- Manuals
- Brands
- Mitsubishi
- Relay
- CAC1-A01D2
- Instruction Manual
Mitsubishi CAC1-A01D2 Relay Instruction Manual PDF
Summary of Content for Mitsubishi CAC1-A01D2 Relay Instruction Manual PDF
1 JEP0-IL9432-F
Request Ensure that this Instruction Manual is delivered to
the end users and the maintenance manager.
JEP0-IL9432 2
Safety section
This Safety section should be read before starting any work on the relay. Be sure to read the instruction manuals and other related documents prior to commencing any work on the relay in order to maintain them in a safe condition. Be sure to be familiar with the knowledge, safety information and all caution items of the product prior to use.
CAUTION Caution means that failure to un-observe safety information, incorrect use, or improper use may endanger personnel and equipment and cause personnel injury or physical damage.
Items as classified to the caution may become to occur more sever results according to the circumstance. Therefore, all items described in the safety section are important and to be respected without fail.
CAUTION
1. Items concerning transportation (1) Be sure the equipment to be kept in normal direction (2) Avoid the bumps, shock, and vibration, otherwise the product performance /life might be unfavorably
affected. 2. Items concerning storage
(1) Environment shall be as below, otherwise the product performance/life might be unfavorably affected. -Ambient temperature: -20+60 (with no condensation nor freezing) -Relative humidity: 30~80% average of a day -Altitude: Less than 2000m -Avoid applying unusual shock, vibration or leaning or magnetic field -Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material or wind, rain.
3. Items concerning mounting/wiring work (1) Mounting and wiring work should be done correctly.
Otherwise, damage, burning or erroneous operation might occur. (2) Screw terminal should be tightened securely.
Otherwise, damage and burning might occur. (3) Grounding should be done correctly in case it is required.
Otherwise, electric shock, damage, burning or erroneous operation might occur. (4) Wiring should be done without mistake especially observing the correct polarity. Otherwise, damage, burning or erroneous operation might occur. (5) Wiring should be done without mistake especially observing the phase ordering. Otherwise, damage, or erroneous operation might occur. (6) Auxiliary power source, measuring transformer and power source which have enough capacity for
correct operation of product should be used. Otherwise, an erroneous operation might occur.
(7) Be sure to restore the front cover, terminal cover, protection cover, etc to the original position, which have been removed during the mounting/ wiring work. Otherwise, electrical shock might occur at the time of checking.
(8) Connection should be done correctly using designated and right connectors. Otherwise, damage or burning might occur.
(9) Fully insert the sub unit into the case until you can hear a click while pressing the handles located on both sides of the sub unit front face. Otherwise, incomplete inserting the sub unit might only establish a poor contact with the terminals located on the back side of unit, which might cause erroneous operation or heating.
4. Concerning equipment operation and settings (1) Operational condition should be as below.
Otherwise, the product performance/life might be unfavorably affected. -Deviation of auxiliary power: within +10%~-15% of rated voltage -Deviation of frequency: within 5% of rated frequency -Ambient temperature: 0+40 (-10+50 is permissible during couples of hour per day, with no condensation nor freezing)
-Relative humidity: 30~80% average of a day -Altitude: Less than 2000m -Avoid to be exposed to unusual shock, vibration, leaning or magnetic field -Not expose to harmful smoke, gas, salty air, water, vapor, dust, powder, explosive material, wind or rain.
JEP0-IL9432 3
(2) Qualified personnel may work on or operate this product, otherwise, the product performance/life might be unfavorably affected and/or burning or erroneous operation might occur.
(3) Be sure to read and understand the instruction manuals and other related documents prior to commencing operation and maintenance work on the product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(4) While energizing product, be sure not to remove any unit or parts without permissible one. Otherwise, damage, or erroneous operation might occur.
(5) While energizing product, be sure to make short circuit of current transformer secondary circuits before setting change or drawing out the sub unit. Otherwise, secondary circuit of live current transformer might be opened and damage or burning might occur due to the high level voltage.
(6) While energizing product, be sure to open trip lock terminal before setting change or drawing out the internal unit of product. Otherwise, erroneous operation might occur.
(7) Be sure to use the product within rated voltage and current. Otherwise, damage or mal-operation might be occurred.
(8) While energizing product, be sure not to clean up the product. Only wiping a stain on the front cover of product with a damp waste might be
allowable. (Be sure to wring hardly the water out of the waste.) 5. Items concerning maintenance and checking
(1) Be sure that only qualified personnel might work on or operate this product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(2) Be sure to read and understand the instruction manuals and other related documents prior to commencing operation and maintenance work on the product. Otherwise, electrical shock, injury, damage, or erroneous operation might occur.
(3) In case of replacing the parts, be sure to use the ones of same type, rating and specifications, etc. If impossible to use above parts, be sure to contact the sales office or distributor nearest you. Otherwise, damage or burning might occur.
(4) Testing shall be done with the following conditions. -Ambient temperature: 2010 -Relative humidity: Less than 90% -Magnetic field: Less than 80A/m -Atmospheric pressure: 86~106103 Pa -Installation angle: Normal direction2 -Deviation of frequency: within 1% of nominal frequency -Wave form(in case of AC): Distortion factor less than 2%
(Distortion factor=100%effective value of harmonics/effective value of fundamental) -Ripple (in case of DC): Ripple factor less than 3% (Ripple factor=100%(max-min)/average of DC) -Deviation of auxiliary power: within 2% of nominal voltage -Be sure not to inject the voltage or current beyond the overload immunity. Otherwise, damage or burning might occur. -Be careful not to touch the energized parts. Otherwise, the electric shock might occur. 6. Items concerning modification and/or repair work
Be sure to ask any modification and/ or repair work for product to the sales office or distributor nearest you.
Unless otherwise, any incidents occurred with modification or repair works (including software) done by any other entity than MITSUBIHI ELECTRIC CORPORATION shall be out of scope on warranty covered by MITSUBISHI ELECTRIC CORPORATION.
7. Items concerning disposal Particular regulations within the country of operation shall be applied to the disposal.
JEP0-IL9432 4
- Introduction -
Thank for your purchasing MITSUBISHI ELECTRIC MELPRO TM D Series Digital Protection Relay.
Please read this manual carefully to be familiar with the functions and performances enough to use the
product properly.
It is necessary to forward end users this instruction manual.
For operation of the product, this manual should be used in conjunction with the following materials: Title of document Document No.
MELPRO D Series Protection Relay General Operation Manual JEP0-IL9416
When the protection relay is used together with a communication card, use the following documents too:
(For CC-Link) Title of document Document No.
MELPRO D Series Protection Relay CC-COM Communication Card (CC-Link) Operation Manual (General information) JEP0-IL9517
MELPRO D Series Protection Relay CC-COM Communication Card (CC-Link) Operation Manual (Model-specific information) JEP0-IL9418
JEP0-IL9432 5
CONTENTS 1 Features.......................................................................................................................................................6
1.1 General description ......................................................................................................................6 1.2 Features .......................................................................................................................................6
2 Ratings and specifications ...........................................................................................................................8 2.1 General information ......................................................................................................................8 2.2 Protection element........................................................................................................................9 2.3 Measurement elements..............................................................................................................10
3 Characteristics ...........................................................................................................................................11 3.1 Protective elements ....................................................................................................................11 3.2 Common technical data..............................................................................................................14
4 Functions ...................................................................................................................................................15 4.1 Protection ...................................................................................................................................15 4.2 Setting.........................................................................................................................................20 4.3 Measurement..............................................................................................................................25 4.4 Self-diagnosis .............................................................................................................................26 4.5 Communication (option) .............................................................................................................28
5 Configuration..............................................................................................................................................30 5.1 Internal configuration..................................................................................................................30 5.2 External connection ....................................................................................................................33
6 Handling.....................................................................................................................................................41 6.1 Unpacking...................................................................................................................................41 6.2 Transportation and storage ........................................................................................................41 6.3 Appearance and how to pull sub unit out ...................................................................................41 6.4 How to use front control panel....................................................................................................46
7 Mounting ....................................................................................................................................................56 7.1 Mounting dimension ...................................................................................................................56 7.2 Standard operating environment ................................................................................................56
8 Test ............................................................................................................................................................57 8.1 Appearance inspection...............................................................................................................57 8.2 Characteristic test.......................................................................................................................58
9 Maintenance ..............................................................................................................................................61 9.1 Daily inspection ..........................................................................................................................61 9.2 Periodical inspection...................................................................................................................61
10 Ordering .....................................................................................................................................................62 11 Guarantee ..................................................................................................................................................62
11.1 Guarantee period........................................................................................................................62 11.2 Scope of guarantee ....................................................................................................................62 11.3 Exclusion of loss in opportunity and secondary loss from warranty liability...............................63 11.4 Applications of products .............................................................................................................63 11.5 Onerous repair term after discontinuation of product.................................................................64 11.6 Changes in product specification ...............................................................................................64 11.7 Scope of service .........................................................................................................................64
12 Improvement of protection function ...........................................................................................................64
JEP0-IL9432 6
1 Features 1.1 General description
Mitsubishi Electric MELPRO-D Series is a digital protection relay product with a microprocessor for
protecting high/extra-high-voltage electric power system.
With its improved functions, including operation support using the advanced communication networks,
data saving at the power system faults and power system voltage/current measurement, this series of
protection relay will allow stable and effective control and monitoring of electric power systems as well as
provide high-reliable protection.
1.2 Features
(1) High-reliable protection
CAC1-A01D2 relay contains a 3-phase biased differential protection element and a 3-phase
differential overcurrent protection element. Just this one relay is enough to protect a transformer. In
addition, it also contains a 3-phase second-harmonic blocking element in order to avoid incorrect
operation caused by inrush current.
(2) Communication Network (With the addition of optional communication card)
- With an open field bus system, the relays can be used to build a high-speed, high-performance
network system. In addition, the relays multi-drop serial wiring reduces the amount of labor
required for communication wiring.
- Monitoring of measurement values, operation status, as well as setting changes, etc., can be
performed from a remote location.
- In consideration of future network system variations and compatibility with communication
networks, communication features are mounted in the relay using a replaceable card.
(3) Measurement & Recording Functions
- Real time monitor of relay input data
The relay can measure steady state relay input values, supporting energy management.
- Fault Data Monitor
When a fault occurs, the relay saves the past 5 effective input values, and waveform data and 2nd
harmonic component ratio to assist with fault analysis.
(4) Programmable Output Configuration
The operating output contacts (DO) can be set by combining the outputs of the protection relay
element using OR logic, thereby simplifying sequence design.
(5) High Accurate Digital Computation
The digital computation using high-speed sampling minimizes the effect of high harmonics, etc., and
results in highly accurate protection.
(6) Self-diagnosis
The relay continuously monitors electronic circuits from input to output so that it can detect internal
failure before that failure causes damage on the power system, thereby improving reliability.
(7) Easy Replacement
The dimensions of the panel cutout are the same as the prior MULTICAP series. Changing from an
existing relay type to this new type is easy.
JEP0-IL9432 7
(8) Easy Maintenance
The relays are adopted as draw-out unit mechanisms with automatic CT shorting at drawing, thereby
making maintenance easy.
(9) Easy wiring check
It is possible to carry out forced operation of the output contacts individually. This will allow an easy
wiring check.
JEP0-IL9432 8
2 Ratings and specifications 2.1 General information
Type name CAC1-A01D2 Without direct communication port 302PMB 303PMB 326PMB 327PMB
Style With direct communication port 561PMB 562PMB 563PMB 564PMB
Biased differential element 3 2ndharmonic blocking element 3 Protection
Differential overcurrent element 3 Elements
Measurement Restraining current, Differential current, 2f harmonic component ratio Frequency 50 Hz 60 Hz 50 Hz 60 Hz
Phase current 5 A *20 1 A *20 Voltage Common use for 100 ~ 220VDC / 100 ~ 220VAC Ratings
Auxiliary power supply *21 Operative
range DC : 85 ~ 242 V (Range of 80 ~ 286VDC is allowable temporarily.) AC : 85 ~ 242 V (Range of 80 ~ 253VAC is allowable temporarily.)
RUN Indicate the result of self-diagnosis. The lamp is lit for normal conditions and off for abnormal.
Unit Indicate the unit symbol for measurements.
Item No., Item data Display measurement, status, setting and option data selected with an item number.
Display
Communication With a communication card installed: the lamp is lit for normal conditions, blinking during communication and off for abnormal. With a communication card not installed: the lamp is off.
Self-diagnosis Monitor the electronic circuit and internal power supply to output signal to the RUN LED and self-diagnosis output (ALARM).
For trip 2 make contacts: X4 and X5 (programmable output) For signaling 4 make contacts: X0 to X3 (programmable output) Configurations
For self-diagnosis output
1 break contact: Y (open for normal result of self-diagnosis with power on)
Make 110VDC, 15A, 0.5 s (L/R = 0 s) 220VDC, 10A, 0.5 s (L/R = 0 s)
Break 110VDC, 0.3A (L/R 40 ms) 220VDC, 0.15A (L/R 40 ms)
For trip
Carry 1.5 A , continuously Make and break 500 VA (cos= 0.4), 60W (L/R = 0.007 s) Max. current 5 A
Output contacts
Capacity
For signaling and self-diagnosis
output Max. voltage 380VAC, 125VDC Direct communication port Standard equipment (PC software for direct communication) : option
Communication Remote communication card Option for CC-Link
Phase current circuit 0.5 VA or less (with rated current)
Burden Auxiliary power supply circuit
100VDC : approx. 7W (approx. 9W including communication card) 100VAC : approx. 25VA (approx. 27VA including communication card) 220VDC : approx. 9W (approx. 11W including communication card) 220VAC : approx. 30VA (approx. 32VA including communication card)
Mass Net weight of relay unit : approx. 3.8 kg Including case : approx. 5.0 kg
Case/cover Size : D2 type *20 Permissible continuous current value is 8.7A(for 5A rating) and 1.7A (for 1A rating). *21 When an uninterruptible AC power source is not provided in your system for the auxiliary supply voltage, use the
type B-T1 backup power supply or commercially available uninterruptible power supply (UPS). Type B-T1 back up power supply unit can be applied for DASH series protection relay with 100V200V auxiliary power supply voltage rating only. In addition, the power supply duration of the type B-T1 back up power supply is confirmed about 2 seconds in combination with one MELPRO-D series relay. Therefore, in the case that the required power supply duration after power source loss exceeds 2 seconds, please use a suitable commercial uninterruptible power supply. When the power supply back up for the control power supply of a circuit breaker is required, it is necessary to prepare the backup power supply different from the type B-T1 back up power supply.
JEP0-IL9432 9
2.2 Protection element Without direct communication port 302PMB 303PMB 326PMB 327PMB Style With direct communication port 561PMB 562PMB 563PMB 564PMB
Matching tap 1 IT1(IT)
2.2 ~ 12.5A (0.1A step)
0.44 ~ 2.5A (0.02A step)
Matching tap 2 IT2(IT)
2.212.5A (0.1A step)
0.44 ~ 2.5A (0.02A step)
Operation current IT(LOCK203040%) Bias
(=Differential current/Restraining
current)
203040-%
Biased differential protection
DIF test *22 oFF(When running)-on(When testing)
2nd harmonic blocking
2nd harmonic blocking ratio
2nd harmonic component (If2)/ fundamental component (If1)=10~25%
(5% step)
Settings
Differential overcurrent Operation current IT(5~12) (1 step)
Forced operation Forced operation is available for any trip or signaling contacts individually.
Operation indication When the relay operates, the operation indicator LED (red) will come on. And when 2nd harmonic wave is found out, the detection LED (yellow) comes on.
*22 When DIF test is set on, the single phase relay test can be carried out with the differential current monitor blocked.
JEP0-IL9432 10
2.3 Measurement elements Without direct communication port 302PMB 303PMB 326PMB 327PMB Style With direct communication port 561PMB 562PMB 563PMB 564PMB
Measurement Effective current in stationary state [multiplying factor against IT] Range * 0~9999[%] Real time Update Approx. 200ms Measurement Max. effective current [multiplying factor against IT] Max.
records Range * 0~9999[%] Measurement Effective current when tripping [multiplying factor against IT]
Restraining current
Fault records Range * 0~9999[%]
Measurement Effective current at stationary state [multiplying factor against IT] Range * 0~9999[%] Real time Update Approx. 200ms Measurement Max. effective current [multiplying factor against IT] Max.
records Range * 0~9999[%] Measurement Effective current when tripping [multiplying factor against IT]
Differential current
Fault records Range * 0~9999[%]
Measurement If2/ If1 at stationary state
Range * 0~9999[%] Real time Update Approx. 200ms Measurement If2/ If1 when tripping
Display
2f component
ratio Fault records Range * 0~9999[%]
* The form of display depends on value range as shown in the tables below. When displaying value exceeds the maximum of the range, display will be blinked with the maximum value.
Display range Display form Display range Display form Display range Display form Display range Display form 0~9[%] [%] 10~99[%] [%] 100~999[%] [%] 1000~9999[%] [%]
*When a communication card is connected, wave form data in the case of the power system fault can be monitored. (See the section 4 Function).
JEP0-IL9432 11
3 Characteristics
Common conditions
(1) Rated frequency:1%
(2) Aux. supply voltage : Rated voltage 2% (3) Ambient temperature: 20C10C
The conditions shown on the left should be applied unless otherwise specified.
3.1 Protective elements Items Conditions Guaranteed performance
Biased differential element Iop=ITOperation current (%) Operation value Differential overcurrent
element Iop=ITDifferential overcurrent Within 5% of Iop
Biased differential element Iop=ITOperation current (%) Reset value Differential overcurrent
element Iop=
ITDifferential overcurrent
Operation value95%or more
Biased differential element 0[A] Iop300% 50ms or less Operation time Differential overcurrent
element 0[A] Iop300% 40ms or less
Biased differential element Iop300% 0[A] Reset time Differential overcurrent
element Iop300% 0[A] Within 20025ms
Biased differential characteristics
Matching tap IT1 = IT2 = IT At minimum matching tap setting I2 = IT 200%
| I1 I2 | I1 or I2*
Bias=
(* Whichever is greater)
I1 I2
When = 20% setting = 15%25%
When = 30% setting = 25%35%
When = 40% setting = 35%45%
Both lead and lag operation phase angle between I1 and I2 are shown below: Nominal bias ratio
20 [%] 168.55
30 [%] 162.75
Phase characteristics
At minimum matching tap setting | I1 | = | I2 |
=IT 200
Internal fault side
Through fault side 40 [%] 156.95
At minimum matching tap setting IDC = IT 80% *Refer to the 8.2.2 characteristic test circuit
Setting value : 10% IAC = 254330% () Setting value : 15% IAC = 137188% () Setting value : 20% IAC = 81119% () Setting value : 25% IAC = 4777% () :Range to be possible
to block
2nd harmonic blocking characteristics
In case of 2nd harmonic current superposing method If1=IT300%
2nd restraining ratio: Setting value10%
JEP0-IL9432 12
Items Conditions Guaranteed performance Operation value
Reset value
(1)Rated frequency (2) Rated deviation range of Aux,
supply voltage
5% or less of operation/resent value at rating aux, voltage.
Operation time
Reset time
(1)Rated frequency (2)Rated deviation range of Aux,
supply voltage
5% ms or less at rating aux, voltage.
Biased differential characteristics
(1)Rated frequency (2)Rated deviation range of Aux,
supply voltage (3)At minimum matching tap and
I2I1200%
In response to the at rating aux, voltage, When = 20%
= 15%25 When = 30%
= 25%35 When = 40%
= 35%45
Auxiliary supply voltage deviation
characteristic
Phase characteristics
(1)Rated frequency (2)Rated deviation range of Aux,
supply voltage (3)I1=I2= IT200%
5% or less of phase angle at rating aux, voltage.
Operation value
Reset value
(1)Rated aux, voltage (2)Frequency deviation 5% of rated frequency
5% or less of the value at the rated frequency
Operation time
Reset time
(1) Rated aux, voltage (2)Frequency deviation
5% of rated frequency
5 on less of at the rated frequency
Biased differential characteristics
(1)Rated aux, supply voltage (2)At minimum matching tap and
I2IT200% (3)Frequency deviation5% of rated
frequency
5 on less of at the rated frequency
Frequency characteristics
Phase characteristics
(1)Rated aux, supply voltage (2)I1=I2= IT200% (3)Frequency deviation5% of rated
frequency
5% or less of phase angle at the rated frequency.
2020 5% or less of the value at 20
Operation value Reset value
(1)Rated frequency (2)Rated aux supply
voltage 2030 10% or less of the value at 20
2020 Operation time
Reset time
(1)Rated frequency (2)Rated aux supply
voltage 2030
5 ms or less of the value at 20
2020 5 or less of the value at 20
Biased differential characteristics
(1)Rated frequency (2)Rated aux supply
voltage (3)I2IT200%
2030 10 or less of the value at 20
5 or less of the value at 20
Temperature characteristics
Phase characteristics
(1)Rated aux, supply voltage (2)I1=I2= IT200% (3)Frequency deviation5% of rated
frequency 10 or less of the value at 20
JEP0-IL9432 13
Items Conditions Guaranteed performance
Relative humidity characteristics
Temperature 40 Relative humidity 95RH
no condensed Testing duration 4 days
Operation value 5% or less of the value at normal condition Operation time 10% or less of the value at normal condition Phase angle 5or less of the value at normal condition
*31 Mitsubishi electric corporation adopt the scheme that maximum current is applied for restrain current. Therefore, biased differential characteristics is calculated such as the differential current divided by the
maximum current. On the other hand, biased differential characteristics calculated by outflow current base scheme is
described in the following table. Differential currentRestrain currentoutflow current
Ratio Inflow Flow-out
Differential current
Ratio
(Adopted scheme by Mitsubishi electric corporation.) (outflow current base scheme)
JEP0-IL9432 14
3.2 Common technical data ITEM DESCRIPTION CONDITION STANDARD
Ambient operating temperature
-10C to +55C IEC60255-6
Ambient storage and transport temperature
-25C to +70C IEC60255-6 Environment
Damp heat +40C, 95%RH, 4 days IEC60068-2-3 VT 1.15Vn, 3h Thermal
withstand CT 40In, 1s
Circuit of 60V or below 500VAC, 1min.
Circuit of more than 60V and 500v or below
2000VAC 1min.
1) Between each circuit and the exposed conductive parts, the terminals of each independent circuit being connected together
2) Between independent circuits, the terminals of each independent circuit being connected together
Dielectric test
Open contact 1000VAC, 1min. Between open contact poles
IEC60255-5
Impulse voltage test 5kV, 1.2s/50s
1) Between each circuit and the exposed conductive parts, the terminals of each independent circuit being connected together
2) Between independent circuits, the terminals of each independent circuit being connected together
IEC60255-5
Common mode 2.5kV peak, 1MHz with 200 source impedance for 2s
Between independent circuits, and between independent circuit and earth
High-frequency disturbance test
Differential mode 1.0kV peak, 1MHz with 200 source impedance for 2s
Across terminals of the same circuit
IEC60255-22-1 class 3
8kV Contact discharge Electrostatic discharge test
15kV Air discharge IEC60255-22-2 Class 4
Radiated electromagnetic field disturbance test
68 to 87Mhz 146 to 174MHz 420 to 470MHz
IEC60255-22-3 class 3
Fast transient disturbance test 2.0kV, 5ns/50ns, 1min IEC60255-22-4
Vibration test Refer to class 1 IEC60255-21-1 Class 1
Shock response Refer to class 2 IEC60255-21-2 Class 2
Shock withstand Refer to class 1 IEC60255-21-2 Class 1
Bump Refer to class 1 IEC60255-21-2 Class 1
Enclosure protection IP51 IEC60529
Vn: Rated voltage, In: Rated current
JEP0-IL9432 15
4 Functions 4.1 Protection
4.1.1 Protection elements
Fig. 4.1 shows internal function block diagram of Biased differential element and differential overcurrent
element.
In this relay, a differential element with bias blocking, a 2nd harmonic blocking element (2f blocking
element) and a differential overcurrent element are provided for each phase protection of 2-winding
transformer. Fig. 4.2 shows the biased differential characteristic. The relay output is blocked by the
operation of the 2nd harmonic blocking element which is designed to detect the exciting inrush current
generated at energizing the transformer. The internal or external fault can be distinguished by differential
element with bias. And the internal heavy fault can be protected quickly by differential overcurrent element
with instantaneous operation characteristic.
I2A Biased differential
characteristic
Level distinguish
87-A operating signal
Effective value
f
Matching tap
2f Matching tap
Max. value
2f blocking element
Level distinguish 2f-Block-A operating signal
Effective value
Biased differential
element Effective
value
Effective value
2f
Matching tap
Matching tap
f
Minimum operation value
Level distinguish
87H-A
operating signal
Differential overcurrent
element Level distinguishI1A
Biased differential
element
Id/I>-A
Id>-A
2fB-A
Figure 4.1 Biased differential elementDifferential overcurrent element Internal function diagram
(Only one phase expressed)
(1) Matching tap
The CT ratio and CT connection are designed to compensate the current difference between HV side and
LV side as a consequence of the transformer ratio and winding connection so that current of HV side and LV
side are become to almost same value.
To obtain perfectly same current value of HV side and LV side, matching tap installed in the relay can be
applied.
The matching tap should be set according to that the current value calculated by the rated transformer operation currentrated input current of relay/setting of matching tap will be quite closer value of rated input
current of relay.
(2) Biased differential
To detect the internal faults of transformer, current differential scheme can be applied in principle.
However, CT error in the condition of large current has to be considered in the actual application.
Then, biased differential scheme in which internal faults will be detected by the ratio between differential
current and maximum current in circuit, is applied.
JEP0-IL9432 16
The definition of biased differential in the relay is as follows. Biased differential = Differential current/Restraining current100%
Differential current: HV side currentLV side current
(The above equation is based on that generally the HV current is inflow and
the LV current is outflow in the normal condition of transformer.)
Restraining current: | HV current | or | LV current | whichever is greater.
The following is the actual calculation executed in the relay. (I1In/IT1I2In/IT2)
(I1In/IT1 or I2In/IT2 whichever is greater) 100
Minimum operating value (I1In/IT1I2In/IT2)In(Setting value of operation current/100)
For example, minimum operating value at HV side Iop can be derived with I2=0 as below. I1In/(In/IT1)(setting of operation current/100) I1IT1(setting of operation current/100)
(3) At the time of internal fault
At the time of internal fault, the differential current IDIF overcomes the restraining current IRES, so that the
biased differential element operates with high-speed. Moreover, at the time of an internal fault with heavy
fault current, the differential overcurrent element can operate instantaneously.
=40% 30%
20%
I2 IDF
I1
3
IRES
IDIF
IMIN-OP
2
1
5 4 3 2 1 0
Multiples of tap value current IT
Operating zone
No operating zone
current : Rated In e)tting valung tap (Se : Matchi, II
urrentecondary c : CT s, II )ting value40% ) (Set20%, 30%, : Bias (
g value) ) (Settin current I tap valuef matching30%, 40% ont ( 20%, ting curre : OperaI
) I I
, I I I
rent of ILarger curcurrent ( ng Restraini :I
) I I
I I I
Icurrent ( fferential : DiI
T2T1
21
TMin. op
T2
n 2
T1
n 1RES
T2
n 2
T1
n 1DIF
Figure 4.2 Biased differential characteristic
JEP0-IL9432 17
(4) At the time of external fault
At the time of external fault, the relay does not operate, because no differential current is produced if
Ct error is negligible. Moreover, even if CT saturation may arise due to a heavy external fault, the
relay does not make any unwanted operation owing to the ratio differential characteristics.
(5) At the time of exciting inrush
In the exciting inrush current, a large quantity of 2nd harmonic component is included but in the
internal fault current it is not so much included as shown on the below table. This difference is utilized
and 2nd harmonic blocking principle is adopted for this relay so that unwanted operation due to the
transformer inrush is prevented. Once the 2nd harmonic component is detected at the operation
status of the biased differential element, the operation indication LED (yellow) comes on.
When 2nd harmonic component includes more than the setting value of 2nd blocking ratio, it operates
and prevents the operation of biased differential element. So the unwanted operation caused by
exciting inrush current can be prevented. There are two methods to lock the biased differential
element by the operation of the 2nd harmonic blocking element; one is the All Phase OR Lock method
(Once inrush is detected in any phase, all phases will be locked) and the other is the Segregated
Phase Lock method (only the detected phase is locked). The two methods are switched automatically
according to the following conditions:
a. The biased differential element is operating
b. The load terminal current* is nearly equal to 0
* I, or I2 whichever smaller
Only in the case when above two conditions are met, the All Phase OR Lock method is adopted.
Otherwise, the Segregated Phase Lock method is adopted. So it is possible to prevent the unwanted
operation caused by exciting inrush current when power is switched on.
Trip command
Biased differential element
C phase
2nd harmonic bloking
Load terminal current Is0
A phase
And gate
OR gate 2nd harmonic bloking
Biased differential element
Load terminal current Is0
Differential overcurrent element
Load terminal current Is0
Biased differential element
B phase
2nd harmonic bloking
Differential overcurrent element
Differential overcurrent element
And gate
2f segregated phase Lock
2f all phase OR Lock
And gate
And gate
OR gate
And gate
And gate
OR gate
2f all phase OR Lock
2f all phase OR Lock
Figure4.3 Load terminal current Is1/2setting value of biased differential element
JEP0-IL9432 18
Harmonic component ratio to fundamental component (%) Exciting inrush current Internal fault current
1st cycle 2nd cycle 8th cycle No CT saturation CTsaturation DC component 58 58 58 38 0 Fundamental component 100 100 100 100 100
2nd harmonic component 62 63 65 9 4
3rd harmonic component 25 28 30 4 32
4th harmonic component 4 5 7 7 9
5th harmonic component 2 3 3 4 2
JEP0-IL9432 19
4.1.2 General functions
(1) Operation indication
When operating signals come out for the biased differential element and differential overcurrent
element, the corresponding operation indicator LED will come on instantaneously.
For the 2nd harmonic blocking element, when the 2nd harmonic component ratio of input current
becomes more than the operation setting, the corresponding operation indicator LED will blink.
The operation indicator LED has been set to self-hold in the factory. This setting can be freely
changed to auto reset.
With the self-hold setting, data of the latest operation indication will be stored in the internal memory
even if the auxiliary power supply runs down.
The data stored will be cleared when the indicator reset switch is pressed.
Up to latest five phenomena can be stored and displayed as a history record. (Older data than the
latest five phenomena will automatically be cleared). Item No. History Sequence of recording
311 1st phenomena 312 2nd phenomena 313 3rd phenomena 314 4th phenomena 315 5th phenomena
Latest fault record data
Oldest fault record data
(2) Output contacts
The signaling outputs X0 to X3 and trip outputs X4 and X5 are all programmable type.
The factory default setting of the arrangement of these outputs is as shown in the internal function
block diagram of Figure 5.2. This setting can be freely changed by specifying outputs of the internal
elements based on the OR logic.
All the output contacts have been set to auto reset in the factory. Any of them can be changed to
self-hold.
X0
X5
X3
X4
I >>
I >
I >>
I > Signaling
(4 circuits)
Trip (2 circuits)
Set output logic as desired by using
OR logic.
Figure 4.4 Schematic image of Programmable Outputs (example: COC4-A01D1)
(3) Forced operation
It is possible to carry out forced operation of any of the signaling outputs X0 to X3 and trip outputs X4
and X5 independently. Forced operation is useful for checking the wiring.
When forced operation is carried out, the corresponding LED lamps will come on to show the current
status of the programmable outputs. Checking the lamp status will be useful not only for the wiring
check but also to check the programmable outputs arrangement.
JEP0-IL9432 20
4.2 Setting
87T
1000/5A CT
300/5A CT
Example of transformer circuit for setting calculation
In order to set the relay correctly, please carry out the setting calculation as shown below and set the relay
according to the calculation results.
4.2.1 Setting of CT ratio matching tap
(1) Required data for calculation
a. Rated capacity of the protected transformer
b. Rated voltage of transformer (High voltage side: VH, Low voltage side: VL)
c. Transformation ratio of CT
d. Exciting characteristic of CT (It is not always required)
e. One way conductor resistance of CT secondary (Including CT winding resistance) (RL: value at
25C) f. Connecting method of CT secondary
(2) Meanings of various symbols
a. IP = CT primary current at rated output of transformer
b. IS = CT secondary current at rated output of transformer
c. IR = Relay input current at rated output of transformer
IRH: High voltage side, IRL: Low voltage side
d. ITH = IT1 = CT matching tap value (High voltage side)
ITL = IT2= CT matching tap value (Low voltage side)
f. ZT = CT secondary total burden
(3) Calculation method
a. Selection method of CT ratio
Select the CT ratio according to the following concepts.
- CT secondary current at the transformer rated capacity is less than 2 times rated current of relay
(In).
-To keep the sensitivity, CT secondary current is more than 2.2A (when In = 5A) or more
than0.44A (when In = 1A)
(Because minimum matching tap is 2.2A and 0.44A.)
JEP0-IL9432 21
b. Calculation of mismatch ratio
% mismatch = 100 [(IRH/IRL)-(ITH/ITL)]/S
In this equation, S shows the smaller value of IRH/IRL and ITH/ITL.
In the case of transformer with tap changer, perform the setting basing on the rated value at the
midpoint of the tap changer. Then, the mismatch of tap changer must be added into the above
mismatch.
Thus, select the appropriate CT matching tap so that the calculated mismatch ratio is not more
than 15%.
c. Examination of CT operation characteristics
For the calculation of CT error, it is required to obtain a total burden including CT winding
resistance. Total burden ZT can be determined by the following equation.
ZT = CT secondary resistance + relay burden
= 1.13 RL + relay burden (In the case of -CT)
In the case of -CT, ZT becomes 3 times of the above value. And the above coefficient 1.13 is
used to add the increased resistance of RL due to the temperature rise during the fault continuity.
The CT ratio error (% for secondary current) at the external fault is calculated by the CT exciting
current presumed from the CT exciting characteristic using the total burden voltage calculated by
the total burden and the fault current,
It is the proper condition that the sum of The CT ratio error and the mismatch ratio (%) does not
exceed the bias setting value of the relay (20%, 30%, 40%) throughout the external fault
condition,
(4) Calculation example
Data
Transformer rating
High voltage side: 7500kVA 22kV
Low voltage side: 7500kVA 6.6kV
Calculation
Calculate according to the following procedure.
High voltage side Low voltage side
a. IP A 196.8= 3kV 22
kVA 7500 A 656.1
3kV 6.6 kVA 7500
=
JEP0-IL9432 22
b. Set the CT ratio 60=A5300 200=A51000
c. IR A 5.68=3 60
A 8.196 =IRH A 3.28=
200 A 1.656
=IRL
d. IT A 68.5=I=I RHTH A 28.3=I=I RLTL
The relay will be set at the nearest value to the above calculation results based on the setting
step.
A 7.5=I=I TH1T A 3.3=I=I TL2T
Note
When the calculated IT1 or IT2 are outside the CT matching setting range (2.212.5A), calculate the
setting value again after changing the relay rated current (In) to a value which is possible to set.
For instance, if a calculation result IRH was less than 2.2A (for example IRH=2A), it becomes
impossible to set the relay.
In this case, the calculation should be done again like the following.
Let
A 2.2=ITH
Then
A 3.63= A 2 A 2.2
A 3.3=ITL
The relay will be set at the nearest value to the above calculation results based on the setting step.
A 2.2=I=I TH1T A 6.3=I=I TL2T
e. Calculation of
mismatch ratio
( ) ( ) % 0.58=
1.72 1.72-1.73
= S
II-II =ratio Mismatch
72.1= 3.3 7.5
= I I
73.1= 28.3 68.5
= I I
TLTHRLRH
TL
TH
RL
RH
JEP0-IL9432 23
4.2.2 Setting of minimum operation value Minop
(1) Required data for calculation
a. Transformer tap changing error
b. CT error at normal condition (Ratio error, phase angle error)
c. Relay operation value error
d. Mismatch error
(2) Calculation example Data
a. Transformer tap changing error
Max.10%
b. CT error at normal condition (in case of class 1.0)
Ratio error2One degree phase angle error2 (0.01)2SIN(1)2
0.02
2% c. Relay operation value error
Operation value 10%
d. Mismatch error
0.58%
Calculation Sum of the above error (a to d) is the differential error at normal condition (% to CT matching tap value).
more) or times 2~1.5 :allowance of standard The (
(times) 1.93= 15.58%
30% =allowance the y,Accordingl
15.58%= 30%=op Min. Assume,
op.Min1.0+12.58%= %58.0+op.Min1.0+%2+%0.10=
JEP0-IL9432 24
4.2.3 Setting of bias ratio
Data
a. Transformer tap changing error 10% at external fault (in the case of transformer with tap changer)
b. CT error Max. 10% at external fault
c. Relay bias ratio error Bias ratio 5%
d. Mismatch error 0.58%
Calculation
Sum of the above error (a to d) is the differential error at external fault (% to through fault current).
4.2.4 Setting of differential overcurrent element
It is recommended to set the differential overcurrent element with a value more than the exciting
inrush current.
IT Setting value of operation current of differential overcurrent element > Exciting inrush current
more)or times2~1.5 :allowance of standard The (
(times) 1.56 25.58%
40%allowamce they,Accordingl
40% Assume, 25.58%
0.58%%510%10%
==
= =
+++=
JEP0-IL9432 25
4.3 Measurement
Currents input to the relay are measured and converted into freely set CT primary currents, then indicated
on the display.
(1) Real time measurement
The effective current (Restraining current and differential current) inputting into the relay under steady
state is displayed for each phase.
Please confirm there is no differential current larger than the assumption.
(2) Max. record
The maximum effective current is recorded and stored for each phase.
The max. record will be all cleared when aux. power supply OFF or max. record reset operation is
made.
(3) Fault record
In the event of system fault, the effective current, 2nd harmonic component ratio and waveform data
that have been measured at the time when one of the protection elements operates to issue an
output signal are stored. Data of up to five phenomena can be stored and displayed for each phase.
With aux. power supply OFF, only the wave form data will be cleared and the effective current data
will remain. With fault record reset operation, however, both of the data items will be all cleared.
(Records older than the 5th phenomenon will automatically be cleared.) Item No. History Sequence of recording
211 1st phenomena 212 2nd phenomena 213 3rd phenomena 214 4th phenomena 215 5th phenomena
Latest fault record data
Oldest fault record data
The following fault waveform data can be collected if a communication card is installed:
The peak value of waveform data is n derived from CT secondary current with matching tap conversion. Item Specification
Data sampling cycle Fixed to the electric angle of 30 of rated frequency Data storing capacity (for a phenomenon)
224 cycles of rated frequency (Data point: 224360/30 = 2688 points)
Permissible setting range 224 cycles before trip ~ 224 cycles after trip
Collected data The range for data collection can be set by cycle within the data storing capacity in the permissible set range.
224 cycles after trip224 cycles before trip
Collected data Up to 224 cycles
Data sampling cycle
Trip occurs!
Output contact ON
OFF
Permissible set range
Figure 4.5 Recording concept of fault waveform
JEP0-IL9432 26
4.4 Self-diagnosis
The self-diagnosis function monitors the electronic circuit and built-in power source continuously. If an
abnormal condition occurs, the protection elements will be locked for operation. Also, the RUN LED lamp
will go off and self-diagnosis output contact (break contact) will be closed.
(1) Checking the defect code at failure detection
When a failure is detected, the defect code will be recorded. This defect code can be checked
through self-diagnosis (ALARM) status indication .
(2) Resetting self-diagnosis output
If a failure is detected, the failure status may be reset by turning off/on the power.
In this case, be sure to lock the trip circuit on the external wiring of the relay before resetting.
(If the failure persists, an erroneous output may be caused.)
(3) Clearing the defect code
The defect code data stored at failure detection can not be cleared only by carrying out the power
on/off procedure in the item (2) above. All the defect code numbers that have been detected since
the previous self-diagnosis reset (RESET ALARM) operation was made are accumulated in the
memory.
To clear the record data, carry out self-diagnosis reset (RESET ALARM)operation.
(4) Differential current check (Defect code 0017)
The followings are the explanation of the differential current check.
This check item monitors the differential current calculated inside of the relay and issue the alarm
when the differential current is more than 80% of minimum operating value (Inoperating current
setting (20%~40%) and such condition is continued more than 20 seconds.
The differential current check monitoring is effective to prevent the relay from miss operation due to
the defects of parts caused by aging.
Therefore, differential current alarm will be issued with the following cases.
In case of one side current injection test, defect code 0017 will be issued when injection period is
more than 20 seconds.
To prevent such a detection, setting item [DIF test] should be set as [ON[ position during the test.
DIF test LED(yellow) will come on when DIF test set as [ON] and please pay attention that never
forget to change the DIF test setting from [ON] to [OFF] after completion of the test and confirm
the LED coming off.
Occurrence of differential current due to miss setting of matching taps.
Occurrence of differential current due to wrong connection of cables located outside of relay.
JEP0-IL9432 27
Table 4.1 Output for protection relay failures
Output Display Status Detected items
RUN Defect code
ALARM (break
contact)
Operation output lock
Normal - On Open Not locked Power circuit
failure - Locked
CPU stop -
No display
45 ROM check 0001 RAM check 0002 A/D accuracy check 0003 A/I check 0004 A/D check 0005 SRAM check 0006 D/O status check 0008 D/O operation check 0009 Analog filter check 0010 A/I double check 0011 D/I check *41 0012 E2PROM check 0013 Computing function check 0014 WDT check 0015 Data transfer check *42 0016 Differential current check *43
Off
0017
Closed
Locked
Communication card check *44 0028 Communication card channel No. switch setting error *44 0029 Communication card baud rate switch setting error *44 0030 Communication card channel No. switch change error *44 0031
Monitor error
Communication card baud rate switch change error *44
On
0032
Open Not locked
*41 Monitored only in the models with built-in D/I function. *42 Monitored only in the models with D2 unit. *43 Monitored only the biased differential relay. *44 Monitored only when communication card is installed inside the relay. *45 No necessary to lock the output as any output would not be possible during CPU stop.
JEP0-IL9432 28
4.5 Communication (option) Figure 4.6 shows an example of network system configuration.
For more information on the communication facilities, see the materials shown in the introduction (page 2).
Figure 4.6 Example of communication network system configuration
Central Control System
The network system enables the central control system to fully access to the protection relays, and achieve remote monitoring of the measurement values, operational status etc as well as remote operation such as change of settings. Thereby efficient operation and maintenance are realized.
- CC-Link RTU
Remote Operation and Monitoring
By connecting PC with relay via the RS232C port located on the relay panel, local operation and monitoring are enabled as same as the remote operation and monitoring. Thereby the maintenance work at site is strongly supported.
RS232C
Local Operation and Monitoring for Site Maintenance
- Measurement value - Relay settings - Relay operation status - Fault Record - Monitoring status - Time
- Measurement setting - Relay setting - Time Adjustment
Remote Operation Remote Monitoring
Local Operation Local Monitoring
JEP0-IL9432 29
By connecting PC with relay via the direct communication port (as standard equipment located on the relay front
panel, local operation and monitoring are enabled as same as the remote operation and monitoring.
Please note that optional HMI software for PC is needed for local operation and monitoring.
Using the communication facilitates, it is possible to perform Remote Monitoring and Remote Operation with
the various useful functions shown in Table 4.2.
Table 4.2 Outline of functions enabled by communication network
Direction of communication Item Description
Setting Read the settings stored in the protection relay. Measurement Read the measurements stored in the protection relay. Max. value Read the max. values stored in the protection relay. Fault record Read the measurements at the time of trip. Self- diagnosis (ALARM) Read the result of self-diagnosis. Operation element Read the elements that operated at the time of trip. Operation time Read the time at the time of trip. Current time Read the internal time of the communication card.
Remote Monitoring
RTU Protection relay
Wave form record Read the wave form at the time of trip. Setting Change the setting of the protection relay. Indicator reset Reset the LED lamp that came on at the time of trip. Self-diagnosis reset (RESET ALARM)
Clear the result of self-diagnosis
Fault record reset Clear the fault record, operation elements and operation time data.
Max. record reset Clear the max. records. Forced operation Carry out forced operation of output contact.
Remote Operation
RTU Protection
relay Time Set time of communicate card.
JEP0-IL9432 30
5 Configuration 5.1 Internal configuration
(1) I/O and CPU circuits
Fig. 5.1 shows the internal block diagram of the model CAC1-A01D2.
Current input is converted into AC signals at the electronic circuit level via the auxiliary transformer
and filter circuits. These signals are retained as a form of DC signal in the sample hold circuit on each
channel sharing a same time. The multiplexer selects a channel to take the signal and send it to an
A/D converter. The signals are converted to digital signals sequentially in the converter to be sent to
the CPU.
The setting circuit is used to input setting data into the CPU.
These inputs will be used to carry out the functions shown in Fig. 5.2 Internal function block diagram,
then issue output signals to the display and output relay.
(2) Self-diagnosis circuit
When the self-diagnosis function detects that the electronic and power circuits are normal, the output
relay will be energized to open the self-diagnosis output contact (break contact).
The self-diagnosis output contact (break contact) will be closed when a failure occurs in the circuits
above or when the built-in power fuse burns.
3 1
J E P 0 - I L 9 4 3 2
M P
X
Setting switches
A/D
C P
U
Numerical display
A-phase biased diff. ind. A-17
IA1
A-18
S/H Filter
For trip X5
X4
2f blocking (A,B,C phase) X3
C-phase biased diff./diff. O.CX2
B-phase biased diff./diff. O.CX1
A-phase biased diff./diff. O.CX0
Communication indicator
Unit indicator
Trip operation indicator
C-phase 2f blocking ind.
C-phase diff. overcurrent
C-phase biased diff. ind.
B-phase 2f blocking ind.
B-phase diff. overcurrent
B-phase biased diff. ind.
A-phase 2f blocking ind.
Power circuit monitor
A-01 AC/DC DC/DC Power source
Auxiliary power supply
A-03
+
Y
X5 B-19
B-20
X4 B-17
B-18 Trip
Programmable output
B-11
B-12
X2
B-13
B-14
X3
Biased diff. /diff. O.C
A-phase
Biased diff. /diff. O.C
B-phase
Biased diff. /diff. O.C
C-phase
2f blocking A,B,C phase
Signaling
Self-diagnosis output Y
Self-diagnosis output B-05
B-06
Serial communication bus
DAB-01
DBB-02
DGB-03
SLDB-04E A-02
RUN indicator
Self-diagnosis (Excluding comm. card)
Communication card
Self-diagnosis (only comm. card)
Reception circuit
Transmission circuit
A-19
IB1
A-20
S/H Filter
A-21
IC1
A-22
S/H Filter
A-11
IA2
A-12
S/H Filter
+
A-13
IB2
A-14
S/H Filter
A-15
IC2
A-16
S/H Filter
P rim
ar y
w in
di ng
s S
ec on
da ry
w in
di ng
s
A-phase diff. overcurrent
X B-07
B-08
X1 B-09
B-10
Figure 5.1 Internal block diagram of Type CAC1-A01D2 relay
3 2
J E P 0 - I L 9 4 3 2
A-phase biased diff. ind.
B-phase 2f blocking ind.
A-phase 2f blocking ind.
Power circuit monitor
Self-diagnosis (Excluding comm.card)
A-01
A-03
+
A-phase diff. overcurrent
B-phase biased diff. ind.
C-phase diff. overcurrent
B-phase diff. overcurrent
C-phase biased diff. ind.
Trip operation indicator
B-phase biased diff./diff. O.CX1
A-phase biased diff./diff. O.CX0
C-phase biased diff./diff. O.CX2
2f blocking (A,B,C phase) X3
For trip X4
Self-diagnosis output Y
B-05
B-06
Y
X5 B-19
B-20
X4 B-17
B-18
X3 B-13
B-14
X2 B-11
B-12
X1 B-09
B-10
X0 B-07
B-08
A-17
IA1
A-18
DAB-01
DBB-02
DGB-03
SLDB-04E A-02
RUN indicator
Communication indicator
A-13
IB2
A-14
A-19
IB1
A-20
A-21
IC1
A-22 A-11
IA2
A-12
A-15
IC2
A-16
S ec
on da
ry w
in di
ng s
Pr im
ar y
w in
di ng
s
Biased differential
A-phase
B-phase
C-phase
C-phase 2f blocking ind. Biased differential
Differential overcurrent
2f blocking ratio
2f blocking ratio
Differential overcurrent
Biased differential
Auxiliary power supply
AC/DC DC/DC Power source
Programmable output X5
Communication card
Self-diagnosis(only comm. card)
Reception circuit
Transmission circuit Serial communication bus
Programmable output
Trip
Signaling
Biased diff. /diff. O.C
A-phase
Biased diff. /diff. O.C
B-phase
Biased diff. /diff. O.C
C-phase
2f blocking A,B,C phase
Self-diagnosis output 2f blocking ratio
Differential overcurrent
Figure 5.2 Internal function block diagram of type CAC1-A01D2
JEP0-IL9432 33
5.2 External connection
(1) Connection diagram
Figures 5.4 to 5.7 show examples of input circuit (AC circuit) connection, Figure 5.8 shows an
example of control circuit (DC circuit) connection and Figure 5.9 shows the terminal arrangement.
In the terminals, M3.5 screws should be used and wires of 2 mm2 or less are recommended using.
(2) Precautions for wiring work
a. Important facilities should be provided with the redundant system such as the fail-safe system, the
dual system or the 2 out of 3 system to improve reliability of the facilities.
b. Effects of external surge
Some type of surge with a certain condition may inversely affect the relay. If so, take it into account
to install MF type surge absorbers made by Mitsubishi Electric .
c. Guarantee of AC auxiliary power supply against power interruption
The AC auxiliary supply of the relay is not guaranteed against power interruption. When you do not
have an uninterruptible AC power source, use the type B-T1 backup power supply manufactured by
Mitsubishi Electric or uninterruptible power source (UPS) that is commercially available.
d. Inrush current of auxiliary supply
Since inrush current may flow in the relay when the auxiliary power supply is turned on as shown in
the figure below, make consideration of this point when selecting the breaker for auxiliary power
supply circuit.
Input voltage Inrush current Ip
110V Approx. 20ADC 220V Approx. 55A 100V Approx. 25A
AC 220V Approx. 65A
Figure 5.3 Inrush current of auxiliary power supply
e. Trip circuit
Only the contacts X4 and X5 can be used for the trip circuit. Please keep in mind that the contacts X0
to X3 cannot be used for the trip circuit. (If used, the contact may burn).
Connect the pallet contact (52a) of the circuit breaker to the trip circuit.
f. Self-diagnosis output circuit
The self-diagnosis output contact is so configured that the auxiliary relay can be energized (break
contact) with normal result of monitoring, in order to be able to continue monitoring even if the
built-in power fuse burns. Therefore, connect the timer to the external wiring. (See Fig. 5.8 DC
circuit connection diagram).
g. Earth circuit
Be sure to earth the earth terminal located on the back of the relay according to the Class D earth
wiring method.
Inrush current
Ip
Approx. 2ms
Inputting
Input voltage
Input current
0V
0A
JEP0-IL9432 34
Self-diagnosis output
Trip
E
DA DB
SLD
DG
B-06
B-05
B-07
B-08
B-09
B-10
B-11
B-12
B-13
B-14
B-17
B-18
B-19
B-20
B-01
B-02
B-03
B-04 A-02 option
Auxiliary power Supply
A-01
A-03
A-17
A-18
A-19
A-20
A B C Y
X0
X1
X3
X4
X5
X2
Programmable output
Signaling
Biased differential Differentia overcurrent A phase
A-21
A-22
C
A
B A
B
A-11
A-12
A-13
A-14
A-15
A-16
IA
IB
IC
IA
IB
IC
k
k
l
l
(ED)(ED)
(ED)
CT1
CT2
K
L
K
L
Transfotmer - (Dd0)
IA IB IC 2f blocking (ABC phase)
Biased differential Differentia overcurrent A phase or B phase or C phase
IA IB IC
Dd0
IA IB IC
C HV side
LV side C om
m . c
ar d
Biased differential Differentia overcurrent B phase
Biased differential Differentia overcurrent C phase
Serial communication bus Dont input the withstand voltage for test
CT secondary circuit should be connected so as HV side current to be inflow to the Ry terminal of HV side and LV side current to be out flow from the Ry terminal of LVside with keeping same phase angle between bothside, when flow through current is placed.
Figure 5.4 External connection diagram (AC circuit) for CAC1-A01D2 relay
[Example 1]
JEP0-IL9432 35
A B C
A
B C
A
B
C
A-17 A-18 A-19 A-20 A-21 A-22
A-11 A-12 A-13 A-14 A-15 A-16
IA2 IB2 IC2
IA1 IB1 IC1
IA IB IC
IA-B IB-C IC-A
IA-B IB-C IC-A
CAC1-A01D2 Yd11
IA IB IC
IA-B IB-C IC-A
IA-B IB-C IC-A
IA
IB
IC
HV side
LV side
CT secondary circuit should be connected so as HV side current to be inflow to the Ry terminal of HV side and LV side current to be out flow from the Ry terminal of LVside with keeping same phase angle between bothside, when flow through current is placed. Refer to the Figure 5.4 on the out circuit.
Figure 5.5 External connection diagram (AC circuit) for CAC1-A01D2 relay
[Example 2]
JEP0-IL9432 36
A B C
A
B C
A
B
C
A-17 A-18 A-19 A-20 A-21 A-22
A-11 A-12 A-13 A-14 A-15 A-16
IA2 IB2 IC2
IA1 IB1 IC1
IA IB IC
IA-C IB-A IC-B
IA-C IB-A IC-B
CAC1-A01D2 Yd1
IA IB IC
IA-C IB-A IC-B
IA-C IB-A IC-B
IA
IB
IC
HV side
LV side
CT secondary circuit should be connected so as HV side current to be inflow to the Ry terminal of HV side and LV side current to be out flow from the Ry terminal of LVside with keeping same phase angle between bothside, when flow through current is placed. Refer to the Figure 5.4 on the out circuit.
Figure 5.6 External connection diagram (AC circuit) for CAC1-A01D2 relay
[Example 3]
JEP0-IL9432 37
A B C
A
B C
A
B
C A-17 A-18 A-19 A-20 A-21 A-22
A-11 A-12 A-13 A-14 A-15 A-16
IA2 IB2 IC2
IA1 IB1 IC1
IA IB IC
IA-C IB-A IC-B
IA-C IB-A IC-B
IC-B IB-AIA-C
CAC1-A01D2
Dy11
IA IB IC
IA-C IB-A IC-B IC
IB
IA HV side
LV side
CT secondary circuit should be connected so as HV side current to be inflow to the Ry terminal of HV side and LV side current to be out flow from the Ry terminal of LVside with keeping same phase angle between bothside, when flow through current is placed. Refer to the Figure 5.4 on the out circuit.
Figure 5.7 External connection diagram (AC circuit) for CAC1-A01D2 relay
[Example 4]
JEP0-IL9432 38
A B C
A
B C
A
B
C
A-17 A-18 A-19 A-20 A-21 A-22
A-11 A-12 A-13 A-14 A-15 A-16
IA2 IB2 IC2
IA1 IB1 IC1
IA IB IC
IA-B IB-C IC-A
IA-B IB-C IC-A
IC-A IB-CIA-B
CAC1-A01D2
Dy1
IA IB IC
IA-B IB-C IC-A
IA
IB
IC
HV side
LV side
CT secondary circuit should be connected so as HV side current to be inflow to the Ry terminal of HV side and LV side current to be out flow from the Ry terminal of LVside with keeping same phase angle between bothside, when flow through current is placed. Refer to the Figure 5.4 on the out circuit.
Figure 5.8 External connection diagram (AC circuit) for CAC1-A01D2 relay
[Example 5]
3 9
J E P 0 - I L 9 4 3 2
Self-diagnosis output
DB
SLD
DG
B-02
B-03
B-04
Serial communication bus
E A-02
+ Auxiliary power supply
A-01
A-03
Programmable output
Signaling
B-T1 type back up power supply
or
UPS()
52a
100VDC ~ 220VDC 100VAC ~ 220VAC()
TC
To master station (when communication card installed)
Note 1) The self-diagnosis output contact is so configured as below mentioned that alarm can be issued even after the built-in power fuse burns. This type of auxiliary relay circuit configured such that relay will be energized (break contact opened) when normal result of self-diagnosis is received. Therefore, the break contact is closed when the power is applied and will be opened after about 50ms. If the auxiliary power supply of the relay and the self-diagnosis output contact shares a same power source, the break contact will be closed temporarily after the auxiliary power supply is turned on. In the case where the phenomenon stated in the above would conflict with your system requirement, it is recommended that the self-diagnosis output contact should be connected via the time-delayed timer as shown in the left of the figure.
Note 2) Regarding to the type B-T1 back up power supply or commercially available uninterruptible power supply (UPS), refer to the note *21 in the section 2.1 General information.
N
Trip
DA
B-06
B-05
B-07
B-08
B-09
B-10
B-11
B-12 B-13
B-14
B-17
B-18 B-19
B-20
B-01
Earth fault instantaneous
I >>
Phase fault time-delayed
I>
Earth fault time-delayed
I > Phase fault
instantaneous I>>
Y
X0
X1
X3
X4
X5
X2
To control system (alarm and other signals)
Time-delayed operation contact
(make contact Approx. 1s)
TL
P
() Refer to the page 33, 5.2 External connection (2) Precautions for wiring work c. Guarantee of AC auxiliary power supply against power interruption.
Figure 5.9 Auxiliary power supply circuit connection example of type CAC1-A01D2 relay
JEP0-IL9432 40
02
04
06
08
10
12
14
16
18
20
01
03
05
07
09
11
13
15
17
19
Auxiliary
power supply +
Earth circuit
ED
02
04
06
08
10
12
01
03
05
07
09
11
14
16
18
20
22
13
15
17
19
21
62-M3.5 screws
02
04
06
08
10
12
14
16
18
20
01
03
05
07
09
11
13
15
17
19
Figure 5.10 Rear view of type CAC1-A01D2 relay
JEP0-IL9432 41
6 Handling 6.1 Unpacking
Usually this relay is packed in a D2 case for transportation. However, it may occur that only the sub unit is
transported independently for the convenience at repair. In such a case, fully brush off the dust, dirt, etc.
adhered to the sub unit after completion of unpacking, and further visually check that the parts mounted
on the front panel or built in the sub unit are not damaged.
6.2 Transportation and storage
To carry the equipment within the place of use, handle it carefully so that the parts installed on the front
panel of the sub unit or built-in parts cannot be deformed or broken.
6.3 Appearance and how to pull sub unit out
The relay is so constructed that the sub unit can be drawn out, in order to facilitate inspection or test. It is
possible to pull the sub unit out without disconnecting the external wiring.
Note that the sub unit should not be drawn out with the line hot. Before drawing out, be sure to take the
following actions.
- Lock the tripping circuit including breakers.
- Stop the main circuit.
- Shorten and isolate the CT circuit.
- Open the auxiliary power supply circuit.
Bear in mind that careless opening of circuits may result in opening the other control circuits too to impair
the protective function. Be sure to only shut off the concerned circuit.
The CT circuit is provided with an automatic short circuit mechanism. In case that you have pulled the sub
unit out without isolating the CT circuit by mistake, the automatic short circuit mechanism will work to
prevent the CT secondary circuit from opening.
Lock levers
Case
Sub unit
Cover
Draw-out handles
Communication card
Cover operating buttons Draw-out auxiliary levers
Temporary stopper
Option
Figure 6.1 Outside view of type CAC1-A01D2 relay
JEP0-IL9432 42
6.3.1 How to draw sub unit out
(1) Removing the cover
Hold the lock levers, which are located at both sides of the cover, on their front sections. Take off the cover straight toward you while pushing the levers inwards.
(2) Drawing the sub unit
Please from under to upper direction turn round the draw-out auxiliary levers located on both sides of the front of the sub unit until the levers touch the metallic parts located on both sides of draw-out handles completely. (Rotated angle is approx. 120) Note) Be careful not to put your fingers into the
space between drawing-out auxiliary levers and the case.
With the draw-out auxiliary levers touching the metallic parts, exert your strength to turn round the levers continuously, the sub unit will be drawn out a little from the case. Then be careful not to let the draw-out auxiliary levers fall down and to make the draw-out auxiliary levers into a locked status by the with-holders located on the both sides upper the auxiliary levers please. (Rotated angle is from approx. 120to 180) Note) Be careful not to put your fingers into the
space between drawing-out auxiliary levers and the case.
JEP0-IL9432 43
Grip the draw-out handles (located at both sides of the front of the sub unit), and pull the sub unit towards you until about a half portion of the sub unit is pulled out of the case. Note) Be careful not to pull out the sub unit too
much in order to prevent the sub unit falling.
When about a half portion of the sub unit is pulled out of the case, just stop the drawing motion. Then, hold the top and bottom of the sub unit to pull it out completely, in order to prevent the unit from falling. Note) Be careful not to touch the printed circuit
board and parts inside the sub unit.
JEP0-IL9432 44
6.3.2 Housing the sub unit
(1) Housing the sub unit
Hold the sub unit on the top and bottom to push the unit into the case approx. a half of the unit. Note) - Be careful not to touch the PCB and parts inside
the sub unit. - The sub unit is so constructed that it can not be
housed in the case upside down.
Under holding the auxiliary levers locked status by the with-holder (not to let the draw-out auxiliary levers fall down), Insert the sub unit into the case until the auxiliary levers touch the metallic parts while pressing the handles located on both sides of the front of the sub unit.
More fully insert the sub unit into the case until the auxiliary levers fall down automatically and catch the metal holes inside with its hooks. (Rotating angle is from 180 to approx. 45) Note) If the auxiliary levers are not available to
complement the wanted operation automatically, operate the auxiliary levers and make it achieve the above status please.
At this time be also careful that do not injure your fingers.
JEP0-IL9432 45
Exert your strength to press the lower parts of the auxiliary levers to fully insert the sub unit into the case until you hear a click. (Rotated angle is from 45 to approx. 0) Note) Please note that inserting the sub-unit
incompletely may only establish a poor contact of the terminals located on the back of the unit, which may cause operational failure or heating.
(2) Attaching the cover
Fit the cover straight to the case. Hold the cover frame to fully push the lock levers, located both side of the cover, to case side until it is clicked and locked. Note) After setting the cover, check if the buttons
can be smoothly pressed from over the cover.
JEP0-IL9432 46
6.4 How to use front control panel
6.4.1 Front control panel layout
C -P HA
SE
B -P HA
SE
5 D
o w
n s
w it c h
6 In
di ca
tio n/
In d. E
nd s
w itc
h
7 O
pe ra
ti on
in di
ca to
r R es
et
ST YL
E
AU X.
V
JE J2
95 15
H0 1
BI AS
ED D
IF FE
RE NT
IA L R
EL AY
OP ER
AT IO
N IN
DI CA
TO R
TR IP
SE T.E
ND SE T
SE LE
CT
CA NC
EL
SE TT
ING
IT EM
D AT
A
YE AR
-D
SE RI
AL
RA TIN
G
C A
C 1-
A 01
D 2
EN D
IN D.
IN
D.
DO W
N
UP
A -P HA
SE
A CO MM
.
RU N
%
DI F-
TE ST
Id >
-C
2f B-
C 2f
B- B
2f B-
A
Id >
-B
Id >
-A
RE SE
T
Id/ I>
-C
TR IP
Id/ I>
-A
Id/ I>
-B
1 S
e tt
in g/
C an
c e l sw
it c h
8 I te
m N
o . in
di c at
o r
L E D
14 S
et ti ng
/C an
ce l i
nd ic
at or
3 S et
ti ng
e nd
/T ri p
sw it ch
15 S
et ti ng
e nd
/T ri p
in di
ca to
r
1 6 O
pe ra
ti o n i n d ic
at o rs
2 S
e le
c t/
S e t
sw it c h
R
S- 23
2C
PC
TM
IT EM
N o.
M E
LP R
O
1 2 U
n it L
E D
1 3 P
h as
e L
E D
9 I te
m d
at a
L E D
10 R U N L E D
11 C o m m u n i c a t i o n L E D
ST AT
US
AL AR
M
OP .-E
LE ME
NT
ME AS
UR EM
EN T
I R ES
(M AX
.-R EC
) I D
IF (R
EA L.-
TIM E)
2f / 1
f (R EA
L-T IM
E)
I R ES
(R EA
L-T IM
E)
I D IF
(M AX
.-R EC
.)
I R ES
(F AU
LT -R
EC .)
I D IF
(F AU
LT -R
EC .)
2f / 1f
(FA UL
T-R EC
.)
CT -M
AC TC
H.- PR
I.(A )
CT -M
AC TC
H.- SE
C.( A)
CU RR
EN T(
MU L.)
SE TT
IN G
Id / I
[D IF
]
CU RR
EN T(
% )
BI AS
(% )
DI F-
TE ST
2fB
LO CK
[2f B]
2fB
R AT
E( %
) Id
> [H
OC ]
CT - P
OL AR
ITY CH
EC K
PA SS
WO RD
ON / O
FF
RE SE
T F AU
LT R
EC .
OP TIO
N
RE SE
T A LA
RM
TE ST
LE D
FO RC
ED OP
ER AT
ION
CO NT
AC T X
5 O P.
CO NT
AC T X
0 O P.
CO NT
. X 0
X5 AR
R.
OP .IN
D. -H
OL D
(R EF
.M AN
UA L)
RE SE
T M AX
. - R EC
(R
EF .M
AN UA
L)
Tu rn
o n
th e
se tti
ng
of th
e ite
m N
o. 51
5 in
th e
te st
in g
17 D
ir ec
t co
m m
un ic
at io
n po
rt
Figure 6.2 Front view of type CAC1-A01D2 relay
JEP0-IL9432 47
Table 6.1 Front control panel guide
No. Designation Symbol Description 1 Setting / Cancel
SETTING/CANCEL
Pressing this switch will start the procedure for setting, forced operation or option. When this switch is pressed again instead of the SET.END/TRIP switch, data that has been programmed
will be all cleared to terminate the selected procedure. The SETTING/CANCEL indicator LED is lit during the procedure.
2 Select / Set
SELECT/SET
This switch is used to select an item number and to program item data during setting, forced operation or option procedure. When data is programmed to be ready for replacing the currently used setting, the SET.END/TRIP LED will blink.
3 Setting End / Trip
SET. END/TRIP
When the SET.END/TRIP switch is pressed with its LED blinking during setting, forced operation or option procedure, the currently enabled setting will be replaced by data given by programming. The new setting will be thus enabled.
4 UP select UP
5 DOWN select DOWN
These switches are used for selecting data elements. Pressing these switches for a while will allow fast forwarding. With the cover operating buttons, you can use the switches without removing the cover.
6 Indication / Indication End
IND./IND.END
Pressing this switch will start or end the display of settings and measurements. With the cover operating button, you can use the switch without removing the cover.
7
O pe
ra tio
na l k
ey s
w itc
he s
Reset
RESET
Pressing this switch will reset output contacts after the relay operated and extinguish the operation indicator LEDs. With the cover operating button, you can use the switch without removing the cover.
8 Item No. Green -
A number allocated to the selected setting, forced operation or option item is indicated here.
9 Item Data Red
-
Data that corresponds to the item number selected is displayed here. For the indication of individual letters, see the Table6.2 manual specifically prepared for each model.
10 RUN Green -
Indicate the result of the automatic self-check. The lamp will be lit for normal results while off for abnormal.
11 Communication Green
-
Indicate the operational status of the communication card. - With a communication card installed: the lamp will be lit
for normal conditions, blinking during communication and off for abnormal conditions.
- With a communication card not installed: the lamp will be off.
12 Unit Yellow - Indicate the unit used for the item data. 13 Phase Yellow - Indicate the phase that corresponds to the item data. 14 Setting / Cancel Yellow
- This lamp will be lit during setting, forced operation or option procedure.
15 Setting End / Trip Yellow -
This lamp will blink when new data is programmed to be ready for replacing the currently enabled setting.
16
In di
ca to
r L E
D s
Operation / Detection / Test
Red Yellow Yellow
-
-
-
Indicate the operation elements and phases. (Trip, Id/I>, Id>) Indicate the detection elements and phases. (2fB) Indicate the test mode when setting.(DIF TEST)
17 Direct communication port
[current editions] - By connecting PC installed dedicated HMI software with relay, local operation and monitoring are enabled.
JEP0-IL9432 48
Table 6.2 Letter representation of item data indicator LEDs
Item Designation Letters
Display in item data box
On ON
Off OFF
Yes YES
No NO
Operation lock LOCK
JEP0-IL9432 49
6.4.2 Operational procedure For more information about the operational procedure shown below, see the MELPRO-D Series General
Operation Manual (JEP0-IL9416). 6.4.2.1 Relay without RS232C communication I/F
Table 6.3 Operational procedure
Item Corresponding section of general operation manual
No. Designation Description Indication mode
Setting/forced operation/option
mode
010 Restraining current (Real time value) Measure and display effective input value of restraining current at real time. A-1
011 Restraining current (Max. records) Display the max. effective restraining current. A-2
020 Differential current (Real time value) Measure and display effective input value of differential current at real time. A-1
021 Differential current (Max. records) Display the max. effective differential current. A-2
030 2f / 1f (Real time) Measure and display effective input value of 2f component ratio at real time. A-1
211 1st phenomena (Restraining current) 212 2nd phenomena (Restraining current) 213 3rd phenomena (Restraining current) 214 4th phenomena (Restraining current)
215 5th phenomena (Restraining current)
Record and display effective value of restraining current for the latest 5 phenomena of relay trip caused by system fault. The 1st phenomena is the latest trip and the 5th is the oldest one.
221 1st phenomena (Differential current) 222 2nd phenomena (Differential current) 223 3rd phenomena (Differential current) 224 4th phenomena (Differential current) 225 5th phenomena (Differential current)
Record and display effective value of differential current for the latest 5 phenomena of relay trip caused by system fault. The 1st phenomena is the latest trip and the 5th is the oldest one.
231 1st phenomena (2f / 1f) 232 2nd phenomena (2f / 1f) 233 3rd phenomena (2f / 1f) 234 4th phenomena (2f / 1f) 235
M ea
su re
m en
t
Fa ul
t r ec
or d
5th phenomena (2f / 1f)
Record and display effective value of 2f component ratio for the latest 5 phenomena of relay trip caused by system fault. The 1st phenomena is the latest trip and the 5th is the oldest one.
A-3
311 1st phenomena 312 2nd phenomena 313 3rd phenomena 314 4th phenomena 315 O
pe ra
tio n
el em
en ts
5th phenomena
Record and display the status of the operation indicator LEDs for up to five latest phenomena of relay trip caused by system fault. The 1st phenomena is the latest trip and the 5th is the oldest one.
A-4
400
S ta
tu s
Self-diagnosis (ALARM) Keep in record and display defect codes in the case where an abnormal condition is detected by the self-diagnosis.
A-6
511 Matching tap primary [A] 512 Matching tap secondary [A] 513 Operation current [%] 514 Bias [%] 515
Biased differential elements
DIF test
521 2f blocking 2f blocking rate [%]
531
S et
tin gs
P ha
se fa
ul t
Differential overcurrent
Operation current [Multiplier]
Set and display settings. A-7 B-1
700 Contact X0 operation 710 Contact X1 operation 720 Contact X2 operation 730 Contact X3 operation 740 Contact X4 operation 750
Fo rc
ed
op er
at io
n
Contact X5 operation
Carry out forced operation of output contacts individually . The setting of programmable outputs can be checked through the operation indicator LEDs.
C-1
800 Contact X0 810 Contact X1 820 Contact X2 830 Contact X3 840
O pt
io n
Contact arrangement
Contact X4
Configure programmable output. Also, set and display self-hold/reset setting of programmable outputs. For the guide for setting, see the section 6.4.2.3 (1) below.
A-7 D-1
JEP0-IL9432 50
850 Contact X5
860 Operation indicator LED hold Set and display self-hold/auto reset setting of the operation indicator LEDs. For the guide for setting, see the section 6.4.2.3 (2) below.
A-7 D-2
901 Reset Max. record Clear the data of the max. records. 902 Reset fault record Clear the data of the fault records. 903 Self-diagnosis reset (REST ALARM) Clear data of the self-diagnosis records.
D-4
904 Test LED lamp Carry out forced illumination of all the LED lamps on the front of the relay unit. D-5
905
O pt
io n
Check CT polarity Check the polarity of connected CT when connecting.
D-8
6.4.2.2 Relay with RS232C communication I/F
Item Corresponding section of general operation manual
No. Designation Description Indication mode
Setting / forced operation /
option mode
As the same as Table 6.3 described in item 6.4.2.1 about the No. 010860.
901 Relay password enable/disable option Set relay password enable or disable for setting. A-7 D-9
902 Max. record reset Clear data of the max. record. 903 Fault record reset Clear data of the fault record. 904 Self-diagnosis reset (RESET ALARM) Clear data of the self- diagnosis record.
D-4
905 LED lamp test Carry out forced illumination of all the LED lamps on the front of the relay unit. D-5
906
O pt
io n
Check CT polarity Check the polarity of connected CT when connecting.
D-8
JEP0-IL9432 51
6.4.2.3 Guide for option function (1) Specifying contact arrangement data of output contacts
The table below shows the setting guide table. See the section D-1 of the general operation manual for the detailed procedure.
Input Digit No. Setting item
0 1 0 Self hold / auto reset upon reset Reset Hold 1 Biased differential A-phase(Note 2) Off On 2 Biased differential B-phase(Note 2) Off On 3 Biased differential C-phase(Note 2) Off On 4 Differential overcurrent A-phase Off On 5 Differential overcurrent B-phase Off On 6 Differential overcurrent C-phase Off On 7 2nd harmonic blocking A-phase(Note 1) Off On 8 2nd harmonic blocking B-phase(Note 1) Off On 9 2nd harmonic blocking C-phase(Note 1) Off On
10 Not used 11 Not used 12 Not used 13 Not used 14 Not used 15
O R
e le
m en
t c om
bi na
tio n
Not used
00000 0
Same as left
Same as left
Contact arrangement data 0
Conversion from binary number to hexadecimal
Binary Hexadecimal Binary Hexadecimal Binary Hexadecimal 0 0 0 0 0 0 1 1 0 6 1 1 0 0 C
0 0 0 1 1 0 1 1 1 7 1 1 0 1 D
0 0 1 0 2 1 0 0 0 8 1 1 1 0 E
0 0 1 1 3 1 0 0 1 9 1 1 1 1 F
0 1 0 0 4 1 0 1 0 A
0 1 0 1 5 1 0 1 1 B
Same as left
When the product is shipped from the factory, contact arrangement data are set as follows.
Contact Item number
Contact arrangement data Setting of the element
X0 800 0012 Biased differential/Differential overcurrent A-phase X1 810 0024 Biased differential/Differential overcurrent B-phase X2 820 0048 Biased differential/Differential overcurrent C-phase X3 830 0380 2nd harmonic blocking A,B,C-phase X4 840 007E Biased differential/Differential overcurrent A,B,C-phase X5 850 007E Biased differential/Differential overcurrent A,B,C-phase
*The Self hold/auto reset setting are Reset (auto reset) for all contacts. (Note 1) If the 2nd harmonic blocking elements (the digit number 7 to 9) are set to ON for a contact arrangement, the contact will make when the 2nd harmonic blocking element operate. Therefore, set to OFF for the trip contact. (Note 2) Biased differential element for each phase has the 2nd harmonic blocking function. (Output of biased differential element for each phase is blocked by the 2nd harmonic blocking element operation signal.
JEP0-IL9432 52
(2) Specifying operation indicator LED hold data The table below shows the setting guide table. See the section D-2 in the general operation
manual for the detailed procedure.
Input Digit
No. Setting item 0 1
0 Trip Reset Hold 1 Biased differential A-phase Reset Hold 2 Biased differential B-phase Reset Hold 3 Biased differential C-phase Reset Hold 4 Differential overcurrent A-phase Reset Hold 5 Differential overcurrent B-phase Reset Hold 6 Differential overcurrent C-phase Reset Hold 7 Not used 8 Not used 9 Not used 10 Not used 11 Not used 12 Not used 13 Not used 14 Not used 15 Not used
00000 0 0
Same as left
Same as left
Operation indicator LED hold data 0
Conversion from binary number to hexadecimal
Binary Hexadecimal Binary Hexadecimal Binary Hexadecimal 0 0 0 0 0 0 1 1 0 6 1 1 0 0 C
0 0 0 1 1 0 1 1 1 7 1 1 0 1 D
0 0 1 0 2 1 0 0 0 8 1 1 1 0 E
0 0 1 1 3 1 0 0 1 9 1 1 1 1 F
0 1 0 0 4 1 0 1 0 A
0 1 0 1 5 1 0 1 1 B
Same as left
When the product is shipped from the factory, all LEDs are set to self-hold.
Item number Operation indicator LED hold data
860 007F
JEP0-IL9432 53
(3) CT polarity check
This relay has a function that it can detect out the incorrect connection (polarity error or
phase-sequence error) of CT connected with the primary winding and secondary winding of
transformer. Be careful that it cannot detect out correctly if no current is flowing.(more than current
0.12A on the CT secondary side (relay input) is needed to detect correctly)
As the result of detection, if the code 0000 is displayed, it means that all of connection of CT is
correct. Otherwise it means that the connection of CT is incorrect.
The following table 6.4 shows the indicated codes (one instance) when carrying out CT polarity
check. You can reference it even for the other codes when you inform this function.
Please refer to the item 8 ofGeneral operation manualin which the detailed operation is
described.
JEP0-IL9432 54
Table 6.4 Codes of CT polarity check (one instance)
Primary side Secondary side
A-phase B-phase C-phase A-phase B-phase C-phase Codes
0000
Polarity 0001
Polarity 0020
Polarity 0400
Polarity 0001
Polarity 0020
Polarity 0400
Phase Phase 0082
Phase Phase 1040
Phase Phase 0804
Phase Phase 0044
Phase Phase 0880
Phase Phase 1002
Phase/Polarity Phase 0090
Phase Phase/Polarity 0102
Phase Phase Polarity 0482
Polarity Phase Phase 1041
Phase/Polarity Phase 1200
Phase Phase/Polarity 2040
Phase/Polarity Phase 0808
Phase Polarity Phase 0824
Phase Phase/Polarity 4004
Phase/Polarity Phase 0048
Phase Phase/Polarity 0204
Phase Phase Polarity 0444
Polarity Phase Phase 0881
Phase/Polarity Phase 0900
Phase Phase/Polarity 4080
Phase/Polarity Phase 1010
Phase Polarity Phase 1022
Phase Phase/Polarity 2002
* The meanings of symbols in this table is shown below.
Polarity: CT polarity is incorrect.
Phase : The phase sequence is incorrect.
: No abnormality
JEP0-IL9432 55
How to read and understand the CT polarity check codes
Output Digit No.
Error 0 1
0 Polarity error Correct Error
1 Phase sequence error (A-B[Prim.],A-C[Sec.]) Correct Error
2 Phase sequence error (A-B[Sec.],A-C[Prim.]) Correct Error
3 PhasePolarity error (A-B[Sec.],A-C[Prim.]) Correct Error
A - p h a s e
4
PhasePolarity error (A-B[Prim.],A-C[Sec.]) Correct Error
5 Polarity error Correct Error
6 Phase sequence error (A-B[Prim.],B-C[Sec.]) Correct Error
7 Phase sequence error (A-B[Sec.],B-C[Prim.]) Correct Error
8 PhasePolarity error (A-B[Sec.],B-C[Prim.]) Correct Error
B - p h a s e
9
PhasePolarity error (A-B[Prim.],B-C[Sec.]) Correct Error
10 Polarity error Correct Error
11 Phase sequence error (A-C[Prim.],B-C[Sec.]) Correct Error
12 Phase sequence error (A-C[Sec.],B-C[Prim.]) Correct Error
13 PhasePolarity error (A-C[Sec.],B-C[Prim.]) Correct Error
C - p h a s e
14
PhasePolarity error (A-C[Prim.],B-C[Sec.]) Correct Error
15 Not used 0
0
Binary Hexadecimal
0 0 0 0 0
0 0 0 1 1
0 0 1 0 2
0 0 1 1 3
0 1 0 0 4
0 1 0 1 5
Binary Hexadecimal
0 1 1 0 6
0 1 1 1 7
1 0 0 0 8
1 0 0 1 9
1 0 1 0 A
1 0 1 1 B
Binary Hexadecimal
1 1 0 0 C
1 1 0 1 D
1 1 1 0 E
1 1 1 1 F
Conversion from binary to hexadecimal
Same as left Same as left Same as left
Indication data of CT polarity
For instance, converse the displayed code from hexadecimal to binary, If (Digit No.=0) = 1, A-phase polarity (CT primary or secondary) is error. If (Digit No.=1) = 1, the phase sequence of A and B is error. (CT primary side) or the phase sequence of A and C is error (CT secondary side). If (Digit No.=3) = 1, the A-phase polarity of CT primary and secondary is error.
or the phase sequence of A and B is error (CT secondary side) or the phase sequence of A and C is error (CT primary side).
JEP0-IL9432 56
7 Mounting 7.1 Mounting dimension
Mount the case to the panel according to Fig. 7.1 Mounting dimension.
Figure 7.1 Outside dimension /drilling drawing (D2 Case)
7.2 Standard operating environment
Install the relay in the environment described in section 3.3 Common technical data. In addition, the
following conditions should be kept:
- Abnormal vibration, shock, inclination or magnetic field should be avoided.
- Harmful smoke or gas, salt gas, excessive humidity, water drop or vapor, excessive dust or
fine powder, rain and wind should be avoided.
251
20 5
18 4
203
(18)
35
(185)
4-M5 screws(for mounting) M3.5 screw(for terminals)
19 4
15 0
4- 6 holes 214
230
Dimension in mm
JEP0-IL9432 57
8 Test The relay has been fully tested prior to shipment. However, it is recommended to carry out a test again by
referring to the following test guide before use.
8.1 Appearance inspection
Check the relay for appearance according to the following procedure: Objects Check points Coil/conductor (1) Discoloring and burning due to overheat.
(2) Abnormal conditions including loosened screws. Printed card (1) Discoloring of the printed card due to overheated parts.
(2) Contact between the printed card and connector Unit Mechanism (1) Deformation
(2) Operation of the operating key switches. (3) Damage of the draw-out lever of the sub unit. (4) Discoloring and deformation of the name plate on the front panel. (5) Damage of the terminal section.
Case/cover (1) Damage of the cover. (2) Stain of the cover. (3) Clouding of the cover. (4) Damage of the lock lever of the cover. (5) Damage of the operating buttons of the cover. (6) Operation of the operating buttons of the cover. (7) Damage of the terminal section.
Others Invasion of foreign matters including dust and iron chips.
JEP0-IL9432 58
8.2 Characteristic test
8.2.1 Precautions in testing
(1) Standard test conditions
Ensure the following test conditions whenever possible:
Note that carrying out a test under an environment that significantly differs from the following
conditions may produce a incorrect result.
- Ambient temperature : 20C10C
- Rated frequency : 5%
- Waveform (AC) : 2% (distortion ratio)
- Auxiliary power supply voltage : rated voltage 2%
(2) Characteristic control point
See the section 3 Characteristics.
The characteristic control point refers to the characteristic of a relay unit only. Note that, when a
characteristic test is carried out on a relay system connected with external equipment such as CT
and ZCT, the result obtained would be a combined characteristic added with the fluctuation of the
external equipment.
For special control in terms of a specific control point (for instance, using the operation setting), first
carry out a test at Characteristic control point at the time when the relay is received or put in service
to determine the acceptance/rejection. Thereafter, perform another test at each control point, so that
the data obtained can be used for future reference.
(3) Changing setting
Change the setting according to the section 6 Handling.
Please pay attention that the setting item of DIF test (515) should be set ON when you carry out
characteristic test. Because this relay has continuously monitoring function of differential current, so
that the monitoring abnormality (0017) will occur when current applied on. The DIF test LED (yellow)
will become on when setting. And do not forget to set the DIF test (515) OFF after finishing the
characteristic test.
(4) Operation judgment
Determine the operation currents and time and other values of the relay unit basically by turning on
and off the corresponding output relay contact of each element.
(5) Determination of 2-terminal biased differential characteristic
As the determination condition, let the outflow current (I2) be tap value (IT) 200%, and let the inflow
current (I1) raise slowly from tap value (IT) 200%, determine the operation value. Please calculate
the bias based on the determined operation value according to the following formula.
[ ]% 100 I
I-I =
1
21
(6) Determination of differential overcurrent element operation value
When you want to determine the differential overcurrent operation value, please set the operation
setting of differential element LOCK so that the relay will not response to the differential current.
And do not forget to set the setting value with original one after finishing the determination.
JEP0-IL9432 59
(7) The calculation method of current value in case of the matching tap IT1 setting and IT2setting is
different.
As described in the item 3 [Characteristics], the testing condition is IT1=IT2 and the matching tap
setting is minimum value.
However, in case of IT1 and IT2 is not equal, please calculate the current as following manner.
( Please refer to item 4.1(2) biased differential about calculation of current inside of the relay.)
The biased differential = differential current/ restraining current
| I 1 I n /IT1 I 2 I n /I T2 | I 1 I n /IT1 | or |I 2 I n /I T2 whichever is greater
In: Rated current, : Setting value of the biased differential
In case of I1>I2, the value of I2 for testing should be 200% of matching tap T1 which is the fixed value.
| I1In/IT1I2In/IT2
| I1In/IT1| According to the above equation, I1=I2IT1/IT21/(1-)
The criteria for evaluation for the testing results as below should be based on 2 cases in which value
of is changed to (5%) and (5%).
Lower limit of criteria
I1=I2IT1/IT2(1 /(1-0.15))=2.353IT1
Upper limit of criteria
I1=I2IT1/IT2(1 /(10.25))=2.667IT1
=
=
M at
ch in
g ta
p
D iff
er en
tia l
R es
tra in
in g M
at ch
in g
ta p
JEP0-IL9432 60
8.2.2 Characteristic test
(1) Test circuit
Connect the external wiring referring to the AC input circuit diagram shown below:
a. Biased differential characteristic
A-17
Voltage
The example of A-phase
CAC1-A01D2
Phase Terminals of primary windings
Terminals of secondary windings
A-phase A-17~A-18 A-11~A-12 B-phase A-19~A-20 A-13~A-14 C-phase A-21~A-22 A-15~A-16
A-18
I1
A-11
A-12
I2
AC moving-iron current meter
Class 0.5
~
A ~
A ~
A ~
b. Phase characteristic
A-17 Voltage
CAC1-A01D2
A-18
The example of A-phase
A-11
A-12
Phase meter
I1
I2
Voltage
AC moving-iron current meter
Class 0.5 A ~
A ~
A ~ ~
~
c. 2nd harmonic blocking characteristic
A-17
Voltage
CAC1-A01D2
A-18
IAC
IDC
DC moving-coil current meter
Class 0.5
Example of A-phase
~
A ~
A
A
IAC: SIN wave current IDC: Half wave rectifier current
(%) 100 I
2 +I 2
I 3 2
= I I
DCAC
DC
f1
f2
JEP0-IL9432 61
(2) Test items and characteristic control point
a. Forced operation test
See Front control panel operational procedure in the section 6 Handling.
b. Operation value test
See the item Operation and reset values in the section 3 Characteristics.
c. Operation time test
See the item Operation time in the section 3 Characteristics.
d. Reset time test
See the item Reset time in the section 3 Characteristics.
9 Maintenance 9.1 Daily inspection
Take every opportunity to carry out the following inspection:
- Check that the cover is not damaged and is attached properly.
- Check that no dust or iron chips have invaded into the unit.
- Check that the cover is not clouded notably.
- Check that abnormal noise is not generated.
- Check that the RUN LED lamp is lit.
9.2 Periodical inspection
It is recommended to carry out periodic inspections to check the relay for proper function.
For periodical inspections, perform the appearance inspection and characteristic test in accordance with
the section 8 Test.
JEP0-IL9432 62
10 Ordering The product and specification shown in this manual may subject to changes (including specification
change and production suspend) without notice. It is advisory to inquire the nearest Mitsubishi Electric s
branch or sales office, if required, to confirm that the latest information is given in the manual, prior to
placing an order.
Notify the following items when placing an order. Item Example of orderRemarks
Model CAC1-A01D2For more information, see the section 2 Rating and specification.
Frequency 50 HzSelect 50Hz or 60Hz. Rating Phase current: 5AFor more information, see the section
2 Rating and specification.
Communication card
One of the followings can be selected: a. CC-Link communication card (Manual No.:
JEP0-IL9517, JEP0-IL9418) b. No communication card
Only purchasing a communication card separately will allow customer to add the communication facilities. If customer does not need the communication facilitates at the time of introducing the system, just purchase the relay unit without communication card. Customer can add the communication facilities whenever he/she needs to introduce them. This will help decrease the initial cost and upgrade the system in stages.
Direct communication application
PC-DISW HMI software
By connecting PC with relay via the direct communication port (as standard equipment located on the relay front panel, local operation and monitoring are enabled as same as the remote operation and monitoring.
11 Guarantee 11.1 Guarantee period
The guarantee period of this product should be one year after delivery, unless otherwise specified by
both parties.
11.2 Scope of guarantee
When any fault or defect is detected during the period of guarantee and such fault or defect is proved to
be caused apparently at the responsibility of MITSUBISHI ELECTRIC CORPORATION, the defective
unit concerned will be repaired or replaced with substitute with free of charge.
However, the fee for our engineer dispatching to site has to be covered by the user.
Also, site retesting or trial operation caused along with replacing the defect units should be out of scope
of our responsibilities.
It is to be acknowledged that the following faults and defects should be out of this guarantee.
When the faults or defects are resulted from the use of the equipment at the range exceeding the
condition/environment requirements stated in the catalogue and manual.
JEP0-IL9432 63
When the faults or defects are resulted from the reason concerning without our products.
When the faults or defects are resulted from the modification or repair carried out by any other entity
than MITSUBISHI ELECTRIC CORPORATION.
When the faults or defects are resulted from a phenomenon which can not be predicted with the
science and technology put into practical use at the time of purchase or contract
In case of integrating our products into your equipment, when damages can be hedged by the proper
function or structure in the possession of your equipment which should be completed according to the
concept of the de fact standard of industry.
In case of that the faults or defects are resulted from un-proper application being out of instruction of
MITSUBISHI ELECTRIC CORPORATION.
In case that the faults or defects are resulted from force majeure such a fire or abnormal voltage and
as an act of God such as natural calamity or disaster.
11.3 Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, MITSUBISHI ELECTRIC CORPORATION shall not be liable for
compensation of damages caused by any cause found not be the responsibility of MITSUBISHI
ELECTRIC CORPORATION, loss in opportunity, lost profits incurred to the user by failures of
MITSUBISHI ELECTRIC CORPORATION products, special damages and secondary damages whether
foreseeable or not, compensation for accidents, and compensation for damages to products other than
MITSUBISHI ELECTRIC CORPORATION products and other tasks
11.4 Applications of products
The user is requested to confirm the standards, the regulations and the restrictions which should be
applied, in case of utilizing products described in this catalogue and another one in combination.
Also, the user is requested to confirm the suitability of our products to your applied system or
equipment or apparatus by yourself.
MITSUBISHI ELECTRIC CORPORATION shall not be liable for any suitability of our products to your
utilization.
This MITSUBISHI ELECTRIC CORPORATION products described in the catalogue have been
designed and manufactured for application in general industries, etc. Thus, application in which the life
or an asset could be affected by special application such as medical system for life-sustaining, in
nuclear power plants, power plants, aerospace, transportation devices(automobile, train, ship,
etc )shall be excluded from the application. In addition to above, application in which the life or an
asset could be affected by potentially chemical contamination or electrical interference and also in
which the circumstances and condition are not mentioned in this catalogue shall be excluded from the
application.
Note even if the user wants to use for these applications with users responsibility, the user to be
requested to approve the specification of MITSUBISHI ELECTRIC CORPORATION products and to
contact to the technical section of MITSUBISHI ELECTRIC CORPORATION prior to such applications.
If the user applies MITSUBISHI ELECTRIC CORPORATION products to such applications without any
contact to our technical section, MITSUBISHI ELECTRIC CORPORATION shall not be liable for any
items and not be insured, independently from mentioned in this clause.
JEP0-IL9432 64
In using MITSUBISHI ELECTRIC CORPORATION product, the working conditions shall be that the
application will not lead to a major accident even if any problem or fault occur, and that backup or
duplicate system built in externally which should be decided depend on the importance of facility, is
recommended.
The application examples given in this catalogue are reference only and you are requested to confirm
function and precaution for equipment and apparatus and then, use our products
The user is requested to understand and to respect completely all warning and caution items so that
unexpected damages of the user or the third party arising out of un-correct application of our products
would not be resulted.
11.5 Onerous repair term after discontinuation of product
MITSUBISHI ELECTRIC CORPORATION shall accept onerous product repairs for 7(seven) years
after production of the product is discontinued. (However, please consider the replacement of products
after 15 years have been passed from ex-work of products.)
Product supply (including repair parts) is not available after production is discontinued.
11.6 Changes in product specification
The specification given in the catalogue, manuals or technical documents are subject to change without
prior to notice.
11.7 Scope of service
The technical service fee such as engineer dispatching fee is excluded in the price of our products.
Please contact to our agents if you have such a requirement.
12 Improvement of protection function Any parts and materials applied to the protection relay have limited life time which will bring the
degradation to the relay.
The degree of degradation will be variable and depend on the purpose, period in use, applied
circumstance and unevenness on the performance of each part.
MITSUBISHI ELECTRIC CORPORATION design the relay so as to realize that the recommended
replaced duration is more them 15 years.
However, there may be some possibilities to occur some defects before reaching 15 years due to above
mentioned the degree of degradation of parts and materials being depended on the condition in use.
To prevent unwanted operation or no operation of relay due to above reasons, it is recommended to apply
the relay with self-diagnosis function and/or multiplexing relay system such as dual or duplex scheme.
Revised in Nov. 2012
HEAD OFFICE 7-3 MA
Related manuals for Mitsubishi CAC1-A01D2 Relay Instruction Manual
Manualsnet FAQs
If you want to find out how the CAC1-A01D2 Mitsubishi works, you can view and download the Mitsubishi CAC1-A01D2 Relay Instruction Manual on the Manualsnet website.
Yes, we have the Instruction Manual for Mitsubishi CAC1-A01D2 as well as other Mitsubishi manuals. All you need to do is to use our search bar and find the user manual that you are looking for.
The Instruction Manual should include all the details that are needed to use a Mitsubishi CAC1-A01D2. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.
The best way to navigate the Mitsubishi CAC1-A01D2 Relay Instruction Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.
This Mitsubishi CAC1-A01D2 Relay Instruction Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.
You can download Mitsubishi CAC1-A01D2 Relay Instruction Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.
To be able to print Mitsubishi CAC1-A01D2 Relay Instruction Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Mitsubishi CAC1-A01D2 Relay Instruction Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.