Before operating the instrument, you should first read thoroughly this operation manual for safe operation and optimized performance of the product. Deliver this users manual to the end user.
Electronic Multi-Measuring Instrument Types ME110SSR ME110SSR-4AP ME110SSR-4APH ME110SSR-4A2P
ME110SSR-C ME110SSR-CH ME110SSR-MB
Users Manual: Detailed Edition
Check on your delivery
Check the following point as soon as you receive Mitsubishi Electronic Multi-Measuring Instrument :
Parts name Quantity Specifications
Users Manual (Simplified) 1 A3 size
Attaching nuts 2 M5 belleville spring nuts (contained in a bag)
The package is in good condition. The product has not been damaged during transit. The product corresponds to your order specifications. This product has the following accessories.
1
Check on your delivery 1 Contents 2 Safety Precaution 4 EMC DIRECTIVE INSTRUCTION 6 Features 7
Operation
1. Display and Button Functions of Each Part 8 2. Function Modes 10 3. Settings 11
3.1 Setting ow Diagram 11 3.2 Setting Menu 1: Setting the Phase Wire Method, Display Pattern, VT/Direct Voltage,
CT Primary Current, and constant for Demand Time 13 3.3 Setting Menu 2: Model code, Backlight, and Display Update Time 18 3.4 Setting Menu 3: Setting the Bar Graph, Unit Display, Expanded counting, and Harmonics Display 19 3.5 Setting Menu 4: Index Indicator Setting 21 3.6 Setting Menu 5: Setting the Upper/Lower Limit Alarm, Backlight Flickers During Alarms and Motor Startup Current Delay Function 22 3.7 Setting Menu 6: Setting the Analog Output and Pulse Output 25 3.8 Setting Menu 7: Setting the Communication 30
Setting Menu 7: Setting the ModBus Communication 31 3.9 Setting Menu 8: Setting the Operating Time Display, CO2 Emission Display,
and Element Information 32 3.10 Setting Value Con rmation Menu 1: Con rming the Setting Values for Setting Menu 1 33 3.11 Setting Value Con rmation Menus 2 to 8: Con rming the Set Values for Setting Menus 2 to 8 34 3.12 Initializing Related Items by Changing Settings 35 3.13 Initializing All Settings 35 3.15 Setting the Special Display Pattern P00 36 3.16 Examples of Simple Settings 38
4. Using Test Mode 40 4.1 Test Menu 1: Incorrect Wiring Determination Support Display 41 4.2 Test Menu 2: Zero Span Adjustment for Analog Output 43 4.3 Test Menu 3: Analog Output Operation Test 44 4.4 Test Menu 4: Pulse Output Operation Test 45 4.5 Test Menu 5: Alarm Output Operation Test 45 4.6 Test Menu 6: Communication Test 46
5. Operation 47 5.1 Basic Operations 47
Switching display 47 Switching phase 47 Bar graph display 48 Switching measurement factors displayed on bar graphs 48 Cyclic display 48 Harmonics display 49 Maximum value and minimum value display 50 Display of maximum value and minimum value 50 Clear the maximum/minimum value 50 Active energy and reactive energy display 51 Enlarged 3 digital gures. 51 Wh and varh zero reset 51 Reactive energy measurement method (2 quadrant / 4 quadrant counting) 52 Each measurement item display during power transmission 52 Demand time and demand value 52
Contents
2
5.2 Usage According to Purpose 53 Display and operation of the upper/lower limit alarm 53 Canceling the upper/lower limit alarm 54 Stopping backlight ickering caused by upper/lower limit alarm generation 54 Operation time display 54 Clearing the operation time 54 CO 2 emission display 55 Clearing the CO 2 emission value 55 Display and operation of the digital input status 56 Preventing maximum value update by motor startup current 57 Indicator display 57
6. Other 58 6.1 Display Pattern Contents 58 6.2 Maximum Scale Value 60 6.3 Possible Setting Range for Maximum Scale 62 6.4 Measurement Items and Correspondence between Display and Output 64 6.5 Measurement Characteristic 66 6.6 Troubleshooting 67
7. Warranty 68
Installation
1. External Dimensions 69 2. Mounting 71 3. Wiring 72 4. Wiring Diagram 74
Speci cations
Speci cation 79 Communication Speci cation 80 Settings Table (Factory Settings and Customer Setting Note) 81
Contents
3
4
Safety Precaution
(Always read these instructions before using this equipment) For personnel and product safety please read the contents of these operating instructions carefully before using. Please save this manual to make it accessible when required and always forward it to the end user.
CAUTION
Indicates that incorrect handling may cause hazardous conditions. Always follow the instructions because they are important to personal safety. Otherwise, it could result in electric shock, re, erroneous operation, and damage of the instrument.
Normal service conditions
CAUTION
Use the instrument in an environment that meets the Normal service conditions as following points: Ambient temperature :-5 to 50C, average day temperature: 35C or lower Humidity :30~85%RH, non condensing. Altitude: 1000m or less Pollution Degree : 2 Atmosphere without corrosive gas, dust, salt, oil mist. A place without excessive shocks or vibration. Do not expose to rain and water drips. Do not expose to direct sunlight. An area where no pieces of metal and no inductive substances disperse. Do not expose to strong electromagnetic eld and ambient noises.
Installation instructions
CAUTION
This instrument should be installed and used by a quali ed electrician. The instrument must not be powered and used until its de nitive assembly on the cabinets door. Verify the following points; Auxiliary power supply and Measuring ratings
Auxiliary power supply 100-240V AC+10 -15%(50-60Hz) 10VA
100V DC+40 -25% 6W
Ratings Voltage 277V AC phase-neutral / 480V AC phase-phase Current 5A or 1A (via current transformer) Frequency 50/60Hz
Current circuits, C1, C2 and C3 are Measurement category . Voltage circuits, P1, P2 and P3 are Measurement category . The instrument is to be mounted on panel. All connections should be kept inside the cabinet. Tighten the terminal screws with the speci ed torque and use the suitable pressure connectors
and suitable wire size. (see page 72) When wiring in the instrument, be sure that it is done correctly by checking the instrument s wiring
diagrams. (see pages 74 to 78) Be sure there are no foreign substances such as sawdust or wiring debris inside the instrument. Do not drop this instrument from high place. If you drop it and the display is cracked, do not touch
the liquid crystal and get it in your mouth. If touching the liquid crystal, wash it away at once. In order to prevent invasion of noise, do not bunch the control wires or communication cables
with the main circuit or power wire, or install them close to each other. The distance between communicational signal lines, input signal lines and power lines, and high voltage lines when running parallel to each other are shown below.
Conditions Length Below 600V, or 600A power lines 30cm or more Other power lines 60cm or more
5
Operation instructions
CAUTION
When the external terminals are connected to the external equipments, the instrument and the external equipments must not be powered and used until its de nitive assembly on the cabinets door.
The rating of the terminal of the external equipment should satisfy the rating of the external terminal of this instrument. (See Speci cations.)
Maintenance instructions
CAUTION
Do not touch the terminals while all the circuits connected to this instrument are alive. Do not disassemble or modify the instrument. Do not allow a chemical dust cloth to be in contact with the instrument for a long time, or do not
wipe it with benzene, thinner, alcohol.
Wipe dirt on surface with a soft dry cloth. Check the following points, Condition of the appearance Condition of the Display Unusual sound, a smell, and generation of heat Condition of the wiring and the attachment Storage conditions Ambient temperature: -20 to 60C, average day temperature: 35C or lower Humidity range 30~85%RH, non condensing. Atmosphere without corrosive gas, dust, salt, oil mist. A place without excessive shocks or vibration. Do not expose to rain and water drips. Do not expose to direct sunlight. An area where no pieces of metal and no inductive substances disperse.
Disposal When disposing of this product , treat it as industrial waste. The battery is not used for this product.
Guarantee The period of guarantee is for 1 year from the sale date, except in the case that the failure has been caused by bad handling of the product, provided that it has been installed according to the manufactures instructions.
6
This section summarizes the precautions on conformance to the EMC Directive of the cabinet constructed using this Instrument. However, the method of conformance to the EMC Directive and the judgment on whether or not the cabinet conforms to the EMC Directive has to be determined nally by the manufacturer.
1. EMC Standards EN 61326-1:2006 EN 61000-3-2:2006/A1:2009/A2:2009 EN 61000-3-3:2008
2. Installation (EMC directive) The instrument is to be mounted on panel of a cabinet. Therefore, the construction of a cabinet is important not only for safety but also for EMC. The instrument is examined by the following conditions. Use a conductive cabinet. Six faces of a cabinet have to be ensured conductivity for each other. A cabinet has to be connected to earth by a thick wire of low impedance. Holes on faces of cabinet have to be 10 cm or less in diameter. The terminals for protective earth and functional earth have to be connected to earth by a thick
wire of low impedance. (A terminal for protective earth is important not only for safety but also for EMC.)
Protective earth: Maintains the safety of the instrument and improves the noise resistance. Functional earth: Improves the noise resistance.
All connections should be kept inside the cabinet. Wirings outside the cabinet have to be used with the shielded cable.
The following diagram shows how to provide good contact of the shielded cable. Remove part of the outer cover. Remove part of the paint musk on the cabinet. Connect those parts with the clamp.
Shield section
Paint mask
Shielded cable
Screw
Clamp fitting
EMC DIRECTIVE INSTRUCTION
7
Features
This instrument measures the load status by inputting the secondary side of the VT and CT, and displays various measurement values. In addition, telemonitoring can be done by a variegated output function.
Various measurement parameters Phase wire system 3P4W 3P3W,1P3W 1P2W
Current A A1,A2,A3,AN,Aavg A1,A2,A3 A1 Current Demand DA DA1,DA2,DA3,DAN,DAavg DA1,DA2,DA3 DA1
Voltage V V12,V23,V31,Vavg(L-L), V1N,V2N,V3N,Vavg(L-N) V12,V23,V31 V12
Active Power W W,W1,W2,W3 W W Active Demand Power DW DW,DW1,DW2,DW3 DW DW
Reactive Power var var,var1,var2,var3 var var Apparent Power VA VA,VA1,VA2,VA3 - -
Power Factor cos cos,cos1,cos2,cos3 cos cos Frequency Hz Hz
Active Energy Wh Import, Export
Reactive Energy varh Import lag, Import lead, Export lag, Export lead
Harmonic Current HI HI1, HI2, HI3, HIN HI1,HI3 HI1
THD,h1...h13(without even number) RMS value and Distortion ratio(max.100%)
Harmonic Voltage HV HV1N,HV2N,HV3N HV12,HV23 HV12
THD,h1...h13(without even number) RMS value and Distortion ratio(max.20%)
Referred to as follows in this manual: average value : avg three phase total RMS : phase to phase : L-L phase to neutral : L-N
ex) average value of current : Aavg
Three phase active power : W 1-phase to 2-phase voltage : V12 1-phase to neutral voltage : V1N
4 measurement items appear on one display By combination of bar graph and digital 3-stage display, 4 measurement items can be displayed on one display. For example, voltage, current, power factor and active power can be displayed at the same time.
RS485 interface, ModBus RTU(ME110SSR-MB)
CC-Link communication Measured values can be sent to PC or PLC via CC-Link communications. (ME110SSR-C,-CH)
Analog 4 outputs + pulse output + alarm relay output (ME110SSR-4APH) For example, the analog outputs of voltage, current, active power, and power factor, the pulse output of active energy, and the alarm output of THD can be performed by one unit.
Harmonics It is equipped with harmonics current and harmonics voltage measurement function as standard one.
Back light auto off function It is equipped with energy saving mode function where the back light is turned off when there is no key operation for 5 minutes.
7 6
3 5
11
13
12
1 2
4
8
9
10
14
15 16 17 18
Note: The above display is an example for explanation.
No. Segment Name Description 1 LEAD status Shows direction power factor or reactive power on bar graph.
Turns on at the additional display of reactive energy.2 LAG status 3 Scale of the bar graph Shows the scales at the bar graph. 4 Under scale input Turns on when measuring values fall below the minimum scale. 5 Over scale input Turns on when measuring values exceed the maximum scale. 6 Alarm indicator When upper/lower limit alarm set, ickers at the limit setting value. 7 Index indicator When set, turns on at the index indicator setting value.
8 Bar graph status Shows the item displayed on the bar graph. When the item is the same as a digital displayed item,indicated with , otherwise indicated with
9 Digital status Phase status, 123N , MAX/MIN,demand etc. displayed. 10 Digital display Measured values displayed in digital. 11 Units Units of measuring value displayed. 12 Multiplying factor Indicates the multiplying factor for calculating energy. 13 Metering status Flickers when counting active energy.(Note.1) 14 Harmonics Turns on when harmonics displayed.
15 Setup mode status Turns on at setting mode. Flickers at setting value con rmation mode.
16 Test mode status Turns on at the test mode. 17 Upper/lower limit alarm status Flickers when upper/lower limit alarm is generated.
18 Communication status
The following are displayed for models with a transmission function.
Model On Blinking Off
ME110SSR-C
ME110SSR-CH Normal
CC-Link compatible version mismatch
Hardware error Hardware error
ME110SSR-MB Normal Communication error (Such as
wrong address) Hardware error
* Products other than above dont illuminate.
Note 1. The blinking cycle is constant regardless of the size of the measured input.
Operation 1. Display and Button Functions of Each Part
Display
8
5. Operation
Functions of operation buttons
The operation button have various functions according to how they are pressed down.
Meaning of code: (Press), (press over 1 second), (press over 2 seconds), (press simultaneously) Operation
Mode
Key name
Function SET RESET Max/
Min PHASE DISPLAY
O pe
ra tio
n m
od e
B A
S IC
Display changes.
Phase changes.
Mode changes to the max./min. display and the instantaneous display
The item expressed with the bar graph is changed.
Harmonics number changes when harmonics displayed.
Displays change cyclically. (Refer to page 48)
Phases change cyclically. (Refer to page 48)
The counting values of three digits of low rank are displayed. After pressing once again, the display returns. (Refer to page 51)
S pe
ci al
Maximum values and minimum values on the display are reset to the present value. Only available for
maximum/minimum value screenAll of the Maximum values and minimum
values are reset to the present value.
All of the counting values are zero reset.
The operation time is zero veset (Screen operation time only)
An alarm condition is canceled. (Screen element is canceled) Available only when
manual cancelation is setAll alarm conditions are canceled.
(Element is canceled for all screens)
The latching data of digital input on the display is canceled. (Available only for contact point input screen)
M od
e S
w itc
h The display of Set value con rmation mode appears.
The display of Setup mode appears.
S et
-u p
m od
e/ S
et v
al ue
c on r
m at
io n
m od
e
S et
tin g
O pe
ra tio
n
The set-up items are saved, and set-up item is changed to next item.
Back to the previous item.
The values of set-up is changed. (If it presses for 1 sec or more fast forward or fast return.)
Back to the Setup display.
S pe
ci al
O pe
ra tio
n Returns from infrared mode to operation mode (Available only for infrared mode)
Back to the Setup display.
Returns set contents to the default settings (Only effective in CANCEL display) (Refer to page 35)
Note: While the back light is off, if the operation key is pressed, the back light is always lit. If the operation button is pressed once again, the function in the above table appears. Note: When Wh and varh are cleared to zero, the CO2 emission value is also cleared.
CAUTION
If the function of maximum value and minimum value reset and Wh, varh zero reset
are done,data will be lost. If this data is needed,please record the data before the reset operation.
If the function of meter restart is done, the entire measurement(measure-ment display,
alarm, analog output, pulse) stops.
Operation 1. Display and Button Functions of Each Part
SET RESET MAX/MIN PHASE DISPLAY
Set key Reset key
Maximum/minimum key
Phase change key
Display change key
+/ key
9
5. Operation2. Function Modes
The following function modes are available for this Multi-Measuring instrument. Operation mode is displayed after auxiliary power turns on. It is then possible to switch to the desired mode.
Mode Description Reference
Pages Operation Mode This mode is for displaying each measured value using digital numerical
values and bar graphs. Operation mode contains "Current Value Display" that displays the current value, and "Maximum/Minimum Value Display" that displays old maximum/ minimum values. In addition, for each display, the cyclic display function can be used to switch between the screens every 5 seconds.
P. 47 to P. 57
Setting mode This mode is for changing the setting values related to measurement and output functions. The following special operations can be executed from the "CANCEL Display" for changing/cancelling setting values.
The instrument is reset. Reset the settings to the factory defaults (Note)
P. 12 to P. 32 P. 35 to P. 39
Setting value con rmation mode
This mode is for con rming the setting values for each setting item. (In this mode, settings cannot be changed in order to prevent accidental changing of settings.) This mode contains test functions that can be used for equipment startup.
Incorrect Wiring Determination Support Display : This displays information such as voltage and current phase angle display for determining improper wiring.
Analog Output Adjustment : Analog output can be adjusted (zero adjustment and span adjustment).
Output Test : Analog output can be switched, pulse output can be executed, and alarm contact points can be opened/closed without measurement input (voltage/current).
Communication Test : Fixed numerical data can be returned without measurement input (voltage/current).
P. 33 and P. 34 P. 40 to P. 46
Note: When the purchased product already has settings, the setting values will not longer be available after this operation. Diagram of Each Mode
Operation mode Setting mode END
Display
CANCEL Display
Setting value confirmation mode
+ simultaneously for 2 secondsPressing
Test function
+ , -
Save the settings
Cancel the settings
Press for 2 seconds
When "End" is selected from the menu
When "End" is selected from the menu
Maximum/minimum value display
Current value display
SET
SET RESET
SET
SET
SET
SET
SET
SET
10
3.1 Setting Procedure
3. Settings
3.1 Setting Procedure
To measure, it is necessary to use Setting mode to set the phase wire system, VT / direct voltage, and CT primary current. From Operation mode, move to Setting mode and then set necessary items. Factory default settings will be used for items that you do not set. Only the settings in Setting menu 1 (basic set-up) are needed for normal use. For more information about the settings, refer to the following pages. For more information about the factory default settings, refer to the setting table on page 81.
CAUTION Keep in mind that when a setting is changed, the related setting items and measurement data will be reset to the default settings. (Refer to page 35.)
Operation Mode
Setting Menu End Setting Menu 1 (Basic Set up) Setting Menu 2 Setting Menu 3
Phase wire system
Display Pattern
Time constant for active power demand
Time constant for current demand
Primary current
VT/direct voltage
Model + Option code
Backlight brightness
Backlight auto off
Display update time
END Display
Cancel Display
Cancel the settings.
Automatic migration.
Save the setting.
Factory default setting
Model display +
Option display
Phase wire system +
Display pattern
VT secondary voltage +
VT primary voltage
CT secondary current +
CT primary current
Time constant for active power demand
Time constant for current demand
Menu 1 for Setting Value
Confirmation Mode
Example of Setting Mode Example of Setting Value Confirmation Mode
ON Blinking
Current maximum scale
Active power maximum
scale
Active power unit W/kW/MW
Reactive power maximum scale
Reactive power unit
Harmonics
Expanded counting
ow
11
3.1 Setting ow
3. Settings
Press SET and RESET simultaneously for 2
seconds to get in the set-up mode. Select a set-up menu number by or .
Use the SET key to select a set-up menu number.
Set each setting item. (Refer to page 14 and later
pages.) After completion of set-up, select End in the set-
up menu and press SET .
When the End display appears, press SET once
again.
Setting Menu 4 Setting Menu 5 Setting Menu 6
Indicator item
Indicator value
Alarm item
Alarm value
Alarm cancel method
Alarm delay time
Back light flickers during alarms
Motor starting current delay time
Analog output 1
Analog output 2
Analog output 3
Analog output 4
Analog output Limit
Pulse output
Power data resolution
CC-Link station number
CC-Link baud rates
CC-Link module reset
CC-Link version
ModBus address
ModBus baud rates
ModBus parity
ModBus stop bit
ModBus module reset
Digital input setting
Digital input cancel methad
ME110SSR-C ME110SSR-CH
Enable/disable operation time display
Enable/disable CO2 display
Switch element information
Test Mode
Arrow in Figure Action Key operation
Shift from the operation mode to the set-up mode.
Memorize the setting contents, and go back to the operation mode.
Cancel the settings.
Skip remaining setting items during setting.
Select "CANCEL."
Shift from the operation mode to the set value confirmation mode.
Select the menu number to set or End .
Get into each setting screen. Shift to the next setting item.
Go back to the previous setting item.
Select a set value.
Shift to the End screen.
Set values return to the factory default value.
Omitted in figure
SET RESET Press them simultaneously for 2 seconds.
Press it for 1 second
Press it for 2 seconds
Press it for 2 seconds.
Press it several times.
Press it several times.
Press it.
Press it.
Press it.
Press it.
Press it.
Press it.
SET
SET
SET
SET
SET
SET
or
or
or
DISPLAY
RESET PHASE
1: For Setting Value Confirmation, it returns to Operation Mode. 2: Repeat settings for up to 4 elements. 3: Setting is only possible for ME110SSR-4AP,4APH and -4A2P. 4: Setting is only possible for ME110SSR-CH. 5: This is not display in Setting Mode.
Setting Menu 7 Setting Menu 8 Setting Value Confirmation Menu 9
Setting Mode or Setting Value Confirmation Mode
12
5. Operation
Basic Operations for set-up Function Operation Remarks
Select a set value Press or . Fast-forward when pressed over 1 sec.
Set-up items are saved Press SET . Set-up item will be cared and shift to the next item.
Go back to the previous setting item Press DISPLAY . The set value for the setting item just before returning is still available.Skip removing setting items
during setting Press and hold SET for 1 sec.
This section is about setting the phase wire method, display pattern, VT/direct voltage, CT primary current, and
In the operation mode, after pressing SET and RESET simultaneously for 2 seconds or more, the following operation becomes available.
3. Settings
3.2 Setting Menu 1: Se ting he Phase Wire System, Display Pattern, VT/Direct Voltage, CT Primary Current, and Time constant for Demand
Set the display pattern.
Set the setting menu number to 1.
Setting Menu
Set the phase wire system. Supplemental Information: Underlined portions indicate the default values. (Same from here.)
3P33CT 3P32CT 3P4
: Three-phase 3-wire (3CT) : Three-phase 3-wire (2CT) : Three-phase 4-wire
1N2 1P3 : Single-phase 3-wire (1N2) 1N3 1P3 : Single-phase 3-wire (1N3)
1P2 : Single-phase 2-wire
Additional Screen (Supplemental)
D isplay P
attern
C urrent
N phase current
dem and current
N Phase dem and Current
Line V oltage
P hase V
oltage
A ctive P
ow er
Active dem and Pow
er
P ow
er factor
R eactive pow
er
Frequency
A ctive E
nergy
Reactive Energy
A pparent pow
er
A ctive E
nergy (E
xported)
R eactive Energy
(Special)
H arm
onic current
N Phase Harmonic Current
H arm
onic voltage
D igital input
(D I1 to D
I3)
O peration tim
e
C O
2 E m
ission
P01 P02 P03 P04 P05 P06 P07 P08 P09 P10 P11 P12 P13 P00
(a) For three-phase 4-wire
The following table shows the measurement elements that can be displayed by each display pattern. (For more details about display patterns, refer to page 62.)In addition, if there is no display pattern that you want from P01 to P13 (P14 and P15), select the special display pattern P00 to configure the screen freely.(For more information about setting the special display pattern P00.)
: Displayable at this display setting. : Set at other additional settings. : Select "P00" and set the display order and display position.
DISPLAY SET
DISPLAY SET
DISPLAY SET
Display Pattern
Phase Wire system
Measurement element on additional screen Setting item Electric energy Power sending / reactive electric energy Special Set-up Menu 3 Electric energy Transmission power display Harmonic current / Harmonic voltage Set-up Menu 3 Harmonics display Contact point input status (DI1 to DI3) Set-up Menu 7 Digital input setting Operation time Set-up Menu 8 Operation time display CO2 emission Set-up Menu 8 CO2 emission display
Reference Pages Page 20 Page 20 Page 30 Page 32 Page 32
13
3. Settings
3.2 Setting Menu 1: Setting the Phase Wire System, Display Pattern, VT/Direct Voltage, CT Primary Current, and Time constant for Demand
(1) When using VT Set the secondary and primary voltages of the VT.
DISPLAY SET
Page 20 Page 20 Page 30 Page 32 Page 32
DISPLAY SET
To CT primary current
(a) For three-phase, 4-wire
63.5V 100V 110V 115V 120V
VT / direct voltage
(b) For other phase wire system except three-phase 4-wire Additional Screen (Supplemental)
D isplay P
attern
C urrent
em and current
N Phase dem and Current
V oltage
A ctive P
ow er
Active dem and Pow
er
P ow
er factor
R eactive pow
er
Frequency
A ctive E
nergy
Reactive Energy
A ctive E
nergy (E
xported)
R eactive Energy
(Special)
H arm
onic current
H arm
onic voltage
D igital input
(D I1 to D
I3)
O peration tim
e
C O
2 E m
ission
P01 P02 P03 P04 P05 P06 P07 P08 P09 P10 P11 P12 P13 P14 P15 P00
Note: The following settings are required for displaying elements on an additional screen. Measurement element on additional screen Setting item
Active Energy(Exported) / Reactive(Special) Setting Menu 3 Expanded counting Harmonic current / Harmonic voltage Setting Menu 3 Harmonics Display
Digital input (DI1 to DI3) Setting Menu 7 Digital input setting Operation time
Setting Menu 8 Operation time display
CO2 emission Setting Menu 8 CO2 emission display
Reference Pages
yES no
SET
SET
When using VT Select yES, and then press , shift to following (1)
When direct input (without VT) Select no, and then press , shift to following (2).
DISPLAY
SET
SET
From top digit, select the value of the flickering digit by and .
The setting digit can be moved to right by . The setting digit can be moved to left by . Setting is available in range from 60 to 750000V.
Less than 100V : Upper 2 digits setting Over 100V : Upper 3 digits setting * Error display (E05) appears when set out of 60 to
750000V range. After that, please press , review the setting value and set it once again. Press at the lowest digit, the setting step will shift to the next one.
14
3. Settings
(2) For direct input (without VT) Set the direct voltage.
"Special Primary Voltage" Settings (Default value: 10,000V)
DISPLAY SET
110V 220V
100V 110V 220V
220V 440V 690V
1100V 1.1kV
2200V 2.2kV
3300V 3.3kV
6600V 6.6kV 11kV
13.2kV 13.8kV
15kV 16.5kV
22kV 24kV 33kV 66kV 77kV
110kV 132kV 154kV 187kV 220kV 275kV 380kV
500kV 550kV
SP.
DISPLAY SET
DISPLAY SET
(b) For three-phase 3-wire (2CT, 3CT) or single-phase 2-wire
(a)
(b) For three-phase 3-wire (2CT, 3CT) or single-phase 2-wire
63.5/110V 100V/173V 110V/190V 220V/380V 240V/415V 254V/440V 277V/480V
To CT Primary Current When setting "SP." Setting except "SP."
To following "Special Primary Voltage"
Note: If there is no primary voltage in the above that you want to set, select "SP." for a special primary voltage setting.
To CT primary current
For three-phase 4-wire (phase to neutral voltage / phase to phase voltage)
DISPLAY
SET
SET
From top digit, select the value of the flickering digit by and .
The setting digit can be moved to right by . The setting digit can be moved to left by . Setting is available in range from 60 to 750000V.
Less than 100V : Upper 2 digits setting Over 100V : Upper 3 digits setting
* Error display (E05) appears when set out of 60 to 750000V range. After that, please press , review
the setting value and set it once again. Press at the lowest digit, the setting step will shift to the next one.
15
3.2 Setting Menu 1: Setting the Phase Wire System, Display Pattern, VT/Direct Voltage, CT Primary Current, and Time constant for Demand
3.1 Setting Procedure
3. Settings
Set the primary current of the CT you want to combine.
1A 5A 6A
7.5A 8A
10A 12A 15A 20A 25A 30A 40A
50A 60A 75A 80A
100A 120A 150A 200A 250A 300A 400A
500A 600A 750A 800A
1000A 1kA
1200A 1.2kA
1500A 1.5kA
1600A
1.6kA 2000A
2kA 2500A 2.5kA
3000A 3kA
4000A 4kA
5000A 5kA
6000A 6kA
7500A 7.5kA
8000A 8kA
10kA 12kA 20kA 25kA 30kA SP.
DISPLAY SET
DISPLAY SET
Primary Current Setting (Default Setting: 5A)
DISPLAY SET
CT primary current
DISPLAY SET
(a) For three-phase 4-wire
"Special Primary Current" Settings (Default Setting: 5A)
SET
SET
DISPLAY
SET
From top digit, select the value of the flickering digit by and .
The setting digit can be moved to right by the . The setting digit can be moved to left by the . Setting is available in range from 1.0A to 30000.0A
Less than 10A : Upper 2 digits setting Over 10A : Upper 3 digits setting * Error display (E05) appears when set out of 1.0 to 30000.0A range. After that, please press , review the setting value and set it once again.
Press at the lowest digit, the setting step will shift to the next one.
SET
SET
DISPLAY
SET
From top digit, select the value of the flickering digit by and .
The setting digit can be moved to right by the . The setting digit can be moved to left by the . Setting is available in range from 1.0A to 30000.0A
Less than 10A : Upper 2 digits setting Over 10A : Upper 3 digits setting * Error display (E05) appears when set out of 1.0 to 30000.0A range. After that, please press , review the setting value and set it once again.
Press at the lowest digit, the setting step will shift to the next one.
(b) For other phase wire system except Three-phase 4-wire
Note 1: If there is no primary current in the above that you want to set, select "SP." for special primary current setting.
Setting except SP : To When setting SP : To following Special Primary Current
Time constant for Active power demand
To Time constant for Active power demand
To Time constant for Active power demand
Note 1
16
2 ting Menu 1: Setting the Phase Wire System, Display Pattern, VT/Direct Voltage, CT Primary Current, and Time constant for Demand
3. Settings
Time constant for current demand
According to the setting flow (page 11), save the changed contents, or continue to the other set-up menu.
Set-up menu
SET
Time constant for active power demand
DISPLAY SET
Set up the time constant for active power demand.
0 second
10 seconds
20 seconds
30 seconds
40 seconds
50 seconds
1 minute
2 minutes
3 minutes
4 minutes
5 minutes
6 minutes
7 minutes
8 minutes
9 minutes
10 minutes
15 minutes
20 minutes
25 minutes
30 minutes
Note) Even when the display pattern not display the active power demand, this screen appears. If the active power demand is not necessary, press the as it is.SET
SET
Set the time constant for current demmand.
0 second
10 seconds
20 seconds
30 seconds
40 seconds
50 seconds
1 minute
2 minutes
3 minutes
4 minutes
5 minutes
6 minutes
7 minutes
8 minutes
9 minutes
10 minutes
15 minutes
20 minutes
25 minutes
30 minutes
Note) Even when the display pattern not display the current demand, this screen appears. If the current demand is not necessary, press the as it is.
In the case of use only by the Setting menu 1, please go to 5. Operation in page 47. In the case to use additional functions, please go to Setting Menus 2 - 8 (from page 18 to 32).
Note If the contents in the setting menu 1 are changed, the maximum value, minimum value, demand value of related measurement items will be reset. (However, active energy and reactive energy will not be reset.)
17
3.2 Setting Menu 1: Setting the Phase Wire System, Display Pattern, VT/Direct Voltage, CT Primary Current, and Time constant for Demand
5. Operation
3.2 Setting Menu 13.3 Setting Menu 2: Model code,Backlight,Display Update Time Setting
3. Settings
The backlight brightness can be adjusted.
Backlight brightness 1 2 3 4 5
Dark Bright
1 second
Display update time
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
SET
The model can be confirm. (This is only display, and settings cannot be changed.)
Display information Model
Blank ME110SSR ME110SSR-4AP ME110SSR-4APH ME110SSR-4A2P ME110SSR-C
ME110SSR-MB ME110SSR-CH
Model + option code
The backlight can be set to continuous on (HoLd) or auto off (Auto).
Backlight auto off HoLd Auto
Continuous on Auto off
Note: At this moment, the display is not changed. When the operation button is pressed once again, the display is changed.
Set the set-up menu number to 2.
Setting menu
According to the setting flow (page 11), save the changed contents, or continue to the other setting menu.
Seting menu
A: Current specification (4-20mA)
Lower LineMiddle Line
0.5 second
The display update time for the measured value can be change. If the display switches too quickly for you to read the displayed value, set it to 1.0 second. (Normally, leave this setting to 0.5 second.)
This section is for con rming model and set the backlight and the display update time. (These settings are not needed for normal use.)
In the operation mode, press SET + RESET simultaneously for 2 seconds or more, and the following operation becomes available.
18
5. Operation3. Settings
In this setting menu, you can do in detail set up for the bar-graph, unit, expanded counting, harmonics.
In the operation mode, press SET and RESET simultaneously for 2 seconds or more, and the following operation becomes available.
3.4 Setting Menu 3: Setting the Bar Graph, Unit Display, Expanded counting, and Harmonics Display
Set the single deflection / double deflection of reactive power. Single deflection is the LEAD polarity. (The default setting is double deflection.)Reactive power
maximum scale
Set the reactive power unit (var, kvar, Mvar). Reactive power unit
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
Set the set-up menu number to "3".
Setting menu
Set the current maximum scale.
Current maximum scale
Set the maximum scale of Active power, active power demand.
(1) Maximum scale value
(2) single deflection / double deflection
Active power maximum scale
DISPLAY SET
Set Active power unit (W, kW, and MW).
Maximum scale value Setting range
1,000kW or higher 8,000kW or less
W kW
kW MW
Note: The unit cannot be changed beyond the above range.
Active power unit 8,000W or less1,000W or higher
+3 STEP (About 120%) to 0 STEP (100%: Rating) to -10 STEP (About 40%)
+3 STEP (About 120%) to 0 STEP (100%: Rating) to -18 STEP (About 20%)
double deflectionsingle deflection
Note: The maximum scale value becomes the value in the table on page 62.
Note: The maximum scale value becomes the value in the table on page 63.
The setting method is same as that of Active power unit .
The setting method is same as that of Active power maximum scale .
19
5. Operation
3.4 Setting Menu 3: Setting the Bar Graph, Unit Display, Expanded counting, and Harmonics Display
Set the harmonic measurement.
When the display is set to "on," the harmonic measured value can be displayed on an additional screen of the display pattern.
Harmonics oFF on
DISPLAY SET
SET
According to the setting flow diagram (page 11), save the changed contents, or continue to the other setting menu.
Setting menu
Set the combinations of imported / exported and lag / lead for active energy and reactive energy you want to display, and set the measurement method for reactive energy.
Active energy (Wh)
Reactive energy (varh)
Imported Imported Imported Imported Exported
Exported Exported Exported
I II III IV
Note: For more information about the measurement method for reactive energy, refer to page 52.
Combination I, II It is suitable for the counting of equipment without the private electric generator and the reactive power of the capacitor load at the power factor = 0, generally.
Combination III, IV It is suitable for the counting of equipment with the private electric generator.
Expanded counting
Note
Accuracy is defined to rated current. Although the maximum scale may display 120% or more of rated current and rated voltage in order to make a scale easy to read depending on the settings of VT/direct voltage and CT primary current, current input is within 100% of rated current.
Combination (Setting value)
Combination I Combination II Combination III Combination IV
lag lag laglag(lead) lead lead lead
Reactive energy measurement method(Note)
2 quadrant measurement
4 quadrant measurement
(Displayed)(Not displayed)
Even if a display pattern is selected that cannot display active power, reactive power, active energy, and reactive energy, it is possible to display the sign according to 2 quadrant / 4 quadrant measurement of the power factor and reactive power due to Expanded counting , so setting items for Expanded counting will be displayed.
3. Settings
20
3.1 Setting Procedure
3. Settings
3.5 etting Menu 4: Index Indicator Setting
3. ettings
The Index indicator () of bar graph is set here. Up to 4 measurement items can be set.
In the operation mode, press and simultaneously for 2 seconds or more, and the following operation
becomes available.
SET RESET
Set the set-up menu number to 4.
Setting menu
Set the measurement element to be assigned to 1.
Indicator item 1
non : No indicator display A : Current DA : Current demand V : Voltage W : Active power DW : Active power demand var : Reactive power cos : Power factor
Set the value of Index indicator 1. The setting range is as shown in the following table.
Measuring element Setting range Setting step (Note) A, DA 5 to 100 to 120(%) 1% V 25 to 100 to 135(%)
-120 to 100 to 120(%) -0.5 to 1 to 0.5
1% W, DW, var 1% cos 0.05
Note: A, DA, W, DW, and var show the percentage for the maximum scale value (0 step) . "V" shows the percentage for the VT primary voltage (or direct voltage).
Indicator value 1
Set the measurement items to be allowed to 2 - 4. Elements that are set elsewhere cannot be set.Indicator item 2 to 4
Set the indicator value for Indicators 2 to 4. Indicator value 2 to 4
DISPLAY SET
DISPLAY SET
SET
DISPLAY SET
DISPLAY SET
According to the setting flow diagram (page 11), save the changed contents, or continue to the other setting menu.
Setting menu
Display when "non" is selected
Display when "A" is selected
The setting method is same as that of Indicator item 1 .
The setting method is same as that of Indicator value 1 .
21
3.1 Setting Procedure
3. Settings
This section shows how to set the upper/lower limit alarm, backlight flickering during alarm, and motor starting current delay time. In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.
SET
For more details about each function, refer to the corresponding pages. Upper/lower limit alarm Page 53, Motor startup current Page 57
Set the Alarm item 1 to be allowed to measurement items. The upper/lower limit measurement values can be monitored by this setting.
Alarm item 1
Note 1. Measurement items that are not selected in the display pattern can be selected. Note 2. DA: Current demand, DAN: N-phase demand current, V (L-N): Phase to neutral voltage, V (L-L): phase to phase voltage, DW: Active power demand
non A upper limit A lower limit DA upper limit DA lower limit V upper limit V lower limit W upper limit W lower limit
DW upper limit DW lower limit var upper limit var lower limit cos upper limit cos lower limit Hz upper limit Hz lower limit Harmonic current total RMS value Harmonic voltage total distortion ratio
DISPLAY SET
DISPLAY SET
Set the set-up menu number to 5.
Setting menu
Display when "A upper limit" is selected
non A upper limit A lower limit AN upper limit DA upper limit DA lower limit DAN upper limit V (L-N) upper limit V (L-N) lower limit V (L-L) upper limit V (L-L) lower limit W upper limit W lower limit
DW upper limit DW lower limit var upper limit var lower limit cos upper limit cos lower limit Hz upper limit Hz lower limit Harmonic current total RMS value
Harmonic voltage total distortion ratio
N-phase harmonic current total RMS value
(b) For other phase wire system except three-phase 4-wire
(a) For three-phase 4-wire
RESET
Display when "non" is selected
3. ettings
22
3.6 Setting Menu 5: Setting the Upper/Lower Limit Alarm, Backlight Flickers During Alarms, and Motor Startup Current Delay Time
3.1 Setting Procedure
3. Settings
Set the alarm value for the upper/lower limit alarm items 2 to 4.
The setting method is the same as Alarm value 1 .Alarm value 2 to 4
Set the alarm mask time for when you want to prevent a momentary overload or noise alarm. When this is set, an alarm is generated only when the alarm value is over the upper/lower limit alarm value for a longer time than the delay time. On the setting screen, seconds are indicated by "s" and minutes are indicated by "M".Alarm delay time
Set the alarm cancel method at generation of alarm. (screen, relay)
Reset method (Set-up value)
Description (Refer to pages 53 and 54)
Automatic When there is no alarm generation condition, alarm is automatically reset.
Manual (HoLd)
The alarm will continue even when the alarm generated conditions no longer exist. It is necessary to execute button operation to cancel the alarm.
Alarm cancel method
DISPLAY SET
DISPLAY SET
DISPLAY SET
Note: When all settings for Alarm item 1 and Alarm item 2 to 4 are set to "non," this setting will be skipped.
Note: When all settings for Alarm item 1 and Alarm item 2 to 4 are set to "non," this setting will be skipped.
Set the measurement element assigned to the upper/lower limit alarm items 2 to 4. Elements that are set elsewhere cannot be set.
The setting method is the same as Alarm item 1 . Alarm item 2 to 4
DISPLAY SET
DISPLAY SET
Set the alarm value for upper/lower limit alarm element 1. The following table shows the setting range.
Measuring element Setting range Setting (Note) step
A, AN, DA, DAN upper limit 5 to 100 to 120(%) 3 to 10 to 95(%) 25 to 110 to 135(%) 20 to 70 to 95(%) -95 to 100 to 120(%) -120 to 3 to 95(%)
-0.05 to -0.5 to 0.05 -0.05 to 1 to 0.05
45 to 65 (Hz) 45 to 65 (Hz) 1 to 35 to 120(%) 1 to 35 to 120(%) 0.5 to 3.5 to 20(%)
1% A, DA lower limit 1% V (L-N), V (L-L) upper limit 1% V (L-N), V (L-L) lower limit 1% W, DW, var upper limit 1% W, DW, var lower limit 1% cos upper limit 0.05
0.05cos lower limit Hz upper limit 1Hz Hz lower limit 1Hz
Harmonic current total RMS value N-phase harmonic current total RMS value
1% 1%
Harmonic voltage total distortion ratio 0.5 Note: A, AN, DA, DAN, W, DW, and var show the percentage for the maximum scale value (0 step). "V" shows the percentage for the VT primary voltage (or direct voltage). (The "V" for 1-phase 3-wire is the percentage for 110V. Alarm monitoring is executed using twice the value which set upper/lower limit alarm for the 12-phase and 13-phase.)
Alarm value 1
(Auto)
0 seconds 5 seconds 10 seconds 20 seconds
30 seconds 40 seconds 50 seconds
1 minute
2 minutes 3 minutes 4 minutes 5 minutes
3. ettings
3.6 Setting Menu 5: Setting the Upper/Lower Limit Alarm, Backlight Flickers During Alarms, and Motor Startup Current Delay Time
23
3.1 Setting Procedure
3. Settings3. ettings
SET
By using this setting for motor current monitoring delay time, it is possible to prevent unnecessary maximum value updating and unnecessary alarms caused by the motor startup current.
When this setting is not needed Select "oFF" and press , and return to the Setting Menu.SET
When this setting is executed Select "on" and press , and go to (1) below.SET
(1) Motor starting current value.
Set the value for detecting the motor starting current.
Setting range Setting step (Note)
1%3 to 5 to 120(%)
* This is the percentage for the maximum scale value for the current (0 step).
(2) Motor starting current delay time After the motor starting current is detected, maximum value update is not executed and an alarm is not generated for the delay time. On the setting screen, seconds are indicated by "s" and minutes are indicated by "M".
Motor starting current delay time
oFF on
DISPLAY SET
1 s 3 s 5 s
10 s
15 s 20 s 30 s 45 s
1 M 1.5 M
2 M 3 M
4 M 5 M
According to the setting flow (page 11), save the changed contents, or continue to the other setting menu.
It is possible to make the backlight to flicker when an alarm is generated.
Backlight flickers during alarms
oFF on
DISPLAY SET
Setting menu
(Flicker)(Not flicker)
Note: When all settings for Alarm item 1 and Alarm item 2 to 4 are set to "non," this setting will be skipped.
24
3.6 Setting Menu 5: Setting the Upper/Lower Limit Alarm, Backlight Flickers During Alarms, and Motor Startup Current Delay Time
3.1 Setting Procedure
3. Settings
3.7 setting Menu 6: Setting the Analog Output and Pulse Output
Set the measurement item to be output to analog output CH1.
Select a measurement item for output from the following table.
Analog output CH1 output item
DISPLAY SET
DISPLAY SET
DISPLAY SET
Output item of analog output, pulse output, pulse unit and so forth are set here.
In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.
Setting menu
AVG: Average : Total RMS value
non A1
A2
A3
AN
AAVG (CH1) Demand A1
Demand A2
Demand A3
Demand AN
Demand AAVG
V1N
V2N
V3N
VAVG (L-N)(CH2) V12
V23
V31
VAVG (L-L)
W1
W2
W3
W (CH3) Demand W1
Demand W2
Demand W3
Demand W var1
var2
var3
var
VA1
VA2
VA3
VA
cos1
cos2
cos3
cos (CH4) Hz Harmonic A1
Harmonic A2
Harmonic A3
Harmonic AN
Harmonic V1N
Harmonic V2N
Harmonic V3N
3-phase 4-wire
SET RESET
Set the setting menu number to 6.
Analog output specification is displayed. (Cannot be changed)
Analog output specification
For current specification(4-20mA)
3. ettings
25
3.1 Setting Procedure
3. Settings
26
3.7 etting Menu 6: Setting the Analog Output and Pulse Output
DISPLAY
3-phase 3-wire (2CT, 3CT)
1-phase 3-wire (1N2 display)
1-phase 3-wire (1N3 display) 1-phase 2-wire
non A1 (CH1) A2
A3 Demand A1 Demand A2
Demand A3
VRS (CH2) V23 VT1
W (CH3) Demand W var cos (CH4) Hz Harmonic A1
A2(3CT)Harmonic Harmonic A3
Harmonic V12
Harmonic V23
non A1 (CH1) AN
A2 Demand A1 Demand AN
Demand A2
VRN (CH2) VN2 V12
W (CH3) Demand W var cos (CH4) Hz Harmonic A1 Harmonic A2
Harmonic V1N
Harmonic V2N
non A1 (CH1) AN
AT Demand A1 Demand AN
Demand A3
VRN (CH2) VNT VT1
W (CH3) Demand W var cos (CH4) Hz Harmonic A1 Harmonic A3
Harmonic V1N
Harmonic V3N
non A (CH1) Demand A V (CH2) W (CH3) Demand W var cos (CH4) Hz Harmonic A Harmonic V
SET
Note 1:The same measurement item can be set for each analog output. Note 2:It is possible to select measurement item that are not included in the set display pattern. Note 3:Setting to "non" are minimum output. In addition, it moves to the next analog output setting. Note 4:For the harmonic current, the total RMS value is output by a scale from 0 to 60% of the rating. For the harmonic voltage, the total distortion ratic is output by scaling 0 to 20%. Note 5:Underlined portions are the factory default settings for measurement elements assigned to each analog output.
3.1 Setting Procedure
3. Settings
3.7 etting Menu 6: Setting the Analog Output and Pulse Output
Analog output detailed set-up (The following setting can be made separately from the measurement items included in the display pattern.) (1) When the current / current demand / active power / active power demand / reactive power are set as output elements
(a) Set the measurement value for the maximum analog output value.
Output item Setting range
A Demand A
W Demand W
var
(b) Set the Singledeflection / dauble deflection / special deflection for analog output.
Output item Setting range
W Demand W
var
(c) For special deflection, set the measurement value for the minimum analog output value.
Output item Setting range
W Demand W
(2)
(3)
(4)
When voltage is set as an output item for 1-phase 3-wire Set V1N and V2N (V3N) for the maximum analog output value.
When power factor is set as an output item Set the power factor value for the maximum analog output values.
When the frequency is set as an output item Set the frequency range for analog output.
Analog output CH1 detailed setting
*1. When A or Demand A are set as output items, it moves to the next analog output settings. *2. When other than special deflection is selected, it moves to the next analog output settings. *3. Detailed setting values are according to the values shown in the table on pages 62 and 63.
0 STEP (100%: Rating)
-10 STEP (About 40%)
+3 STEP (About 120%)
0 STEP (100%: Rating)
-18 STEP (About 20%)
+3 STEP (About 120%)
mA
4 12 20
- 40kW 40kW0
mA
4
20
40kW0
mA
4
20
- 7.5kW 40kW0
0
STEP (About 25%)
STEP (About 100%)
-21
-15
STEP (About 15%)
DISPLAY SET
To next CH settings
*1
*2
mA
4 12 20
- 0.5 0.51.0
mA
4 12 20
- 0 01
Note: V12 (V13) is fixed at 300V.
150V mA
4
20
0 150
mA
4
20
0 300
- 0.5 to 1.0 to 0.5
- 0 to 1 to 0
mA
4 12 20
45Hz 55Hz50Hz
mA
4 12 20
55Hz 65Hz60Hz
45 to 50 to 55(Hz)
55 to 60 to 65(Hz)
DISPLAY SET
DISPLAY SET
DISPLAY SET
*3
*3
300V
to
to
to
to
to
to
Single deflection
Single deflection Dauble deflection
Dauble deflection
Special deflection
3. ettings
27
3.1 Setting Procedure
3. Settings
3.7 etting Menu 6: Setting the Analog Output and Pulse Output
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
Set the measurement item that is output to analog output CH2 to CH4.
The setting method is the same as Analog output CH1 output item .
Analog output CH2 to CH4 measurement item
Analog output CH2-CH4 detailed set-up
The setting method is the same as Analog output CH1 detailed setting . Analog output CH2 to CH4 detailed settings
Set analog output for when full scale is over the limit.
Setting value Description oFF
(No limit) For the span value, the maximum output is +5% and the minimum output is -5%.
on (Limited)
For the span value, the maximum output is +1% and the minimum output is -1%.
Note: When the output items for all analog output are set to "non," this setting is skipped.
Analog output limit
Set the item that is output to pulse output 1.
DisplaySetting value Section (A) Section (B) Section (C)
Active energy (Imported) OFF
Active energy (Exported) OFF
Reactive energy (Imported, Lag)
Reactive energy (Imported, Lead)
Reactive energy (Exported, Lag)
Reactive energy (Exported, Lead)
non (No output) OFF OFF
Pulse output 1 output item
Section (A) Section (B)
Section (C)
Note: The segment shown in the left table flickers according to the selected element.
Set the pulse value of pulse output 1. Pulse value is selected from the table below, according to total load [kW].
(CT Primary Current)(VT Primary Voltage)Total load [kW]= 1000
*1: For 1-phase 3-wire setting, the VT primary voltage is calculated using 110V. *2: For direct voltage setting, the direct voltage is used for calculation instead of the VT primary voltage. *3: For 3-phase 4-wire setting, the VT primary voltage is calculated using the phase to neutral voltage.
Display formatTotal load [kW] Digital display Multiplier
Possible pulse unit settings [kWh/pulse]
Less than 10 8888.88 1 1 0.1 0.01 0.001
10 or higher but less than 100 88888.8 1 10 1 0.1 0.01
100 or higher but less than 1000 88888.8 10 100 10 1 0.1
1000 or higher but less than 10000 88888.8 100 1000 100 10 1
10000 or higher but less than 100000 88888.8 1000 10000 1000 100 10
100000 or higher 88888.8 10000 100000 10000 1000 100
Note 1: When Pulse output 1 output item is set to "non," this setting will be skipped. Note 2: The factory default setting values are minimum values for the pulse unit that can be set. Note 3: For reactive power, kW in the above table needs to be read as kvar, and kWh needs to be read as kvarh.
Pulse output 1 pulse unit
: 1 1-phase 2-wire 2
3
1-phase 3-wire
3-phase 4-wire 3 3-phase 3-wire
3. ettings
28
3.1 Setting Procedure
3. Settings
3.7 etting Menu 6: Setting the Analog Output and Pulse Output
Set the element that is output to pulse output 2. (ME110SSR-4A2P) The same elements as pulse output 1 can be set.
The setting method is the same as Pulse output 1 output item . (Factory default setting value: Reactive energy (Imported, Lag)
Pulse output 2 output item
Set a pulse unit for pulse output 2. (ME110SSR-4A2P)
The setting method is the same as for Pulse output 1 pulse unit .
(Factory default setting values: Minimum possible value for pulse unit)
Pulse output 2 pulse unit
DISPLAY SET
DISPLAY SET
SET
Set the pulse width for output pulse. Set according to the input pulse conditions for the receiver.
Note When the pulse unit is set to the minimum value and the pulse width is set to 0.500s or 1.000s, the pulse output cannot follow if the load is too large, which can result in a decrease in the pulse output number.
Pulse width 0.125s 0.500s 1.000s
According to the setting flow (page 11), save the changed contents, or continue to the other setting menu.
Setting menu
3. ettings
29
3.1 Setting Procedure
3. Settings
In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.
Set the CC-Link station number.
Selectable station number: 1 to 64CC-Link station number
Set the CC-Link baud rate.
Set the CC-Link version according to the configuration of the used CC-LInk system.
CC-Link baud rates 156kbps 625kbps 2.5Mbps 5Mbps 10Mbps
Select a resolution monitorong data for power (reactive power).
To maintain data compatibility with multi-indicator instruments on our older products, select tyPE2. For details , please reter to the programming manuals.
Power data resolution tyPE1 (High resolution) tyPE2 (Conventional compatible)
When the changed abore settings are enabled, set to "on." (If this is not set to "on," the changed station number, baud rates, power data resolution and CC-Link version will not be applied.)
oFF on
DISPLAY SET
DISPLAY SET
DISPLAY SET
SET
DISPLAY SET
Set the set-up menu number to 7.
Setting menu
According to the setting flow diagram (page 11), save the changed contents, or continue to the other setting menu.
Setting Menu
Set whether to display the digital input status (DI1 to DI3). (ME110SSR-CH only)
When the display is set to on (displayed), the digital input status can be displayed on an additional screen of the display pattern.
Digital input status (DI1 to DI3) display oFF on
(Not displayed)(Displayed)
Set the digital input (DI1 to DI3) cance method. (ME110SSR-CH only)
Cancel method (Set-up value)
Description
Auto reset (Auto)
If the digital input turns off (open), the digital input status automatically turns off (open).
Latch (HoLd)
After it is detected that digital input is on (closed), digital input status is kept on (closed) until executing latch cancelation, even when the digital input turns off (open).
DISPLAY
DISPLAY SET
SET
DISPLAY SET
For ME110SSR-C, the following settings can be skipped.
Digital input reset method (DI1 to DI3)
SET RESET
(Ver.1 remote device) (Ver.2 remote device)
CC-Link version
Communication reset
3. ettings
3.8 etting Menu 7: Communication Set-up (ME110SSR-C,ME110SSR-CH)
30
3.1 Setting Procedure
3. Settings
3.8 etting Menu 7: Communication Set-up (ME110SSR-MB)
Set the ModBus address number.
Selectable addresses: 1 to 255ModBus address
Set the ModBus baud rate.
ModBus baud rates
2400bps 4800bps 9600bps 19.2kbps 38.4kbps
Set the ModBus parity.
ModBus parity
Set the ModBus stop bit.
ModBus stop bit Stop bit 1 Stop bit 2
To enable the changed address, baud rate, parity, and stop bit, select "on."
If you dont select "on", the changed address, baud rate, parity, and stop bit will not be applied.
Communication module reset
oFF on
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
DISPLAY SET
SET
Set the set-up menu number to 7.
Setting menu
According to the setting flow (page 11), save the changed contents, or continue to the other setting menu.
Setting menu
non odd EVEn ( )
In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.
SET RESET
3. ettings
31
3.1 Setting Procedure
3. Settings
3.9 setting Menu 8: Setting the Operating Time Display, CO2 Emission Display, and Element Information
This section shows how to set the operation time and CO2 emission display.
The current measurement time is calculated and is displayed as the load operation time. Select whether to display or not the operation time. (The operation time is calculated only when on is selected.)Operation time display
oFF on (Not displayed) (Displayed)
DISPLAY
DISPLAY
SET
DISPLAY SET
SET
SET
Set the set-up menu number to 8.
Setting menu
CO2 emissions are converted based on the active energy (imported) and are displayed. When CO2 emission display is needed
When CO2 emission display is not needed
Set a CO2 conversion factor. (Factory default setting: 0.555kg-CO2/kWh)
CO2 emission display
DISPLAY SET
Select a value using and for the blinking digit from the highest digit.
According to the setting flow (page 11), save the changed contents, or continue to the other setting menu.
Setting menu
It is possible to change the line element information for displaying.
(However, bar graph display is expressed using RSTN and 123N.)
The following is element information. Switch element information
RST 123 123 1N2 1N3123N UVW UVW UNV UNWUVWN RYB RYB RNY RNBRYBN ABC ABC ANB ANCABCN XYZ XYZ XNY XNZXYZN
RSTN
3P4W 3P3W 1P3W (1N2 display)
1P3W (1N3 display)
RST RNS RNT
123 UVW RYB ABC XYZ
SET
SET
oFF on (Not displayed) (Displayed)
+ -
SET
DISPLAY
SET
In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.
SET RESET
Select "on", press , and go to the following settings. Select "oFF", press , and go to the Set-up Menu.
Setting is possible within the range from 0.000 to 0.999 (kg-CO2/kWh). Use to move the setting digit (blinking digit) higher.
Use to move the setting digit (blinking digit) lower.
Press at the lowest digit to return to the Setting Menu.
3. ettings
32
3.1 Setting Procedure
3. Settings
3.10 Setting Value Con rmation Menu 1: Con rming the Setting Values for Setting Menu 1
This section shows how to confirm the setting values for Setting Menu 1 (phase wire system, display pattern, VT/direct voltage, CT primary current, etc.). When is pressed for at least 2 seconds in the operation mode, the following operation becomes available.
DISPLAY SET
DISPLAY SET
DISPLAY SET
Set the setting value confirmation menu number to 1.
Setting value confirmation menu
It is possible to confirm the model. The following table shows the display contents and corresponding model.
Display information Middle Bottom
Model
Blank ME110SSR ME110SSR-4AP ME110SSR-4APH ME110SSR-4A2P ME110SSR-C
ME110SSR-MB ME110SSR-CH
Model display
It is possible to confirm the setting values for the phase wire system and display pattern.
Phase wire system + display pattern
Phase wire system
Display pattern
Screen number Measurement items on the first screen from upper to lower
DISPLAY SET
DISPLAY SET
This continues according to the set number of screens. (Up to 4 screens)
A: Current specification (4-20mA)
SET
3. ettings
33
3.1 Setting Procedure
3. Settings
3.10 Setting Value Con rmation Menu 1: Con rming the Setting Values for Setting Menu 1
It is possible to confirm the set values for VT / direct voltage. When the phase wire system is 1P3W, this screen will be skipped.
It is possible to confirm the set values for CT secondary current (specified when ordered) and CT primary current.CT secondary current +
CT primary current
It is possible to confirm the set value for time constant for active power demand
It is possible to confirm the set value for time constant for carrent demand
When is pressed for at least 2 seconds in the operation mode, operation becomes possible. The screen transitions and operations are the same as for Setting Menus 2 to 8. Refer to Set-up Menus 2 to 8 (pages 18 to 32). (Note: Settings cannot be changed in the Setting value confirmation mode.)
DISPLAY SET
DISPLAY SET
DISPLAY SET
SET
Complete the set value confirmation or continue the set value confirmation using other set value confirmation menus according to the setting flow (page 13).Setting value
confirmation menu
VT / direct voltage
VT secondary voltage
VT primary voltage Direct voltage
CT secondary current
CT primary current
[For 3P4W]
SET
Time constant for active power demand
Time constant for current demand
3.11 Setting Value Con rmation Menus 2 to 8: Con rming the Setting Values for Setting Menus 2 to 8
3. ettings
34
3.1 Setting Procedure
3. Settings
3.12 Initializing Related Items by Changing Settings
3.13 Initializing All Settings
When a setting value is changed, the related setting items and measurement data (maximum/minimum values) will return to the default settings. Refer to the following list.
Menu 4 Menu 5
P hase w
ire system
D isplay pattern
D isplay pattern P
00 screen configuration
V T/direct voltage
C T prim
ary current
Indicator item
U pper/low
er lim it alarm
item
Phase wire system Display pattern
Display pattern P00 screen configuration VT/direct voltage
Current scale Power scale Power unit Reactive power scale Reactive power unit Indicator item Indicator value Upper/lower limit alarm item Upper/lower limit alarm value Analog output detailed settings
For A For DA For V (For 1P3W only) For W For VA
For DW For var
Harmonic current Maximum value
Setting item to be changed
Initialized item
Menu 1
S etting item
Menu 1
Menu 3
Menu 4
Menu 5
Menu 6 Output element
Harmonic voltage Maximum value
M easurem
ent data Current Maximum/minimum value Current demand Maximum/minimum value Voltage Maximum/minimum value Active power Maximum/minimum value Active power demand power Maximum/minimum value Reactive power Maximum/minimum value
Power factor Maximum/minimum value Frequency Maximum/minimum value
: This indicates that the setting value is the default value and the measurement data is zero. *1: This is the default value changing from 3P4W to others.
When the following operations are executed, all settings are initialized to the factory defaults. Only the settings are initialized to the defaults. Adjusted values (Test Mode Menu 2) and active energy values are not changed. To initialize all settings to the factory defaults, execute the following operation from the CANCEL screen in the setting mode. For more information about how to get to the CANCEL screen, refer to 3.1 Setting flow (page 11).
Setting mode Initialization completed
CANCEL screen Measurement screen
Press the + for 2 seconds.
For cos For Hz
Apparent power Maximum/minimum value
CT primary current
RESET PHASE
*1 *1
3. ettings
35
3.1 Setting Procedure
3. Settings
3.15 Setting the Special Display Pattern P00
Select P00 by or and press .
Even if there is no display pattern that you like in the display patterns P01 to P13 (P14, P15), individual set-up is available by the display pattern P00. This set-up is made in the setting menu 1. Explanation begins with the set P00 in display pattern of the setting menu 1 (page 13). (Others are omitted here, so refer to the setting menu 1.)
The number of settable display is up to 4. And the number of measurement elements to be displayed is up to 12 items.
Upper stage: measurement item 1
Middle stage: measurement item 2
Lower stage: measurement item 3
Upper stage: measurement item 4
Middle stage: measurement item 5
Lower stage: measurement item 6
Upper stage: measurement item 7
Middle stage: measurement item 8
Lower stage: measurement item 9
Upper stage: measurement item 10
Middle stage: measurement item 11
Lower stage: measurement item 12
Screen 4-1
Screen 2-1 Screen 2-2
Screen 4-2 Screen 4-3 Screen 4-4
DISPLAY DISPLAY DISPLAY DISPLAY
Explanation is made with the example of the following display pattern.
Setting method
DISPLAY DISPLAY
Upper stage: A Middle stage: V Lower stage: Wh
Upper stage: cos Middle stage: DW Lower stage: Not displayed
Display pattern
Set the display pattern.
1) Select P00 .
SET
2) Set the upper stage of the display 4-1 to A.
Note: Set the stage where "" is flickering. (This is same to the following explanations.)
3) Set the middle stage of the display 4-1 to V.
4) Set the lower stage of the display 4-1 to Wh.
SET
SET
SET
SET
Select A by or and press .SET
Select V by or and press .SET
Select Wh by or and press .SET
3. ettings
36
3.1 Setting Procedure
3. Settings
3.15 Setting the Special Display Pattern P00
5) Set the display of the display 4-2.
6) Set the upper stage of the display 4-2 to cos.
7) Set the middle stage of the display 4-2 to DW.
8) Set the lower stage of the display 4-2 to no display. Set the unit code of the lower stage to no display by or and press .
Note: When the display 4-3 is set to no display, the display 4-4 is also set to no display automatically.
When not to display the display 2, select no and press .
9) Set the display 4-3 to no display.
SET
SET
SET
SET
SET
VT / direct voltage (hereafter same as the setting menu 1)
1. The following measurement items cannot be set by the display pattern P00. Set them separately in the setting menu 3 (page 19) or setting menu 8 (page 32).
2. Phase cannot be specified by current, voltage. Press PHASE in the operation mode to change phase.
3. Active energy(Exported), and reactive energy cannot be displayed at the upper stage and the middle stage. Active energy (Imported) cannot be set to the top line.
4. For settings other than 3-phase 4-wire, the following measurement elements cannot be set. N-phase current, N-phase demand current, and apparent power.
Exported active energy, exported reactive energy, capacitive reactive energy, inductive reactive energy, harmonic current, harmonic voltage, operation time, and CO2 emission
Note
SET
SET
Select yES by or and press .SET
Select cos by or and press .SET
Select cos by or and press .SET
Select no by or and press .SET
37
3.1 Setting Procedure
3. Set-up
6 Examples of Simple Settings
Setting menu
Phase wire system
SETDisplay pattern
SETVT/direct voltage selection
SET ( keys)Direct voltage
SET ( keys)CT primary current
SETTime constant for active power demand
Set the setting menu number to "6" and then press .
Model: ME110SSR-4APH(4-20mA specification) Phase wire system: 3-phase 4-wire Measuring element: AAVG, VAVG(L-N), W, cos
Direct voltage: 254V/440V CT primary current: 200A Active power scale: 160kW (Standard: Rating 100%) Analog output: CH1(AAVG, 200A), CH2(VAVG(L-N)), CH3(W, 160kW), CH4(cos ), no output limit Pulse output: Electric energy (power reception), pulse unit (1kWh/pulse)
Operation mode
Setting menu
SET RESET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
Time constant for current demand
Press and at the same time for 2 seconds
Setting Example The following shows a simple setting example.
Note: For more details about setting contents, refer to pages 13 to 32.
SETSet the setting menu number to "1" and then press .
SET
The factory default setting is "P04," so just press .
The factory default setting is "No VT," so just press .
Set VL-N to "254V" and then press .
Set to "200A" and then press .
The factory default setting is "0 second," so just press .
The factory default setting is "0 second," so just press .
The factory default setting is "3-phase 4-wire," so just press .
Setting Procedure Items of which setting value need to be changed are indicated by .
38
tings
3.1 Setting Procedure
3. Set-up
6 Examples of Simple Settings
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
Analog output 1 item
Analog output 1 detailes setup
Analog output 2 item
The factory default setting is "W," so just press .Analog output 3 item
Analog output 3 detailed setup
Analog output 3 detailed setup
Analog output limit
Pulse output 1
( keys)Pulse output 1 pulse unit
Pulse width
Setting menu
Press again. The changed setting are determined.End screen
Measurement begins according to the settings you changed.Operation mode
Analog output 4 detailed setup
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
Analog output 4 element
Analog output specification "4-20A" is displayed, so just press .
The factory default setting is "AAVG," so just press .
This is "200.0A," so just press .
The factory default setting is "Active Energy (Imported)," so just press .
The factory default setting is "VAVG (L-N)," so just press .
This is "160.0kW," so just press .
The factory default setting is "Single deflection," so just press .
The factory default setting is "cos," so just press .
The factory default setting is "-0.5 to 1 to 0.5," so just press .
The factory default setting is "oFF," so just press .
Set to "1kWh/pulse" and then press .
The factory default setting is "0.125 second," so just press .
Set the set-up menu number to "End" and then press .
39
tings
4. Using Test Mode
Test mode includes functions that can be used for start-up of equipment. The following table shows what can be done in the test mode.
Test menu Description
1. Incorrect wiring determination support display
Displays the phase angle for the current/voltage and active energy/voltage/current for each phase. By confirming each displayed value, it is easier to determine whether there is incorrect wiring at connections for measurement (voltage/current) input.
2. Zero span adjustment for analog output
For functions with analog output, zero span adjustment can be done for analog output. Adjust this when matching with the receiver side and when output changes.
3. Analog output operation test For functions with analog output, it is possible to confirm analog output operation without measurement (voltage/current) input. Use this for confirming connection with the receiver.
4. Pulse output operation test For functions with pulse output, it is possible to confirm pulse output operation without measurement (voltage/current) input. Use this for confirming connection with the receiver.
Test Procedure
SET
SET
Press for 2 seconds to move to the set value confirmation mode.
Select setting value confirmation menu number "9" by and
to move to test mode.
Execute tests using each test menu. (Refer to pages 41 to 46)
Press
Test Mode Flow
SET
SET
Test menu
End
Test menu 1 (Incorrect wiring determination)
Test menu 2 (Analog output adjustment)
Test menu 3 (Analog output test)
Test menu 4 (Pulse output test)
Test menu 5 (Alarm output test)
Test menu 6 (Communication test)
Setting value confirmation menu "9"
Operation mode
Test mode
(Note) (Note) The screen momentarily turns off.
For models with a communication function, it is possible to monitor fixed numerical data without measurement (voltage/current) input. Use this for checking with the host system.
6. Communication test
For functions with alarm output, it is possible to confirm alarm output (contact point output) without measurement (voltage/current) input. Use this for confirming connection with the contacted device.
Alarm output operation test5.
40
5. Operation
3.2 Setting Menu 1
4. Using Test Mode
4.1 Test Menu 1: Incorrect Wiring Determination Support Display
In the setting value confirmation mode, when the menu number is set to "9", you will enter the test mode. (You cannot enter from the set-up mode.) The following operations are available in the test mode.
Set the test menu number to "1".
Test menu
Phase angle display, active power display, voltage display, and current display are shown. <3-phase 4-wire example>
Display example of Incorrect wiring support function For more information about display examples of each kind of Incorrect wiring, refer to pages 42 and 43.
V16
I1
I3
I1
I3
I2 I2
SET
SET
Test menu
V12 V1N
V23 V2N or V3N
I3 I2 or I3
<3-phase 3-wire example>
Current display
Power display
Active power display
Voltage display
Voltage display (Phase voltage)
Current display
Phase angle display (Current)
Phase angle display (Current)
Phase angle display (Voltage)
Phase angle display (Voltage)
About the phase angle The phase angle is displayed clockwise based on V12 as the standard (0 degree).
V23
V23
V23 I1 I2 I3 : Phase angle between I3 and V12
Note: For 1-phase 3-wire, the phase needs to be read according to the following.
: Phase angle between I2 and V12 : Phase angle between I1 and V12 : Phase angle between V23 and V12
Select "End" as the test menu number and then press .SET You will return to the operation mode.
Incorrect wiring determination support display
41
5. Operation
3.2 Setting Menu 14.1 Test Menu 1: Improper Wiring Determination Support Display
4. Using Test Mode
ncorrect
No.
Normal
1
2
3
4
5
Power Factor (Input)
LEAD 0.707
LEAD 0.866
1.000
LAG 0.866
LAG 0.707
LEAD 0.707
LEAD 0.866
1.000
LAG 0.866
LAG 0.707
LEAD 0.707
LEAD 0.866
1.000
LAG 0.866
LAG 0.707
LEAD 0.707
LEAD 0.866
1.000
LAG 0.866
LAG 0.707
LEAD 0.707
LEAD 0.866
1.000
LAG 0.866
LAG 0.707
LEAD 0.707
LEAD 0.866
1.000
LAG 0.866
LAG 0.707
Phase Angle Display
V12 V23 I1 I3 W1
225
240
270
300
315
45
60
90
120
135
45
60
90
120
135
225
240
270
300
315
345
0
30
60
75
105
120
150
180
195
345
0
30
60
75
165
180
210
240
255
165
180
210
240
255
165
180
210
240
255
225
240
270
300
315
225
240
270
300
315
W1>W 3
W1=W 3
W1
W1=W3=0
W1=0
For Balanced Loading (V12=V23, I1=I3)
Active Power Display
W3 V12 V23 V31 I1
0
0
0
0
0
0
300
60
120
300
300
300
V12 =V 23 =V 31
V12 =V 23 =V 31
V12 =V23
V12 =V 23 =V 31
V12 =V 23 =V 31
V12 =V23 =V 31
I1=I 2 =I 3
I1=I 2 =I 3
I1=I 2 =I 3
I1=I 3
Using Test Mode
2 T s Menu 2: Zero Span Adjustment for Analog Output (ME110SSR-4AP, -4APH, -4A2P)
3 T s Menu 3: Analog Output Operation Test (ME110SSR-4AP, -4APH, -4A2P)
Using Test Mode
4 T s Menu 4: P lse Output Operation Test (ME110SSR-4AP, -4APH, -4A2P)
Using Test Mode
6 T s Menu 6: Communication Test (ME110SSR-C, -CH, -MB)
Using Test Mode
Bas c Operation
Operation
Bas c Operation
Operation
Operation
Bas c Operation
Bas c Operation
Operation
Bas c Operation
Operation
Bas c Operations
Operation
2 Usage According to Purpose
Operation
2 Usage According to Purpose
Operation
2 Usage According to Purpose
Operation
2 Usage According to Purpose
Operation
Possible cause Solution
isplay
easurem
peration
ther
Item Specications
Item Specications
Country/Region Corporation Name Address Telephone
Related manuals for Mitsubishi ME110SSR-C Measuring Instrument User's Manual V2
Manualsnet FAQs
If you want to find out how the ME110SSR-C Mitsubishi works, you can view and download the Mitsubishi ME110SSR-C Measuring Instrument User's Manual V2 on the Manualsnet website.
Yes, we have the User's Manual for Mitsubishi ME110SSR-C as well as other Mitsubishi manuals. All you need to do is to use our search bar and find the user manual that you are looking for.
The User's Manual should include all the details that are needed to use a Mitsubishi ME110SSR-C. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.
The best way to navigate the Mitsubishi ME110SSR-C Measuring Instrument User's Manual V2 is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.
This Mitsubishi ME110SSR-C Measuring Instrument User's Manual V2 consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.
You can download Mitsubishi ME110SSR-C Measuring Instrument User's Manual V2 free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.
To be able to print Mitsubishi ME110SSR-C Measuring Instrument User's Manual V2, simply download the document to your computer. Once downloaded, open the PDF file and print the Mitsubishi ME110SSR-C Measuring Instrument User's Manual V2 as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.