Pelco KBD200A C526-J Keyboard Installation Manual PDF

1 of 36
1 of 36

Summary of Content for Pelco KBD200A C526-J Keyboard Installation Manual PDF

Installation/Operation

KBD200A Universal Keyboard

C526M-J (3/04)

SHIFT

SEQUENCE

F1

F2

F3

F4

F5

MON

ACK PREV

NEXT HOLD

PATTERN PRESET MACRO

PGM

ZOOM

WIDE

CLOSE

FAR

IRIS

1 2

34 5

67 8

9 0

CLEAR

CAM

KBD200AMADE IN USA.

Pelco World Headquarters 3500 Pelco Way, Clovis, CA 93612-5699 USA www.pelco.com USA & Canada: Tel: 800/289-9100 Fax: 800/289-9150

International: Tel: 1-559/292-1981 Fax: 1-559/348-1120

[ 2 ] Pelco Manual C526M-J (3/04)

CONTENTS

Section Page

IMPORTANT SAFTY INSTRUCTIONS ............................................................................................................. 4

REGULATORY NOTICES .................................................................................................................................. 5

DESCRIPTION ................................................................................................................................................. 6

INSTALLATION CM6700 MODE .................................................................................................................. 8 Connecting a Keyboard to the Local Keyboard Port ............................................................................. 8 Connecting Keyboards to the Remote Keyboard(s) Port ...................................................................... 8

INSTALLATION CM6800 MODE ................................................................................................................ 10 Connecting KBD200A Direct-Powered Keyboards ............................................................................. 10 Connecting KBD200A Remote Keyboards .......................................................................................... 12

INSTALLATION DIRECT MODE .................................................................................................................. 14 Connecting the Keyboard ................................................................................................................... 14

INSTALLATION CM6700 ASCII MODE ...................................................................................................... 16 RS-232 Interface (CM6700) ................................................................................................................ 16 RS-422 Interface (CM6700) ................................................................................................................ 18

INSTALLATION CM6800 ASCII MODE ...................................................................................................... 20 RS-232 Interface (CM6800) ................................................................................................................ 20 RS-485 Interface (CM6800) ................................................................................................................ 22

SWITCH SETTINGS ...................................................................................................................................... 25

PROGRAMMING AND OPERATION .............................................................................................................. 26 Scanning Functions ............................................................................................................................ 31 Programming Limit Stops ................................................................................................................... 31 Zones .................................................................................................................................................. 32

SPECIFICATIONS ........................................................................................................................................... 33

PRODUCT WARRANTY AND RETURN INFORMATION ................................................................................ 34

Pelco Manual C526M-J (3/04) [ 3 ]

List of Illustrations

Figure Page Figure 1. Wiring Diagram for Local/Remote Keyboards 9 Figure 2. Keyboard Cabling Diagram ............................................................................................................ 9 Figure 3. Data Cables Plugged into COM 5 and 6 (CM6800-48X8 Shown) ................................................ 11 Figure 4. Connecting Remote Keyboards (CM6800-48X8 Shown) .............................................................. 13 Figure 5. Direct Mode Keyboard and Receiver Wiring ............................................................................... 15 Figure 6. RS-232 Interface connections (CM6700) ..................................................................................... 17 Figure 7. RS-422 Interface Connections (CM6700) ..................................................................................... 19 Figure 8. RS-232 Interface Connections (CM6800-48X8 Shown) ............................................................... 21 Figure 9. RS-485 Interface Connections (CM6800-48X8 Shown) ............................................................... 23 Figure 10. COM Port Connections and RJ-45 Connector Pin-Outs ............................................................. 24 Figure 11. Keyboard Rear Panel .................................................................................................................. 25 Figure 12. Keyboard Functions .................................................................................................................... 29

List of Tables

Table A. KBD200A Operational Features ..................................................................................................... 7 Table B. Keyboard Addresses ...................................................................................................................... 25 Table C. Keyboard Modes ........................................................................................................................... 25 Table D. Keyboard Functions ....................................................................................................................... 26 Table E. KBD200A Button Functions ........................................................................................................... 30 Table F. Operating Scan Functions with Various Receivers ........................................................................ 31 Table G. Limit Set Codes ............................................................................................................................. 31 Table H. Zone Programming Procedure ....................................................................................................... 32

[ 4 ] Pelco Manual C526M-J (3/04)

IMPORTANT SAFTY INSTRUCTIONS

Read these instructions.

Keep these instructions.

Heed all warnings.

Follow all instructions.

Do not use this apparatus near water.

Clean only with dry cloth.

Do not block any ventilation openings. Install in accordance with the manufacturers instructions.

Do not install near any heat sources such as radiators, heat registers, stoves, or other apparatus (including amplifiers) that produce heat.

Only use attachments/accessories specified by the manufacturer.

Refer all servicing to qualified service personnel. Servicing is required when the apparatus has been damaged in any way, such as power-supply cord or plug is damaged, liquid has been spilled or objects have fallen into the apparatus, the apparatus has been exposed to rain or moisture, does not operate normally, or has been dropped.

Apparatus shall not be exposed to dripping or splashing and that no objects filled with liquids, such as vases shall be placed on the apparatus.

WARNING: To reduce the risk of fire or electric shock, do not expose this apparatus to rain or moisture.

Installation should be done only by qualified personnel and conform to all local codes.

Unless the unit is specifically marked as a NEMA Type 3, 3R, 3S, 4, 4X, 6, or 6P enclosure, it is designed for indoor use only and it must not be installed where exposed to rain and moisture.

CAUTION: These servicing instructions are for use by qualified service personnel only. To reduce the risk of electric shock do not perform any servicing other that contained in the operating instructions unless you are qualified to do so.

Only use replacement parts recommended by Pelco.

Pelco Manual C526M-J (3/04) [ 5 ]

REGULATORY NOTICES

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference re- ceived, including interference that may cause undesired operation.

RADIO AND TELEVISION INTERFERENCE This equipment has been tested and found to comply with the limits of a Class B digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful in- terference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However there is no guarantee that the interference will not occur in a particu- lar installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the inter- ference by one or more of the following measures:

Reorient or relocate the receiving antenna. Increase the separation between the equipment and the receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is

connected. Consult the dealer or an experienced radio/TV technician for help.

You may also find helpful the following booklet, prepared by the FCC: How to Identify and Resolve Radio- TV Interference Problems. This booklet is available from the U.S. Government Printing Office, Washington D.C. 20402.

Changes and Modifications not expressly approved by the manufacturer or registrant of this equipment can void your authority to operate this equipment under Federal Communications Commissions rules.

[ 6 ] Pelco Manual C526M-J (3/04)

DESCRIPTION The KBD200A Universal Keyboard has many operational features (refer to Table A) and can be used in numerous operational modes:

CM6700 Mode: Program and operate the CM6700 Matrix Switcher/Controller Unit (SCU). Also control a Genex multiplexer from a CM6700 SCU. Multiple keyboards can be used in this mode.

CM6800 Mode: Program and operate the CM6800 Matrix Switcher/Controller Unit (SCU). Also control a Genex multiplexer from a CM6800. Multiple keyboards can be used in this mode.

Direct P Mode: Control up to 16 receivers connected directly to the keyboard. Only one keyboard can be used in this mode. A separate system, such as an MS500 or VA6100 Switcher, is needed to route video to the monitor.

NOTE: The KBD200A keyboard also can be used in Direct Mode to program a CM9760-MDA Master Distribution Amplifier. Refer to the CM9760-MDA manual for details.

CM6700 ASCII Mode: Use an RS-232 or RS-422 interface to operate the CM6700 and RS-232 or RS-485 to operate the CM6800. Also control a Genex multiplexer from a CM6700 or CM6800. Use this mode with communication facilities that introduce any type of delay, such as dial-up or fiber optic. The ASCII Mode uses a non-polling protocol that is immune to delays. One keyboard can be used in ASCII Mode, but oth- ers may be connected at the local and remote keyboard ports (CM6700 Mode or CM6800 Mode). The CM6700 and CM6800 cannot be programmed from a keyboard operating in ASCII Mode.

The latest firmware release (version 5.00) allows two additional modes:

CM6800 ASCII Mode: This mode supports the CM6800 GPI commands. The F1, F2, and F3 keys control the relays on an REL2064 that is connected to a CM6800 switcher. To enable this mode, DIP switch 6 must be ON and DIP switch 8 must be ON.

Direct D Mode: This mode is similar to the Direct P Protocol that already exists, except that the same set of commands are now sent in Direct D Protocol. To enable this mode, DIP switches 5 and 6 must be ON.

NOTE: You must upgrade your KBD firmware to version 5.00 if the application requires you to select two-digit monitor numbers.

Pelco Manual C526M-J (3/04) [ 7 ]

Table A. KBD200A Operational Features

CM6700/ Direct CM6700 CM6800 Direct Function CM6800 P* ASCII** ASCII*** D***

Automatically recognize the mode Yes Yes No No No

Select cameras Yes Yes Yes Yes Yes

Select monitors Yes No Yes Yes No

Control lenses Yes Yes Yes Yes Yes

Set and call presets/patterns Yes Yes Yes Yes Yes

Create Zones Yes Yes Yes Yes Yes

Control latching receiver auxiliaries Yes Yes Yes Yes Yes

Control momentary receiver auxiliaries Yes Yes Yes Yes Yes

Control multiplexer Yes No Yes Yes No Control Matrix Switcher Yes No Yes Yes No Program Matrix Switcher Yes No No No No

Sequencing Yes No Yes Yes No

Operate frame, auto, and random scans Yes Yes Yes Yes Yes

Program and operate patterns Yes Yes Yes Yes Yes

Control CM6700 auxiliaries Yes No Yes No No

Control CM6800 GPIs Yes No No Yes No

***Firmware version 2.00 and higher ***Firmware version 3.00 and higher ***Firmware version 5.00 and higher

[ 8 ] Pelco Manual C526M-J (3/04)

INSTALLATION CM6700 MODE

There are two keyboard ports on the CM6700 SCU.

The LOCAL KEYBOARD port is for connecting a single keyboard within a distance of 25 feet (7.6 meters).

The REMOTE KEYBOARD(S) port is for connecting additional remote keyboards.

Connecting a Keyboard to the Local Keyboard Port Use the data cable that is supplied with the keyboard. Plug one end of the cable into the RJ-45 connec-

tor on the rear of the keyboard and the other end into the LOCAL KEYBOARD port on the SCU (refer to Figure 1). Set the switches according to the instructions in the Switch Settings section. Go to step 2 to install remote keyboards, or go to step 10.

Connecting Keyboards to the Remote Keyboard(s) Port NOTE: A KBDKIT or KBDKIT-X is required for this application. The KBDKIT consists of two RJ-45 wall blocks and a 120 VAC to 12 VAC transformer. The KBDKIT-X is for 230 VAC. Use one KBDKIT for each keyboard.

Refer to Figures 1 and 2 for the following steps.

Decide on a suitable location for each keyboard and wall block. Keyboards must be within 25 feet (7.6 meters) of the wall block. Wall blocks must be within 6 feet (1.8 m) of the nearest suitable electrical out- let. Do not mount the wall block at this time.

Run wall block interconnect cable (user-supplied) from the SCU to the closest keyboard location, then to the next nearest location, and the next, etc.

Communication to the keyboards is RS-485. Maximum cable distance for RS-485 communication over 24- gauge wire is 4,000 feet (1,219 m). Pelco recommends using shielded twisted pairs cable that meets or exceeds the basic requirements for EIA RS-485 applications.

Remove the wall block cover and make cable connections at each wall block.

At each wall block, wire the transformer to pins 3 and 4. Polarity is unimportant.

Replace the cover on the wall block. Secure the wall block to a suitable surface. A double-sided sticky pad is provided to mount the wall block.

Set the switches for each keyboard according to the instructions in the Switch Settings section.

Plug in all keyboard data cables.

Plug the KBDKIT or KBDKIT-X transformer into a suitable outlet.

To initialize the keyboard, wait five seconds after powering-up the CM6700, enter the number for the monitor you are viewing (1-4), and press MON. The LED display shows the number entered.

NOTE: You must re-initialize whenever power is cycled.

Go to the Programming and Operation section and program and test for proper operation.

Pelco Manual C526M-J (3/04) [ 9 ]

KBDKIT

25-FOOT KEYBOARD DATA CABLE

KBD KBD

ADDITIONAL KEYBOARDS

USER-SUPPLIED CABLE

25-FOOT KEYBOARD DATA CABLE

KBD

LOCAL KEYBO ARD

LOCAL KEYBOARD

REMOTE KEYBOARDS

8 8 2 2

3

1

CM6700

6 REPLACE COVER

7

6 REPLACE COVER

7

25-FOOT KEYBOARD DATA CABLE

SET SWITCHES (PAGE 12)

Figure 1. Wiring Diagram for Local/Remote Keyboards

TERMINAL

1

2

3

4

5

6

7

8

TERMINAL

1

2

3

4

5

6

7

8

R+R-T-T+

LOCAL

RJ-45WALL BLOCK TERMINALS

1

2

3

4 5

6

7

8

12 VAC12 VAC

4 4 TX+

TX-

AC

AC

GND

RX-

RX+

5 5

9 9

USER-SUPPLIED CABLE TX+

TX-

AC

AC

GND

RX-

RX+

Figure 2. Keyboard Cabling Diagram

[ 10 ] Pelco Manual C526M-J (3/04)

INSTALLATION CM6800 MODE

You can connect up to eight KBD200A keyboards to any of the following ports:

For the CM6800-48X8: COM 5 (one direct-powered keyboard or up to eight remotely connected keyboards) COM 6 (same as COM 5) COM 7 (up to eight remotely connected keyboards) COM 8 (same as COM 7)

The total number of KBD200A Series keyboards connected to the CM6800-48X8 cannot exceed 16.

For the CM6800-32X6: COM 4 (up to eight remotely connected keyboards) COM 5 (one direct-powered keyboard or up to eight remotely connected keyboards)

The total number of KBD200A Series keyboards connected to the CM6800-32X6 cannot exceed eight.

Connecting KBD200A Direct-Powered Keyboards For direct-powered local keyboards, use COM 5 and 6 (serial ports 5 and 6) for the CM6800-48X8 and COM 5 (serial port 5) for the CM6800-32X6. Each port can power one KBD200A keyboard. A KBDKIT(-X) is required if the distance between the CM6800 and the keyboard exceeds 25 feet.

Refer to Figure 3 (CM6800-48X8 shown).

Using the 25-foot (7.62 m) straight data cable supplied with the keyboard, plug one end into the RJ-45 connector on the rear of the keyboard. Plug the other end into either COM 5 or 6 on the CM6800-48X8 or COM 5 on the CM6800-32X6.

Set the keyboard switches according to the instructions in the Switch Settings section. Go to the next section, Connecting KBD200A Remote Keyboards. Go to step 1 to install remote keyboards, or go to step 9.

Pelco Manual C526M-J (3/04) [ 11 ]

C O M 1

1

2

3

4

5

6

7

8

16

87

3231

43

VIDE O O UTPUTS 120/230~ 50/60 HZ

25 WATT S

C O M

AL AR M 1 2 3 4 5 6 7 8

C O NTR O L

PTZ

O UT

A T +

T -

R +

R -

T +

T -

R +

R -

B

1 2

F 3

MAXIMUM NUMBER OF KEYBOARDS POWERED BY COM 5 & 6: 1 PER PORT NOTE: THE TOTAL NUMBER OF KBD200A SERIES KEYBOARDS CONNECTED TO THE CM6800 CANNOT EXCEED 16. KBDKIT(-X) REQUIRED WHEN WIRING MORE THAN 1 KEYBOARD TO A PORT.

KBD200A RJ-45 PIN-OUTS

1 Tx+ 2 Tx- 3 12V 4 12V 5 GROUND 6 NC 7 Rx- 8 Rx+

CM6800 COM 5 & 6 RJ-45 PIN-OUTS

1 Rx+ 2 Rx- 3 KBD 12V 4 KBD GROUND 5 GROUND 6 NC 7 Tx- 8 Tx+

KBD200AKBD200A

01233

Figure 3. Data Cables Plugged into COM 5 and 6 (CM6800-48X8 Shown)

[ 12 ] Pelco Manual C526M-J (3/04)

Connecting KBD200A Remote Keyboards

For remote keyboard connections, use COM 5, 6, 7, or 8 for the CM6800-48X8 and COM 4 or 5 for the CM6800-32X6. Each port can support up to eight KBD200A keyboards. Do not exceed 16 total keyboards for the CM6800-48X8 and eight total keyboards for the CM6800-32X6.

A KBDKIT or KBDKIT(-X) is required to connect remote keyboards. Each kit contains two RJ-45 wall blocks and a transformer. Use one wall block for each keyboard.

Refer to Figure 4 (CM6800-48X8 shown).

Pick a suitable location for each keyboard and wall block. Wall blocks must be within 6 feet (1.8 m) of a suitable electrical outlet. Do not mount the wall blocks yet.

Connect each keyboard to a wall block, using the supplied keyboard data cable.

Remove the wall block covers and wire the connections between each wall block. Connect to a final wall block (which will be connected to the CM6800).

Communication to the keyboards is RS-485. Maximum cable distance for RS-485 communication over 24-gauge wire is 4,000 feet (1,219 m). Pelco recommends using shielded twisted pair cable that meets or exceeds the basic requirements for EIA RS-485 applications.

At each wall block, wire the KBDKIT or KBDKIT(-X) transformer to pins 3 and 4. Polarity is unimportant.

Replace the wall block cover. Secure the wall block to a suitable surface using the double-sided sticky pad.

Set the address switches for each keyboard (refer to the Switch Settings section). (If using COM 7 or 8, the port settings on the CM6800-48X8 must be changed from the default settings. Refer to the CM6800 manual.)

Connect the final wall block to COM 5, 6, 7, or 8 on the CM68000-48X8 or COM 4 or 5 for the CM6800-32X6 using a straight data cable (supplied with the CM6800).

Plug the KBDKIT or KBDKIT-X transformers into a suitable outlet.

To initialize the keyboard, wait five seconds after powering-up the CM6800, enter the number for the monitor you are viewing, and press MON. The LED display shows the number entered.

NOTE: You must re-initialize whenever power is cycled.

Go to the Programming and Operation section and program and test for proper operation.

Pelco Manual C526M-J (3/04) [ 13 ]

COM 1

1

2

3

4

5

6

7

8

16

87

3231

43

VIDEO OUTPUTS 120/230~

50/60 HZ

25 WATTS

COM

ALARM

1 2 3 4 5 6 7 8

CONTROL

PTZ

OUT

A T +

T -

R +

R -

T +

T -

R +

R -

B

1 2

F 3

MAXIMUM NUMBER OF KEYBOARDS: 8 PER PORT NOTE: THE TOTAL NUMBER OF KBD200A SERIES KEYBOARDS CONNECTED TO THE CM6800 CANNOT EXCEED 16.

KBD200A RJ-45 PIN-OUTS

1 Tx+ 2 Tx- 3 NC 4 NC 5 GROUND 6 NC 7 Rx- 8 Rx+

CM6800 COM 7 & 8 RJ-45 PIN-OUTS

1 Rx+ 2 Rx- 3 12V 4 12V 5 GROUND 6 NC 7 Tx- 8 Tx+

2

3

4 5

6

7

1 8

2

3

4 5

6

7

1 8

2

3

4 5

6

7

1 8

2

3

4 5

6

7

1 8

KBD200A

KBDKIT(-X) 1 REQUIRED PER KEYBOARD

WALL BLOCK

12V TRANSFORMER

4-CONDUCTOR, SHIELDED, 24-GAUGE, SUCH AS BELDEN 9843 (USER-SUPPLIED)

KBD200A

KBD200A

Figure 4. Connecting Remote Keyboards (CM6800-48X8 Shown)

[ 14 ] Pelco Manual C526M-J (3/04)

INSTALLATION DIRECT MODE

Direct Mode is for a single-keyboard installation only. You can communicate using Pelco P or Pelco D Pro- tocol. The keyboard is wired directly to a maximum of 16 receivers. Direct Mode installation/operation is not the same as CM6700 Mode or CM6800 Mode installation/operation. A separate system, such as an MS500 or VA6100 switcher, is required for routing video to the monitor(s).

In Direct P and Direct D modes you can now change the zoom speed of a PTZ by entering a number from 1 to 4 followed by a zoom command. This causes the zoom speed command to be sent.

Connecting the Keyboard Refer to Figure 5.

Make sure all receivers are configured to communicate using Pelco P or Pelco D Protocol and that each receiver has a unique address. Refer to your receiver manual for switch settings.

NOTE: A KBDKIT or KBDKIT-X is required to use the keyboard in Direct Mode. The KBDKIT consists of two RJ-45 wall blocks and a 120 VAC to 12 VAC transformer. The KBDKIT-X is for 230 VAC. Only one wall block is required for this application.

Decide on a suitable location for the keyboard and wall block. The keyboard must be within 25 feet (7.6 meters) of the wall block. The wall block must be within 6 feet (1.8 m) of the nearest suitable electrical outlet. Do not mount the wall block at this time.

Remove the cover from the KBDKIT or KBDKIT-X wall block. Connect the transmission wires from the receiver (Spectra/Esprit system) to the wall block. Refer to Figure 10 and do the following: Connect RX+ from receiver/driver to TX+ (terminal 1) on the wall block. Connect RX- from receiver/driver to TX- (terminal 2) on the wall block

NOTE: Communication to the keyboards is RS-422. Maximum cable distance for RS-422 communica- tion over 24-gauge wire is 4,000 feet (1,219 m). Pelco recommends using shielded twisted pair cable that meets or exceeds the basic requirements for EIA RS-422 applications.

At the wall block wire the transformer to pins 3 and 4. Polarity is unimportant.

Replace the cover on the wall block. A double-sided sticky pad is provided to mount the wall block. Secure the wall block to a suitable surface.

Set the keyboard DIP switches according to the instructions in the Switch Settings section.

Plug in the keyboard data cable.

Plug the KBDKIT or KBDKIT-X transformer into a suitable outlet. The LED display shows number 1, which is the default camera number.

Go to the Programming and Operation section and program and test for proper operation.

Pelco Manual C526M-J (3/04) [ 15 ]

6 REPLACE COVER

2

3

4 5

6

7

1 8

KBD300A

25-FOOT KEYBOARD DATA CABLE

TO RECEIVER(S) RX-/RX+

TWISTED PAIR

12 VA C

TX-

TX+

KBDKIT OR KBDKIT-X

9

CONFIGURE RECEIVERS

6 SET SWITCHES

20110

Figure 5. Direct Mode Keyboard and Receiver Wiring

[ 16 ] Pelco Manual C526M-J (3/04)

INSTALLATION CM6700 ASCII MODE

One ASCII keyboard can be installed, using either an RS-232 or RS-422 interface. If additional local and remote keyboards are used, you should install them according to the instructions in theInstallation CM6700 Mode and Installation CM6800 Modesections before doing an ASCII installation.

For installation at a remote location that is served by an RS-232 communications facility (such as via dial- up phone lines), use an RS-232 connection at both the KBD keyboard and the matrix switcher. (Refer to the RS-232 Interface section below.)

For installation at a remote location that is served by an RS-422 communications facility (such as direct-wire or fiber-optic terminals), use an RS-422 connection at both the KBD keyboard and the matrix switcher. (Refer to the RS-422 Interface section.)

NOTE: A KBDKIT or KBDKIT-X is required to use the keyboard in ASCII Mode. The KBDKIT consists of two RJ-45 wall blocks and a 120 VAC to 12 VAC transformer. The KBDKIT-X is for 230 VAC. Use one wall block.

RS-232 Interface (CM6700) An RS-232/RS-422 converter and power supply (Pelco part number PV130) are required. They are not in- cluded and must be ordered separately.

Refer to Figure 6.

Remove the cover from the CM6700 SCU and verify that the DIP switches for COM 2 are set for RS-232. Refer to the COM 2 Port section in the CM6700 Installation/Operation Manual for setting the switches. Reinstall the cover.

Use an existing CM6700 keyboard to program the COM 2 communication port. (If there is no other keyboard, use the one you are installing. Set all DIP switches OFF and plug the keyboard into the Lo- cal Keyboard port on the back of the CM6700. Remove when programming is completed.) Refer to the Setting COM 2 Communication Parameters section in the CM6700 Installation/Operation Manual for programming instructions. Set COM 2 port parameters as follows:

Baud: 9600, Parity: Odd, Stop Bits: 1

At the CM6700 SCU, connect the COM 2 RS-232 port to the output of the RS-232 device at the SCU side of the transmission link.

Decide on a suitable location for the keyboard and wall block. The keyboard must be within 25 feet (7.6 m) of the wall block. The wall block must be within 6 feet (1.8 m) of the nearest suitable electri- cal outlet. Do not mount the wall block at this time.

Remove the wall block cover and make connections between the wall block and the RS-232/RS-422 converter.

Wire the +12 VDC power supply to the converter.

Connect the RS-232 side of the converter to an RS-232 device that interfaces the transport network.

At the wall block wire the transformer to pins 3 and 4. Polarity is unimportant.

Replace the cover on the wall block. A double-sided sticky pad is provided to mount the wall block. Secure the wall block to a suitable surface.

Pelco Manual C526M-J (3/04) [ 17 ]

LOCAL KEYBOARD

1

2

3

4

5

6

7

8

12 VA C

KBDKIT RJ-45 WALL BLOCK

TERMINALS

RS-232 RS-422

CM6700SCU

RS-232 DEVICE

RS-232 DEVICE

PV130 RS-232/RS-422

CONVERTER RD (B) RD (A)

TD (A) TD (B)

TX+ TX-

TERMINAL

RX- RX+

POWER SUPPLY

+12 VDC GND

9-PIN, MALE CONNECTOR ON CONVERTER

CUSTOMER SUPPLIED WIRING. 50 FEET MAXIMUM DISTANCE.

MAXIMUM DISTANCE OF 4,000 FEET. USE SHIELDED TWISTED PAIRS SUCH AS BELDEN 9843 OR EQUIVALENT.

SCU COM 2 PIN 7 (TX+) 9 (GND) 12 (RX+)

12

6

7

13

5 8

RS-232 CUSTOMER SUPPLIED WIRING. 50 FEET MAXIMUM DISTANCE.

3

KBD200A

4

25-FOOT KEYBOARD DATA CABLE

10

WALL BLOCK

1

2

3

14 POWERUP

SCU

9 REPLACE COVER

11 SET SWITCHES

DB9 PINS 3(TX+) 2(RX+)

5(GND)

ANY RS-232 NETWORK

TRANSPORT NETWORK

1

2

3

4 5

6

7

8

NOTE: A SEPARATE PATH MUST BE PROVIDED FOR VIDEO TO THE MONITOR.

Set the keyboard DIP switches for ASCII Mode according to the instructions in the Switch Settings section.

Plug in the keyboard data cable.

Plug the +12 VDC power supply into a suitable outlet.

Plug the KBDKIT or KBDKIT-X transformer into a suitable outlet.

Apply power to the CM6700 SCU (if not already powered). To initialize the keyboard, wait five sec- onds after power-up, enter the number for the monitor you are viewing (1-4), and press MON. The LED display shows the number entered. You can now use the keyboard to perform all normal keyboard functions except you cannot program the CM6700.

Go to the Programming and Operation section and program and test for proper operation.

Figure 6. RS-232 Interface connections (CM6700)

[ 18 ] Pelco Manual C526M-J (3/04)

RS-422 Interface (CM6700) Refer to Figure 7.

Remove the cover from the CM6700 SCU and verify that the DIP switches for COM 2 are set for RS-422. Refer to the COM 2 Port section in the CM6700 Installation/Operation Manual for setting the switches. Reinstall the cover.

Use an existing CM6700 keyboard to program the COM 2 communication port. (If there is no other keyboard, use the one you are installing. Set all DIP switches OFF and plug the keyboard into the Lo- cal Keyboard port on the back of the CM6700. Remove when programming is completed.) Refer to the Setting COM 2 Communication Parameters section in the CM6700 Installation/Operation Manual for programming instructions. Set COM 2 port parameters as follows:

Baud: 9600, Parity: Odd, Stop Bits: 1

Decide on a suitable location for the keyboard and wall block. The keyboard must be within 25 feet (7.6 meters) of the wall block. The wall block must be within 6 feet (1.8 m) of the nearest suitable electrical outlet. Do not mount the wall block at this time.

Remove the wall block cover and make connections between the wall block and COM 2 of the CM6700 SCU.

At the wall block wire the transformer to pins 3 and 4. Polarity is unimportant.

Replace the cover on the wall block. A double-sided sticky pad is provided to mount the wall block. Secure the wall block to a suitable surface.

Set the keyboard DIP switches according to the instructions in the Switch Settings section.

Plug in the keyboard data cable.

Plug the KBDKIT or KBDKIT-X transformer into a suitable outlet.

Apply power to the CM6700 (if not already powered). To initialize the keyboard, wait five seconds after power-up, enter the number for the monitor you are viewing (1-4), and press MON. The LED dis- play shows the number entered.

Once you apply power to the keyboard and the CM6700 SCU, you can use the keyboard in the same manner as a normal keyboard except that in ASCII Mode you cannot program the CM6700.

Go to the Programming and Operation section and program and test for proper operation.

Pelco Manual C526M-J (3/04) [ 19 ]

KBDKIT RJ-45 WALL BLOCK

TERMINALS POWERUP

SCU

REPLACE COVER

SCU COM 2 PIN 12 (RX+) 11 (RX-) 8 (TX-) 7 (TX+)

WALL BLOCK TERMINAL 1 (TX+) 2 (TX-) 7 (RX-) 8 (RX+)

TO

1

2

3

4 5

6

7

8

10

SET SWITCHES

LOCAL KEYBOARD

1

2

3

4

5

6

7

8

12 VA C

CM6700SCU

TERMINAL

MAXIMUM DISTANCE OF 4,000 FEET. USE SHIELDED TWISTED PAIRS SUCH AS BELDEN 9843 OR EQUIVALENT.

KBD200A

25-FOOT KEYBOARD DATA CABLE

1

2

4

3 5

7 4

9

6

8

NOTE: A SEPARATE PATH MUST BE PROVIDED FOR VIDEO TO THE MONITOR.

Figure 7. RS-422 Interface Connections (CM6700)

[ 20 ] Pelco Manual C526M-J (3/04)

INSTALLATION CM6800 ASCII MODE

RS-232 Interface (CM6800) An RS-232/RS-422 converter and power supply (Pelco part number PV130) are required. They are not in- cluded and must be ordered separately.

Refer to Figures 8 (CM6800-48X8 shown) and 10.

Use an existing CM6800 keyboard to program the COM 1, 2, 7, or 8 communication port for the CM6800-48X8 or COM 1 or 2 communication port for the CM6800-32X6. (If there is no other key- board, use the one you are installing. Set all DIP switches OFF and plug the keyboard into the Local Keyboard port on the back of the CM6800. Remove when programming is complete.)

Do the following to program the COM port:

a. Press the PGM key. At the prompt, enter the password (default is 2899100). The CM6800 Main Menu appears.

b. Select PORT. The Set Serial Port screen appears.

c. Select the number of the desired port.

d. Set COM port parameters as follows: Device: ASCII, Type: RS-232, Baud: 9600, Parity: Odd, Data Bits: 8, Stop Bits: 1.

e. Select RETURN, and RETURN again.

At the CM6800, connect the COM 1, 2, 7, or 8 RS-232 port (CM6800-48X8) or COM 1 or 2 RS-232 port (CM6800-32X6) to the output of the RS-232 device on the CM6800 side of the transmission link.

Decide on a suitable location for the keyboard and wall block. The keyboard must be within 25 feet (7.6 m) of the wall block. The wall block must be within 6 feet (1.8 m) of the nearest suitable electri- cal outlet. Do not mount the wall block yet.

Remove the wall block cover and make the connections between the wall block and the RS-232/RS-422 converter.

Wire the +12 VDC power supply to the converter.

Connect the RS-232 side of the converter to an RS-232 device that interfaces the transport network.

At the wall block, wire the transformer to pins 3 and 4. Polarity is unimportant.

Replace the cover on the wall block. Use the double-sided sticky pad to mount the wall block to a suitable surface.

Set the keyboard DIP switches according to the instructions in the Switch Settings section.

Plug in the keyboard data cable.

Plug the +12 VDC power supply into a suitable outlet.

Plug the KBDKIT or KBDKIT-X transformer into a suitable outlet.

Pelco Manual C526M-J (3/04) [ 21 ]

1

2

3

4

5

6 7

8

12 VAC

KBDKIT RJ-45 WALL BLOCK

TERMINALS

RS-232 RS-422

RS-232 DEVICE

RS-232 DEVICE

PV130 RS-232/RS-422 CONVERTER

RD (B) RD (A)

TD (A) TD (B)

TX+ TX-

TERMINAL

RX- RX+

POWER SUPPLY

+12 VDC GND

9-PIN, MALE CONNECTOR ON CONVERTER

CUSTOMER -SUPPLIED WIRING. 50 FEET MAXIMUM DISTANCE.

TX

GND RX

7 KBD200A

25-FOOT KEYBOARD DATA CABLE

WALL BLOCK

REPLACE COVER

SET SWITCHES

DB9 PINS 3(TX+) 2(RX+) 5(GND)

ANY RS-232 NETWORK

TRANSPORT NETWORK

1

2

3

4 5

6

7

8

6

12 13

5 8 4

11 10

9

3

MAXIMUM DISTANCE OF 4,000 FEET. USE SHIELDED TWISTED PAIRS SUCH AS BELDEN 9843 OR EQUIVALENT.

CUSTOMER -SUPPLIED WIRING. 50 FEET MAXIMUM DISTANCE.

C O M 1

1

2

3

4

5

6

7

8

16

87

3231

43

VIDE O O UTPUTS 120/230~ 50/60 HZ

25 WATT S

C O M

AL AR M 1 2 3 4 5 6 7 8

C O NTR O L

PTZ

O UT

A T +

T -

R +

R -

T +

T -

R +

R -

B

1 2

F 3

COM 1, 2, 7, OR 8

14 POWER UP SCU

NOTE: A SEPARATE PATH MUST BE PROVIDED FOR VIDEO TO THE MONITOR.

1

NOTE: SEE FIGURE 11 FOR PIN-OUTS

PELCO SWITCHER MODEL CM6800

MAIN MENU

1 CAMERA 2 LOGICAL CAMERA 3 MONITOR 4 ACCESS 5 TIME & DATE 6 PORT 7 PRIORITY 8 SEQUENCE 9 MACRO

10 ALARM CONTACTS 11 EVENT TIMER 12 SET AUXILIARY MENU 13 SET PASSWORD 14 ABOUT CM6800

ENGLISH

RETURN

SET SERIAL PORT 05

2

CM6800

DEVICE: TYPE: BAUD RATE: PARITY: DATA BITS: STOP BITS:

ASCII RS232 9600 ODD 8 1

RETURN

RS-232

4

01235

Apply power to the CM6800 (if not already powered). To initialize the keyboard, wait five seconds after power-up, enter the number for the monitor you are viewing, and press MON. The LED display shows the number entered. You can now use the keyboard to perform all normal keyboard functions, except you cannot program the CM6800.

Go to the Programming and Operation section and program and test for proper operation.

Figure 8. RS-232 Interface Connections (CM6800-48X8 Shown)

[ 22 ] Pelco Manual C526M-J (3/04)

RS-485 Interface (CM6800) Refer to Figures 9 (CM6800-48X8 shown) and 10.

Use an existing CM6800 keyboard to program the COM 4, 7, or 8 communication port (CM6800-48X8) or COM 4 communications port (CM6800-32X6). (If there is no other keyboard, use the one you are install- ing. Set all DIP switches OFF and plug the keyboard into the Local Keyboard port on the back of the CM6800. Remove when programming is complete.)

Do the following to program the COM port:

a. Press the PGM key. At the prompt, enter the password (default is 2899100). The CM6800 Main Menu appears.

b. Select PORT. The Set Serial Port screen appears.

c. Select the number of the desired port.

d. Set COM port parameters as follows: Device: ASCII, Type: RS-485, Baud: 9600, Parity: Odd, Data Bits: 8, Stop Bits: 1.

e. Select RETURN, and RETURN again.

Decide on a suitable location for the keyboard and wall block. The keyboard must be within 25 feet (7.6 m) of the wall block. The wall block must be within 6 feet (1.8 m) of the nearest suitable electri- cal outlet. Do not mount the wall block yet.

Remove the wall block cover and make connections between the wall block and COM 4, 7, or 8 of the CM6800-48X8 or COM 4 of the CM6800-32X6.

At the wall block, wire the transformer to pins 3 and 4. Polarity is unimportant.

Replace the cover on the wall block. Use the double-sided sticky pad to mount the wall block to a suitable surface.

Set the keyboard DIP switches according to the instructions in the Switch Settings section.

Plug in the keyboard data cable.

Plug the KBDKIT or KBDKIT-X transformer into a suitable outlet.

Apply power to the CM6800 (if not already powered). To initialize the keyboard, wait five seconds after power-up, enter the number for the monitor you are viewing (1-8), and press MON. The LED dis- play shows the number entered. Once you apply power to the keyboard and the CM6800, you can use the keyboard in the same way as a normal keyboard except that in ASCII Mode you cannot pro- gram the CM6800.

Go to the Programming and Operation section and program and test for proper operation.

Pelco Manual C526M-J (3/04) [ 23 ]

C O M 1

1

2

3

4

5

6

7

8

16

87

3231

43

VIDE O O UTPUTS 120/230~ 50/60 HZ

25 WATT S

C O M

AL AR M 1 2 3 4 5 6 7 8

C O NTR O L

PTZ

O UT

A T +

T -

R +

R -

T +

T -

R +

R -

B

1 2

F 3

COM 4, 7, OR 8

6

NOTE: A SEPARATE PATH MUST BE PROVIDED FOR VIDEO TO THE MONITOR.

10

NOTE: SEE FIGURE 11 FOR PIN-OUTS

CM6800

1 (TX+) 2 (TX-) 7 (RX-) 8 (RX+)

1

2

3

4 5

6

7

8

1

2

3

4

5 6

7

8

1 2 VAC

KBD200A

MAXIMUM DISTANCE OF 4,000 FEET. USE SHIELDED TWISTED PAIRS SUCH AS BELDEN 9843 OR EQUIVALENT.

WALL BLOCK TERMINAL

TERMINAL

3

8 7

9

4 5

4

SET SWITCHES

25-FOOT KEYBOARD DATA CABLE

1

POWER UP SCU

PELCO SWITCHER MODEL CM6800

MAIN MENU

1 CAMERA 2 LOGICAL CAMERA 3 MONITOR 4 ACCESS 5 TIME & DATE 6 PORT 7 PRIORITY 8 SEQUENCE 9 MACRO

10 ALARM CONTACTS 11 EVENT TIMER 12 SET AUXILIARY MENU 13 SET PASSWORD 14 ABOUT CM6800

ENGLISH

RETURN

SET SERIAL PORT 05

2

DEVICE: TYPE: BAUD RATE: PARITY: DATA BITS: STOP BITS:

ASCII RS485 9600 ODD 8 1

RETURN

KBDKIT RJ-45 WALL BLOCK

TERMINALS

REPLACE COVER

01231

Figure 9. RS-485 Interface Connections (CM6800-48X8 Shown)

[ 24 ] Pelco Manual C526M-J (3/04)

Figure 10. COM Port Connections and RJ-45 Connector Pin-Outs

PIN 1

PIN 8

COM PORTS 1, 2 RS-232

PIN 1

PIN 8

COM PORT 3 M, RS-485

PIN 1

PIN 8

COM PORT 4 RS-485

PIN 1

PIN 8

COM PORTS 5, 6 RS-485

1-----Rx 2-----NC 3-----NC 4 5-----GROUND 6 7 8-----Tx

-----NC

-----NC -----NC

1-----MRx+ 2-----MRx- 3 4 5-----GROUND 6-----NC 7-----MTx- 8-----MTx+

-----NC -----NC

1-----Rx+ 2-----Rx- 3 4 5-----GROUND 6-----NC 7-----Tx- 8-----Tx+

-----NC -----NC

PIN 1

PIN 8

COM PORTS 7, 8 RS-485 (PROGRAMMABLE TO RS-232)

RS-232 FUNCTIONRS-485 FUNCTION

1-----Rx+ 2-----Rx- 3 4 5-----GROUND 6-----NC 7-----Tx- 8-----Tx+

-----KBD 12V -----KBD GROUND

1-----Rx+ 2-----Rx- 3 4 5-----GROUND 6-----NC 7-----Tx- 8-----Tx+

-----NC -----NC

1-----Rx 2 3 4 5-----GROUND 6-----NC 7-----NC 8-----Tx

-----NC -----NC -----NC

NC = NO CONNECTION 01232

Pelco Manual C526M-J (3/04) [ 25 ]

O N

1 2 3 4 5 6 7 8

}

PIN 1

1 TX+ 5 GND 2 TX 6 3 12 VAC/DC 7 RX 4 NONPOLAR 8 RX+

KBD200 RJ-45 JACK PINOUTS1

3

1

3 2

DOWN = ON

Figure 11. Keyboard Rear Panel

SWITCH SETTINGS

To set the switches on the keyboard (refer to Figure 11):

Remove the two screws and the DIP switch cover plate from the rear of the keyboard.

Set the switches:

Address (Switches 1-4) Position the switches according to Table B. Each keyboard in the system must have a different address, including the local keyboard. To make programming easier, address keyboards in as- cending order. NOTE: CM6700 accepts only eight addresses.

Table B. Keyboard Addresses

Keyboard Switch Settings 1 2 3 4

1 OFF OFF OFF OFF 2 ON OFF OFF OFF 3 OFF ON OFF OFF 4 ON ON OFF OFF 5 OFF OFF ON OFF 6 ON OFF ON OFF 7 OFF ON ON OFF 8 ON ON ON OFF 9 OFF OFF OFF ON

10 ON OFF OFF ON 11 OFF ON OFF ON 12 ON ON OFF ON 13 OFF OFF ON ON 14 ON OFF ON ON 15 OFF ON ON ON 16 ON ON ON ON

Mode (Switches 5, 6, 8) Position the switches according to Table C. Switch 7 is not used.

Table C. Keyboard Modes

CM6700/CM6800** Direct P** CM6700 ASCII CM6800 ASCII Direct D CM9760-MDA* Switch 5 OFF ON OFF OFF ON ON Switch 6 OFF OFF ON ON ON OFF Switch 8 OFF OFF OFF ON OFF ON

**Firmware version 4.00 and higher. **Firmware version 4.20 and higher automatically recognizes CM6700/CM800 and Direct P Mode.

Replace the cover plate.

[ 26 ] Pelco Manual C526M-J (3/04)

PROGRAMMING AND OPERATION

Table D. Keyboard Functions Circled numbers refer to Figure 13.

Function Procedure Select Monitor* LED display shows monitor number in run mode.

Enter monitor number (1-4) and press MON to select. Select Camera Enter camera number (1-16) and press CAM to select.

NOTE: The CM6700 and CM6800 can be programmed to restrict some monitors from viewing certain cameras. To display a cameras view on your monitor, be sure that your keyboard shows the number of the monitor you are viewing and be sure that the CM6700 or CM6800 has not been programmed to restrict view- ing of that camera.

Pan/Tilt Press and hold the appropriate pan/tilt key until the camera reaches the de- sired position. To change the speed of movement, press a number (1-9) key first (1=slowest, 9=fastest).

Lens Control Focus, zoom, iris Press and hold the appropriate lens control key until the desired effect is seen. To change the speed of focus, press a number (1-4) key , then press FAR .

Presets Enter preset number (1-66) and press PRESET to put camera in preset po- sition. To program, position camera, enter desired preset number (1-66) , and hold down PRESET for two seconds. In CM6700 and CM6800 modes, a label appears on the monitor. Use F1 and F2 to edit the label, and then select SET and press ACK or the pan right key .

Patterns Programming and operation varies with the receiver type. Spectra domes (before version 3.0) can use one long (1 minute) or two short (0.5 minute) patterns. Spectra domes (version 3.0), Spectra II domes and Esprit Integrated Positioning Systems can use one long (1.5, 3 or 6 minutes) or two short (0.75, 1.5 or 3 minutes) patterns. (Select pattern lengths at the positioning systems menu.) Spectra III can use four patterns of varying length (all drawing from the same block of memory, which is almost infinite). To program Spectra and Esprit, select a camera (1-16) , select a long pattern by holding down PATTERN for two seconds, or select short pattern 1 or 2 by en- tering 1 or 2 and holding down PATTERN for two seconds. The monitor will indicate the programming function is active. Move the camera position as desired for the pattern and press ACK to close the programming function. To run a long pattern, press PATTERN . To run a short pattern, enter 1 or 2 and press PATTERN . Press a pan/tilt key or call a preset to stop. Direct Mode is the same as above, except: Do not program a pattern with pan/tilt speed set to 9. To program Spectra III, enter 95, an then hold down PRESET for about five seconds until the main menu appears. Use the PAN/TILT keys to position the cursor beside Patterns, and then press IRIS OPEN . Position the cursor beside Pattern Number, and then press IRIS OPEN. Position the cursor beside Program Pattern, and then press IRIS OPEN. Follow the directions displayed on the monitor. Another way to program the Spectra III is by pressing the pattern number (1-4) and then PATTERN for two seconds. To run a Spectra III pattern, press the pattern number (1-4) and then PATTERN . Press a PAN/TILT key to stop.

*This function is not used in Direct Mode.

Pelco Manual C526M-J (3/04) [ 27 ]

Continued on next page

Table D. Keyboard Functions (continued)

Function Procedure

Sequence* Sequence steps through all 16 cameras. Camera number, camera title, sequence status, and time/date are shown on the monitor. Press PREV 4A to step back one camera. Hold for two seconds for a backward sequence. Monitor shows B. Press during sequence to speed up. Press during a forward sequence to reverse. Press NEXT 4B to step forward one camera. Hold for two seconds for a forward sequence. Monitor shows F. Press during sequence to speed up. Press during a backward sequence to go forward. Press HOLD 4C to hold a sequence. Monitor shows H. Press HOLD to resume. Manually select a camera or press CAM to turn off a sequence. Monitor shows O.

Macro Sequence* Enter 1 or 2 and press MACRO to start a group camera sequence. Monitor shows M. Refer to the CM6700 manual for macro/sequence programming.

Multiplexer Press SHIFT . Shift key LED lights. The function keys F1 through F5 Displays* can now be used to display the images from multiple cameras on the monitor.

F1/LATCH: Zoom F2/OFF: PIP display F3/MOM: Quad display AUX ON: 9-screen display AUX OFF: 16-screen display

Auxiliaries/Relays For the CM6700: F1 F3 control only the auxiliaries built into the CM6700 SCU. These outputs can be programmed for momentary, keyed, latched, or alarm op- eration. Refer to the CM6700 manual for programming instructions. F1/LATCH: Activate/deactivate auxiliary 1 relay.* F2/OFF: Activate/deactivate switcher auxiliary 2 TTL output.* F3/MOM: Activate/deactivate switcher auxiliary 3 TTL output.* The AUX ON and AUX OFF keys control the auxiliaries in receivers. Enter the auxiliary number, and then press AUX ON key to turn on. Hold, and then release for momentary functions. Enter the auxiliary number, and then press the AUX OFF key to turn off.

For the CM6800: F1 F3 can address auxiliary functions on the CM6800 and on the REL2064 (a separate auxiliary relay box) to provide additional auxiliary points. F1/LATCH: Enter the auxiliary number and press and release F1 to turn on an auxiliary (latching). F2/OFF: Enter the auxiliary number and press and release F2 to turn off an auxil- iary (latching). F3/MOM: Enter the auxiliary number and press and hold down F3 to turn on an auxiliary (momentary). Release F3 to turn off the auxiliary.

Direct Mode: In Direct Mode, F1- F3 have no function. LED shows receiver auxiliary num- ber for two seconds after the AUX ON or AUX OFF is pressed.

Acknowledge Alarm* Press ACK to acknowledge an alarm. Refer to the CM6700 or CM6800 manual for further information on alarms.

[ 28 ] Pelco Manual C526M-J (3/04)

Table D. Keyboard Functions (continued)

Function Procedure

Program For the CM6700:

(CM6700) To program the CM6700 switcher, press PGM . (CM6800) Follow the programming procedure in the CM6700 manual. LED display

** shows P in program mode. To exit, naviate to the RETURN field and press ACK or the pan right key . For the CM6800:

To program the CM6800 switcher, press PGM . Follow the programming procedure in the CM6800 manual. To exit, navigate to the RETURN field and press the pan right key . Or, press the PGM key to return to the previous screen or menu.

LED LED shows monitor number (in CM6700, CM6800, and ASCII modes) or camera/ receiver number (in Direct Mode) and P (in Program Mode).

Firmware Version LED flashes for a few seconds to show firmware version on power up (not functional on versions prior to 4.0).

Clear Press CLEAR to cancel a number that has been entered (CM6700/CM6800 modes only). In Direct Mode, this key erases any numerical entries and redisplays the current camera number selected.

Infrared Filter This function applies to Spectra color/black-white model SD5BCBW only. (IR Cut Filter) a. To turn on the filter: press 8, 8, PRESET .

b. To turn off the filter: press 8, 9, PRESET . Shift* Press SHIFT to allow the keyboard to send multiplexer commands.

*This function is not used in Direct Mode. **This function is not used in ASCII Mode.

Pelco Manual C526M-J (3/04) [ 29 ]

SHIFT

SEQUENCE

MON ACK PREV NEXT HOL D P AT TERN PRESET MACR O PGM

F1/LATCH F2/OFF F3/MOM ON AUX OFF

ZOOM

PAN / TILT

KBD20 0A

TELE

WIDE C LO SEFAR

NE AR O PE N

FOCUS IRIS1 2 3

4 5 6

7 8 9

0 CLEARCAM

MADE IN USA.

11 2 3 4 5 6

7

8

9

10

11

1213

14

15

16

17

A 4 B 4 C

Figure 12. Keyboard Functions

[ 30 ] Pelco Manual C526M-J (3/04)

Table E. KBD200A Button Functions

Reference Description Number

1 LED display 2 Shift key 3 Shift key LED

4A-C Sequence keys: Previous, Next, Hold

5 Function keys F1, F2, F3 control auxiliaries. With Shift on they control multiplexer display.

6 The AUX ON and AUX OFF keys control receiver auxiliaries. With Shift on they control multiplexer display.

7 Program key 8 Macro sequence key 9 Preset key

10 Pattern key 11 Focus, zoom, iris keys

(iris keys can be used to scroll through menus on the CM6800 only) 12 Pan and tilt keys 13 Clear key 14 Camera selection key 15 Keypad (numbers 1 through 0) 16 Acknowledge key 17 Monitor selection key

Pelco Manual C526M-J (3/04) [ 31 ]

Table F. Operating Scan Functions with Various Receivers Function

Receiver Controlling Auto Random Frame Preset Stop Model Protocol Scan Scan Scan Scan

All 15-bit 97 97

96 Pelco

(standard) Preset Preset N/A (2) PresetCoaxitron (1) (3) (1)

98 Preset IRD2024 Extended or 97

N/A N/A 96

ERD2200 Coaxitron 99 Preset Preset Preset (3)

All Spectra Ext. Coax.,

99 97 98 96

All Esprit Serial Pelco

Preset Preset Preset N/A Preset

P or D or PTZ

LRD41C Ext. Coax., 99 99 96(before Serial Pelco Preset Preset N/A N/A

Presetver. 2.98) P or D (1) (3) (1)

LRD41C Ext. Coax., 99 97 96(ver 2.98 Serial Pelco Preset

Preset N/A N/A

Presetand later) P or D (3)

ERD97P21-U Serial Pelco P N/A 97 Preset 98 Preset N/A 96 Preset

(1) First entry starts random scan, next entry changes to auto scan, etc. (2) Enter dwell time (5-64 sec.) and press IRIS CLOSE. (3) Changes to random scan after 30 minutes.

Programming Limit Stops Spectra and Esprit can be programmed for scan and manual limit stops.

Program left limit before programming right limit. Locate camera at desired limit. Enter the set code from Table G. Hold the PRESET key for two seconds. In CM6700 and CM6800 modes, a label appears on the monitor. Use F1 and F2 to edit the label, and then select SET and press ACK or the pan right key.

To cancel all limit stops, enter 95. Hold the preset key for two seconds. Use the up down tilt keys to move the pointer to Other. Press IRIS OPEN. Move the pointer to Limit Stops. Press IRIS OPEN. Use the tilt keys to change limit stops to off. Press IRIS OPEN. Move the pointer to EXIT. Press IRIS OPEN. Move pointer to exit. Press IRIS OPEN.

Table G. Limit Set Codes

Direction Scan Limit Manual Limit

Left Limit 92 90

Right Limit 93 91

Scanning Functions Operation of the scanning functions depends on the kind of receiver or pan/tilt mechanism you have and the operating mode of your keyboard (CM6700, CM6800, or Direct Mode).

There are four types of scanning functions: auto (moves camera back and forth between stops), random (moves camera in a random pattern), frame (moves camera back and forth in 10 degree steps), and preset (se- quences camera through all programmed presets, pausing between each).

Operate scans according to Table F.

[ 32 ] Pelco Manual C526M-J (3/04)

Zones

The Zone function is available on Esprit and Spectra positioning systems. This function puts a label on the screen to identify the viewing area. Zones can also be blanked to prevent viewing while the camera is po- sitioned in the zone.

Up to eight pan (horizontal) zones can be defined (zones are not affected by tilt or zoom). Higher num- bered zones take precedence so that if zones overlap, the one with the higher number is in effect. Zone programming is outlined in Table H.

Table H. Zone Programming Procedure

Step Procedure

1. Set left zone limit. a. Use the pan left/right keys to position the camera at the start (left limit) of the zone.

2. Access zone a. Press 8, followed by the zone number N (N = 1 through 8), and F4 programming. to display the zone menu.

3. Define a label. a. Use F1 and F2 to find the characters for each position in the label HINT: To ease (26 upper case letters, 26 lower case letters and 10 numbers). future title editing, b. Pan left/right to move between character positions. Continue start each title with selecting characters until the title is completed (up to 20 charac-

ters). Z(N), where c. Move down to the SET field and press ACK or the pan right key. N = zone number.

4. Set right zone limit. a. Position camera at the right limit of the zone. b. Press 8, followed by the zone number, and F5. c. To view zone titles go to step 6.

5. Clear zones. a. Press 8, followed by the zone number, and F4. b. Move down to the SET field and press ACK.

NOTE: DO NOT pan right. c. Press 8, followed by the zone number, and F5.

6. Turn on zone labeling. a. Press 9, 1, F4.

7. Turn off zone labeling. a. Press 9, 2, F4.

8. Blank zones. a. Press 9, 5 and hold Preset for about 2 seconds to display the Edit Preset 95 menu.

b. Move down to the SET field and press ACK. c. Move down to the field and press Iris Open to

display the Alarms, Zone Blank menu. d. Move down to the field and press Iris Open to display

the Zone Blank menu. e. Move down to the zone number you wish to blank and press Iris

Open to move the cursor arrow to the zone blanking status value. f. Pan up to turn blanking on, pan down to turn blanking off. g. Press Iris Open to accept new status; press Iris Close to cancel. h. Repeat steps 8e through 8g for each zone you wish to change, and

then go to step 8i. i. Move down to Exit and press Iris Open repeatedly to move up

through the menus and return to the normal display.

Pelco Manual C526M-J (3/04) [ 33 ]

SPECIFICATIONS

GENERAL

Keyboard Keypad: Electromechanical

Digital Display: Red LED, 7-segment, 2 cells

Shift Mode Indicator: Green LED

Ambient Operating Temperature: 20 to 120F (-7 to 49C)

Humidity: 1090% non-condensing

Dimensions: 8.125 (W) x 7.125 (D) x 2.25 (H) inches (20.64 x 18.10 x 5.72 cm)

Weight: 2.1 lb (0.95 kg)

ELECTRICAL

Input Voltage: 12 VAC or 12 VDC

Power Consumption: 5 watts

Connector Type: RJ-45, 8-pin, modular (female)

Keyboard Communication CM6700/CM6800 Mode

Interface: RS-485 Protocol: Pelco ASCII Baud: 9600 Communication Parameters: 8 data bits, 1 stop bit, odd parity

CM6700 ASCII Mode Interface: RS-422 Protocol: Pelco ASCII Baud: 9600 Communication Parameters: 8 data bits, 1 stop bit, odd parity

CM6800 ASCII Mode Interface: RS-485 Protocol: Pelco ASCII Baud: 9600 Communication Parameters: 8 data bits, 1 stop bit, odd parity

Direct P Mode Interface: RS-485 Protocol: Pelco P Baud: 4800 Communication Parameters: 8 data bits, 1 stop bit, no parity

Direct D Mode Interface: RS-485 Protocol: Pelco D Baud: 2400 Communication Parameters: 8 data bits, 1 stop bit, no parity

(Design and product specifications subject to change without notice.)

[ 34 ] Pelco Manual C526M-J (3/04)

Pelco, the Pelco logo, Spectra, Genex, Legacy, Coaxitron, Esprit and Camclosure are registered trademarks of Pelco. Spectra II and Spectra III are trademarks of Pelco.

Copyright 2004, Pelco. All rights reserved.

WARRANTY Pelco will repair or replace, without charge, any merchandise proved defective in material or workmanship for a period of one year after the date of shipment.

Exceptions to this warranty are as noted below: Five years on Pelco manufactured cameras (CC3500/CC3600/CC3700 and MC3500/MC3600/MC3700 Series); two years on all

other cameras. Three years on Genex Series (multiplexers, server, and keyboard) and 090 Series Camclosure Camera System. Two years on 100/150, 200 and 300 Series Camclosure Camera Systems. Two years on cameras and all standard motorized or fixed focal length lenses. Two years on Legacy, CM6700/CM6800/CM8500/CM9500/CM9740/CM9760 Matrix, DF5 and DF8 Series Fixed Dome products. Two years on Spectra, Esprit, and PS20 Scanners, including when used in continuous motion applications. Two years on Esprit and WW5700 series window wiper (excluding wiper blades). Eighteen months on DX Series digital video recorders. One year (except video heads) on video cassette recorders (VCRs). Video heads will be covered for a period of six months. Six months on all pan and tilts, scanners or preset lenses used in continuous motion applications (that is, preset scan, tour and auto

scan modes).

Pelco will warrant all replacement parts and repairs for 90 days from the date of Pelco shipment. All goods requiring warranty repair shall be sent freight prepaid to Pelco, Clovis, California. Repairs made necessary by reason of misuse, alteration, normal wear, or accident are not covered under this warranty.

Pelco assumes no risk and shall be subject to no liability for damages or loss resulting from the specific use or application made of the Products. Pelcos liability for any claim, whether based on breach of contract, negligence, infringement of any rights of any party or product liability, relating to the Products shall not exceed the price paid by the Dealer to Pelco for such Products. In no event will Pelco be liable for any special, incidental or consequential damages (including loss of use, loss of profit and claims of third parties) however caused, whether by the negligence of Pelco or otherwise. The above warranty provides the Dealer with specific legal rights. The Dealer may also have additional rights, which are subject to variation from state to state.

If a warranty repair is required, the Dealer must contact Pelco at (800) 289-9100 or (559) 292-1981 to obtain a Repair Authorization number (RA), and provide the following information:

1. Model and serial number 2. Date of shipment, P.O. number, Sales Order number, or Pelco invoice number 3. Details of the defect or problem

If there is a dispute regarding the warranty of a product which does not fall under the warranty conditions stated above, please include a written explanation with the product when returned. Method of return shipment shall be the same or equal to the method by which the item was received by Pelco.

RETURNS In order to expedite parts returned to the factory for repair or credit, please call the factory at (800) 289-9100 or (559) 292-1981 to obtain an authorization number (CA number if returned for credit, and RA number if returned for repair). All merchandise returned for credit may be subject to a 20% restocking and refurbishing charge. Goods returned for repair or credit should be clearly identified with the assigned CA or RA number and freight should be prepaid. Ship to the appropriate address below.

If you are located within the continental U.S., Alaska, Hawaii or Puerto Rico, send goods to: Service Department Pelco 3500 Pelco Way Clovis, CA 93612-5699

If you are located outside the continental U.S., Alaska, Hawaii or Puerto Rico and are instructed to return goods to the USA, you may do one of the following:

If the goods are to be sent by a COURIER SERVICE, send the goods to: Pelco 3500 Pelco Way Clovis, CA 93612-5699 USA

If the goods are to be sent by a FREIGHT FORWARDER, send the goods to: Pelco c/o Expeditors 473 Eccles Avenue South San Francisco, CA 94080 USA Phone: 650-737-1700 Fax: 650-737-0933

PRODUCT WARRANTY AND RETURN INFORMATION

Pelco Manual C526M-J (3/04) [ 35 ]

REVISION HISTORY

Manual # Date Comments C526M 6/97 Original version.

4/98 Revised to add 230 VAC transformer and keyboard to parts list in Section 2.0. Clarified installation instructions. Changed manual pagination.

C526M-A 5/98 Revised installation instructions as a result of hardware changes to the rear panel of the CM6700 SCU. Removed references to KBD200-X because model has been replaced with KBDKIT-X.

6/98 Added Section 1.2, Regulatory Notices and Section 2.1, Certifications. 9/98 Revised Table A and Figure 4.

C526M-B 4/99 Completely revised manual. 6/99 Revised the sequence key definitions. Added material on programming Spectra features to the Direct

Mode Operation section. C526M-C 3/00 Added pattern programming and operation in Direct Mode Operation section to support revision 4

firmware. Added CM9760-MDA mode. C526M-D 7/00 Revised format. C526M-E 10/01 Added information about the CM6800 Matrix Switcher and additional functionality of the iris and pan right

keys. C526M-F 7/02 Revised keyboard drawings to reflect key labeling changes. Several procedures revised because of the

labeling change. Revised pattern programming in Table D to include procedures for Spectra III. Stated that firmware versions 4.20 and higher automatically recognize CM6700/CM6800 and direct mode.

C526M-G 11/02 Updated with firmware version 5.00 information as per ECO 02-8447. Added two modes to the Description and Installation sections and renamed ASCII Mode to CM6700 ASCII Mode. Revised Tables A, C, and D. Updated Specifications.

C526M-H 12/02 Revised Tables A, D, and H. Removed RS-232 from Specifications. C526M-I 9/03 Added UL certification seal and changed power specification. C526M-J 3/04 Revised directions for direct mode installation. Revised safety instructions. Changed FCC notice.

Removed references to use 18-gauge wiring for EIA RS-485 communication.

World Headquarters 3500 Pelco Way

Clovis, California 93612 USA

USA & Canada Tel: 800/289-9100 Fax: 800/289-9150

International Tel: 1-559/292-1981 Fax: 1-559/348-1120

www.pelco.com

ISO9001

Orangeburg, New York | Las Vegas, Nevada | Eindhoven, The Ne

Manualsnet FAQs

If you want to find out how the KBD200A Pelco works, you can view and download the Pelco KBD200A C526-J Keyboard Installation Manual on the Manualsnet website.

Yes, we have the Installation Manual for Pelco KBD200A as well as other Pelco manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Installation Manual should include all the details that are needed to use a Pelco KBD200A. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Pelco KBD200A C526-J Keyboard Installation Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Pelco KBD200A C526-J Keyboard Installation Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Pelco KBD200A C526-J Keyboard Installation Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Pelco KBD200A C526-J Keyboard Installation Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Pelco KBD200A C526-J Keyboard Installation Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.