REL2064 Relay Interface Unit

C1518M-A (11/02)

I N S T A L L A T I O N / O P E R A T I O N

2 C1518M-A (11/02)

CONTENTS

Section Page

IMPORTANT SAFEGUARDS AND WARNINGS .................................................................................................................................................................. 3

OVERVIEW .......................................................................................................................................................................................................................... 4 DESCRIPTION ............................................................................................................................................................................................................ 4 FRONT VIEW .............................................................................................................................................................................................................. 4 REAR VIEW ................................................................................................................................................................................................................ 5

INSTALLATION .................................................................................................................................................................................................................... 6 MOUNTING ............................................................................................................................................................................................................... 6 WIRING RELAYS ........................................................................................................................................................................................................ 6 CONNECTING TO THE CM6800 ................................................................................................................................................................................ 9 SETTING THE DIP SWITCHES .................................................................................................................................................................................. 10

OPERATION ........................................................................................................................................................................................................................ 12 MEMORY FEATURE .................................................................................................................................................................................................. 12 OPERATING RELAYS FROM THE KBD960 ................................................................................................................................................................ 13

ACTIVATING RELAYS USING F12 .................................................................................................................................................................... 13 ACTIVATING RELAYS FROM THE GPI MENUS ................................................................................................................................................ 13

MOMENTARY ......................................................................................................................................................................................... 13 LATCHING ............................................................................................................................................................................................... 13

TROUBLESHOOTING .......................................................................................................................................................................................................... 15

APPENDIX A ...................................................................................................................................................................................................................... 16

SPECIFICATIONS ................................................................................................................................................................................................................ 18

REGULATORY NOTICES ..................................................................................................................................................................................................... 19

WARRANTY AND RETURN INFORMATION ...................................................................................................................................................................... 19

LIST OF ILLUSTRATIONS

Figure Page

1 Front View with Panel Removal ....................................................................................................................................................................... 4 2 Rear View of the REL2064 ................................................................................................................................................................................ 5 3 Rack-Mount Installation ................................................................................................................................................................................... 6 4 Relay Interface Contact Configuration ............................................................................................................................................................. 7 5 Wiring Relays to Peripheral Equipment ........................................................................................................................................................... 8 6 Connection to the CM6800 .............................................................................................................................................................................. 9 7 SW1 DIP Switches .......................................................................................................................................................................................... 11 8 SW2 DIP Switches .......................................................................................................................................................................................... 11 9 SW3 DIP Switches .......................................................................................................................................................................................... 11 10 Power Input Fuse Replacement ....................................................................................................................................................................... 15 11 REL2064 Dimension Diagram .......................................................................................................................................................................... 18

LIST OF TABLES

Table Page

A Switch 1 ........................................................................................................................................................................................................... 10 B Switch 2 ........................................................................................................................................................................................................... 10 C Switch 3 ........................................................................................................................................................................................................... 10 D Relay Unit 1 ..................................................................................................................................................................................................... 14 E Relay Unit 2 ..................................................................................................................................................................................................... 14

C1518M-A (11/02) 3

IMPORTANT SAFEGUARDS AND WARNINGS

1. Read, keep, and follow these instructions.

2. Heed all warnings.

3. There are no user-serviceable parts inside this unit. Only authorized service personnel may open the unit.

4. Installation and servicing should only be done by qualified service personnel and conform to all local codes.

5. WARNING: To reduce the risk of fire or electric shock, do not expose this unit to rain or moisture if this unit is designed for indoor use only.

6. Unless this unit is specifically marked as a NEMA Type 3, 3R, 3S, 4, 4X, 6 or 6P enclosure, it is designed for indoor use only and it must not be installed where exposed to rain or moisture.

7. Do not expose this unit to dripping or splashing. Do not place objects filled with liquids, such as vases, on this unit.

8. Do not block any ventilation openings. Install in accordance with the manufacturers instructions.

9. The installation method and materials should be capable of supporting four times the weight of the unit and equipment.

10. Do not install near any heat source.

11. Only use attachments/accessories specified by the manufacturer.

12. Clean only with dry cloth.

13. Do not defeat the safety purpose of the polarized or grounding-type plug.

14. Protect the power cord from being walked on or pinched, particularly at plugs, convenience receptacles, and the point where they exit from the unit.

15. Unplug this unit during lightning storms or when unused for long periods of time.

The product and/or manual may bear the following marks:

Please thoroughly familiarize yourself with the information in this manual prior to installation and operation.

FOR QUALIFIED SERVICE PERSONNEL ONLY 1. Only use replacement parts recommended by Pelco.

2. After replacement/repair of this units electrical components, conduct a resistance measurement between line and exposed parts to verify the exposed parts have not been connected to line circuitry.

This symbol indicates that dangerous voltage constituting a risk of electric shock is present within this unit.

This symbol indicates that there are important operating and maintenance instructions in the literature accompanying this unit.

C A U T I O N :

RISK OF ELECTRIC SHOCK. DO NOT OPEN.

4 C1518M-A (11/02)

Figure 1. Front View with Panel Removal

OVERVIEW

DESCRIPTION

The REL2064 Relay Interface Unit provides up to 64 single-pole, single-throw (SPST) dry contact outputs for direct or automatic control of peripheral equipment. Using Pelcos proprietary M protocol, the relay unit communicates with Pelcos CM6800 matrix switcher via an RS-485 communication interface. The relay unit can be located remotely from the system controller and still communicate back to the central system when an alarm occurs.

Other features include the following:

Multiple units can be cascaded to provide multiple relay contact points on a single M port connection. Relay output contacts can be configured for normally open (N.O.) or normally closed (N.C.) operation. With the memory feature, relay groups can retain their contact position in the event of a power failure or front panel reset. The unit is powered by an auto-ranging power supply. The unit occupies one rack unit (1.75 inches or 4.45 cm), accommodating multiple types of mounting.

FRONT VIEW

The left side of the front panel includes the green power LED light. This light comes on at power-up.

The right side of the front panel includes the red data LED light. This light continually flashes on and off at a regular rate (about one-second intervals) until the unit is online and communicating with the CM6800. Once online, the LED remains ON. If for any reason communication is lost, the LED flashes again until communication is re-established.

When you remove the front panel, you have access to a reset button and configuration DIP switches.

00696

C1518M-A (11/02) 5

REAR VIEW

The rear of the REL2064 unit consists of the following:

1. Four groups of 16 contact pairs, each with mating plugs for the attachment of peripheral equipment; only the group for the first 16 contact pairs is shown in Figure 2 with mating plugs

2. One RS-485 output communication port (RJ-45 type connector)

3. One RS-485 input communication port (RJ-45 type connector)

4. One RS-232 diagnostic communication port (DB9 type connector)

5. The grouped input power functions consisting of input power terminals, a fuse, and an on/off switch

Figure 2. Rear View of the REL2064

00700

6 C1518M-A (11/02)

Figure 3. Rack-Mount Installation

WIRING RELAYS

The relay unit has four groups of relay contacts. Each group represents 16 pairs of relay contacts:

Group I 1-8, 9-16 Group II 17-24, 25-32 Group III 33-40, 41-48 Group IV 49-56, 57-64

Each of the four groups contains two connectors with input mating plugs. The top connector is for the first eight pairs of relay contacts and the bottom connector is for the last eight pairs of relay contacts. Each mating plug has 16 screw terminals and 16 pins. When you place a wire into a pin, tighten the screw to secure it.

Refer to Figure 4 to determine the screw terminal number for a particular contact. The numbers that appear on the mating plugs in Figure 4 are for illustration only. The terminal positions on the actual physical plugs are not numbered.

Refer to Figure 5 for wiring the relays to peripheral equipment.

00701

INSTALLATION

The following items are supplied:

REL2064 Relay Interface Unit 120 VAC power cord 220 VAC power cord Pelco screwdriver 10-foot (3 m) straight RJ-45 cable (8-conductor) 4 #10 screws with nylon washers

MOUNTING

Install the relay unit in a 19-inch rack. The unit occupies one rack unit (1.75 inches or 4.45 cm) of space. You can mount the relay unit to something other than a standard 19-inch rack by relocating the rack ears to another location.

C1518M-A (11/02) 7

Figure 4. Relay Interface Contact Configuration

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

00702

8 C1518M-A (11/02)

Figure 5. Wiring Relays to Peripheral Equipment

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

32-122F (0-50C)

+

9 WARNING:

WARNING:

00703

C1518M-A (11/02) 9

CONNECTING TO THE CM6800

Connect the supplied RJ-45 straight cable from the REL2064 OUT port to the CM6800 COM 3 port. The active pin-outs are associated with the four outer pins: 1, 2, 7, and 8. Refer to Figure 6.

If you want to place the relay unit some distance from the CM6800, the RS-485 communication from the relay unit to the controller should not exceed 4,000 feet (1,219 m). You need an RJ-45 wall-block terminal (part number CON12J008Z03G0Z) if operating from a remote site.

To cascade two relay units, connect a straight cable from the OUT port of the second relay unit to the IN port of the first relay unit. The first unit is the one you connect to the CM6800.

Figure 6. Connection to the CM6800

00704

10 C1518M-A (11/02)

SETTING THE DIP SWITCHES

The positioning of the DIP switches on the front of the relay unit determines how the relay unit operates. You must recycle power whenever you make changes to the DIP switches.

1. Remove the front panel by unscrewing the five flat-head Phillips screws. You see three switches.

1-16 17-32 33-48 49-64

Off Off Off Off

On On On On

Norm Open (N.O.)

Norm Closed (N.C.)

Table A. Switch 1

SW1 Communications/Relay Type Selection Baud Relay Range GPI Contacts 1200 Off Off Off 1-64 Off Off Off 1 2400 On Off Off 65-128 On Off Off 9 4800 Off On Off 129-192 Off On Off 17 9600 On On Off 193-256 On On Off 25

19200 Off Off On 257-320 Off Off On 33 38400 On Off On 321-384 On Off On 41 57600 Off On On 385-448 Off On On 49 115200 On On On 449 On On On 57

DIP Switch 1 2 3 4 5 6 7 8 9 10

Table B. Switch 2

Address SW2 Address 1 Off Off Off Off Off Off Off Off Off Off 2 On Off Off Off Off Off Off Off Off Off 3 Off On Off Off Off Off Off Off Off Off 4 On On Off Off Off Off Off Off Off Off 5 Off Off On Off Off Off Off Off Off Off 6 On Off On Off Off Off Off Off Off Off 7 Off On On Off Off Off Off Off Off Off 8 On On On Off Off Off Off Off Off Off 9 Off Off Off On Off Off Off Off Off Off

10 On Off Off On Off Off Off Off Off Off 11 Off On Off On Off Off Off Off Off Off 12 On On Off On Off Off Off Off Off Off 13 Off Off On On Off Off Off Off Off Off 14 On Off On On Off Off Off Off Off Off 15 Off On On On Off Off Off Off Off Off 16 On On On On Off Off Off Off Off Off

DIP Switch 1 2 3 4 5 6 7 8 9 10

Table C. Switch 3

SW3 Power-On Initialization N/A Initialization Relay Relay Relay Relay

State 1-16 17-32 33-48 49-64 Initialize Off Off Off Off

Off Maintain Last State On On On On

Off

DIP Switch 1, 2 3 4 5 6 7-10

C1518M-A (11/02) 11

2. Set the DIP switches.

Figure 7. SW1 DIP Switches

DIAGNOSTICS: OFF

LOCAL DEVICE ADDRESS

ON

1 2 3 4 5 6 7 8 9 10

NOT USED: OFF

DEFAULT SETTINGS: LOCAL DEVICE ADDRESS 1, DIP SWITCH 9 OFF, DIP SWITCH 10 ON

00697

NOT USED: OFF

MEMORY (MEM) CONTACTS 1-16: OFF OR ON 17-32: OFF OR ON 33-48: OFF OR ON 49-64: OFF OR ON

NOT CONNECTED: OFF

MEM ON: SETTINGS REMAIN IN MEMORY IN CASE OF POWER FAILURE OR ACCIDENTAL RESET

MEM OFF: SETTINGS GO BACK TO THE FACTORY DEFAULT IN CASE OF POWER FAILURE OR ACCIDENTAL RESET

ON

1 2 3 4 5 6 7 8 9 10

DEFAULT SETTINGS: MEMORY FEATURE DISABLED, DIP SWITCHES 1, 2, AND 7-10 OFF

00698

BAUD RATE 1200: OFF, OFF, OFF 2400: ON, OFF, OFF 4800: OFF, ON , OFF 9600: ON, ON, OFF 19200: OFF, OFF, ON 38400: ON, OFF, ON 57600: OFF, ON, ON 115200: ON, ON, ON

BEGIN RELAY RANGE/BEGIN GPI 1-64/1: OFF, OFF, OFF 65-128/9: ON, OFF, OFF 129-192/17: OFF, ON, OFF 193-256/25: ON, ON, OFF 257-320/33: OFF, OFF, ON 321-384/41: ON, OFF, ON 385-448/49: OFF, ON, ON 449/57: ON, ON, ON

RELAY CONTACT GROUPS 7 (1-16): OFF (N.O.) ON (N.C.) 8 (17-32): OFF (N.O.) ON (N.C.) 9 (33-48): OFF (N.O.) ON (N.C.) 10 (49-64): OFF (N.O.) ON (N.C.)

N.O. = NORMALLY OPEN N.C. = NORMALLY CLOSED SUP = SUPERVISED UNSUP = UNSUPERVISED

ON

1 2 3 4 5 6 7 8 9 10

DEFAULT SETTINGS: BAUD 19200, RELAY RANGE 1-64, RELAY CONTACT GROUPS N.O.

NOTE: REFER TO APPENDIX A FOR EACH LOCAL DEVICE ADDRESS (1-253).

Figure 8. SW2 DIP Switches

Figure 9. SW3 DIP Switches

3. Replace the front panel.

12 C1518M-A (11/02)

OPERATION

The function of the relay unit is to operate relays to control peripheral equipment. Each relay unit processes and executes only commands with addresses that match those of the relay units.

When power is turned on, the green power LEDs on the front and back of the unit light. The red data LED light on the front continually flashes on and off at a regular rate (about one-second intervals) until the unit is online and communicating with the CM6800. Once online, the LED remains ON. If for any reason communication is lost, the LED flashes again until communication is re-established.

MEMORY FEATURE

Although relay groups retain their contact position in the event of a power failure, the unit does not report relay status when requested after power is recycled. Since the firmware has no battery backed up memory, it does not know the state of the relays and may report them incorrectly. If a KBD960 keyboard is present on the system, it can contain inaccurate information in the GPI menu.

If the memory feature is disabled, the relays are all placed in a known state at startup. Under these conditions, the state of the relays are all known and are reported when requested. True relay status shows up on the keyboard display.

C1518M-A (11/02) 13

OPERATING RELAYS FROM THE KBD960

To operate relays from a KBD960 keyboard, you must know which GPI to call, and which auxiliary (AUX) to select on the keyboard.

You can cascade two relay units. Each relay unit has eight GPIs. Relay Unit 1 has a GPI range of 1-8, and Relay Unit 2 has a GPI range of 9-16. Refer to Tables C and D.

There are two ways you can operate relays from the KBD960.

ACTIVATING RELAYS USING F12

NOTE: You hear a brief click from the relay unit whenever you activate a momentary or latching relay contact.

Follow these steps to activate a momentary relay:

1. Go to Main Menu 1. 2. Enter a logical relay contact number (1-128). 3. Press F12.

A momentary relay does not remain on. Only a latched relay remains on. If you want a latched relay, you must activate it from the GPI Menus.

ACTIVATING RELAYS FROM THE GPI MENUS You can activate relays from the GPI Menus as momentary or latching. A momentary relay goes on briefly and then turns off. A latched relay remains on until you turn it off.

Momentary To activate relay contact 4, for example, follow these steps:

1. Go to Main Menu 1 and enter 1 (GPI). GPI 1 is associated with relay contact 4. Refer to Table C.

2. Select GPI to bring up GPI Menu 1. This menu displays auxiliaries 1-4. Make sure MTRY is highlighted. When MTRY is highlighted, any

relay you activate becomes momentary.

3. Select 4 .

Latching To activate the same relay as latching, follow these steps:

1. Go to Main Menu 1 and enter 1 (GPI).

2. Select GPI to bring up GPI Menu 1.

3. Select MTRY so that it is not highlighted. When MTRY is not highlighted, any relay you activate latches (remains on).

4. Select 4 . This icon becomes highlighted.

5. Select MTRY and then the highlighted auxiliary icon to turn off the latched relay.

14 C1518M-A (11/02)

Table D. Relay Unit 1

GPI Relay Contacts

1 1 2 3 4 5 6 7 8

2 9 10 11 12 13 14 15 16

3 17 18 19 20 21 22 23 24

4 25 26 27 28 29 30 31 32

5 33 34 35 36 37 38 39 40

6 41 42 43 44 45 46 47 48

7 49 50 51 52 53 54 55 56

8 57 58 59 60 61 62 63 64

Associated Aux 1 2 3 4 5 6 7 8

Table E. Relay Unit 2

GPI Relay Contacts

9 65 66 67 68 69 70 71 72

10 73 74 75 76 77 78 79 80

11 81 82 83 84 85 86 87 88

12 89 90 91 92 93 94 95 96

13 97 98 99 100 101 102 103 104

14 105 106 107 108 109 110 111 112

15 113 114 115 116 117 118 119 120

16 121 122 123 124 125 126 127 128

Associated Aux 1 2 3 4 5 6 7 8

NOTE: In Relay Unit 2, GPIs 9-16 are associated with the physical relays (1-64) on the back of the unit. However, GPIs 9-16 are also associated with logical relays 65-128. For example, the physical relays for GPI 9 are 1-8 and the logical relays are 65-72.

C1518M-A (11/02) 15

Figure 10. Power Input Fuse Replacement

Problem

Why were the contact positions lost when there was a power failure?

Why is the unit not operating as it should?

What is the DB9 port used for?

Solution

Make sure DIP switches 3-6 of SW3 are enabled so that your settings remain in memory.

Make sure the power cord is plugged in and the power switch is turned on. If the unit still fails to operate, remove the front panel and press the reset button. This initializes the unit to its start-up settings. Make sure the DIP switch settings and software settings are correct. Check the input power fuse. You may need to replace it. Refer to Figure 10.

This port is used for diagnostics. A technical support representative may ask you to enable this feature should a problem arise with the unit. This port is not needed for the everyday operation of the REL2064.

00699

TROUBLESHOOTING

16 C1518M-A (11/02)

DIP Switch Address 1 2 3 4 5 6 7 8

1 0 0 0 0 0 0 0 0 2 1 0 0 0 0 0 0 0 3 0 1 0 0 0 0 0 0 4 1 1 0 0 0 0 0 0 5 0 0 1 0 0 0 0 0 6 1 0 1 0 0 0 0 0 7 0 1 1 0 0 0 0 0 8 1 1 1 0 0 0 0 0 9 0 0 0 1 0 0 0 0

10 1 0 0 1 0 0 0 0 11 0 1 0 1 0 0 0 0 12 1 1 0 1 0 0 0 0 13 0 0 1 1 0 0 0 0 14 1 0 1 1 0 0 0 0 15 0 1 1 1 0 0 0 0 16 1 1 1 1 0 0 0 0 17 0 0 0 0 1 0 0 0 18 1 0 0 0 1 0 0 0 19 0 1 0 0 1 0 0 0 20 1 1 0 0 1 0 0 0 21 0 0 1 0 1 0 0 0 22 1 0 1 0 1 0 0 0 23 0 1 1 0 1 0 0 0 24 1 1 1 0 1 0 0 0 25 0 0 0 1 1 0 0 0 26 1 0 0 1 1 0 0 0 27 0 1 0 1 1 0 0 0 28 1 1 0 1 1 0 0 0 29 0 0 1 1 1 0 0 0 30 1 0 1 1 1 0 0 0 31 0 1 1 1 1 0 0 0 32 1 1 1 1 1 0 0 0 33 0 0 0 0 0 1 0 0 34 1 0 0 0 0 1 0 0 35 0 1 0 0 0 1 0 0 36 1 1 0 0 0 1 0 0 37 0 0 1 0 0 1 0 0 38 1 0 1 0 0 1 0 0 39 0 1 1 0 0 1 0 0 40 1 1 1 0 0 1 0 0 41 0 0 0 1 0 1 0 0 42 1 0 0 1 0 1 0 0 43 0 1 0 1 0 1 0 0 44 1 1 0 1 0 1 0 0 45 0 0 1 1 0 1 0 0 46 1 0 1 1 0 1 0 0 47 0 1 1 1 0 1 0 0 48 1 1 1 1 0 1 0 0 49 0 0 0 0 0 1 0 0 50 1 0 0 0 1 1 0 0 51 0 1 0 0 1 1 0 0 52 1 1 0 0 1 1 0 0 53 0 0 1 0 1 1 0 0 54 1 0 1 0 1 1 0 0 55 0 1 1 0 1 1 0 0 56 1 1 1 0 1 1 0 0 57 0 0 0 1 1 1 0 0 58 1 0 0 1 1 1 0 0 59 0 1 0 1 1 1 0 0 60 1 1 0 1 1 1 0 0 61 0 0 1 1 1 1 0 0 62 1 0 1 1 1 1 0 0

(Continued on next page)

DIP Switch Address 1 2 3 4 5 6 7 8

63 0 1 1 1 1 1 0 0 64 1 1 1 1 1 1 0 0 65 0 0 0 0 0 0 1 0 66 1 0 0 0 0 0 1 0 67 0 1 0 0 0 0 1 0 68 1 1 0 0 0 0 1 0 69 0 0 1 0 0 0 1 0 70 1 0 1 0 0 0 1 0 71 0 1 1 0 0 0 1 0 72 1 1 1 0 0 0 1 0 73 0 0 0 1 0 0 1 0 74 1 0 0 1 0 0 1 0 75 0 1 0 1 0 0 1 0 76 1 1 0 1 0 0 1 0 77 0 0 1 1 0 0 1 0 78 1 0 1 1 0 0 1 0 79 0 1 1 1 0 0 1 0 80 1 1 1 1 0 0 1 0 81 0 0 0 0 1 0 1 0 82 1 0 0 0 1 0 1 0 83 0 1 0 0 1 0 1 0 84 1 1 0 0 1 0 1 0 85 0 0 1 0 1 0 1 0 86 1 0 1 0 1 0 1 0 87 0 1 1 0 1 0 1 0 88 1 1 1 0 1 0 1 0 89 0 0 0 1 1 0 1 0 90 1 0 0 1 1 0 1 0 91 0 1 0 1 1 0 1 0 92 1 1 0 1 1 0 1 0 93 0 0 1 1 1 0 1 0 94 1 0 1 1 1 0 1 0 95 0 1 1 1 1 0 1 0 96 1 1 1 1 1 0 1 0 97 0 0 0 0 0 1 1 0 98 1 0 0 0 0 1 1 0 99 0 1 0 0 0 1 1 0

100 1 1 0 0 0 1 1 0 101 0 0 1 0 0 1 1 0 102 1 0 1 0 0 1 1 0 103 0 1 1 0 0 1 1 0 104 1 1 1 0 0 1 1 0 105 0 0 0 1 0 1 1 0 106 1 0 0 1 0 1 1 0 107 0 1 0 1 0 1 1 0 108 1 1 0 1 0 1 1 0 109 0 0 1 1 0 1 1 0 110 1 0 1 1 0 1 1 0 111 0 1 1 1 0 1 1 0 112 1 1 1 1 0 1 1 0 113 0 0 0 0 1 1 1 0 114 1 0 0 0 1 1 1 0 115 0 1 0 0 1 1 1 0 116 1 1 0 0 1 1 1 0 117 0 0 1 0 1 1 1 0 118 1 0 1 0 1 1 1 0 119 0 1 1 0 1 1 1 0 120 1 1 1 0 1 1 1 0 121 0 0 0 1 1 1 1 0 122 1 0 0 1 1 1 1 0 123 0 1 0 1 1 1 1 0 124 1 1 0 1 1 1 1 0

0 = OFF 1 = ON

APPENDIX A

C1518M-A (11/02) 17

DIP Switch Address 1 2 3 4 5 6 7 8

125 0 0 1 1 1 1 1 0 126 1 0 1 1 1 1 1 0 127 0 1 1 1 1 1 1 0 128 1 1 1 1 1 1 1 0 129 0 0 0 0 0 0 0 1 130 1 0 0 0 0 0 0 1 131 0 1 0 0 0 0 0 1 132 1 1 0 0 0 0 0 1 133 0 0 1 0 0 0 0 1 134 1 0 1 0 0 0 0 1 135 0 1 1 0 0 0 0 1 136 1 1 1 0 0 0 0 1 137 0 0 0 1 0 0 0 1 138 1 0 0 1 0 0 0 1 139 0 1 0 1 0 0 0 1 140 1 1 0 1 0 0 0 1 141 0 0 1 1 0 0 0 1 142 1 0 1 1 0 0 0 1 143 0 1 1 1 0 0 0 1 144 1 1 1 1 0 0 0 1 145 0 0 0 0 1 0 0 1 146 1 0 0 0 1 0 0 1 147 0 1 0 0 1 0 0 1 148 1 1 0 0 1 0 0 1 149 0 0 1 0 1 0 0 1 150 1 0 1 0 1 0 0 1 151 0 1 1 0 1 0 0 1 152 1 1 1 0 1 0 0 1 153 0 0 0 1 1 0 0 1 154 1 0 0 1 1 0 0 1 155 0 1 0 1 1 0 0 1 156 1 1 0 1 1 0 0 1 157 0 0 1 1 1 0 0 1 158 1 0 1 1 1 0 0 1 159 0 1 1 1 1 0 0 1 160 1 1 1 1 1 0 0 1 161 0 0 0 0 0 1 0 1 162 1 0 0 0 0 1 0 1 163 0 1 0 0 0 1 0 1 164 1 1 0 0 0 1 0 1 165 0 0 1 0 0 1 0 1 166 1 0 1 0 0 1 0 1 167 0 1 1 0 0 1 0 1 168 1 1 1 0 0 1 0 1 169 0 0 0 1 0 1 0 1 170 1 0 0 1 0 1 0 1 171 0 1 0 1 0 1 0 1 172 1 1 0 1 0 1 0 1 173 0 0 1 1 0 1 0 1 174 1 0 1 1 0 1 0 1 175 0 1 1 1 0 1 0 1 176 1 1 1 1 0 1 0 1 177 0 0 0 0 1 1 0 1 178 1 0 0 0 1 1 0 1 179 0 1 0 0 1 1 0 1 180 1 1 0 0 1 1 0 1 181 0 0 1 0 1 1 0 1 182 1 0 1 0 1 1 0 1 183 0 1 1 0 1 1 0 1 184 1 1 1 0 1 1 0 1 185 0 0 0 1 1 1 0 1 186 1 0 0 1 1 1 0 1 187 0 1 0 1 1 1 0 1 188 1 1 0 1 1 1 0 1 189 0 0 1 1 1 1 0 1

DIP Switch Address 1 2 3 4 5 6 7 8

190 1 0 1 1 1 1 0 1 191 0 1 1 1 1 1 0 1 192 1 1 1 1 1 1 0 1 193 0 0 0 0 0 0 1 1 194 1 0 0 0 0 0 1 1 195 0 1 0 0 0 0 1 1 196 1 1 0 0 0 0 1 1 197 0 0 1 0 0 0 1 1 198 1 0 1 0 0 0 1 1 199 0 1 1 0 0 0 1 1 200 1 1 1 0 0 0 1 1 201 0 0 0 1 0 0 1 1 202 1 0 0 1 0 0 1 1 203 0 1 0 1 0 0 1 1 204 1 1 0 1 0 0 1 1 205 0 0 1 1 0 0 1 1 206 1 0 1 1 0 0 1 1 207 0 1 1 1 0 0 1 1 208 1 1 1 1 0 0 1 1 209 0 0 0 0 1 0 1 1 210 1 0 0 0 1 0 1 1 211 0 1 0 0 1 0 1 1 212 1 1 0 0 1 0 1 1 213 0 0 1 0 1 0 1 1 214 1 0 1 0 1 0 1 1 215 0 1 1 0 1 0 1 1 216 1 1 1 0 1 0 1 1 217 0 0 0 1 1 0 1 1 218 1 0 0 1 1 0 1 1 219 0 1 0 1 1 0 1 1 220 1 1 0 1 1 0 1 1 221 0 0 1 1 1 0 1 1 222 1 0 1 1 1 0 1 1 223 0 1 1 1 1 0 1 1 224 1 1 1 1 1 0 1 1 225 0 0 0 0 0 1 1 1 226 1 0 0 0 0 1 1 1 227 0 1 0 0 0 1 1 1 228 1 1 0 0 0 1 1 1 229 0 0 1 0 0 1 1 1 230 1 0 1 0 0 1 1 1 231 0 1 1 0 0 1 1 1 232 1 1 1 0 0 1 1 1 233 0 0 0 1 0 1 1 1 234 1 0 0 1 0 1 1 1 235 0 1 0 1 0 1 1 1 236 1 1 0 1 0 1 1 1 237 0 0 1 1 0 1 1 1 238 1 0 1 1 0 1 1 1 239 0 1 1 1 0 1 1 1 240 1 1 1 1 0 1 1 1 241 0 0 0 0 1 1 1 1 242 1 0 0 0 1 1 1 1 243 0 1 0 0 1 1 1 1 244 1 1 0 0 1 1 1 1 245 0 0 1 0 1 1 1 1 246 1 0 1 0 1 1 1 1 247 0 1 1 0 1 1 1 1 248 1 1 1 0 1 1 1 1 249 0 0 0 1 1 1 1 1 250 1 0 0 1 1 1 1 1 251 0 1 0 1 1 1 1 1 252 1 1 0 1 1 1 1 1 253 0 0 1 1 1 1 1 1

0 = OFF 1 = ON

18 C1518M-A (11/02)

Figure 11. REL2064 Dimension Diagram

19.00 (48.26)

PWR ALARM

REL2064 Relay Interface Unit

Made in USA

17.40 (44.20)

1.75 (4.45)

8.15 (20.70)

NOTE: VALUES IN PARENTHESES ARE CENTIMETERS; ALL OTHERS ARE INCHES

00695

SPECIFICATIONS

ELECTRICAL Input Voltage: 100-240 VAC, 50/60 Hz, auto-ranging Power: 30 VA Data Ports

Diagnostic: RS-232, DB9 connector Input: RS-485, RJ-45 connector Output: RS-485, RJ-45 connector

Indicators: Two green power LEDs One data LED

Fusing: 500 mA, 250V Relay Contacts

Type: Normally open Max. Switching Capacity: 60 watts Max. Operating Voltage: 125 VAC/VDC Maximum Current: 2 amps Contact Resistance: 75 milliohms Rated Load Parameters: .5A @ 125 VAC; 2A @ 30 VDC Relay Output: Load rating for relay contacts: 0.50A at 125 VAC or 1A at 25 VAC

GENERAL Dimensions: See Figure 11. Operating Temperature: 32 to 122F (0 to 50C) Unit Weight: 8 lb (3.63 kg)

MECHANICAL Connectors

Relay Inputs: Screw terminals Power: 3-wire receptacle, #18 AWG RS-485: Two RJ-45 connectors RS-232: One DB9 connector (factory use only)

(Design and product specifications subject to change without notice.)

C1518M-A (11/02) 19

REVISION HISTORY

Manual # Date Comments C1518M 5/01 Original version. C1518M-A 11/02 Updated manual to new format. Revised Table A and updated Table B.

Pelco, the Pelco logo, Spectra, Genex, Esprit, Camclosure, and Legacy are registered trademarks of Pelco. Copyright 2002, Pelco. All rights reserved.

REGULATORY NOTICES

This equipment has been tested and found to comply with the limits of a Class B digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However there is no guarantee that the interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try and correct the interference by one or more of the following measures:

Reorient or relocate the receiving antenna. Increase the separation between the equipment and the receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help.

WARRANTY AND RETURN INFORMATION

WARRANTY Pelco will repair or replace, without charge, any merchandise proved defective in material or workmanship for a period of one year after the date of shipment. Exceptions to this warranty are as noted below:

Five years on Pelco manufactured cameras (CC3500/CC3600/CC3700 and MC3500/MC3600 Series); two years on all other cameras.

Three years on Genex Series (multiplexers, server, and keyboard) and 090 Series Camclosure

Camera System. Two years on 100/150, 200, and 300 Series Camclosure Camera Systems. Two years on all standard motorized or fixed focal length lenses. Two years on Legacy, CM6700/CM6800/CM8500/CM9500/CM9740/CM9760 Matrix, DF5

and DF8 Series Fixed Dome products. Two years on Spectra, Esprit, and PS20 Scanners, including when used in continuous

motion applications. Two years on Esprit and WW5700 series window wiper (excluding wiper blades). Eighteen months on DX Series digital video recorders. One year (except video heads) on video cassette recorders (VCRs). Video heads will be

covered for a period of six months. Six months on all pan and tilts, scanners or preset lenses used in continuous motion applica-

tions (that is, preset scan, tour and auto scan modes).

Pelco will warrant all replacement parts and repairs for 90 days from the date of Pelco shipment. All goods requiring warranty repair shall be sent freight prepaid to Pelco, Clovis, California. Repairs made necessary by reason of misuse, alteration, normal wear, or accident are not covered under this warranty.

Pelco assumes no risk and shall be subject to no liability for damages or loss resulting from the specific use or application made of the Products. Pelcos liability for any claim, whether based on breach of contract, negligence, infringement of any rights of any party or product liability, relating to the Products shall not exceed the price paid by the Dealer to Pelco for such Products. In no event will Pelco be liable for any special, incidental or consequential damages (including loss of use, loss of profit and claims of third parties) however caused, whether by the negligence of Pelco or otherwise.

The above warranty provides the Dealer with specific legal rights. The Dealer may also have additional rights, which are subject to variation from state to state.

If a warranty repair is required, the Dealer must contact Pelco at (800) 289-9100 or (559) 292-1981 to obtain a Repair Authorization number (RA), and provide the following information:

1. Model and serial number 2. Date of shipment, P.O. number, Sales Order number, or Pelco invoice number 3. Details of the defect or problem

If there is a dispute regarding the warranty of a product which does not fall under the warranty conditions stated above, please include a written explanation with the product when returned.

Method of return shipment shall be the same or equal to the method by which the item was received by Pelco.

RETURNS In order to expedite parts returned to the factory for repair or credit, please call the factory at (800) 289- 9100 or (559) 292-1981 to obtain an authorization number (CA number if returned for credit, and RA number if returned for repair).

All merchandise returned for credit may be subject to a 20% restocking and refurbishing charge.

Goods returned for repair or credit should be clearly identified with the assigned CA or RA number and freight should be prepaid. Ship to the appropriate address below.

If you are located within the continental U.S., Alaska, Hawaii or Puerto Rico: Service Department Pelco 3500 Pelco Way Clovis, CA 93612-5699

If you are located outside the continental U.S., Alaska, Hawaii or Puerto Rico: Intermediate Consignee Ultimate Consignee American Overseas Air Freight Pelco 320 Beach Road 3500 Pelco Way Burlingame, CA 94010 Clovis, CA 93612-5699 USA USA

World Headquarters 3500 Pelco Way

Clovis, California 93612 USA

USA & Canada Tel: 800/289-9100 Fax: 800/289-9150

International Tel: 1-5

Manualsnet FAQs

If you want to find out how the REL2064 Pelco works, you can view and download the Pelco REL2064 C1518M-A Interface Operation Manual on the Manualsnet website.

Yes, we have the Operation Manual for Pelco REL2064 as well as other Pelco manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Operation Manual should include all the details that are needed to use a Pelco REL2064. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Pelco REL2064 C1518M-A Interface Operation Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Pelco REL2064 C1518M-A Interface Operation Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Pelco REL2064 C1518M-A Interface Operation Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Pelco REL2064 C1518M-A Interface Operation Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Pelco REL2064 C1518M-A Interface Operation Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.