supply pilot valve input is prohibited
Press the button to set. Return to function selection mode.
[F 2] Setting of OUT2 complete.
1: Selected parameter become effective after pressing the button.
2: After setting is made valid by the button, it is possible to move to measurement mode by pressing the button for 2 seconds or
longer.
3: OFF point (H_2) of the supply pilot valve is automatically corrected by setting the input prohibited range (H_4) of ON point of the
supply pilot valve.
Press the or button to change the set points.
A
-29-
NO.ZK2-OM00501-B
[F 3] Response time
Select the response time of the switch output.
Output chattering can be prevented by setting the response time.
Press the or button in function selection mode to display [F 3].
Press the button. Move on to setting of response time.
Press the button to set. Return to function selection mode.
Setting of [F 3] Response time completed.
Setting of response time
Press the or button to select the
response time.
-30-
NO.ZK2-OM00501-B
[F 4] Auto-preset function This function calculates and sets the pressure values automatically based on the on-going operation.
Press the or button in function selection mode to display [F 4].
Press the button. Move on to setting of auto-preset function.
Press the button to set. Return to function selection mode.
Setting of [F 4] Auto-preset completed.
Press button in measurement mode to set pressure. (Refer to page 31)
Then press button again to change the pressure while the display is flashing.
: ON/OFF point of the supply pilot valve and the set point of the input prohibited range of the supply pilot valve may be corrected
by the auto-preset function.
Setting of auto-preset
Press the or button to select auto-preset.
-31-
NO.ZK2-OM00501-B
Auto-preset
When auto-preset is selected in function selection mode, the set value can be calculated and memorized
from the measured pressure. Repeating the suction and release of a workpiece several times automatically
optimizes the set value.
1, Selection of auto-preset OUT1
Press the button in measurement mode to display "AP1".
2, Preparation of equipment for OUT1
Prepare equipment for which the pressure of OUT1 is to be set.
3, Setting of auto-preset for OUT1
Press the button, the display will show A1L" and pressure measurement
begins.
Operate the equipment and change the pressure.
When the a pressure change is detected, [A1H] will be displayed automatically,
continue operating the equipment in the same manner for several cycles.
4, Completion of setting
Press the button to set [P_1] and [H_1] (in reverse output mode [n_1] and [H_1] are set) and complete
auto-preset mode. The pressure switch will then return to measurement mode.
([n_1] and [H_1] are set in reverse output mode.)
The settings made in auto-preset mode are as follows.
P_1 = A-(A-B)/4 A = Maximum pressure value
H_1 = | (A-B)/2| B = Minimum pressure value
To clear the stored auto-preset settings, press the and buttons simultaneously for 1 second or
longer.
-32-
NO.ZK2-OM00501-B
[F 6] Fine adjustment of display value
This function is used to manually perform fine adjustment of the displayed pressure.
It is adjustable within the range 5% R.D.
Press the or button in function selection mode to display [F 6].
Press the button. Move on to setting of fine adjustment of display value.
Press the button to set.
Press the button to set. Return to function selection mode.
Setting of [F 6] Fine adjustment of display value completed.
Setting of fine adjustment of display value
Current pressure value is displayed.
Press the or button to adjust the display value.
To initialize the adjustment value, when [FSC] is displayed, press the and buttons simultaneously for more than 1 second.
-33-
NO.ZK2-OM00501-B
[F11] Display resolution
This function is used to change the pressure display resolution.
This can be used to prevent the digits from flickering on the display.
Press the or button in function selection mode to display [F11].
Press the button. Move on to setting of display resolution.
Press the button to set. Return to function selection mode.
Setting of [F11] Display resolution completed.
: It may not be possible to change the resolution depending on the unit of pressure selected..
The units that allow display resolution to be selected are MPa, kPa, kgf/cm2, psi and inHg.
(The units kgf/cm2, bar, psi and inHg can only be set when using a product with unit conversion function.)
[F 0] Unit selection function on page 24.
Setting of display resolution
Press the or button to select display resolution.
-34-
NO.ZK2-OM00501-B
[F80] Power saving mode
Power saving mode is selectable.
When selected and no buttons are pressed for 30 seconds, the pressure switch will shift to power saving
mode.
The default setting is normal mode (power saving mode off).
Press the or button in function selection mode to display [F80].
Press the button. Move on to setting of power saving mode.
Press the button to set. Return to function selection mode.
Setting of [F80] Power saving mode completed.
Power saving mode 1 remains enabled until turned off.
In power saving mode 1, the brightness of the whole display is reduced.
In power saving mode 2, when buttons are pressed the display is normal, but if no buttons are pressed for
30 seconds, it will revert to power saving mode. (Power saving is only enabled in measurement mode).
In power saving mode 2, a decimal point flashes and moves across the display.
(In saving mode 2, a decimal point flashes and modes across the display.)
Setting of power saving mode
Press the or button to select power saving mode.
-35-
NO.ZK2-OM00501-B
[F81] Security code
A security code can be selected, which must be entered to unlock the keys when the keys are locked.
In the default setting, entry of a security code number is not required.
Press the or button in function selection mode to display [F81].
Press the button. Move on to setting of security code.
Press the button to set. Return to function selection mode.
Setting of [F81] Security code complete.
If the security code is used, it becomes necessary to enter the security code to release the key lock.
The security code number can be set to a different value by an operator.
The default setting is "000".
Refer to page 44 or details of operation when the security code is used.
Setting of security code
Press the or button to select security code.
-36-
NO.ZK2-OM00501-B
[F90] Setting of all functions
All functions can be set, one after the other.
Press the or button in function selection mode to display [F90].
Press the button. Move on to setting of all functions.
[oFF] (unused)
selected.
Press the button
to set.
Return to function
selection mode.
[[on] (used) selected.
1: Setting of each function.
After the change to [oFF] (unused),
press the button to set.
Return to function selection mode.
Press the
button for 2
seconds or longer.
[F90] Setting of all functions completed. Measurement mode.
1: Setting of functions
Every time the button is pressed, the function steps in the order of "Order of function of setting" on page 37
Set by using the or buttons.
For details of how to set each function, refer to the relevant setting of function section in this manual.
Setting of all functions
Press the or button to select all functions.
-37-
NO.ZK2-OM00501-B
Order of function of setting
Order Function
1 Selection of display unit
2 Setting of output mode (OUT1)
3 Setting of reversed output (OUT1)
4 Setting of pressure (OUT1)
5 Setting of hysteresis (OUT1)
6 Setting of output mode (OUT2)
7 Supply pilot valve signal ON point
8 Supply pilot valve signal OFF point
9 Setting of hysteresis (OUT2)
Set the range in which the supply pilot valve input is prohibited
10 Setting of response time
11 Setting of display resolution
12 Setting of auto-preset
13 Setting of initialization of fine adjustment of display value
14 Setting of power saving mode
15 Setting of security code
: Return to measurement mode from any setting item by pressing the S button for 2 seconds or longer.
-38-
NO.ZK2-OM00501-B
[F96] Check of suction command signal
Press the or button in function selection mode to display [F96].
Press the button. Move on to the suction signal input check.
Press the button. Return to function selection mode.
[F96] Check of suction command signal completed.
Check of the input of suction command
signal status
When suction signal is not input, oFF is
displayed.
When suction signal is input, on is
displayed.
-39-
NO.ZK2-OM00501-B
[F98] Check of output
Output from the switch can be confirmed.
The output can be turned ON/OFF manually.
Press the or button in function selection mode to display [F98].
Press the button. Move on to check of output.
If [n] (normal
output) is
selected,
press the
button to set.
Return to
function
selection mode.
If [F] (forcibly output) is elected,
press the button to set.
Press the button to set.
Output check
Press the or button to select output check.
OUT1 check of output
Press the or button to
select OUT1 check of output.
-40-
NO.ZK2-OM00501-B
After returning to [n](normal output),
press the button to complete the
output check.
Press the
button for 2
seconds or
longer.
Setting of [F98] Check of output completed. Measurement mode.
Return to measurement mode from any point by pressing the button for 2 seconds or longer.
OUT2 check of output
Press the or
button to select check of
output2.
-41-
NO.ZK2-OM00501-B
[F99] Reset to the default setting
If the setting of the pressure switch becomes unknown, the default setting can be restored.
Press the or button in function selection mode to display [F 99].
Press the button. Move on to reset to the default setting.
All settings are returned to the
default values. Return to
function selection mode.
[oFF] (unused) selected.
Press the button to
confirm selection.
Return to the function
selection mode.
Setting of [F99] Reset to the default setting completed
Reset to the default setting
Set the display [ON] by pressing the or button,
then press the and buttons simultaneously for 5
seconds or longer.
-42-
NO.ZK2-OM00501-B
Other Settings
Peak/Bottom hold value display
The maximum (minimum) vacuum pressure from when the power was supplied to this moment is detected
and updated.
For peak display, when the button is pressed for 1 second or longer, the maximum vacuum pressure and
"Hi" starts flashing, and is held.
To release the display of the peak pressure value, press the button for 1 second or longer.
For bottom display, when the button is pressed for 1 second or longer, the minimum vacuum pressure
and "Lo" starts flashing and is held.
To release the display of the bottom pressure value, press the button for 1 second or longer again to
return to measurement mode.
If the and buttons are pressed simultaneously for 1 second or longer while the vacuum pressure is
being held, the maximum (minimum) values are reset.
Zero clear
The displayed value can be adjusted to zero when the pressure to be measured is within +/-3.5%F.S. of the
zero point set at the time of shipment from the factory.
Perform zero-clear while pressure is not applied.
The zero clear range varies by 1%F.S. due to variation between individual products.
When the and buttons are pressed for 1 second or longer simultaneously, display is reset to zero.
Measurement mode is returned to automatically.
Key-lock function
The key lock function is used to prevent errors occurring due to unintentional changes of the set values.
If a button operation is performed while the key lock setting is ON, "LoC" is displayed for approximately 1
second.
(When the button is pressed, the set pressure will be displayed following "LoC".)
(1) Press and hold the button for 5 seconds or longer in measurement mode.
The current setting "LoC" or "UnL" is displayed.
(To release key-lock, repeat the above operation)
(2) Press either the or button to select between locking and unlocking the keys.
(3) Press the button to enter the setting.
-43-
NO.ZK2-OM00501-B
Locking
1, Press and hold the button for 5 seconds or longer in measurement mode.
[UnL] is displayed.
2, Press the or button to select locking of the keys [LoC].
3, Press the button to enter the setting.
Unlocking
1, Press and hold the button for 5 seconds or longer in measurement mode.
[LoC] is displayed.
2, Press the or button to select locking of the keys [UnL].
3, When the button is pressed, input of the security code will be requested.
For how to enter the security code, refer to "How to entry the security code" on page 44.
4, If the security code entered is correct, the display changes to [UnL], and pressing any of the , or
buttons releases the key lock and returns the device to measurement mode.
If the security code entered is incorrect, [FAL] is displayed, following which the security code input
screen returns.
If the wrong security code is entered 3 times, [LoC] is displayed and the device returns to measurement
mode.
-44-
NO.ZK2-OM00501-B
How to change the security code
At the time of shipment, the security code is set to [000], but this can be changed to any number.
1, After the key lock setting has been completed, perform all three steps in the unlock setting
procedure. (page 43, "3,").
2, After the security code is entered and the indication changes to [UnL], Press and hold the and
buttons simultaneously for 5 seconds or longer.
[000] is displayed and the new security code should be entered.
For how to input the security code, refer to "How to input and change the security code".
The new security code will be displayed.
3, Check the new security code is as desired and press the button for 1 second or longer.
Return to the measurement mode.
At this time, if the or button is pressed, the security code is not changed and a new security
code should be entered.
How to entry the security code
The left most digit starts flashing.
Press the or button to change the value.
Press the button to make the next digit to the right flash.
(If the button is pressed when the last digit is flashing, the left
most digit starts flashing again).
After the setting is complete, Press and hold the button
for 1 second or longer.
(If an operation is not performed for 30 seconds during input or
change of the security code, it will return to measurement mode.)
-45-
NO.ZK2-OM00501-B
How to stop energy-saving control function If a large amount of leakage is generated at the work piece adsorption surface, energy-saving control
frequently occurs (the valve is turned ON and OFF when the vacuum is generated / stopped). In order to avoid this phenomenon, update the switch setting to stop the energy-saving control as shown below.
Normal energy- saving control
How to stop energy-
saving function
For stopping the energy-saving function, change the setting of H_3 to P_1 H_3 100.
Refer to page 25F 2OUT2 setting for the setting of H_3.
E.g.) In case of P_1-60 kPa, enter 45 to H_3.
(The equation will be changed to P_1H_3-60-45-105, so the vacuum pressure does not
reach the point where the energy-saving function is triggered.)
* The minimum value of P_1H_3 is -105. Values less than that cannot be entered.
* When the P_1 value needs to be changed, change the value of H_3 every time to maintain the
equation P_1 H_3 100.
B
Change of the switch setting
-46-
NO.ZK2-OM00501-B
Maintenance
How to reset the product for power cut or forcible de-energizing
The setting of the product will be retained as it was before a power cut or de-energizing.
The output condition is also basically recovered to that before a power cut or de-energizing, but may change
depending on the operating environment. Therefore, check the safety of the whole facility before operating the
product.
If the facility is under accurate control, wait until it has warmed up. (Approximately 10 to 15 minutes)
-47-
NO.ZK2-OM00501-B
Troubleshooting
Troubleshooting
Applicable Pressure switch: ZK2-ZSV-A
If an operational failure of the pressure switch occurs, please select the cause of failure from the flow chart
below.
If a cause applicable to the failure cannot be identified and normal operation can be recovered by
replacement with a new pressure switch, this indicates that the pressure switch itself was faulty.
The damage to the pressure switch may have been caused by the operating environment (network
construction, etc.). Consult with SMC separately to obtain countermeasures.
Yes
No
The pressure
switch does not
operate correctly
Refer to error
No.1 The switch output
is ON
The indication
LED is ON
The indication LED
operates incorrectly
The switch output
is OFF
The switch output is
chattering
The indication
LED is OFF
The indication
LED is OFF
The indication
LED is ON
Product
failure
Refer to error
No.2
Refer to error
No.1
Refer to error
No.4
Refer to error No.3
Product
failure
Product
failure
Refer to error No.6
Slow switch
output response
Refer to error No.5
An error is
displayed
-48-
NO.ZK2-OM00501-B
The units cannot be changed
The buttons cannot be operated
The display fluctuates
The product is noisy
The display disappears
The display flashes
Pressure display difference when using
2 or more Pressure switches
Refer to
reference No.7 The display is not
normal
Refer to
reference No.8
Refer to
reference No.9
Refer to
reference No.10
Refer to
reference No.13
Refer to
reference No.12
Refer to
reference No.14
The display breaks off
Refer to
reference No.15
Refer to
reference No.9
The display accuracy does not satisfy the
specifications
Refer to
reference No.11
Yes
No
A
-49-
NO.ZK2-OM00501-B
Cross-reference for troubleshooting
Error
No. Problem Possible cause Investigation method Countermeasure
1
Output remains
ON.
Indication LED
remains ON.
Output remains
OFF.
Indication LED
remains OFF.
Incorrect pressure
setting
(1) Check the set pressure value.
(2) Check the settings of the
hysteresis and output type.
(Normal output/reversed
output(out1) )
(1) Reset the pressure
settings.
(2) Reset the function
settings.
Product failure Replace the product.
2
Output remains
ON.
Indication LED
works correctly.
Incorrect wiring
Check the wiring of the output.
Check if the load is connected
directly to DC(+) or DC(-).
Correct the wiring.
Product failure Replace the product.
3
Output remains
OFF.
Indication LED
works correctly.
Incorrect wiring
Check the wiring of the output.
Check if the load is connected
directly to DC(+) or DC(-).
Correct the wiring.
Unsuitable model
selection
Check if PNP is used even though
NPN should have been selected, or
the other way around.
Review the selected model
(output type).
Broken lead wire
Check if there is bending stress
applied to any parts of the lead wire.
(Bending radius and tensile force
applied).
Correct the wiring.
(adjust the tensile force and
increase the bending radius).
Product failure Replace the product.
4
The switch output
generates
chattering.
Incorrect wiring
Check the wiring.
Check if the brown and blue wires
are connected to DC(+) and DC(-)
respectively, and if the output wiring
is loose (contact failure).
Correct the wiring.
Incorrect setting
(1) Check the pressure settings.
(2) Check if the hysteresis range is
too narrow.
(3) Check the setting of the response
time.
Check if the response time is too
short.
(1) Reset the pressure
settings.
(2) Increase the hysteresis.
(3) Change the response
time setting.
Product failure Replace the product.
5 Slow switch output
response.
Incorrect pressure
setting
Check the pressure settings.
Check if the detected pressure and
the set pressure values are the same
or are too close.
Adjust the set pressure
value.
Ensure the set pressure
value is not too close to the
detected pressure value.
-50-
NO.ZK2-OM00501-B
Error
No. Problem Possible cause Investigation method Countermeasure
6
An over current
error (Er1, 2) is
displayed.
System error
(Er0, 4, 6, 7, 8 or
9) is displayed.
HHH is
displayed.
LLL is
displayed.
Residual
pressure error
(Er3) is
displayed.
Over current to the
output (Er1 and 2)
(1) Check if the output current is 80
mA or more.
(2) Check if the specified load is
connected.
(3) Check if a relay without a surge
voltage suppressor is connected.
(4) Check if the wiring is in the same
route as (or bundled together with) a
high-voltage or power line.
(1)(2) Connect the
appropriate load.
(3) Use a relay with a surge
voltage suppressor or
take measures to
prevent noise.
(4) Separate the wiring from
the high-voltage and/or
power line.
Incorrect internal
data processing of
the product (Er0,
4, 6, 7, 8 or 9)
(1) Check if there is noise interference
(such as static electricity.
(2) Check if the power supply voltage
is in the range 24 VDC 10%.
(1) Remove the noise and the
noise source (or take
measures to prevent
noise interference), and
reset the product (or turn
off and then turn back on
the power supply.
(2) Supply power in the
range 24 VDC 10%.
Applied pressure
is over the upper
limit (HHH).
(1) Check that the pressure is not
above the upper limit of the set
pressure range.
(2) Check that foreign matter has not
entered the piping.
(1) Reset applied pressure
to a level within the set
pressure range.
(2) Take measures to prevent
foreign matter from
getting into the piping.
Applied pressure
is under the lower
limit (LLL).
(1) Check that the pressure is not
below the lower limit of the set
pressure range.
(2) Check that foreign matter has not
entered the piping.
(1) Bring the pressure back
within the set pressure
range.
(2) Take measures to prevent
foreign matter from
entering the piping.
Pressure is not
atmospheric
pressure at
zero-clear
operation (Er3).
Check that a pressure above
3.5%F.S. was not applied, during
zero-clear operation.
Return the applied pressure
to atmospheric pressure,
and retry the zero clear
operation.
Product failure Replace the product.
-51-
NO.ZK2-OM00501-B
Error
No. Problem Possible cause Investigation method Countermeasure
7 Displayed values
fluctuates.
Incorrect power
supply
Check if the power supply voltage is in
the range 24 VDC 10%.
Supply power supply
voltage of 24 VDC 10%.
Incorrect wiring
Check the power supply wiring
Check if the brown and blue wires are
connected to DC(+) and DC(-)
respectively, and if the wiring is
secure.
Correct the wiring and/or
load resistance.
Factory line
pressure is not
stable.
Check if the factory line pressure is
changing.
If the fluctuation is not
acceptable, the number of
digits (display sensitivity)
can be reduced by changing
the display resolution.
8
The display turns
OFF.
Part of the
display is
missing.
Incorrect power
supply
Check if the power supply voltage is in
the range 24 VDC 10%.
Supply power supply
voltage of 24 VDC 10%.
Incorrect wiring
Check the power supply wiring.
Check if the brown and blue wires are
connected to DC(+) and DC(-)
respectively, and if the wiring is
secure.
Correct the wiring.
Power saving
mode
Check if power saving mode is
selected.
Reset the setting of
function.
Product failure Replace the product.
9 The display
flashes.
Peak value/bottom
value display
mode is selected.
Check if peak value or bottom value
display mode is selected.
Turn off the peak
value/bottom value display
mode.
Wiring failure
(1) Check the power supply wiring.
(2) Check if bending stress is being
applied to a specific part of the
lead wire.
(1) Correct the wiring.
(2) Correct the wiring
(bending radius and
stress).
10
Pressure display
difference when
using 2 or more
Pressure switches
Dispersion within
the display
accuracy range
Check if the dispersion is within the
display accuracy range.
Use the fine adjustment
mode to adjust the display if
the dispersion is within the
display accuracy range.
Product failure Replace the product.
-52-
NO.ZK2-OM00501-B
Error
No. Problem Possible cause Investigation method Countermeasure
11
The pressure
display accuracy
does not meet the
specifications.
Foreign matter Check if any foreign matter has
entered the pressure port.
Install a 5 m filter to
prevent foreign matter from
getting into the pressure
port.
Also, clean the filter
regularly to prevent
drainage deposits.
Air or liquid
leakage
Check if air or liquid are leaking from
the piping.
Rework the piping.
If the tightening torque is
exceeded, the mounting
screws, brackets and the
pressure switch may be
damaged.
Insufficient
warm-up time
Check if the product satisfies the
specified accuracy 10 minutes after
supplying power.
After energizing, the display
and output can drift
For precise pressure
detection, allow the product
to warm up for 10 to 15
minutes.
Product failure Replace the product.
12
The display units
cannot be
changed.
Improper model
selection
(Selection of
model "without
unit selection
function")
Check if there is a "-M" at the end of
the part number printed on the
product.
"-M" in the part number
means that the
measurement unit cannot
be changed.
(kPa or MPa can be
selected.)
: The unit selection function is
not available in Japan due to
a new measurement law.
: It is fixed to the SI unit "kPa",
"MPa".
Product failure Replace the product.
13
The buttons
cannot be
operated.
Key-lock mode is
activated.
Check if the key-lock function is turned
on.
Release the key-lock
function.
Product failure Replace the product.
14 The product is
noisy.
Air or liquid
leakage
Check if air or liquid are leaking from
the piping.
Rework the piping.
If the tightening torque is
exceeded, the mounting
screws, brackets and the
pressure switch may be
damaged.
Product failure Replace the product.
-53-
NO.ZK2-OM00501-B
Error
No. Problem Possible cause Investigation method Countermeasure
15
Operation is
unstable
(chattering).
Effect of line
pressure
fluctuation
because
hysteresis is too
narrow or
response time is
too short
(1) Check the set pressure values
(hysteresis)
(2) Check the response time.
(1) Widen the hysteresis.
(2) Change the response
time setting.
Incorrect wiring/
broken lead wire
(1) Check the power supply wiring.
(2) Check if there is bending stress
applied to any parts of the lead
wire.
(Bending radius and tensile force
applied to the lead wire)
(1) Correct the wiring and/or
load resistance
(2) Correct the wiring.
(Reduce the tensile force
or increase the bending
radius.)
Product failure Replace the product.
A
-54-
NO.ZK2-OM00501-B
Error Indication
This function is to display error location and content when a problem or an error occurs.
Error Name Error Display Error Type Troubleshooting Method
Over current Error
The switch output load current is more than 80 mA.
Turn the power off and remove the
cause of the over current.
Then turn the power on.
Zero-clear Error
During the zero clear operation, pressure above 3.5%F.S. has been applied. After 1 second, the mode will return to measurement mode. The zero clear range can vary 1%F.S. with individual product differences.
Perform zero clear operation again
after restoring the applied pressure to
an atmospheric pressure condition.
Pressurizing Error
Pressure has exceeded the upper limit
of the set pressure range. Adjust the applied pressure to a level
within the set pressure range.
Pressure has exceeded the lower limit
of the set pressure range.
System Error
Displayed in the case of an internal
data error.
Turn the power off and turn it on again.
If resetting fails, an investigation by
SMC Corporation will be required.
If the error can not be reset after the above measures are taken, then please contact SMC.
-55-
NO.ZK2-OM00501-B
Specification
Specifications
Rated pressure range 100.0 to -100.0 kPa
Set pressure range 105.0 to -105.0 kPa
Proof pressure 500 kPa
Min. display unit 0.1 kPa
Applicable fluid Air, inert gas and non-flammable gas
Power supply voltage 24 VDC 10%, ripple max. 10%pk-pk (with polarity protection )
Current consumption 40 mA or less
Switch
Output NPN or PNP open collector
OUT1: General-purposeOUT2: Valve control
Maximum load current 80 mA
Max. applied voltage DC26.4 V
Residual voltage Max. 2 V (at 80 mA load current)
Response time 2.5 ms or less (response times available for anti-chattering function: : 20,
100, 500, 1000 or 2000 ms)
Short circuit protection Provided
Repeatability 0.2%F.S.1 digit
Hyster
esis Hysteresis mode Adjustable (can be set from 0) 1
Display 3 1/2 digits, 7-segment display, color display (Red)
Indicator accuracy +/-2%F.S., +/-1 digit (at ambient temperature 25+/-3 oC)
Indication LED Light when ON OUT1: Green OUT2: Red
Environ
ment
Enclosure IP40
Ambient temperature range 5 to 50 oC
Withstand voltage 1000 VAC for 1 minute between live parts and case insulation resistance
Insulation resistance 50 M or more at 500 VDC Between lead block and case
Temperature characteristic 2%F.S. (25 oC reference)
Lead wire
cable 5 cores 3.5, 2 m
Sectional area of conductor: 0.15 mm2 (AWG26)
Outside diameter of insulator: 1.0 mm
Standard CE marking, RoHS
1: If the applied pressure fluctuates around the set value, the hysteresis must be set to a value more than the amount of fluctuation or
chattering will occur.
NO.ZK2-OM00501-B
Revision history
A: Shorten the start-up time Elimination of copying function Fixed output of OUT2
B:How to stop energy-saving control
function
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer. 2011 SMC Corporation
Related manuals for SMC ZK2-ZSV-A Ejector Operation Manual
Manualsnet FAQs
If you want to find out how the ZK2-ZSV-A SMC works, you can view and download the SMC ZK2-ZSV-A Ejector Operation Manual on the Manualsnet website.
Yes, we have the Operation Manual for SMC ZK2-ZSV-A as well as other SMC manuals. All you need to do is to use our search bar and find the user manual that you are looking for.
The Operation Manual should include all the details that are needed to use a SMC ZK2-ZSV-A. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.
The best way to navigate the SMC ZK2-ZSV-A Ejector Operation Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.
This SMC ZK2-ZSV-A Ejector Operation Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.
You can download SMC ZK2-ZSV-A Ejector Operation Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.
To be able to print SMC ZK2-ZSV-A Ejector Operation Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the SMC ZK2-ZSV-A Ejector Operation Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.