Mitsubishi CZ-112S Transformer User's Manual PDF

1 of 1
1 of 1

Summary of Content for Mitsubishi CZ-112S Transformer User's Manual PDF

E

A

H

6

5 2

4 0

2 8

B

G

C

D

F 7.7

Hole

Mounting bracket Mounting bracket

Hole Secondary terminalM3.5 Secondary terminalM3.5 Test terminalM4

Upper core

Short bar

D

B

C

9

A

100

7 30

9 0

7 0E1 2

kt lt

k

l

3 0

Through type zero-phase current transformer

Split type zero-phase current transformer Model ZT15B/ZT30B/ZT40B/ZT60B/ZT80B/ZT100B Model CZ-22S/ CZ-30S/ CZ-55S/ CZ-77S/ CZ-112S

Users Manual This instruction manual is for zero-phase current transformer(not included) and split type zero-phase current transformer(not included) that use with measuring unit. Be sure to read this instruction manual and the manual of measuring unit before use. The following items for zero-phase current transformer(not included) are included in package. Check that no items are missing Through type zero-phase current transformer(ZT15B/ZT30B/ZT40B/ZT60B/ZT80B/ZT100B)1

or split type zero-phase current transformer(CZ-22S/ CZ-30S/ CZ-55S/ CZ-77S/ CZ-112S)1 Instruction manual1(CZ-22S/ CZ-30S/ CZ-55S/ CZ-77S/ CZ-112S)

1Safety Precautions 1.1 1.1 Precautions concerning working environment and conditions

Do not use the unit in any of the following places. Doing so may cause malfunctions or a reduction in service life. Places where the ambient temperature exceeds the working temperature range(-5C to +55C).

Places exposed to direct sunlight. Places where the out of the cabinet.

Places where the humidity exceeds the humidity range (30% to 85%RH) or where condensation occurs.

Places where metal pieces or inductive substances are laying around.

Places with strong electromagnetic field or noise.

Places with a lot of dust, corrosive gas, salt or oily smoke. Places with a lot of vibration or impacts. Places where the unit may be exposed to rain or drops of water.

Place where the altitude exceeds 2000m. Places where the circuit with many harmonics.

Places where the daily average temperature exceeds 35C.

1.2 Precautions concerning preparations before using the equipment Use the unit in the specified usage environment and conditions.

Check the current and voltage ratings of the equipment.

Dont give this product vibration, a shock at the time of the transportation as much as possible.

1.3 Precautions concerning installation and connection

Danger Perform installation, disassembly, the wiring work after intercepting a power supply by all means . There might be the damage of an electric shock or the product.

Before installing and connecting the unit, read the instruction manual without fail. For safety, the unit shall be installed and connected by experts in electrical work. Connect the wires carefully, checking the wiring diagram. Incorrect wiring can cause unit failures, fires, and electric shocks. ULc-UL listed corresponds, use the wires according to the following conditions and UL-listed crimp type terminals.

Single wireAWG24AWG18(0.51.0mm), Stranded wireAWG20AWG16(0.81.3mm2) Connect the wires carefully, checking the wiring diagram. Incorrect wiring can cause unit failures, fires, and electric shocks. Use an electric wire of the size of penetrating this ZERO PHASE CURRENT TRANSFORMER (ZCT) for primary side cable, do not use a non-insulation electric wire or a metal for a primary cable Zero phase current transformer is high-precision magnetic material. Please use not to applied weight of primary through type electric wire and external force. Please hold not to applied weight of primary through type electric wire to zero phase current transformer. It might be cause of exterior destruction. Use the crimp-type terminal for secondary terminal and test terminal. If inappropriate crimp-type terminal is used, a wire breakage or a contact failure may occur, which may cause a device malfunction, a failure, a burnout or a fire. Please wire not give vibration and impact directly in secondary terminal. Read the manual of measuring units which is used with zero-phase current transformer, and is used well, and follow it. Use this zero-phase current transformer in cabinet certainly. Confirm that a terminal is closed surely. The lack of clamping causes malfunction of the machinery, a fire, the electric shock. Carry out the clamping of the crimp-type terminal lugs by prescribed torque. The excessive clamping becomes the ruination of a terminal and the screw. As for the panel, it be assumed that it was given the following matters.

a) It is necessary to attach a key to the cabinet. b) The structure that a power supply is intercepted automatically is necessary when opening a cabinet.

1.4 Precautions concerning in using

Use the unit within the rated range stated here. Using the unit out of the rated range may cause not only malfunctions or unit failure, but also fires or burnout. Do not open the secondary side of the ZCT while the primary current is running.

1.5 Precautions concerning maintenance and inspection Wipe off the surface dirt with tender cloth. Dont let chemical cloths touch it for a long time, and do not wipe it with benzine or thinner. Use a soft dry cloth to clean off dirt of the unit division surface. Check for the following items to use this unit properly for long time.

1Daily inspection Does not this product have the damage? Are not there an abnormal sound, bad-smelling fever?

2Periodic inspectionCheck once in 6 months to 1 year Are not there installation, the slack of the screw?

1.6 Precautions concerning storage When storing the unit, turn off power, disconnect cables and wires, and put them in vinyl bags or the like. When storing the unit for a long time, avoid keeping it in the places shown below.

Places where the ambient temperature is out of the range from -10C to +60C.

Places with a lot of vibration or impact.

Places where the humidity exceeds the humidity range (5% to 95%RH) . Places where the unit is exposed directly to rain, water droplets. Places with a lot of dust, corrosive gas, salt or oily smoke. Places where metallic particles or inductive substances are laying

around.

Caution

Caution

1.7 Precautions concerning disposal Dispose this product appropriately in accordance with the national or community rule. 1.8About packaging materials and this manual

For reduction of environment load, packaging materials are produced with cardboard, and this manual is printed on recycled paper. 2Installation

Parts names and installation

1) Primary wire pass hole. 2) Wiring secondary terminal. *For the details, see the manual for measurement unit. Table of dimensions change Dimensions [mm]

ZT15B ZT30B ZT40B ZT60B ZT80B ZT100B A 48 68 85 140 160 185 B 15 30 40 60 80 100 C 29 37 43 73 82 93 D 62 82 92 150 169 190 E 46 66 81 46 48 50 F 15 30 40 G 70 90 100 H 25 50 50

Parts names and installation

1) Unscrew the short bar and take off the one side of the short bar. 2) Loosen a joining screw of ZCT in right and left side alternation equality and take off

upper core. 3) Put a primary wire through lower core. And Tighten a joining screw in right and left

equality. 4) Tighten shorting bar.And wiring secondary terminal. *For the details, see the manual for measurement unit. Table of dimensions change Dimensions [mm]

CZ-22S CZ-30S CZ-55S CZ-77S CZ-112S 22 30 55 77 112 27 27 32 41 57 100 114 148 198 234 112 130 160 210 246 128 144 177 232 268 5 5 7 10 8 30 30 36 45 62 12 12 12 12 12 41 47 66 90 109 K 77 89 124 171 207

Table of the biggest electric wire diameter and the tolerance current

8 60 100 325 22 60 250 500

61 217 298 650 (115) 217 (556) (842)

3.5 38 100 250 500 800 22 38 200 500 1000

44 190 355 620 920 1285 (130) 190 (545 920 1470

8 38 100 250 500 22 38 200 500

61 162 298 556 842 (115) 162 (469 (842)

2 38 60 200 400 600 14 38 150 400 1000

31 190 255 545 (815) 1005 (100) 190 (455 815 (1470)

8 38 60 200 400 14 38 150 325

(61) (162) (217) (469) (745) (88) (162) (395) (650)

22 60 150 325 600 8 22 150 325 600

(130) (255) (455) (725) (1005) (72) (130) (455) (725) (1005)

Wiring method

Wiring type

Type of current wire ZT15B ZT30B Number of

electric wire

600V Closs-linked polyethylene insulated Vinyl sheathed cable, SingleCV cable

3P4W 4

600V cable insulate by Vinyl IV cable

1P2W 2

600V cable insulate by Vinyl IV cable

3

600V cable insulate by Vinyl IV cable

600V Closs-linked polyethylene insulated Vinyl sheathed cable, SingleCV cable

1P3W 3P3W 600V Closs-linked polyethylene insulated

Vinyl sheathed cable, SingleCV cable

CZ-77SCZ-55SCZ-30SCZ-22S

Diameter of electric wire throughable mm2 acceptable current(A)

CZ-112SZT100BZT40B ZT60B ZT80B

* Please confirm dimensions. Because there is the case that I cannot penetrate by a finish external form, the transformation (curves) of the electric wire, Confirm dimensions.

3Specification

Model ZT15B ZT30B ZT40B ZT60B ZT80B ZT100B CZ-22S CZ-30S CZ-55S CZ-77S CZ-112S

Hole diameter (mm) 15 30 40 60 80 100 22 30 55 77 112

Maximum voltage (voltage to ground / line voltage)

AC 600V

Frequency 50/60Hz Rated short time current (Peak value)

50kA (100kA)

Measurement (installation) category CAT Pollution degree 2 Compatible specification EMC: EN61326-1: 2013 UL: UL61010-1 Safety standard: EN-61010-1: 2010 Combination unit * This zero phase current transformer conforms to CE, UL in a condition to make combination use with EMU4-LG1-MB.

*1 When combine it with a ZCT (ModelZT60B,ZT80B,ZT100B),it confirms UL standard.

4Customer Service

(1)ZT15B/ZT30/ZT40B (2)ZT60B/ZT80B/ZT100B

(3)CZ-22S/CZ-30S/CZ-55S/CZ-77S (4)CZ-112S

Hole

Joining screws

Lower core

Mounting bracket

Secondary terminalM4

Test terminalM4

Upper core

Short bar kt lt

k

l

Hole

Joining screws

Lower core

Mounting bracket

Secondary terminalM4

Please refer to "catalog" or users manual (Details) for more detail. HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, J

Manualsnet FAQs

If you want to find out how the CZ-112S Mitsubishi works, you can view and download the Mitsubishi CZ-112S Transformer User's Manual on the Manualsnet website.

Yes, we have the User's Manual for Mitsubishi CZ-112S as well as other Mitsubishi manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The User's Manual should include all the details that are needed to use a Mitsubishi CZ-112S. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Mitsubishi CZ-112S Transformer User's Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Mitsubishi CZ-112S Transformer User's Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Mitsubishi CZ-112S Transformer User's Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Mitsubishi CZ-112S Transformer User's Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Mitsubishi CZ-112S Transformer User's Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.