Contents

Mitsubishi MR-J4-DU-B-RJ Drive Unit Instruction Manual PDF

1 of 372
1 of 372

Summary of Content for Mitsubishi MR-J4-DU-B-RJ Drive Unit Instruction Manual PDF

General-Purpose AC Servo

Power Regeneration Converter Unit MODEL

MR-CV_ Resistance Regeneration Converter Unit MODEL

MR-CR55K_ SSCNET /H Interface Drive Unit MODEL

MR-J4-DU_B_(-RJ) General-Purpose Interface Drive Unit MODEL

MR-J4-DU_A_(-RJ) INSTRUCTION MANUAL

F

A - 1

Safety Instructions Please read the instructions carefully before using the equipment.

To use the equipment correctly, do not attempt to install, operate, maintain, or inspect the equipment until you have read through this Instruction Manual, Installation guide, and appended documents carefully. Do not use the equipment until you have a full knowledge of the equipment, safety information and instructions. In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION". WARNING Indicates that incorrect handling may cause hazardous conditions,

resulting in death or severe injury. CAUTION Indicates that incorrect handling may cause hazardous conditions,

resulting in medium or slight injury to personnel or may cause physical damage.

Note that the CAUTION level may lead to a serious consequence depending on conditions. Please follow the instructions of both levels because they are important to personnel safety. What must not be done and what must be done are indicated by the following diagrammatic symbols.

Indicates what must not be done. For example, "No Fire" is indicated by .

Indicates what must be done. For example, grounding is indicated by .

In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so on are classified into "POINT". After reading this Instruction Manual, keep it accessible to the operator.

A - 2

1. To prevent electric shock, note the following

WARNING Before wiring, turn off the power and wait for 20 minutes or more until the charge lamp turns off. Then, confirm that the voltage between L+ and L- is safe with a voltage tester or others. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp is off or not, be sure to look at the lamp from the front of the converter unit. Ground the converter unit, drive unit, and servo motor securely. Any person who is involved in wiring and inspection should be fully competent to do the work. Do not attempt to wire the converter unit, drive unit, and servo motor until they have been installed. Otherwise, it may cause an electric shock. Do not operate switches with wet hands. Otherwise, it may cause an electric shock. The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric shock. During power-on or operation, do not open the front cover of the converter unit and the drive unit. Otherwise, it may cause an electric shock. Do not operate the converter unit and the drive unit with the front cover removed. High-voltage terminals and charging area are exposed and you may get an electric shock. Except for wiring or periodic inspection, do not remove the front cover of the converter unit and the drive unit even if the power is off. The converter unit and the drive unit are charged, and you may get an electric shock. To prevent an electric shock, be sure to connect the protective earth (PE) terminal (marked ) of the converter unit and the drive unit to the protective earth (PE) of the cabinet. To avoid an electric shock, insulate the connections of the power supply terminals.

2. To prevent fire, note the following

CAUTION Install the converter unit, the drive unit, the servo motor, and the regenerative resistor on incombustible material. Installing them directly or close to combustibles will lead to smoke or a fire. Be sure to connect a magnetic contactor between the power supply and the main circuit power supply (L1/L2/L3) of the converter unit, in order to configure a circuit that shuts off the power supply by the magnetic contactor. If the magnetic contactor is not connected, a continuous flow of a large current may cause smoke or a fire when the converter unit or the drive unit malfunctions. Be sure to connect a magnetic contactor for each converter unit between the power supply and the main circuit power supply (L1/L2/L3) of the converter unit, in order to configure a circuit that shuts off the power supply by the magnetic contactor. If a molded-case circuit breaker or fuse is not connected, a continuous flow of a large current may cause smoke or a fire when the converter unit malfunctions. When using the regenerative resistor, shut the power off with an alarm signal. Otherwise, a regenerative transistor malfunction or the like may overheat the regenerative resistor, causing smoke or a fire. Provide adequate protection to prevent screws and other conductive matter, oil and other combustible matter from entering the converter unit, the drive unit, and the servo motor.

3. To prevent injury, note the following

CAUTION Only the power/signal specified in the Instruction Manual should be applied to each terminal. Otherwise, it may cause an electric shock, fire, injury, etc. Connect cables to the correct terminals. Otherwise, a burst, damage, etc., may occur. Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc., may occur. The heat sink of the converter unit and drive unit, the regenerative resistor, the servo motor, etc. may be hot while power is on and for some time after power-off. Take safety measures such as providing covers to avoid accidentally touching them by hands and parts such as cables.

A - 3

4. Additional instructions The following instructions should also be fully noted. Incorrect handling may cause a malfunction, injury, electric shock, fire, etc. (1) Transportation and installation

CAUTION Transport the products correctly according to their mass. Use the eyebolts of the converter unit and of the drive unit only for transporting. Do not use the eyebolts for transporting with the converter unit and the drive unit mounted on a machine. Do not overtighten the eyebolts of the converter unit and of the drive unit. Tightening too hard may damage the tap. Stacking in excess of the specified number of product packages is not allowed. Do not hold the front cover, cables, or connectors when carrying the converter unit and drive unit. Otherwise, it may drop. Install the converter unit, the drive unit, and the servo motor in a load-bearing place in accordance with the Instruction Manual. Do not get on or put heavy load on the product. Otherwise, it may cause injury. The equipment must be installed in the specified direction. Maintain specified clearances between the converter unit/drive unit and the inner surfaces of a control cabinet or other equipment. Do not install or operate the converter unit, the drive unit, and the servo motor which have been damaged or have any parts missing. Do not block the intake and exhaust areas of the converter unit and the drive unit. Otherwise, it may cause a malfunction. Do not drop or apply heavy impact on the converter units, the drive units, and the servo motors. Otherwise, it may cause injury, malfunction, etc. Do not strike the connector. Otherwise, it may cause a connection failure, malfunction, etc. When you keep or use the equipment, please fulfill the following environment.

Item Environment Ambient

temperature Operation 0 C to 55 C (non-freezing)

Storage -20 C to 65 C (non-freezing) Ambient

humidity Operation

5 %RH to 90 %RH (non-condensing)

Storage Ambience Indoors (no direct sunlight), free from corrosive gas, flammable gas, oil mist, dust, and dirt Altitude 2000 m or less above sea level (Contact your local sales office for the altitude for options.) Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (X, Y, Z axes)

When the product has been stored for an extended period of time, contact your local sales office. When handling the converter unit and the drive unit, be careful with the sharp edges of the converter unit and drive unit. The converter unit and the drive unit must be installed in a metal cabinet. When fumigants that contain halogen materials, such as fluorine, chlorine, bromine, and iodine, are used for disinfecting and protecting wooden packaging from insects, they cause a malfunction when entering our products. Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products, or treat packaging with methods other than fumigation, such as heat treatment. Additionally, disinfect and protect wood from insects before packing the products. To prevent a fire or injury in case of an earthquake or other natural disasters, securely install, mount, and wire the servo motor in accordance with the Instruction Manual.

A - 4

(2) Wiring

CAUTION Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly. Make sure to connect the cables and connectors by using the fixing screws and the locking mechanism. Otherwise, the cables and connectors may be disconnected during operation. Do not install a power capacitor, surge killer, or radio noise filter (optional FR-BIF(-H)) on the drive unit output side. To avoid a malfunction of the servo motor, connect the wires to the correct phase terminals (U/V/W) of the drive unit and the servo motor. Connect the drive unit power outputs (U/V/W) to the servo motor power inputs (U/V/W) directly. Do not connect a magnetic contactor and others between them. Otherwise, it may cause a malfunction.

U Servo motor

MV

W

U

V

W

U

MV

W

U

V

W

Drive unit Servo motorDrive unit

The connection diagrams in this Instruction Manual are shown for sink interfaces, unless stated otherwise. Install the surge absorbing diode to the DC relay for control output signals in the converter unit and the drive unit in the specified direction. Otherwise, the converter unit and the drive unit will malfunction and will not output signals, disabling the emergency stop and other protective circuits.

DOCOM 24 V DC

Converter unit Drive unit

RA

For sink output interface

Control output signal

DOCOM

Control output signal

24 V DC

Converter unit Drive unit

RA

For source output interface

When the wires are not tightened enough to the terminal block, the wires or terminal block may generate heat because of the poor contact. Be sure to tighten the wires with specified torque. Connecting a servo motor of the wrong axis to U, V, W, or CN2 of the drive unit may cause a malfunction. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM2 or EM1 when the main circuit power is turned off. To prevent malfunction, avoid bundling the power lines (input/output) of the converter unit and the signal cables together or running them in parallel to each other. Separate the power lines from the signal cables.

(3) Test run and adjustment

CAUTION When executing a test run, follow the notice and procedures in this instruction manual. Otherwise, it may cause a malfunction, damage to the machine, or injury. Before operation, check and adjust the parameter settings. Improper settings may cause some machines to operate unexpectedly.

A - 5

CAUTION Never make a drastic adjustment or change to the parameter values as doing so will make the operation unstable. Do not get close to moving parts during the servo-on status.

(4) Usage

CAUTION For equipment in which the moving part of the machine may collide against the load side, install a limit switch or stopper to the end of the moving part. The machine may be damaged due to a collision. Do not disassemble, repair, or modify the product. Otherwise, it may cause an electric shock, fire, injury, etc. Disassembled, repaired, and/or modified products are not covered under warranty. Before resetting an alarm, make sure that the run signal of the drive unit is off to prevent a sudden restart. Otherwise, it may cause an accident. Use a noise filter, etc., to minimize the influence of electromagnetic interference. Electromagnetic interference may affect the electronic equipment used near the converter unit and the drive unit. Do not burn or destroy the converter unit and the drive unit. Doing so may generate a toxic gas. Use the converter unit and the drive unit with the specified servo motor. Correctly wire options and peripheral equipment, etc. in the correct combination. Otherwise, it may cause an electric shock, fire, injury, etc. The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used for ordinary braking. For such reasons as incorrect wiring, service life, and mechanical structure (e.g. where a ball screw and the servo motor are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety, install a stopper on the machine side. If the dynamic brake is activated at power-off, alarm occurrence, etc., do not rotate the servo motor by an external force. Otherwise, it may cause a fire.

(5) Corrective actions

CAUTION Ensure safety by confirming the power off, etc. before performing corrective actions. Otherwise, it may cause an accident. If it is assumed that a power failure, machine stoppage, or product malfunction may result in a hazardous situation, use a servo motor with an electromagnetic brake or provide an external brake system for holding purpose to prevent such hazard. When an alarm occurs, eliminate its cause, ensure safety, and deactivate the alarm to restart operation. If the molded-case circuit breaker or fuse is activated, be sure to remove the cause and secure safety before switching the power on. If necessary, replace the converter unit and drive unit, and recheck the wiring. Otherwise, it may cause smoke, fire, or an electric shock. Provide an adequate protection to prevent unexpected restart after an instantaneous power failure. To prevent an electric shock, injury, or fire from occurring after an earthquake or other natural disasters, ensure safety by checking conditions, such as the installation, mounting, wiring, and equipment before switching the power on.

A - 6

CAUTION Configure an electromagnetic brake circuit which is interlocked with an external emergency stop switch.

Servo motor

Electromagnetic brake

B

RA

Contacts must be opened with the emergency stop switch.

Contacts must be opened when ALM (Malfunction) or MBR (Electromagnetic brake interlock) turns off.

24 V DC

(6) Maintenance, inspection and parts replacement

CAUTION Make sure that the emergency stop circuit operates properly such that an operation can be stopped immediately and a power is shut off by the emergency stop switch. It is recommended that the converter unit and the drive unit be replaced every 10 years when it is used in general environment. When using a converter unit or a drive unit whose power has not been turned on for a long time, contact your local sales office.

(7) General instruction

To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn without covers and safety guards. When the equipment is operated, the covers and safety guards must be installed as specified. Operation must be performed in accordance with this Instruction Manual.

A - 7

DISPOSAL OF WASTE Please dispose a servo amplifier and other options according to your local laws and regulations.

EEP-ROM life

The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If the total number of the following operations exceeds 100,000, the converter unit and the drive unit may malfunction when the EEP-ROM reaches the end of its useful life.

Write to the EEP-ROM due to parameter setting changes Write to the EEP-ROM due to device changes Home position setting in the absolute position detection system (MR-J4-DU_A_(-RJ))

STO function of the drive unit

When using the STO function of the drive unit, refer to chapter 13 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" or "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". For the MR-J3-D05 safety logic unit, refer to app. 5 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" or "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". Compliance with global standards

Refer to section 10.2 for the compliance with global standards.

A - 8

About the manual

You must have this Instruction Manual and the following manuals to use this servo. Be sure to prepare all the instruction manuals necessary to use the servo safely. Power resistance regeneration converter units and resistance regeneration converter units are written as converter units in this manual under certain circumstances, unless otherwise stated.

Relevant manuals

Manual name Manual No.

MELSERVO MR-J4-_A(-RJ) Servo Amplifier Instruction Manual (Note 1) SH(NA)030107ENG MELSERVO MR-J4-_B(-RJ) Servo Amplifier Instruction Manual (Note 2) SH(NA)030106ENG MR-J4-_A_-RJ Servo Amplifier Instruction Manual (Positioning Mode) (Note 4) SH(NA)030143ENG MR-J4-_A_-RJ Servo Amplifier Instruction Manual (Modbus RTU Protocol) (Note 5) SH(NA)030175ENG MELSERVO-J4 Servo Amplifier Instruction Manual (Troubleshooting) SH(NA)030109ENG MELSERVO Servo Motor Instruction Manual (Vol. 3) SH(NA)030113ENG MELSERVO Linear Servo Motor Instruction Manual (Note 6) SH(NA)030110ENG MELSERVO Linear Encoder Instruction Manual (Note 3) SH(NA)030111ENG MELSERVO EMC Installation Guidelines IB(NA)67310ENG MELSERVO MR-D30 Instruction Manual (Note 7) SH(NA)030132ENG

Note 1. It is necessary for using an MR-J4-DU_A_(-RJ) drive unit. 2. It is necessary for using an MR-J4-DU_B_(-RJ) drive unit. 3. It is necessary for using the fully closed loop system. 4. It is necessary for using an MR-J4-DU_A_-RJ drive unit in the positioning mode. 5. It is necessary for using the Modbus RTU communication function. 6. It is necessary for using a linear servo motor. 7. It is necessary for using an MR-D30 functional safety unit.

This Instruction Manual does not describe the following items. The following are the same as those for MR-J4-_(-RJ). For the details of the items, refer to each chapter/section indicated in the detailed explanation field. "MR-J4-_B_" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

Model Item Detailed explanation

MR-J4-DU_B_(-RJ) NORMAL GAIN ADJUSTMENT MR-J4-_B_ chapter 6 SPECIAL ADJUSTMENT FUNCTIONS (Note) MR-J4-_B_ chapter 7 ABSOLUTE POSITION DETECTION

SYSTEM MR-J4-_B_ chapter 12

USING STO FUNCTION MR-J4-_B_ chapter 13 USING A LINEAR SERVO MOTOR MR-J4-_B_ chapter 14 FULLY CLOSED LOOP SYSTEM MR-J4-_B_ chapter 16 APPLICATION OF FUNCTIONS MR-J4-_B_ chapter 17 MR-J4-DU_A_(-RJ) NORMAL GAIN ADJUSTMENT MR-J4-_A_ chapter 6 SPECIAL ADJUSTMENT FUNCTIONS (Note) MR-J4-_A_ chapter 7 ABSOLUTE POSITION DETECTION

SYSTEM MR-J4-_A_ chapter 12

USING STO FUNCTION MR-J4-_A_ chapter 13 COMMUNICATION FUNCTION (MITSUBISHI

ELECTRIC GENERAL-PURPOSE AC SERVO PROTOCOL)

MR-J4-_A_ chapter 14

FULLY CLOSED LOOP SYSTEM MR-J4-_A_ chapter 17

Note. Refer to chapter 9 in this Instruction Manual for the compatibility with the SEMI-F47 standard.

A - 9

Cables used for wiring

Wires mentioned in this Instruction Manual are selected based on an ambient temperature of 40 C. Contents of the package

Unpack the converter unit and the drive unit, and check the rating plates to see if the units are as you ordered.

(1) Power regeneration converter unit

Contents Quantity

Power regeneration converter unit 1 Eyebolt (for 55 kW or more) 2 Magnetic contactor wiring connector 1 MELSERVO-J4 Series Instructions and Cautions for Safe Use of AC Servos 1

(2) Resistance regeneration converter unit

Contents Quantity

Resistance regeneration converter unit 1 Eyebolt 2 Digital I/O connector 1 MELSERVO-J4 Series Instructions and Cautions for Safe Use of AC Servos 1

(3) Drive unit

Contents Quantity

Drive unit 1 Bus bar (for 30 kW or more) 2 Eyebolt (for 30 kW or more) 2 MELSERVO-J4 Series Instructions and Cautions for Safe Use of AC Servos 1

A - 10

MEMO

1

CONTENTS

1. FUNCTIONS AND CONFIGURATION 1- 1 to 1-28

1.1 Summary ........................................................................................................................................... 1- 1 1.2 Model designation ............................................................................................................................. 1- 2

1.2.1 MR-CV_ power regeneration converter unit .............................................................................. 1- 2 1.2.2 MR-CR_ resistance regeneration converter unit ........................................................................ 1- 3 1.2.3 Drive unit .................................................................................................................................... 1- 4

1.3 Combinations of converter units, drive units and servo motors ........................................................ 1- 5 1.3.1 Combinations of the power regeneration converter unit and drive unit ..................................... 1- 5 1.3.2 Combinations of the resistance regeneration converter unit and drive unit .............................. 1-11 1.3.3 Combinations of drive unit and servo motors .......................................................................... 1-12

1.4 Standard specifications .................................................................................................................... 1-13 1.4.1 MR-CV_ power regeneration converter unit ............................................................................. 1-13 1.4.2 MR-CR_ resistance regeneration converter unit ....................................................................... 1-15 1.4.3 Drive unit ................................................................................................................................... 1-16

1.5 Function list ...................................................................................................................................... 1-24 1.6 Configuration including peripheral equipment ................................................................................. 1-25

1.6.1 MR-CV_ power regeneration converter unit ............................................................................. 1-25 1.6.2 MR-CR_ resistance regeneration converter unit ....................................................................... 1-27

2. INSTALLATION 2- 1 to 2- 8

2.1 Installation direction and clearances ................................................................................................. 2- 2 2.1.1 When using MR-CV_ power regeneration converter unit .......................................................... 2- 2 2.1.2 When using MR-CR_ resistance regeneration converter unit ................................................... 2- 5

2.2 Keeping out of foreign materials ....................................................................................................... 2- 6 2.3 Inspection items ................................................................................................................................ 2- 6 2.4 Parts having service life .................................................................................................................... 2- 7 2.5 Restrictions when using this product at altitude exceeding 1000 m and up to 2000 m

above sea level ................................................................................................................................. 2- 8

3. MR-CV_ POWER REGENERATION CONVERTER UNIT 3- 1 to 3-82

3.1 Function block diagram ..................................................................................................................... 3- 2 3.2 Structure (parts identification) ........................................................................................................... 3- 4 3.3 Signals and wiring ............................................................................................................................. 3- 7

3.3.1 Connection example of power circuit ......................................................................................... 3- 8 3.3.2 Explanation of power supply system ......................................................................................... 3-34 3.3.3 Connectors and pin assignment ................................................................................................ 3-41 3.3.4 Signal (device) explanations ..................................................................................................... 3-45 3.3.5 Alarm occurrence timing chart .................................................................................................. 3-46 3.3.6 Forced stop in the power regeneration converter unit .............................................................. 3-55 3.3.7 Interfaces ................................................................................................................................... 3-59 3.3.8 Grounding .................................................................................................................................. 3-61

3.4 Startup.............................................................................................................................................. 3-62 3.4.1 Switching power on for the first time ......................................................................................... 3-63 3.4.2 Startup ....................................................................................................................................... 3-66 3.4.3 Switch setting and operation section of power regeneration converter unit ............................. 3-67

3.5 Characteristics ................................................................................................................................. 3-71

2

3.5.1 Overload protection characteristics ........................................................................................... 3-71 3.5.2 Power supply capacity and generated loss ............................................................................... 3-74 3.5.3 Inrush currents at power-on of the main circuit and control circuit power supplies .................. 3-77

3.6 Disabling the protection coordination mode (stand-alone drive) ..................................................... 3-78 3.6.1 200 V class ................................................................................................................................ 3-79 3.6.2 400 V class ................................................................................................................................ 3-81

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT 4- 1 to 4-66

4.1 Function block diagram ..................................................................................................................... 4- 2 4.2 Structure ........................................................................................................................................... 4- 6

4.2.1 Parts identification ...................................................................................................................... 4- 6 4.2.2 Opening and closing of the terminal block cover ....................................................................... 4- 7

4.3 Signals and wiring ............................................................................................................................ 4-11 4.3.1 Input power supply circuit .......................................................................................................... 4-12 4.3.2 Explanation of power supply system ......................................................................................... 4-23 4.3.3 Connectors and pin assignment ................................................................................................ 4-28 4.3.4 Signal (device) explanations ..................................................................................................... 4-29 4.3.5 Alarm occurrence timing chart .................................................................................................. 4-30 4.3.6 Forced stop in the resistance regeneration converter unit ........................................................ 4-38 4.3.7 Interfaces ................................................................................................................................... 4-42 4.3.8 Grounding .................................................................................................................................. 4-44

4.4 Startup.............................................................................................................................................. 4-45 4.4.1 Switching power on for the first time ......................................................................................... 4-46 4.4.2 Startup ....................................................................................................................................... 4-51 4.4.3 Display and operation section of the resistance regeneration converter unit ........................... 4-52

4.5 Parameters ...................................................................................................................................... 4-59 4.5.1 Parameter list ............................................................................................................................ 4-59 4.5.2 Detailed list of parameters ........................................................................................................ 4-60

4.6 Characteristics ................................................................................................................................. 4-62 4.6.1 Overload protection characteristics ........................................................................................... 4-62 4.6.2 Power supply capacity and generated loss ............................................................................... 4-63 4.6.3 Inrush currents at power-on of main circuit/control circuit......................................................... 4-65

5. MR-J4-DU_(-RJ) DRIVE UNIT 5- 1 to 5-44

5.1 Structure (Parts identification) .......................................................................................................... 5- 1 5.1.1 MR-J4-DU_B_(-RJ) .................................................................................................................... 5- 2 5.1.2 MR-J4-DU_A_(-RJ) .................................................................................................................... 5- 9

5.2 Signals and wiring ............................................................................................................................ 5-14 5.2.1 Signal explanations ................................................................................................................... 5-15 5.2.2 Connectors and pin assignment ................................................................................................ 5-16

5.3 Parameter ........................................................................................................................................ 5-18 5.3.1 MR-J4-DU_B_(-RJ) ................................................................................................................... 5-18 5.3.2 MR-J4-DU_A_(-RJ) ................................................................................................................... 5-23

5.4 Characteristics ................................................................................................................................. 5-24 5.4.1 Drive unit ................................................................................................................................... 5-24 5.4.2 Dynamic brake characteristics .................................................................................................. 5-27 5.4.3 Inrush currents at power-on of control circuit ............................................................................ 5-34

5.5 Mounting and removing MR-D30 ..................................................................................................... 5-35 5.5.1 MR-J4-DU900B-RJ to MR-J4-DU22KB-RJ/MR-J4-DU900B4-RJ to MR-J4-DU22KB4-RJ ...... 5-36

3

5.5.2 MR-J4-DU30K_-RJ to MR-J4-DU37K_-RJ/MR-J4-DU30K_4-RJ to MR-J4-DU55K_4-RJ ....... 5-40

6. TROUBLESHOOTING 6- 1 to 6-16

6.1 MR-CV_ Power regeneration converter unit ..................................................................................... 6- 1 6.1.1 Explanation for the lists .............................................................................................................. 6- 1 6.1.2 Alarm/warning list ....................................................................................................................... 6- 1

6.2 MR-CR_ Resistance regeneration converter unit ............................................................................. 6- 2 6.2.1 Explanation for the lists .............................................................................................................. 6- 2 6.2.2 Alarm/warning list ....................................................................................................................... 6- 2

6.3 Drive unit ........................................................................................................................................... 6- 3 6.3.1 Explanation for the lists .............................................................................................................. 6- 3 6.3.2 Alarm list ..................................................................................................................................... 6- 4 6.3.3 Warning list ................................................................................................................................ 6-14

7. DIMENSIONS 7- 1 to 7-12

7.1 MR-CV_ Power regeneration converter unit ..................................................................................... 7- 1 7.1.1 MR-CV11K(4)/MR-CV18K(4) ..................................................................................................... 7- 1 7.1.2 MR-CV30K(4)/MR-CV37K(4)/MR-CV45K(4) ............................................................................. 7- 2 7.1.3 MR-CV55K ................................................................................................................................. 7- 3 7.1.4 MR-CV55K4/MR-CV75K4 .......................................................................................................... 7- 4

7.2 MR-CR55K(4) Resistance regeneration converter unit .................................................................... 7- 5 7.3 Drive unit ........................................................................................................................................... 7- 6

7.3.1 MR-J4-DU_B_(-RJ) .................................................................................................................... 7- 6 7.3.2 MR-J4-DU_A_(-RJ) ................................................................................................................... 7-10

8. OPTIONS AND PERIPHERAL EQUIPMENT 8- 1 to 8-70

8.1 Cable/connector sets ........................................................................................................................ 8- 2 8.1.1 Combinations of cable/connector sets ....................................................................................... 8- 2 8.1.2 Protection coordination cable ..................................................................................................... 8- 4

8.2 Regenerative option .......................................................................................................................... 8- 6 8.2.1 Combination and regenerative power ........................................................................................ 8- 6 8.2.2 Selection of regenerative option ................................................................................................. 8- 7 8.2.3 Parameter setting ....................................................................................................................... 8- 9 8.2.4 Connection of regenerative option ............................................................................................ 8-10 8.2.5 Dimensions ................................................................................................................................ 8-12

8.3 External dynamic brake ................................................................................................................... 8-13 8.3.1 Selection of external dynamic brake ......................................................................................... 8-14 8.3.2 Connection example ................................................................................................................. 8-14 8.3.3 Timing chart ............................................................................................................................... 8-18 8.3.4 Dimensions ................................................................................................................................ 8-19

8.4 Selection example of wires .............................................................................................................. 8-22 8.4.1 Connection of converter unit and drive unit .............................................................................. 8-22 8.4.2 Connection of power regeneration converter unit and servo amplifier ..................................... 8-26

8.5 Molded-case circuit breakers, fuses, magnetic contactors .............................................................. 8-28 8.5.1 For main circuit power supply ................................................................................................... 8-28 8.5.2 For control circuit power supply ................................................................................................ 8-29

8.6 Power factor improving DC reactor .................................................................................................. 8-32 8.7 AC reactor ........................................................................................................................................ 8-33

4

8.8 Noise reduction techniques.............................................................................................................. 8-34 8.8.1 Noise reduction techniques ....................................................................................................... 8-34 8.8.2 Noise reduction techniques ....................................................................................................... 8-37

8.9 Earth-leakage current breaker ......................................................................................................... 8-38 8.9.1 Selection method....................................................................................................................... 8-38 8.9.2 Selection example ..................................................................................................................... 8-40

8.10 EMC filter (recommended) ............................................................................................................. 8-41 8.10.1 Combinations with the converter unit ...................................................................................... 8-41 8.10.2 Connection example ............................................................................................................... 8-42 8.10.3 Dimensions .............................................................................................................................. 8-43

8.11 FR-BU2-(H) brake unit ................................................................................................................... 8-48 8.11.1 Selection .................................................................................................................................. 8-48 8.11.2 Brake unit parameter setting ................................................................................................... 8-49 8.11.3 Connection example of combination with FR-BR-(H) resistor unit ......................................... 8-49 8.11.4 Combination with MT-BR5-(H) resistor unit ............................................................................ 8-54 8.11.5 Connection instructions ........................................................................................................... 8-62 8.11.6 Wires ....................................................................................................................................... 8-63 8.11.7 Crimp terminals for L+ and L- terminals of TE2-1 of

resistance regeneration converter unit .................................................................................... 8-64 8.11.8 Dimensions .............................................................................................................................. 8-65

8.12 MR-DCBAR_ bus bar .................................................................................................................... 8-67 8.12.1 Bus bar .................................................................................................................................... 8-67 8.12.2 Adjustment bar ........................................................................................................................ 8-69

9. COMPLIANCE WITH SEMI-F47 STANDARD 9- 1 to 9- 4

9.1 Parameter setting .............................................................................................................................. 9- 2 9.2 Requirement of SEMI-F47 standard ................................................................................................. 9- 3 9.3 Calculation of tolerance against instantaneous power failure .......................................................... 9- 3

9.3.1 Delta connection ......................................................................................................................... 9- 3 9.3.2 Star connection .......................................................................................................................... 9- 3

10. APPENDIX 10- 1 to 10-18

10.1 Peripheral equipment manufacturer (for reference) ..................................................................... 10- 1 10.2 Compliance with global standards ................................................................................................ 10- 1

10.2.1 Terms related to safety .......................................................................................................... 10- 1 10.2.2 About safety ........................................................................................................................... 10- 1 10.2.3 Installation direction and clearances ...................................................................................... 10- 7 10.2.4 Electrical Installation and configuration diagram .................................................................... 10- 8 10.2.5 Signals ................................................................................................................................... 10-10 10.2.6 Maintenance and service ...................................................................................................... 10-11 10.2.7 Transportation and storage ................................................................................................... 10-12 10.2.8 Technical data ....................................................................................................................... 10-13 10.2.9 Check list for user documentation ......................................................................................... 10-14

10.3 Special coating-specification product (IEC 60721-3-3 Class 3C2) .............................................. 10-15 10.3.1 Summary ............................................................................................................................... 10-15 10.3.2 Specifications ........................................................................................................................ 10-15

10.4 EC declaration of conformity ........................................................................................................ 10-16 10.5 Status of general-purpose AC servo products for compliance with the China RoHS directive ... 10-17

10.5.1 Summary ............................................................................................................................... 10-17

5

10.5.2 Status of our products for compliance with the China RoHS directive ................................. 10-17 10.5.3 Difference between the China RoHS directive and the EU RoHS directive ......................... 10-18 10.5.4 Status of our products for compliance with the China RoHS directive (Chinese) ................. 10-18

6

MEMO

1. FUNCTIONS AND CONFIGURATION

1 - 1

1. FUNCTIONS AND CONFIGURATION

1.1 Summary

POINT MR-CV_ power regeneration converter unit is used in a combination with MR-J4- DU_B_(-RJ) drive units and MR-J4-_B_(-RJ) servo amplifiers. MR-CV_ cannot be used with MR-J4-DU_A_(-RJ) drive units and MR-J4-_A_(-RJ) servo amplifiers. For summary, also refer to section 1.1 of each servo amplifier instruction manual.

In MELSERVO-J4 series, drive units with the CN2L connector are also available as MR-J4-DU_A_-RJ and MR-J4-DU_B_-RJ. An A/B/Z-phase differential output type external encoder can be connected through the CN2L connector. In a fully closed loop system or a linear servo motor system, a four-wire type external encoder is connectable as well. The following table indicates the communication method and the connector of external encoders compatible with the drive unit.

Operation mode

External encoder communication

method

Connector

MR-J4-DU_A_ MR-J4-DU_A_-RJ MR-J4-DU_B_ MR-J4-DU_B_-RJ

Fully closed loop system

Two-wire type CN2 (Note 1, 2)

CN2L

CN2 (Note 1, 2)

CN2L Four-wire type

A/B/Z-phase differential output

method

Scale measurement function

Two-wire type

CN2 (Note 1, 2)

CN2L Four-wire type

A/B/Z-phase differential output

method

Linear servo motor system

Two-wire type

CN2 (Note 1) CN2 (Note 1) Four-wire type A/B/Z-phase

differential output method

CN2L (Note 3)

Note 1. The MR-J4FCCBL03M branch cable is necessary. 2. When the communication method of the servo motor encoder is four-wire type, MR-J4-DU_A_ and MR-J4-

DU_B_ cannot be used. Use an MR-J4-DU_A_-RJ or MR-J4-DU_B_-RJ. 3. Connect a thermistor to CN2.

MR-CV_ power regeneration converter unit enables regenerative power generated during deceleration of the servo motor to be returned back to the power supply. MR-CV_ power regeneration converter unit connects with multiple MR-J4-DU_B_(-RJ) drive units and MR-J4-_B_(-RJ) servo amplifiers by sharing the bus voltage, enabling energy-conservation, less wiring, and space-saving. MR-CV_ power regeneration converter unit is compatible with drive units with software version C5 or later. MR-CR_ resistance regeneration converter unit enables regenerative power generated during deceleration of the servo motor to be consumed by a regenerative resistor.

1. FUNCTIONS AND CONFIGURATION

1 - 2

1.2 Model designation

1.2.1 MR-CV_ power regeneration converter unit

(1) Rating plate The following shows an example of the rating plate for explanation of each item.

Serial number

TOKYO 100-8310, JAPAN MADE IN JAPAN

DATE: 2016-3

MR-CV55K SER. A33001001

AC SERVO

CAPACITY INPUT OUTPUT STD.: IEC/EN61800-5-1 MAN.: IB(NA)0300228 Max. Surrounding Air Temp.: 55C IP20 (Terminal block IP00)

: 55kW : 3AC200-240V 200.0A 50Hz/60Hz : DC270-324V 238.0A

MSIP-REI-MEK- TC300A911G51

Model Capacity Applicable power supply Rated output current Standard, Manual number Ambient temperature IP rating KC certification number The year and month of manufacture Country of origin

(2) Model The following describes what each block of a model name indicates. Not all combinations of the symbols are available.

Series

Capacity Symbol Power supply None 3-phase 200 V AC to 240 V AC

4 3-phase 380 V AC to 480 V AC

Power supply

37K

Symbol Capacity [kW]

30K 37

45K 45 55K 55 75K 75

30 18K 18 11K 11

M R - C V 7 5 K 4

1. FUNCTIONS AND CONFIGURATION

1 - 3

1.2.2 MR-CR_ resistance regeneration converter unit

(1) Rating plate The following shows an example of the rating plate for explanation of each item.

Serial number

TOKYO 100-8310, JAPAN MADE IN JAPAN

DATE: 2016-3

MR-CR55K SER. A33001001

AC SERVO

POWER INPUT OUTPUT STD.: IEC/EN61800-5-1 MAN.: IB(NA)0300228 Max. Surrounding Air Temp.: 55C IP20 (Terminal block IP00)

: 55kW : 3AC200-240V 191.3A 50Hz/60Hz : DC270-324V 215.9A

MSIP-REI-MEK- TC300A911G51

Model Capacity Applicable power supply Rated output current Standard, Manual number Ambient temperature IP rating KC certification number The year and month of manufacture Country of origin

(2) Model The following describes what each block of a model name indicates. Not all combinations of the symbols are available.

Series

Rated output: 55 kW

Symbol Power supply None 3-phase 200 V AC to 240 V AC

4 3-phase 380 V AC to 480 V AC

Symbol Special specifications None Standard -EB MR-CR_ with a special coating specification (3C2) (Note)

Special specifications

M R - C R 5 5 K 4 - E B

Power supply

Note. Type with a specially-coated resistance regeneration converter unit board (IEC 60721-3-3 Class 3C2). Refer to section 10.3 for details.

1. FUNCTIONS AND CONFIGURATION

1 - 4

1.2.3 Drive unit

(1) Rating plate The following shows an example of the rating plate for explanation of each item.

Serial number

TOKYO 100-8310, JAPAN MADE IN JAPAN

DATE: 2016-3

MR-J4-DU30KB SER. A33001001

AC SERVO

POWER INPUT OUTPUT STD.: IEC/EN61800-5-1 MAN.: IB(NA)0300228 Max. Surrounding Air Temp.: 55C IP20 (Terminal block IP00)

: 30kW : DC270-324V 117.7A : 3PH170V 0-360Hz 174.0A

MSIP-REI-MEK- TC300A916G51

Model Capacity Applicable power supply Rated output current Standard, Manual number Ambient temperature IP rating KC certification number The year and month of manufacture Country of origin

(2) Model The following describes what each block of a model name indicates. Not all combinations of the symbols are available.

37K

Symbol Power supply

Series

None 3-phase 200 V AC to 240 V AC 4 3-phase 380 V AC to 480 V AC

Symbol Rated output [kW]

30K

Rated output

37 Power supply

Interface

45K 45 55K 55

30

11K 900

11 15K 15 22K 22

9

Indicates drive unit

B

Symbol Interface A

SSCNET III/H General-purpose interface

Symbol Special specifications None

-RJ

-EB

-KS

Fully closed loop control four-wire type/load-side encoder A/B/Z-phase input compatible Positioning mode compatible (Note 1) Compatible with MR-D30 functional safety unit (Note 2)

Special specifications

Standard

MR-J4-DU_ with a special coating specification (3C2) (Note 3) MR-J4-DU_-RJ with a special coating specification (3C2) (Note 3)

-M R - J 4 3 0D U K B 4 - R J

Note 1. The positioning mode is available only with MR-J4-DU_A_-RJ. 2. MR-D30 functional safety unit is compatible with drive units with software version B5 or later. 3. Type with a specially-coated drive unit board (IEC 60721-3-3 Class 3C2). This type is available with the drive unit of 30

kW or more. Refer to section 10.3 for details.

1. FUNCTIONS AND CONFIGURATION

1 - 5

1.3 Combinations of converter units, drive units and servo motors

1.3.1 Combinations of the power regeneration converter unit and drive unit

(1) Connecting one drive unit to one power regeneration converter unit The drive units are driven at the rated output with the following combinations: When operating drive units at a load ratio lower than the rated, and having met the selection conditions of (2) in this section, you can select drive units with capacity larger than those of the combinations in the following table.

(a) 200 V class

Power regeneration

converter unit Drive unit

MR-CV18K MR-J4-DU900B(-RJ) MR-J4-DU11KB(-RJ)

MR-CV30K MR-J4-DU15KB(-RJ) MR-CV37K MR-J4-DU22KB(-RJ)

MR-CV55K MR-J4-DU30KB(-RJ) MR-J4-DU37KB(-RJ)

(b) 400 V class

Power regeneration

converter unit Drive unit

MR-CV18K4 MR-J4-DU900B4(-RJ) MR-J4-DU11KB4(-RJ)

MR-CV30K4 MR-J4-DU15KB4(-RJ) MR-CV37K4 MR-J4-DU22KB4(-RJ)

MR-CV55K4

MR-J4-DU30KB4(-RJ) MR-J4-DU37KB4(-RJ) MR-J4-DU45KB4(-RJ) MR-J4-DU55KB4(-RJ)

1. FUNCTIONS AND CONFIGURATION

1 - 6

(2) Connecting multiple drive units to one power regeneration converter unit

(a) Selection method Select a power regeneration converter unit which meets the following conditions. When all the conditions are fulfilled, multiple drive units can be connected to one power regeneration converter unit. When connecting the multiple drive units, mount the drive units in descending order of capacity, from the right side of the power regeneration converter unit.

1) Maximum capacity of MR-J4-DU_ connected to MR-CV_ [kW] Maximum capacity of MR-J4-

DU_ drivable with MR-CV_ [kW]

2) Effective value of total output power of servo motors [kW] Continuous rating of MR-CV_ [kW]

3) Maximum value of total output power of servo motors [kW] 1.2 Instantaneous maximum rating of MR-CV_ [kW]

4) Total widths of MR-J4-DU_ 800 mm

MR-CV_ (200 V class) MR-CV_ (400 V class) 11K 18K 30K 37K 45K 55K 11K4 18K4 30K4 37K4 45K4 55K4 75K4

Maximum capacity of MR-J4-DU_ drivable with MR-CV_

[kW] 11 15 30 37 37 37 11 15 30 37 45 55 55

Continuous rating [kW] 7.5 11 20 22 22 37 7.5 11 20 25 25 55 55 Instantaneous maximum rating [kW] 39 60 92 101 125 175 39 60 92 101 125 175 180 Total widths of MR-J4-DU_ 800 mm or less

MR-J4-DU-_ (200 V class) MR-J4-DU-_ (400 V class)

900B 11KB 15KB 22KB 30KB 37KB 900B4 11KB4 15KB4 22KB4 30KB4 37KB4 45KB4 55KB4 Unit width [mm] 150 240 300 150 240 300

1. FUNCTIONS AND CONFIGURATION

1 - 7

(b) Selection example of power regeneration converter unit

Select a power regeneration converter unit for the following drive units: Drive unit MR-J4-DU900B/servo motor HG-SR702 Drive unit MR-J4-DU11KB/servo motor HG-JR11K1M Drive unit MR-J4-DU22KB/servo motor HG-JR22K1M

Calculate running power and regenerative power from the servo motor speed and torque as follows:

For rotary servo motor Running power and regenerative power [W] = Servo motor speed [r/min] Torque [Nm]/9.55

For linear servo motor Running power and regenerative power [W] = Servo motor speed [m/s] Thrust [N]

(Running power with a positive sign, and regenerative power with a negative sign)

Calculate the total output power of the servo motors from the running power and regenerative power of each servo motor.

-15 kW

-15 kW-15 kW

0.1 s

One cycle time: 1.2 s

0.1 s 10 kW

0.1 s

30 kW

0.5 s

0.7 s

0.6 s

0.2 s0.3 s

0.2 s

0.1 s 0.2 s

0.1 s

0.1 s

0.1 s

0.1 s

0.1 s 0.1 s

5 kW

20 kW

20 kW

15 kW

-5 kW

10 kW 0.1 s 0.1 s

0.1 s

-5 kW

10 kW

15 kW

10 kW

Regenerative power

Power running energy

Power running energy

Regenerative power

Power running energy

Regenerative power

Power running energyMR-J4-DU900B/

HG-SR702

MR-J4-DU11KB/ HG-JR11K1M

MR-J4-DU22KB/ HG-JR22K1M

Total output power of servo motors

Total output power of servo motors

Regenerative power

0.1 s

0.1 s

0.6 s

1. FUNCTIONS AND CONFIGURATION

1 - 8

1) Maximum capacity of the drive unit [kW] = 22 kW

MR-CV30K or more

2) Effective value of total output power of servo motors [kW] = (102 0.2 + 52 0.1 + 202 0.5 + 302 0.1 + 102 0.1 + (-15)2 0.1)/1.2 = 17 kW MR-CV30K or more

3) Maximum value of total output power of servo motors [kW] 1.2 = 30 kW 1.2 = 36 kW

MR-CV11K or more

4) Total widths of drive units = 240 mm (MR-J4-DU22KB) + 150 mm (MR-J4-DU11KB) + 150 mm (MR-J4-DU11KB) = 540 mm 800 mm

From the calculation, MR-CV30K is selected for the power regeneration converter unit.

Mount the MR-J4-DU_B_(-RJ) drive units in descending order of capacity, from the right side of the MR-CV_ as follows. Refer to section 2.1 for installation.

MR-CV30K MR-J4-DU22KB MR-J4-DU11KB MR-J4-DU900B

1. FUNCTIONS AND CONFIGURATION

1 - 9

(3) Connecting multiple drive units and servo amplifiers to one power regeneration converter unit

(a) Selection method Select a power regeneration converter unit which meets the following conditions. When all the conditions are fulfilled, multiple drive units and servo amplifiers can be connected to one power regeneration converter unit. When connecting the multiple drive units, mount the drive units in descending order of capacity, from the right side of the power regeneration converter unit.

1) Maximum capacity [kW] of MR-J4-DU_ connected to MR-CV_ Maximum capacity [kW] of MR-

J4-DU_ drivable with MR-CV_

2) Total capacity of servo amplifiers [kW] Total capacity of servo amplifiers drivable with MR-CV_ [kW]

3) Number servo amplifiers connected to one MR-CV_ 6

4) Effective value of total output power of servo motors [kW] Continuous rating of MR-CV_ [kW]

5) Maximum value of total output power of servo motors [kW] 1.2 Instantaneous maximum rating

of MR-CV_ [kW]

6) Total widths of MR-J4-DU_ 800 mm

MR-CV_ (200 V class) MR-CV_ (400 V class)

11K 18K 30K 37K 45K 55K 11K4 18K4 30K4 37K4 45K4 55K4 75K4 Maximum capacity of MR-J4-DU_ drivable with MR-CV_

[kW] 11 15 30 37 37 37 11 15 30 37 45 55 55

Total capacity of drivable servo amplifiers [kW] 7.5 5 15 11 11 27.5 7.5 5 15 11 11 27.5 27.5

Continuous rating [kW] 7.5 11 20 22 22 37 7.5 11 20 25 25 55 55 Instantaneous maximum rating [kW] 39 60 92 101 125 175 39 60 92 101 125 175 180 Maximum number of connectable servo amplifiers

6

Total widths of MR-J4-DU_ 800 mm or less

MR-J4-DU-_ (200 V class) MR-J4-DU-_ (400 V class)

900B 11KB 15KB 22KB 30KB 37KB 900B4 11KB4 15KB4 22KB4 30KB4 37KB4 45KB4 55KB4 Unit width [mm] 150 240 300 150 240 300

(b) Selection example of power regeneration converter unit

Select a power regeneration converter unit for the following drive units and servo amplifiers: Servo amplifier MR-J4-500B/servo motor HG-SR502 Servo amplifier MR-J4-500B/servo motor HG-SR502 Drive unit MR-J4-DU11KB/servo motor HG-JR11K1M Drive unit MR-J4-DU22KB/servo motor HG-JR22K1M

Calculate running power and regenerative power from the servo motor speed and torque as follows:

For rotary servo motor Running power and regenerative power [W] = Servo motor speed [r/min] Torque [Nm]/9.55

For linear servo motor Running power and regenerative power [W] = Servo motor speed [m/s] Thrust [N]

(Running power with a positive sign, and regenerative power with a negative sign)

1. FUNCTIONS AND CONFIGURATION

1 - 10

Calculate the total output power of the servo motors from the running power and regenerative power of each servo motor.

-15 kW

-15 kW-15 kW

0.1 s

One cycle time: 1.2 s

0.1 s

5 kW 0.1 s

40 kW

0.5 s

0.7 s

0.6 s

0.2 s0.3 s

0.1 s

0.1 s 0.2 s

0.1 s

0.1 s

0.1 s

0.1 s

0.1 s 0.1 s

5 kW

20 kW

20 kW

15 kW

-5 kW

10 kW 0.1 s 0.1 s

0.1 s

-5 kW

10 kW

15 kW

20 kW

MR-J4-500B/ HG-SR502

MR-J4-11KB/ HG-JR11K1M

MR-J4-DU22KB/ HG-JR22K1M

Total output power of servo motors

0.2 s

0.1 s

0.6 s

0.1 s 0.1 s

0.1 s-5 kW

10 kW 0.1 s 0.1 s

-5 kW

10 kW MR-J4-500B/ HG-SR502

0.1 s

0.6 s Power running energy

Regenerative power

Power running energy

Regenerative power

Power running energy

Regenerative power

Power running energy

Regenerative power

Power running energy

Regenerative power

Total output power of servo motors

1) Maximum capacity of the drive unit [kW] = 22 kW MR-CV30K or more

2) Total of servo amplifier capacities [kW] = 5 kW + 5 kW = 10 kW

MR-CV30K or more

3) Effective value of total output power of servo motors [kW] = (202 0.1 + 52 0.2 + 202 0.5 + 402 0.1 + 52 0.1 + (-15)2 0.1)/1.2 = 18.93 kW MR-CV30K or more

4) Maximum value of total output power of servo motors [kW] 1.2 = 40 kW 1.2 = 48 kW

MR-CV18K or more

5) Number of servo amplifiers: 2 6

6) Total width of drive units = 240 mm (MR-J4-DU22KB) + 150 mm (MR-J4-DU11KB) = 390 mm 800 mm

1. FUNCTIONS AND CONFIGURATION

1 - 11

From the calculation, MR-CV30K is selected for the power regeneration converter unit. Mount the MR-J4-DU_B_(-RJ) drive units in descending order of capacity, from the right side of the MR-CV_ as follows. Refer to section 2.1 for installation.

MR-CV30K MR-J4-DU22KB MR-J4-DU11KB

MR-J4-500B MR-J4-500B

1.3.2 Combinations of the resistance regeneration converter unit and drive unit

(1) 200 V class

Resistance regeneration converter unit Drive unit

MR-CR55K

MR-J4-DU30KB(-RJ) MR-J4-DU30KA(-RJ) MR-J4-DU37KB(-RJ) MR-J4-DU37KA(-RJ)

(2) 400 V class

Resistance regeneration converter unit Drive unit

MR-CR55K4

MR-J4-DU30KB4(-RJ) MR-J4-DU30KA4(-RJ) MR-J4-DU37KB4(-RJ) MR-J4-DU37KA4(-RJ) MR-J4-DU45KB4(-RJ) MR-J4-DU45KA4(-RJ) MR-J4-DU55KB4(-RJ) MR-J4-DU55KA4(-RJ)

1. FUNCTIONS AND CONFIGURATION

1 - 12

1.3.3 Combinations of drive unit and servo motors

(1) 200 V class

Drive unit Rotary servo motor Linear servo motor

(primary side) HG-SR HG-JR MR-J4-DU900B(-RJ)

702 (Note 2)

601 801

701M (Note 2) 503 (Note 1) 703 (Note 2)

903

LM-FP2F-18M-1SS0 LM-FP4D-24M-1SS0

MR-J4-DU11KB(-RJ)

12K1 11K1M

LM-FP4F-36M-1SS0

MR-J4-DU15KB(-RJ)

15K1 15K1M

LM-FP4H-48M-1SS0

MR-J4-DU22KB(-RJ)

20K1 25K1

22K1M

MR-J4-DU30KB(-RJ) MR-J4-DU30KA(-RJ)

30K1

30K1M

MR-J4-DU37KB(-RJ) MR-J4-DU37KA(-RJ)

37K1

37K1M

Note 1. The maximum torque can be increased to 400% of the rated torque. 2. By enabling the maximally increased torque function when drive unit is connected with

[Pr. PC23], the maximum torque can be increased. (Refer to section 5.3.1.)

(2) 400 V class

Drive unit Rotary servo motor Linear servo motor

(primary side) HG-SR HG-JR MR-J4-DU900B4(-RJ)

7024 (Note 2)

6014 8014

701M4 (Note 2) 5034 (Note 1) 7034 (Note 2)

9034

MR-J4-DU11KB4(-RJ)

12K14 11K1M4

MR-J4-DU15KB4(-RJ)

15K14 15K1M4

MR-J4-DU22KB4(-RJ)

20K14 22K1M4 25K14

LM-FP5H-60M-1SS0

MR-J4-DU30KB4(-RJ) MR-J4-DU30KA4(-RJ)

30K14

30K1M4

MR-J4-DU37KB4(-RJ) MR-J4-DU37KA4(-RJ)

37K14

37K1M4

MR-J4-DU45KB4(-RJ) MR-J4-DU45KA4(-RJ)

45K1M4

MR-J4-DU55KB4(-RJ) MR-J4-DU55KA4(-RJ)

55K1M4

Note 1. The maximum torque can be increased to 400% of the rated torque. 2. By enabling the maximally increased torque function when drive unit is connected with

[Pr. PC23], the maximum torque can be increased. (Refer to section 5.3.1.)

1. FUNCTIONS AND CONFIGURATION

1 - 13

1.4 Standard specifications

1.4.1 MR-CV_ power regeneration converter unit

(1) 200 V class Model: MR-CV_ 11K 18K 30K 37K 45K 55K

Output Rated voltage 270 V DC to 324 V DC Rated current [A] 41 76 144 164 198 238

Main circuit power supply input

Voltage/Frequency 3-phase 200 V AC to 240 V AC, 50 Hz/60 Hz Rated current [A] 35 65 107 121 148 200 Permissible voltage fluctuation 3-phase 170 V AC to 264 V AC

Permissible frequency fluctuation Within 3%

Power supply capacity [kVA] Refer to section 3.5.2.

Inrush current [A] Refer to section 3.5.3.

Control circuit power supply input

Voltage/Frequency 1-phase 200 V AC to 240 V AC, 50 Hz/60 Hz Rated current [A] 0.2 Permissible voltage fluctuation 1-phase 170 V AC to 264 V AC

Permissible frequency fluctuation Within 3%

Power consumption [W] 30

Inrush current [A] Refer to section 3.5.3. Interface power supply

Voltage 24 V DC 10% Current capacity [A] 0.35 (Note 1)

Capacity [kW] 11 18 30 37 45 55

Protective functions Undervoltage protection, regenerative error protection, regenerative overvoltage shut-off,

MC drive circuit error, open-phase detection, inrush current suppression circuit error, main circuit device overheat, cooling fan error, and overload shut-off (electronic thermal)

Main circuit type Converter with power regeneration function Continuous rating [kW] 7.5 11 20 22 22 37 Instantaneous maximum rating [kW] 39 60 92 101 125 175

Compliance with global standards

CE marking LVD: EN 61800-5-1 EMC: EN 61800-3

MD: EN ISO 13849-1, EN 61800-5-2, EN 62061

UL standard UL 508C Structure (IP rating) Force cooling, open (IP20) (Note 2)

Environment

Ambient temperature

Operation 0 C to 55 C (non-freezing) Storage -20 C to 65 C (non-freezing)

Ambient humidity

Operation 5 %RH to 90 %RH (non-condensing)

Storage

Ambience Indoors (no direct sunlight),

free from corrosive gas, flammable gas, oil mist, dust, and dirt Altitude 2000 m or less above sea level (Note 3) Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (X, Y, Z axes)

Mass [kg] 6.1 12.1 25.0 Note 1. 0.35 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of

I/O points. 2. Except for the terminal block. 3. Follow the restrictions in section 2.5 when using this product at altitude exceeding 1000 m and up to 2000 m above sea level.

1. FUNCTIONS AND CONFIGURATION

1 - 14

(2) 400 V class Model: MR-CV_ 11K4 18K4 30K4 37K4 45K4 55K4 75K4

Output Rated voltage 513 V DC to 648 V DC Rated current [A] 21 38 72 82 99 119 150

Main circuit power supply input

Voltage/Frequency 3-phase 380 V AC to 480 V AC, 50 Hz/60 Hz Rated current [A] 18 35 61 70 85 106 130 Permissible voltage fluctuation 3-phase 323 V AC to 528 V AC

Permissible frequency fluctuation Within 3%

Power supply capacity [kVA] Refer to section 3.5.2.

Inrush current [A] Refer to section 3.5.3.

Control circuit power supply input

Voltage/Frequency 1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz Rated current [A] 0.1 Permissible voltage fluctuation 1-phase 323 V AC to 528 V AC

Permissible frequency fluctuation Within 3%

Power consumption [W] 30

Inrush current [A] Refer to section 3.5.3. Interface power supply

Voltage 24 V DC 10% Current capacity [A] 0.35 (Note 1)

Capacity [kW] 11 18 30 37 45 55 75

Protective functions Undervoltage protection, regenerative error protection, regenerative overvoltage shut-off,

MC drive circuit error, open-phase detection, inrush current suppression circuit error, main circuit device overheat, cooling fan error, and overload shut-off (electronic thermal)

Main circuit type Converter with power regeneration function Continuous rating [kW] 7.5 11 20 25 25 55 55 Instantaneous maximum rating [kW] 39 60 92 101 125 175 180

Compliance with global standards

CE marking LVD: EN 61800-5-1 EMC: EN 61800-3

MD: EN ISO 13849-1, EN 61800-5-2, EN 62061 UL standard UL 508C

Structure (IP rating) Force cooling, open (IP20) (Note 2)

Environment

Ambient temperature

Operation 0 C to 55 C (non-freezing) Storage -20 C to 65 C (non-freezing)

Ambient humidity

Operation 5 %RH to 90 %RH (non-condensing)

Storage

Ambience Indoors (no direct sunlight), free from corrosive gas, flammable gas, oil mist, dust, and dirt

Altitude 2000 m or less above sea level (Note 3) Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (X, Y, Z axes)

Mass [kg] 6.1 12.1 25.0 Note 1. 0.35 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of

I/O points. 2. Except for the terminal block. 3. Follow the restrictions in section 2.5 when using this product at altitude exceeding 1000 m and up to 2000 m above sea level.

1. FUNCTIONS AND CONFIGURATION

1 - 15

1.4.2 MR-CR_ resistance regeneration converter unit

Model: MR-CR_ 55 K 55K4

Output Rated voltage 270 V DC to 324 V DC 513 V DC to 648 V DC Rated current [A] 215.9 113.8

Main circuit power supply input

Voltage/Frequency 3-phase 200 V AC to 240 V AC, 50 Hz/60 Hz

3-phase 380 V AC to 480 V AC, 50 Hz/60 Hz

Rated current [A] 191.3 100.7 Permissible voltage fluctuation 3-phase 170 V AC to 264 V AC 3-phase 323 V AC to 528 V AC

Permissible frequency fluctuation Within 5%

Power supply capacity [kVA] Refer to section 4.6.2. Inrush current [A] Refer to section 4.6.3.

Control circuit power supply input

Voltage/Frequency 1-phase 200 V AC to 240 V AC, 50 Hz/60 Hz

1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz

Rated current [A] 0.3 0.2 Permissible voltage fluctuation 1-phase 170 V AC to 264 V AC 1-phase 323 V AC to 528 V AC

Permissible frequency fluctuation Within 5%

Power consumption [W] 45 Inrush current [A] Refer to section 4.6.3.

Interface power supply

Voltage 24 V DC 10% Current capacity [A] 0.15 (Note 1)

Rated output [kW] 55

Regenerative power (regenerative option) One MR-RB139: 1300 W

Three MR-RB137: 3900 W One MR-RB137-4: 1300 W

Three MR-RB13V-4: 3900 W

Protective functions Regenerative overvoltage shut-off, overload shut-off (electronic thermal), regenerative error protection, undervoltage protection, and instantaneous power failure protection

Compliance with global standards

CE marking LVD: EN 61800-5-1 EMC: EN 61800-3

UL standard UL 508C Structure (IP rating) Force cooling, open (IP20) (Note 2)

Environment

Ambient temperature

Operation 0 C to 55 C (non-freezing) Storage -20 C to 65 C (non-freezing)

Ambient humidity Operation

5 %RH to 90 %RH (non-condensing) Storage

Ambience Indoors (no direct sunlight),

free from corrosive gas, flammable gas, oil mist, dust, and dirt Altitude 2000 m or less above sea level (Note 3) Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (X, Y, Z axes)

Mass [kg] 22 Note 1. 0.15 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of

I/O points. 2. Except for the terminal block. 3. Follow the restrictions in section 2.5 when using this product at altitude exceeding 1000 m and up to 2000 m above sea level.

1. FUNCTIONS AND CONFIGURATION

1 - 16

1.4.3 Drive unit

(1) MR-J4-DU_B_(-RJ) (a) 200 V class

Model MR-J4-DU_(-RJ) 900B 11KB 15KB 22KB 30KB 37KB

Output Rated voltage 3-phase 170 V AC Rated current [A] 54 68 87 126 174 204

Main circuit power supply input The main circuit power of the drive unit is supplied by the converter unit.

Control circuit power supply input

Voltage/Frequency 1-phase 200 V AC to 240 V AC, 50 Hz/60 Hz Rated current [A] 0.3 Permissible voltage fluctuation 1-phase 170 V AC to 264 V AC

Permissible frequency fluctuation Within 5%

Power consumption [W] 45

Inrush current [A] Refer to section 5.4.3. Interface power supply

Voltage 24 V DC 10% Current capacity [A] 0.3 (including CN8 connector signals) (Note 1)

Control method Sine-wave PWM control, current control method Dynamic brake External option (Note 6, 7) SSCNET III/H communication cycle (Note 5) 0.222 ms, 0.444 ms, 0.888 ms Fully closed loop control Compatible Scale measurement function Compatible Load-side encoder interface (Note 4) Mitsubishi Electric high-speed serial communication Communication function USB: connection to a personal computer or others (MR Configurator2-compatible) Encoder output pulses Compatible (A/B/Z-phase pulse) Analog monitor Two channels

Protective functions

Overcurrent shut-off, overload shut-off (electronic thermal), servo motor overheat protection, encoder error protection, undervoltage protection, instantaneous power failure protection, overspeed protection, error excessive protection, magnetic pole

detection protection, and linear servo control fault protection Functional safety STO (IEC/EN 61800-5-2)

Safety performance

Standards certified by CB (Note 8) EN ISO 13849-1 category 3 PL e, IEC 61508 SIL 3, EN 62061 SIL CL3, EN 61800-5-2

Response performance 8 ms or less (STO input off energy shut off) Test pulse input (STO) (Note 2)

Test pulse interval: 1 Hz to 25 Hz Test pulse off time: Up to 1 ms

Mean time to dangerous failure (MTTFd) MTTFd 100 [years] (314a)

Diagnostic coverage (DC) DC = Medium, 97.6 [%]

Probability of dangerous Failure per Hour (PFH) 6.4 10-9 [1/h]

Compliance with global standards

CE marking LVD: EN 61800-5-1 EMC: EN 61800-3

MD: EN ISO 13849-1, EN 61800-5-2, EN 62061 UL standard UL 508C

Structure (IP rating) Force cooling, open (IP20) (Note 3)

Environment

Ambient temperature

Operation 0 C to 55 C (non-freezing) Storage -20 C to 65 C (non-freezing)

Ambient humidity

Operation 5 %RH to 90 %RH (non-condensing)

Storage

Ambience Indoors (no direct sunlight),

free from corrosive gas, flammable gas, oil mist, dust, and dirt Altitude 2000 m or less above sea level (Note 9) Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (X, Y, Z axes)

Mass [kg] 9.9 15.2 21

1. FUNCTIONS AND CONFIGURATION

1 - 17

Note 1. 0.3 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of

I/O points. 2. Test pulse is a signal which instantaneously turns off a signal to the drive unit at a constant period for external circuit to self-

diagnose. 3. Except for the terminal block. 4. The MR-J4-DU_B drive unit is compatible only with the two-wire type. The MR-J4-DU_B-RJ drive unit is compatible with the

two-wire type, four-wire type, and A/B/Z-phase differential output method. Refer to section 1.1 for details. 5. The communication cycle depends on the controller specifications and the number of axes connected. 6. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not

stop immediately but coasts at emergency stop. Ensure the safety in the entire equipment. For wiring of the external dynamic brake, refer to section 8.3.

7. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) with [Pr. PD07] to [Pr. PD09]. Doing so will cause the drive unit to become servo-off when an instantaneous power failure occurs.

8. The safety level depends on the setting value of [Pr. PF18 STO diagnosis error detection time] and whether STO input diagnosis by TOFB output is performed or not. For details, refer to the Function column of [Pr. PF18] in section 5.2.6 of "MR- J4-_B_(-RJ) Servo Amplifier Instruction Manual".

9. Follow the restrictions in section 2.5 when using this product at altitude exceeding 1000 m and up to 2000 m above sea level.

1. FUNCTIONS AND CONFIGURATION

1 - 18

(b) 400 V class

Model MR-J4-DU_(-RJ) 900B4 11KB4 15KB4 22KB4 30KB4 37KB4 45KB4 55KB4

Output Rated voltage 3-phase 323 V AC Rated current [A] 25 32 41 63 87 102 131 143

Main circuit power supply input The main circuit power of the drive unit is supplied by the converter unit.

Control circuit power supply input

Voltage/Frequency 1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz Rated current [A] 0.2 Permissible voltage fluctuation 1-phase 323 V AC to 528 V AC

Permissible frequency fluctuation Within 5%

Power consumption [W] 45

Inrush current [A] Refer to section 5.4.3. Interface power supply

Voltage 24 V DC 10% Current capacity [A] 0.3 (including CN8 connector signals) (Note 1)

Control method Sine-wave PWM control, current control method Dynamic brake External option (Note 6, 7) SSCNET III/H communication cycle (Note 5) 0.222 ms, 0.444 ms, 0.888 ms Fully closed loop control Compatible Scale measurement function Compatible Load-side encoder interface (Note 4) Mitsubishi Electric high-speed serial communication Communication function USB: connection to a personal computer or others (MR Configurator2-compatible) Encoder output pulses Compatible (A/B/Z-phase pulse) Analog monitor Two channels

Protective functions

Overcurrent shut-off, overload shut-off (electronic thermal), servo motor overheat protection, encoder error protection, undervoltage protection, instantaneous power failure protection, overspeed protection,error excessive protection, magnetic pole

detection protection, and linear servo control fault protection Functional safety STO (IEC/EN 61800-5-2)

Safety performance

Standards certified by CB (Note 8) EN ISO 13849-1 category 3 PL e, IEC 61508 SIL 3, EN 62061 SIL CL3, EN 61800-5-2

Response performance 8 ms or less (STO input off energy shut off) Test pulse input (STO) (Note 2)

Test pulse interval: 1 Hz to 25 Hz Test pulse off time: Up to 1 ms

Mean time to dangerous failure (MTTFd) MTTFd 100 [years] (314a)

Diagnostic coverage (DC) DC = Medium, 97.6 [%]

Probability of dangerous Failure per Hour (PFH) 6.4 10-9 [1/h]

Compliance with global standards

CE marking LVD: EN 61800-5-1 EMC: EN 61800-3

MD: EN ISO 13849-1, EN 61800-5-2, EN 62061 UL standard UL 508C

Structure (IP rating) Force cooling, open (IP20) (Note 3)

Environment

Ambient temperature

Operation 0 C to 55 C (non-freezing) Storage -20 C to 65 C (non-freezing)

Ambient humidity

Operation 5 %RH to 90 %RH (non-condensing)

Storage

Ambience Indoors (no direct sunlight),

free from corrosive gas, flammable gas, oil mist, dust, and dirt Altitude 2000 m or less above sea level (Note 9) Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (X, Y, Z axes)

Mass [kg] 9.9 15.2 16 21

1. FUNCTIONS AND CONFIGURATION

1 - 19

Note 1. 0.3 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of

I/O points. 2. Test pulse is a signal which instantaneously turns off a signal to the drive unit at a constant period for external circuit to self-

diagnose. 3. Except for the terminal block. 4. The MR-J4-DU_B drive unit is compatible only with the two-wire type. The MR-J4-DU_B-RJ drive unit is compatible with the

two-wire type, four-wire type, and A/B/Z-phase differential output method. Refer to section 1.1 for details. 5. The communication cycle depends on the controller specifications and the number of axes connected. 6. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not

stop immediately but coasts at emergency stop. Ensure the safety in the entire equipment. For wiring of the external dynamic brake, refer to section 8.3.

7. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) with [Pr. PD07] to [Pr. PD09]. Doing so will cause the drive unit to become servo-off when an instantaneous power failure occurs.

8. The safety level depends on the setting value of [Pr. PF18 STO diagnosis error detection time] and whether STO input diagnosis by TOFB output is performed or not. For details, refer to the Function column of [Pr. PF18] in section 5.2.6 of "MR- J4-_B_(-RJ) Servo Amplifier Instruction Manual".

9. Follow the restrictions in section 2.5 when using this product at altitude exceeding 1000 m and up to 2000 m above sea level.

1. FUNCTIONS AND CONFIGURATION

1 - 20

(2) MR-J4-DU_A_(-RJ)

(a) 200 V class Model MR-J4-DU_(-RJ) 30KA 37KA

Output Rated voltage 3-phase 170 V AC Rated current [A] 174 204

Main circuit power supply input The main circuit power of the drive unit is supplied by the converter unit.

Control circuit power supply input

Voltage/Frequency 1-phase 200 V AC to 240 V AC, 50 Hz/60 Hz Rated current [A] 0.3 Permissible voltage fluctuation 1-phase 170 V AC to 264 V AC

Permissible frequency fluctuation Within 5%

Power consumption [W] 45

Inrush current [A] Refer to section 5.4.3. Interface power supply

Voltage 24 V DC 10% Current capacity [A] 0.5 (including CN8 connector signals) (Note 1)

Control method Sine-wave PWM control, current control method Dynamic brake External option (Note 5, 7) Fully closed loop control Compatible Load-side encoder interface (Note 6) Mitsubishi Electric high-speed serial communication

Communication function USB: connection to a personal computer or others (MR Configurator2-compatible)

RS-422/RS-485: 1 : n communication (up to 32 axes) Encoder output pulses Compatible (A/B/Z-phase pulse) Analog monitor Two channels

Position control mode

Max. input pulse frequency 4 Mpulses/s (for differential receiver) (Note 4), 200 kpulses/s (for open collector)

Positioning feedback pulse Encoder resolution (resolution per servo motor revolution): 22 bits

Command pulse multiplying factor Electronic gear A/B multiple, A:1 to 16777215, B:1 to 16777215, 1/10 < A/B < 4000

In-position range setting 0 pulse to 65535 pulses (command pulse unit) Error excessive 3 revolutions Torque limit Set with parameter or external analog input (0 V DC to +10 V DC/maximum torque)

Speed control mode

Speed control range Analog speed command 1: 2000, internal speed command 1: 5000 Analog speed command input 0 to 10 V DC/rated speed (The speed at 10 V is changeable with [Pr. PC12].)

Speed fluctuation ratio 0.01% or less (load fluctuation 0% to 100%), 0% (power fluctuation 10%), 0.2% or less (ambient temperature 25 C 10 C) when using analog speed command

Torque limit Set with parameter or external analog input (0 V DC to +10 V DC/maximum torque)

Torque control mode

Analog torque command input 0 V DC to 8 V DC/maximum torque (input impedance 10 k to 12 k)

Speed limit Set by parameter setting or external analog input (0 V DC to 10 V DC/rated speed)

Positioning mode Refer to section 1.1 of "MR-J4-_A_-RJ Servo Amplifier Instruction Manual (Positioning

Mode)" The positioning mode is available with MR-J4-DU_A_-RJ drive units with software version B3 or later.

Protective functions Overcurrent shut-off, overload shut-off (electronic thermal), servo motor overheat

protection, encoder error protection, undervoltage protection, instantaneous power failure protection, overspeed protection, and error excessive protection

Functional safety STO (IEC/EN 61800-5-2)

1. FUNCTIONS AND CONFIGURATION

1 - 21

Model MR-J4-DU_(-RJ) 30KA 37KA

Standards certified by CB (Note 9) EN ISO 13849-1 category 3 PL e, IEC 61508 SIL 3, EN 62061 SIL CL3, EN 61800-5-2

Response performance 8 ms or less (STO input off energy shut off)

Safety performance

Test pulse input (STO) (Note 3)

Test pulse interval: 1 Hz to 25 Hz Test pulse off time: Up to 1 ms

Mean time to dangerous failure (MTTFd) MTTFd 100 [years] (314a)

Diagnostic coverage (DC) DC = Medium, 97.6 [%]

Probability of dangerous Failure per Hour (PFH) 6.4 10-9 [1/h]

Compliance with global standards

CE marking LVD: EN 61800-5-1 EMC: EN 61800-3

MD: EN ISO 13849-1, EN 61800-5-2, EN 62061 UL standard UL 508C

Structure (IP rating) Force cooling, open (IP20) (Note 3)

Environment

Ambient temperature

Operation 0 C to 55 C (non-freezing) Storage -20 C to 65 C (non-freezing)

Ambient humidity

Operation 5 %RH to 90 %RH (non-condensing)

Storage

Ambience Indoors (no direct sunlight),

free from corrosive gas, flammable gas, oil mist, dust, and dirt Altitude 2000 m or less above sea level (Note 10) Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (X, Y, Z axes)

Mass [kg] 21 Note 1. 0.5 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of

I/O points. 2. Test pulse is a signal which instantaneously turns off a signal to the drive unit at a constant period for external circuit to self-

diagnose. 3. Except for the terminal block. 4. 1 Mpulse/s or lower commands are supported in the initial setting. When inputting commands between over 1 Mpulse/s and 4

Mpulses/s, change the setting in [Pr. PA13]. 5. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not

stop immediately but coasts at emergency stop. Ensure the safety in the entire equipment. For wiring of the external dynamic brake, refer to section 8.3.

6. The MR-J4-DU_A drive unit is compatible only with the two-wire type. The MR-J4-DU_A-RJ drive unit is compatible with the two-wire type, four-wire type, and A/B/Z-phase differential output method. Refer to section 1.1 for details.

7. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) with [Pr. PD23] to [Pr. PD26], [Pr. PD28], and [Pr. PD47]. Doing so will cause the drive unit to become servo-off when an instantaneous power failure occurs.

8. RS-485 communication is available with drive units manufactured in January 2015 or later. 9. The safety level depends on the setting value of [Pr. PF18 STO diagnosis error detection time] and whether STO input

diagnosis by TOFB output is performed or not. For details, refer to the Function column of [Pr. PF18] in section 5.2.6 of "MR- J4-_A_(-RJ) Servo Amplifier Instruction Manual".

10. Follow the restrictions in section 2.5 when using this product at altitude exceeding 1000 m and up to 2000 m above sea level.

1. FUNCTIONS AND CONFIGURATION

1 - 22

(b) 400 V class

Model MR-J4-DU_(-RJ) 30KA4 37KA4 45KA4 55KA4

Output Rated voltage 3-phase 323 V AC Rated current [A] 87 102 131 143

Main circuit power supply input The main circuit power of the drive unit is supplied by the converter unit. Voltage/Frequency 1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz Rated current [A] 0.2

Control circuit power supply input

Permissible voltage fluctuation 1-phase 323 V AC to 528 V AC

Permissible frequency fluctuation Within 5%

Power consumption [W] 45

Inrush current [A] Refer to section 5.4.3. Interface power supply

Voltage 24 V DC 10% Current capacity [A] 0.5 (including CN8 connector signals) (Note 1)

Control method Sine-wave PWM control, current control method Dynamic brake External option (Note 5, 7) Fully closed loop control Compatible Load-side encoder interface (Note 6) Mitsubishi Electric high-speed serial communication

Communication function USB: connection to a personal computer or others (MR Configurator2-compatible)

RS-422/RS-485: 1 : n communication (up to 32 axes) Encoder output pulses Compatible (A/B/Z-phase pulse) Analog monitor Two channels

Position control mode

Max. input pulse frequency 4 Mpulses/s (for differential receiver) (Note 4), 200 kpulses/s (for open collector)

Positioning feedback pulse Encoder resolution (resolution per servo motor revolution): 22 bits

Command pulse multiplying factor Electronic gear A/B multiple, A:1 to 16777215, B:1 to 16777215, 1/10 < A/B < 4000

In-position range setting 0 pulse to 65535 pulses (command pulse unit) Error excessive 3 revolutions Torque limit Set with parameter or external analog input (0 V DC to +10 V DC/maximum torque)

Speed control mode

Speed control range Analog speed command 1: 2000, internal speed command 1: 5000 Analog speed command input 0 to 10 V DC/rated speed (The speed at 10 V is changeable with [Pr. PC12].)

Speed fluctuation ratio 0.01% or less (load fluctuation 0% to 100%), 0% (power fluctuation 10%), 0.2% or less (ambient temperature 25 C 10 C) when using analog speed command

Torque limit Set with parameter or external analog input (0 V DC to +10 V DC/maximum torque)

Torque control mode

Analog torque command input 0 V DC to 8 V DC/maximum torque (input impedance 10 k to 12 k)

Speed limit Set by parameter setting or external analog input (0 V DC to 10 V DC/rated speed)

Positioning mode Refer to section 1.1 of "MR-J4-_A_-RJ Servo Amplifier Instruction Manual (Positioning

Mode)" The positioning mode is available with MR-J4-DU_A_-RJ drive units with software version B3 or later.

Protective functions Overcurrent shut-off, overload shut-off (electronic thermal), servo motor overheat

protection, encoder error protection, undervoltage protection, instantaneous power failure protection, overspeed protection, and error excessive protection

Functional safety STO (IEC/EN 61800-5-2)

1. FUNCTIONS AND CONFIGURATION

1 - 23

Model MR-J4-DU_(-RJ) 30KA4 37KA4 45KA4 55KA4

Safety performance

Standards certified by CB (Note 9) EN ISO 13849-1 category 3 PL e, IEC 61508 SIL 3, EN 62061 SIL CL3, EN 61800-5-2

Response performance 8 ms or less (STO input off energy shut off) Test pulse input (STO) (Note 3)

Test pulse interval: 1 Hz to 25 Hz Test pulse off time: Up to 1 ms

Mean time to dangerous failure (MTTFd) MTTFd 100 [years] (314a)

Diagnostic coverage (DC) DC = Medium, 97.6 [%]

Probability of dangerous Failure per Hour (PFH) 6.4 10-9 [1/h]

Compliance with global standards

CE marking LVD: EN 61800-5-1 EMC: EN 61800-3

MD: EN ISO 13849-1, EN 61800-5-2, EN 62061 UL standard UL 508C

Structure (IP rating) Force cooling, open (IP20) (Note 3)

Environment

Ambient temperature

Operation 0 C to 55 C (non-freezing) Storage -20 C to 65 C (non-freezing)

Ambient humidity

Operation 5 %RH to 90 %RH (non-condensing)

Storage

Ambience Indoors (no direct sunlight),

free from corrosive gas, flammable gas, oil mist, dust, and dirt Altitude 2000 m or less above sea level (Note 10) Vibration resistance 5.9 m/s2, at 10 Hz to 55 Hz (X, Y, Z axes)

Mass [kg] 16 21 Note 1. 0.5 A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of

I/O points. 2. Test pulse is a signal which instantaneously turns off a signal to the drive unit at a constant period for external circuit to self-

diagnose. 3. Except for the terminal block. 4. 1 Mpulse/s or lower commands are supported in the initial setting. When inputting commands between over 1 Mpulse/s and 4

Mpulses/s, change the setting in [Pr. PA13]. 5. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not

stop immediately but coasts at emergency stop. Ensure the safety in the entire equipment. For wiring of the external dynamic brake, refer to section 8.3.

6. The MR-J4-DU_A drive unit is compatible only with the two-wire type. The MR-J4-DU_A-RJ drive unit is compatible with the two-wire type, four-wire type, and A/B/Z-phase differential output method. Refer to section 1.1 for details.

7. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock) with [Pr. PD23] to [Pr. PD26], [Pr. PD28], and [Pr. PD47]. Doing so will cause the drive unit to become servo-off when an instantaneous power failure occurs.

8. RS-485 communication is available with drive units manufactured in January 2015 or later. 9. The safety level depends on the setting value of [Pr. PF18 STO diagnosis error detection time] and whether STO input

diagnosis by TOFB output is performed or not. For details, refer to the Function column of [Pr. PF18] in section 5.2.6 of "MR- J4-_A_(-RJ) Servo Amplifier Instruction Manual".

10. Follow the restrictions in section 2.5 when using this product at altitude exceeding 1000 m and up to 2000 m above sea level.

1. FUNCTIONS AND CONFIGURATION

1 - 24

1.5 Function list

For the drive unit functions not mentioned in this section, refer to section 1.5 of "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual" for MR-J4-DU_B_(-RJ) drive unit and "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" for MR-J4-DU_A_(-RJ) drive unit.

Function Description Supported model

MR-J4- DU_A_(-RJ)

MR-J4- DU_B_(-RJ)

MR-J4- _A_(-RJ)

MR-J4- _B_(-RJ)

Power monitoring function

This function calculates the power running energy and the regenerative power from the data in the servo amplifier such as speed and current. MR Configurator2 is necessary for this function. In principal, when the drive unit and servo amplifier are used with the converter unit, an error of approximately 15% may occur between the calculated value and the value measured by your power measuring instrument.

MR-CV_ power regeneration converter unit

MR-CV_ power regeneration converter unit returns regenerative power generated during deceleration of the servo motor back to the power supply, and share a common bus voltage with multiple MR-J4- DU_B_(-RJ) drive units and MR-J4-_B_(-RJ) servo amplifiers. MR-CV_ is compatible with MR-J4-DU_B_(-RJ) drive units and MR-J4-_B_(-RJ) servo amplifiers with software version C5 or later. Check the software version with MR Configurator2.

MR-CR_ resistance regeneration converter unit

MR-CR_ resistance regeneration converter unit consumes regenerative power generated during deceleration of the servo motor with the regenerative resistor.

1. FUNCTIONS AND CONFIGURATION

1 - 25

1.6 Configuration including peripheral equipment

1.6.1 MR-CV_ power regeneration converter unit

The diagram shows MR-J4-DU30KB4 and MR-J4-DU37KB4. The interface connection of the drive unit is the same as that of 22 kW or less servo amplifier. Refer to each servo amplifier instruction manual.

(Note 6) AC reactor (MR-AL-_K)

+

R S T

L1 L2

L11 L21

L3

L11 L21

L-

Protection coordination cable

USB cable

Drive unit

MR Configurator2

BU BV BW E U V W

L+ L-

Power regeneration converter unit

L+

(Note 3) Servo motor cooling fan power supply

R S T

L+ L-

Drive unit

Encoder cable

BU BV BW E U V W

R S T

Molded-case circuit breaker (MCCB)

L11 L21

(Note 2) Power supply

Line noise filter (FR-BLF)

(Note 4) Magnetic contactor (MC)

(Note 7) Magnetic contactor operation coil (I/O signal)

Molded-case circuit breaker (MCCB)

Molded-case circuit breaker (MCCB)

Personal computer

Servo motor

Servo motor

(Note 1)

(Note 8)

(Note 9)

(Note 9)

(Note 9)

1. FUNCTIONS AND CONFIGURATION

1 - 26

Note 1. In the actual connection, the power regeneration converter unit is closely mounted to the drive unit. 2. For the power supply specifications, refer to section 1.4. 3. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". 4. An bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration

during a forced stop deceleration. When dynamic brake deceleration is not required, delay the time to turn off the magnetic contactor.

5. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to section 8.5.)

6. Be sure to install an MR-AL-_AC reactor. 7. For the driving output of the magnetic contactor, refer to section 3.2. 8. When using the same power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-

CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor. Connect them closer to the power supply side than the broken line area.

9. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the selection of the overcurrent protection device.

1. FUNCTIONS AND CONFIGURATION

1 - 27

1.6.2 MR-CR_ resistance regeneration converter unit

The diagram shows MR-J4-DU30KB4 and MR-J4-DU37KB4. The interface connection of MR-J4-DU_(-RJ) is the same as that of MR-J4-_(-RJ). Refer to each servo amplifier instruction manual.

BV BWBU

L11 L21

L11

Line noise filter (FR-BLF)

R S T

+

MR Configurator2

L+

L-

(Note 1)

Resistance regeneration converter unit

VUE W

P2

P1

L1 L2 L3

P

C

S

R

L21

L-

R S T

L+

L11

L21

P1P2C

(Note 5)

(Note 2) Power supply

Personal computer

USB cable

Molded-case circuit breaker (MCCB)

(Note 4) Magnetic contactor (MC)

(Note 3) Servo motor cooling fan power supply

Magnetic contactor operation coil (I/O signal)

Molded-case circuit breaker (MCCB)

Encoder cable

Servo motor

Drive unit

Protection coordination cable

Regenerative option

Power factor improving DC reactor

(Note 6)

(Note 6)

1. FUNCTIONS AND CONFIGURATION

1 - 28

Note 1. The bus bars on L+ and L- for connecting the resistance regeneration converter unit to the drive unit are standard accessories.

In the actual connection, the resistance regeneration converter unit is closely mounted to the drive unit. 2. For the power supply specifications, refer to section 1.4. 3. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". 4. An bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration

during a forced stop deceleration. When dynamic brake deceleration is not required, delay the time to turn off the magnetic contactor.

5. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to section 8.5.)

6. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the selection of the overcurrent protection device.

2. INSTALLATION

2 - 1

2. INSTALLATION

WARNING To prevent electric shock, ground each equipment securely.

CAUTION

Stacking in excess of the specified number of product packages is not allowed. Do not hold the front cover, cables, or connectors when carrying the converter unit and drive unit. Otherwise, it may drop. Install the equipment on incombustible material. Installing them directly or close to combustibles will lead to a fire. Install the converter unit, the drive unit, and the servo motor in a load-bearing place in accordance with the Instruction Manual. Do not get on or put heavy load on the equipment. Otherwise, it may cause injury. Use the equipment within the specified environment. For the environment, refer to section 1.4. Provide adequate protection to prevent screws and other conductive matter, oil and other combustible matter from entering the converter unit and the drive unit. Do not block the intake and exhaust areas of the converter unit and the drive unit. Otherwise, it may cause a malfunction. Do not drop or apply heavy impact on the converter units, the drive units, and the servo motors. Otherwise, it may cause injury, malfunction, etc. Do not install or operate the converter unit and the drive unit which have been damaged or have any parts missing. When the product has been stored for an extended period of time, contact your local sales office. When handling the converter unit and the drive unit, be careful with the sharp edges of the converter unit and drive unit. The converter unit and the drive unit must be installed in a metal cabinet. When fumigants that contain halogen materials, such as fluorine, chlorine, bromine, and iodine, are used for disinfecting and protecting wooden packaging from insects, they cause a malfunction when entering our products. Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products, or treat packaging with methods other than fumigation, such as heat treatment. Additionally, disinfect and protect wood from insects before packing the products.

The following items are the same as those for MR-J4-_(-RJ). For the details of the items, refer to each chapter/section indicated in the detailed explanation field. "MR-J4-_B_" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

Model Item Detailed explanation MR-J4-DU_B_(-RJ) Encoder cable stress MR-J4-_B_ section 2.3 SSCNET III cable laying MR-J4-_B_ section 2.4 MR-J4-DU_A_(-RJ) Encoder cable stress MR-J4-_A_ Section 2.3

2. INSTALLATION

2 - 2

2.1 Installation direction and clearances

CAUTION

The equipment must be installed in the specified direction. Otherwise, it may cause a malfunction. Maintain specified clearances between the converter unit/drive unit and the inner surfaces of a control cabinet or other equipment. Otherwise, it may cause a malfunction.

2.1.1 When using MR-CV_ power regeneration converter unit

POINT Make sure to connect a drive unit to the right side of a power regeneration converter unit as shown in the diagram.

(1) Installation

(a) MR-CV_ power regeneration converter unit/MR-J4-DU_B_ drive unit

Drive unit 1 Drive unit 2Converter unit 30 mm or more

30 mm or more

80 mm or more

Side

100 mm or more

120 mm or more

Top

Bottom

2. INSTALLATION

2 - 3

(b) MR-CV_ power regeneration converter unit/MR-J4-DU_B_drive unit/MR-J4-_B_ servo amplifier

Keep the wiring length between L+/L- of the power regeneration converter unit and P4/N- of the servo amplifier 1.5 m or longer, and total wiring length 5 m or shorter.

Servo amplifier 1

Servo amplifier 2

Servo amplifier 3

Servo amplifier 4

10 mm or more

Terminal block

Converter unit

30 mm or more

30 mm or more

80 mm or more

100 mm or more

120 mm or more

Top

BottomTerminal block

Terminal block

Terminal block

Side

2. INSTALLATION

2 - 4

(2) Mounting hole process drawing

Power regeneration converter unit

Punched hole

Drive unit

Punched hole

38 0

36 0

0.

5 10

(1 0)

34 2

19 (1

9)

W6

W8 W7 W9 (W10)

(W8) W10

36 0

0.

5 10

(1 0)

34 2

19 (1

9)

W1

W3 W2 W4 (W5)

(W3) W5

4-A screw 4-B screw

38 0

36 0

0.

5 10

(1 0)

34 2

19 (1

9)

W6

W8 W7 W9 (W10)

(W8) W10

(W3)

36 0

0.

5 10

(1 0)

34 2

19 (1

9)

W1

W3 W4 (W5)W5

Power regeneration converter unit

Punched hole

Drive unit

Punched hole

2-A screw 2-B screw

For MR-CV_ 30 kW or more For MR-CV_ 18 kW or less

Drive unit Variable dimensions [mm] Screw size

W1 W2 W3 W4 W5 W6 W7 W8 W9 W10 A B MR-CV11K MR-CV18K MR-CV11K4 MR-CV18K4

90 45 82 4 M5

MR-CV30K MR-CV37K MR-CV45K MR-CV30K4 MR-CV37K4 MR-CV45K4

150 60 0.5 45 142 4 M5

MR-CV55K MR-CV55K4 MR-CV75K4

300 180 0.5 60 282 9 M5

MR-J4-DU30KB(-RJ) MR-J4-DU37KB(-RJ) MR-J4-DU45KB4(-RJ) MR-J4-DU55KB4(-RJ)

300 260 0.5 20 281 9.5 M6

MR-J4-DU900B(-RJ) MR-J4-DU11KB(-RJ) MR-J4-DU900B4(-RJ) MR-J4-DU11KB4(-RJ)

150 60 0.5 45 142 4 M5

MR-J4-DU15KB(-RJ) MR-J4-DU22KB(-RJ) MR-J4-DU15KB4(-RJ) MR-J4-DU22KB4(-RJ) MR-J4-DU30KB4(-RJ) MR-J4-DU37KB4(-RJ)

240 120 0.5 60 222 9 M5

2. INSTALLATION

2 - 5

2.1.2 When using MR-CR_ resistance regeneration converter unit

(1) Installation

POINT Make sure to connect a drive unit to the right side of a resistance regeneration converter unit as shown in the diagram.

Drive unit Resistance regeneration

converter unit 30 mm or more30 mm

or more

80 mm or more

100 mm or more

120 mm or more

Top

Bottom

SideFront

(2) Mounting hole process drawing

9.5

38 0

300

36 0

0.

5 10

20 260 0.5

(1 0)

281

34 2

19 (1

9)

(9.5) (20)

W1

W3 W2 W4 (W5)

(W3) W5

36 0

0.

5 10

(1 0)

34 2

19 (1

9)

Resistance regeneration converter unit

Punched hole

Drive unit

Punched hole

4-M6 screw 4-A screw

Resistance regeneration converter unit

Drive unit

Variable dimensions [mm] Screw

size

W1 W2 W3 W4 W5 A

MR-J4-DU30K_(-RJ) MR-J4-DU37K_(-RJ) MR-J4-DU45K_4(-RJ) MR-J4-DU55K_4(-RJ)

300 260 0.5 20 281 9.5 M6

MR-J4-DU30K_4(-RJ) MR-J4-DU37K_4(-RJ)

240 120 0.5 60 222 9 M5

(3) Others When using heat generating equipment such as the regenerative option, install them with full consideration of heat generation so that the converter unit and drive unit are not affected. Install the converter unit and drive unit on a perpendicular wall in the correct vertical direction.

2. INSTALLATION

2 - 6

2.2 Keeping out of foreign materials

(1) When drilling in the cabinet, prevent drill chips and wire fragments from entering the converter unit and the drive unit.

(2) Prevent oil, water, metallic dust, etc. from entering the converter unit and the drive unit through openings

in the cabinet or a cooling fan installed on the ceiling. (3) When installing the cabinet in a place where toxic gas, dirt, and dust exist, conduct an air purge (force

clean air into the cabinet from outside to make the internal pressure higher than the external pressure) to prevent such materials from entering the cabinet.

2.3 Inspection items

WARNING

Before starting maintenance and/or inspection, turn off the power and wait for 20 minutes or more until the charge lamp turns off. Then, confirm that the voltage between L+ and L- is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp is off or not, be sure to look at the lamp from the front of the converter unit. To avoid an electric shock, only qualified personnel should attempt inspections. For repair and parts replacement, contact your local sales office.

CAUTION Do not perform insulation resistance test on the converter unit and the drive unit. Otherwise, it may cause a malfunction. Do not disassemble and/or repair the equipment on customer side.

It is recommended that the following points periodically be checked. (1) Check for loose terminal block screws. Retighten any loose screws. (2) Check for scratches and cracks of cables and the like. Inspect them periodically according to operating

conditions especially when the servo motor is movable. (3) Check that the connectors are securely connected to the converter unit and the drive unit. (4) Check that the wires are not coming off from the connector. (5) Check for dust accumulation on the converter unit and the drive unit. (6) Check for unusual noise generated from the converter unit and the drive unit. (7) Make sure that the emergency stop circuit operates properly such that an operation can be stopped

immediately and a power is shut off by the emergency stop switch.

2. INSTALLATION

2 - 7

2.4 Parts having service life

Service life of the following parts is listed below. However, the service life varies depending on operating methods and environment. If any fault is found in the parts, they must be replaced immediately regardless of their service life. For parts replacement, please contact your local sales office.

Part name Life guideline Smoothing capacitor 10 years

Relay Number of power-on, forced stop by EM1

(Forced stop 1), controller forced stop, and on/off for STO: 100,000 times

Cooling fan 10,000 hours to 30,000 hours (2 years to 3 years)

Absolute position battery Refer to each servo amplifier instruction manual.

(1) Smoothing capacitor

The characteristic of smoothing capacitor is deteriorated due to ripple currents, etc. The life of the capacitor greatly depends on ambient temperature and operating conditions. The capacitor will reach the end of its life in 10 years of continuous operation in air-conditioned environment (ambient temperature of 40 C or less).

(2) Relays

Contact faults will occur due to contact wear arisen from switching currents. Relays reach the end of their lives when the number of power-on, forced stop by EM1 (Forced stop 1), controller forced stop, and on/off for STO while the servo motor is stopped under servo-off state reaches 100,000 times. However, the lives of relays may depend on the power supply capacity.

(3) Cooling fan

The cooling fan bearings reach the end of their lives in 10,000 hours to 30,000 hours. Normally, therefore, the cooling fan must be replaced in a few years of continuous operation as a guideline. If unusual noise or vibration is found during inspection, the cooling fan must also be replaced. The life indicates under the yearly average ambient temperature of 40 C, free from corrosive gas, flammable gas, oil mist, dust and dirt.

2. INSTALLATION

2 - 8

2.5 Restrictions when using this product at altitude exceeding 1000 m and up to 2000 m above sea level

(1) Effective load ratio and regenerative load ratio As heat dissipation effects decrease in proportion to decreasing air density, use the product within the effective load ratio and regenerative load ratio shown in the following figure.

0 20001000 Altitude

95 100

0

R eg

en er

at iv

e lo

ad ra

tio Ef

fe ct

iv e

lo ad

ra tio

[%]

[m]

(2) Input voltage Generally, a withstand voltage decreases as the altitude increases; however, there is no restriction on the withstand voltage. Use in the same manner as in 1000 m or less. (Refer to section 1.4.)

(3) Parts having service life

(a) Smoothing capacitor The capacitor will reach the end of its life in 10 years of continuous operation in air-conditioned environment (ambient temperature of 30 C or less).

(b) Relay

There is no restriction. Use in the same manner as in 1000 m or less. (Refer to section 2.4.)

(c) Cooling fan of the converter unit/drive unit There is no restriction. Use in the same manner as in 1000 m or less. (Refer to section 2.4.)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 1

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

POINT MR-CV_ power regeneration converter unit can be used in a combination with MR-J4-DU_B_(-RJ) drive units and MR-J4-_B_(-RJ) servo amplifiers.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 2

3.1 Function block diagram

The function block diagram of this servo is shown below.

POINT The diagram shows the combination of the MR-J4-DU_B_-RJ drive unit and power regeneration converter unit as an example. The MR-J4-DU_B_ drive unit does not have the CN2L connector.

AC reactor

+

MC Thyristor

Control circuit power supply

L11

L21

L1

L2

L3

I/F

Charge lamp

Power regeneration converter unit

Power supply

Cooling fan

CPU

Malfunction, forced stop

Power regeneration converter unit Protection coordination

To CN40A of drive unit

To L11 of drive unit

To L21 of drive unit

To L+ of drive unitL+

To L- of drive unitL-

MC drive

Current detection

Voltage detection

MCCB

+

MCCB

MCCB

U

Base amplifier

CN23 CN24 CN25 CN4

Alarm output

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 3

External dynamic brake

(optional)

(Note 3)

From CN4 of power regeneration converter unit

Model position control

Model speed control

Position command

input

Model position

Actual position control

Actual speed control

Current control

Model speed Model torque

Virtual motor

Virtual encoder

C N

40 A

CN5

USB

USB

Personal computer

Controller or

drive unit

I/F Control

Drive unit or cap

CN1A CN1B CN3

D/A

Analog monitor (2 channels)

Digital I/O control

BU BV BW

Base amplifier

L11

L21

Drive unit

Current detection

Current detector

C N

2

U

V

W

U

V

W M

From MCCB

Overcurrent protection

Control circuit power supply

(Note 1) Power supply

From L+ of power regeneration converter unit

L+

From L- of power regeneration converter unit

L-

Battery (for absolute position detection system)

C N

4

Cooling fan

MCCB

+

C N

2L

C N

8STO Switch

STO Control circuit

External encoder

(Note 2)

Step- down circuit

Servo motor

Encoder

Cooling fan (Note 4)

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". 2. This is for the MR-J4-DU_B_-RJ drive unit. The MR-J4-DU_B_ drive unit does not have the CN2L connector. 3. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not

stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For wiring of the external dynamic brake, refer to section 8.3. For alarms in which the servo motor does not decelerate to stop, refer to chapter 6.

4. When using the same power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR- CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 4

3.2 Structure (parts identification)

(1) MR-CV18K(4) or less

POINT The unit is shown with the terminal cover open. For opening or closing of the terminal cover, refer to section 4.2.2.

(1) (2)

(12)

(5)

(4)

(14)

(11)

(7)

(10)

(13)

(9)

(8)

(6)

(3)

No. Name/Application Detailed explanation

(1) Display The 1-digit, 7-segment LED display shows the power regeneration converter unit status and the alarm number.

Section 3.4.3

(2) Converter setting rotary switch (SW1) Set the function of the power regeneration converter unit.

Section 3.4.3

(3) Protection coordination connector (CN4) Connect to CN40A of the drive unit.

Section 3.3.1

(4)

Manufacturer setting connector (CN9) This is for manufacturer setting. Although the shape is similar to the protection coordination connector (CN4), do not connect anything including the protection coordination cable.

(5)

Manufacturer setting connector (CN41) This is for manufacturer setting. Although the shape is similar to the protection coordination connector (CN4), do not connect anything including the protection coordination cable.

(6) I/O signal connector (CN24) Used to connect digital I/O signals.

Section 3.3.4

(7)

Magnetic contactor control connector (CNP23) Connect to the coil of the magnetic contactor.

Section 3.3.1

Section 3.3.3

(8) Charge lamp When the main circuit is charged, this will light up. While this lamp is lit, do not reconnect the wires.

(9) L+/L- terminal (TE2) Connect to a drive unit with a bus bar.

Section 3.3.1

(10) Control circuit terminal L11/L21 (TE3) Connect to the control circuit power supply.

Section 3.3.1

(11)

Alarm output connector (CN25) This connector, having a form C contact, outputs an alarm when the protective function of the power regeneration converter unit is activated and the power output to the drive unit is stopped.

Section 3.3.4

(12) Main circuit terminal block (TE1) Connect to the input power supply.

Section 3.3.1

(13) Protective earth (PE) terminal Section 3.3.8

(14) Rating plate Section 1.2

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 5

(2) MR-CV30K(4)/MR-CV37K(4)/MR-CV45K(4)

(1) (2)

(12)

(5)

(4)

(14)

(11)

(7)

(10)

(13)

(9)

(8)

(6)

(3)

No. Name/Application Detailed explanation

(1) Display The 1-digit, 7-segment LED display shows the power regeneration converter unit status and the alarm number.

Section 3.4.3

(2) Converter setting rotary switch (SW1) Set the function of the power regeneration converter unit.

Section 3.4.3

3 Protection coordination connector (CN4) Connect to CN40A of the drive unit.

Section 3.3.1

(4)

Manufacturer setting connector (CN9) This is for manufacturer setting. Although the shape is similar to the protection coordination connector (CN4), do not connect anything including the protection coordination cable.

(5)

Manufacturer setting connector (CN41) This is for manufacturer setting. Although the shape is similar to the protection coordination connector (CN4), do not connect anything including the protection coordination cable.

(6) I/O signal connector (CN24) Used to connect digital I/O signals.

Section 3.3.4

(7)

Magnetic contactor control connector (CNP23) Connect to the coil of the magnetic contactor.

Section 3.3.1

Section 3.3.3

(8) Charge lamp When the main circuit is charged, this will light up. While this lamp is lit, do not reconnect the wires.

(9) L+/L- terminal (TE2) Connect to a drive unit with a bus bar.

Section 3.3.1

(10) Control circuit terminal L11/L21 (TE3) Connect to the control circuit power supply.

Section 3.3.1

(11)

Alarm output connector (CN25) This connector, having a form C contact, outputs an alarm when the protective function of the power regeneration converter unit is activated and the power output to the drive unit is stopped.

Section 3.3.4

(12) Main circuit terminal block (TE1) Connect to the input power supply.

Section 3.3.1

(13) Protective earth (PE) terminal Section 3.3.8

(14) Rating plate Section 1.2

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 6

(3) MR-CV55K(4)/MR-CV75K4/MR-CV55K

The diagram shows MR-CV55K4.

(13) (10)(14)(11)

(1)

(12)

(8)

(2) (6) (15)

(7)

(9)

(4)

(3)

(5)

No. Name/Application Detailed explanation

(1) Display The 1-digit, 7-segment LED display shows the power regeneration converter unit status and the alarm number.

Section 3.4.3

(2) Converter setting rotary switch (SW1) Set the function of the power regeneration converter unit.

Section 3.4.3

(3) Protection coordination connector (CN4) Connect to CN40A of the drive unit.

Section 3.3.1

(4)

Manufacturer setting connector (CN9) This is for manufacturer setting. Although the shape is similar to the protection coordination connector (CN4), do not connect anything including the protection coordination cable.

(5)

Manufacturer setting connector (CN41) This is for manufacturer setting. Although the shape is similar to the protection coordination connector (CN4), do not connect anything including the protection coordination cable.

(6) I/O signal connector (CN24) Used to connect digital I/O signals.

Section 3.3.4

(7)

Magnetic contactor control connector (CNP23) Connect to the coil of the magnetic contactor.

Section 3.3.1

Section 3.3.3

(8) Charge lamp When the main circuit is charged, this will light up. While this lamp is lit, do not reconnect the wires.

(9) Manufacturer setting terminal (TE2-1) This is for manufacturer setting. Leave this open.

to 10 L+/L- terminal (TE2-2) Connect to a drive unit with a bus bar.

Section 3.3.1

(11) Control circuit terminal L11/L21 (TE3) Connect to the control circuit power supply.

Section 3.3.1

(12)

Alarm output connector (CN25) This connector, having a form C contact, outputs an alarm when the protective function of the power regeneration converter unit is activated and the power output to the drive unit is stopped.

Section 3.3.4

(13) Main circuit terminal block (TE1) Connect to the input power supply.

Section 3.3.1

(14) Protective earth (PE) terminal Section 3.3.8

(15) Rating plate Section 1.2

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 7

3.3 Signals and wiring

WARNING

Any person who is involved in wiring should be fully competent to do the work. Before wiring, turn off the power and wait for 20 minutes or more until the charge lamp turns off. Then, confirm that the voltage between L+ and L- is safe with a voltage tester or others. Otherwise, an electric shock may occur. In addition, when confirming whether the charge lamp is off or not, be sure to look at the lamp from the front of the power regeneration converter unit. Ground the power regeneration converter unit, drive unit, and servo motor securely. Do not attempt to wire the power regeneration converter unit, drive unit, and servo motor until they have been installed. Otherwise, it may cause an electric shock. The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric shock. To avoid an electric shock, insulate the connections of the power supply terminals.

CAUTION

Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly, resulting in injury. Connect cables to the correct terminals. Otherwise, a burst, damage, etc., may occur. Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc., may occur. The surge absorbing diode installed to the DC relay for control output should be fitted in the specified direction. Otherwise, the servo amplifier will malfunction and will not output signals, disabling the emergency stop and other protective circuits.

DOCOM

RA

24 V DC

Power regeneration converter unit

For sink output interface

Control output signal

DOCOM

Power regeneration converter unit

RAControl output signal

24 V DC

For source output interface

Use a noise filter, etc., to minimize the influence of electromagnetic interference. Electromagnetic interference may affect the electronic equipment used near the power regeneration converter unit and the drive unit. Do not modify the equipment.

The following items are the same as those for MR-J4-_(-RJ). For the details of the items, refer to each chapter/section indicated in the detailed explanation field. "MR-J4-_B_" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

Model Item Detailed explanation

MR-J4-DU_B_(-RJ) I/O signal connection example MR-J4-_B_ section 3.2 Forced stop deceleration function MR-J4-_B_ section 3.6 SSCNET III cable connection MR-J4-_B_ section 3.9

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 8

3.3.1 Connection example of power circuit

WARNING Insulate the connections of the power supply terminals. Otherwise, an electric shock may occur.

CAUTION

Be sure to connect a magnetic contactor between the power supply and the main circuit power supply (L1/L2/L3) of the power regeneration converter unit, in order to configure a circuit that shuts off the power supply by the magnetic contactor. If the magnetic contactor is not connected, a large current keeps flowing and may cause a fire when the power regeneration converter unit or the drive unit malfunctions. Use ALM (Malfunction) to shut the power off. Not doing so may cause a fire when the power regeneration converter unit malfunctions and causes the AC reactor to overheat. The power regeneration converter unit has a built-in surge absorber (varistor) to reduce exogenous noise and to suppress lightning surge. Exogenous noise or lightning surge deteriorates the varistor characteristics, and the varistor may be damaged. To prevent a fire, use a molded-case circuit breaker or fuse for the input power supply. Check the power regeneration converter unit model, and then input proper voltage to the power regeneration converter unit power supply. If input voltage exceeds the upper limit, the power regeneration converter unit and the drive unit will break down.

POINT

For drive units, EM2 has the same function as EM1 in the torque control mode. For the MR-J4-DU_B_(-RJ) drive units, do not shut off the control circuit power supply even if an alarm occurs. When the control circuit power supply is shut off, an optical module does not operate, and optical transmission of SSCNET III/H communication is interrupted. Therefore, the next servo amplifiers and drive units show "AA" on the display and shut off the base circuit, stopping the servo motors with the dynamic brake.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 9

(1) Magnetic contactor control connector (CNP23)

By enabling magnetic contactor drive output, the main circuit power supply can be shut off automatically when an alarm occurs in the power regeneration converter unit or the drive unit. To enable magnetic contactor drive output, set the converter setting rotary switch (SW1) of the power regeneration converter unit to "0" or "4".

(a) When magnetic contactor drive output is enabled

Connecting the magnetic contactor control connector (CNP23) to the operating coil of the magnetic contactor enables to control the magnetic contactor.

MCCB

Power regeneration converter unit

1MC1

3MC2

CN23

L1

L2

L3

(Note 2) MC

L11

L21

RA2 MC

SK (Note 1)

RA1 (Note 1)

AC reactor

(Note 3)

Drive unit malfunction

Drive unit malfunction Emergency stop

switch Operation ready OFF/ON

3-phase 200 to 240 V AC, 50/60 Hz

Note 1. When multiple drive units are connected to a converter unit, configure a circuit that the forced stop of the servo system controller is inputted by an alarm signal of each drive unit, and create a sequence in which the states of all drive units will be ready-off if an alarm occurs in one of the drive units. When the state of the drive unit and servo amplifier is ready-off (forced stop state by the controller), the servo motor coasts. Set a dynamic brake to stop the servo motor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. When one drive unit is connected, and the forced stop deceleration is enabled, a bus voltage may drop, depending on the main circuit voltage and operation pattern, causing dynamic brake deceleration during forced stop deceleration. When dynamic brake deceleration is not required, delay the time to turn off the magnetic contactor.

3. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others). (Refer to section 8.5.)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 10

When the power regeneration converter unit receives a start command from the drive unit, CNP23-1 pin (MC1) and CN23-3 pin (MC2) which are connected to the AC power supply will be shorted to supply a power to the control circuit of the magnetic contactor. When the control circuit power is supplied, the magnetic contactor turns on, and the main circuit power will be supplied to the power regeneration converter unit. In the following cases, CN23-1 (MC1) and CN23-1 pin (MC2) in the power regeneration converter unit will be opened, and the main circuit power supply will be automatically shut off.

1) An alarm has occurred in the power regeneration converter unit.

2) An alarm has occurred in the drive unit.

3) The EM1 (forced stop) of the power regeneration converter unit was turned off.

4) [AL. 95 STO warning] has occurred in the drive unit.

(b) When magnetic contactor drive output is disabled

The main circuit power supply does not shut off automatically even when an alarm occurs in the power regeneration converter unit or the drive unit. Therefore, configure an external circuit to shut off the main circuit power supply when an alarm is detected.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 11

(2) Wiring

(a) Connecting one drive unit to one power regeneration converter unit 1) When magnetic contactor drive output is enabled (factory setting)

POINT

The power regeneration converter unit controls the magnetic contactor. Connect the power regeneration converter unit and the adjacent drive unit with MR-CUL06M protection coordination cable. Be sure to simultaneously turn on and off the control circuit power supplies of the power regeneration converter unit and the drive unit.

a) 200 V class

Drive unit

L+

L-

L+ L-

L11

L21

TE3

CN3

EM2

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

(Note 3) Main circuit power supply

CN40A

CN1A CN1B

CN2 CN2

Dynamic brake

Servo system controller

BV

M

(Note 1) Power supply

BW

BU

(Note 4)

To drive unit or servo amplifier in other power supply system

V

U

W

V

U

W

Protection coordination

cable

Dedicated bus bar

CN4

(Note 5)

(Note 6)

SSCNET III cableSSCNET III cable

Short-circuit connector (packed with the drive unit)

MCCB

1MC1

3MC2

CN23

L1

L2

L3

(Note 2) MC

L11

L21

RA1 (Note 5)

SK

L+

L-

(Note 7, 8)

(Note 7, 8)

MC

RA1

Drive unit malfunction Emergency stop

switch Operation ready

OFF/ON

3-phase 200 to 240 V AC, 50/60 Hz

AC reactor

Power regeneration converter unit

Plate

Cooling fan

Servo motor

Encoder

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 12

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same

power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. Configure a sequence that will shut off the main circuit power when an alarm occurs. 6. When EM2 is used to decelerate the servo motor to a stop, the converter unit shuts off the main circuit power supply with the

protection coordination after the servo motor has stopped. 7. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to

section 8.5.) 8. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 13

b) 400 V class

L+

L-

L+ L-

L11

L21

TE3

CN3

EM2

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

CN8

CN2 CN2

BV

M

BW

BU

(Note 4)

V

U

W

V

U

W

CN4

(Note 5)

(Note 6)

MCCB

1MC1

3MC2

CN23

L1

L2

L3

(Note 2) MC

3-phase 380 to 480 V AC, 50/60 Hz

L11

L21

L+

L-

(Note 7, 9)

(Note 7, 9)

(Note 8) Step-down transformer

RA1

SK

MC

CN40A

CN1A CN1B

RA1 (Note 5)

Drive unit malfunction Emergency stop

switch Operation ready

OFF/ON

AC reactor Drive unit

Power regeneration converter unit

Dedicated bus bar

Protection coordination

cable

Servo system controller

SSCNET III cable SSCNET III cable

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

Plate

To drive unit or servo amplifier in other power supply system

Dynamic brake

Cooling fan

Servo motor

Encoder

(Note 1) Power supply

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 14

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same

power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. Configure a sequence that will shut off the main circuit power when an alarm occurs. 6. When EM2 is used to decelerate the servo motor to a stop, the converter unit shuts off the main circuit power supply with the

protection coordination after the servo motor has stopped. 7. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to

section 8.5.) 8. A step-down transformer is required when the coil voltage of the magnetic contactor is 200 V class. 9. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 15

2) When magnetic contactor drive output is disabled

POINT

The power regeneration converter unit controls the magnetic contactor. Connect the power regeneration converter unit and the adjacent drive unit with MR-CUL06M protection coordination cable. Be sure to simultaneously turn on and off the control circuit power supplies of the power regeneration converter unit and the drive unit.

a) 200 V class

RA1

L+

L-

L+ L-

L11

L21

TE3

CN3

EM2

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM

CN8

CN2 CN2

BV

M

BW

BU

(Note 4)

V

U

W

V

U

W

CN4

(Note 5)

MCCB

BB

CC

(Note 7) CN25

L1

L2

L3

L11

L21

Converter unit malfunction

RA2 (Note 5)

SK

L+

L-

(Note 6, 8)

(Note 6, 8)

RA2

24 V DC

MC

CN40A

CN1A CN1B

RA1 (Note 5)

Drive unit malfunction Emergency stop

switch Operation ready

OFF/ON

(Note 2) MC

AC reactor

3-phase 200 to 240 V AC, 50/60 Hz

Dedicated bus bar

Protection coordination

cable

Servo system controller

SSCNET III cable

Drive unit Power regeneration

converter unit

24 V DC

Plate

SSCNET III cable

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

Dynamic brake

Cooling fan

Servo motor

Encoder

(Note 1) Power supply

To drive unit or servo amplifier in other power supply system

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 16

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same

power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. Configure a sequence that will shut off the main circuit power when an alarm occurs. 6. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to

section 8.5.) 7. Connect to an error output (A/B/C) via a relay coil, etc. 8. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 17

b) 400 V class

RA1

L+

L-

L+ L-

L11

L21

TE3

CN3

EM2

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

CN8

CN2 CN2

BV

M

BW

BU

V

U

W

V

U

W

CN4

(Note 5)

MCCB

BB

CC

(Note 8) CN25

L1

L2

L3

L11

L21

SK

L+

L-

(Note 6, 9)

(Note 6, 9)

RA2

24 V DC

MC

(Note 7) Step-down transformer

CN40A

CN1A CN1B

(Note 1) Power supply

Cooling fan

Servo motor

Encoder

(Note 4)

To drive unit or servo amplifier in other power supply system

Dynamic brake

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

SSCNET III cable SSCNET III cable

Plate

Dedicated bus bar

Protection coordination

cable

Servo system controller

Drive unit Power regeneration

converter unit (Note 2)

MC AC reactor

Converter unit malfunction

RA2 (Note 5) Emergency stop

switch Operation ready

OFF/ON

3-phase 380 to 480 V AC, 50/60 Hz

Drive unit malfunction

RA1 (Note 5)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 18

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same

power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. Configure a sequence that will shut off the main circuit power when an alarm occurs. 6. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to

section 8.5.) 7. A step-down transformer is required when the coil voltage of the magnetic contactor is 200 V class. 8. Connect to an error output (A/B/C) via a relay coil, etc. 9. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 19

(b) Connecting multiple drive units to one power regeneration converter unit

1) When magnetic contactor drive output is enabled (factory setting)

POINT The power regeneration converter unit controls the magnetic contactor. Connect the power regeneration converter unit and the adjacent drive unit with MR-CUL06M protection coordination cable. When multiple drive units are connected to one power regeneration converter unit, use EM1 for the emergency stop of the drive unit, and stop the servo motor with the dynamic brake if an error occurs. Set [Pr. PA04] to "0000" to enable EM1. Set [Pr. PA02] to "4700" and [Pr. PF03] to "0100" for the drive unit to which the protection coordination cable is not connected. Be sure to simultaneously turn on and off the control circuit power supplies of the power regeneration converter unit and the drive unit.

a) 200 V class

L+

L-

L+ L-

L11

L21

TE3

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

CN8

CN2 CN2

BV

M

BW

BU

(Note 4) (Note 4)

V

U

W

V

U

W

CN2 CN2

BV

M

BW

BU

V

U

W

V

U

W

CN4

L+

L-

L11

L21

TE3

(Note 5)

(Note 6)

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

(Note 5)

(Note 6)

24 V DC

Forced stop (Note 6)

CN8

MCCB

1MC1

3MC2

CN23

L1

L2

L3

3-phase 200 to 240 V AC, 50/60 Hz

L11

L21

SK

L+

L-

(Note 7, 8)

(Note 7, 8)

(Note 7, 8)

MC

RA1 RA2

CN40A

CN1A CN1B

Drive unit malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch

Drive unit malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch

Operation ready OFF/ON

(Note 2) MC

AC reactor Drive unit Drive unit

Power regeneration converter unit

Dedicated bus bar

Dedicated bus bar

Protection coordination

cable

SSCNET III cable SSCNET III cableServo system controller

(Note 1) Power supply

(Note 1) Power supply

Plate Plate

Cooling fan Cooling fan

Servo motor Servo motor

Encoder Encoder

Dynamic brake

Dynamic brake

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 20

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same

power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM1 in the drive unit when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. When connecting multiple drive units, configure a sequence that will shut off the main circuit power if an alarm occurs even in one axis.

6. Configure a sequence in which the servo system controller will stop all the drive units if an alarm occurs even in one drive unit. 7. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to

section 8.5.) 8. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 21

b) 400 V class

L+

L-

L+ L-

L11

L21

TE3

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

CN8

CN2 CN2

BV

M

BW

BU

(Note 4) (Note 4)

V

U

W

V

U

W

CN2 CN2

BV

M

BW

BU

V

U

W

V

U

W

CN4

L+

L-

L11

L21

TE3

(Note 5)

(Note 6)

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

(Note 5)

(Note 6)

24 V DC

CN8

MCCB

1MC1

3MC2

CN23

L1

L2

L3

(Note 8) Step-down transformer

L11

L21

SK

L+

L-

(Note 7, 9)

(Note 7, 9)

(Note 7, 9)

MC

RA1 RA2

CN40A

CN1A CN1B

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

Cooling fan

Servo motor

Encoder

Dynamic brake

Cooling fan

Servo motor

Encoder

Dynamic brake

(Note 1) Power supply

(Note 1) Power supply

Plate Plate

SSCNET III cable SSCNET III cable

Drive unit Drive unit

Dedicated bus bar

Dedicated bus bar

Protection coordination

cable

Power regeneration converter unit

Servo system controller

Forced stop (Note 6)

Drive unit malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch

(Note 2) MC

AC reactor

Drive unit malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch Operation ready

OFF/ON

3-phase 380 to 480 V AC, 50/60 Hz

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM1 in the drive unit when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. When connecting multiple drive units, configure a sequence that will shut off the main circuit power if an alarm occurs even in one axis.

6. Configure a sequence in which the servo system controller will stop all the drive units if an alarm occurs even in one drive unit. 7. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to

section 8.5.) 8. A step-down transformer is required when the coil voltage of the magnetic contactor is 200 V class. 9. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 22

2) When magnetic contactor drive output is disabled

a) 200 V class

L+

L-

L+ L-

L11

L21

TE3

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

CN8

CN2 CN2

BV

M

BW

BU

(Note 4) (Note 4)

V

U

W

V

U

W

CN2 CN2

BV

M

BW

BU

V

U

W

V

U

W

CN4

L+

L-

L11

L21

TE3

(Note 5)

(Note 6)

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

(Note 5)

(Note 6)

24 V DC

CN8

MCCB L1

L2

L3

L11

L21

SK

L+

L-

(Note 7, 9)

(Note 7, 9)

(Note 7, 9)

MC

RA1 RA2

BB

CC

(Note 8) CN25

RA3

24 V DC

CN40A

CN1A CN1B

Drive unit malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch Operation ready

OFF/ON

Converter unit malfunction

RA3 (Note 5)

Drive unit malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch

Forced stop (Note 6)

Servo system controller

SSCNET III cable SSCNET III cable

Dynamic brake

Dynamic brake

Dedicated bus bar

Dedicated bus bar

Protection coordination

cable

(Note 2) MC

AC reactor Drive unit Drive unit

Power regeneration converter unit

3-phase 200 to 240 V AC, 50/60 Hz

Plate Plate

(Note 1) Power supply

(Note 1) Power supply

Cooling fan

Servo motor

Encoder

Cooling fan

Servo motor

Encoder

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 23

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same

power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM1 in the drive unit when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. When connecting multiple drive units, configure a sequence that will shut off the main circuit power if an alarm occurs even in one axis.

6. Configure a sequence in which the servo system controller will stop all the drive units if an alarm occurs even in one drive unit. 7. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to

section 8.5.) 8. Connect to an error output (A/B/C) via a relay coil, etc. 9. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 24

b) 400 V class

L+

L-

L+ L-

L11

L21

TE3

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

CN8

CN2 CN2

BV

M

BW

BU

(Note 4) (Note 4)

V

U

W

V

U

W

CN2 CN2

BV

M

BW

BU

V

U

W

V

U

W

CN4

L+

L-

L11

L21

TE3

(Note 5)

(Note 6)

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

(Note 5)

(Note 6)

24 V DC

CN8

MCCB L1

L2

L3

L11

L21

SK

L+

L-

(Note 7, 10)

(Note 7, 10)

(Note 7, 10)

MC

RA1 RA2

BB

CC

(Note 8) CN25

RA3

24 V DC

CN40A

CN1A CN1B

Drive unit malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch Operation ready

OFF/ON

Converter unit malfunction

RA3 (Note 5)

Drive unit Drive unit

Dedicated bus bar

Dedicated bus bar

Power regeneration converter unit

(Note 2) MC

AC reactor

3-phase 380 to 480 V AC, 50/60 Hz

(Note 9) Step-down transformer

Protection coordination

cable

Servo system controller

Forced stop (Note 6)

Drive unit malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch

SSCNET III cable SSCNET III cable

Plate Plate

Cooling fan

Servo motor

Encoder

Dynamic brake

Cooling fan

Servo motor

Encoder

Dynamic brake

(Note 1) Power supply

(Note 1) Power supply

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM1 in the drive unit when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. When connecting multiple drive units, configure a sequence that will shut off the main circuit power if an alarm occurs even in one axis.

6. Configure a sequence in which the servo system controller will stop all the drive units if an alarm occurs even in one drive unit. 7. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to

section 8.5.) 8. Connect to an error output (A/B/C) via a relay coil, etc. 9. A step-down transformer is required when the coil voltage of the magnetic contactor is 200 V class. 10. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 25

(c) Connecting multiple drive units and servo amplifiers to one power regeneration converter unit

1) When magnetic contactor drive output is enabled (factory setting)

POINT The power regeneration converter unit controls the magnetic contactor. Connect the power regeneration converter unit and the adjacent drive unit with MR-CUL06M protection coordination cable. When multiple drive units and servo amplifiers are connected to one power regeneration converter unit, use EM1 for the emergency stop of the drive units and servo amplifiers, and stop the servo motors with the dynamic brake if an error occurs. Set [Pr. PA04] to "0000" to enable EM1. Set [Pr. PA02] to "4700" and [Pr. PF03] to "0100" for the drive unit to which the protection coordination cable is not connected. Be sure to simultaneously turn on and off the control circuit power supplies of the power regeneration converter unit, drive unit, and servo amplifier.

a) 200 V class

L+

L-

L+ L-

L11

L21

TE3

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

CN8

CN2 CN2

BV

M

BW

BU

(Note 4)

V

U

W

V

U

W

CN2 CN2

BV

M

BW

BU

V

U

W

V

U

W

CN4

Servo amplifier

To the next servo amplifier

P4 (Note 8)

N-

L11

L21

TE3

(Note 5)

(Note 9)

(Note 6)

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

(Note 5)

(Note 6)

24 V DC

CN8

MCCB

1MC1

3MC2

CN23

L1

L2

L3

L11

L21

SK

L+

L-

(Note 7, 12)

(Note 7)

(Note 7, 12)

MC

RA1 RA2

(Note 10, 11)

CN40A

CN1A CN1B

Servo amplifier malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch

Servo amplifier malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch

Operation ready OFF/ON

3-phase 200 to 240 V AC, 50/60 Hz

(Note 2) MC

AC reactor

Power regeneration converter unit Drive unit

Dedicated bus bar

Protection coordination

cable

SSCNET III cable SSCNET III cable

Plate Plate

Forced stop (Note 6)

Servo system controller

(Note 1) Power supply

(Note 1) Power supply

Cooling fan

Servo motor

Encoder

Cooling fan

Servo motor

Encoder

Dynamic brake

(Note 3) Main circuit power supply

Short-circuit connector (Packed with the servo amplifier)

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 26

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same

power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit and servo amplifier, configure a circuit to turn off EM1 in the drive unit and servo amplifier when the main circuit power is turned off.

4 Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. When connecting multiple drive units and servo amplifiers, configure a sequence that will shut off the main circuit power if an alarm occurs even in one axis.

6. Configure a sequence in which the servo system controller will stop all the drive units (servo amplifiers) if an alarm occurs even in one drive unit (servo amplifier).

7. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to section 8.5.)

8. For the terminal block and connector, refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". 9. Connect the main circuit power supply of the servo amplifier via a terminal block, and keep the wiring length of 1.5 m or longer. 10. Be sure to disconnect between P3 and P4. 11. When using the servo amplifier of 7 kW or less, make sure to connect the built-in regenerative resistor. (factory-wired) (5 kW

or less: P+ and D, 7 kW or less: P+ and C) 12. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 27

b) 400 V class

L+

L-

L+ L-

L11

L21

TE3

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

CN8

CN2 CN2

BV

M

BW

BU

V

U

W

V

U

W

CN2 CN2

BV

M

BW

BU

V

U

W

V

U

W

CN4

P4 (Note 9)

N-

L11

L21

TE3

(Note 10)

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

24 V DC

CN8

MCCB

1MC1

3MC2

CN23

L1

L2

L3

L11

L21

SK

L+

L-

(Note 7, 13)

(Note 7)

(Note 7, 13)

MC

RA1 RA2

CN40A

CN1A CN1B

Servo amplifier malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch Operation ready

OFF/ON

(Note 2) MC

AC reactor

Dedicated bus bar

Power regeneration converter unit Drive unit

Protection coordination

cable

SSCNET III cable SSCNET III cableServo system controller

Servo amplifier malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch

Forced stop (Note 6)

(Note 1) Power supply

(Note 1) Power supply

Cooling fan

Servo motor

Cooling fan

Servo motor

Encoder Encoder

(Note 4)Dynamic brake

Plate Plate (Note 3) Main circuit power supply

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

Short-circuit connector (Packed with the servo amplifier)

(Note 5)

(Note 6)

(Note 5)

(Note 6)

(Note 11, 12)Servo amplifier

To the next servo amplifier

3-phase 380 to 480 V AC, 50/60 Hz

(Note 8) Step-down transformer

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 28

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same

power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit and servo amplifier, configure a circuit to turn off EM1 in the drive unit and servo amplifier when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. When connecting multiple drive units and servo amplifiers, configure a sequence that will shut off the main circuit power if an alarm occurs even in one axis.

6. Configure a sequence in which the servo system controller will stop all the drive units (servo amplifiers) if an alarm occurs even in one drive unit (servo amplifier).

7. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to section 8.5.)

8. A step-down transformer is required when the coil voltage of the magnetic contactor is 200 V class. 9. For the terminal block and connector, refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". 10. Connect the main circuit power supply of the servo amplifier via a terminal block, and keep the wiring length of 1.5 m or longer. 11. Be sure to disconnect between P3 and P4. 12. When using the servo amplifier of 7 kW or less, make sure to connect the built-in regenerative resistor. (factory-wired) (5 kW

or less: P+ and D, 7 kW or less: P+ and C) 13. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 29

2) When magnetic contactor drive output is disabled

a) 200 V class

L+

L-

L+ L-

L11

L21

TE3

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

CN8

CN2 CN2

BV

M

BW

BU

(Note 4)

V

U

W

V

U

W

CN2 CN2

BV

M

BW

BU

V

U

W

V

U

W

CN4

P4 (Note 8)

N-

L11

L21

TE3

(Note 5)

(Note 9)

(Note 6)

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

(Note 5)

(Note 6)

24 V DC

CN8

MCCB L1

L2

L3

L11

L21

SK

L+

L-

(Note 7, 13)

(Note 7)

(Note 7, 13)

MC

RA1 RA2

(Note 11, 12)

BB

CC

(Note 10) CN25

RA3

24 V DC

CN40A

CN1A CN1B

3-phase 200 to 240 V AC, 50/60 Hz

Servo amplifier malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch Operation ready

OFF/ON

Converter unit malfunction

RA3 (Note 5)

(Note 2) MC

AC reactor

Dedicated bus bar

Servo amplifier Power regeneration

converter unit Drive unit

To the next servo amplifier

Protection coordination

cable

SSCNET III cable SSCNET III cableServo system controller

Forced stop (Note 6)

Servo amplifier malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch

Plate Plate

(Note 1) Power supply

(Note 1) Power supply

Cooling fan

Servo motor

Encoder

Cooling fan

Servo motor

Encoder

Dynamic brake

(Note 3) Main circuit power supply

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

Short-circuit connector (Packed with the servo amplifier)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 30

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same

power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit and servo amplifier, configure a circuit to turn off EM1 in the drive unit and servo amplifier when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. When connecting multiple drive units and servo amplifiers, configure a sequence that will shut off the main circuit power if an alarm occurs even in one axis.

6. Configure a sequence in which the servo system controller will stop all the drive units (servo amplifiers) if an alarm occurs even in one drive unit (servo amplifier).

7. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to section 8.5.)

8. For the terminal block and connector, refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". 9. Connect the main circuit power supply of the servo amplifier via a terminal block, and keep the wiring length of 1.5 m or longer. 10. Connect to an error output (A/B/C) via a relay coil, etc. 11. Be sure to disconnect between P3 and P4. 12. When using the servo amplifier of 7 kW or less, make sure to connect the built-in regenerative resistor. (factory-wired) (5 kW

or less: P+ and D, 7 kW or less: P+ and C) 13. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 31

b) 400 V class

L+

L-

L+ L-

L11

L21

TE3

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

CN8

CN2 CN2

BV

M

BW

BU

(Note 4)

V

U

W

V

U

W

CN2 CN2

BV

M

BW

BU

V

U

W

V

U

W

CN4

P4 (Note 9)

N-

L11

L21

TE3

(Note 5)

(Note 10)

(Note 6)

CN3

EM1

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM 24 V DC

(Note 5)

(Note 6)

24 V DC

CN8

MCCB L1

L2

L3

L11

L21

SK

L+

L-

(Note 7, 14)

(Note 7)

(Note 7, 14)

MC

RA1 RA2

(Note 12, 13)

BB

CC

(Note 11) CN25

RA3

24 V DC

CN40A

CN1A CN1B

Servo amplifier malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch Operation ready

OFF/ON

Converter unit malfunction

RA3 (Note 5)

3-phase 380 to 480 V AC, 50/60 Hz

(Note 8) Step-down transformer

(Note 2) MC

AC reactor Servo amplifier

Power regeneration converter unit Drive unit

To the next servo amplifier

Dedicated bus bar

Protection coordination

cable Plate Plate

SSCNET III cable SSCNET III cableServo system controller

Forced stop (Note 6)

Servo amplifier malfunction

RA2 (Note 5)

Drive unit malfunction

RA1 (Note 5) Emergency stop

switch

Cooling fan

Servo motor

Encoder

Dynamic brake

Cooling fan

Servo motor

Encoder

(Note 1) Power supply

(Note 1) Power supply

(Note 3) Main circuit power supply

(Note 3) Main circuit power supply

Short-circuit connector (packed with the drive unit)

Short-circuit connector (Packed with the servo amplifier)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 32

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". When using the same

power supply for the main circuit and cooling fan for MR-CV_, do not supply power between the MR-CV_ and AC reactor or to the inductive load from the secondary side of the magnetic contactor.

2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80 ms or less. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration during a forced stop deceleration.

3. To prevent an unexpected restart of the drive unit and servo amplifier, configure a circuit to turn off EM1 in the drive unit and servo amplifier when the main circuit power is turned off.

4. Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3. When using the external dynamic brake, assign DB (Dynamic brake interlock) to the CN3 connector pin with [Pr. PD07] to [Pr. PD09].

5. When connecting multiple drive units and servo amplifiers, configure a sequence that will shut off the main circuit power if an alarm occurs even in one axis.

6. Configure a sequence in which the servo system controller will stop all the drive units (servo amplifiers) if an alarm occurs even in one drive unit (servo amplifier).

7. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to section 8.5.)

8. A step-down transformer is required when the coil voltage of the magnetic contactor is 200 V class. 9. For the terminal block and connector, refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". 10. Connect the main circuit power supply of the servo amplifier via a terminal block, and keep the wiring length of 1.5 m or longer. 11. Connect to an error output (A/B/C) via a relay coil, etc. 12. Be sure to disconnect between P3 and P4. 13. When using the servo amplifier of 7 kW or less, make sure to connect the built-in regenerative resistor. (factory-wired) (5 kW

or less: P+ and D, 7 kW or less: P+ and C) 14. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 33

(3) How to use the bus bars

POINT The bus bars attached to the drive unit are only for the connection with the MR- CR_ resistance regeneration converter unit. The bus bars attached to the drive unit of 30 kW or more may not be usable. Refer to section 8.12 for the combinations of the bus bars. When mounting a drive unit in the right side of MR-J4-DU900B(4)(-RJ) or MR- J4-DU11KB(4)(-RJ), place the bus bars on top of each other on the TE2 terminal block of MR-J4-DU900B(4)(-RJ) or MR-J4-DU11KB(4)(-RJ), and screw them together. When the total number of MR-J4-DU900B(4)(-RJ) and MR-J4- DU11KB(4)(-RJ) drive units connected to the power regeneration convert unit is even, there is a gap of bar thickness between the bus bar and TE2 terminal block of the final drive unit. Place adjustment bars in the gap and screw them together. Please purchase the adjustment bars separately. (Refer to section 8.12.2.)

Connect L+ and L- of the power regeneration converter unit and those of drive unit as follows with the dedicated bus bars. The units are shown with the terminal cover open. When connecting the multiple drive units to one power regeneration converter unit, mount the drive units in descending order of capacity, from the right side of the power regeneration converter unit.

L+

L-

MR-J4-DU22KB4 MR-J4-DU11KB4 MR-J4-DU900B4MR-CV55K4

Bus bar 1 Bus bar 2 Bus bar 3

Adjustment bar

Screw the bus bars 2 and 3 together by placing one over the other.

When a space is found between the bus bar 3 and the TE2 terminal block of the drive unit, place adjustment bars between, and screw them together.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 34

3.3.2 Explanation of power supply system

(1) Signal explanations

POINT For the location of the terminal block, refer to chapter 7 DIMENSIONS.

Connection target

(application) Symbol Terminal block

Description MR-CV11K to MR-CV55K MR-CV11K4 to MR-CV75K4

Main circuit power supply L1/L2/L3 TE1 Supply 3-phase 200 V AC to 240 V AC,

50 Hz/60 Hz power to L1, L2, and L3. Supply 3-phase 380 V AC to 480 V AC, 50 Hz/60 Hz power to L1, L2, and L3.

Control circuit power supply L11/L21 TE3 Supply 1-phase 200 V AC to 240 V AC,

50 Hz/60 Hz power to L11 and L21. Supply 1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz power to L11 and L21.

Drive unit L+/L- TE2 Connect the L+ and L- of the drive unit to these terminals. Use bus bars for the connection.

Protective earth (PE) PE Connect this terminal to the protective earth (PE) of the cabinet.

(2) Power-on sequence

(a) Power-on procedure 1) Be sure to use a magnetic contactor for the main circuit power supply wiring (L1/L2/L3) as shown

in above section 3.3.1 (2). Configure a circuit to switch off the magnetic contactor by an external sequence as soon as an alarm occurs.

2) Turn on the control circuit power supplies (L11/L21) of the power regeneration converter unit and

drive unit simultaneously with or before the main circuit power supply. A warning appears on the display if the main circuit power supply is not turned on. When it is turned on, the warning disappears, and the operation starts normally.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 35

(b) Timing chart

1) Connecting one drive unit to one power regeneration converter unit a) When magnetic contactor drive output is enabled and the status remains at ready-on

The main circuit power does not shut off with servo-off.

OFF

ON

OFF

Servo-on command (from servo system controller)

(95 ms)

ON

OFF

(3 s) (Note 4)

Tb

ON

OFF

ON

ON

OFF

Power regeneration Converter unit control circuit power supply

ON

OFF

0 r/minServo motor speed

0 r/min

(Note 2)

Drive unit Control circuit power supply

Main circuit power supply

Base circuit

MBR (Electromagnetic brake interlock) (Note 1)

Position command (Note 3)

Note 1. When an electromagnetic brake is installed externally, configure a sequence which operates the electromagnetic brake with MBR as follows. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. Give a position command after the external electromagnetic brake is released. 3. This is in position control mode. 4. In [Pr. PC02 Electromagnetic brake sequence output], set a delay time (Tb) from MBR off to base circuit shut-

off at servo-off.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 36

b) When magnetic contactor drive output is enabled and the status returns to ready-off

The magnetic contactor of the converter unit turns off with ready-off, and the main circuit power supply shuts off.

OFF

ON

OFF

(3 s)

(3 s)

ON

OFF

ON

OFF

ON

OFF

ON

ON

OFF

0 r/min

0 r/min

(Note 2)

Servo-on command (from servo system controller)

Power regeneration Converter unit control circuit power supply

Servo motor speed

Drive unit Control circuit power supply

Main circuit power supply

Base circuit

MBR (Electromagnetic brake interlock) (Note 1)

Position command (Note 3)

Note 1. When an electromagnetic brake is installed externally, configure a sequence which operates the electromagnetic brake with MBR as follows. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. Give a position command after the external electromagnetic brake is released. 3. This is in position control mode.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 37

c) When magnetic contactor drive output is disabled

When an alarm occurs, turn off the magnetic contactor using the external sequence, and shut off the main circuit power supply.

(95 ms)

(3 s)

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

0 r/min

0 r/min

(Note 2)

Servo-on command (from servo system controller)

Power regeneration Converter unit control circuit power supply

Servo motor speed

Drive unit Control circuit power supply

Main circuit power supply

Base circuit

MBR (Electromagnetic brake interlock) (Note 1)

Position command (Note 3)

(Note 4, 5) Tb

Note 1. When an electromagnetic brake is installed externally, configure a sequence which operates the electromagnetic brake with MBR as follows. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. Give a position command after the external electromagnetic brake is released. 3. This is in position control mode. 4. In [Pr. PC02 Electromagnetic brake sequence output], set a delay time (Tb) from MBR off to base circuit shut-off

at servo-off. 5. The base circuit remains ready-on status at servo-off. When the status is ready-off, the base circuit and the

servo-on command turn off at the same time. (Tb = 0)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 38

2) Connecting multiple drive units and servo amplifiers to one power regeneration converter unit

a) When magnetic contactor drive output is enabled and the status remains at ready-on

(95 ms)

Drive unit (axis the protection coordination cable is connected) Base circuit

(3 s)

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Control circuit power supply

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Drive unit (axis the protection coordination cable is connected) Control circuit power supply

Power regeneration converter unit Control circuit power supply

Drive unit (axis the protection coordination cable is connected) MBR (Electromagnetic brake interlock) (Note 1)

0 r/min Drive unit (axis the protection coordination cable is not connected) or servo amplifier Servo motor speed

0 r/min Drive unit (axis the protection coordination cable is connected) Servo motor speed

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Base circuit

(3 s) Tb

Drive unit (axis the protection coordination cable is not connected) or servo amplifier MBR (Electromagnetic brake interlock) (Note 1)

0 r/min Drive unit (axis the protection coordination cable is connected) Position command (Note 3)

(Note 2)

(Note 2)

0 r/min Drive unit (axis the protection coordination cable is not connected) or servo amplifier Position command (Note 3)

(Note 5)

(Note 4) Tb

Main circuit power supply

Servo-on command (from servo system controller)

Note 1. When an electromagnetic brake is installed externally, configure a sequence which operates the electromagnetic brake with MBR as follows. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. Give a position command after the external electromagnetic brake is released. 3. This is in position control mode. 4. In [Pr. PC02 Electromagnetic brake sequence output], set a delay time (Tb) from MBR off to base circuit shut-off at

servo-off. 5. The main circuit power does not shut off with servo-off.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 39

b) When magnetic contactor drive output is enabled and the status returns to ready-off

When the axis, which the protection coordination cable is connected to, turns to servo-off, the magnetic contactor of the power regeneration converter unit turns off, and the main circuit power supply shuts off. Even when an axis other than the cable connected turns to servo-off, the main circuit power supply will not shut off.

(3 s)

(3 s)

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

0 r/min

0 r/min

(3 s)

0 r/min

0 r/min

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Control circuit power supply

Drive unit (axis the protection coordination cable is connected) Control circuit power supply

Power regeneration converter unit Control circuit power supply

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Servo motor speed

Drive unit (axis the protection coordination cable is connected) Servo motor speed

Main circuit power supply

Drive unit (axis the protection coordination cable is connected) Base circuit

Drive unit (axis the protection coordination cable is connected) MBR (Electromagnetic brake interlock) (Note 1)

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Base circuit Drive unit (axis the protection coordination cable is not connected) or servo amplifier MBR (Electromagnetic brake interlock) (Note 1)

Servo-on command (from servo system controller)

Drive unit (axis the protection coordination cable is connected) Position command (Note 3)

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Position command (Note 3)

(Note 2)

(Note 2)

Note 1. When an electromagnetic brake is installed externally, configure a sequence which operates the electromagnetic brake with MBR as follows. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. Give a position command after the external electromagnetic brake is released. 3. This is in position control mode.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 40

c) When magnetic contactor drive output is disabled

When an alarm occurs, turn off the magnetic contactor using the external sequence, and shut off the main circuit power supply.

(95 ms)

(3 s)

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

0 r/min

0 r/min

(3 s) Tb

0 r/min

0 r/min

Drive unit (axis the protection coordination cable is connected) Base circuit

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Control circuit power supply

Drive unit (axis the protection coordination cable is connected) Control circuit power supply

Power regeneration converter unit Control circuit power supply

Drive unit (axis the protection coordination cable is connected) MBR (Electromagnetic brake interlock) (Note 1)

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Servo motor speed

Drive unit (axis the protection coordination cable is connected) Servo motor speed

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Base circuit Drive unit (axis the protection coordination cable is not connected) or servo amplifier MBR (Electromagnetic brake interlock) (Note 1)

Drive unit (axis the protection coordination cable is connected) Position command (Note 3)

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Position command (Note 3)

Main circuit power supply

Servo-on command (from servo system controller)

(Note 2)

(Note 2)

(Note 4, 5) Tb

Note 1. When an electromagnetic brake is installed externally, configure a sequence which operates the electromagnetic brake with MBR as follows. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. Give a position command after the external electromagnetic brake is released. 3. This is in position control mode. 4. In [Pr. PC02 Electromagnetic brake sequence output], set a delay time (Tb) from MBR off to base circuit shut-off at

servo-off. 5. The base circuit remains ready-on status at servo-off. When the status is ready-off, the base circuit and the servo-on

command turn off at the same time. (Tb = 0)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 41

3.3.3 Connectors and pin assignment

POINT The pin assignment of the connectors is as viewed from the cable connector wiring section. When using the CN24 connector, MR-CVCN24S connector set and a crimping tool are necessary.

(1) Connectors and pin assignment of MR-CV_ power regeneration converter unit

CN41 Leave this open.

CN9 Leave this open.

CN25 Connect to an error output signal.

CN4 Used to connect CN40A of the drive unit.

CN23 Connect to the operation coil of the magnetic contactor. (Note)

CN24 Used to connect digital I/O signals.

CN4

CN24

CN25 A

B

8

4

5

1

20

11

10

1

C

3

2

1

CN23

Note. The connector for CN23 and an open tool are supplied with the power regeneration converter unit.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 42

(2) Connecting wire to CN25

POINT When stripping wire, be careful not to damage the conductor. Using this equipment with the conductor damaged may cause an insulation failure, loose connection, or wire breakage. After connecting wire, pull each wire lightly to confirm that the wire does not easily come out. Using this equipment without connecting the wire properly may cause a loose connection and wire breakage. After connecting wire, be careful that the tension (torsional force) of the wire is not directly applied to the part where the closed part of the terminal block and the wire are connected. Applying the torsional force may cause a loose connection or wire breakage. When opening the spring, do not apply an extreme force. Otherwise, the housing may break.

(a) Fabrication on cable insulator

Stripped length of the wire insulator should be approx. 5 to 6 mm. The appropriate stripped length of wire depends on the wire type, etc. Set the length considering their status. Stranded wire or solid wire of AWG 28 to 14 can be connected to CN25. Any wire whose insulator is too thick to be inserted to the insertion hole of CN25 cannot be used.

Insulator Core

5 mm to 6 mm

Twist strands lightly and straighten them as follows.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 43

(b) Inserting wire

Insert only one wire in each wire insertion hole of CN25 (the round hole).

1) Insert a driver diagonally in the square hole.

2) Stand the driver up pressing to the end. If inserted properly, the driver keeps standing with hands off.

3) Insert the properly-stripped wire in the wire insertion hole.

4) Once the wire is pressed to the end, pull out the driver holding the wire.

5) Pull the wire lightly to confirm that the wire does not come out. Do not pull the wire too hard. In addition, make sure that no conductor wire sticks out of the connector. You can remove the wire with the driver inserted in the square hole.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 44

(c) Drivers to be used

For mounting wire, dedicated drivers shown in the following are recommended.

Model number

Type Brand

210-720 Standard type (Made in Europe) 210-120J Standard type (Made in Japan) WAGO 210-657J Mini type (Made in Japan)

When using general drivers, the width must be 3.5 mm. Those drivers, which are too large to be inserted in the driver slot, or are unable to open the springs properly, cannot be used.

3.5 mm

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 45

3.3.4 Signal (device) explanations

The following table lists signals (devices) of the power regeneration converter unit. For the I/O interfaces (symbols in I/O division column in the table), refer to section 3.3.7. (1) I/O signal connector (CN24)

Signal (device) Symbol Connector pin No. Function and application I/O

division Forced stop EM1 CN24-1 To enable EM1, set the converter setting rotary switch (SW1) of the power

regeneration converter unit to "4". When EM1 is turned off, the converter unit will be in a forced stop state. In this state, the magnetic contactor turns off, [AL. E9 Main circuit off warning] occurs in the drive unit, and the servo-on turns off. The forced stop state will be reset when EM1 is turned on.

DI

Reset RES CN24-2 This signal is used for resetting alarms. Turn RES off after it has been on for 100 ms or longer. Some alarms cannot be rest by RES. Refer to chapter 6 for the alarms that can be reset. If RES is turned on while no alarm is occurring, the state will be ready-off. Do not turn this device on during an operation as it is not for stopping the operation.

DI

Alarm ALM CN24-3 When an alarm occurs, ALM turns off. DO Digital I/F power supply input

DICOM CN24-4 Input 24 V DC (24 V DC 10% 500 mA) for I/O interface. The power supply capacity varies, depending on the number of I/O interface points to be used. For sink interface, connect + of the 24 V DC external power supply. For source interface, connect - of the 24 V DC external power supply.

Ready RDYA CN24-5 RDYA turns on when the power regeneration converter unit is ready. It is a reverse logic to RDYB. RDYA remains off until the unit turns on after the power is turned on.

DO

Operation permission RDYB CN24-6 RDYB turns on when an error occurs in the power regeneration converter unit and when the reset is inputted. It is a reverse logic to RDYA. RDYB remains off until the unit turns off after the power is turned on.

DO

Converter reset RSO CN24-7 RSO turns on when RES is inputted to the power regeneration converter unit. DO Digital I/F common DOCOM CN24-8 This is a common terminal for input signal. This is separated from LG.

For sink interface, connect - of the 24 V DC external power supply. For source interface, connect + of the 24 V DC external power supply.

(2) Alarm output connector (CN25)

Signal (device) Symbol Connector pin No. Function and application I/O

division Alarm output A

B C

CN25-1 CN25-2 CN25-3

This connector, having a form C contact, outputs an alarm when the protective function of the power regeneration converter unit is activated and the power output to the drive unit is stopped. Abnormal: B and C are not conducted. (A and C are conducted.) Normal: B and C are conducted. (A and C are not conducted.)

DO

(3) Magnetic contactor control connector (CNP23)

Signal (device) Symbol Connector pin No. Function and application I/O

division Magnetic contactor

drive output MC1 CN23-1 Connect this device to the operation coil of the magnetic contactor and the

power supply for controlling the magnetic contactor. When the power regeneration converter unit receives a start command from the drive unit, MC1 (CNP23-1 pin) and MC2 (CN23-3 pin) will be shorted. When not executing control using the connector for controlling magnetic contactor, set the converter setting rotary switch (SW1) of the power regeneration converter unit to "1". (Refer to section 3.4.3.)

MC2 CN23-3

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 46

3.3.5 Alarm occurrence timing chart

CAUTION When an alarm has occurred, remove its cause, make sure that the operation signal is not being inputted, ensure safety, and reset the alarm before restarting operation.

(1) Connecting one drive unit to one power regeneration converter unit

(a) When magnetic contactor drive output is enabled 1) Power regeneration converter unit

When an alarm occurs in the power regeneration converter unit, the magnetic contactor turns off and the main circuit magnetic contactor shuts off. The drive unit in operation stops. To deactivate the alarm, cycle the control circuit power or request the operation from the driver unit. However, the alarm cannot be deactivated unless its cause is removed.

2)Power regeneration converter unit Control circuit power supply

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF Servo-on command (from servo system controller)

Power regeneration converter unit Alarm

(3 s) (3 s)

1) 4) 3)

ON

OFF Reset command (from servo system controller)

1.5 s

Main circuit power supply

Drive unit Control circuit power supply

Base circuit

Drive unit Alarm

No alarm Alarm

No alarm

No alarm

No alarm

Alarm

Alarm

Alarm occurrence Alarm occurrence

No alarm

1) in figure Even if an alarm occurs in the power regeneration converter unit when the drive unit is at servo-off, the alarm is not detected.

2) and 3) in figure To deactivate the alarm of the power regeneration converter unit, cycle the power of the

power regeneration converter unit (2)), or turn on the servo-on command (3)). Refer to section 6.1 for the alarms that can be reset with the servo-on command on.

4) in figure If an alarm occurs in the power regeneration converter unit when the drive unit is at

servo-on, the alarm also occurs in the drive unit, and the drive unit becomes servo-off.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 47

2) Drive unit

When an alarm occurs in the drive unit, the base circuit shuts off and the servo motor coasts. When an external dynamic brake is used, the external dynamic brake is activated to stop the servo motor. To deactivate the alarm, cycle the control circuit power, or give the error reset or CPU reset command from the servo system controller. However, the alarm cannot be deactivated unless its cause is removed.

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

(3 s) (3 s)

ON

OFF

1) 1)

1.5 s Alarm occurrence

Power regeneration converter unit Control circuit power supply

Servo-on command (from servo system controller)

Power regeneration converter unit Alarm

Reset command (from servo system controller)

Main circuit power supply

Drive unit Control circuit power supply

Base circuit

Drive unit Alarm Alarm No alarmNo alarm

No alarm

1) in figure After the drive unit has started, and when the drive unit and power regeneration converter unit have no alarms, the main circuit power is supplied.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 48

(b) When magnetic contactor drive output is disabled

1) Power regeneration converter unit When an alarm is occurs in the power regeneration converter unit, servo-off occurs. However, the main circuit power supply does not shut off; therefore, shut off the main circuit power supply with the external sequence. When the alarm is deactivated in the power regeneration converter unit, (and in the drive unit if an alarm has also occurred in the drive unit), turn on the error reset command from the servo system controller to resume the operation.

2) ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

(3 s) (3 s)

1) 4) 3)

ON

OFF

5)

1.5 s

Power regeneration converter unit Control circuit power supply

Servo-on command (from servo system controller)

Power regeneration converter unit Alarm

Reset command (from servo system controller)

Main circuit power supply

Drive unit Control circuit power supply

Base circuit

Drive unit Alarm Alarm

Alarm Alarm

No alarm

No alarm

No alarm

No alarm

Alarm occurrenceAlarm occurrence

No alarm

1) in figure Even if an alarm occurs in the power regeneration converter unit when the drive unit is at servo-off, the alarm is not detected.

2) and 3) in figure To deactivate the alarm of the power regeneration converter unit, cycle the power of the

power regeneration converter unit (2)), or turn on the servo-on command (3)). Refer to section 6.1 for the alarms that can be reset with the servo-on command on.

4) in figure If an alarm occurs in the power regeneration converter unit when the drive unit is at

servo-on, the alarm also occurs in the drive unit, and the drive unit becomes servo-off. 5) in figure Shut off the main circuit power supply with the external sequence at the same time with

the alarm occurrence.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 49

2) Drive unit

When an alarm occurs in the drive unit, servo-off occurs. However, the main circuit power supply does not shut off; therefore, shut off the main circuit power supply with the external sequence. After the alarm is deactivated in the drive unit, turn on the error reset command from the servo system controller to resume the operation.

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

(3 s) (3 s)

ON

OFF

2)1)

1.5 s

Power regeneration converter unit Control circuit power supply

Servo-on command (from servo system controller)

Power regeneration converter unit Alarm

Reset command (from servo system controller)

Main circuit power supply

Drive unit Control circuit power supply

Base circuit

Drive unit Alarm No alarm

No alarm

No alarmAlarm

Alarm occurrence

1) in figure When an alarm occurs in the drive unit, shut off the main circuit power supply with the external sequence.

2) in figure Turn on the main circuit power supply after the alarm in the drive unit is deactivated.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 50

(2) Connecting multiple drive units and servo amplifiers to one power regeneration converter unit

(a) When magnetic contactor drive output is enabled 1) Power regeneration converter unit

When an alarm occurs in the power regeneration converter unit, the magnetic contactor turns off and the main circuit magnetic contactor shuts off. Make all the axes servo-off by inputting the forced stop signal from the servo system controller to the drive unit or servo amplifier in operation. To deactivate the alarm, cycle the control circuit power or request the operation from the axis which the protection coordination cable is connected to. However, the alarm cannot be deactivated unless its cause is removed.

2) ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

(3 s) (3 s)

1) 4)

5)

3)

ON

OFF

ON

OFF

ON

OFF

1.5 s

Drive unit (axis the protection coordination cable is connected) Control circuit power supply

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Control circuit power supply

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Base circuit

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Alarm

Main circuit power supply

Power regeneration converter unit Alarm

Power regeneration converter unit Control circuit power supply

Drive unit (axis the protection coordination cable is connected) Base circuit

Drive unit (axis the protection coordination cable is connected) Alarm

Servo-on command (from servo system controller)

Reset command (from servo system controller)

No alarm

No alarm

No alarm

No alarm

Alarm

Alarm

No alarm No alarmAlarm

Alarm occurrence Alarm occurrence

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 51

1) in figure Even if an alarm occurs in the power regeneration converter unit when the drive unit is at

servo-off, the alarm is not detected. 2) and 3) in figure To deactivate the alarm of the power regeneration converter unit, cycle the power of the

power regeneration converter unit (2)), or turn on the servo-on command (3)). Refer to section 6.1 for the alarms that can be reset with the servo-on command on.

4) in figure If an alarm occurs in the power regeneration converter unit when the drive unit is at

servo-on, the alarm also occurs in the axis which the protection coordination cable is connected to, and the drive unit becomes servo-off.

5) in figure When an alarm occurs in the power regeneration converter unit, make all the axes servo-

off by inputting the forced stop signal from the servo system controller.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 52

2) Drive unit

When an alarm occurs in the drive unit which the protection coordination cable is connected to, the base circuit shuts off and the servo motor coasts. When an alarm occurs in the servo amplifier or drive unit which the protection coordination cable is not connected to, shut off the main circuit power supply by turning off the magnetic contactor with the external sequence. When an external dynamic brake is used, the external dynamic brake is activated to stop the servo motor. When an alarm occurs in any axis, make all the axes servo-off by inputting the forced stop signal from the servo system controller. To deactivate the alarm, cycle the control circuit power, or give the error reset or CPU reset command from the servo system controller. However, the alarm cannot be deactivated unless its cause is removed.

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

(3 s) (3 s)

ON

OFF

1) 1)

ON

OFF

ON

OFF

1.5 s

2)

Drive unit (axis the protection coordination cable is connected) Control circuit power supply

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Control circuit power supply

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Base circuit

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Alarm

Main circuit power supply

Power regeneration converter unit Alarm

Power regeneration converter unit Control circuit power supply

Drive unit (axis the protection coordination cable is connected) Base circuit

Drive unit (axis the protection coordination cable is connected) Alarm

Servo-on command (from servo system controller)

Reset command (from servo system controller)

No alarm

No alarm

No alarm

No alarmAlarm

Alarm occurrence

1) in figure After the drive unit has started, and when the drive unit and power regeneration converter unit have no alarms, the main circuit power is supplied.

2) in figure When an alarm occurs in any axis, make all the axes servo-off by inputting the forced

stop signal from the servo system controller.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 53

(b) When magnetic contactor drive output is disabled

1) Power regeneration converter unit When an alarm is occurs in the power regeneration converter unit, servo-off occurs. However, the main circuit power supply does not shut off; therefore, shut off the main circuit power supply with the external sequence. Make all the axes servo-off by inputting the forced stop signal from the servo system controller to the drive unit or servo amplifier in operation. When the alarm is deactivated in the power regeneration converter unit, (and in the drive unit or servo amplifier if an alarm has also occurred in the drive unit or servo amplifier), turn on the error reset command from the servo system controller to resume the operation.

2) ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

(3 s) (3 s)

1) 4) 3)

ON

OFF

5)

5)

ON

OFF

ON

OFF

1.5 s

Drive unit (axis the protection coordination cable is connected) Control circuit power supply

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Control circuit power supply

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Base circuit

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Alarm

Main circuit power supply

Power regeneration converter unit Alarm

Power regeneration converter unit Control circuit power supply

Drive unit (axis the protection coordination cable is connected) Base circuit

Drive unit (axis the protection coordination cable is connected) Alarm

Servo-on command (from servo system controller)

Reset command (from servo system controller)

No alarm Alarm No alarm

No alarm Alarm No alarm

No alarm

No alarmAlarm

Alarm occurrenceAlarm occurrence

1) in figure Even if an alarm occurs in the power regeneration converter unit when the drive unit is at servo-off, the alarm is not detected.

2) and 3) in figure To deactivate the alarm of the power regeneration converter unit, cycle the power of the

power regeneration converter unit (2)), or turn on the servo-on command (3)). Refer to section 6.1 for the alarms that can be reset with the servo-on command on.

4) in figure If an alarm occurs in the power regeneration converter unit when the drive unit is at

servo-on, the alarm also occurs in the drive unit, and the drive unit becomes servo-off. 5) in figure When an alarm occurs in the power regeneration converter unit, make all the axes servo-

off by inputting the forced stop signal from the servo system controller.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 54

2) To drive unit or servo amplifier

When an alarm occurs in the drive unit or servo amplifier, servo-off occurs. However, the main circuit power supply does not shut off; therefore, shut off the main circuit power supply with the external sequence. Make all the axes servo-off by inputting the forced stop signal from the servo system controller to the drive unit or servo amplifier in operation. After the alarm is deactivated in the drive unit or servo amplifier, turn on the error reset command from the servo system controller to resume the operation.

3)

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

(3 s) (3 s)

ON

OFF

2)1)

ON

OFF

ON

OFF

1.5 s

Drive unit (axis the protection coordination cable is connected) Control circuit power supply

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Control circuit power supply

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Base circuit

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Alarm

Main circuit power supply

Power regeneration converter unit Alarm

Power regeneration converter unit Control circuit power supply

Drive unit (axis the protection coordination cable is connected) Base circuit

Drive unit (axis the protection coordination cable is connected) Alarm

Servo-on command (from servo system controller)

Reset command (from servo system controller)

No alarm

No alarm

No alarm

Alarm No alarm

Alarm occurrence

1) in figure When an alarm occurs in the drive unit, shut off the main circuit power supply with the external sequence.

2) in figure Turn on the main circuit power supply after the alarm in the drive unit is deactivated. 3) in figure When an alarm occurs in any axis, make all the axes servo-off by inputting the forced

stop signal from the servo system controller.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 55

3.3.6 Forced stop in the power regeneration converter unit

(1) Connecting one drive unit to one power regeneration converter unit (a) When magnetic contactor drive output is enabled

When EM1 (Forced stop) is disabled in the power regeneration converter unit, the magnetic contactor turns off and the main circuit power supply shuts off. The base circuit of the drive unit in operation shuts off, and [AL. E9 Main circuit off warning] appears on the drive unit. When EM1 is enabled in the power regeneration converter unit, the magnetic contactor turns on, the main circuit power is supplied, and then the drive unit automatically resumes the operation.

(50 ms)

Alarm

No alarm

ON

OFF

ON

(3 s)

(3 s)

2)

2)

1)

ON

OFF

OFF

Dynamic brake

MBR (Electromagnetic brake interlock)

Base circuit

Servo motor speed

Converter main circuit warning

Main circuit power supply

EM1 (Forced stop)

(Note 1) ON

OFF (Enabled)

(Note 2)

Note 1. When an electromagnetic brake is installed externally, configure a sequence which operates the electromagnetic brake with MBR as follows. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. There are delays caused by a magnetic contactor built into the external dynamic brake (about 50 ms) and by external relays.

1) in figure When EM1 is enabled in the power regeneration converter unit, the main circuit power is

supplied. 2) in figure When the capacitor in the main circuit is fully charged, the base circuit and MBR turn on.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 56

(b) When magnetic contactor drive output is disabled

When EM1 (Forced stop) is disabled in the power regeneration converter unit, the base circuit of the drive unit that is in operation shuts off, and [AL. E9 Main circuit off warning] appears on the drive unit. When EM1 is enabled in the power regeneration converter unit, the drive unit automatically resumes the operation.

(50 ms)

OFF

ON

OFF

ON

OFF

ON

(3 s)

(3 s)

1)Alarm

No alarm

MBR (Electromagnetic brake interlock)

Base circuit

Servo motor speed

Converter main circuit warning

Main circuit power supply

EM1 (Forced stop)

(Note 1) ON

OFF (Enabled)

Dynamic brake

(Note 2)

Note 1. When an electromagnetic brake is installed externally, configure a sequence which operates the electromagnetic brake with MBR as follows. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. There are delays caused by a magnetic contactor built into the external dynamic brake (about 50 ms) and by external relays.

1) in figure When EM1 is enabled, the converter main circuit off warning is released.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 57

(2) Connecting multiple drive units and servo amplifiers to one power regeneration converter unit

POINT The EM1 (forced stop) of the power regeneration converter unit and drive units should be turned off simultaneously.

(a) When magnetic contactor drive output is enabled

When EM1 (Forced stop) is disabled in the power regeneration converter unit, the magnetic contactor turns off and the main circuit power supply shuts off. The base circuit of the drive unit in operation shuts off, and [AL. E9 Main circuit off warning] appears on the drive unit. When EM1 is enabled in the power regeneration converter unit, the magnetic contactor turns on, the main circuit power is supplied, and then the drive unit automatically resumes the operation.

Drive unit (axis the protection coordination cable is connected) MBR (Electromagnetic brake interlock) (Note 1)

(50 ms)

ON

OFF

Drive unit (axis the protection coordination cable is connected) Base circuit

ON

OFF

Drive unit (axis the protection coordination cable is connected) Servo motor speed

Drive unit (axis the protection coordination cable is connected) Converter main circuit warning

ON

OFF

ON

(3 s)

(3 s)

2)

2)

1)

Drive unit (axis the protection coordination cable is not connected) or servo amplifier MBR (Electromagnetic brake interlock) (Note 1)

(50 ms)

ON

OFF

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Base circuit

ON

OFF

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Servo motor speed

(3 s)

(3 s)

2)

2)

Main circuit power supply

EM1 (Forced stop) (Note 3)

Dynamic brake

(Note 2)

Dynamic brake

(Note 2)

Alarm

No alarm

OFF (Enabled)

Note 1. When an electromagnetic brake is installed externally, configure a sequence which operates the electromagnetic brake with MBR as follows. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. There are delays caused by a magnetic contactor built into the external dynamic brake (about 50 ms) and by external relays.

3. The EM1 (forced stop) of the power regeneration converter unit and drive units should be turned off simultaneously.

1) in figure When EM1 is enabled in the power regeneration converter unit, the main circuit power is

supplied. 2) in figure When the capacitor in the main circuit is fully charged, the base circuit and MBR turn on.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 58

(b) When magnetic contactor drive output is disabled

When EM1 (Forced stop) is disabled in the power regeneration converter unit, the base circuit of the drive unit that is in operation shuts off, and [AL. E9 Main circuit off warning] appears on the drive unit. When EM1 is enabled in the power regeneration converter unit, the magnetic contactor turns on, the main circuit power is supplied, and then the drive unit automatically resumes the operation.

(50 ms)

ON

OFF

ON

OFF

ON

OFF

ON

(3 s)

(3 s)

1)

(50 ms)

ON

OFF

ON

OFF

(3 s)

(3 s)

Drive unit (axis the protection coordination cable is connected) MBR (Electromagnetic brake interlock) (Note 1)

Drive unit (axis the protection coordination cable is connected) Base circuit

Drive unit (axis the protection coordination cable is connected) Servo motor speed

Drive unit (axis the protection coordination cable is connected) Converter main circuit warning

Drive unit (axis the protection coordination cable is not connected) or servo amplifier MBR (Electromagnetic brake interlock) (Note 1)

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Base circuit

Drive unit (axis the protection coordination cable is not connected) or servo amplifier Servo motor speed

Main circuit power supply

EM1 (Forced stop) (Note 3) OFF (Enabled)

Alarm

No alarm

Dynamic brake

Dynamic brake

(Note 2)

(Note 2)

Note 1. When an electromagnetic brake is installed externally, configure a sequence which operates the electromagnetic brake with MBR as follows. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. There are delays caused by a magnetic contactor built into the external dynamic brake (about 50 ms) and by external relays.

3. The EM1 (forced stop) of the power regeneration converter unit and drive units should be turned off simultaneously.

1) in figure When EM1 is enabled, the converter main circuit off warning is released.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 59

3.3.7 Interfaces

(1) Sink I/O interface (a) Digital input interface DI

This is an input circuit in which photocoupler cathode side is the input terminal. Transmit signals from sink (open-collector) type transistor output, relay switch, etc. The following is a connection diagram for sink input. Refer to (2) in this section for source input.

10%

Approx. 4.1 k

Approx. 5 mA

VCES 1.0 V ICEO 100 A

TR

24 V DC 350 mA

Switch

For transistor EM1 etc.

Power regeneration converter unit

DICOM

(b) Digital output interface DO This is a circuit in which the collector of the output transistor is the output terminal. When the output transistor is turned on, the current will flow to the collector terminal. A lamp, relay, or photocoupler can be driven. Install a diode (D) for an inductive load, or install an inrush current suppressing resistor (R) for a lamp load. (Rated current: 40 mA or less, maximum current: 50 mA or less, inrush current: 100 mA or less) A maximum of 2.6 V voltage drop occurs in the power regeneration converter unit. The following shows a connection diagram for sink output. Refer to (2) in this section for source output.

24 V DC 10% 350 mA

Power regeneration converter unit

ALM, etc.

Load

(Note)

DOCOM

If polarity of diode is reversed, the power regeneration converter unit will malfunction.

Note. If the voltage drop (maximum of 2.6 V) interferes with the relay operation, apply a high voltage (maximum of 26.4 V) from an external source.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 60

(2) Source I/O interface

In this power regeneration converter unit, source type I/O interfaces can be used.

(a) Digital input interface DI This is an input circuit in which the anode of the photocoupler is the input terminal. Transmit signals from source (open-collector) type transistor output, relay switch, etc.

10% VCES 1.0 V ICEO 100 A

24 V DC 350 mA

EM1 etc.

DICOM

TR

For transistor

Approx. 5 mA

Switch Approx. 4.1 k

Power regeneration converter unit

(b) Digital output interface DO This is a circuit in which the emitter of the output transistor is the output terminal. When the output transistor is turned on, the current will flow from the output terminal to a load. A maximum of 2.6 V voltage drop occurs in the power regeneration converter unit.

ALM,

DOCOM

24 V DC 10% 350 mA

Power regeneration converter unit

etc. Load

If polarity of diode is reversed, the power regeneration converter unit will malfunction.

(Note)

Note. If the voltage drop (maximum of 2.6 V) interferes with the relay operation, apply a high voltage (maximum of 26.4 V) from an external source.

(3) Alarm output

B and C are conducted in normal operation of the power regeneration converter unit. When an alarm occurs, A and C are conducted. Connect to an error output (A/B/C) via a relay coil, etc.

Permissible load: 230 V AC 0.3 A, 30 V DC 0.3 A (Note) A

B

C

Power regeneration converter unit

Note. To comply with the IEC/EN/UL/CSA standard, keep it 30 V DC or lower.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 61

3.3.8 Grounding

WARNING

Ground the power regeneration converter unit, drive unit, and servo motor securely. To prevent an electric shock, be sure to connect the protective earth (PE) terminal (marked ) of the power regeneration converter unit and the drive unit to the protective earth (PE) of the cabinet.

The drive unit switches the power transistor on-off to supply power to the servo motor. Depending on the wiring and ground cable routing, the drive unit may be affected by the switching noise (due to di/dt and dv/dt) of the transistor. Be sure to ground to prevent such a fault by referring to the following diagram. To conform to the EMC Directive, refer to "EMC Installation Guidelines".

V

U

Servo motor

Servo motor

M U V WW

Drive unit

Drive unit

(Note 2)

(Note 2)

Cabinet

L1

L2

L3

Outer box

MCCB Line filter AC reactor (Note 3)

Protective earth (PE)

Power regeneration converter unit

L+L-

L+L-

V

U M

U V WW

Controller

L+L-

L+L-

MC (Note 1) Power supply

Note 1. For the power supply specifications, refer to section 1.4. 2. Be sure to connect the grounding terminal of the servo motor to the PE terminal of the drive unit. Do not connect the wire

directly to the protective earth of the cabinet. 3. Be sure to install an MR-AL-_AC reactor.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 62

3.4 Startup

WARNING When executing a test run, follow the notice and procedures in this instruction manual. Otherwise, it may cause a malfunction, damage to the machine, or injury. Do not operate switches with wet hands. Otherwise, it may cause an electric shock.

CAUTION

Before starting operation, check the parameters. Improper settings may cause some machines to operate unexpectedly. The heat sink of the power regeneration converter unit and drive unit, and the servo motor, etc. may be hot while power is on and for some time after power-off. Take safety measures such as providing covers to avoid accidentally touching them by hands and parts such as cables. During operation, never touch the rotor of the servo motor. Otherwise, it may cause injury. Before wiring, switch operation, etc., eliminate static electricity. Otherwise, it may cause a malfunction.

The following items are the same as those for MR-J4-_(-RJ). Refer to the section of the detailed explanation field for details. Read the corresponding section by replacing "servo amplifier" to "drive unit". "MR-J4-_B_" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

Model Item Detailed explanation MR-J4-DU_B_(-RJ) Switch setting and display of the servo

amplifier MR-J4-_B_ section 4.3

Test operation MR-J4-_B_ section 4.4 Test operation mode MR-J4-_B_ section 4.5

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 63

3.4.1 Switching power on for the first time

When switching the power on for the first time, follow this section to startup. "MR-J4-_B_" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

Wiring check

Surrounding environment check

Axis No. settings

Parameter setting

Test operation of the servo motor alone in test operation mode

Test operation of the servo motor alone by commands

Test operation with the servo motor and machine connected

Gain adjustment

Actual operation

Stop

Description Reference Check whether the power regeneration converter unit, the drive unit, and the servo motor are wired correctly by visual inspection, DO forced output function, etc.

(2) in this section

Check the surrounding environment of the power regeneration converter unit, the drive unit and the servo motor.

MR-J4-_B_ Section 4.1.3

Confirm that the control axis No. set with the auxiliary axis number setting switches (SW2-3 and SW2-4) and with the converter setting rotary switch (SW1) match the control axis No. set with the servo system controller.

MR-J4-_B_ Section 4.3.1

(3) Section 3.4.3

Set the parameters as necessary for the operation mode, etc.

Section 5.3

For the test operation, with the servo motor disconnected from the machine and operated at the speed as low as possible, check whether the servo motor rotates correctly.

MR-J4-_B_ Section 4.5

For the test operation, give commands to the drive unit with the servo motor disconnected from the machine and operated at the speed as low as possible, check whether the servo motor rotates correctly.

Connect the servo motor with the machine, and check machine motions by transmitting operation commands from the servo system controller.

Make gain adjustment to optimize the machine motions. MR-J4-_B_ Chapter 6

Stop giving commands and stop operation.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 64

(2) Wiring check

(a) Power supply system wiring Before switching on the main circuit and control circuit power supplies, check the following items.

1) Power supply system wiring

a) The power supplied to the power input terminals (L1/L2/L3/L11/L21) of the power regeneration converter unit and the power input terminals (L11/L21) of the drive unit should satisfy the defined specifications. (Refer to section 1.4.)

b) When magnetic contactor drive output is enabled, the magnetic contactor control connector

(CN23) should be connected to the coil of the magnetic contactor.

2) Connection of drive unit and servo motor a) The power outputs (U/V/W) of the drive unit should match in phase with the power inputs

(U/V/W) or the servo motor. Drive unit Servo motor

M

U

V

W

U

V

W

b) The power supplied to the power regeneration converter unit should not be connected to the power outputs (U/V/W) of the drive unit. Otherwise, the drive unit and servo motor will fail.

M

U

V

W

U

V

W

Drive unit Servo motor

c) The grounding terminal of the servo motor is connected to the PE terminal of the drive unit.

M

Drive unit Servo motor

4) The CN2 connector of the drive unit should be connected to the encoder of the servo motor securely using the encoder cable.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 65

(b) I/O signal wiring

1) Power regeneration converter unit a) A voltage exceeding 24 V DC should not be applied to the pins of the CN24 connector.

b) The wire between the plate and DOCOM of the CN24 connector should not be shorted.

Power regeneration converter un

DOCOM

Plate

CN24

2) MR-J4-DU_B_(-RJ) drive unit a) The I/O signals should be connected correctly.

Use DO forced output to forcibly turn on/off the pins of the CN3 connector. You can use this function to check the wiring. In this case, turn on the control circuit power supply only. For details of I/O signal connection, refer to section 3.2 of "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". For details of DO forced output, refer to section 4.5.1 of "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

b) A voltage exceeding 24 V DC should not be applied to the pins of the CN3 connector.

c) The plate and DOCOM of the CN3 connector should not be shorted.

Drive unit

DOCOM

CN3

Plate

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 66

3.4.2 Startup

(1) Power on

POINT Set [Pr. PA02] to "_7 _ _" for the drive unit which is connected to the power regeneration converter unit with the protection coordination cable. Set [Pr. PA02] to "4_ _ _" and [Pr. PF03] to "_1 _ _" for the drive unit which is not connected to the power regeneration converter unit with the protection coordination cable. Set [Pr. PF07] to "_1 _ _" to keep the main circuit power supply on at STO (when [AL. 95 occurs]). Set [Pr. PF07] "1_ _ _" to keep the main circuit power supply on when the forced stop is inputted (when [AL. E6 occurs]). For the drive unit which is not connected to the power regeneration converter unit with the protection coordination cable, make sure that the power regeneration converter unit is in ready-on state, and then turn on the servo-on with a command from the controller.

Startup of the MR-J4-DU_B_(-RJ) is the same as that of the MR-J4-_B_(-RJ). For details, refer to section 4.2 of "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". The power regeneration converter unit shows "C" (ready-off) on the display at power-on. When an error occurs or EM1 (Forced stop) is disabled in the power regeneration converter unit, the operation will stop.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 67

3.4.3 Switch setting and operation section of power regeneration converter unit

Forced stop, protection coordination, and magnetic contactor drive output can be set with the switch on the power regeneration converter unit. The 1-digit, 7-segment LED display shows the power regeneration converter unit status and the alarm number. (1) Switches

WARNING Use an insulated screw driver for the converter setting rotary switch (SW1). Do not use a metal screw driver. Touching patterns on electronic boards, lead of electronic parts, etc. may cause an electric shock.

POINT

Do not set any values other than described to the converter setting rotary switch (SW1). The setting of the switch will be enabled after the main circuit power supply and control circuit power supply are cycled.

Set the converter setting rotary switch to enable/disable the forced stop, protection coordination, and magnetic contactor drive output. The following shows the setting of the converter setting rotary switch and a combination of enabling/disabling each function.

Power regeneration

converter unit Rotary switch for

setting converter (SW1)

No. Forced stop

Protection coordination Magnetic contactor drive

output Protection

coordination Stand-alone

drive 0 (initial value) Disabled Enabled Disabled Enabled

1 Disabled Enabled Disabled Disabled 4 Enabled Enabled Disabled Enabled 8 Disabled Disabled Enabled Disabled

Other than above Not used

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 68

(2) Scrolling display

(a) Normal display When the control section of the power regeneration converter unit is turned on, the 1-digit, 7- segment LED display shows the progress of the initial setting. In normal operation, the 1-digit, 7- segment LED is always on.

Initialization completed (Ready-off)

During ready-on Contactor on (Charging)

During servo-on (Charging completed)

Drive unit Forced stop

Initializing

(b) Alarm display When an alarm or warning occurs, each digit of the corresponding number is alternately displayed by blinking.

1) Displaying 2-digit number

Each of the two digits of the alarm or warning No. and blank are repeatedly displayed. The following shows when [AL. 61] is occurring as an example.

Displays blank Displays "6" of [AL. 61]

Displays "1" of [AL. 61]

After 1.5 s

After 1.5 s

After 1 s

2) Displaying 3-digit number Each of the three digits of the alarm or warning No. and blank are repeatedly displayed. The following shows when [AL. 6E.1] is occurring as an example.

Displays "6" of [AL. 6E.1]

Displays "1" of [AL. 6E.1]

Displays "E" of [AL. 6E.1] Displays blank

After 1 s

After 1 s

After 1 s

After 1 s

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 69

(3) Display sequence

Initializing

Ready-off (charging)

Ready-on (charging completed)

Forced stop

When an alarm occurs, its alarm code appears.

Blinking

Blinking

Blinking

Blinking

Blinking

Example: When [AL 61] has occurred

Example: When [AL 6E.1] has occurred

Alarm reset or warning cleared

When an alarm No. or warning No. is displayed

1.5 s 1 s

1.5 s 1 s

1 s

1 s

1 s Displays blank

Displays blank

Initialization completed

(4) Display transition of the power regeneration converter unit/MR-J4-DU_B_(-RJ) drive unit The following shows the display transition of the power regeneration converter unit in which a protection coordination is enabled and MR-J4-DU_B_(-RJ) drive unit.

Initialization completed

Power regeneration converter unit Display

MR-J4-DU_B_(-RJ) drive unit Display (Note)

Ready-on

Ordinary operation Ordinary operation

Servo-on

Ready-off (charging)

Ready-on (charging completed)

Ready-off, Servo-off

Ready-on, Servo-off

Ready-on, Servo-on

Magnetic contactor on

Charging completed

Note. For the detailed display transition of the drive unit, refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 70

(5) Status display list

The following table lists the power regeneration converter unit statuses.

Display Status Description

Initializing Displays during initialization.

Initialization completed Displays when initialization is complete, or during ready-off or servo-off.

Ready-off (charging) Displays in servo-off.

Ready-on (charging completed) Displays in servo-off.

(Note) Alarm and warning The alarm No. and the warning No. that occurred are displayed.

Note. "*" indicates the alarm No. and the warning No.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 71

3.5 Characteristics

3.5.1 Overload protection characteristics

An electronic thermal is built in the power regeneration converter unit to protect the unit from overloads. [AL. 7E Overload 1] occurs if overload operation above the electronic thermal protection curve shown in this section is performed. [AL. 7F Overload 2] occurs if the operation is continued exceeding the rated speed and rated torque. Use the unit on the left-side area of the graph. The following table shows combinations of each power regeneration converter unit and graph of overload protection characteristics.

Power regeneration converter unit

Graph of overload protection characteristics

MR-CV11K MR-CV30K MR-CV37K MR-CV45K

MR-CV11K4 MR-CV30K4 MR-CV37K4 MR-CV45K4

Characteristics A

MR-CV18K MR-CV18K4

Characteristics B

MR-CV55K Characteristics C MR-CV55K4 MR-CV75K4

Characteristics D

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 72

(1) Characteristics A

0.1

1

0 100 200 300 400 500 600

10000

1000

100

10 O

pe ra

tio n

tim e

[s ]

(Note) Load ratio [%]

Note. Load ratio 100% indicates the continuous rating of the converter unit.

(2) Characteristics B

0.1

1

0 100 200 300 400 500 600

10000

1000

100

10

O pe

ra tio

n tim

e [s

]

(Note) Load ratio [%]

Note. Load ratio 100% indicates the continuous rating of the converter unit.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 73

(3) Characteristics C

0.1

1

0 100 200 300 400 500

10000

1000

100

10 O

pe ra

tio n

tim e

[s ]

(Note) Load ratio [%]

Note. Load ratio 100% indicates the continuous rating of the converter unit.

(4) Characteristics D

0.1

1

0 100 200 300 400

10000

1000

100

10

O pe

ra tio

n tim

e [s

]

(Note) Load ratio [%]

Note. Load ratio 100% indicates the continuous rating of the converter unit.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 74

3.5.2 Power supply capacity and generated loss

(1) Generated heat of the power regeneration converter unit and drive unit The following tables indicate the generated loss under rated load and the power supply capacity per combination of the power regeneration converter unit and drive unit.

Power regeneration converter

unit

Power supply capacity [kVA]

Generated heat of power regeneration converter unit [W]

Area required for heat

dissipation [m2] At rated output

At rated output (Generated heat in the

cabinet when cooled outside

the cabinet)

With servo-off

MR-CV11K 16 124 25 25 2.5 MR-CV18K 27 193 32 25 3.9 MR-CV30K 43 317 45 25 6.4 MR-CV37K 53 396 53 25 8.0 MR-CV45K 64 496 104 25 10.0 MR-CV55K 78 595 164 30 12.0 MR-CV11K4 16 124 25 25 2.5 MR-CV18K4 27 193 32 25 3.9 MR-CV30K4 43 317 45 25 6.4 MR-CV37K4 53 402 53 25 8.1 MR-CV45K4 64 496 104 25 10.0 MR-CV55K4 78 596 164 30 12.0 MR-CV75K4 107 842 228 30 16.9

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 75

Drive unit

Generated heart of drive unit [W]

Area required for heat dissipation [m2] At rated output

At rated output (Generated heat in the cabinet when

cooled outside the cabinet)

With servo-off

MR-J4-DU900B(-RJ) 366 81 30 7.4 MR-J4-DU11KB(-RJ) 409 81 30 8.2 MR-J4-DU15KB(-RJ) 566 105 30 11.4 MR-J4-DU22KB(-RJ) 755 105 30 15.1 MR-J4-DU30KB(-RJ) 900 132 30 18.0 MR-J4-DU37KB(-RJ) 1000 132 30 20.0 MR-J4-DU900B4(-RJ) 366 81 30 7.4 MR-J4-DU11KB4(-RJ) 409 81 30 8.2 MR-J4-DU15KB4(-RJ) 566 105 30 11.4 MR-J4-DU22KB4(-RJ) 755 105 30 15.1 MR-J4-DU30KB4(-RJ) 790 132 30 15.8 MR-J4-DU37KB4(-RJ) 910 132 30 18.2 MR-J4-DU45KB4(-RJ) 1110 216 30 22.2 MR-J4-DU55KB4(-RJ) 1440 216 30 28.8

Even when multiple drive units and servo amplifiers are connected to one power regeneration converter unit, calculate the power supply capacity from the power regeneration converter unit capacity. The power supply capacity will be lower than the listed values when the total output wattage of the servo motors driven by the drive units and servo amplifiers connected to the power regeneration converter unit is lower than the converter capacity. The servo motor requires 2 times to 2.5 times greater instantaneous power for acceleration, and therefore, use the power supply which ensures that the voltage lies within the permissible voltage fluctuation at the main circuit power supply terminals (L1/L2/L3) of the power regeneration converter unit. The power supply capacity will vary according to the power supply impedance. The actual generated heat falls within the ranges at rated output and at servo-off according to the frequencies of use during operation. When designing an enclosed cabinet, use the values in the table, considering the worst operating conditions.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 76

(2) Heat dissipation area for an enclosed type cabinet

The enclosed type cabinet (hereafter called the cabinet) which will contain the power regeneration converter unit and drive unit should be designed to ensure that its temperature rise is within +10 C at the ambient temperature of 40 C. (allowing a margin of approximately 5 C for the ambient temperature of 55 C maximum) The necessary cabinet heat dissipation area can be calculated by next equation.

A = K T

P

A: Heat dissipation area [m2] P: Loss generated in the cabinet [W] T: Difference between internal and ambient temperatures [C] K: Heat dissipation coefficient [5 to 6]

When calculating the heat dissipation area with the equation, assume that P is the sum of all losses generated in the cabinet. Refer to (1) in this section for the generated heat of the power regeneration converter unit and drive unit. "A" indicates the effective area for heat dissipation, but if the cabinet is directly installed on an insulated wall, that extra amount must be added to the cabinet's surface area. The required heat dissipation area will vary with the conditions in the cabinet. If convection in the cabinet is poor and heat builds up, effective heat dissipation will not be possible. Therefore, arrangement of the equipment in the cabinet and the use of a cooling fan should be considered. The above (1) in this section lists the cabinet dissipation area (guideline) when this unit and drive unit are operated at the ambient temperature of 40 C under rated load. When air flows along the outer wall of the cabinet, effective heat exchange will be possible, because the temperature slope inside and outside the cabinet will be steeper.

(Outside the cabinet) (Inside the cabinet)

Air flow

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 77

3.5.3 Inrush currents at power-on of the main circuit and control circuit power supplies

Since large inrush currents flow in the power supplies, be sure to use molded-case circuit breakers and magnetic contactors. (Refer to section 8.5.) When circuit protectors are used, it is recommended that the inertia delay type, which is not tripped by an inrush current, be used. (1) 200 V class

The following table indicates the inrush currents (reference data) that will flow when 240 V AC is applied.

Power regeneration converter unit Inrush currents (A0-P)

Main circuit power supply (L1/L2/L3) Control circuit power supply (L11/L21) MR-CV11K 38 A (attenuated to approx. 10 A in 45 ms)

23 A (attenuated to approx. 2 A in 5 ms)

MR-CV18K 38 A (attenuated to approx. 10 A in 70 ms) MR-CV30K 81 A (attenuated to approx. 20 A in 65 ms) MR-CV37K MR-CV45K

81 A (attenuated to approx. 20 A in 86 ms)

MR-CV55K 57 A (attenuated to approx. 20 A in 137 ms)

(2) 400 V class

The following table indicates the inrush currents (reference data) that will flow when 480 V AC is applied.

Power regeneration converter unit Inrush currents (A0-P)

Main circuit power supply (L1/L2/L3) Control circuit power supply (L11/L21) MR-CV11K4 24 A (attenuated to approx. 10 A in 22 ms)

15 A (attenuated to approx. 2 A in 5 ms) MR-CV18K4 24 A (attenuated to approx. 10 A in 35 ms) MR-CV30K4 48 A (attenuated to approx. 20 A in 35 ms) MR-CV37K4 MR-CV45K4

48 A (attenuated to approx. 20 A in 45 ms)

MR-CV55K4 MR-CV75K4

42 A (attenuated to approx. 20 A in 66 ms) 15 A (attenuated to approx. 2 A in 7 ms)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 78

3.6 Disabling the protection coordination mode (stand-alone drive)

CAUTION

Do not supply power to the main circuit power supply terminals (L1/L2/L3) of the servo amplifier. Otherwise, the servo amplifier and MR-CV_ power regeneration converter unit will malfunction. Connect the DC power supply between the MR-CV_ and servo amplifier with correct polarity. If incorrectly connected, the MR-CV_ and servo amplifier will malfunction.

POINT

When using the servo amplifier (not the drive unit) with the MR-CV_, set the converter setting rotary switch (SW1) of the MR-CV_ to "8" to disable the protection coordination mode. Two or more MR-CV_ power regeneration converter units cannot be installed to improve regeneration capability. Do not connect multiple MR-CV_s in a same DC power supply line. When using the servo amplifier with MR-CV_, set [Pr. PA04] of the servo amplifier to "0 0 _ _" to enable EM1 (Forced stop 1). In this configuration, only the STO function is supported. The forced stop deceleration function is not available. When using the power regeneration converter unit, set [Pr. PA02] to "0001".

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 79

3.6.1 200 V class

CN2

V

U

W

V

U

W

CN3

EM1

3

20

SD

DICOM 10

ALM 15

DOCOM

5DICOM

RA2

24 V DC

RESET

Servo amplifier (Note 9) Servo amplifier (Note 9)

P4

N-

L11

L21

CN8

CN2

M V

U

W

V

U

W

P4

N-

L11

L21

CN3

EM1

3

20

SD

DICOM 10

ALM 15

DOCOM

5DICOM

RA1

24 V DC

Main circuit power supply

Main circuit power supply

CN8

MCCB L1

L2

L3

MC

L11

L21

DOCOM

DICOM A

B

C

DICOM

MC

SK

L+

L-

(Note 7)

(Note 7)

(Note 7)

RES

RDYB

RDYA

RSO

DOCOM

RA3

(Note 1)

(Note 2)

(Note 3)

(Note 4)

(Note 1)

(Note 8)(Note 8) (Note 4)

24 V DC

24 V DC

M

(Note 10) (Note 10)

(Note 5)

Terminal block

CN1A CN1B CN1A

(Note 5)

Servo amplifier malfunction

RA1 (Note 1)

Servo amplifier malfunction

RA1

Servo amplifier malfunction

RA2

Servo amplifier malfunction

RA2 (Note 1)

Converter unit malfunction

RA3 (Note 1)

Converter unit malfunction

RA3

Emergency stop

switch

Emergency stop switch

Operation ready OFF/ON

Power regeneration converter unit

AC reactor

Servo system controller

Forced stop (Note 4)

SSCNET III cable SSCNET III cable

Servo motor Servo motor

PlatePlate

EncoderEncoder

Short-circuit connector (Packed with the servo amplifier)

Short-circuit connector (Packed with the servo amplifier)

3-phase 200 to 240 V AC, 50/60 Hz

(Note 6) (Note 6)

(Note 8)

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 80

Note 1. Configure a sequence that will shut off the main circuit power when:

An alarm has occurred at FR-CV or servo amplifier. EM1 (Forced stop 1) is enabled.

After MR-CV_ is in ready-on state, if the main circuit power supply for MR-CV_ is shut-off, alarms monitoring the power supply ([AL. 62 Frequency error], [AL. 67 open-phase], or [AL. 71 Undervoltage]) will occur. Remove what cause the main circuit power supply of MR-CV_ to shut off and cycle the power.

2. For the servo amplifier, configure a sequence that will switch the servo-on after the MR-CV_ is ready. 3. The RSO signal turns off when the reset signal is inputted and MR-CV_ is ready for operation. Configure a sequence that will

make the servo inoperative when the RSO signal is on. 4. Configure a sequence that will stop the MR-CV_ with the emergency stop input from the servo system controller if an alarm

occurs in the MR-CV_. When the servo system controller does not have an emergency stop input, use the forced stop input of the servo amplifier to make a stop as shown in the diagram.

5. When using MR-CV_, be sure to disconnect wiring between P3 and P4 terminals. 6. Set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1). 7. Use a molded-case circuit breaker to L11 and L21. 8. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they

can be configured by one. 9. When using the servo amplifier of 7 kW or less, make sure to connect the built-in regenerative resistor. (factory-wired) (5 kW

or less: P+ and D, 7 kW or less: P+ and C) 10. Twist or bundle the wires between L+/L- of the power regeneration converter unit and P4/N- of the servo amplifier with cable

ties to keep the two wires close to each other. Keep the wiring length between L+/L- of the power regeneration converter unit and P4/N- of the servo amplifier 1.5 m or longer, and total wiring length 5 m or shorter.

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 81

3.6.2 400 V class

CN2

V

U

W

V

U

W

CN3

EM1

3

20

SD

DICOM 10

ALM 15

DOCOM

5DICOM

RA2

24 V DC

RESET

P4

N-

L11

L21

CN8

CN2

M V

U

W

V

U

W

P4

N-

L11

L21

CN3

EM1

3

20

SD

DICOM 10

ALM 15

DOCOM

5DICOM

RA1

24 V DC

CN8

MCCB L1

L2

L3

MC

L11

L21

DOCOM

DICOM A

B

C

DICOM

MC

SK

L+

L-

(Note 7)

(Note 7)

(Note 7)

RES

RDYB

RDYA

RSO

DOCOM

RA3

(Note 2)

(Note 3)

24 V DC

24 V DC

Step-down transformer

M

(Note 10) (Note 10)

(Note 5)

CN1A CN1B CN1A

(Note 5)

(Note 1)

(Note 4)

(Note 1)

(Note 8)(Note 8)

(Note 8)

(Note 4)

3-phase 380 to 480 V AC, 50/60 Hz

Terminal blockAC reactor

Servo system controller

Forced stop (Note 4)

SSCNET III cable SSCNET III cable

Servo motor Servo motor

Encoder Encoder

Plate Plate

Servo amplifier malfunction

RA1 (Note 1)

Servo amplifier malfunction

RA2 (Note 1)

Converter unit malfunction

RA3 (Note 1)

Servo amplifier malfunction

RA1

Servo amplifier malfunction

RA2

Converter unit malfunction

RA3

Emergency stop switch

Operation ready OFF/ON

Short-circuit connector (Packed with the servo amplifier)

Short-circuit connector (Packed with the servo amplifier)

Main circuit power supply

Main circuit power supply

(Note 6) (Note 6)

Emergency stop

switch

Servo amplifier (Note 9) Servo amplifier (Note 9)

Power regeneration converter unit

3. MR-CV_ POWER REGENERATION CONVERTER UNIT

3 - 82

Note 1. Configure a sequence that will shut off the main circuit power when:

An alarm has occurred at FR-CV or servo amplifier. EM1 (Forced stop 1) is enabled.

After MR-CV_ is in ready-on state, if the main circuit power supply for MR-CV_ is shut-off, alarms monitoring the power supply ([AL. 62 Frequency error], [AL. 67 open-phase], or [AL. 71 Undervoltage]) will occur. Remove what cause the main circuit power supply of MR-CV_ to shut off and cycle the power.

2. For the servo amplifier, configure a sequence that will switch the servo-on after the MR-CV_ is ready. 3. The RSO signal turns off when the reset signal is inputted and MR-CV_ is ready for operation. Configure a sequence that will

make the servo inoperative when the RSO signal is on. 4. Configure a sequence that will stop the MR-CV_ with the emergency stop input from the servo system controller if an alarm

occurs in the MR-CV_. When the servo system controller does not have an emergency stop input, use the forced stop input of the servo amplifier to make a stop as shown in the diagram.

5. When using MR-CV_, be sure to disconnect wiring between P3 and P4 terminals. 6. Set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1). 7. Use a molded-case circuit breaker to L11 and L21. 8. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they

can be configured by one. 9. When using the servo amplifier of 7 kW or less, make sure to connect the built-in regenerative resistor. (factory-wired) (3.5

kW or less: P+ and D, 7 kW or less: P+ and C) 10. Twist or bundle the wires between L+/L- of the power regeneration converter unit and P4/N- of the servo amplifier with cable

ties to keep the two wires close to each other. Keep the wiring length between L+/L- of the power regeneration converter unit and P4/N- of the servo amplifier 1.5 m or longer, and total wiring length 5 m or shorter.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 1

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

POINT MR-CR_ resistance regeneration converter unit can be used in a combination with MR-J4-DU_(-RJ) drive units of 30 kW or more.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 2

4.1 Function block diagram

(1) MR-J4-DU_B_(-RJ) The function block diagram of this servo is shown below.

POINT

The diagram shows the combination of the MR-J4-DU_B_-RJ drive unit and resistance regeneration converter unit as an example. The MR-J4-DU_B_ drive unit does not have the CN2L connector.

+

MC Thyristor

Power supply

Control circuit power supply

L11

L21

L1

L2

L3

CN1 I/F

CHARGE lamp

Regenerative option

Resistance regeneration converter unit

Diode stack

P1 P2

Cooling fan

C

CPU

Malfunction, warning, forced stop

CN40

Resistance regeneration converter unit protection coordination

To CN40A of drive unit

To L11 of drive unit

To L21 of drive unit

To L+ of drive unitL+

To L- of drive unitL-

Regene- rative TR

Power factor improving DC reactor

CNP1

MC drive

Current detection

Voltage detection

Base amplifier

MCCB

+ U U

U

MCCB

MCCB

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 3

From CN40 of resistance regeneration converter unit C

N 40

A

CN5

USB

USB

Personal computer

Controller or

drive unit

I/F Control

Drive unit or cap

CN1A CN1B CN3

D/A

Analog monitor (2 channels)

Digital I/O control

BU BV BW

L11

L21

C N

2

U

V

W

U

V

W M

From MCCB

From L+ of resistance regeneration converter unit

L+

From L- of resistance regeneration converter unit

L-

C N

4

MCCB

+

C N

2L

C N

8

External dynamic brake

(optional)

(Note 3)

Model position control

Model speed control

Position command

input

Virtual motor

Virtual encoder

Base amplifier

Encoder

Servo motorDrive unit

Current detection

Overcurrent protection

Control circuit power supply

Current detector

(Note 1) Power supply

Cooling fan

Cooling fan

STO switch

STO control circuit

External encoder

(Note 2)

step- down circuit

Model position Model speed Model torque

Current control

Actual position control

Actual speed control

Battery (for absolute position detection system)

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". 2. This is for the MR-J4-DU_B_-RJ drive unit. The MR-J4-DU_B_ drive unit does not have the CN2L connector. 3. Use an external dynamic brake for the drive unit. Failure to do so will cause an accident because the servo motor does not

stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For wiring of the external dynamic brake, refer to section 8.3. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 4

(2) MR-J4-DU_A_(-RJ)

The function block diagram of this servo is shown below.

POINT The diagram shows the combination of the MR-J4-DU_A_-RJ drive unit and resistance regeneration converter unit as an example. The MR-J4-DU_A_ drive unit does not have the CN2L connector.

+

MC Thyristor

Power supply

Control circuit power supply

L11

L21

L1

L2

L3

CN1 I/F

CHARGE lamp

Regenerative option

Diode stack

P1 P2

Cooling fan

C

CPU

Malfunction, warning, forced stop

CN40

Resistance regeneration converter unit protection coordination

To CN40A of drive unit

To L11 of drive unit

To L21 of drive unit

To L+ of drive unitL+

To L- of drive unitL-

Regene- rative TR

Power factor improving DC reactor

CNP1

MC drive

Current detection

Voltage detection

Base amplifier

MCCB

+ U U

U

MCCB

MCCB

Resistance regeneration converter unit

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 5

CN5 CN3 CN6

Analog monitor (2 channels)

I/F

USB RS-422/ RS-485

RS-422/ RS-485

D/AA/D

USB

ControllerPersonal computer

Analog (2 channels)

D I/O control

CN1

External dynamic brake

(optional)

(Note 3)

Model position control

Model speed control

Position command

input

Virtual motor

Virtual encoder

C N

40 A

BU BV BW

Base amplifier

Encoder

Servo motor

L11

L21

Drive unit

Current detection C

N 2

U

V

W

U

V

W M

Overcurrent protection

Control circuit power supply

Current detector

(Note 1) Power supply

L+

L-

C N

4

Cooling fan

Cooling fan

MCCB

+

C N

2L

C N

8STO switch

STO control circuit

External encoder

(Note 2)

step- down circuit

Model position Model speed Model torque

Current control

Actual position control

Actual speed control

Battery (for absolute position detection system)

Servo-on Input command pulse Start Malfunction, etc.

From CN40 of resistance regeneration converter unit

From MCCB

From L+ of resistance regeneration converter unit

From L- of resistance regeneration converter unit

Note 1. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". 2. This is for the MR-J4-DU_A_-RJ drive unit. The MR-J4-DU_A_ drive unit does not have the CN2L connector. 3. Use an external dynamic brake for the drive unit. Failure to do so will cause an accident because the servo motor does not

stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For wiring of the external dynamic brake, refer to section 8.3. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 6

4.2 Structure

4.2.1 Parts identification

POINT

The resistance regeneration converter unit is shown with the terminal cover open. For opening or closing of the terminal cover, refer to section 4.2.2.

(1) (2) (15) (3) (4)

(5)

(6)

(7)

(8)

(9)

(10)

(12)(11)(13)(12)(14)

No. Name/Application Detailed explanation

(1) Magnetic contactor control connector (CNP1) Used to connect the coil of the magnetic contactor.

Section 4.3.3 (2)

I/O signal connector (CN1) Used to connect digital I/O signals.

(3) Charge lamp Lights up when the main circuit is charged. While this lamp is lit, do not reconnect the cables.

(4) Display The 3-digit, 7-segment LED display shows the resistance regeneration converter unit status and the alarm number.

Section 4.4.3

(5)

Operation section Used to perform status display, diagnostic, alarm, and parameter setting operations.

Used to set data.

MODE UP DOWN SET

Used to change the display or data in each mode. Used to change the mode.

(6)

Manufacturer setting connector (CN6) This is for manufacturer setting. Although the shape is similar to the analog monitor connector (CN6) of the drive unit, do not connect anything including an analog monitor.

(7) Protection coordination connector (CN40) Used to connect CN40A of the drive unit.

Section 4.3.1

(8)

Manufacturer setting connector (CN3) This is for manufacturer setting. Although the shape is similar to the RS-422/RS-485 communication connector (CN3) of the drive unit, do not connect anything, including a personal computer and parameter unit.

(9) L+/L- terminal (TE2-2) Used to connect a drive unit using a bus bar supplied with the drive unit.

Section 4.3.1 Section 4.3.2

(10) Control circuit terminal L11 and L21 (TE3) Used to connect the control circuit power supply.

(11)

Regenerative option/Power factor improving DC reactor (TE1-2) Used to connect a regenerative option or a power factor improving DC reactor.

(12) Protective earth (PE) terminal Grounding terminal

(13) Main circuit terminal block (TE1-1) Used to connect the input power supply.

(14) L+/L- terminal (TE2-1) When using a brake unit, connect it to this terminal. Do not connect anything other than the brake unit.

Section 8.11

(15) Rating plate Section 1.2

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 7

4.2.2 Opening and closing of the terminal block cover

WARNING

Before opening or closing the terminal block cover, turn off the power and wait for 20 minutes or more until the charge lamp turns off. Then, confirm that the voltage between L+ and L- is safe with a voltage tester or others. Otherwise, an electric shock may occur. In addition, always confirm that the charge lamp is off from the front of the resistance regeneration converter unit.

The following shows how to open and close the terminal block cover using illustrations of resistance regeneration converter unit as an example. For a drive unit, the shape of the main unit is different. However, the terminal block cover can be opened or closed in the same procedure. (1) Upper terminal block cover

(a) How to open

A)

A)

1) Pull up the cover using point A) as a support.

2) The cover is fixed when pulled up to the position as shown in the illustration.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 8

(b) How to close

A)

A)

Setting tab

1) Close the cover using point A) as a support.

Setting tab

2) Press the cover against the terminal box until the installing knobs click.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 9

(2) Lower terminal block cover

(a) How to open

1) Hold the bottom of the terminal block cover with both hands.

B)

B)

2) Pull up the cover using point B) as a support.

3) The cover is fixed when pulled up to the top.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 10

(b) How to close

Setting tab

Setting tab

1) Hold the bottom of the terminal block cover with both hands.

B)

B)

2) Close the cover using point B) as a support.

Setting tab

3) Press the cover against the terminal box until the installing knobs click.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 11

4.3 Signals and wiring

WARNING

A person who is involved in wiring should be fully competent to do the work. Before wiring, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between L+ and L- is safe with a voltage tester or others. Otherwise, an electric shock may occur. In addition, always confirm that the charge lamp is off from the front of the resistance regeneration converter unit. Ground the resistance regeneration converter unit, the drive unit and the servo motor securely. Do not attempt to wire the resistance regeneration converter unit, the drive unit, and the servo motor until they have been installed. Otherwise, it may cause an electric shock. The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric shock. To avoid an electric shock, insulate the connections of the power supply terminals.

CAUTION

Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly, resulting in injury. Connect cables to the correct terminals. Otherwise, a burst, damage, etc. may occur. Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc. may occur. The surge absorbing diode installed to the DC relay for control output should be fitted in the specified direction. Otherwise, the emergency stop and other protective circuits may not operate.

DOCOM 24 V DC

Resistance regeneration converter unit

RA

For sink output interface

Control output signal

DOCOM

Control output signal

24 V DC

RA

For source output interface

Resistance regeneration converter unit

Use a noise filter, etc. to minimize the influence of electromagnetic interference. Electromagnetic interference may be given to the electronic equipment used near the resistance regeneration converter unit and the drive unit. When using the regenerative resistor, switch power off with the alarm signal. Otherwise, a transistor fault or the like may overheat the regenerative resistor, causing a fire. Do not modify the equipment.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 12

The following items are the same as those of MR-J4-_(-RJ). For details of the items, refer to each chapter/section indicated in the detailed explanation field. "MR-J4-_B" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

Model Item Detailed explanation

MR-J4-DU_B_(-RJ) I/O signal connection example MR-J4-_B_ section 3.2 Forced stop deceleration function MR-J4-_B_ section 3.6 SSCNET III cable connection MR-J4-_B_ section 3.9

MR-J4-DU_A_(-RJ) I/O signal connection example MR-J4-_A_ section 3.2 Forced stop deceleration function MR-J4-_A_ section 3.7

4.3.1 Input power supply circuit

WARNING

Insulate the connections of the power supply terminals. Otherwise, an electric shock may occur. Always connect the magnetic contactor wiring connector to CNP1 of the resistance regeneration converter unit. If the connector is not connected, an electric shock may occur.

CAUTION

Always connect the magnetic contactor between the power supply and the main circuit power supply (L1/L2/L3) of the resistance regeneration converter unit, in order to configure a circuit that shuts down the power supply on the side of the resistance regeneration converter unit power supply. If the magnetic contactor is not connected, a large current keeps flowing and may cause a fire when the resistance regeneration converter unit or the drive unit malfunctions. Use ALM (Malfunction) to switch power off. Not doing so may cause a fire when a regenerative transistor malfunctions or the like may overheat the regenerative resistor. The resistance regeneration converter unit has a built-in surge absorber (varistor) to reduce exogenous noise and to suppress lightning surge. Exogenous noise or lightning surge deteriorates the varistor characteristics, and the varistor may be damaged. To prevent a fire, use a molded-case circuit breaker or fuse for input power supply. Check the resistance regeneration converter unit model, and then input proper voltage to the resistance regeneration converter unit power supply. If input voltage exceeds the upper limit, the resistance regeneration converter unit and the drive unit will break down.

POINT

For drive units, EM2 has the same function as EM1 in the torque control mode. For the MR-J4-DU_B_(-RJ) drive units, do not switch off the control circuit power supply even though an alarm occurs. When the control circuit power supply is switched off, optical module does not operate, and optical transmission of SSCNET III/H communication is interrupted. Therefore, the next axis servo amplifier and the drive unit display "AA" at the indicator and turn into base circuit shut-off. The dynamic brake operates, bringing the servo motor to a stop.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 13

(1) Magnetic contactor control connector (CNP1)

CAUTION Always connect the magnetic contactor wiring connector to the resistance regeneration converter unit. If the connector is not connected, an electric shock may occur since CNP1-1 and L11 are always conducting.

By enabling magnetic contactor drive output, the main circuit power supply can be shut off automatically when an alarm occurs in the resistance regeneration converter unit or the drive unit. To enable magnetic contactor drive output, set [Pr. PA02] of the resistance regeneration converter unit to "_ _ _ 1" (initial value).

Magnetic contactor drive output selection 0: Disabled 1: Enabled

1 [Pr. PA02]

0 0 0

(a) When magnetic contactor drive output is enabled To control the magnetic contactor, connect the magnetic contactor control connector (CNP1) to the coil of the magnetic contactor.

Internal connection diagram of CNP1

MCCB

Resistance regeneration converter unit

L11

L21

Power supply

1MC1

2MC2

CNP1

RA1 RA2

Resistance regeneration converter unit malfunction Operation ready

OFF/ON

Drive unit malfunction Emergency stop

switch

L1

L2

L3

(Note 1)

MC

SK

(Note 2, 3) MC

Note 1. A step-down transformer is required when coil voltage of the magnetic contactor is 200 V class, and the resistance regeneration converter unit and the drive unit are 400 V class.

2. The bus voltage decreases depending on the main circuit voltage and operation pattern, which may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

3. When the voltage between L11 and L21 drops due to an instantaneous power failure and others, the magnetic contactor is turned off.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 14

When the resistance regeneration converter unit receives a start command from the drive unit, CNP1-2 and L21 are shorted, and the control circuit power is supplied to the magnetic contactor. When the control circuit power is supplied, the magnetic contactor is turned on, and the main circuit power is supplied to the resistance regeneration converter unit. In the following cases, CNP1-2 and L21 in the resistance regeneration converter unit are opened, and the main circuit power supply is automatically shut off.

1) An alarm occurred in the resistance regeneration converter unit.

2) An alarm occurred in the drive unit.

3) The forced stop (EM1) of the resistance regeneration converter unit was disabled.

4) [AL. 95 STO warning] occurred in the drive unit.

(b) When magnetic contactor drive output is disabled

The main circuit power supply is not automatically shut off even when an alarm occurs in the resistance regeneration converter unit or the drive unit. Therefore, configure an external circuit to shut off the main circuit power supply when detecting an alarm.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 15

(2) Wiring diagram

(a) When magnetic contactor drive output is enabled (factory setting)

POINT The resistance regeneration converter unit controls the magnetic contactor. Connect the resistance regeneration converter unit and the drive unit with MR- J3CDL05M protection coordination cable. Always turn on or off the control circuit power supplies of the resistance regeneration converter unit and the drive unit simultaneously.

1) 200 V class

RA3RA1 RA2

Optional thermal Operation ready

OFF/ON

Drive unit malfunction Emergency stop

switch MC

SK

RA1

MC (Note 4)

MCCB

RA2

(Note 1) Regenerative

option

L+

L-

MR-J3CDL05M cable

Drive unit

L1

L2

L3

L11

L21

3-phase 200 V AC to 240 V AC

1MC1

2MC2 CN40 CN40A

(Note 11) CN2

External dynamic brake

(optional)

BV

M

Encoder

V

U

W

V

U

W

Servo motor

(Note 3) Power supply

TE2-2 L+

L-

TE2-1

C

P1

P2

Power factor improving DC reactor (optional)

(Note 2)

L11

L21

G4G3

P C

G4G3

P C

S1R1

G4G3

P C

Cooling fan

(Note 1) Regenerative

option Cooling fan

(Note 1) Regenerative

option Cooling fan

S1R1 S1R1

CNP1

CN1

1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

CN3

EM2

3

20

SDPlate

DICOM10

ALM15

DOCOM

5 DICOM

(Note 7) Encoder cable

24 V DC

24 V DC

MCCB

BW

BU

Cooling fan

(Note 5) Main circuit power supply

(Note 6, 14)

RA3

24 V DC

(Note 10) Short-circuit connector (packed with the drive unit)

CN8

(Note 11)

(Note 8)

(Note 12)

(Note 9, 15)

(Note 13)

Resistance regeneration converter unit

Resistance regeneration converter unit malfunction

(Note 9, 15)

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 16

Note 1. This is for MR-RB137. For the MR-RB137, three units are used as one set (permissible regenerative power: 3900 W). 2. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing

the short bar across them. Refer to section 8.6 for details. 3. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". 4. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. The bus voltage decreases depending on the main circuit voltage and operation pattern, which may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

5. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off.

6. Use an external dynamic brake for the drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3.

7. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual (Vol. 3)".

8. This diagram shows sink I/O interface. For source I/O interface, refer to section 4.3.6 (2). 9. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section

8.5.) 10. When not using the STO function, attach the short-circuit connector supplied with the drive unit. 11. Do not connect a servo motor of the wrong axis to U, V, W, or CN2 of the drive unit. Otherwise, a malfunction may occur. 12. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)". 13. The wiring is for MR-J4-DU_B_(-RJ). The connections to the interfaces of MR-J4-DU_(-RJ) are the same as in the case of

MR-J4-_(-RJ). Refer to each servo amplifier instruction manual. 14. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB. Failure to do so will

cause the drive unit to become servo-off when an instantaneous power failure occurs. 15. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 17

2) 400 V class

RA1

MCMCCB

RA2

L+

L-

L1

L2

L3

L11

L21

CN40 CN40A

M V

U

W

V

U

W

TE2-2 L+

L-

TE2-1 (Note 15)

C

P1

P2

L11

L21

G4G3 P C

G4G3

P C

S400R400

G4G3

P C

S400R400 S400R400

CN1 1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

CN3

EM2

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM

BW

BV

BU MCCB

RA3RA1 RA2 MC

SK

1MC1

2MC2

CNP1

(Note 3) Step-down transformer

RA3

CN8

Optional thermal Operation ready

OFF/ON

Drive unit malfunction Emergency stop

switch

(Note 5)

(Note 1) Regenerative

option

MR-J3CDL05M cable

Drive unit

3-phase 380 V AC to 480 V AC

(Note 12) CN2

External dynamic brake

(optional)

Encoder

Servo motor

(Note 4) Power supply

Power factor improving DC reactor (optional)

(Note 2)

Cooling fan

(Note 1) Regenerative

option Cooling fan

(Note 1) Regenerative

option Cooling fan

Plate

(Note 8) Encoder cable

24 V DC

24 V DC

Cooling fan

(Note 6) Main circuit power supply

(Note 7, 16)

24 V DC

(Note 11) Short-circuit connector (packed with the drive unit)

(Note 12)

(Note 9)

(Note 13)

(Note 10, 17)

(Note 14)

Resistance regeneration converter unit

Resistance regeneration converter unit malfunction

(Note 10, 17)

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 18

Note 1. This is for MR-RB13V-4. For the MR-RB13V-4, three units are used as one set (permissible regenerative power: 3900 W). 2. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing

the short bar across them. Refer to section 8.6 for details. 3. A step-down transformer is required when the coil voltage of the magnetic contactor is 200 V class. 4. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". 5. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. The bus voltage decreases depending on the main circuit voltage and operation pattern, which may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

6. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off.

7. Use an external dynamic brake for the drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3.

8. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual (Vol. 3)".

9. This diagram shows sink I/O interface. For source I/O interface, refer to section 4.3.6 (2). 10. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section

8.5.) 11. When not using the STO function, attach the short-circuit connector supplied with the drive unit. 12. Do not connect the servo motor of a wrong axis to U, V, W, or CN2 of the drive unit. Otherwise, a malfunction may occur. 13. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)". 14. The wiring is for MR-J4-DU_B_(-RJ). The connections to the interfaces of MR-J4-DU_(-RJ) are the same as in the case of

MR-J4-_(-RJ). Refer to each servo amplifier instruction manual. 15. For the MR-J4-DU30K_4(-RJ) and MR-J4-DU37K_4(-RJ), the terminal block is TE2. 16. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB. Failure to do so will

cause the drive unit to become servo-off when an instantaneous power failure occurs. 17. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 19

(b) When magnetic contactor drive output is disabled

POINT

Connect the resistance regeneration converter unit and the drive unit with MR- J3CDL05M protection coordination cable. Always turn on or off the control circuit power supplies of the resistance regeneration converter unit and the drive unit simultaneously.

1) 200 V class

RA1

MC (Note 5)

RA2

L+

L-

MR-J3CDL05M cable

Drive unit

L1

L2

L3

L11

L21

MCCB

CN40A

(Note 12) CN2

External dynamic brake

(optional)

M V

U

W

V

U

W

Servo motor

TE2-2 L+

L-

TE2-1

C

P1

P2

Power factor improving DC reactor (optional)

(Note 2)

L11

L21

G4G3

P C

G4G3

P C

S1R1

G4G3

P C

S1R1 S1R1

CN1 1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

CN3

EM2

3

20

SDPlate

DICOM10

ALM15

DOCOM

5 DICOM

(Note 8) Encoder cable

24 V DC

24 V DC

BW

BV

BU Encoder (Note 4) Power supply

MCCB

Cooling fan

(Note 6) Main circuit power supply

(Note 7, 15)

RA3RA1 RA2

MC

MC

SK

CN40

1MC1

2MC2

CNP1

RA3

24 V DC

(Note 10, 16)

(Note 14)

(Note 11) Short-circuit connector (packed with the drive unit)

CN8

(Note 9)

(Note 13)

(Note 3)

(Note 12)

(Note 10, 16)

Optional thermal

Operation readyDrive unit malfunction Emergency stop

switch

(Note 1) Regenerative

option

3-phase 200 V AC to 240 V AC

Cooling fan

(Note 1) Regenerative

option Cooling fan

(Note 1) Regenerative

option Cooling fan

ONOFF

Resistance regeneration converter unit

Resistance regeneration converter unit malfunction

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 20

Note 1. This is for MR-RB137. For the MR-RB137, three units are used as one set (permissible regenerative power: 3900 W). 2. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing

the short bar across them. Refer to section 8.6 for details. 3. Always connect the magnetic contactor wiring connector to CNP1 of the resistance regeneration converter unit. If the

connector is not connected, an electric shock may occur. 4. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". 5. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. The bus voltage decreases depending on the main circuit voltage and operation pattern, which may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

6. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off.

7. Use an external dynamic brake for the drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3.

8. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual (Vol. 3)".

9. This diagram shows sink I/O interface. For source I/O interface, refer to section 4.3.6 (2). 10. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section

8.5.) 11. When not using the STO function, attach the short-circuit connector supplied with the drive unit. 12. Do not connect the servo motor of a wrong axis to U, V, W, or CN2 of the drive unit. Otherwise, a malfunction may occur. 13. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)". 14. The wiring is for MR-J4-DU_B_(-RJ). The connections to the interfaces of MR-J4-DU_(-RJ) are the same as in the case of

MR-J4-_(-RJ). Refer to each servo amplifier instruction manual. 15. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB. Failure to do so will

cause the drive unit to become servo-off when an instantaneous power failure occurs. 16. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 21

2) 400 V class

BW

BV

BU (Note 5) Power supply

MCCB

Cooling fan

(Note 7) Main circuit power supply

RA1

MC (Note 6)

RA2

L+

L-

MR-J3CDL05M cable

Drive unit

L1

L2

L3

L11

L21

MCCB

CN40A

(Note 13) CN2

External dynamic brake

(optional)

M

Encoder

V

U

W

V

U

W

Servo motor

TE2-2 L+

L-

TE2-1 (Note 16)

C

P1

P2

Power factor improving DC reactor (optional)

(Note 2)

L11

L21

G4G3

P C

G4G3

P C

S400R400

G4G3

P C

S400R400 S400R400

CN1 1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

CN3

EM2

3

20

SD

DICOM10

ALM15

DOCOM

5 DICOM

(Note 9) Encoder cable

24 V DC

24 V DC

(Note 8, 17)

CN40

1MC1

2MC2

CNP1

RA3RA1 RA2

MC

MC

SK

RA3

24 V DC

(Note 11, 18) (Note 13)

(Note 12) Short-circuit connector (packed with the drive unit)

CN8

(Note 10)

(Note 4)

(Note 15)

(Note 14)

(Note 11, 18)

(Note 3) Step-down transformer

Optional thermal

Drive unit malfunction Emergency stop

switch

(Note 1) Regenerative

option

3-phase 380 V AC to 480 V AC

Cooling fan

(Note 1) Regenerative

option Cooling fan

(Note 1) Regenerative

option Cooling fan

Plate

Operation ready

ONOFF

Resistance regeneration converter unit

Resistance regeneration converter unit malfunction

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 22

Note 1. This is for MR-RB13V-4. For the MR-RB13V-4, three units are used as one set (permissible regenerative power: 3900 W). 2. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing

the short bar across them. Refer to section 8.6 for details. 3. A step-down transformer is required when the coil voltage of the magnetic contactor is 200 V class. 4. Always connect the magnetic contactor wiring connector to CNP1 of the resistance regeneration converter unit. If the

connector is not connected, an electric shock may occur. 5. For specifications of the cooling fan power supply, refer to "Servo Motor Instruction Manual (Vol. 3)". 6. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. The bus voltage decreases depending on the main circuit voltage and operation pattern, which may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

7. To prevent an unexpected restart of the drive unit, configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off.

8. Use an external dynamic brake for the drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. For wiring of the external dynamic brake, refer to section 8.3.

9. For the encoder cable, use of the option cable is recommended. For selecting cables, refer to "Servo Motor Instruction Manual (Vol. 3)".

10. This diagram shows sink I/O interface. For source I/O interface, refer to section 4.3.6 (2). 11. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section

8.5.) 12. When not using the STO function, attach the short-circuit connector supplied with the drive unit. 13. Do not connect the servo motor of a wrong axis to U, V, W, or CN2 of the drive unit. Otherwise, a malfunction may occur. 14. For connecting servo motor power wires, refer to "Servo Motor Instruction Manual (Vol. 3)". 15. The wiring is for MR-J4-DU_B_(-RJ). The connections to the interfaces of MR-J4-DU_(-RJ) are the same as in the case of

MR-J4-_(-RJ). Refer to each servo amplifier instruction manual. 16. For the MR-J4-DU30K_4(-RJ) and MR-J4-DU37K_4(-RJ), the terminal block is TE2. 17. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB. Failure to do so will

cause the drive unit to become servo-off when an instantaneous power failure occurs. 18. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 23

(3) How to use the bus bars

Make sure to use the supplied bus bars and connect the L+ and L- of the drive unit to those of the resistance regeneration converter unit as shown below. Never use bus bars other than the ones supplied with the drive unit. Both the units are shown with the terminal cover open.

Bus bar

L+

L-

L+

L-

Drive unit Resistance regeneration

converter unit

4.3.2 Explanation of power supply system

(1) Signal explanations

POINT For the layout of the terminal block, refer to chapter 7 DIMENSIONS.

Connection target

(application) Symbol (Note)

Terminal block

Description

MR-CR55K MR-CR55K4

Main circuit power supply L1/L2/L3 TE1-1 Supply 3-phase 200 V AC to 240 V AC,

50 Hz/60 Hz power to L1, L2, and L3. Supply 3-phase 380 V AC to 480 V AC, 50 Hz/60 Hz power to L1, L2, and L3.

Control circuit power supply L11/L21 TE3 Supply 1-phase 200 V AC to 240 V AC,

50 Hz/60 Hz power to L11 and L21. Supply 1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz power to L11 and L21.

Power factor improving DC reactor P1/P2 TE1-2 When using the power factor improving DC reactor, connect P1 and P2 after

removing the short bar across them. Regenerative option P2/C TE1-2 Connect the regenerative option between P2 and C.

Brake unit L+/L- TE2-1 When using a brake unit, connect it to this terminal. Do not connect anything other than the brake unit.

Drive unit L+/L- TE2-2 Connect the L+ and L- of the drive unit to this terminal. Use the bus bars supplied with the drive unit to connect.

Protective earth (PE) PE Connect the protective earth (PE) of the cabinet to this terminal. Note. The permissible tension applied to any of the terminal blocks TE1-1, TE1-2, TE2-1, TE2-2 is 350 N.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 24

(2) Power-on sequence

(a) MR-J4-DU_B_(-RJ) 1) Power-on procedure

a) Always use a magnetic contactor for the main circuit power supply wiring (L1/L2/L3) as shown in above section 4.3.1 (2). Configure an external sequence to switch off the magnetic contactor as soon as an alarm occurs.

b) Turn on the control circuit power supplies (L11/L21) of the resistance regeneration converter

unit and drive unit simultaneously with the main circuit power supply or before turning on the main circuit power supply. If the main circuit power supply is not on, the display shows the corresponding warning. However, by switching on the main circuit power supply, the warning disappears and the drive unit will operate properly.

2) Timing chart

a) When magnetic contactor drive output is enabled and the status remains at ready-on The main circuit power is not shut off with servo-off.

ON

OFF Main circuit power supply

ON

OFF

Servo-on command (from servo system controller)

(95 ms)

ON

OFF Base circuit

(3 s) (Note 4)

Tb

ON

OFF

ON

OFF

(Note 1) ON

OFF

MBR (Electromagnetic brake interlock)

0 r/minServo motor speed

0 r/min Position command (Note 3)

(Note 2)

Resistance regeneration converter unit Control circuit power supply

Drive unit Control circuit power supply

Note 1. When setting up an electromagnetic brake at customer's side, make up a sequence which will operate the electromagnetic brake as follow using MBR. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. Give a position command after the external electromagnetic brake is released. 3. This is in position control mode. 4. In [Pr. PC02 Electromagnetic brake sequence output], set a delay time (Tb) from MBR off to base circuit

shut-off at a servo-off.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 25

b) When magnetic contactor drive output is enabled and the status returns to ready-off

The magnetic contactor of the resistance regeneration converter unit is turned off with ready- off, and the main circuit power supply is shut off.

ON

OFF Main circuit power supply

ON

OFF

Servo-on command (from servo system controller)

(3 s)

ON

OFF Base circuit

(3 s)

ON

OFF

ON

OFF

(Note 1) ON

OFF

MBR (Electromagnetic brake interlock)

0 r/minServo motor speed

0 r/min Position command (Note 3)

(Note 2)

Drive unit Control circuit power supply Resistance regeneration converter unit Control circuit power supply

Note 1. When setting up an electromagnetic brake at customer's side, make up a sequence which will operate the electromagnetic brake as follow using MBR. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. Give a position command after the external electromagnetic brake is released. 3. This is in position control mode.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 26

c) When magnetic contactor drive output is disabled

When an alarm occurs, turn off the magnetic contactor using the external sequence, and shut off the main circuit power supply.

ON

OFF Main circuit power supply

ON

OFF

Servo-on command (from servo system controller)

(95 ms)

ON

OFF Base circuit

(3 s) (Note 4, 5)

Tb

ON

OFF

ON

OFF

Drive unit Control circuit power supply

(Note 1) ON

OFF

MBR (Electromagnetic brake interlock)

0 r/minServo motor speed

0 r/min Position command (Note 3)

(Note 2)

Resistance regeneration converter unit Control circuit power supply

Note 1. When setting up an electromagnetic brake at customer's side, make up a sequence which will operate the electromagnetic brake as follow using MBR. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. Give a position command after the external electromagnetic brake is released. 3. This is in position control mode. 4. In [Pr. PC02 Electromagnetic brake sequence output], set a delay time (Tb) from MBR off to base circuit

shut-off at a servo-off. 5. The base circuit remains ready-on status at servo-off. When the status is ready-off, the base circuit and

the servo-on command turn off at the same time. (Tb = 0)

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 27

(b) MR-J4-DU_A_(-RJ)

1) Power-on procedure a) Always use a magnetic contactor for the main circuit power supply wiring (L1/L2/L3) as shown

in above section 4.3.1 (2). Configure an external sequence to switch off the magnetic contactor as soon as an alarm occurs.

b) When enabling magnetic contactor drive output, turn on the control circuit power supplies

(L11/L21) of the resistance regeneration converter unit and the drive unit simultaneously. The main circuit power supply is automatically turned on after the resistance regeneration converter unit and drive unit are started. When using an external sequence to control the magnetic contactor, turn on the control circuit power supplies (L11/ L21) of the resistance regeneration converter unit and drive unit simultaneously with the main circuit power supply or before turning on the main circuit power supply. If the main circuit power supply is not on, the display shows the corresponding warning. However, by switching on the main circuit power supply, the warning disappears and the drive unit will operate properly.

2) Timing chart

ON

OFF Main circuit power supply

ON

OFF SON (servo-on)

(95 ms)

ON

OFF Base circuit

(3 s) (Note 4)

Tb

ON

OFF

ON

OFF

MBR (Electromagnetic brake interlock)

0 r/minServo motor speed

0 r/minPosition command (Note 3)

(Note 2)

ON

OFF

(Note 1)

Drive unit Control circuit power supply Resistance regeneration converter unit Control circuit power supply

Note 1. When setting up an electromagnetic brake at customer's side, make up a sequence which will operate the electromagnetic brake as follow using MBR. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. Give a position command after the external electromagnetic brake is released. 3. This is in position control mode. 4. In [Pr. PC16 Electromagnetic brake sequence output], set a delay time (Tb) from MBR off to base circuit

shut-off at a servo-off.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 28

4.3.3 Connectors and pin assignment

POINT The pin assignment of the connectors is as viewed from the cable connector wiring section.

CN6 Leave this open.

CN40 Connect to CN40A of the drive unit.

CN3 Leave this open.

CN1CNP1

CN1 (Digital I/O connector) Model: 17JE-23090-02(D8A)K11-CG (D-sub 9 pin or equivalent) (DDK)

DICOM

WNG

9 DOCOM

5

2

4

6

7 3

1

8

DOCOM

EM1

DICOM ALM

CNP1 (Magnetic contactor wiring connector) Model: GFKC 2,5/2-STF-7,62

(Phoenix Contact)

1 MC1

2 MC2

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 29

4.3.4 Signal (device) explanations

The following table lists the resistance regeneration converter unit signals (devices). For the I/O interfaces (symbols in I/O division column in the table), refer to section 4.3.6 (1).

Signal (device) Symbol Connector pin No. Function and application I/O

division Digital I/F power supply input

DICOM CN1-1 CN1-6

Input 24 V DC (24 V DC 10% 150 mA) for I/O interface. The power supply capacity changes depending on the number of I/O interface points to be used. For sink interface, connect + of 24 V DC external power supply. For source interface, connect - of 24 V DC external power supply.

Forced stop EM1 CN1-7 When MR-CR55K is used with MR-J4-DU_(-RJ), EM1 is not used. Connect between EM1 and DOCOM externally. Turn EM1 off to bring the resistance regeneration converter unit to a forced stop state. In this state, the magnetic connector is turned off, [AL. E9 Main circuit off warning] occurs in the drive unit, and the servo-on turns off. When the resistance regeneration converter unit is in the forced stop state, turning EM1 on resets the state.

DI

Malfunction ALM CN1-2 ALM turns off when power is switched off or the protective circuit is activated. When no alarm occurs, ALM turns on 1.5 s after power-on.

DO

Warning WNG CN1-8 When warning has occurred, WNG turns on. DO Digital I/F common DOCOM CN1-5

CN1-9 Common terminal for the ALM and WNG output signals of the resistance regeneration converter unit. This is separated from LG. Pins are connected internally. For sink interface, connect - of 24 V DC external power supply. For source interface, connect + of 24 V DC external power supply.

Magnetic contactor drive output

MC1 CNP1-1 Connect it to the coil of the magnetic contactor. Always supplies the control circuit power since it is conducted with L11 in the resistance regeneration converter unit.

WARNING

Always connect the magnetic contactor wiring connector to CNP1 of the resistance regeneration converter unit. Disconnected state may cause an electric shock.

MC2 CNP1-2 Connect it to the coil of the magnetic contactor. When the resistance

regeneration converter unit receives a start command from the drive unit, CNP1-2 and L21 are shorted, and the control circuit power is supplied to the magnetic contactor. Set "_ _ _ 0" in [Pr. PA02] when controlling the magnetic contactor without magnetic contactor control connector (CNP1). (Refer to section 4.3.1 (1).)

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 30

4.3.5 Alarm occurrence timing chart

CAUTION

When an alarm has occurred, remove its cause, make sure that the operation signal is not begin inputted, ensure safety, and reset the alarm before restarting operation. As soon as an alarm occurs, make the Servo-off status and interrupt the main circuit power.

(1) MR-J4-DU_B_(-RJ)

(a) When magnetic contactor drive output is enabled 1) Resistance regeneration converter unit

When an alarm occurs in the resistance regeneration converter unit, the magnetic contactor is turned off and the main circuit magnetic contactor is shut off. The drive unit in operation stops. To deactivate the alarm, cycle the control circuit power or request the operation from the driver unit. However, the alarm cannot be deactivated unless its cause is removed.

2)

Drive unit Control circuit power supply

Main circuit power supply

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Servo-on command (from servo system controller)

Drive unit Alarm

Reset command (from servo system controller)

Base circuit

No alarmAlarmNo alarm 1.5 s

Resistance regeneration converter unit Alarm

No alarmNo alarm Alarm No alarm

(3 s) (3 s)

1) 4)

Alarm occurrence

Alarm

Alarm occurrence

3)

Resistance regeneration converter unit Control circuit power supply

1) in figure When the drive unit is at servo-off, even if an alarm occurs in the resistance regeneration converter unit, the drive unit does not detect the alarm.

2) and 3) in figure To deactivate the alarm of the resistance regeneration converter unit, cycle the power

of the resistance regeneration converter unit (2)), or turn on the servo-on command (3)). Refer to section 6.1 for the alarms that can be reset with the servo-on command on.

4) in figure If an alarm occurs in the resistance regeneration converter unit when the drive unit is

at servo-on, the alarm also occurs in the drive unit and the drive unit becomes servo- off.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 31

2) Drive unit

When an alarm occurs on the drive unit, the base circuit is shut off and the servo motor coasts. When an external dynamic brake is used, the external dynamic brake is activated to stop the servo motor. To deactivate the alarm, cycle the control circuit power, or give the error reset or CPU reset command from the servo system controller. However, the alarm cannot be deactivated unless its cause is removed.

Drive unit Control circuit power supply

Main circuit power supply

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Servo-on command (from controller)

Drive unit Alarm

Reset command (from controller)

Base circuit

No alarmAlarmNo alarm 1.5 s

Resistance regeneration converter unit Alarm

No alarm

(3 s) (3 s)

Alarm occurrence

1) 1)

Resistance regeneration converter unit Control circuit power supply

1) in figure After the start-up of the drive unit is completed, the main circuit power is supplied while the drive unit and the resistance regeneration converter unit have no alarm.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 32

(b) When magnetic contactor drive output is disabled

1) Resistance regeneration converter unit When an alarm occurs in the resistance regeneration converter unit, the resistance regeneration converter unit turns into servo-off, but the main circuit power supply is not shut off. Therefore, shut off the main circuit power supply using the external sequence. Cancel the alarm in the resistance regeneration converter unit. If an alarm also occurs in the drive unit, cancel the alarm in the drive unit as well. Then, turn on the error reset command from the servo system controller to resume the operation.

2)

Drive unit Control circuit power supply

Main circuit power supply

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Servo-on command (from servo system controller)

Drive unit Alarm

Reset command (from servo system controller)

Base circuit

No alarmAlarmNo alarm 1.5 s

Resistance regeneration converter unit Alarm

No alarmNo alarm Alarm No alarm

(3 s) (3 s)

1) 4)

Alarm occurrence

Alarm

Alarm occurrence

3)

5)

Resistance regeneration converter unit Control circuit power supply

1) in figure When the drive unit is at servo-off, even if an alarm occurs in the resistance regeneration converter unit, the drive unit does not detect the alarm.

2) and 3) in figure To deactivate the alarm of the resistance regeneration converter unit, cycle the power

of the resistance regeneration converter unit (2)), or turn on the servo-on command (3)). Refer to section 6.1 for the alarms that can be reset with the servo-on command on.

4) in figure If an alarm occurs in the resistance regeneration converter unit when the drive unit is

at servo-on, the alarm also occurs in the drive unit and the drive unit becomes servo- off.

5) in figure Shut off the main circuit power supply using the external sequence as soon as an

alarm occurs.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 33

2) Drive unit

When an alarm occurs in the drive unit, the drive unit turns into the servo-off, but the main circuit power supply is not shut off. Therefore, shut off the main circuit power supply using the external sequence. After cancelling the alarm in the drive unit, turn on the error reset command from the servo system controller to resume the operation.

Drive unit Control circuit power supply

Main circuit power supply

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Servo-on command (from servo system controller)

Drive unit Alarm

Reset command (from servo system controller)

Base circuit

No alarmAlarmNo alarm 1.5 s

Resistance regeneration converter unit Alarm

No alarm

(3 s) (3 s)

Alarm occurrence

1) 2)

Resistance regeneration converter unit Control circuit power supply

1) in figure When an alarm occurs in the drive unit, shut off the main circuit power supply using the external sequence.

2) in figure Turn on the main circuit power supply while an alarm in the drive unit is cancelled.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 34

(2) MR-J4-DU_A_(-RJ)

(a) When magnetic contactor drive output is enabled 1) Resistance regeneration converter unit

When an alarm occurs in the resistance regeneration converter unit, the magnetic contactor is turned off and the main circuit magnetic contactor is shut off. The drive unit in operation stops. To deactivate the alarm, cycle the control circuit power. However, the alarm cannot be deactivated unless its cause is removed.

Drive unit Control circuit power supply

Main circuit power supply

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

SON (servo-on)

Drive unit Alarm

RES (reset)

Base circuit

No alarmAlarmNo alarm 1.5 s

50 ms or more

Resistance regeneration converter unit Alarm

No alarmNo alarm Alarm No alarm

(3 s)

Alarm occurrence

Alarm

2)

3)1)

Alarm occurrence

4)

Resistance regeneration converter unit Control circuit power supply

1) in figure When the drive unit is at servo-off, even if an alarm occurs in the resistance regeneration converter unit, the drive unit does not detect the alarm.

2) in figure To deactivate the alarm of the resistance regeneration converter unit, cycle the power

of the resistance regeneration converter unit. 3) in figure If an alarm occurs in the resistance regeneration converter unit when the drive unit is

at servo-on, the alarm also occurs in the drive unit and the drive unit becomes servo- off.

4) in figure When alarms occur in both the resistance regeneration converter unit and the drive

unit, cancelling the alarm in the drive unit will also cancel the alarm in the resistance regeneration converter unit.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 35

2) Drive unit

When an alarm occurs in the drive unit, the base circuit is shut off and the servo motor coasts. When an external dynamic brake (option) is used, the external dynamic brake is activated to stop the servo motor. To deactivate an alarm, cycle the control circuit power, click "SET" in the current alarm window, or cycle the RES (Reset). However, the alarm cannot be deactivated unless its cause is removed.

Drive unit Control circuit power supply

Main circuit power supply

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

SON (servo-on)

Drive unit Alarm

RES (reset)

Base circuit

No alarmAlarmNo alarm 1.5 s

50 ms or more

Resistance regeneration converter unit Alarm

No alarm

(95 ms) (3 s)

Alarm occurrence

1) 1)

Resistance regeneration converter unit Control circuit power supply

1) in figure After the start-up of the drive unit is completed, the main circuit power is supplied while the drive unit and the resistance regeneration converter unit have no alarm.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 36

(b) When magnetic contactor drive output is disabled

1) Resistance regeneration converter unit When an alarm occurs in the resistance regeneration converter unit, the resistance regeneration converter unit turns into servo-off, but the main circuit power supply is not shut off. Therefore, shut off the main circuit power supply using the external sequence. Cancel the alarm in the resistance regeneration converter unit. If an alarm also occurs in the drive unit, cancel the alarm in the drive unit as well. Then, turn on the RES (Reset) to resume the operation.

Drive unit Control circuit power supply

Main circuit power supply

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

SON (servo-on)

Drive unit Alarm

RES (reset)

Base circuit

No alarmAlarmNo alarm 1.5 s

50 ms or more

Resistance regeneration converter unit Alarm

No alarmNo alarm Alarm No alarm

(3 s)

Alarm occurrence

Alarm

Alarm occurrence

4)

1)

3)

2) 1)

5) 6)

2)

Resistance regeneration converter unit Control circuit power supply

1) in figure When an alarm occurs in the resistance regeneration converter unit, shut off the main circuit power supply using the external sequence.

2) in figure Turn on the main circuit power supply while an alarm in the drive unit is cancelled. 3) in figure When the drive unit is at servo-off, even if an alarm occurs in the resistance

regeneration converter unit, the drive unit does not detect the alarm. 4) in figure To deactivate the alarm of the resistance regeneration converter unit, cycle the power

of the resistance regeneration converter unit. 5) in figure If an alarm occurs in the resistance regeneration converter unit when the drive unit is

at servo-on, the alarm also occurs in the drive unit and the drive unit becomes servo- off.

6) in figure When alarms occur in both the resistance regeneration converter unit and the drive

unit, cancelling the alarm in the drive unit will also cancel the alarm in the resistance regeneration converter unit.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 37

2) Drive unit

When an alarm occurs in the drive unit, the drive unit turns into the servo-off, but the main circuit power supply is not shut off. Therefore, shut off the main circuit power supply using the external sequence. After cancelling the alarm in the drive unit, turn on the RES (Reset) to resume the operation.

Drive unit Control circuit power supply

Main circuit power supply

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

SON (servo-on)

Drive unit Alarm

RES (reset)

Base circuit

No alarmAlarmNo alarm 1.5 s

50 ms or more

Resistance regeneration converter unit Alarm

No alarm

(95 ms) (3 s)

Alarm occurrence

1) 2)

Resistance regeneration converter unit Control circuit power supply

1) in figure When an alarm occurs in the drive unit, shut off the main circuit power supply using the external sequence.

2) in figure Turn on the main circuit power supply while an alarm in the drive unit is cancelled.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 38

4.3.6 Forced stop in the resistance regeneration converter unit

(1) MR-J4-DU_B_(-RJ) (a) When magnetic contactor drive output is enabled

When EM1 (Forced stop) is disabled in the resistance regeneration converter unit, the magnetic contactor turns off and the main circuit power supply shuts off. The drive unit in operation stops, and [AL. E9 Main circuit off warning] appears. When EM1 is enabled in the resistance regeneration converter unit, the magnetic contactor turns on, the main circuit power is supplied, and then the drive unit automatically resumes the operation.

Dynamic brake

MBR (Electromagnetic brake interlock)

(50 ms) (Note 2)

Base circuit

Servo motor speed

Converter main circuit off warning

Existence

Nothing

Main circuit power supply

ON

OFF

EM1 (forced stop) ON

OFF (Enabled)

(3 s)

(3 s)

2)

2)

1)

ON

OFF

(Note 1) ON

OFF

Note 1. When setting up an electromagnetic brake at customer's side, make up a sequence which will operate the electromagnetic brake as follow using MBR. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. There is delay caused by magnetic contactor built into the external dynamic brake (about 50 ms) and delay caused by the external relay.

1) in figure When EM1 is enabled in the resistance regeneration converter unit, the main circuit

power is supplied. 2) in figure After the capacitor in the main circuit is fully charged, the base circuit and MBR

(Electromagnetic brake interlock) turn on.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 39

(b) When magnetic contactor drive output is disabled

When EM1 (Forced stop) is disabled in the resistance regeneration converter unit, the base circuit of the drive unit that is in operation shuts off, and [AL. E9 Main circuit off warning] appears on the drive unit. When EM1 is enabled in the resistance regeneration converter unit, the drive unit automatically resumes the operation.

Dynamic brake

MBR (Electromagnetic brake interlock)

(50 ms) (Note 2)

(Note 1) ON

OFF

Base circuit ON

OFF

Servo motor speed

Converter main circuit off warning

Existence

Nothing

Main circuit power supply

ON

OFF

EM1 (forced stop) ON

OFF (Enabled)

(3 s)

(3 s)

1)

Note 1. When setting up an electromagnetic brake at customer's side, make up a sequence which will operate the electromagnetic brake as follow using MBR. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. There is delay caused by magnetic contactor built into the external dynamic brake (about 50 ms) and delay caused by the external relay.

1) in figure When EM1 is enabled, the converter main circuit off warning is released.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 40

(2) MR-J4-DU_A_(-RJ)

(a) When magnetic contactor drive output is enabled When EM1 (Forced stop) is disabled in the resistance regeneration converter unit, the magnetic contactor turns off and the main circuit power supply shuts off. The drive unit in operation stops, and [AL. E9 Main circuit off warning] appears. When EM1 is enabled in the resistance regeneration converter unit, the magnetic contactor turns on, the main circuit power is supplied, and then the drive unit automatically resumes the operation.

Dynamic brake

MBR (Electromagnetic brake interlock)

(50 ms)

(Note 1) ON

OFF

Base circuit ON

OFF

Servo motor speed

Converter main circuit off warning

Existence

Nothing

Main circuit power supply

ON

OFF

EM1 (forced stop) ON

OFF (Enabled)

(3 s)

(3 s)

(Note 2)

2)

2)

1)

Note 1. When setting up an electromagnetic brake at customer's side, make up a sequence which will operate the electromagnetic brake as follow using MBR. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. There is delay caused by magnetic contactor built into the external dynamic brake (about 50 ms) and delay caused by the external relay.

1) in figure When EM1 is enabled in the resistance regeneration converter unit, the main circuit

power is supplied. 2) in figure After the capacitor in the main circuit is fully charged, the base circuit and MBR

(Electromagnetic brake interlock) turn on.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 41

(b) When magnetic contactor drive output is disabled

When EM1 (Forced stop) is disabled in the resistance regeneration converter unit, the base circuit of the drive unit that is in operation shuts off, and [AL. E9 Main circuit off warning] appears on the drive unit. When EM1 is enabled in the resistance regeneration converter unit, the drive unit automatically resumes the operation.

MBR (Electromagnetic brake interlock)

(Note 1) ON

OFF

Base circuit ON

OFF

Servo motor speed

Converter main circuit off warning

Existence

Nothing

Main circuit power supply

ON

OFF

EM1 (forced stop) ON

OFF (Enabled)

(50 ms) (3 s)

(3 s)

Dynamic brake

(Note 2)

1)

Note 1. When setting up an electromagnetic brake at customer's side, make up a sequence which will operate the electromagnetic brake as follow using MBR. ON: Electromagnetic brake is not activated. OFF: Electromagnetic brake is activated.

2. There is delay caused by magnetic contactor built into the external dynamic brake (about 50 ms) and delay caused by the external relay.

1) in figure When EM1 is enabled, the converter main circuit off warning is released.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 42

4.3.7 Interfaces

(1) Detailed explanation of interfaces This section provides the details of the I/O signal interfaces (refer to the I/O division in the table) given in section 4.3.4. Refer to this section and make connections to the external device.

(a) Digital input interface DI

This is an input circuit in which the cathode of the photocoupler is the input terminal. Transmit signals from sink (open-collector) type transistor output, relay switch, etc. The following shows a connection diagram for sink input. Refer to (2) in this section for source input.

10%

Approx. 6.2 k

Approx. 5 mA

VCES 1.0 V ICEO 100 A

TR

24 V DC 150 mA

Switch

For transistor EM1 etc.

DICOM

Resistance regeneration converter unit

(b) Digital output interface DO This is a circuit in which the collector of the output transistor is the output terminal. When the output transistor is turned on, the current will flow to the collector terminal. A lamp, relay, or photocoupler can be driven. Install a diode (D) for an inductive load, or install an inrush current suppressing resistor (R) for a lamp load. (Rated current: 40 mA or less, maximum current: 50 mA or less, inrush current: 100 mA or less) A maximum of 2.6 V voltage drop occurs in the resistance regeneration converter unit. The following shows a connection diagram for sink output. Refer to (2) in this section for source output.

(Note) 24 V DC 10% 150 mA

If polarity of diode is reversed, resistance regeneration converter unit will malfunction.ALM,

etc. Load

DOCOM

Resistance regeneration converter unit

Note. If the voltage drop (maximum of 2.6 V) interferes with the relay operation, apply high voltage (maximum of 26.4 V) from external source.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 43

(2) Source I/O interfaces

In this resistance regeneration converter unit, source type I/O interfaces can be used.

(a) Digital input interface DI This is an input circuit in which the anode of the photocoupler is the input terminal. Transmit signals from source (open-collector) type transistor output, relay switch, etc.

Approx. 6.2 k

10% VCES 1.0 V ICEO 100 A

24 V DC 150 mA

Approx. 5 mA

Switch

DICOM

TR

For transistor

EM1 etc.

Resistance regeneration converter unit

(b) Digital output interface DO This is a circuit in which the emitter of the output transistor is the output terminal. When the output transistor is turned on, the current will flow from the output terminal to a load. A maximum of 2.6 V voltage drop occurs in the resistance regeneration converter unit.

ALM, etc.

DOCOM

Load

(Note) 24 V DC 10% 150 mA

If polarity of diode is reversed, resistance regeneration converter unit will malfunction.

Resistance regeneration converter unit

Note. If the voltage drop (maximum of 2.6 V) interferes with the relay operation, apply high voltage (maximum of 26.4 V) from external source.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 44

4.3.8 Grounding

WARNING

Ground the resistance regeneration converter unit, the drive unit and the servo motor securely. To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the resistance regeneration converter unit and drive unit to the protective earth (PE) of the cabinet.

The drive unit switches the power transistor on-off to supply power to the servo motor. Depending on the wiring and ground cable routing, the drive unit may be affected by the switching noise (due to di/dt and dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always ground. To conform to "EMC Directive, refer to the EMC Installation Guidelines".

Ensure to connect it to PE terminal of the drive unit. Do not connect the wire directly to the protective earth of the cabinet.

Li ne

fi lte

r

(Note) Power supply

V

U

Cabinet

Servo motor

M U V WW

Encoder

CN2

Drive unit

L11

L1

L2

L3

L21

Protective earth (PE) Outer box

MCMCCB

Resistance regeneration converter unit

L+

L- CN40 CN40A

L11

L21

L+

L- C

on tro

lle r

Note. Refer to section 1.4 for the power supply specifications.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 45

4.4 Startup

WARNING

Do not operate the switches with wet hands. Otherwise, it may cause an electric shock.

CAUTION

Before starting operation, check the parameters. Improper settings may cause some machines to operate unexpectedly. The heat sink of the resistance regeneration converter unit and the drive unit, the regenerative resistor, the servo motor, etc. may become hot while power is on or for some time after power-off. Take safety measures, such as providing covers, to avoid accidentally touching the parts (cables, etc.) by hand. During operation, never touch the rotor of the servo motor. Otherwise, it may cause injury.

The following items are the same as those of the MR-J4-_(-RJ). For details of the items, refer to each chapter/section of the detailed explanation field. Read the corresponding section or chapter by replacing "servo amplifier" to "drive unit". "MR-J4-_B_" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

Model Item Detailed explanation MR-J4-DU_B_(-RJ) Switch setting and display of the servo amplifier MR-J4-_B_ section 4.3 Test operation MR-J4-_B_ section 4.4 Test operation mode MR-J4-_B_ section 4.5 MR-J4-DU_A_(-RJ) Display and operation section MR-J4-_A_ section 4.5

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 46

4.4.1 Switching power on for the first time

When switching the power on for the first time, follow this section to startup. (1) Startup procedure

(a) MR-J4-DU_B_(-RJ) "MR-J4-_B_" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

Wiring check

Surrounding environment check

Axis No. settings

Parameter setting

Test operation of servo motor alone in test operation mode

Test operation of servo motor alone by commands

Test operation with servo motor and machine connected

Gain adjustment

Actual operation

Stop

Description Reference Check whether the resistance regeneration converter unit, the drive unit, and the servo motor are wired correctly using visual inspection, DO forced output function, etc.

(2) in this section

Check the surrounding environment of the resistance regeneration converter unit, the drive unit and the servo motor.

MR-J4-_B_ Section 4.1.3

Confirm that the control axis No. set with the auxiliary axis number setting switches (SW2-3 and SW2-4) and with the axis selection rotary switch (SW1) match the control axis No. set with the servo system controller.

MR-J4-_B_ Section 4.3.1

(3)

Set the parameters as necessary, such as the used operation mode and regenerative option selection.

Section 4.5 Section 5.3

For the test operation, disconnect the servo motor from the machine, and check whether the servo motor rotates correctly at the slowest speed.

MR-J4-_B_ Section 4.5

For the test operation, disconnect the servo motor from the machine, give commands to the drive unit, and check whether the servo motor rotates correctly at the lowest speed.

Connect the servo motor with the machine, and check machine motions by transmitting operation commands from the servo system controller.

Make gain adjustment to optimize the machine motions. MR-J4-_B_ Chapter 6

Stop giving commands and stop operation.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 47

(b) MR-J4-DU_A_(-RJ)

"MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

Wiring check

Parameter setting

Test operation of servo motor alone in test operation mode

Test operation of servo motor alone by commands

Test operation with servo motor and machine connected

Gain adjustment

Actual operation

Stop

Surrounding environment check

Description Reference Check whether the resistance regeneration converter unit, the drive unit, and the servo motor are wired correctly using visual inspection, DO forced output function, etc.

(2) in this section

Check the surrounding environment of the resistance regeneration converter unit, the drive unit and the servo motor.

MR-J4-_A_ Section 4.1.3

Set the parameters as necessary, such as the used operation mode and regenerative option selection.

Section 4.5

For the test operation, disconnect the servo motor from the machine, and check whether the servo motor rotates correctly at the slowest speed.

MR-J4-_A_ Section 4.2.3 Section 4.3.3 Section 4.4.3

For the test operation, disconnect the servo motor from the machine, give commands to the drive unit, and check whether the servo motor rotates correctly at the lowest speed.

Connect the servo motor with the machine, and check machine motions by transmitting operation commands from the controller.

Make gain adjustment to optimize the machine motions. MR-J4-_A_ Chapter 6

Stop giving commands and stop operation.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 48

(2) Wiring check

(a) Power supply system wiring Before turning on the power supplies of the main circuit and the control circuit, check the following items.

1) Power supply system wiring

a) The power supplied to the resistance regeneration converter unit power input terminals (L1/L2/L3/L11/L21) and the drive unit power input terminals (L11/L21) should satisfy the defined specifications. (Refer to section 1.4.)

b) When magnetic contactor drive output is enabled, the magnetic contactor control connector

(CNP1) should be connected to the coil of the magnetic contactor.

c) When the power factor improving DC reactor is not used, P1 and P2 in the resistance regeneration converter unit should be connected.

P1

P2

Resistance regeneration converter unit

2) Connection of drive unit and servo motor a) The drive unit power outputs (U/V/W) should match in phase with the servo motor power input

terminals (U/V/W). Drive unit Servo motor

M

U

V

W

U

V

W

b) The power supplied to the resistance regeneration converter unit should not be connected to the drive unit power outputs (U/V/W). Doing so will fail the connected drive unit and servo motor.

Drive unit Servo motor

M

U

V

W

U

V

W

c) The grounding terminal of the servo motor is connected to the PE terminal of the drive unit. Drive unit Servo motor

M

d) The CN2 connector of the drive unit should be connected to the encoder of the servo motor securely by using the encoder cable.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 49

3) When using options and peripheral equipment

a) When using a regenerative option The regenerative option should be connected to P+ and C terminals of the resistance regeneration converter unit. A twisted wire should be used. (Refer to section 8.2.4.)

b) When using a brake unit

The brake unit should be connected to L+ and L- terminals of TE2-1 of the resistance regeneration converter unit. (Refer to section 8.11.3.) A twisted wire should be used for the wiring over 5 m and equal to or less than 10 m when the brake unit is used. (Refer to section 8.11.3.)

c) The power factor improving DC reactor should be connected between P1 and P2 of the

resistance regeneration converter unit. (Refer to section 8.6.)

(Note)

Power factor improving DC

reactor P1

P2

Resistance regeneration converter unit

Note. Always disconnect wiring between P1 and P2.

(b) I/O signal wiring

1) Resistance regeneration converter unit a) The I/O signals should be connected correctly.

Use DO forced output to forcibly turn on/off the pins of the CN1 connector. You can use this function to check the wiring. In this case, turn on the control circuit power supply only. For details of I/O signal connection, refer to section 4.3.1 (2). For details of DO forced output, refer to section 4.4.3 (4) (c).

b) A voltage exceeding 24 V DC is not applied to the pins of the CN1 connector.

c) Between plate and DOCOM of the CN1 connector should not be shorted.

DOCOM

Plate

CN1

Resistance regeneration converter unit

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 50

2) Drive unit

a) MR-J4-DU_A_(-RJ) The I/O signals should be connected correctly. Use DO forced output to forcibly turn on/off the pins of the CN1 connector. You can use this function to check the wiring. In this case, turn on the control circuit power supply only. For details of I/O signal connection, refer to section 3.2 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual". For details of DO forced output, refer to section 4.5.8 of "MR-J4-_A_(- RJ) Servo Amplifier Instruction Manual".

A voltage exceeding 24 V DC is not applied to the pins of the CN1 connector.

Between plate and DOCOM of the CN1 connector should not be shorted.

Drive unit

DOCOM

Plate

CN1

b) MR-J4-DU_B_(-RJ) The I/O signals should be connected correctly. Use DO forced output to forcibly turn on/off the pins of the CN3 connector. You can use this function to check the wiring. In this case, turn on the control circuit power supply only. For details of I/O signal connection, refer to section 3.2 of "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". For details of DO forced output, refer to section 4.5.1 of "MR-J4-_B_(- RJ) Servo Amplifier Instruction Manual".

A voltage exceeding 24 V DC is not applied to the pins of the CN3 connector.

Between plate and DOCOM of the CN3 connector should not be shorted.

Drive unit

DOCOM

Plate

CN3

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 51

4.4.2 Startup

(1) MR-J4-DU_A_(-RJ) Startup of the MR-J4-DU_A_(-RJ) is the same as that of the MR-J4-_A_(-RJ). For details, refer to section 4.2 to 4.4 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual". The resistance regeneration converter unit display shows "ron" (ready-on) at power-on. When an error occurs or EM1 (Forced stop) is disabled in the resistance regeneration converter unit, the operation will stop.

(2) MR-J4-DU_B_(-RJ)

Startup of the MR-J4-DU_B_(-RJ) is the same as that of the MR-J4-_B_(-RJ). For details, refer to section 4.2 of "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". The resistance regeneration converter unit display shows "roF" (ready-off) at power-on. When an error occurs or EM1 (Forced stop) is disabled in the resistance regeneration converter unit, the operation will stop.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 52

4.4.3 Display and operation section of the resistance regeneration converter unit

(1) Display flowchart The resistance regeneration converter unit has the display (3-digit, 7-segment LED) and the operation section (4 pushbuttons) for resistance regeneration converter unit status display, alarm display, parameter setting, etc. Set the parameters before operation, diagnose an alarm, confirm external sequences, and/or confirm the operation status. The following shows the operation procedure after power-on.

Current alarm

Sixth alarm in past

DOWN

Status display

UP

MODE Button

Alarm Basic parameters

Effective load ratio [%]

Peak load ratio [%]

Bus voltage [V]

First alarm in past [Pr. PA02]

[Pr. PA01]

Parameter error No. [Pr. PA19]

[Pr. PA18]

External I/O signal display

Output signal (DO) forced output

Diagnostic

Software version - Upper

Software version - Lower

Regenerative load ratio [%]

Status

(Note 1)

(Note 1)

(Note 1)

(Note 1)

Unit power consumption 1 [kW] (Note 2)

Unit total power consumption 1 [kWh]

Unit total power consumption 2 [MWh]

Note 1. When a parameter is selected, the parameter group and the parameter No. are displayed alternately. Refer to (6) in this section for details.

2. The unit of unit power consumption 1 can be changed with [Pr. PA15].

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 53

(2) Display transition of the resistance regeneration converter unit/MR-J4-DU_B_(-RJ) drive unit

The following shows the display transition of the resistance regeneration converter unit in which the protection coordination is enabled and MR-J4-DU_B_(-RJ) drive unit.

Ready-off

Ready-on

Ready-on

Ready-on, Servo-off

Resistance regeneration converter unit Display

MR-J4-DU_B_(-RJ) drive unit Display (Note)

Ready-off, Servo-off

Ready-on, Servo-on

Ordinary operation Ordinary operation

Magnetic contactor on

Charging completed

Servo-on

Note. For the detailed display transition of the drive unit, refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 54

(3) Status display mode

The resistance regeneration converter unit status during operation is shown on the 3-digit, 7-segment LED display. Press the "UP" or "DOWN" button to change display data as desired. When the required data is selected, the corresponding symbol is displayed. Press the "SET" button to display that data.

(a) Display examples

The following table shows the display examples.

Item State Displayed data

Status

Ready-off

Ready-on

Bus voltage 300 [V]

Effective load ratio 67 [%]

Peak load ratio 95 [%]

Regenerative load ratio 90 [%]

(b) Status display list

The following table lists the resistance regeneration converter unit statuses that may be displayed.

Status display Symbol Unit Description Indication range

Status

Ready -off Ready-off is displayed during initialization or alarm occurrence, in the

external forced stop status, or when the bus voltage is not established. roF

Ready -on

Ready-on is displayed when the servo was switched on after completion of initialization and the resistance regeneration converter unit is ready to operate.

ron

Bus voltage Pn V The bus voltage is displayed. 0 to 999 Effective load ratio J % The effective load ratio in the past 15 s is displayed relative to the rated load

of 100%. 0 to 300

Peak load ratio b % The peak load ratio in the past 15 s is displayed relative to the rated load of 100%. 0 to 400

Regenerative load ratio L % The ratio of regenerative power to permissible regenerative power is

displayed in %. 0 to 300

Unit power consumption 1 PC1 kW (Note) Unit power consumption is displayed by increment of 1 kW or 0.1 kW. 0 to 999

Unit total power consumption 1 TP1 kWh Unit total power consumption is displayed by increment of 1 kWh. 0 to 999

Unit total power consumption 2 TP2 MWh Unit total power consumption is displayed by increment of 1 MWh. 0 to 999

Note. The unit of unit power consumption 1 can be changed with [Pr. PA15].

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 55

(4) Diagnostic mode

(a) Diagnostic list

Name Display Description

External I/O signal display Indicates the on/off status of external I/O signal. Refer to (3) (b) in this section for details.

Output signal (DO) forced output Indicates that the digital output signal can be switched on/off forcibly. Refer to (3) (c) in this section for details.

Software version - Lower Indicates the version of the software.

Software version - Upper Indicates the system number of the software.

(b) External I/O signal display

The on/off states of the digital I/O signals connected to the resistance regeneration converter unit can be confirmed.

1) Operation

The following shows the display screen at power-on. Using the "MODE" button, display the diagnostic screen.

External I/O signal display screen

Press MODE once.

2) Display definition The LED segment corresponding to the pin is lit to indicate on, and is extinguished to indicate off. The 7-segment LED segments and CN1 connector pins correspond as shown below.

CN1-7: EM1 (Forced stop 1)

CN1-2: ALM (Malfunction)CN1-8: WNG (Warning)

Light on: on Light off: off

Input signal

Output signals

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 56

(c) Output signal (DO) forced output

Output signals can be forcibly switched on/off independently of the resistance regeneration converter unit status. Use this function for checking output signal wiring, etc. The following shows the display screen at power-on. When turning CN1-8 on and off

External I/O signal display screen

Press SET for longer than 2 s.

CN1-8

CN1-8 CN1-2

Press MODE once.

Press UP once.

Switch on/off the signal below the lit segment.

Indicates on/off of output signal. (Light on: on, light off: off)

Press MODE once.

The lit LED moves to the upper LED of CN1-8.

Press UP once.

CN1-8 switches on. (Between CN1-8 and DOCOM are connected.)

Press DOWN once.

CN1-8 switches off.

Press SET for longer than 2 s.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 57

(5) Alarm mode

The current alarm, past alarm history, and parameter error are displayed. The lower 2 digits on the display indicate the alarm number that has occurred or the parameter number in error.

Name Display Description

Current alarm

Indicates no occurrence of an alarm.

Indicates that [AL. 33 Overvoltage] occurred. Blinks at alarm occurrence.

Indicates that the last alarm is [AL. 50 Overload 1].

Indicates that the second alarm in the past is [AL. 33 Undervoltage].

Alarm history

Indicates that the third alarm in the past is [AL. 10 Undervoltage].

Indicates that the fourth alarm in the past is [AL. 10 Undervoltage].

Indicates that the fifth alarm in the past is [AL. 10 Undervoltage].

Indicates that the sixth alarm in the past is [AL. 50 Overload 1].

Parameter error No.

Indicates no occurrence of [AL. 37 Parameter error].

Displayed alternately Indicates that the data of [Pr. PA01 Regenerative option] is

faulty.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 58

Functions at alarm occurrence (a) Any mode screen displays the current alarm.

(b) Even during alarm occurrence, the other screen can be viewed by pressing the button in the

operation area. At this time, the decimal point in the third digit remains blinking.

(c) For any alarm, remove its cause and clear it in any of the following methods. (Refer to chapter 6 for the alarms that can be cleared.)

1) Switch power off, then on.

2) Press the "SET" button on the current alarm screen.

(d) Use [Pr. PA09] to clear the alarm history.

(6) Parameter mode

POINT The display of the resistance regeneration converter unit has three digits. When a parameter No. is displayed, the parameter group and the parameter No. are displayed alternately. For example, when [Pr. PA01] is displayed, "PA" and "01" are displayed alternately.

The following example shows how to select MR-RB137 in [Pr. PA01 Regenerative option] after power- on.

Displayed alternately

( _ _ _ 2: MR-RB137 (3 pcs.) are used.)

(Note)

Press MODE three times. The parameter number is displayed. For [Pr. PA01], "PA" and "01" are displayed alternately.

Press UP or DOWN to change the number.

Press MODE twice. The set value of the specified parameter number blinks. In this case, the lower three digits of the setting value "0 0 0 0" are displayed.

Press MODE once. During blinking, the set value can be changed.

Use UP or DOWN. When a negative value is set, the decimal point blinks.

Press SET to enter.

Note. When the lower three digits of the four digits are displayed, pressing the "MODE" button displays the fourth digit. However, do not change the setting of the fourth digit. Pressing the "MODE" button again resets the display to the lower three digits.

To shift to the next parameter, press the "UP" or "DOWN" button. When changing the [Pr. PA01] setting, change its setting value, and then cycle the power to enable the new value.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 59

4.5 Parameters

CAUTION

Never make a drastic adjustment or change to the parameter values as doing so will make the operation unstable. Do not change the parameter settings as described below. Doing so may cause an unexpected condition, such as failing to start up the resistance regeneration converter unit.

Changing the values of the parameters for manufacturer setting. Setting a value out of the range. Changing the fixed values in the digits of a parameter.

4.5.1 Parameter list

POINT To enable a parameter whose symbol is preceded by *, cycle the power after setting it.

No. Symbol Name Initial value Unit

PA01 *REG Regenerative option 0000h PA02 *MCC Magnetic contactor drive output selection 0001h PA03

For manufacturer setting 0001h

PA04 0 PA05 100 PA06 0 PA07 100 PA08 *DMD Status display selection 0000h PA09 *BPS Alarm history clear 0000h PA10

For manufacturer setting 0

PA11 0000h PA12 *DIF Input filter setting 0002h PA13

For manufacturer setting 0000h

PA14 0000h PA15 AOP3 Function selection A-3 0000h PA16 For manufacturer setting 0000h PA17 *AOP5 Function selection A-5 0001h PA18 CVAT SEMI-F47 function - Instantaneous power failure detection time 200 [ms] PA19 For manufacturer setting 0000h

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 60

4.5.2 Detailed list of parameters

POINT Set a value to each "x" in the "Setting digit" columns.

No./symbol/

name Setting

digit Function Initial value [unit]

PA01 *REG Regenerative option

_ _ x x Regenerative option Select a regenerative option. Incorrect setting will trigger [AL. 37 Parameter error]. 00: Regenerative option is not used.

When using the FR-BU2-(H) brake unit, select the value. 01: MR-RB139 02: MR-RB137 (3 pcs.) 13: MR-RB137-4 14: MR-RB13V-4 (3 pcs.)

00h

_ x _ _ For manufacturer setting 0h x _ _ _ 0h

PA02 *MCC Magnetic contactor drive output selection

_ _ _ x Magnetic contactor drive output selection Select the magnetic contactor drive output. 0: Disabled 1: Enabled

1h

_ _ x _ For manufacturer setting 0h

_ x _ _ 0h x _ _ _ 0h PA08 *DMD Status display selection

_ _ _ x Status display selection Select a status display shown at power-on. 0: Status 1: Bus voltage 2: Effective load ratio 3: Peak load ratio 4: Regenerative load ratio 5: Unit power consumption 1 6: Unit total power consumption 1 7: Unit total power consumption 2

0h

_ _ x _ For manufacturer setting 0h _ x _ _ 0h x _ _ _ 0h PA09 *BPS Alarm history clear

_ _ _ x Alarm history clear Used to clear the alarm history. 0: Disabled 1: Enabled When you select "Enabled", the alarm history will be cleared at next power-on. After the alarm history is cleared, the setting is automatically disabled.

0h

_ _ x _ For manufacturer setting 0h _ x _ _ 0h x _ _ _ 0h

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 61

No./symbol/

name Setting

digit Function Initial value [unit]

PA12 *DIF Input filter setting

_ _ _ x Input filter setting Select the input filter. If external input signal causes chattering due to noise, etc., input filter is used to suppress it. 0: None 1: 1.777 [ms] 2: 3.555 [ms] 3: 5.333 [ms]

2h

_ _ x _ For manufacturer setting 0h _ x _ _ 0h x _ _ _ 0h PA15 AOP3 Function selection A-3

_ _ _ x Selection of unit power consumption display unit 0: increment of 1 kW 1: increment of 0.1 kW

0h

_ _ x _ For manufacturer setting 0h _ x _ _ 0h x _ _ _ 0h PA17 *AOP5 Function selection A-5

The [Pr. PA17 SEMI-F47 function selection] and [Pr. PA18 SEMI-F47 function - Instantaneous power failure detection time] settings of the resistance regeneration converter unit must be the same as [Pr. PA20 SEMI-F47 function selection] and [Pr. PF25 SEMI-F47 function - Instantaneous power failure detection time] settings of the drive unit. _ _ _ x [AL. 10 Undervoltage] detection method selection

Set this parameter when [AL. 10] occurs due to distorted power supply voltage waveform. 0: [AL. 10] not occurrence 1: [AL. 10] occurrence

1h

_ _ x _ SEMI-F47 function selection 0: Disabled 1: Enabled Selecting "1" enables to avoid triggering [AL. 10 Undervoltage] using the electrical energy charged in the capacitor in case that an instantaneous power failure occurs during operation. In [Pr. PA18 SEMI-F47 function - Instantaneous power failure detection time], set the time until the occurrence of [AL. 10 Undervoltage].

0h

_ x _ _ For manufacturer setting 0h x _ _ _ 0h PA18 CVAT SEMI-F47 function - Instanta- neous power failure detection time

The [Pr. PA17 SEMI-F47 function selection] and [Pr. PA18 SEMI-F47 function - Instantaneous power failure detection time] settings of the resistance regeneration converter unit must be the same as [Pr. PA20 SEMI-F47 function selection] and [Pr. PF25 SEMI-F47 function - Instantaneous power failure detection time] settings of the drive unit.

Set the time until the occurrence of [AL. 10 Undervoltage]. To disable the parameter setting value, select "Disabled (_ _ 0 _)" of "SEMI-F47 function selection" in [Pr. PA17]. Setting range: 30 to 200

200 [ms]

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 62

4.6 Characteristics

4.6.1 Overload protection characteristics

(1) Converter unit An electronic thermal is built in the resistance regeneration converter unit to protect the resistance regeneration converter unit from overloads. [AL. 50 Overload 1] occurs if overload operation performed is above the electronic thermal protection curve shown in the following figure. [AL. 51 Overload 2] occurs if the maximum current is applied continuously for several seconds due to machine collision, etc. [AL. 51 Overload 2] occurs if the maximum current is applied continuously for several seconds due to machine collision, etc. Use the equipment on the left-side area of the graph.

10000

1000

100

10

1 0 100 200 300

Operating

50 150 250

(Note) Load ratio [%]

O pe

ra tio

n tim

e [s

]

Note. Load ratio 100% indicates the rated output of the resistance regeneration converter unit. Refer to section 1.4.2 for rated output.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 63

4.6.2 Power supply capacity and generated loss

(1) Generated heat of the resistance regeneration converter unit/drive unit The following table indicates the generated loss under rated load and the power supply capacity per combination of the resistance regeneration converter unit and drive unit.

Resistance regeneration converter unit

Drive unit

Power supply capacity [kVA] Drive unit-generated heat [W] (Note) Area

required for heat

dissipation [m2]

Power factor improving DC reactor is not

used

Power factor improving DC reactor is used

At rated output

At rated output [Generated heat in the

cabinet when cooled outside

the cabinet]

With servo-off

MR-CR55K MR-J4-DU30K_(-RJ) 48 40 1350 (900 + 450) 470 27.0 MR-J4-DU37K_(-RJ) 59 49 1550 (1000 + 550) 550 31.0

MR-J4-DU30K_4(-RJ) 48 40 1070 (790 + 280) 390 60 (30 + 30)

21.4

MR-CR55K4 MR-J4-DU37K_4(-RJ) 59 49 1252 (910 + 342) 470 25.1 MR-J4-DU45K_4(-RJ) 71 59 1580 (1110 + 470) 550 31.6

MR-J4-DU55K_4(-RJ) 87 72 1940 (1440 + 500) 650 38.8

Note. The heat generated by the drive unit is indicated in the left term within the parentheses, and the heat generated by the resistance regeneration converter unit in the right term.

When the servo motors are run at less than the rated speed, the power supply equipment capacity is lower than the value in the table but the heat generated does not change. Since the servo motor requires 2 times to 2.5 times greater instantaneous power for acceleration, use the power supply which ensures that the voltage lies within the permissible voltage fluctuation at the main circuit power supply terminals (L1/L2/L3) of the resistance regeneration converter unit. The power supply equipment capacity changes with the power supply impedance. The actually generated heat falls within the ranges at rated output and at servo-off according to the frequencies of use during operation. When designing an enclosed cabinet, use the values in the table, considering the worst operating conditions. The generated heat in this table does not include heat produced during regeneration.

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 64

(2) Heat dissipation area for an enclosed type cabinet

The enclosed type cabinet (hereafter called the cabinet) which will contain the resistance regeneration converter unit and drive unit should be designed to ensure that its temperature rise is within +10 C at the ambient temperature of 40 C. (With an approximately 5 C safety margin, the system should operate within a maximum 55 C limit.) The necessary cabinet heat dissipation area can be calculated by next equation.

A = K T P

A: Heat dissipation area [m2] P: Loss generated in the cabinet [W] T: Difference between internal and ambient temperatures [C] K: Heat dissipation coefficient [5 to 6]

When calculating the heat dissipation area with the equation, assume that P is the sum of all losses generated in the cabinet. Refer to (1) in this section for the generated heat of the resistance regeneration converter unit/drive unit. "A" indicates the effective area for heat dissipation, but if the cabinet is directly installed on an insulated wall, that extra amount must be added to the cabinet's surface area. The required heat dissipation area will vary with the conditions in the cabinet. If convection in the cabinet is poor and heat builds up, effective heat dissipation will not be possible. Therefore, arrangement of the equipment in the cabinet and the use of a cooling fan should be considered. The above (1) in this section lists the cabinet dissipation area (guideline) when this unit and drive unit are operated at the ambient temperature of 40 C under rated load. When air flows along the outer wall of the cabinet, effective heat exchange will be possible, because the temperature slope inside and outside the cabinet will be steeper.

(Outside the cabinet) (Inside the cabinet)

Air flow

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 65

4.6.3 Inrush currents at power-on of main circuit/control circuit

POINT The inrush current values can change depending on frequency of turning on/off the power and ambient temperature.

Since large inrush currents flow in the power supplies, always use molded-case circuit breakers and magnetic contactors. (Refer to section 8.5.) When circuit protectors are used, it is recommended that the inertia delay type, which is not tripped by an inrush current, be used. When the converter unit and drive unit are connected by passing wiring, the total inrush current of them flow. (1) 200 V class

The following table indicates the inrush currents (reference data) that will flow when 240 V AC is applied.

Resistance regeneration converter unit

Inrush currents (A0-P) Main circuit power supply

(L1/L2/L3) Control circuit power supply

(L11/L21)

MR-CR55K 154 A (Attenuated to approx. 20 A in 150 ms)

31 A (attenuated to approx. 2 A in 60 ms)

(2) 400 V class

The following table indicates the inrush currents (reference data) that will flow when 480 V AC is applied.

Resistance regeneration converter unit

Inrush currents (A0-P) Main circuit power supply

(L1/L2/L3) Control circuit power supply

(L11/L21)

MR-CR55K4 305 A (attenuated to approx. 20 A in 70 ms)

27 A (attenuated to approx. 2 A in 45 ms)

4. MR-CR_ RESISTANCE REGENERATION CONVERTER UNIT

4 - 66

MEMO

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 1

5. MR-J4-DU_(-RJ) DRIVE UNIT

5.1 Structure (Parts identification)

POINT The drive unit is shown with the terminal cover open. For opening or closing of the terminal cover, refer to section 4.2.2.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 2

5.1.1 MR-J4-DU_B_(-RJ)

"MR-J4-_B_" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". (1) 200 V class

(a) MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ)

(1)(17) (2) (3) (4)

(19)

(12) (16) (12)

(20) (5)

(6) (7) (11) (8) (9) (18) (10)

(14)

(13)

(15)

No. Name/Application Detailed explanation

(1) Display The 3-digit, 7-segment LED display shows the drive unit status and the alarm number.

MR-J4-_B_ Section 4.3 (2) Axis selection rotary switch (SW1)

Set the axis No. of the drive unit.

(3) Control axis setting switch (SW2) The test operation switch, the disabling control axis switch, and the auxiliary axis number setting switch are available.

(4) USB communication connector (CN5) Connect with the personal computer.

MR-J4-_B_ Section 11.7

(5) I/O signal connector (CN3) Connect digital I/O signals.

MR-J4-_B_ Section 3.2 Section 3.4

(6) STO input signal connector (CN8) Connect the MR-J3-D05 safety logic unit and external safety relay.

MR-J4-_B_ Chapter 13

App. 5

(7) SSCNET III cable connector (CN1A) Connect a servo system controller or the previous axis servo amplifier (drive unit). MR-J4-_B_

Section 3.2 Section 3.4 (8)

SSCNET III cable connector (CN1B) Connect the next axis servo amplifier (drive unit). For the final axis, put a cap.

(9) (Note

2)

Encoder connector (CN2) Connect the servo motor encoder or external encoder.

MR-J4-_B_ Section 3.4 "Servo Motor Instruction Manual (Vol. 3)" Section 1.1

(10) Battery connector (CN4) Connect the battery for absolute position data backup.

MR-J4-_B_ Chapter 12

(11) Battery holder Install the battery for absolute position data backup.

MR-J4-_B_ Section 12.2

(12) Protective earth (PE) terminal

Section 5.2.1 (13)

L+/L- terminal (TE2-1) Connect with the L+ and L- terminals of the converter unit or another drive unit by bus bars.

(14) Rating plate Section 1.2

(15) Control circuit terminal L11/L21 (TE3) Connect to the control circuit power supply.

Section 5.2.1 (16) Servo motor power output terminal (TE1)

Connect the servo motor.

(17)

Protection coordination connector (CN40A) For the drive unit adjacent to the converter unit, connect with the CN4 of the power regeneration converter unit or the CN40 of the resistance regeneration converter unit.

(18) (Note

1)

External encoder connector (CN2L) (Note 2) Connect the external encoder.

Section 5.2.2 "Linear Encoder Instruction Manual" Section 1.1

(19)

Optional unit connector (CN7) This connector is attached on the MR-J4-DU_B_-RJ drive unit. Connect an optional unit. The MR-J4-DU_B_ drive unit does not have this connector.

(20)

Optional unit connector (CN9) This connector is attached on the MR-J4-DU_B_-RJ drive unit. Connect an optional unit. The MR-J4-DU_B_ drive unit does not have this connector.

Note 1. This is for the MR-J4-DU_B_-RJ drive unit. The MR-J4-DU_B_ drive unit does not have the CN2L connector. 2. "External encoder" is a term for the linear encoder used in the linear servo system, the load-side encoder used in the fully

closed loop system, and the scale measurement encoder used with the scale measurement function in this manual.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 3

(b) MR-J4-DU15KB(-RJ)/MR-J4-DU22KB(-RJ)

(3)

(4)

(1)

(5)

The broken line area is the same as MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ).

(2)

No. Name/Application Detailed explanation

(1) Control circuit terminal L11/L21 (TE3) Connect to the control circuit power supply.

Section 5.2.1 (2) Servo motor power output terminal (TE1)

Connect the servo motor. (3) Rating plate Section 1.2

(4) L+/L- terminal (TE2-1) Connect with the L+ and L- terminals of the converter unit or another drive unit by bus bars.

Section 5.2.1

(5) Protective earth (PE) terminal Section 5.2.1

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 4

(c) MR-J4-DU30KB(-RJ)/MR-J4-DU37KB(-RJ)

(14) (17)

(16)(12)(13)

(1)

(2) (3) (4) (20) (5) (19) (6) (7) (11) (Note 3) (8) (9) (18)

(21)

(15)

(10)

No. Name/Application Detailed explanation

(1) Display The 3-digit, 7-segment LED display shows the drive unit status and the alarm number.

MR-J4-_B_ Section 4.3 (2) Axis selection rotary switch (SW1)

Used to set the axis No. of the drive unit.

(3) Control axis setting switch (SW2) The test operation switch, the disabling control axis switch, and the auxiliary axis number setting switch are available.

(4) USB communication connector (CN5) Used to connect the personal computer.

MR-J4-_B_ Section 11.7

(5) I/O signal connector (CN3) Used to connect digital I/O signals.

MR-J4-_B_ Section 3.2 Section 3.4

(6) STO input signal connector (CN8) Used to connect the MR-J3-D05 safety logic unit and external safety relay.

MR-J4-_B_ Chapter 13

App. 5

(7) SSCNET III cable connector (CN1A) Used to connect the servo system controller or the previous axis servo amplifier (drive unit). MR-J4-_B_

Section 3.2 Section 3.4 (8)

SSCNET III cable connector (CN1B) Used to connect the next axis servo amplifier (drive unit). For the final axis, put a cap.

(9) (Note

2)

Encoder connector (CN2) Used to connect the servo motor encoder or external encoder.

MR-J4-_B_ Section 3.4 "Servo Motor Instruction Manual (Vol. 3)" Section 1.1

(10) Battery connector (CN4) Used to connect the battery for absolute position data backup.

MR-J4-_B_ Chapter 12

(11) Battery holder Used to house the battery for absolute position data backup.

MR-J4-_B_ Section 12.2

(12) Protective earth (PE) terminal Grounding terminal

Section 5.2.1 (13)

L+/L- terminal (TE2-1) Connect with the L+ and L- terminals of the converter unit or another drive unit by bus bars.

(14) Rating plate Section 1.2 (15) Control circuit terminal L11/L21 (TE3)

Used to connect the control circuit power supply.

Section 5.2.1 (16) Servo motor power output terminal (TE1)

Used to connect the servo motor.

(17)

Protection coordination connector (CN40A) For the drive unit adjacent to the converter unit, connect with the CN4 of the power regeneration converter unit or the CN40 of the resistance regeneration converter unit.

(18)

(Note 1)

External encoder connector (CN2L) (Note 2) Used to connect the external encoder.

Section 5.2.2 "Linear Encoder Instruction Manual" Section 1.1

(19)

Optional unit connector (CN7) This connector is attached on the MR-J4-DU_B_-RJ drive unit. Connect an optional unit. The MR-J4-DU_B_ drive unit does not have this connector.

(20)

Optional unit connector (CN9) This connector is attached on the MR-J4-DU_B_-RJ drive unit. Connect an optional unit. The MR-J4-DU_B_ drive unit does not have this connector.

(21)

L+/L- terminal (TE2-2) Connect with the L+ and L- terminals of another drive unit by bus bars.

Section 5.2.1

Note 1. This is for the MR-J4-DU_B_-RJ drive unit. The MR-J4-DU_B_ drive unit does not have the CN2L connector. 2. "External encoder" is a term for the load-side encoder used in the fully closed loop system and the scale measurement

encoder used with the scale measurement function in this manual. 3. Lines for slots around the battery holder are omitted from the illustration.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 5

(2) 400 V class

(a) MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ)

(19)

(12) (16) (12)

(20) (5)

(6) (7) (11) (8) (9) (18) (10)

(14)

(13)

(15)

(1)(17) (2) (3) (4)

No. Name/Application Detailed explanation

(1) Display The 3-digit, 7-segment LED display shows the drive unit status and the alarm number.

MR-J4-_B_ Section 4.3 (2) Axis selection rotary switch (SW1)

Set the axis No. of the drive unit.

(3) Control axis setting switch (SW2) The test operation switch, the disabling control axis switch, and the auxiliary axis number setting switch are available.

(4) USB communication connector (CN5) Connect with the personal computer.

MR-J4-_B_ Section 11.7

(5) I/O signal connector (CN3) Connect digital I/O signals.

MR-J4-_B_ Section 3.2 Section 3.4

(6) STO input signal connector (CN8) Connect the MR-J3-D05 safety logic unit and external safety relay.

MR-J4-_B_ Chapter 13

App. 5

(7) SSCNET III cable connector (CN1A) Connect a servo system controller or the previous axis servo amplifier (drive unit). MR-J4-_B_

Section 3.2 Section 3.4 (8)

SSCNET III cable connector (CN1B) Connect the next axis servo amplifier (drive unit). For the final axis, put a cap.

(9) (Note

2)

Encoder connector (CN2) Connect the servo motor encoder or external encoder.

MR-J4-_B_ Section 3.4 "Servo Motor Instruction Manual (Vol. 3)" Section 1.1

(10) Battery connector (CN4) Connect the battery for absolute position data backup.

MR-J4-_B_ Chapter 12

(11) Battery holder Install the battery for absolute position data backup.

MR-J4-_B_ Section 12.2

(12) Protective earth (PE) terminal

Section 5.2.1 (13)

L+/L- terminal (TE2-1) Connect with the L+ and L- terminals of the converter unit or another drive unit by bus bars.

(14) Rating plate Section 1.2

(15) Control circuit terminal L11/L21 (TE3) Connect to the control circuit power supply.

Section 5.2.1 (16) Servo motor power output terminal (TE1)

Connect the servo motor.

(17)

Protection coordination connector (CN40A) For the drive unit adjacent to the converter unit, connect with the CN4 of the power regeneration converter unit or the CN40 of the resistance regeneration converter unit.

(18) (Note

1)

External encoder connector (CN2L) (Note 2) Connect the external encoder.

Section 5.2.2 "Linear Encoder Instruction Manual" Section 1.1

(19)

Optional unit connector (CN7) This connector is attached on the MR-J4-DU_B4-RJ drive unit. Connect an optional unit. The MR-J4-DU_B4 drive unit does not have this connector.

(20)

Optional unit connector (CN9) This connector is attached on the MR-J4-DU_B4-RJ drive unit. Connect an optional unit. The MR-J4-DU_B4 drive unit does not have this connector.

Note 1. This is for the MR-J4-DU_B4-RJ drive unit. The MR-J4-DU_B4 drive unit does not have the CN2L connector. 2. "External encoder" is a term for the load-side encoder used in the fully closed loop system and the scale measurement

encoder used with the scale measurement function in this manual.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 6

(b) MR-J4-DU15KB4(-RJ)/MR-J4-DU22KB4(-RJ)

(3)

(4)

(1)

(5)

The broken line area is the same as MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ).

(2)

No. Name/Application Detailed explanation

(1) Control circuit terminal L11/L21 (TE3) Connect to the control circuit power supply.

Section 5.2.1 (2) Servo motor power output terminal (TE1)

Connect the servo motor. (3) Rating plate Section 1.2

(4) L+/L- terminal (TE2-1) Connect with the L+ and L- terminals of the converter unit or another drive unit by bus bars.

Section 5.2.1

(5) Protective earth (PE) terminal Section 5.2.1

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 7

(c) MR-J4-DU30KB4(-RJ)/MR-J4-DU37KB4(-RJ)

(14) (17)

(16)(12)(13)

(1)

(2) (3) (4) (20) (5) (19) (6) (7) (11) (Note 3) (8) (9) (18) (10)

(15)

No. Name/Application Detailed explanation

(1) Display The 3-digit, 7-segment LED display shows the drive unit status and the alarm number.

MR-J4-_B_ Section 4.3 (2) Axis selection rotary switch (SW1)

Used to set the axis No. of the drive unit.

(3) Control axis setting switch (SW2) The test operation switch, the disabling control axis switch, and the auxiliary axis number setting switch are available.

(4) USB communication connector (CN5) Used to connect the personal computer.

MR-J4-_B_ Section 11.7

(5) I/O signal connector (CN3) Used to connect digital I/O signals.

MR-J4-_B_ Section 3.2 Section 3.4

(6) STO input signal connector (CN8) Used to connect the MR-J3-D05 safety logic unit and external safety relay.

MR-J4-_B_ Chapter 13

App. 5

(7) SSCNET III cable connector (CN1A) Used to connect the servo system controller or the previous axis servo amplifier (drive unit). MR-J4-_B_

Section 3.2 Section 3.4 (8)

SSCNET III cable connector (CN1B) Used to connect the next axis servo amplifier (drive unit). For the final axis, put a cap.

(9) (Note

2)

Encoder connector (CN2) Used to connect the servo motor encoder or external encoder.

MR-J4-_B_ Section 3.4 "Servo Motor Instruction Manual (Vol. 3)" Section 1.1

(10) Battery connector (CN4) Used to connect the battery for absolute position data backup.

MR-J4-_B_ Chapter 12

(11) Battery holder Used to house the battery for absolute position data backup.

MR-J4-_B_ Section 12.4

(12) Protective earth (PE) terminal Grounding terminal

Section 5.2.1 (13)

L+/L- terminal (TE2-1) Connect with the L+ and L- terminals of the converter unit or another drive unit by bus bars.

(14) Rating plate Section 1.2 (15) Control circuit terminal L11/L21 (TE3)

Used to connect the control circuit power supply.

Section 5.2.1 (16) Servo motor power output terminal (TE1)

Used to connect the servo motor.

(17)

Protection coordination connector (CN40A) For the drive unit adjacent to the converter unit, connect with the CN4 of the power regeneration converter unit or the CN40 of the resistance regeneration converter unit.

(18)

(Note 1)

External encoder connector (CN2L) (Note 2) Used to connect the external encoder.

Section 5.2.2 "Linear Encoder Instruction Manual" Section 1.1

(19)

Optional unit connector (CN7) This connector is attached on the MR-J4-DU_B_-RJ drive unit. Connect an optional unit. The MR-J4-DU_B_ drive unit does not have this connector.

(20)

Optional unit connector (CN9) This connector is attached on the MR-J4-DU_B_-RJ drive unit. Connect an optional unit. The MR-J4-DU_B_ drive unit does not have this connector.

Note 1. This is for the MR-J4-DU_B-RJ drive unit. The MR-J4-DU_B drive unit does not have the CN2L connector. 2. "External encoder" is a term for the load-side encoder used in the fully closed loop system and the scale measurement

encoder used with the scale measurement function in this manual. 3. Lines for slots around the battery holder are omitted from the illustration.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 8

(d) MR-J4-DU45KB4(-RJ)/MR-J4-DU55KB4(-RJ)

(5)

(1)

(2)(6)(4)

(3) The broken line area is the same as MR- J4-DU30KB4(-RJ)/MRJ4-DU37KB4(-RJ).

No. Name/Application Detailed explanation

(1) Control circuit terminal L11/L21 (TE3) Used to connect the control circuit power supply.

Section 5.2.1 (2) Servo motor power output terminal (TE1)

Used to connect the servo motor. (3) Rating plate Section 1.2

(4) L+/L- terminal (TE2-1) Connect with the L+ and L- terminals of the converter unit or another drive unit by bus bars.

Section 5.2.1

(5) Manufacturer setting terminal (TE2-2) This is for manufacturer setting. Leave this open.

(6) Protective earth (PE) terminal Grounding terminal Section 5.2.1

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 9

5.1.2 MR-J4-DU_A_(-RJ)

"MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 10

(1) 200 V class

(a) MR-J4-DU30KA(-RJ)/MR-J4-DU37KA(-RJ)

(15)(11)(12)

(13) (16) (1)

(2) (3) (4) (5) (18) (6) (10) (Note 3) (7) (8) (17) (9)

(19)

(14)

No. Name/Application Detailed explanation

(1) Display The 5-digit, 7-segment LED display shows the drive unit status and the alarm number.

MR-J4-_A_ Section 4.5

(2)

Operation section Used to perform status display, diagnostic, alarm, and parameter setting operations.

Used to set data. Push this button together with the "MODE" button for 3 s or more to switch to the one-touch tuning mode.

MODE UP DOWN SET

Used to change the display or data in each mode. Used to change the mode. Push this button together with the "SET" button for 3 s or more to switch to the one-touch tuning mode.

MR-J4-_A_ Section 4.5

(3) USB communication connector (CN5) Used to connect the personal computer.

MR-J4-_A_ Section 11.7

(4) Analog monitor connector (CN6) Used to output the analog monitor.

MR-J4-_A_ Section 3.2

(5) RS-422/RS-485 communication connector (CN3) Used to connect the personal computer, etc.

MR-J4-_A_ Chapter 14

(6) STO input signal connector (CN8) Used to connect the MR-J3-D05 safety logic unit and external safety relay.

MR-J4-_A_ Chapter 13

App. 5

(7) I/O signal connector (CN1) Used to connect digital I/O signals.

MR-J4-_A_ Section 3.2 Section 3.4

(8) (Note

2)

Encoder connector (CN2) Used to connect the servo motor encoder or external encoder.

MR-J4-_A_ Section 3.4 "Servo Motor Instruction Manual (Vol. 3)" Section 1.1

(9)

Battery connector (CN4) Used to connect the battery for absolute position data backup.

MR-J4-_A_ Chapter 12

(10) Battery holder Used to house the battery for absolute position data backup.

MR-J4-_A_ Section 12.2

(11) Protective earth (PE) terminal Grounding terminal

Section 5.2.1 (12)

L+/L- terminal (TE2-1) Used to connect the L+ and L- terminals of the resistance regeneration converter unit using the bus bars.

(13) Rating plate Section 1.2 (14) Control circuit terminal L11/L21 (TE3)

Used to connect the control circuit power supply.

Section 5.2.1 (15) Servo motor power output terminal (TE1)

Used to connect the servo motor.

(16) Protection coordination connector (CN40A) Used to connect CN40 of the resistance regeneration converter unit.

(17)

(Note 1)

External encoder connector (CN2L) (Note 2) Used to connect the external encoder.

Section 5.2.2 "Linear Encoder Instruction Manual" Section 1.1

(18)

Optional unit connector (CN7) This connector is attached on the MR-J4-DU_A_-RJ drive unit. Connect an optional unit. The MR-J4-DU_A_ drive unit does not have this connector.

(19)

Optional unit connector (CN9) This connector is attached on the MR-J4-DU_A_-RJ drive unit. Connect an optional unit. The MR-J4-DU_A_ drive unit does not have this connector.

(20) Manufacturer setting terminal (TE2-2) This is for manufacturer setting. Leave this open.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 11

Note 1. This is for the MR-J4-DU_A_-RJ drive unit. The MR-J4-DU_A_ drive unit does not have the CN2L connector. 2. "External encoder" is a term for the load-side encoder used in the fully closed loop system and the scale measurement

encoder used with the scale measurement function in this manual. 3. Lines for slots around the battery holder are omitted from the illustration.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 12

(2) 400 V class

(a) MR-J4-DU30KA4(-RJ)/MR-J4-DU37KA4(-RJ)

(15)(11)(12)

(13) (16) (1)

(2) (3) (4) (5) (18) (6) (10) (Note 3) (7) (8) (17) (9)

(14)

No. Name/Application Detailed explanation

(1) Display The 5-digit, 7-segment LED display shows the drive unit status and the alarm number.

MR-J4-_A_ Section 4.5

(2)

Operation section Used to perform status display, diagnostic, alarm, and parameter setting operations.

Used to set data. Push this button together with the "MODE" button for 3 s or more to switch to the one-touch tuning mode.

MODE UP DOWN SET

Used to change the display or data in each mode. Used to change the mode. Push this button together with the "SET" button for 3 s or more to switch to the one-touch tuning mode.

MR-J4-_A_ Section 4.5

(3) USB communication connector (CN5) Used to connect the personal computer.

MR-J4-_A_ Section 11.7

(4) Analog monitor connector (CN6) Used to output the analog monitor.

MR-J4-_A_ Section 3.2

(5) RS-422/RS-485 communication connector (CN3) Used to connect the personal computer, etc.

MR-J4-_A_ Chapter 14

(6) STO input signal connector (CN8) Used to connect the MR-J3-D05 safety logic unit and external safety relay.

MR-J4-_A_ Chapter 13

App. 5

(7) I/O signal connector (CN1) Used to connect digital I/O signals.

MR-J4-_A_ Section 3.2 Section 3.4

(8) (Note

2)

Encoder connector (CN2) Used to connect the servo motor encoder or external encoder.

MR-J4-_A_ Section 3.4 "Servo Motor Instruction Manual (Vol. 3)" Section 1.1

(9)

Battery connector (CN4) Used to connect the battery for absolute position data backup.

MR-J4-_A_ Chapter 12

(10) Battery holder Used to house the battery for absolute position data backup.

MR-J4-_A_ Section 12.2

(11) Protective earth (PE) terminal Grounding terminal

Section 5.2.1 (12)

L+/L- terminal (TE2-1) Used to connect the L+ and L- terminals of the resistance regeneration converter unit using the bus bars.

(13) Rating plate Section 1.2 (14) Control circuit terminal L11/L21 (TE3)

Used to connect the control circuit power supply.

Section 5.2.1 (15) Servo motor power output terminal (TE1)

Used to connect the servo motor.

(16) Protection coordination connector (CN40A) Used to connect CN40 of the resistance regeneration converter unit.

(17)

(Note 1)

External encoder connector (CN2L) (Note 2) Used to connect the external encoder.

Section 5.2.2 "Linear Encoder Instruction Manual" Section 1.1

(18)

Optional unit connector (CN7) This connector is attached on the MR-J4-DU_A_-RJ drive unit. Connect an optional unit. The MR-J4-DU_A_ drive unit does not have this connector.

(19)

Optional unit connector (CN9) This connector is attached on the MR-J4-DU_A_-RJ drive unit. Connect an optional unit. The MR-J4-DU_A_ drive unit does not have this connector.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 13

Note 1. This is for the MR-J4-DU_A_-RJ drive unit. The MR-J4-DU_A_ drive unit does not have the CN2L connector. 2. "External encoder" is a term for the load-side encoder used in the fully closed loop system and the scale measurement

encoder used with the scale measurement function in this manual. 3. Lines for slots around the battery holder are omitted from the illustration.

(b) MR-J4-DU45KA4(-RJ)/MR-J4-DU55KA4(-RJ)

(5)

(1)

(2)(6)(4)

(3) The broken line area is the same as MR- J4-DU30KA4(-RJ)/MRJ4-DU37KA4(-RJ).

No. Name/Application Detailed explanation

(1) Control circuit terminal L11/L21 (TE3) Used to connect the control circuit power supply.

Section 5.2.1 (2) Servo motor power output terminal (TE1)

Used to connect the servo motor. (3) Rating plate Section 1.2

(4) L+/L- terminal (TE2-1) Used to connect the L+ and L- terminals of the resistance regeneration converter unit using the bus bars.

Section 5.2.1

(5) Manufacturer setting terminal (TE2-2) This is for manufacturer setting. Leave this open.

(6) Protective earth (PE) terminal Grounding terminal Section 5.2.1

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 14

5.2 Signals and wiring

WARNING

A person who is involved in wiring should be fully competent to do the work. Before wiring, turn off the power and wait for 20 minutes or more until the charge lamp turns off. Then, confirm that the voltage between L+ and L- is safe with a voltage tester or others. Otherwise, an electric shock may occur. In addition, always confirm that the charge lamp is off from the front of the converter unit. Ground the converter unit, the drive unit and the servo motor securely. Do not attempt to wire the converter unit, the drive unit, and the servo motor until they have been installed. Otherwise, it may cause an electric shock. The cables should not be damaged, stressed, loaded, or pinched. Otherwise, it may cause an electric shock. To avoid an electric shock, insulate the connections of the power supply terminals.

CAUTION

Wire the equipment correctly and securely. Otherwise, the servo motor may operate unexpectedly, resulting in injury. Connect cables to the correct terminals. Otherwise, a burst, damage, etc. may occur. Ensure that polarity (+/-) is correct. Otherwise, a burst, damage, etc. may occur. The surge absorbing diode installed to the DC relay for control output should be fitted in the specified direction. Otherwise, the emergency stop and other protective circuits may not operate.

DOCOM 24 V DC

Drive unit

RA

For sink output interface

Control output signal

DOCOM

Control output signal

24 V DC Drive unit

RA

For source output interface

Use a noise filter, etc. to minimize the influence of electromagnetic interference. Electromagnetic interference may be given to the electronic equipment used near the converter unit and the drive unit. Do not install a power capacitor, surge killer or radio noise filter (optional FR-BIF(- H)) with the power line of the servo motor. When using the regenerative resistor, switch power off with the alarm signal. Otherwise, a transistor fault or the like may overheat the regenerative resistor, causing a fire. Do not modify the equipment.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 15

CAUTION

Connect the drive unit power outputs (U/V/W) to the servo motor power inputs (U/V/W) directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a malfunction.

U Servo motor

MV

W

U

V

W

U

MV

W

U

V

W

Drive unit Servo motorDrive unit

Do not connect the servo motor of a wrong axis to U, V, W, or CN2 of the drive unit. Otherwise, a malfunction may occur. Before wiring, switch operation, etc., eliminate static electricity. Otherwise, it may cause a malfunction.

The following items are the same as those of MR-J4-_(-RJ). For details of the items, refer to each chapter/section indicated in the detailed explanation field. "MR-J4-_B" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

Model Item Detailed explanation

MR-J4-DU_B_(-RJ) I/O signal connection example MR-J4-_B_ section 3.2 Forced stop deceleration function MR-J4-_B_ section 3.6 SSCNET III cable connection MR-J4-_B_ section 3.9

MR-J4-DU_A_(-RJ) I/O signal connection example MR-J4-_A_ section 3.2 Forced stop deceleration function MR-J4-_A_ section 3.7

5.2.1 Signal explanations

POINT For the layout of the terminal block, refer to chapter 7 DIMENSIONS.

Connection target (application) Symbol

(Note 1) Terminal

block

Description

MR-J4-DU900B(-RJ) MR-J4-DU11KB(-RJ) MR-J4-DU15KB(-RJ) MR-J4-DU22KB(-RJ) MR-J4-DU30KB(-RJ) MR-J4-DU37KB(-RJ) MR-J4-DU30KA(-RJ) MR-J4-DU37KA(-RJ)

MR-J4-DU900B4(-RJ) MR-J4-DU11KB4(-RJ) MR-J4-DU15KB4(-RJ) MR-J4-DU22KB4(-RJ) MR-J4-DU30KB4(-RJ) MR-J4-DU37KB4(-RJ) MR-J4-DU45KB4(-RJ) MR-J4-DU55KB4(-RJ) MR-J4-DU30KA4(-RJ) MR-J4-DU37KA4(-RJ) MR-J4-DU45KA4(-RJ) MR-J4-DU55KA4(-RJ)

Control circuit power supply L11/L21 TE3 Supply 1-phase 200 V AC to 240 V AC,

50 Hz/60 Hz power to L11 and L21. Supply 1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz power to L11 and L21.

Converter unit L+/L- TE2-1 (TE2)

(Note 2)

Connect the L+ and L- of the converter unit to this terminal. Use the bus bars to connect.

Servo motor power input U/V/W TE1

Connect the drive unit power outputs (U/V/W) to the servo motor power inputs (U/V/W) directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a malfunction.

Protective earth (PE) PE Connect the grounding terminal of the servo motor and the protective earth (PE) of the cabinet to this terminal.

Note 1. The permissible tension applied to any of the terminal blocks TE1, TE2-1 (TE2) is 350 N. 2. Explanations in parentheses are for MR-J4-DU30K_4(-RJ) and MR-J4-DU7K_4(-RJ).

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 16

5.2.2 Connectors and pin assignment

POINT The pin assignment of the connectors is as viewed from the cable connector wiring section.

(1) MR-J4-DU_B_(-RJ)

The following shows the front view of MR-J4-DU30KB4-RJ and MR-J4-DU37KB4-RJ drive units. For other views of drive units, connector arrangements, and details, refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

The frames of the CN2 and CN3 connectors are connected to the protective earth terminal in the drive unit.

CN1A (Connector for SSCNET III cable for previous servo amplifier axis) Refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual" section 3.4. CN1B (Connector for SSCNET III cable for next servo amplifier axis) Refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual" section 3.4.

CN3 (I/O signal connector) Refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual" section 3.4.

CN5 (USB connector) Refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual" section 11.7.

CN2 (Encoder connector) Refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual" section 3.4.

CN8 (STO I/O signal connector) Refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual" section 13.2.

CN2L (Load-side encoder connector) Refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual" section 3.4. CN4 (Battery connector) Refer to "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual" section 11.8.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 17

(2) MR-J4-DU_A_(-RJ)

The following shows the front view of MR-J4-DU30KA4-RJ and MR-J4-DU37KA4-RJ drive units. For other views of drive units, connector arrangements, and details, refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

The frames of the CN2 and CN3 connectors are connected to the protective earth terminal in the drive unit.

CN6 (Analog monitor connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 3.4.

CN1 (I/O signal connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 3.4.

CN3 (RS-422/RS-485 connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" chapter 14.

CN5 (USB connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 11.7.

CN2 (Encoder connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 3.4.

CN8 (STO I/O signal connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 13.2.

CN2L (Load-side encoder connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 3.4.

CN4 (Battery connector) Refer to "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual" section 11.8.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 18

5.3 Parameter

CAUTION

Never make a drastic adjustment or change to the parameter values as doing so will make the operation unstable. Do not change the parameter settings as described below. Doing so may cause an unexpected condition, such as failing to start up the drive unit.

Changing the values of the parameters for manufacturer setting Setting a value out of the range Changing the fixed values in the digits of a parameter

5.3.1 MR-J4-DU_B_(-RJ)

CAUTION When you write parameters with the controller, make sure that the control axis No. of the drive unit is set correctly. Otherwise, the parameter settings of another axis may be written, possibly causing the drive unit to be an unexpected condition.

POINT

When you connect the amplifier to a servo system controller, servo parameter values of the servo system controller will be written to each parameter. Setting may not be made to some parameters and their ranges depending on the servo system controller model, drive unit software version, and MR Configurator2 software version. For details, refer to the servo system controller user's manual. The parameter whose symbol is preceded by * is enabled with the following conditions: *: After setting the parameter, cycle the power or reset the controller. **: After setting the parameter, cycle the power. Set a value to each "x" in the "Setting digit" columns.

The following shows parameter settings exclusively for the driver unit. Other parameters are the same as those of MR-J4-_B_(-RJ). Refer to chapter 5 of "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 19

No. Symbol Name and function Initial value [unit]

Setting range

PA02 **REG Regenerative option Select a regenerative option. For the drive unit, select the regenerative option with the converter unit. Selecting other than "_ _ 0 0" or "_ _ 0 1" will trigger [AL. 37 Parameter error].

Refer to the "Name and function" column.

Setting digit Explanation Initial value

_ _ x x Regenerative option selection 00: Regenerative option is not used, or when you use a

regenerative option, set the regenerative option with the converter unit. When using the drive unit with the resistance regeneration converter unit, set this value regardless of whether or not the regenerative option and brake unit are used.)

00h

_ x _ _ Converter unit selection 0: MR-CR_ 7: MR-CV_ Setting a value other than "0" or "7" will trigger [AL. 37].

0h

x _ _ _ Enable or disable the protection coordination mode. 0: Protection coordination mode enabled 4: Protection coordination mode disabled (stand-alone drive) Set "4" for the drive unit which is not connected to the MR-CV_ with the protection coordination cable. To disable the protection coordination mode, set "Protection coordination mode function between converter and drive unit selection" of [Pr. PF03] to "Enabled (_ 1 _ _)", and then this parameter to "Protection coordination mode disabled (4 _ _ _)".

0h

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 20

No. Symbol Name and function Initial value [unit]

Setting range

PA20 *TDS Tough drive setting Alarms may not be avoided with the tough drive function depending on the situations of the power supply and load fluctuation. You can assign MTTR (During tough drive) to pins CN3-9, CN3-13, and CN3-15 with [Pr. PD07] to [Pr. PD09].

Refer to the "Name and function" column.

Setting digit Explanation Initial value

_ _ _ x For manufacturer setting 0h _ _ x _ Vibration tough drive selection

0: Disabled 1: Enabled Selecting "1" enables to suppress vibrations by automatically changing setting values of [Pr. PB13 Machine resonance suppression filter 1] and [Pr. PB15 Machine resonance suppression filter 2] in case that the vibration exceeds the value of the oscillation level set in [Pr. PF23]. For details, refer to section 7.3 of "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

0h

_ x _ _ SEMI-F47 function selection The [Pr. PA20 SEMI-F47 function selection] and [Pr. PF25 SEMI- F47 function - Instantaneous power failure detection time] settings of the drive unit must be the same as [Pr. PA17 SEMI-F47 function selection] and [Pr. PA18 SEMI-F47 function - Instantaneous power failure detection time] settings of the converter unit. 0: Disabled 1: Enabled Selecting "1" enables to avoid triggering [AL. 10 Undervoltage] using the electrical energy charged in the capacitor in case that an instantaneous power failure occurs during operation. In [Pr. PF25 SEMI-F47 function - Instantaneous power failure detection time], set the time until the occurrence of [AL. 10.1 Voltage drop in the control circuit power].

0h

x _ _ _ For manufacturer setting 0h

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 21

No. Symbol Name and function Initial value [unit]

Setting range

PC23 **COP7A Function selection C-7A This parameter setting is available with servo amplifiers with software version D0 or later. When maximum torque increase by compatible servo motors listed on the following table, select the maximally increased torque function when those drive units are connected.

Refer to the "Name and function" column.

Drive unit Servo motor

Maximum torque in percentage to rated

torque

MR-J4-DU900B

HG-SR702 400% HG-JR703 350% HG-JR701M 350%

MR-J4-DU900B4 HG-SR7024 400%

HG-JR7034 350% HG-JR701M4 350% Setting digit Explanation Initial

value

_ _ _ x For manufacturer setting 0h _ _ x _ Maximally increased torque function selection when drive unit is

connected A servo motor's maximum torque can be increased by selecting "1" when using a servo motor which supports maximally increased torque. 0: Disabled 1: Enabled When using a servo motor which does not support maximally increased torque, setting "1" will trigger [AL. 37 Parameter error].

0h

_ x _ _ For manufacturer setting 0h x _ _ _ 0h

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 22

No. Symbol Name and function Initial value [unit]

Setting range

PF03 *FOP5 Function selection F-5 Refer to the Name and function column.

Setting digit Explanation Initial

value

_ _ _ x For manufacturer setting 0h _ _ x _ 0h _ x _ _ Protection coordination mode function between converter and drive

unit selection 0: Disabled 1: Enabled When "Enabled (_ 1 _ _ )" is selected in this parameter, the setting value in "Protection coordination mode selection between converter and drive unit" of [Pr. PA02] is enabled.

0h

x _ _ _ For manufacturer setting 0h

PF07 *FOP6 Function selection F-6 Refer to the Name and function column.

Setting digit Explanation Initial

value

_ _ _ x For manufacturer setting 0h _ _ x _ 0h _ x _ _ Magnetic contactor shut-off selection at STO input

Select whether turning the magnetic contactor off when STO is inputted ([when AL. 95 has occurred]). Selecting "_ 1 _ _" keeps the main circuit power supply on when STO is inputted. 0: Turns the magnetic contactor off when STO is inputted ([when

AL. 95 has occurred]). 1: Keeps the magnetic contactor on when STO is inputted ([when

AL. 95 has occurred]).

0h

x _ _ _ Magnetic contactor shut-off selection at forced stop input Select whether turning the magnetic contactor off when the forced stop is inputted ([when AL. E6 has occurred]). Selecting "_ 1 _ _" keeps the main circuit power supply on when the forced stop is inputted. 0: Turns the magnetic contactor off when the forced stop is

inputted ([when AL. E6 has occurred]). 1: Keeps the magnetic contactor on when the forced stop is

inputted ([when AL. E6 has occurred]). This parameter is enabled only when the power regeneration converter unit is selected ([Pr. PA02]: _ 7 _ _). If MR-CR_ resistance regeneration converter unit is selected ([Pr. PA02]: _ 0 _ _), the magnetic contactor will be kept on when the forced stop is inputted ([when AL. E6 has occurred]) regardless the setting.

0h

PF25 CVAT The [Pr. PA20 SEMI-F47 function selection] and [Pr. PF25 SEMI-F47 function - Instantaneous power failure

detection time] settings of the drive unit must be the same as [Pr. PA17 SEMI-F47 function selection] and [Pr. PA18 SEMI-F47 function - Instantaneous power failure detection time] settings of the converter unit. SEMI-F47 function - Instantaneous power failure detection time Set the time until the occurrence of [AL. 10.1 Voltage drop in the control circuit power]. To disable the parameter setting value, select "Disabled (_ 0 _ _)" of "SEMI-F47 function selection" in [Pr. PA20].

200 [ms]

30 to

200

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 23

5.3.2 MR-J4-DU_A_(-RJ)

POINT To enable a parameter whose symbol is preceded by *, cycle the power after setting it. Set a value to each "x" in the "Setting digit" columns.

The following shows parameter settings exclusively for the driver unit. Other parameters are the same as those of MR-J4-_A_(-RJ). Refer to chapter 5 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

No./symbol/ name

Setting digit Function

Initial value [unit]

PA02 *REG Regenerative option

_ _ x x Regenerative option Select a regenerative option. For the drive unit, select the regenerative option with the converter unit. Selecting other than "_ _ 0 0" or "_ _ 0 1" will trigger [AL. 37 Parameter error]. 00: Regenerative option is not used, or when you use a regenerative option, set the regenerative

option with the converter unit. When using the drive unit with the resistance regeneration converter unit, set this value regardless of whether or not the regenerative option and brake unit are used.)

00h

_ x _ _ For manufacturer setting 0h x _ _ _ 0h

PA20 *TDS Tough drive setting

Alarms may not be avoided with the tough drive function depending on the situations of the power supply and load fluctuation. You can assign MTTR (During tough drive) to pins CN1-22 to CN1-25, CN1-49, CN1-13, and CN1-14 with [Pr. PD23] to [Pr. PD26], [Pr. PD28], and [Pr. PD47]. _ _ _ x For manufacturer setting 0h _ _ x _ Vibration tough drive selection

0: Disabled 1: Enabled Selecting "1" enables to suppress vibrations by automatically changing setting values of [Pr. PB13 Machine resonance suppression filter 1] and [Pr. PB15 Machine resonance suppression filter 2] in case that the vibration exceeds the value of the oscillation level set in [Pr. PF23]. To output the oscillation detection alarm as a warning, set [Pr. PF24 Vibration tough drive function selection]. For details, refer to section 7.3 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

0h

_ x _ _ SEMI-F47 function selection The [Pr. PA20 SEMI-F47 function selection] and [Pr. PF25 SEMI-F47 function - Instantaneous power failure detection time] settings of the drive unit must be the same as [Pr. PA17 SEMI-F47 function selection] and [Pr. PA18 SEMI-F47 function - Instantaneous power failure detection time] settings of the converter unit. 0: Disabled 1: Enabled Selecting "1" enables to avoid triggering [AL. 10 Undervoltage] using the electrical energy charged in the capacitor in case that an instantaneous power failure occurs during operation. In [Pr. PF25 SEMI-F47 function - Instantaneous power failure detection time], set the time until the occurrence of [AL. 10.1 Voltage drop in the control circuit power].

0h

x _ _ _ For manufacturer setting 0h PF25 CVAT SEMI-F47 function - Instanta- neous power failure detection time

The [Pr. PA20 SEMI-F47 function selection] and [Pr. PF25 SEMI-F47 function - Instantaneous power failure detection time] settings of the drive unit must be the same as [Pr. PA17 SEMI-F47 function selection] and [Pr. PA18 SEMI-F47 function - Instantaneous power failure detection time] settings of the converter unit.

Set the time until the occurrence of [AL. 10.1 Voltage drop in the control circuit power]. To disable the parameter setting value, select "Disabled (_ 0 _ _)" of "SEMI-F47 function selection" in [Pr. PA20]. Setting range: 30 to 200

200 [ms]

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 24

5.4 Characteristics

The following items are the same as those of MR-J4-_(-RJ). For details of the items, refer to each chapter/section of the detailed explanation field. "MR-J4-_B_" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

Model Item Detailed explanation MR-J4-DU_B_(-RJ) Cable bending life MR-J4-_B_ section 10.4 MR-J4-DU_A_(-RJ) Cable bending life MR-J4-_A_ section 10.4

5.4.1 Drive unit

An electronic thermal is built in the drive unit to protect the servo motor, drive unit and servo motor power wires from overloads. [AL. 50 Overload 1] occurs if overload operation performed is above the electronic thermal protection curve shown in the following figure. [AL. 51 Overload 2] occurs if the maximum current is applied continuously for several seconds due to machine collision, etc. [AL. 51 Overload 2] occurs if the maximum current is applied continuously for several seconds due to machine collision, etc. Use the equipment on the left-side area of the continuous or broken line in the graph. For the system where the unbalanced torque occurs, such as a vertical axis system, the unbalanced torque of the machine should be kept at 70% or lower of the motor's rated torque. The drive unit has the servo motor overload protective function. (The servo motor overload current (full load current) is set on the basis of 120% rated current of the drive unit.)

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 25

The following table shows combinations of each servo motor and graph of overload protection characteristics.

Rotary servo motor Graph

HG-SR HG-JR 702 7024

503 703 701M 5034 7034

Characteristics A

11K1M 903 9034 12K14 11K1M4 15K1M4 37K14 12K1 37K1 15K1M 801 15K1 20K1 25K1 30K1 22K1M 30K1M 37K1M 8014 15K14 20K14 25K14 30K14 22K1M4 30K1M4 37K1M4 45K1M4

Characteristics B

601 6014 701M4

Characteristics A

55K1M4 Characteristics B

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 26

(1) Characteristics A

4000

1000

50 100 (Note 2)

150 200 250 300 350 1

100

10

Servo-lock

(Note 1, 3) Load ratio [%]

O pe

ra tio

n tim

e [s

] Operating

Note 1. If operation that generates torque more than 100% of the rating is performed with an abnormally high frequency in a servo motor stop status (servo-lock status) or in a 30 r/min or less low-speed operation status, the drive unit may malfunction regardless of the electronic thermal protection.

2. Load ratio 100% indicates the rated output of the drive unit. Refer to section 1.4.3 for rated output.

3. The operation time at the load ratio of 300% to 400% applies when the maximum torque is increased to 400% of rated torque.

(2) Characteristics B

10000

1000

100

10

1 30050 100

(Note 2) 150 200 2500

O pe

ra tio

n tim

e [s

]

Servo-lock

(Note 1) Load ratio [%]

Operating

Note 1. If operation that generates torque more than 100% of the rating is performed with an abnormally high frequency in a servo motor stop status (servo-lock status) or in a 30 r/min or less low-speed operation status, the drive unit may malfunction regardless of the electronic thermal protection.

2. Load ratio 100% indicates the rated output of the drive unit. Refer to section 1.4.3 for rated output.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 27

5.4.2 Dynamic brake characteristics

CAUTION

The coasting distance is a theoretically calculated value which ignores the running load such as friction. The calculated value will be longer than the actual distance. If an enough braking distance is not provided, a moving part may crash into the stroke end, which is very dangerous. Install the anti-crash mechanism such as an air brake or an electric/mechanical stopper such as a shock absorber to reduce the shock of moving parts.

POINT

Do not use dynamic brake to stop in a normal operation as it is the function to stop in emergency. For a machine operating at the recommended load to motor inertia ratio or less, the estimated number of usage times of the dynamic brake is 1000 times while the machine decelerates from the rated speed to a stop once in 10 minutes. Be sure to enable EM1 (Forced stop 1) after servo motor stops when using EM1 frequently in other than emergency. Servo motors for MR-J4 may have the different coasting distance from that of the previous model.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 28

(1) Calculation of coasting distance

The following figure shows the pattern in which the servo motor comes to a stop when the dynamic brake is operated.

V0

OFF

ON

Machine speed

te Time

EM1 (Forced stop 1)

Dynamic brake time constant

Use the following equation to calculate an approximate coasting distance to a stop.

Lmax = 60 V0 te + JM

1 + JL

Lmax : Maximum coasting distance [mm] V0 : Machine's fast feed speed [mm/min] JM : Moment of inertia of the servo motor [ 10-4 kgm2] JL : Load moment of inertia converted into equivalent value on servo motor shaft [ 10-4 kgm2] : Dynamic brake time constant [s] te : Delay time of control section [s]

There is delay caused by magnetic contactor built into the external dynamic brake (about 50 ms) and delay caused by the external relay.

The dynamic brake time constant varies with the servo motor and machine operation speeds. (Refer to (2) in this section.) A working part generally has a friction force. Therefore, actual coasting distance will be shorter than a maximum coasting distance calculated with the following equation.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 29

(2) Dynamic brake time constant

(a) 200 V class HG-SR2000 r/min series

0 500 1000 1500 2000 2500 3000 D

yn am

ic b

ra ke

ti m

e co

ns ta

nt [m

s] Speed [r/min]

0

100 50

200 150

250 300 350

702

(b) 200 V class HG-JR1000 r/min series

0

20 10

30 40 50 60 70 80 90

100

0 500 1000 1500 2000

15K1 25K1

20K1

801 60112K1D

yn am

ic b

ra ke

ti m

e co

ns ta

nt [m

s]

Speed [r/min]

(c) 200 V class HG-JR1500 r/min series

D yn

am ic

b ra

ke ti

m e

co ns

ta nt

[m s]

80

0

70 60 50 40 30 20 10

500 1000 1500 2000 2500 30000

15K1M

11K1M

22K1M

701M

Speed [r/min]

(d) 200 V class HG-JR3000 r/min series

503

260

0

220

180

140

100

60

20 1000 2000 3000 4000 5000 60000

703

903

D yn

am ic

b ra

ke ti

m e

co ns

ta nt

[m s]

Speed [r/min]

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 30

(e) 200 V class HG-JR1000 r/min series

HG-JR30K1

HG-JR37K1

0

10

20

30

40

50

60

0 500 1000 1500 Speed [r/min]

D yn

am ic

b ra

ke ti

m e

co ns

ta nt

[m s]

(f) 200 V class HG-JR1500 r/min series

Speed [r/min]

0

5

10

15

20

25

30

35

40

45

50

0 500 1000 1500 2000 2500

HG-JR30K1M

HG-JR37K1M

D yn

am ic

b ra

ke ti

m e

co ns

ta nt

[m s]

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 31

(g) 400 V class HG-SR series

0 500 1000 1500 2000 2500 3000

100

80

60

40

20

0 7024

D yn

am ic

b ra

ke ti

m e

co ns

ta nt

[m s]

Speed [r/min]

(h) 400 V class HG-JR1000 r/min series

0

10

20

30

40

50

60

0 500 1000 1500 2000 6014

8014

25K14

12K14 20K14

15K14

D yn

am ic

b ra

ke ti

m e

co ns

ta nt

[m s]

Speed [r/min]

(i) 400 V class HG-JR1500 r/min series

50

0

40

30

20

10

500 1000 1500 2000 2500 30000

11K1M4

22K1M4

15K1M4701M4

70

60

D yn

am ic

b ra

ke ti

m e

co ns

ta nt

[m s]

Speed [r/min]

(j) 400 V class HG-JR3000 r/min series

0 1000 2000 3000 4000 5000 6000

5034

120

100

80

60

40

20

0

9034

7034

D yn

am ic

b ra

ke ti

m e

co ns

ta nt

[m s]

Speed [r/min]

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 32

(k) 400 V class HG-JR1000 r/min series

HG-JR30K14

HG-JR37K14

0

5

10

15

20

25

30

35

40

45

50

0 500 1000 1500 Speed [r/min]

D yn

am ic

b ra

ke ti

m e

co ns

ta nt

[m s]

(l) 400 V class HG-JR1500 r/min series

Speed [r/min] 0 500 1000 1500 2000 2500

HG-JR37K1M4

HG-JR45K1M4

HG-JR55K1M4

HG-JR30K1M4

0

10

20

30

40

50

60

70

80

90

D yn

am ic

b ra

ke ti

m e

co ns

ta nt

[m s]

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 33

(3) Permissible load to motor inertia when the dynamic brake is used

Use the dynamic brake under the load to motor inertia ratio indicated in the following table. If the ratio is higher than this value, the dynamic brake may burn. If there is a possibility that the ratio may exceed the value, contact your local sales office. The values of the permissible load to motor inertia ratio in the table are the values at the maximum rotation speed of the servo motor. The value in the parenthesis shows the value at the rated speed.

Servo motor Load to motor inertia ratio

[multiplier] HG-JR703 21 (30) HG-JR601 30 HG-JR701M 14 (30) HG-SR702 18 (30) HG-JR903 18 (30) HG-JR801 30 HG-JR12K1 20 (30) HG-JR11K1M 10 (30) HG-JR15K1 17 (30) HG-JR15K1M 10 (30) HG-JR20K1 26 (30) HG-JR22K1M 20 (30) HG-JR25K1 21 (30) HG-JR7034 21 (30) HG-JR6014 30 HG-JR701M4 14 (30) HG-SR7024 18 (30) HG-JR9034 18 (30) HG-JR8014 30 HG-JR12K14 20 (30) HG-JR11K1M4 10 (30) HG-JR15K14 30 (30) HG-JR15K1M4 10 (30) HG-JR20K14 26 (30) HG-JR22K1M4 20 (30) HG-JR25K14 21 (30) HG-JR30K1

10

HG-JR37K1 HG-JR30K14 HG-JR37K14 HG-JR30K1M HG-JR37K1M HG-JR30K1M4 HG-JR37K1M4 HG-JR45K1M4 8 (10) HG-JR55K1M4 7 (10)

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 34

5.4.3 Inrush currents at power-on of control circuit

Since large inrush currents flow in the power supplies, always use molded-case circuit breakers and magnetic contactors. (Refer to section 8.5.) When circuit protectors are used, it is recommended that the inertia delay type, which is not tripped by an inrush current, be used. (1) 200 V class

The following table indicates the inrush currents (reference data) that will flow when 240 V AC is applied at the power supply capacity.

Drive unit Inrush currents (A0-P)

Control circuit power supply (L11/L21)

MR-J4-DU900B(-RJ)

23 A (attenuated to approx. 2 A in 8 ms) MR-J4-DU11KB(-RJ) MR-J4-DU15KB(-RJ) MR-J4-DU22KB(-RJ) MR-J4-DU30K_(-RJ)

31 A (attenuated to approx. 2 A in 60 ms) MR-J4-DU37K_(-RJ)

(2) 400 V class

The following table indicates the inrush currents (reference data) that will flow when 480 V AC is applied at the power supply capacity.

Drive unit Inrush currents (A0-P)

Control circuit power supply (L11/L21)

MR-J4-DU900B4(-RJ)

15 A (attenuated to approx. 2 A in 9 ms) MR-J4-DU11KB4(-RJ) MR-J4-DU15KB4(-RJ) MR-J4-DU22KB4(-RJ) MR-J4-DU30K_4(-RJ) MR-J4-DU37K_4(-RJ)

27 A (attenuated to approx. 2 A in 45 ms) MR-J4-DU45K_4(-RJ) MR-J4-DU55K_4(-RJ)

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 35

5.5 Mounting and removing MR-D30

WARNING Before mounting and removing MR-D30, turn off the power and wait for 20 minutes or more until the charge lamp turns off. In addition, when confirming whether the charge lamp is off or not, always confirm it from the front of the converter unit.

CAUTION

Do not mount and remove MR-D30 frequently. Otherwise, a contact failure may be caused in the connector. To protect the connectors from dusts and dirt, unpack MR-D30 only when it is ready to be attached. When storing MR-D30, be sure to cover the unit with a packing bag in which the unit had been covered prior to shipping. Do not use MR-D30 if its fixing hook or clips are broken. Otherwise, a contact failure may be caused in the connector. When mounting and removing the MR-D30, do not drop the mounting screws to the inside of the drive unit. Otherwise, the drive unit may malfunction. When mounting the MR-D30, be careful not to damage the control board in the drive unit by the fixing plate. Otherwise, the drive unit may malfunction. Be sure to use the enclosed mounting screws for fixing the MR-D30.

POINT

The internal circuits of the drive unit and MR-D30 may be damaged by static electricity. Always take the following precautions.

Ground human body and work bench. Do not touch the conductive areas, such as connector pins and electrical parts, directly by hand.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 36

5.5.1 MR-J4-DU900B-RJ to MR-J4-DU22KB-RJ/MR-J4-DU900B4-RJ to MR-J4-DU22KB4-RJ

(1) Mounting the MR-D30

1)

1)

a)

b)

2)

1) Remove the mounting screw. 2) Fit your fingers in a) and b) to pull the control interface off the drive unit in the arrow direction. Do

not pull without removing the mounting screws.

3)

4)

e)

d)

f)

c)

3) Remove the mounting screw. 4) While pushing the clips (c), d), e), f)), pull out the case in the arrow direction. Do not pull the case

without removing the mounting screws.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 37

5)

Guide hole MR-D30

Guide pin

5)

5) Insert the guide pins of the MR-D30 in the guide holes located on the side of the control interface.

6)

7)

Knob

6) Push the four corners of the side of the MR-D01 simultaneously to the control interface until the four clips click so that the CN7 and CN9 connectors are connected straight.

7) Fix with the screws which have been removed in 3).

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 38

8)

9) h)

g)

8) Install the control interface on the drive unit along the guide lines (g), h)). Confirm that the model name and the serial numbers on the plate of the drive unit correspond, and that those of the control interface correspond. If the model names and the serial numbers do not correspond, alarms or malfunction may occur.

9) Fix with the screws which have been removed in 1). (2) Removing the MR-D30

1)

1)

a)

b)

2)

1) Remove the mounting screw. 2) Fit your fingers in a) and b) to pull the control interface off the drive unit in the arrow direction. Do

not pull without removing the mounting screws.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 39

3)

4)

e)

d)

f)

c)

3) Remove the mounting screw. 4) While pushing the clips (c), d), e), f)), pull out the MR-D30 in the arrow direction. Do not pull the

MR-D30 without removing the mounting screws.

6)

5)

Knob

5) Push the four corners of the case simultaneously to the control interface until the four clips click. 6) Fix with the screws which have been removed in 3).

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 40

7)

g)

8) h)

7) Install the control interface on the drive unit along the guide lines (g), h)). Confirm that the model name and the serial numbers on the plate of the drive unit correspond, and that those of the control interface correspond. If the model names and the serial numbers do not correspond, alarms or malfunction may occur.

8) Fix with the screws which have been removed in 1). 5.5.2 MR-J4-DU30K_-RJ to MR-J4-DU37K_-RJ/MR-J4-DU30K_4-RJ to MR-J4-DU55K_4-RJ

CAUTION Avoid touching burr remained after the part a) being cut off from the case c) shown in the figure below. Otherwise, it may cause injury.

(1) Mounting the MR-D30

1)

a)

b)

1) While pushing the clips ( a) , b)), and pull out the side cover in the arrow direction.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 41

c)

2) When mounting the MR-D30 for the first time, cut off the part a) from the case after removing the side cover. When cutting off the part c), be careful not to damage the case of the drive unit. After the part a) is cut off, inside of the drive unit will be exposed even after the side cover or the MR- D30 is attached. Prevent foreign materials from entering through the opened area into the drive unit.

3) Insert the guide pins of the MR-D30 in the guide holes located on the side of the drive unit.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 42

Knob

4) 5)

4) Push the four corners of the side of the MR-D01 simultaneously to the control interface until the four clips click so that the CN7 and CN9 connectors are connected straight.

5) Fix the unit on the MR-D30 with the enclosed mounting screws (M4). (2) Removing the MR-D30

2)

c)

d)

a)

b)

1)

1) Remove the mounting screw. 2) While pushing the clips (a), b), c), d)), pull out the MR-D30 in the arrow direction. Do not pull the

MR-D30 without removing the mounting screws.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 43

e)

3)

3)

Side cover Setting clip

3) Insert the side cover setting clips into the recesses e) of the drive unit.

4)

Knob

4) Push against the drive unit at the supporting point e) shown in procedure 1) until the clips clip into place.

5. MR-J4-DU_(-RJ) DRIVE UNIT

5 - 44

MEMO

6. TROUBLESHOOTING

6 - 1

6. TROUBLESHOOTING

6.1 MR-CV_ Power regeneration converter unit

When an error occurs during operation, the corresponding alarm or warning is displayed. When an alarm or warning is displayed, refer to "MELSERVO-J4 Servo Amplifier Instruction Manual (Troubleshooting)" to remove the failure. When an alarm occurs, ALM will turn off. 6.1.1 Explanation for the lists

(1) No./Name Indicates each No./Name of alarms or warnings.

(2) Alarm deactivation

After its cause has been removed, the alarm can be deactivated by any of the methods marked in the alarm deactivation column. Warnings are automatically canceled after the cause of occurrence is removed. Alarms are deactivated by alarm reset, CPU reset, or power cycling.

Alarm deactivation Explanation

Alarm reset 1. Turn on RES (Reset) with an input device. (Note 1) 2. Input the servo-on command for the drive unit connected with the protection

coordination cable. CPU reset Reset the controller itself. (Note 2) Cycling the power Turning the power off and then turning it on again.

Note 1. Deactivate the alarm in servo-off status. If the alarm is deactivated in servo-on status, [AL. 1B Converter error]

occurs. 2. When it is not connected by a protection coordination cable, alarms cannot be deactivated by CPU reset.

6.1.2 Alarm/warning list

Display Name Alarm deactivation Display Name

Alarm reset CPU reset Cycling the power

W ar

ni ng

E9 Instantaneous power failure warning

Al ar

m 61 Overcurrent EA Converter forced stop warning

62 Frequency error EB Excessive regeneration warning 66 Process error EC Overload warning 67 Open phase

EE Cooling fan speed reduction warning 68 Watchdog

69 Ground fault 6A MC drive circuit error

6B Inrush current suppression circuit error

6C Main circuit error 6E_

(Note 1) Board error

70 Converter forced stop error 71 Undervoltage 72 Cooling fan error 73 Regenerative error (Note 2) (Note 2) (Note 2) 75 Overvoltage 76 Switch setting error 77 Main circuit device overheat (Note 2) (Note 2) 7E Overload 1 (Note 2) (Note 2) (Note 2) 7F Overload 2 (Note 2) (Note 2) (Note 2)

Note 1. The third digit may be displayed. Remedies for the alarm is the same as those for [AL. 6E]. 2. After resolving the source of trouble, cool the equipment for approximately 30 minutes.

6. TROUBLESHOOTING

6 - 2

6.2 MR-CR_ Resistance regeneration converter unit

POINT [AL. 37 Parameter error] and warnings are not recorded in the alarm history.

When an error occurs during operation, the corresponding alarm or warning is displayed. When an alarm or warning is displayed, refer to "MELSERVO-J4 Servo Amplifier Instruction Manual (Troubleshooting)" to remove the failure. When an alarm occurs, ALM will turn off. 6.2.1 Explanation for the lists

(1) No./Name Indicates each No./Name of alarms or warnings.

(2) Alarm deactivation

After its cause has been removed, the alarm can be deactivated by any of the methods marked in the alarm deactivation column. Warnings are automatically canceled after the cause of occurrence is removed. Alarms are deactivated with alarm reset or cycling the power.

Alarm deactivation Explanation

Alarm reset Push "SET" on the current alarm screen of the display. Cycling the power Turning the power off and then turning it on again.

6.2.2 Alarm/warning list

Display Name Alarm deactivation Display Name

Alarm reset Cycling the power

W ar

ni ng

A.91 Converter overheat warning A.E0 Excessive regeneration warning

Al ar

m A.10 Undervoltage A.E1 Overload warning 1

A.12 Memory error 1 (RAM) A.E6 Converter forced stop warning A.15 Memory error 2 (EEP-ROM) A.E8 Cooling fan speed reduction warning A.17 Board error A.19 Memory error 3 (Flash-ROM) A.30 Regenerative error (Note) (Note)

A.33 Overvoltage A.37 Parameter error A.38 MC drive circuit error A.39 Open phase A.3A Inrush current suppression circuit error A.45 Main circuit device overheat (Note) (Note) A.47 Cooling fan error A.50 Overload 1 (Note) (Note) A.51 Overload 2 (Note) (Note) 888 Watchdog

Note. After resolving the source of trouble, cool the equipment for approximately 30 minutes.

6. TROUBLESHOOTING

6 - 3

6.3 Drive unit

POINT As soon as an alarm occurs, turn SON (Servo-on) off and interrupt the power. [AL. 37 Parameter error] and warnings (except [AL. F0 Tough drive warning]) are not recorded in the alarm history.

When an error occurs during operation, the corresponding alarm or warning is displayed. When an alarm or warning is displayed, refer to "MELSERVO-J4 Servo Amplifier Instruction Manual (Troubleshooting)" to remove the failure. When an alarm occurs, ALM (Malfunction) will turn off. 6.3.1 Explanation for the lists

(1) No./Name/Detail No./Detail name Indicates each No./Name/Detail No./Detail name of alarms or warnings.

(2) Stop method

For the alarms and warnings in which "SD" is written in the stop method column, the servo motor stops with the dynamic brake after forced stop deceleration. For the alarms and warnings in which "DB" is written in the stop method column, the servo motor stops with the dynamic brake without forced stop deceleration.

(3) Alarm deactivation

After its cause has been removed, the alarm can be deactivated by any of the methods marked in the alarm deactivation column. Warnings are automatically canceled after the cause of occurrence is removed. Alarms are deactivated with alarm reset, CPU reset, or cycling the power.

(a) MR-J4-DU_A_(-RJ)/MR-J4-DU_A_(-RJ)

Alarm deactivation Explanation

Alarm reset 1. Turning on RES (Reset) with input device 2. Pushing the "SET" button while the display of the drive unit is the current alarm

display status 3. Click "Occurring Alarm Reset" in the "Alarm Display" window of MR

Configurator2 Cycling the power Turning the power off and then turning it on again.

(b) MR-J4-_B_(-RJ010)/MR-J4W_-_B_/MR-J4-DU_B_(-RJ)/MR-J4-_GF_(-RJ)

Alarm deactivation Explanation

Alarm reset 1. Error reset command from controller 2. Click "Occurring Alarm Reset" in the "Alarm Display" window of MR

Configurator2 CPU reset Resetting the controller itself Cycling the power Turning the power off and then turning it on again.

(4) Alarm code (Only MR-J4-DU_A_(-RJ))

Alarm codes are outputted only from MR-J4-DU_A_(-RJ). To output alarm codes, set [Pr. PD34] to "_ _ _ 1" when using a MR-J4-DU_A_(-RJ). Alarm codes are outputted by on/off of bit 0 to bit 2. Warnings ([AL. 90] to [AL. F3]) do not have alarm codes. The alarm codes in the following table will be outputted when they occur. The alarm codes will not be outputted in normal condition.

6. TROUBLESHOOTING

6 - 4

6.3.2 Alarm list

No. Name Detail No. Detail name

Stop method (Note 2, 3)

Alarm deactivation Process- ing

system (Note 9)

Stop system (Note 9)

Alarm code (Note 8)

Alarm reset

CPU reset

Cycling the

power

ACD3 (Bit 3)

ACD2 (Bit 2)

ACD1 (Bit 1)

ACD0 (Bit 0)

Al ar

m

10 Undervoltage 10.1 Voltage drop in the control

circuit power DB Common All axes 0 0 1 0

10.2 Voltage drop in the main circuit power SD Common All axes

11 Switch setting error

11.1 Axis number setting error/ Station number setting error DB Common All axes

11.2 Disabling control axis setting error DB Common All axes

12.1 RAM error 1 DB Common All axes 12.2 RAM error 2 DB Common All axes

12 Memory error 1 (RAM)

12.3 RAM error 3 DB Common All axes 0 0 0 0 12.4 RAM error 4 DB Common All axes 12.5 RAM error 5 DB Common All axes 12.6 RAM error 6 DB

13 Clock error 13.1 Clock error 1 DB Common All axes

0 0 0 0 13.2 Clock error 2 DB Common All axes 14.1 Control process error 1 DB Common All axes

14.2 Control process error 2 DB Common All axes 14.3 Control process error 3 DB Common All axes 14.4 Control process error 4 DB Common All axes

Control process error

14.5 Control process error 5 DB Common All axes 0 0 0 0

14 14.6 Control process error 6 DB Common All axes 14.7 Control process error 7 DB Common All axes 14.8 Control process error 8 DB Common All axes 14.9 Control process error 9 DB Common All axes 14.A Control process error 10 DB Common All axes 14.B Control process error 11 DB

15 Memory error 2

(EEP-ROM)

15.1 EEP-ROM error at power on DB Common All axes

0 0 0 0 15.2 EEP-ROM error during

operation DB Common All axes

15.4 Home position information read error DB

16.1 Encoder initial communication - Receive data error 1 DB

Each axis

Each axis

16.2 Encoder initial communication - Receive data error 2 DB

Each axis

Each axis

16.3 Encoder initial communication - Receive data error 3 DB

Each axis

Each axis

16.5 Encoder initial communication - Transmission data error 1 DB

Each axis

Each axis

16.6 Encoder initial communication - Transmission data error 2 DB

Each axis

Each axis

16 Encoder initial communication

error 1

16.7 Encoder initial communication - Transmission data error 3 DB

Each axis

Each axis

0 1 1 0 16.A Encoder initial communication -

Process error 1 DB Each axis

Each axis

16.B Encoder initial communication - Process error 2 DB

Each axis

Each axis

16.C Encoder initial communication - Process error 3 DB

Each axis

Each axis

16.D Encoder initial communication - Process error 4 DB

Each axis

Each axis

16.E Encoder initial communication - Process error 5 DB

Each axis

Each axis

16.F Encoder initial communication - Process error 6 DB

Each axis

Each axis

6. TROUBLESHOOTING

6 - 5

No. Name Detail No. Detail name

Stop method (Note 2, 3)

Alarm deactivation Process- ing

system (Note 9)

Stop system (Note 9)

Alarm code (Note 8)

Alarm reset

CPU reset

Cycling the

power

ACD3 (Bit 3)

ACD2 (Bit 2)

ACD1 (Bit 1)

ACD0 (Bit 0)

Al ar

m 17.1 Board error 1 DB Common All axes

17.3 Board error 2 DB Common All axes 17.4 Board error 3 DB Common All axes

17 Board error

17.5 Board error 4 DB Common All axes 0 0 0 0 17.6 Board error 5 DB Common All axes 17.7 Board error 7 DB 17.8 Board error 6 (Note 6) DB Common All axes 17.9 Board error 8 DB

Memory error 3 (Flash-ROM)

19.1 Flash-ROM error 1 DB Common All axes 0 0 0 0

19 19.2 Flash-ROM error 2 DB Common All axes 19.3 Flash-ROM error 3 DB 1A.1 Servo motor combination error

1 DB Each axis

Each axis

1A Servo motor combination error 1A.2 Servo motor control mode

combination error DB Each axis

Each axis 0 1 1 0

1A.4 Servo motor combination error 2 DB

Each axis

Each axis

1B Converter error 1B.1 Converter unit error DB 0 0 1 0

1E Encoder initial communication

error 2

1E.1 Encoder malfunction DB Each axis

Each axis

0 1 1 0 1E.2 Load-side encoder malfunction DB

Each axis

Each axis

1F Encoder initial communication

error 3

1F.1 Incompatible encoder DB Each axis

Each axis

0 1 1 0 1F.2 Incompatible load-side encoder DB

Each axis

Each axis

20.1 Encoder normal communication - Receive data error 1 DB

Each axis

Each axis

20.2 Encoder normal communication - Receive data error 2 DB

Each axis

Each axis

20.3 Encoder normal communication - Receive data error 3 DB

Each axis

Each axis

20 Encoder normal communication

error 1

20.5 Encoder normal communication - Transmission data error 1 DB

Each axis

Each axis

0 1 1 0 20.6 Encoder normal communication

- Transmission data error 2 DB Each axis

Each axis

20.7 Encoder normal communication - Transmission data error 3 DB

Each axis

Each axis

20.9 Encoder normal communication - Receive data error 4 DB

Each axis

Each axis

20.A Encoder normal communication - Receive data error 5 DB

Each axis

Each axis

21.1 Encoder data error 1 DB Each axis

Each axis

21.2 Encoder data update error DB Each axis

Each axis

Encoder normal communication

error 2

21.3 Encoder data waveform error DB Each axis

Each axis

21 21.4 Encoder non-signal error DB Each axis

Each axis 0 1 1 0

21.5 Encoder hardware error 1 DB Each axis

Each axis

21.6 Encoder hardware error 2 DB Each axis

Each axis

21.9 Encoder data error 2 DB Each axis

Each axis

6. TROUBLESHOOTING

6 - 6

No. Name Detail No. Detail name

Stop method (Note 2, 3)

Alarm deactivation Process- ing

system (Note 9)

Stop system (Note 9)

Alarm code (Note 8)

Alarm reset

CPU reset

Cycling the

power

ACD3 (Bit 3)

ACD2 (Bit 2)

ACD1 (Bit 1)

ACD0 (Bit 0)

Al ar

m

24 Main circuit error 24.1 Ground fault detected by

hardware detection circuit DB Each axis All axes

1 1 0 0 24.2 Ground fault detected by

software detection function DB Each axis All axes

25 Absolute position erased

25.1 Servo motor encoder - Absolute position erased DB

Each axis

Each axis

1 1 1 0 25.2 Scale measurement encoder -

Absolute position erased DB Each axis

Each axis

27.1 Initial magnetic pole detection - Abnormal termination DB

Each axis

Each axis

27.2 Initial magnetic pole detection - Time out error DB

Each axis

Each axis

27.3 Initial magnetic pole detection - Limit switch error DB

Each axis

Each axis

27 Initial magnetic pole detection error 27.4 Initial magnetic pole detection -

Estimated error DB Each axis

Each axis 1 1 1 0

27.5 Initial magnetic pole detection - Position deviation error DB

Each axis

Each axis

27.6 Initial magnetic pole detection - Speed deviation error DB

Each axis

Each axis

27.7 Initial magnetic pole detection - Current error DB

Each axis

Each axis

28 Linear encoder error 2 28.1 Linear encoder - Environment

error DB Each axis

Each axis 0 1 1 0

2A.1 Linear encoder error 1-1 DB Each axis

Each axis

2A.2 Linear encoder error 1-2 DB Each axis

Each axis

2A.3 Linear encoder error 1-3 DB Each axis

Each axis

2A Linear encoder error 1

2A.4 Linear encoder error 1-4 DB Each axis

Each axis

0 1 1 0 2A.5 Linear encoder error 1-5 DB

Each axis

Each axis

2A.6 Linear encoder error 1-6 DB Each axis

Each axis

2A.7 Linear encoder error 1-7 DB Each axis

Each axis

2A.8 Linear encoder error 1-8 DB Each axis

Each axis

2B Encoder counter error

2B.1 Encoder counter error 1 DB Each axis

Each axis

1 1 1 0 2B.2 Encoder counter error 2 DB

Each axis

Each axis

30.1 Regeneration heat error DB (Note 1)

(Note 1)

(Note 1) Common All axes

30 Regenerative error 30.2 Regeneration signal error DB (Note 1)

(Note 1)

(Note 1) Common All axes 0 0 0 1

30.3 Regeneration feedback signal error DB

(Note 1)

(Note 1)

(Note 1) Common All axes

31 Overspeed 31.1 Abnormal motor speed SD Each axis

Each axis 0 1 0 1

32.1

Overcurrent detected at hardware detection circuit (during operation)

DB Each axis All axes

32 Overcurrent

32.2 Overcurrent detected at software detection function (during operation)

DB Each axis All axes

0 1 0 0

32.3 Overcurrent detected at hardware detection circuit (during a stop)

DB Each axis All axes

32.4

Overcurrent detected at software detection function (during a stop)

DB Each axis All axes

33 Overvoltage 33.1 Main circuit voltage error DB Common All axes 1 0 0 1

6. TROUBLESHOOTING

6 - 7

No. Name Detail No. Detail name

Stop method (Note 2, 3)

Alarm deactivation Process- ing

system (Note 9)

Stop system (Note 9)

Alarm code (Note 8)

Alarm reset

CPU reset

Cycling the

power

ACD3 (Bit 3)

ACD2 (Bit 2)

ACD1 (Bit 1)

ACD0 (Bit 0)

Al ar

m

34 SSCNET receive error 1

34.1 SSCNET receive data error SD (Note 5) Common All axes

34.2 SSCNET connector connection error SD Common All axes

34.3 SSCNET communication data error SD

Each axis

Each axis

34.4 Hardware error signal detection SD Common All axes 34.5 SSCNET receive data error

(safety observation function) SD

34.6

SSCNET communication data error (safety observation function)

SD

35 Command frequency error 35.1 Command frequency error SD

Each axis

Each axis 1 1 0 1

36 SSCNET receive error 2

36.1 Continuous communication data error SD

Each axis

Each axis

36.2

Continuous communication data error (safety observation function)

SD

37 Parameter error

37.1 Parameter setting range error DB Each axis

Each axis

1 0 0 0 37.2 Parameter combination error DB Each axis

Each axis

37.3 Point table setting error DB

39 Program error

39.1 Program error DB

0 0 0 0

39.2 Instruction argument external error DB

39.3 Register No. error DB 39.4 Non-correspondence instruction

error DB

3A

Inrush current suppression circuit

error 3A.1 Inrush current suppression

circuit error DB Common All axes 0 0 0 0

3D Parameter setting

error for driver communication

3D.1 Parameter combination error for driver communication on slave

DB

3D.2

Parameter combination error for driver communication on master

DB

3E Operation mode

error 3E.1 Operation mode error DB

Each axis

Each axis

3E.6 Operation mode switch error DB 1 0 0 0

42

Servo control error (for linear servo motor and direct

drive motor)

42.1 Servo control error by position deviation DB (Note 4) (Note 4)

Each axis

Each axis

0 1 1 0

42.2 Servo control error by speed deviation DB (Note 4) (Note 4)

Each axis

Each axis

42.3 Servo control error by torque/thrust deviation DB (Note 4) (Note 4)

Each axis

Each axis

Fully closed loop control error

(for fully closed loop control)

42.8 Fully closed loop control error by position deviation DB (Note 4) (Note 4)

Each axis

Each axis

42.9 Fully closed loop control error by speed deviation DB (Note 4) (Note 4)

Each axis

Each axis

42.A

Fully closed loop control error by position deviation during command stop

DB (Note 4) (Note 4) Each axis

Each axis

45 Main circuit device overheat

45.1 Main circuit device overheat error 1 SD

(Note 1)

(Note 1)

(Note 1) Common All axes 0 0 1 1

45.2 Main circuit device overheat error 2 SD

(Note 1)

(Note 1)

(Note 1) Common All axes

6. TROUBLESHOOTING

6 - 8

No. Name Detail No. Detail name

Stop method (Note 2, 3)

Alarm deactivation Process- ing

system (Note 9)

Stop system (Note 9)

Alarm code (Note 8)

Alarm reset

CPU reset

Cycling the

power

ACD3 (Bit 3)

ACD2 (Bit 2)

ACD1 (Bit 1)

ACD0 (Bit 0)

Al ar

m

46.1 Abnormal temperature of servo motor 1 SD

(Note 1)

(Note 1)

(Note 1) Each axis

Each axis

46.2 Abnormal temperature of servo motor 2 SD

(Note 1)

(Note 1)

(Note 1) Each axis

Each axis

46 Servo motor

overheat

46.3 Thermistor disconnected error SD (Note 1)

(Note 1)

(Note 1)

Each axis

Each axis

0 0 1 1 46.4 Thermistor circuit error SD

(Note 1)

(Note 1)

(Note 1) Each axis

Each axis

46.5 Abnormal temperature of servo motor 3 DB

(Note 1)

(Note 1)

(Note 1) Each axis

Each axis

46.6 Abnormal temperature of servo motor 4 DB

(Note 1)

(Note 1)

(Note 1) Each axis

Each axis

47 Cooling fan error

47.1 Cooling fan stop error SD Common All axes 0 0 1 1

47.2 Cooling fan speed reduction error SD Common All axes

50.1 Thermal overload error 1 during operation SD

(Note 1)

(Note 1)

(Note 1) Each axis

Each axis

50.2 Thermal overload error 2 during operation SD

(Note 1)

(Note 1)

(Note 1) Each axis

Each axis

50 Overload 1

50.3 Thermal overload error 4 during operation SD

(Note 1)

(Note 1)

(Note 1) Each axis

Each axis

0 0 1 1 50.4 Thermal overload error 1 during

a stop SD (Note 1)

(Note 1)

(Note 1)

Each axis

Each axis

50.5 Thermal overload error 2 during a stop SD

(Note 1)

(Note 1)

(Note 1) Each axis

Each axis

50.6 Thermal overload error 4 during a stop SD

(Note 1)

(Note 1)

(Note 1) Each axis

Each axis

51 Overload 2 51.1 Thermal overload error 3 during

operation DB (Note 1)

(Note 1)

(Note 1)

Each axis

Each axis

0 0 1 1 51.2 Thermal overload error 3 during

a stop DB (Note 1)

(Note 1)

(Note 1)

Each axis

Each axis

52.1 Excess droop pulse 1 SD Each axis

Each axis

52 Error excessive

52.3 Excess droop pulse 2 SD Each axis

Each axis

0 1 0 1 52.4 Error excessive during 0 torque

limit SD Each axis

Each axis

52.5 Excess droop pulse 3 DB Each axis

Each axis

54 Oscillation detection 54.1 Oscillation detection error DB

Each axis

Each axis 0 0 1 1

56 Forced stop error

56.2 Over speed during forced stop DB Each axis

Each axis

0 1 1 0 56.3 Estimated distance over during

forced stop DB Each axis

Each axis

61 Operation error 61.1 Point table setting range error DB 0 1 0 1 63.1 STO1 off DB Common All axes 63 STO timing error 63.2 STO2 off DB Common All axes 0 1 1 0 63.5 STO by functional safety unit DB 64.1 STO input error DB

64 Functional safety unit setting error 64.2 Compatibility mode setting

error DB 1 0 0 0

64.3 Operation mode setting error DB

6. TROUBLESHOOTING

6 - 9

No. Name Detail No. Detail name

Stop method (Note 2, 3)

Alarm deactivation Process- ing

system (Note 9)

Stop system (Note 9)

Alarm code (Note 8)

Alarm reset

CPU reset

Cycling the

power

ACD3 (Bit 3)

ACD2 (Bit 2)

ACD1 (Bit 1)

ACD0 (Bit 0)

Al ar

m

65.1 Functional safety unit communication error 1 SD

65.2 Functional safety unit communication error 2 SD

65.3 Functional safety unit communication error 3 SD

Functional safety unit connection

error

65.4 Functional safety unit communication error 4 SD

65 65.5 Functional safety unit communication error 5 SD 0 0 0 0

65.6 Functional safety unit communication error 6 SD

65.7 Functional safety unit communication error 7 SD

65.8 Functional safety unit shut-off signal error 1 DB

65.9 Functional safety unit shut-off signal error 2 DB

66.1 Encoder initial communication - Receive data error 1 (safety observation function)

DB

Encoder initial communication

error (safety observation

function)

66.2 Encoder initial communication - Receive data error 2 (safety observation function)

DB

66 66.3 Encoder initial communication - Receive data error 3 (safety observation function)

DB 0 1 1 0

66.7 Encoder initial communication - Transmission data error 1 (safety observation function)

DB

66.9 Encoder initial communication - Process error 1 (safety observation function)

DB

67.1 Encoder normal communication - Receive data error 1 (safety observation function)

DB

Encoder normal communication

error 1 (safety observation

function)

67.2 Encoder normal communication - Receive data error 2 (safety observation function)

DB

67 67.3 Encoder normal communication - Receive data error 3 (safety observation function)

DB 0 1 1 0

67.4 Encoder normal communication - Receive data error 4 (safety observation function)

DB

67.7 Encoder normal communication - Transmission data error 1 (safety observation function)

DB

68 STO diagnosis error 68.1 Mismatched STO signal error DB Common Common 0 0 0 0

69 Command error

69.1 Forward rotation-side software limit detection - Command excess error

SD

69.2 Reverse rotation-side software limit detection - Command excess error

SD

69.3 Forward rotation stroke end detection - Command excess error

SD

69.4 Reverse rotation stroke end detection - Command excess error

SD

69.5 Upper stroke limit detection - Command excess error SD

69.6 Lower stroke limit detection - Command excess error SD

6. TROUBLESHOOTING

6 - 10

No. Name Detail No. Detail name

Stop method (Note 2, 3)

Alarm deactivation Process- ing

system (Note 9)

Stop system (Note 9)

Alarm code (Note 8)

Alarm reset

CPU reset

Cycling the

power

ACD3 (Bit 3)

ACD2 (Bit 2)

ACD1 (Bit 1)

ACD0 (Bit 0)

Al ar

m

70.1 Load-side encoder initial communication - Receive data error 1

DB Each axis

Each axis

70.2 Load-side encoder initial communication - Receive data error 2

DB Each axis

Each axis

70.3 Load-side encoder initial communication - Receive data error 3

DB Each axis

Each axis

70.5 Load-side encoder initial communication - Transmission data error 1

DB Each axis

Each axis

70.6 Load-side encoder initial communication - Transmission data error 2

DB Each axis

Each axis

70

Load-side encoder initial

communication error 1

70.7 Load-side encoder initial communication - Transmission data error 3

DB Each axis

Each axis

0 1 1 0

70.A Load-side encoder initial communication - Process error 1

DB Each axis

Each axis

70.B Load-side encoder initial communication - Process error 2

DB Each axis

Each axis

70.C Load-side encoder initial communication - Process error 3

DB Each axis

Each axis

70.D Load-side encoder initial communication - Process error 4

DB Each axis

Each axis

70.E Load-side encoder initial communication - Process error 5

DB Each axis

Each axis

70.F Load-side encoder initial communication - Process error 6

DB Each axis

Each axis

71.1

Load-side encoder normal communication - Receive data error 1

DB Each axis

Each axis

71.2

Load-side encoder normal communication - Receive data error 2

DB Each axis

Each axis

71.3

Load-side encoder normal communication - Receive data error 3

DB Each axis

Each axis

71

Load-side encoder normal

communication error 1

71.5 Load-side encoder normal communication - Transmission data error 1

DB Each axis

Each axis

0 1 1 0

71.6 Load-side encoder normal communication - Transmission data error 2

DB Each axis

Each axis

71.7

Load-side encoder normal communication - Transmission data error 3

DB Each axis

Each axis

71.9

Load-side encoder normal communication - Receive data error 4

DB Each axis

Each axis

71.A

Load-side encoder normal communication - Receive data error 5

DB Each axis

Each axis

6. TROUBLESHOOTING

6 - 11

No. Name Detail No. Detail name

Stop method (Note 2, 3)

Alarm deactivation Process- ing

system (Note 9)

Stop system (Note 9)

Alarm code (Note 8)

Alarm reset

CPU reset

Cycling the

power

ACD3 (Bit 3)

ACD2 (Bit 2)

ACD1 (Bit 1)

ACD0 (Bit 0)

Al ar

m

72.1 Load-side encoder data error 1 DB Each axis

Each axis

72.2 Load-side encoder data update error DB

Each axis

Each axis

Load-side encoder

normal communication

error 2

72.3 Load-side encoder data waveform error DB

Each axis

Each axis

72 72.4 Load-side encoder non-signal error DB

Each axis

Each axis 0 1 1 0

72.5 Load-side encoder hardware error 1 DB

Each axis

Each axis

72.6 Load-side encoder hardware error 2 DB

Each axis

Each axis

72.9 Load-side encoder data error 2 DB Each axis

Each axis

74.1 Option card error 1 DB 74.2 Option card error 2 DB 74 Option card error 1 74.3 Option card error 3 DB 74.4 Option card error 4 DB 74.5 Option card error 5 DB

75 Option card error 2 75.3 Option card connection error DB

75.4 Option card disconnected DB

79.1 Functional safety unit power voltage error DB

(Note 7)

79.2 Functional safety unit internal error DB

79 Functional safety

unit diagnosis error 79.3 Abnormal temperature of

functional safety unit SD (Note 7)

1 1 1 1

79.4 Servo amplifier error SD 79.5 Input device error SD 79.6 Output device error SD 79.7 Mismatched input signal error SD 79.8 Position feedback fixing error DB

7A

Parameter setting error

(safety observation function)

7A.1 Parameter verification error (safety observation function) DB

1 0 0 0

7A.2 Parameter setting range error (safety observation function) DB

7A.3 Parameter combination error (safety observation function) DB

7A.4 Functional safety unit combination error (safety observation function)

DB

7B.1 Encoder diagnosis error 1 (safety observation function) DB

7B

Encoder diagnosis error

(safety observation function)

7B.2 Encoder diagnosis error 2 (safety observation function) DB

0 1 1 0 7B.3 Encoder diagnosis error 3

(safety observation function) DB

7B.4 Encoder diagnosis error 4 (safety observation function) DB

7C

Functional safety unit communication

diagnosis error (safety observation

function)

7C.1 Functional safety unit communication setting error (safety observation function)

SD (Note 7)

0 0 0 0

7C.2 Functional safety unit communication data error (safety observation function)

SD (Note 7)

7D Safety observation

error

7D.1 Stop observation error DB (Note 3)

1 1 1 1

7D.2 Speed observation error DB (Note 7)

82 Master-slave operation error 1 82.1 Master-slave operation error 1 DB

6. TROUBLESHOOTING

6 - 12

No. Name Detail No. Detail name

Stop method (Note 2, 3)

Alarm deactivation Process- ing

system (Note 9)

Stop system (Note 9)

Alarm code (Note 8)

Alarm reset

CPU reset

Cycling the

power

ACD3 (Bit 3)

ACD2 (Bit 2)

ACD1 (Bit 1)

ACD0 (Bit 0)

Al ar

m

84 Network module initialization error

84.1 Network module undetected error DB

84.2 Network module initialization error 1 DB

84.3 Network module initialization error 2 DB

85 Network module error

85.1 Network module error 1 SD 85.2 Network module error 2 SD 85.3 Network module error 3 SD

86 Network

communication error

86.1 Network communication error 1 SD 86.2 Network communication error 2 SD 86.3 Network communication error 3 SD

8A

USB communication

time-out error/serial communication

time-out error/Modbus RTU

communication time-out error

8A.1 USB communication time-out error/serial communication time-out error

SD Common All axes

0 0 0 0

8A.2 Modbus RTU communication time-out error SD

8D.1 CC-Link IE communication error 1 SD

8D.2 CC-Link IE communication error 2 SD

CC-Link IE communication

error

8D.3 Master station setting error 1 DB 8D.5 Master station setting error 2 DB

8D 8D.6 CC-Link IE communication error 3 SD

8D.7 CC-Link IE communication error 4 SD

8D.8 CC-Link IE communication error 5 SD

8D.9 Synchronization error 1 SD 8D.A Synchronization error 2 SD

8E.1 USB communication receive error/serial communication receive error

SD Common All axes

8E.2

USB communication checksum error/serial communication checksum error

SD Common All axes

8E

USB communication

error/serial communication

error/Modbus RTU communication

error

8E.3 USB communication character error/serial communication character error

SD Common All axes

0 0 0 0

8E.4

USB communication command error/serial communication command error

SD Common All axes

8E.5

USB communication data number error/serial communication data number error

SD Common All axes

8E.6 Modbus RTU communication receive error SD

8E.7 Modbus RTU communication message frame error SD

8E.8 Modbus RTU communication CRC error SD

88888 Watchdog 8888._ Watchdog DB Common All axes

6. TROUBLESHOOTING

6 - 13

Note 1. After resolving the source of trouble, cool the equipment for approximately 30 minutes. 2. The following shows three stop methods of DB, and SD.

DB: Stops with dynamic brake. Coasts for MR-J4-03A6(-RJ) and MR-J4W2-0303B6. Note that EDB is applied when an alarm below occurs; [AL. 30.1], [AL. 32.2], [AL. 32.4], [AL. 51.1], [AL. 51.2], [AL. 888]

SD: Forced stop deceleration 3. This is applicable when [Pr. PA04] is set to the initial value. The stop system of SD can be changed to DB using [Pr. PA04]. 4. The alarm can be canceled by setting as follows:

For the fully closed loop control: set [Pr. PE03] to "1 _ _ _". When a linear servo motor or direct drive motor is used: set [Pr. PL04] to "1 _ _ _".

5. In some controller communication status, the alarm factor may not be removed. 6. This alarm will occur only in the J3 compatibility mode. 7. Reset this while all the safety observation functions are stopped. 8. Alarm codes are outputted only from MR-J4-_A_(-RJ)/MR-J4-DU_A_(-RJ).

6. TROUBLESHOOTING

6 - 14

6.3.3 Warning list

No. Name Detail No. Detail name

Stop method (Note 2,

3)

Process- ing

system (Note 5)

Stop system (Note 5)

W

ar ni

ng

Home position return incomplete

warning

90.1 Home position return incomplete

90 90.2 Home position return abnormal termination

90.5 Z-phase unpassed

91 Servo amplifier

overheat warning (Note 1)

91.1 Main circuit device overheat warning Common

92

Battery cable disconnection

warning

92.1 Encoder battery cable disconnection warning Each

axis

92.3 Battery degradation Each axis

93 ABS data transfer warning 93.1

ABS data transfer requirement warning during magnetic pole detection

95.1 STO1 off detection DB Common All axes 95.2 STO2 off detection DB Common All axes

95 STO warning

95.3 STO warning 1 (safety observation function) DB

95.4 STO warning 2 (safety observation function) DB

95.5 STO warning 3 (safety observation function) DB

96.1 In-position warning at home positioning Each

axis

96 Home position

setting warning

96.2 Command input warning at home positioning Each

axis

96.3 Servo off warning at home positioning

96.4 Home positioning warning during magnetic pole detection

97

Positioning specification

warning

97.1 Program operation disabled warning

97.2 Next station position warning

98 Software limit

warning

98.1 Forward rotation-side software stroke limit reached

98.2 Reverse rotation-side software stroke limit reached

99.1 Forward rotation stroke end off (Note 4, 7)

99 Stroke limit warning

99.2 Reverse rotation stroke end off (Note 4, 7)

99.4 Upper stroke limit off (Note 7) Each axis

99.5 Lower stroke limit off (Note 7) Each axis

9A Optional unit input

data error warning 9A.1 Optional unit input data sign error

9A.2 Optional unit BCD input data error

9B Error excessive warning

9B.1 Excess droop pulse 1 warning Each axis

9B.3 Excess droop pulse 2 warning Each axis

9B.4 Error excessive warning during 0 torque limit Each

axis

9C Converter error 9C.1 Converter unit error

9D.1 Station number switch change warning

9D CC-Link IE warning

1 9D.2 Master station setting warning

9D.3 Overlapping station number warning 9D.4 Mismatched station number warning

6. TROUBLESHOOTING

6 - 15

No. Name Detail No. Detail name

Stop method (Note 2,

3)

Process- ing

system (Note 5)

Stop system (Note 5)

W ar

ni ng

9E CC-Link IE warning

2 9E.1 CC-Link IE communication warning

9F Battery warning 9F.1 Low battery Each

axis

9F.2 Battery degradation warning Each axis

E0 Excessive

regeneration warning

E0.1 Excessive regeneration warning Common

E1.1 Thermal overload warning 1 during operation Each

axis

E1.2 Thermal overload warning 2 during operation Each

axis

E1.3 Thermal overload warning 3 during operation Each

axis

E1 Overload warning 1

E1.4 Thermal overload warning 4 during operation Each

axis

E1.5 Thermal overload error 1 during a stop Each

axis

E1.6 Thermal overload error 2 during a stop Each

axis

E1.7 Thermal overload error 3 during a stop Each

axis

E1.8 Thermal overload error 4 during a stop Each

axis

E2 Servo motor overheat warning E2.1 Servo motor temperature warning Each

axis

E3.1 Multi-revolution counter travel distance excess warning

E3 Absolute position

counter warning

E3.2 Absolute position counter warning Each axis

E3.4 Absolute positioning counter EEP- ROM writing frequency warning

E3.5 Encoder absolute positioning counter warning Each

axis

E4 Parameter warning E4.1 Parameter setting range error warning Each

axis

E5 ABS time-out

warning

E5.1 Time-out during ABS data transfer E5.2 ABSM off during ABS data transfer E5.3 SON off during ABS data transfer

E6 Servo forced stop warning

E6.1 Forced stop warning SD Common All axes

E6.2 SS1 forced stop warning 1 (safety observation function) SD

E6.3 SS1 forced stop warning 2 (safety observation function) SD

E7 Controller forced stop warning E7.1 Controller forced stop warning SD Common All axes

E8 Cooling fan speed

reduction warning E8.1 Decreased cooling fan speed

warning Common

E8.2 Cooling fan stop Common

E9 Main circuit off warning

E9.1 Servo-on signal on during main circuit off DB Common All axes

E9.2 Bus voltage drop during low speed operation DB Common All axes

E9.3 Ready-on signal on during main circuit off DB Common All axes

E9.4 Converter unit forced stop DB

EA ABS servo-on

warning EA.1 ABS servo-on warning

EB The other axis error warning EB.1 The other axis error warning DB Each

axis (Note 6)

EC Overload warning 2 EC.1 Overload warning 2 Each axis

6. TROUBLESHOOTING

6 - 16

No. Name Detail No. Detail name

Stop method (Note 2,

3)

Process- ing

system (Note 5)

Stop system (Note 5)

W ar

ni ng

ED Output watt excess

warning ED.1 Output watt excess warning Each axis

F0 Tough drive warning F0.1 Instantaneous power failure tough

drive warning Each axis

F0.3 Vibration tough drive warning Each axis

F2 Drive recorder - Miswriting warning

F2.1 Drive recorder - Area writing time- out warning Common

F2.2 Drive recorder - Data miswriting warning Common

F3 Oscillation detection warning F3.1 Oscillation detection warning Each

axis

F4 Positioning warning

F4.4 Target position setting range error warning

F4.6 Acceleration time constant setting range error warning

F4.7 Deceleration time constant setting range error warning

F4.9 Home position return type error warning

F5

Simple cam function - Cam data miswriting warning

F5.1 Cam data - Area writing time-out warning

F5.2 Cam data - Area miswriting warning F5.3 Cam data checksum error

F6.1 Cam axis one cycle current value restoration failed

F6

Simple cam function - Cam control warning

F6.2 Cam axis feed current value restoration failed

F6.3 Cam unregistered error F6.4 Cam control data setting range error F6.5 Cam No. external error F6.6 Cam control inactive

F7 Machine diagnosis warning

F7.1 Vibration failure prediction warning Each axis

F7.2 Friction failure prediction warning Each axis

F7.3 Total travel distance failure prediction warning Each

axis

Note 1. After resolving the source of trouble, cool the equipment for approximately 30 minutes. 2. The following shows two stop methods of DB and SD.

DB: Stops with dynamic brake. Coasts for MR-J4-03A6(-RJ) and MR-J4W2-0303B6.

SD: Forced stop deceleration 3. This is applicable when [Pr. PA04] is set to the initial value. The stop system of SD can be changed to DB

using [Pr. PA04]. 4. For MR-J4-_A_ servo amplifier (drive unit), quick stop or slow stop can be selected using [Pr. PD30].

7. DIMENSIONS

7 - 1

7. DIMENSIONS

POINT Refer to section 2.1 for the mounting hole process drawing.

7.1 MR-CV_ Power regeneration converter unit

7.1.1 MR-CV11K(4)/MR-CV18K(4)

[Unit: mm]

90

38 0

36 0

17 6.

6

13 6

10 6

15 5

19 5

Approx. 80 200

180

6

TE1

PE

TE2

TE3

92

39 .4

12 4.

5

11

24

70

178.5

175.5 16.2

25.6 32.4

72.8 68

73.5

10

6 mounting hole Cooling fan exhaust

Intake

Mass: 6.1 [kg]

L21

L11

PE

Terminal

TE3 L- L+

TE2

TE1 L1 L2 L3

TE1 Screw size: M5 Tightening torque: 2.0 [Nm]

TE2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M5 Tightening torque: 2.0 [Nm]

Mounting screw Screw size: M5 Tightening torque: 3.24 [Nm]

7. DIMENSIONS

7 - 2

7.1.2 MR-CV30K(4)/MR-CV37K(4)/MR-CV45K(4)

[Unit: mm]

45 45

38 0

36 0

17 8

13 2

10 10

66

15 5

19 5

Approx. 80 200 180

6

TE1

PE

TE2

TE3

92

37 .5

1. 5

12 4.

5

11

24

100

178.5

175.5 26

108

88

113.5

60

150

49 52

150

2-6 mounting hole Cooling fan exhaust

Intake

Mass: 12.1 [kg]

L21

L11

PE

Terminal

TE3 L- L+

TE2

TE1 L1 L2 L3

TE1 Screw size: M8 Tightening torque: 6.0 [Nm]

TE2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M8 Tightening torque: 6.0 [Nm]

Mounting screw Screw size: M5 Tightening torque: 3.24 [Nm]

7. DIMENSIONS

7 - 3

7.1.3 MR-CV55K

[Unit: mm]

36 0

10

38 0

300

30 240

For eyebolts

6 6

6018060

15 5

19 5

Approx. 80

10

200

180

100

113 74

37

236 3847

12 4.

5 24

12 4.

5 24

11 92

TE3

TE2-2

TE1

TE2-1

223.5

22 22

22256

PE

17 0.

5

15 8.

5

10 42

178.5 175.5

2-6 mounting hole

Cooling fan exhaust

Intake

Mass: 25.0 [kg]

L21

L11

PE

Terminal

TE3 L- L+

TE2-2

L- L+

TE2-1

TE1 L1 L2 L3

TE1 Screw size: M10 Tightening torque: 12.0 [Nm]

TE2-1 Screw size: M6 Tightening torque: 3.0 [Nm]

TE2-2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M10 Tightening torque: 12.0 [Nm]

Mounting screw Screw size: M5 Tightening torque: 3.24 [Nm]

7. DIMENSIONS

7 - 4

7.1.4 MR-CV55K4/MR-CV75K4

[Unit: mm]

60 60

38 0

36 0

16 1.

5 10

42 10 66

15 5

19 5

Approx. 80 200 180

10

TE2-1 TE2-2

PE

TE1

TE3

12 4.

5 40 .5

24

100

178.5 175.5

2222

180 300

24030

124 52

256

For eyebolts

236

223.5

24

22

26

15 8.

5

92

38

12 4.

5

11

Cooling fan exhaust

2-6 mounting hole

Intake

Mass: 25.0 [kg]

L21

L11

PE

Terminal

TE3 L- L+

TE2-2

L- L+

TE2-1

TE1 L1 L2 L3

TE1 Screw size: M8 Tightening torque: 6.0 [Nm]

TE2-1 Screw size: M6 Tightening torque: 3.0 [Nm]

TE2-2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M8 Tightening torque: 6.0 [Nm]

Mounting screw Screw size: M5 Tightening torque: 3.24 [Nm]

7. DIMENSIONS

7 - 5

7.2 MR-CR55K(4) Resistance regeneration converter unit

[Unit: mm]

300

21045

20 260 20

38 0

36 0

10 37

.3 10

7

100

180

19 5

15 5

200

175.5

178.5 15.5

32

63

2 31 = 62

33

2 31 = 62

230

4159

24 12

4. 5

92 11

192

98 .6

13 0.

3 16

2. 5

22 22 22.522.5

2.3

TE2-1 TE2-2

PE

TE3

PETE1-1 TE1-2

For eyebolts

2-7 mounting hole Cooling fan exhaust

Intake

Mass: 22 [kg]

L- L+

L21

L11

PE

Terminal

TE2-1

TE3 L- L+

TE2-2 TE1-1 Screw size: M10 Tightening torque: 12.0 [Nm]

TE1-2 Screw size: M10 Tightening torque: 12.0 [Nm]

TE2-1 Screw size: M6 Tightening torque: 3.0 [Nm]

TE2-2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M10 Tightening torque: 12.0 [Nm]

TE1-1 TE1-2 PE L1 L2 L3 C P2 P1

Mounting screw Screw size: M6 Tightening torque: 5.49 [Nm]

7. DIMENSIONS

7 - 6

7.3 Drive unit

7.3.1 MR-J4-DU_B_(-RJ)

POINT Only MR-J4-DU_B_-RJ is shown for dimensions. MR-J4-DU_B_ does not have CN2L connector. The dimensions of MR-J4-DU_B_ are the same as those of MR-J4-DU_B_-RJ except CN2L connector.

(1) MR-J4-DU900B(4)(-RJ)/MR-J4-DU11KB(4)(-RJ)

[Unit: mm] 150

6045 45

38 0

36 0

10 10 6 6

Rating plate

17 0.

5

13 7

15 5

19 5

Approx. 80

Approx. 28

200 180

10

42 .5

TE1

36 26

52 97.9 103.4

105.9

PE

TE2

TE3

92 12 4.

5

11

24

100

175.5

178.5

22

PE

1

2-6 mounting hole

With MR-BAT6V1SET

Cooling fan exhaust

Intake

Mass: 9.9 [kg]

L21

L11

PE

Terminal

TE3 L- L+

TE2 TE1 Screw size: M8 Tightening torque: 6.0 [Nm]

TE2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M8 Tightening torque: 6.0 [Nm]TE1 PE

U V W

Mounting screw Screw size: M5 Tightening torque: 3.24 [Nm]

7. DIMENSIONS

7 - 7

(2) MR-J4-DU15KB(4)(-RJ)/MR-J4-DU22KB(4)(-RJ)

[Unit: mm]

240 12060 60

38 0

36 0

10 10

6 6

Rating plate

15 9.

5

14 5.

5

15 5

19 5

Approx. 80

Approx. 28

200

180

10

52

TE1 57

28

56

174

196

224.5

25

22

PE

TE2

TE3

38

92 12 4.

5

11

24

100

175.5 178.5

2-6 mounting hole

With MR-BAT6V1SET

Cooling fan exhaust

Intake

Mass: 15.2 [kg]

L21

L11

PE

Terminal

TE3 L- L+

TE2 TE1 Screw size: M8 Tightening torque: 6.0 [Nm]

TE2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M8 Tightening torque: 6.0 [Nm]TE1 PE

U V W

Mounting screw Screw size: M5 Tightening torque: 3.24 [Nm]

7. DIMENSIONS

7 - 8

(3) MR-J4-DU30KB(-RJ)/MR-J4-DU37KB(-RJ)/MR-J4-DU45KB4(-RJ)/MR-J4-DU55KB4(-RJ)

[Unit: mm]

300

21045

38 0

36 0

16 2.

5

13 0.

1 10

37 .3

20 260

7

20

10

For eyebolts

100 180

15 5

200

175.5 10

178.5

19 5

Approx. 80

Approx. 28

22.5 22 32

118 62 15.5

92 11

4159 12

4. 5

24

TE2-1 TE2-2

TE1

PE

TE3

3128

2-7 mounting hole

With MR-BAT6V1SET

Cooling fan exhaust

Intake

Mass: 21 [kg]

L- L+

L21

L11

PE

Terminal

TE2-1

TE3 L- L+

TE2-2 TE1 Screw size: M10 Tightening torque: 12.0 [Nm]

TE2-1 Screw size: M6 Tightening torque: 3.0 [Nm]

TE2-2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M10 Tightening torque: 12.0 [Nm]

TE1 U V W

Mounting screw Screw size: M6 Tightening torque: 5.49 [Nm]

7. DIMENSIONS

7 - 9

(4) MR-J4-DU30KB4(-RJ)/MR-J4-DU37KB4(-RJ)

[Unit: mm]

17 0.

5

15 2.

5 36

0 10

37 .3

60 120

38 0

240

18030

60

10

6

180 100

15 5

175.5 178.5

200 19

5

10

Approx. 80

Approx. 28

22.5 22 38

105.5

143 56

92 52

11

41

12 4.

5 24

TE2

TE1PE

TE3

28

28

For eyebolts

2-6 mounting hole Cooling fan exhaust

With MR-BAT6V1SET Intake

Mass: 16 [kg]

L- L+

L21

L11

PE

Terminal

TE2 TE3 TE1 Screw size: M8 Tightening torque: 6.0 [Nm]

TE2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M8 Tightening torque: 6.0 [Nm]

TE1 U V W

Mounting screw Screw size: M5 Tightening torque: 3.24 [Nm]

7. DIMENSIONS

7 - 10

7.3.2 MR-J4-DU_A_(-RJ)

POINT Only MR-J4-DU_A_-RJ is shown for dimensions. MR-J4-DU_A_ does not have CN2L connector. The dimensions of MR-J4-DU_A are the same as those of MR- J4-DU_A_-RJ except CN2L connector.

(1) MR-J4-DU30KA(-RJ)/MR-J4-DU37KA(-RJ)/MR-J4-DU45KA4(-RJ)/MR-J4-DU55KA4(-RJ)

[Unit: mm] 16

2. 5

13 0.

1

7

20

10

300

21045

38 0

36 0

10 37

.3

20 260 100

180

15 5

200

175.5 178.5

10

19 5

Approx. 80 Approx. 28

31

22.5 22 32

118 62

15.5

92 11

4159 12

4. 5

24

TE2-1 TE2-2

TE1

PE

TE3

28

For eyebolts

2-7 mounting hole

With MR-BAT6V1SET

Cooling fan exhaust

Intake

Mass: 21 [kg]

L- L+

L21

L11

PE

Terminal

TE2-1

TE3 L- L+

TE2-2 TE1 Screw size: M10 Tightening torque: 12.0 [Nm]

TE2-1 Screw size: M6 Tightening torque: 3.0 [Nm]

TE2-2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M10 Tightening torque: 12.0 [Nm]

TE1 U V W

Mounting screw Screw size: M6 Tightening torque: 5.49 [Nm]

7. DIMENSIONS

7 - 11

(2) MR-J4-DU30KA4(-RJ)/MR-J4-DU37KA4(-RJ)

[Unit: mm]

17 0.

5

15 2.

5 36

0 10

37 .3

60 120

38 0

240

18030

60

10

6

200 100 15

5

175.5 178.5

180

19 5

10

Approx. 80 Approx. 28

22.5 22 38 28

143 105.5

56

92 52

11

41 12

4. 5

24

28

TE2

TE1PE

TE3

For eyebolts

2-6 mounting hole Cooling fan exhaust

With MR-BAT6V1SET Intake

Mass: 16 [kg]

L- L+

L21

L11

PE

Terminal

TE2 TE3 TE1 Screw size: M8 Tightening torque: 6.0 [Nm]

TE2 Screw size: M6 Tightening torque: 3.0 [Nm]

TE3 Screw size: M4 Tightening torque: 1.2 [Nm]

PE Screw size: M8 Tightening torque: 6.0 [Nm]

TE1 U V W

Mounting screw Screw size: M5 Tightening torque: 3.24 [Nm]

7. DIMENSIONS

7 - 12

MEMO

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 1

8. OPTIONS AND PERIPHERAL EQUIPMENT

WARNING

Before connecting any option or peripheral equipment, turn off the power and wait for 20 minutes or more until the charge lamp turns off. Then, confirm that the voltage between L+ and L- is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm whether the charge lamp is off or not from the front of the converter unit.

CAUTION Use the specified peripheral equipment and options to prevent a malfunction or a fire.

POINT

We recommend using HIV wires to wire the converter units, drive units, options, and peripheral equipment. Therefore, the recommended wire sizes may different from those of the used wires for the previous converter units, drive units and others.

The following items are the same as those of MR-J4-_(-RJ). For details of the items, refer to each chapter/section of the detailed explanation field. "MR-J4-_B_" means "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". "MR-J4-_A_" means "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual".

Model Item Detailed explanation

MR-J4-DU_B_(-RJ)

Junction terminal block PS7DW-20V14B-F (recommended)

MR-J4-_B_ section 11.6

MR Configurator2 MR-J4-_B_ section 11.7 Battery MR-J4-_B_ section 11.8 Relay (recommended) MR-J4-_B_ section 11.13

MR-J4-DU_A_(-RJ)

Junction terminal block MR-TB50 MR-J4-_A_ section 11.6 MR Configurator2 MR-J4-_A_ section 11.7 Battery MR-J4-_A_ section 11.8 Relay (recommended) MR-J4-_A_ section 11.13

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 2

8.1 Cable/connector sets

POINT Refer to section 8.13 for the bus bars.

8.1.1 Combinations of cable/connector sets

Parts other than the following cable/connector sets are the same as those of MR-J4-_(-RJ). When you use MR-J4-DU_A_(-RJ), refer to section 11.1 of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual". When you use MR-J4-DU_B_(-RJ), refer to section 11.1 of "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual".

Drive unit MR-CV_ power regeneration

converter unit CN4

CN24

3)

1) CN40A

6)

7)

CN23

Drive unit MR-CR_ resistance regeneration

converter unit CNP1

CN40CN1

4)

5) 3)

CN40A 2)

1)

No. Product name Model Description Application 1) Protection

coordination cable

MR-CUL06M (Refer to section 9.1.2.)

Connector: 10120-3000PE Shell kit: 10320-52F0-008 (3M or equivalent)

Connector: PCR-S20FS+ Case: PCR-LS20LA1 (Honda Tsushin Kogyo)

2) Protection coordination cable

MR-J3CDL05M (Refer to section 9.1.2.)

Connector: 10120-3000PE Shell kit: 10320-52F0-008 (3M or equivalent)

Connector: PCR-S20FS+ Case: PCR-LS20LA1 (Honda Tsushin Kogyo)

3) Connector set MR-J2CN1-A (Refer to section 9.1.2.)

Connector: 10120-3000PE Shell kit: 10320-52F0-008 (3M or equivalent)

Connector: PCR-S20FS+ Case: PCR-LS20LA1 (Honda Tsushin Kogyo)

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 3

No. Product name Model Description Application 4) Magnetic

contactor wiring connector

MR-CR_ side connector (Phoenix Contact) Socket: GFKC 2,5/ 2-STF-7,62

Supplied with resistance regeneration converter unit

5) Digital I/O connector

MR-CR_ side connector (DDK) Connector: 17JE23090-02(D8A)K11-CG

6) Magnetic contactor wiring connector

MR-CV_ side connector Connector: 03JFAT-SAXGSA-L (JST) Open tool J-FAT-OT-EXL (JST)

Supplied with power regeneration converter unit

7) Connector set MR-CVCN24S MR-CV_ side connector Connector: DK-2100D-08R Contact: DK-2RECSLP1-100 (DDK) (Note)

Note. The crimping tool (357J-22733) (DDK) is required.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 4

8.1.2 Protection coordination cable

CAUTION Wire protection coordination cables correctly if they are fabricated. Otherwise, it may cause an unexpected operation.

POINT

MR-J3CDL05M is for the MR-CR_ resistance regeneration converter unit. MR-J3CDL05M cannot be used with the MR-CV_ power regeneration converter unit.

(1) Applications of the protection coordination cable

The cable is used to connect a converter unit to a drive unit.

Protection coordination cable Length [m] Usable converter unit Feature

MR-CUL06M 0.6 MR-CV_/MR-CR_ With ferrite core MR-J3CDL05M 0.5 MR-CR_

(2) Internal wiring diagram

1

11

2

12

3

13

4

14

5

15

6

16

7

17

8

18

9

19

10

20

Plate

1

11

2

12

3

13

4

14

5

15

6

16

Plate

7

17

8

18

9

19

10

20

ACD2

ACD2*

ACD3

ACD3*

PAL

PAL*

ACD1

ACD1*

LG

LG

GOF

GOF*

PMC

PMC*

PSD

PSD*

LG

LG

PRD

PRD*

SD

10120-3000PE (Connector) 10320-52F0-008 (Shell kit)

PCR-S20FS + (Connector) PCR-LS20LA1 (Case)

Drive unit sideConverter unit side

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 5

(3) When fabricating a cable

Prepare MR-J2CN1-A connector set, the recommended wires, and ferrite cores (only for MR-CUL06M), and fabricate the cable according to the wiring diagram in (1) in this section.

Model Length [m]

Core size

[mm2]

Number of cores

Characteristics of one core (Note 2) Cable

OD [mm]

Wire model Ferrite core Structure [Wires/mm]

Conductor resistance

[/km]

(Note 1) Insulator

OD d [mm]

MR-CUL06M 0.6 0.08

20 (10

pairs) 7/0.127 222 or

less 0.38 6.1

UL 20276 AWG#28 10pair (black)

ZCAT1518-0730-BK (TDK)

MR-J3CDL05M 0.5 UL 20276 AWG#28 10pair (cream)

Note 1. The following shows the detail of d.

InsulatorConductor

d

2. Standard OD. Maximum OD is about 10% greater. When fabricating a cable equivalent to MR-CUL06M, attach the ferrite cores as follows.

[Unit: mm]

70

600

Cable ties

Converter unit side Drive unit side

Ferrite core ZCAT1518-0730-BK (TDK)

70

Ferrite core ZCAT1518-0730-BK (TDK)

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 6

8.2 Regenerative option

CAUTION Do not use the resistance regeneration converter unit and drive unit with the regenerative options other than the combinations specified below. Otherwise, it may cause a fire.

POINT

MR-RB_ regenerative option is for the MR-CR_ resistance regeneration converter unit. MR-RB_ cannot be used with the MR-CV_ power regeneration converter unit.

8.2.1 Combination and regenerative power

The regenerative power values in the table are the regenerative power of the resistor and are not the rated power.

Resistance regeneration converter unit

Drive unit

Regenerative power [W]

MR-RB139 (1.3 )

(Note 1) Three MR-RB137 (1.3 ) in parallel

MR-RB137-4 (4 )

(Note 2) Three MR-RB13V-4

(4 ) in parallel

MR-CR55K

MR-J4-DU30KB(-RJ) MR-J4-DU30KA(-RJ) MR-J4-DU37KB(-RJ) MR-J4-DU37KA(-RJ)

1300 3900

MR-CR55K4

MR-J4-DU30KB4(-RJ) MR-J4-DU30KA4(-RJ) MR-J4-DU37KB4(-RJ) MR-J4-DU37KA4(-RJ) MR-J4-DU45KB4(-RJ) MR-J4-DU45KA4(-RJ) MR-J4-DU55KB4(-RJ) MR-J4-DU55KA4(-RJ)

1300 3900

Note 1. The resultant resistance of three options is 1.3 . 2. The resultant resistance of three options is 4 .

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 7

8.2.2 Selection of regenerative option

A regenerative option for a horizontal axis can be selected with the rough calculation shown in this section. To select a regenerative option precisely, use the capacity selection software. (1) Rotary servo motor

(a) Regenerative energy calculation Servo motor

Moving part

N V

WL

FC

2)

1) V

3)

4) Forward rotation

6)

5) 7)

Reverse rotation

8) Time

Feed speed of moving part

tpsa1 t1 tpsd1 t2 tpsa2 t3 t4tpsd2

V: Feed speed of moving part [mm/min] N: Servo motor speed (N = V/S) [r/min] S: Travel distance per servo motor

revolution (S = PB) [mm/rev]

PB: Ball screw lead [mm] LB: Ball screw length [mm] DB: Ball screw diameter [mm] WL: Moving part mass [kg] FC: Load antidrag setting [N] TL: Load torque converted into equivalent

value on servo motor shaft [Nm] [Nm]

: Drive system efficiency : Friction coefficient JL: Load moment of inertia converted into

equivalent value on servo motor shaft [kgcm2]

JM: Moment of inertia of the servo motor [kgcm2] : Pi constant g: Gravitational acceleration [m/s2]

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 8

Formulas for calculating torque and energy in operation

Regenerative power

Torque applied to servo motor [Nm] (Note 1, 2) Energy E [J]

1) T1 = 9.55 104 (JL/+ JM) N

tpsa1

1 + TL E1 = 2

0.1047 N T1 tpsa1

2) T2 = TL E2 = 0.1047 N T2 t1

3) T3 = 9.55 104 -(JL + JM) N

tpsd1

1 + TL E3 = 2

0.1047 N T3 tpsd1

4), 8) T4, T8 = 0 E4, E8 = 0 (No regeneration)

5) T5 = 9.55 104

(JL/+ JM) N tpsa2

1 + TL E5 = 2

0.1047 N T5 tpsa2

6) T6 = TL E6 = 0.1047 N T6 t3

7) T7 = 9.55 104 -(JL + JM) N

tpsd2

1 + TL E7 = 2

0.1047 N T7 tpsd2

Note 1. Load torque converted into equivalent value on servo motor shaft TL can be calculated

with the following expression. TL = {(FC + ( WL g)) S}/(2000 )

2. Load moment of inertia converted into equivalent value on servo motor shaft JL can be calculated with the following expression. JL = JL1 + JL2 + JL3

JL1 is the load moment of inertia of the moving part, JL2 is the load moment of inertia of the ball screw, and JL3 is the load moment of inertia of the coupling. JL1 and JL2 can be calculated with the following expressions. JL1 = WL (S/(20 ))2 JL2 = {( 0.0078 (LB/10))/32} (DB/10)4

From the calculation results in 1) to 8), find the absolute value (Es) of the sum total of negative energies.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 9

(2) Regenerative loss of servo motor and drive unit

The following table lists the efficiencies and other data of the servo motor and drive unit in the regenerative mode.

Resistance

regeneration converter unit

Drive unit Inverse efficiency [%]

Capacitor charging [J]

MR-CR55K

MR-J4-DU30KB(-RJ) MR-J4-DU30KA(-RJ) MR-J4-DU37KB(-RJ) MR-J4-DU37KA(-RJ)

90 450

MR-CR55K4

MR-J4-DU30KB4(-RJ) MR-J4-DU30KA4(-RJ) MR-J4-DU37KB4(-RJ) MR-J4-DU37KA4(-RJ) MR-J4-DU45KB4(-RJ) MR-J4-DU45KA4(-RJ) MR-J4-DU55KB4(-RJ) MR-J4-DU55KA4(-RJ)

Inverse efficiency (m): Efficiency including some efficiencies of the servo motor and drive unit when

rated (regenerative) torque is generated at rated speed. Efficiency varies with the speed and generated torque. Since the characteristics of the electrolytic capacitor change with time, allow for approximately 10% higher inverse efficiency.

Capacitor charging (Ec): Energy charged into the electrolytic capacitor in the resistance regeneration converter unit

Subtract the capacitor charging from the result of multiplying the sum total of regenerative energies by the inverse efficiency to calculate the energy consumed by the regenerative option.

ER [J] = m Es - Ec

Calculate the power consumption of the regenerative option on the basis of one-cycle operation period tf [s] to select the necessary regenerative option.

PR [W] = ER/tf

8.2.3 Parameter setting

POINT The regenerative option cannot be connected to the drive unit. Always set [Pr. PA02] of the drive unit to "_ _ 0 0" (the regenerative option is not used).

Set [Pr. PA01] of the resistance regeneration converter unit according to the option to be used.

Regenerative option selection 00: Regenerative option is not used. 01: MR-RB139 02: MR-RB137 (3 pcs.) 13: MR-RB137-4 14: MR-RB13V-4 (3 pcs.)

[Pr. PA01]

00

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 10

8.2.4 Connection of regenerative option

POINT For the wire sizes used for wiring, refer to section 8.4.

The regenerative option generates heat of 100 C higher than the ambient temperature. Fully consider heat dissipation, installation position, wires used, etc. before installing the option. For wiring, use flame-resistant wires or make the wires flame-resistant and keep them away from the regenerative option. The G3 and G4 terminals act as a thermal protector. Between G3 and G4 is opened when the regenerative option overheats abnormally. Always use twisted cables of max. 5 m length for connection with the resistance regeneration converter unit. (1) Cooling fan

Always supply the following power to a cooling fan.

Item 200 V class 400 V class Model MR-RB137/MR-RB139 MR-RB137-4/MR-RB13V-4

Voltage/Frequency 1-phase 198 V AC to 242 V AC, 50 Hz/60 Hz

1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz

Power consumption [W] 20 (50 Hz)/18 (60 Hz) 20 (50 Hz)/18 (60 Hz)

(2) MR-RB139/MR-RB137-4

R1

Resistance regeneration converter unit

P1 P2

(Note 1)

Power factor improving DC reactor (optional)

C

G4G3 P C

Regenerative option Cooling fan

(Note 2)

5 m or less

(Note 3) Power supply

(Note 4) S1

24 V DC RA P1

P2

Note 1. When using the power factor improving DC reactor, remove the short bar across P1 and P2. 2. G3-G4 contact specifications

Maximum voltage: 120 V AC/DC Maximum current: 0.5 A/4.8 V DC Maximum capacity: 2.4 VA

3. For specifications of cooling fan power supply, refer to (1) in this section. 4. For MR-RB137-4, "R1" is "R400" and "S1" is "S400".

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 11

(3) MR-RB137/MR-RB13V-4

POINT Three of MR-RB137 or MR-RB13V-4 are required per resistance regeneration converter unit. Please purchase three of MR-RB137 or MR-RB13V-4.

Resistance regeneration

converter unit

P1 P2

(Note 1)

C

G4G3 P C

G4G3 P C

G4G3 P C (Note 2)

5 m or less

R1 (Note 4)

S1R1 (Note 4)

S1R1 (Note 4)

S1

24 V DC RA P1

P2

Power factor improving DC reactor (optional)

Regenerative option Cooling fan

Regenerative option Cooling fan

Regenerative option Cooling fan

(Note 3) Power supply

Note 1. When using the power factor improving DC reactor, remove the short bar across P1 and P2.

2. G3-G4 contact specifications Maximum voltage: 120 V AC/DC Maximum current: 0.5 A/4.8 V DC Maximum capacity: 2.4 VA

3. For specifications of cooling fan power supply, refer to (1) in this section. 4. For MR-RB13V-4, "R1" is "R400" and "S1" is "S400".

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 12

8.2.5 Dimensions

[Unit: mm]

48 0

10

260

230

2-10 mounting hole

10

50 0

10

15 15

Cooling fan (Note 1)

1523015

30 42

7 43

197

Intake

15

2.3

215

G4 G3 C PR1 (Note 2)

S1 (Note 2)

Mass [kg]

11

10

Mounting screw: M5 Tightening torque: 2.0 [Nm]

Terminal block signal layout TE1

Regenerative option

MR-RB139/MR-RB137-4

MR-RB137/MR-RB13V-4

Mounting screw Screw size: M8 Tightening torque: 13.2 [Nm]

Note 1. One cooling fan for MR-RB137-4/MR-RB13V-4. 2. For MR-RB137-4/MR-RB13V-4, "R1" is "R400" and "S1" is "S400".

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 13

8.3 External dynamic brake

CAUTION

Use an external dynamic brake for this drive unit. Failure to do so will cause an accident because the servo motor does not stop immediately but coasts at an alarm occurrence for which the servo motor does not decelerate to stop. Ensure the safety in the entire equipment. For alarms for which the servo motor does not decelerate to stop, refer to chapter 6. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB. Doing so will cause the drive unit to become servo- off when an instantaneous power failure occurs.

POINT

For drive units, EM2 has the same function as EM1 in the torque control mode. Configure a sequence which switches off the magnetic contactor of the external dynamic brake after (or as soon as) SON (Servo-on) has been turned off at a power failure or a malfunction. For the external braking time taken when the dynamic brake is operated, refer to section 5.4.2. The external dynamic brake is rated for a short duration. Do not use it very frequently. When the 400 V class external dynamic brake is used, the power supply voltage is restricted to 1-phase 380 V AC to 463 V AC (50 Hz/60 Hz). The specifications of the input power supply for external dynamic brake used for drive units of 30 kW or more are the same as those of the converter unit control circuit power supply. When an alarm, [AL. E6 Servo forced stop warning], or [AL. E7 Controller forced stop warning] occurs, or the power is turned off, the external dynamic brake will operate. Do not use external dynamic brake to stop in a normal operation as it is the function to stop in emergency. For a machine operating at the recommended load to motor inertia ratio or less, the estimated number of usage times of the external dynamic brake is 1000 times while the machine decelerates from the rated speed to a stop once in 10 minutes. Be sure to enable EM1 (Forced stop 1) after servo motor stops when using EM1 frequently in other than emergency.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 14

8.3.1 Selection of external dynamic brake

The external dynamic brake is designed to bring the servo motor to a sudden stop when a power failure occurs or the protective circuit is activated. For MR-J4-DU_A_(-RJ) drive unit, assign DB to any of CN1-22 to CN1-25, CN1-49, CN1-13 and CN1-14 pins in [Pr. PD23] to [Pr. PD26], [Pr. PD28] and [Pr. PD47]. For MR- J4-DU_B_(-RJ) drive unit, assign DB to any of CN3-9, CN3-13, and CN3-15 pins in [Pr. PD07] to [Pr. PD09].

Drive unit External dynamic brake

Molded-case circuit breaker Fuse (Class T) Fuse (Class K5) Frame, rated

current Voltage AC

[V] Current [A] Voltage AC [V] Current [A] Voltage AC

[V]

MR-J4-DU900B(-RJ) DBU-7K-R6

DBU-11K (Note 1)

30 A frame 5 A 240 1 300 1 250

MR-J4-DU11KB(-RJ) DBU-11K MR-J4-DU15KB(-RJ) DBU-15K MR-J4-DU22KB(-RJ) DBU-22K-R1 MR-J4-DU30KB(-RJ) MR-J4-DU30KA(-RJ)

DBU-37K-R1 MR-J4-DU37KB(-RJ) MR-J4-DU37KA(-RJ)

MR-J4-DU900B4(-RJ) DBU-7K-4-2R0

DBU-11K-4 (Note 2)

30 A frame 5 A 480 1 600 1 600

MR-J4-DU11KB4(-RJ) DBU-11K-4 MR-J4-DU15KB4(-RJ) MR-J4-DU22KB4(-RJ)

DBU-22K-4

MR-J4-DU30KB4(-RJ) MR-J4-DU30KA4(-RJ)

DBU-55K-4-R5

MR-J4-DU37KB4(-RJ) MR-J4-DU37KA4(-RJ) MR-J4-DU45KB4(-RJ) MR-J4-DU45KA4(-RJ) MR-J4-DU55KB4(-RJ) MR-J4-DU55KA4(-RJ)

Note 1. When HG-JR801 or HG-JR903 is used. 2. When HG-JR8014 or HG-JR9034 is used.

8.3.2 Connection example

(1) For MR-CV_ power regeneration converter unit Use the following wires to connect the dynamic brake.

External dynamic brake

Wire [mm2] (Note) U/V/W Except U/V/W

DBU-7K-R6 3.5 (AWG 12)

2 (AWG 14)

DBU-11K DBU-15K

DBU-22K-R1 5.5 (AWG 10)

DBU-37K-R1 14 (AWG 6) DBU-7K-4-2R0 3.5 (AWG 12)

DBU-11K-4 DBU-22K-4

5.5 (AWG 10)

DBU-55K-4-R5 14 (AWG 6)

Note. Selection conditions of wire size are as follows. Wire type: 600 V grade heat-resistant polyvinyl chloride insulated wire (HIV wire) Construction condition: Single wire set in midair

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 15

RA1

RA3

Drive unit 1 Power regeneration

converter unit

L1

L2

L3

L11

L21

U

V

W

U

V

W

M

Servo motor

L+

L-

L+

L-

(Note 1)

1MC1

3MC2

CN23

L11

L21

EM2

3

20

SDPlate

DICOM10

DB(Note 3)

(Note 7)

DOCOM

5 DICOM

ALM15

External dynamic brake

13 W14 V U a

bRA3

Dynamic brake interlock

MC

24 V DC

(Note 5)

(Note 6) Main circuit power supply

Operation ready OFF/ONRA1

Drive unit malfunction Emergency stop

switch MC

SK

(Note 2)

(Note 8, 9)

L22

L32

L21

L31

AC reactor L12L11

(Note 4) Power supply

MCCB

(Note 8, 9)

(Note 8) (Note 10)

Note 1. Terminals 13 and 14 are normally open contact outputs. If the dynamic brake is seized, terminals 13 and 14 will open. Therefore, configure an external sequence to prevent servo-on.

2. Step-down transformer is required when coil voltage of the magnetic contactor is 200 V class, and the power regeneration converter unit and the drive unit are 400 V class.

3. Assign DB (Dynamic brake interlock) with the parameter. 4. For the power supply specifications, refer to section 1.4. 5. A bus voltage may drop, depending on the main circuit voltage and operation pattern, causing a dynamic brake deceleration

during a forced stop deceleration. When dynamic brake deceleration is not required, delay the time to turn off the magnetic contactor.

6. Turn off EM2 when the main power circuit power supply is off. 7. The wiring is for MR-J4-DU_B_(-RJ). 8. Install an overcurrent protection device (molded-case circuit breaker, fuse, or others) to protect the branch circuit. (Refer to

section 8.5 and section 8.3.1.) 9. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device. 10. The power supply voltage of the inside magnet contactor for 400 V class external dynamic brake DBU-7K-4-2R0, DBU-11K-4,

and DBU-22K-4 is restricted to 1-phase 380 V AC to 463 V AC (50 Hz/60 Hz). When these external dynamic brakes are used, use them within the range of the power supply.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 16

(2) MR-CR_ resistance regeneration converter unit

Use the following wires to connect the dynamic brake.

Dynamic brake Wire [mm2] (Note)

Except U/V/W U/V/W DBU-37K-R1

14 (AWG 6) 2 (AWG 14) DBU-55K-4-R5

Note. Selection conditions of wire size are as follows.

Wire type: 600 V grade heat-resistant polyvinyl chloride insulated wire (HIV wire) Construction condition: Single wire set in midair

Resistance

regeneration converter unit malfunction

RA1

RA3

(Note 4) Power supply

Drive unit Resistance regeneration

converter unit

L1

L2

L3

L11

L21

U

V

W

U

V

W

M

Servo motor

L+

L-

L+

L-

(Note 1)

1MC1

2MC2

CNP1

L11

L21

EM2

3

20

SDPlate

DICOM10

DB(Note 3, 9)

DOCOM

5 DICOM

ALM15

CN3

CN1 1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

RA2

External dynamic brake

13 W14 V U a

bRA3

Dynamic brake interlock

MCMCCB

24 V DC

24 V DC

(Note 5)

(Note 6) Main circuit power supply

RA1

Drive unit malfunction

MC

SK

(Note 7)

(Note 2)

(Note 8, 10)

(Note 8, 10)

(Note 8)

RA2 Operation ready

OFF/ON

Emergency stop switch

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 17

Note 1. Terminals 13 and 14 are normally open contact outputs. If the dynamic brake is seized, terminals 13 and 14 will open.

Therefore, configure an external sequence to prevent servo-on. 2. Step-down transformer is required when coil voltage of the magnetic contactor is 200 V class, and the resistance regeneration

converter unit and the drive unit are 400 V class. 3. Assign DB (Dynamic brake interlock) with the parameter. 4. For the power supply specifications, refer to section 1.4. 5. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop

deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

6. Turn off EM2 when the main power circuit power supply is off. 7. The wiring is for MR-J4-DU_B_(-RJ). The connection for the interface of MR-J4-DU_(-RJ) is the same as in the case of MR-

J4-_(-RJ). Refer to each servo amplifier instruction manual. 8. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section 8.5

and section 8.3.1.) 9. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB. Doing so will cause

the drive unit to become servo-off when an instantaneous power failure occurs. 10. The control circuit power supply (L11/L21) can be connected by passing wiring. Refer to section 6.8 for the wire size and the

selection of the overcurrent protection device.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 18

8.3.3 Timing chart

Servo motor speed

Coasting

Alarm

ON

OFF

Emergency stop switch

Absent

Disabled

Enabled

Short

Open

a. Timing chart at alarm occurrence b. Timing chart at Emergency stop switch enabled

Dynamic brake

Base circuit

ON

OFF

Coasting

Dynamic brakeDynamic brake

Present

DB (Dynamic brake interlock)

(Note 2) 15 ms to 60 ms

(Note 1) 7 ms

10 ms

Dynamic brake Coasting

Electro magnetic brake interlock

Electro magnetic brake operation delay time

MBR (Electromagnetic brake interlock)

Base circuit ON

OFF

Servo motor speed

ALM (Malfunction)

Main circuit Control circuit

ON

OFF Power

Dynamic brake

ON

OFF

ON OFF (Valid)

ON

OFF

Disabled Enabled

DB (Dynamic brake interlock)

Note 1. When powering off, DB will be turned off, and the base circuit is turned off earlier than usual before an output shortage occurs. (only when DB is assigned as an output signal)

2. Variable according to the operation status.

c. Timing chart when both of the main and control circuit power supply are off

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 19

8.3.4 Dimensions

(1) DBU-7K-R6/DBU-11K/DBU-15K/DBU-22K-R1 [Unit: mm]

C D 100 D

5 E E

B A

5

F 2.3G

Terminal block TE1

a b 13 14

Screw: M3.5 Tightening torque: 0.8 [Nm]

TE2

WVU

Screw: M4 Tightening torque: 1.2 [Nm]

External dynamic brake A B C D E F G Mass [kg]

DBU-7K-R6 DBU-11K

200 190 140 20 5 170 163.5 2

DBU-15K DBU-22K-R1

250 238 150 25 6 235 228 6

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 20

(2) DBU-7K-4-2R0/DBU-11K-4/DBU-22K-4

[Unit: mm]

15

51

25

15

73.75 7

25150

10

200

170

17 8.

5

17 9.

5 15

26 0

28 0

43

10

2-7 mounting hole

195

22 8

26 26

210

2.3

Mass: 6.7 [kg]

Terminal block TE1

a b 13 14

Screw: M3.5 Tightening torque: 0.8 [Nm]

TE2

WVU

Screw: M4 Tightening torque: 1.2 [Nm]

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 21

(3) DBU-37K-R1/DBU-55K-4-R5

TE2

U V W

Screw size: M5 Tightening torque: 2.0 [Nm]

a b

Screw size: M3.5 Tightening torque: 0.8 [Nm]

13 14

TE

[Unit: mm]

Mass [kg]

11

8

External dynamic brake

DBU-37K-R1

DBU-55K-4-R5

39 0

37 0

10 10

260

230 1515

10

1515 230

30 33

0 30

220 15

235

2-10 mounting hole

2.3

TE2 TE1

Terminal block

Mounting screw Screw size: M8 Tightening torque: 13.2 [Nm]

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 22

8.4 Selection example of wires

POINT To comply with the IEC/EN/UL/CSA standard, use the wires shown in section 10.2 for wiring. To comply with other standards, use a wire that is complied with each standard. Selection conditions of wire size are as follows. Construction condition: Single wire set in midair Wire length: 50 m or less

8.4.1 Connection of converter unit and drive unit

The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.

Regenerative option

Converter unit Drive unit Servo motor

C

P1

P2

L1

L2

L3

L11

L21

V

U

W

V

U

W Motor

Encoder

L11

L21

2) Control circuit power supply lead

1) Main circuit power supply lead

4) Motor power supply lead

Encoder cable

3) Regenerative option lead

4)

Power factor improving DC reactor

Power supply

1)

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 23

(1) Example of selecting the wire sizes

Use the 600 V grade heat-resistant polyvinyl chloride insulated wire (HIV wire) for wiring. The following shows the wire size selection example.

Converter unit

(Note 2) Drive unit (Note 2)

Wire [mm2] (Note 1, 3) 1)

L1/L2/L3/ 2)

L11/L21 3)

P2/C 4)

P1/P2 MR-CV11K

8 (AWG 8): h

1.25 to 2 (AWG 16 to 14): g (Note 4)

MR-CV18K 22 (AWG 4): q MR-CV30K 38 (AWG 2): n MR-CV37K 60 (AWG 2/0): j MR-CV45K 60 (AWG 2/0): j MR-CV55K 80 (AWG 3/0): k MR-CV11K4 5.5 (AWG 10): l MR-CV18K4 8 (AWG 8): h MR-CV30K4 14 (AWG 6): m MR-CV37K4 22 (AWG 4): e MR-CV45K4 22 (AWG 4): e MR-CV55K4 38 (AWG 2): n MR-CV75K4 60 (AWG 2/0): j

MR-CR55K MR-J4-DU30K_(-RJ) 38 (AWG 2): c

5.5 (AWG 10): a

60 (AWG 2/0): d MR-J4-DU37K_(-RJ) 60 (AWG 2/0): d 60 (AWG 2/0): d

MR-CR55K4

MR-J4-DU30K_4(-RJ) 22 (AWG 4): b 22(AWG 4): b MR-J4-DU37K_4(-RJ) 22 (AWG 4): b 38 (AWG 2): c MR-J4-DU45K_4(-RJ) 38 (AWG 2): c 38 (AWG 2): c MR-J4-DU55K_4(-RJ) 38 (AWG 2): c 38 (AWG 2): c

Note 1. Alphabets in the table indicate crimping tools. For crimp terminals and applicable tools, refer to (2) in this section. 2. To connect these models to a terminal block, be sure to use the screws that come with the terminal block. 3. Wires are selected based on the highest rated current among combining servo motors. 4. Be sure to use the size of 2 mm2 when corresponding to the IEC/EN/UL/CSA standard.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 24

Drive unit (Note 2)

Wire [mm2] (Note 1, 3) 5)

U/V/W/ 2)

L11/L21 MR-J4-DU900B(-RJ) 14 (AWG 6): m

1.25 to 2 (AWG 16 to 14): g (Note 4)

MR-J4-DU11KB(-RJ) 14 (AWG 6): m MR-J4-DU15KB(-RJ) 22 (AWG 4): e MR-J4-DU22KB(-RJ) 38 (AWG 2): n MR-J4-DU30KB(-RJ) MR-J4-DU30KA(-RJ)

60 (AWG 2/0): d

MR-J4-DU37KB(-RJ) MR-J4-DU37KA(-RJ)

60 (AWG 2/0): d

MR-J4-DU900B4(-RJ) 8 (AWG 8): o MR-J4-DU11KB4(-RJ) 8 (AWG 8): o MR-J4-DU15KB4(-RJ) 8 (AWG 8): o MR-J4-DU22KB4(-RJ) 14 (AWG 6): m MR-J4-DU30KB4(-RJ) MR-J4-DU30KA4(-RJ)

22 (AWG 4): e

MR-J4-DU37KB4(-RJ) MR-J4-DU37KA4(-RJ)

22 (AWG 4): e

MR-J4-DU45KB4(-RJ) MR-J4-DU45KA4(-RJ)

38 (AWG 2): c

MR-J4-DU55KB4(-RJ) MR-J4-DU55KA4(-RJ)

38 (AWG 2): c

Note 1. Alphabets in the table indicate crimping tools. For crimp terminals and applicable

tools, refer to in this section. 2. To connect these models to a terminal block, be sure to use the screws that

come with the terminal block. 3. Wires are selected based on the highest rated current among combining servo

motors. 4. Be sure to use the size of 2 mm2 when corresponding to the IEC/EN/UL/CSA

standard.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 25

(2) Selection example of crimp terminals

The following shows the selection example of crimp terminals for terminal blocks of the drive unit and converter unit when you use wires mentioned in (1) in this section.

Symbol Drive unit/converter unit-side crimp terminal

Crimp terminal (Note 2)

Applicable tool Manufacturer

Body Head Dice a FVD5.5-10 YNT-1210S

JST

b FVD22-10 YF-1 E-4

YNE-38 DH-123 DH-113

c (Note 1)

R38-10 YPT-60-21

TD-124 TD-112 YF-1

E-4 YET-60-1

d (Note 1)

R60-10 YPT-60-21

TD-125 TD-113 YF-1

E-4 YET-60-1

e FVD22-8 YF-1 E-4

YNE-38 DH-123 DH-113

g FVD2-4 YNT-1614

h FVD8-5 YF-1 E-4

YNE-38 DH-121 DH-111

j (Noe 1)

60-S8 YPT-60N

TD-125 TD-113 YF-1

E-4 YET-60-1

k (Note 1)

80-10 YPT-150-1

TD-227 TD-214 YF-1

E-4 YET-150-1

l FVD5.5-5 YNT-1210S

m FVD14-8 YF-1 E-4

YNE-38 DH-122 DH-112

n FVD38-8 YF-1 E-4

YNE-38 DH-124 DH-114

o FVD8-8 YF-1 E-4

YNE-38 DH-121 DH-111

p FVD5.5-8 YNT-1210S

q (Note 1)

22-S5 YPT-60N

DH-123 DH-112 YF-1

E-4 YET-60-1

Note 1. Coat the crimping part with an insulation tube. 2. Some crimp terminals may not be mounted.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 26

8.4.2 Connection of power regeneration converter unit and servo amplifier

POINT When fuse is interposed in the wiring for the DC power supply between the converter unit and servo amplifier, use the wire whose size enable the protection coordination of the wire and fuse.

The following shows the wires used for wiring. Use the wires given in this section or equivalent wires.

L+

L-

P4

N-

P4

N-

Servo amplifier 1 Servo amplifier 2 Power regeneration

converter unit Junction terminals

DC power lead 1

To the next servo amplifier

DC power lead 1

DC power lead 2

DC power lead 2

(1) Wire size The following table indicates the connection wire sizes of the DC power supply (L+/P4 and L-/N-) between the MR-CV and servo amplifier. Use the 600 V grade heat-resistant polyvinyl chloride insulated wire (HIV wire) for wiring.

(a) 200 V

DC power supply lead 1 Total of servo amplifier

capacities [kW]

DC power supply lead 2 Servo amplifier capacity Wire[mm2]

1.9 or less 100 W/200 W/400 W/ 600 W/750 W/1 kW 2 (AWG 14)

From over 1.9 to 3.1 2 kW 3.5 (AWG 12) From over 3.1 to 5.2 3.5 kW/5 kW 5.5 (AWG 10) From over 5.2 to 8.0 7 kW 8 (AWG 8)

From over 8.0 to 11.3 11 kW 14 (AWG 6) From over 11.3 to 15.4 15 kW 22 (AWG 4) From over 15.4 to 20.1 38 (AWG 2) From over 20.1 to 26.2 22 kW 50 (AWG 1/0) (Note) From over 26.2 to 27.5 60 (AWG 2/0) (Note)

Note. 50 mm2 and 60 mm2 wires cannot be installed to L + / L- of MR-CV_. Connect two

wires whose total cross-sectional area of the conductor is equal to or larger than the cross-sectional area shown in this table or connect the wires one by one from TE2-1 or TE2-2.

(b) 400 V

DC power supply lead 1 Total of servo amplifier

capacities [kW]

DC power supply lead 2 Servo amplifier capacity Wire [mm2]

4.4 or less 600 W/1 kW/2 kW/3.5 kW 2 (AWG 14) From over 4.4 to 6.6 5 kW 3.5 (AWG 12) From over 6.6 to 9.9 7 kW 5.5 (AWG 10)

From over 9.9 to 15.2 11 kW/15 kW 8 (AWG 8) From over 15.2 to 22.1 22 kW 14 (AWG 6) From over 22.1 to 27.5 22 (AWG 4)

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 27

(c) Wire size selection example

When connecting multiple servo amplifiers, always use junction terminals for wiring the servo amplifier terminals P4 and N-. Also, connect the servo amplifiers in the order of larger to smaller capacities.

L+

L-

P4

N-

Servo amplifier (15 kW)60 mm2

Overall wiring length 5 m or less

First unit: 60 mm2 assuming that the total of servo amplifier capacities is 27.5 kW since 15 kW + 7 kW + 3.5 kW + 2.0 kW = 27.5 kW.

P4

N-

P4

N-

P4

N-

22 mm2

8 mm2

Junction terminals

22 mm2

8 mm2

5.5 mm2

3.5 mm2

Second unit: 22 mm2 assuming that the total of servo amplifier capacities is 15 kW since 7 kW + 3.5 kW + 2.0 kW = 12.5 kW.

Third unit: 8 mm2 assuming that the total of servo amplifier capacities is 7 kW since 3.5 kW + 2.0 kW = 5.5 kW.

MR-CV55K

Servo amplifier (7 kW)

Servo amplifier (3.5 kW)

Servo amplifier (2 kW)

Wire as short as possible.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 28

8.5 Molded-case circuit breakers, fuses, magnetic contactors

8.5.1 For main circuit power supply

CAUTION To prevent the converter unit and the drive unit from smoke and a fire, select a molded-case circuit breaker which shuts off with high speed. Always use one molded-case circuit breaker and one magnetic contactor with one converter unit.

When using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in this section.

Power regeneration converter unit

Molded-case circuit breaker (Note 1, 3) Fuse Magnetic

contactor (Note 2) Frame, rated current Voltage

AC [V] Class Current [A]

Voltage AC [V]

MR-CV11K 50 A frame 50 A

240

T

100

300

S-T35 MR-CV18K 100 A frame 100 A 175 S-T65 MR-CV30K 225 A frame 150 A 300 S-N125 MR-CV37K 225 A frame 175 A 350 S-N125 MR-CV45K 225 A frame 225 A 400 S-N150 MR-CV55K 400 A frame 300 A 600 S-N220 MR-CV11K4 30 A frame 30 A

480

50

600

S-T21 MR-CV18K4 50 A frame 50 A 100 S-T35 MR-CV30K4 100 A frame 80 A 175 S-T65 MR-CV37K4 100 A frame 100 A 200 S-T80 MR-CV45K4 125 A frame 125 A 250 S-T100 MR-CV55K4 225 A frame 150 A 300 S-N125 MR-CV75K4 225 A frame 200 A 350 S-N150

Note 1. For compliance with the IEC/EN/UL/CSA standard, refer to section 10.2. 2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. 3. Use a molded-case circuit breaker having the operation characteristics equal to or higher than Mitsubishi Electric general-

purpose products.

Resistance regeneration converter unit

Drive unit

Molded-case circuit breaker (Note 1, 3) Fuse Magnetic contactor (Note 2)

Frame, rated current Voltage AC [V] Class Current [A] Voltage

AC [V] Power factor improving DC

reactor is not used

Power factor improving DC reactor is used

MR-CR55K

MR-J4- DU30K_(-RJ) 225 A frame 175 A 225 A frame 150 A

240 T 300

300 S-N150

MR-J4- DU37K_(-RJ) 225 A frame 225 A 225 A frame 175 A 400 S-N180

MR-CR55K4

MR-J4- DU30K_4(-RJ) 100 A frame 100 A 100 A frame 80 A

480 T

175

600

S-N65 S-T65

MR-J4- DU37K_4(-RJ) 125 A frame 125 A 100 A frame 100 A 200

S-N80 S-T80

MR-J4- DU45K_4(-RJ) 225 A frame 150 A 125 A frame 125 A 300

S-N95 S-T100

MR-J4- DU55K_4(-RJ) 225 A frame 175 A 225 A frame 150 A 300 S-N150

Note 1. For compliance with the IEC/EN/UL/CSA standard, refer to section 10.2. 2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. 3. Use a molded-case circuit breaker having the operation characteristics equal to or higher than Mitsubishi Electric general-

purpose products.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 29

8.5.2 For control circuit power supply

Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (1) Converter unit

Converter unit Molded-case circuit breaker (Note) Fuse (Class T) Fuse (Class K5)

Frame, rated current Voltage AC [V] Current [A] Voltage AC [V] Current [A] Voltage AC [V] MR-CR55K MR-CV11K MR-CV18K MR-CV30K MR-CV37K MR-CV45K

30 A frame 5 A 240 1 300 1 250

MR-CR55K4 MR-CV11K4 MR-CV18K4 MR-CV30K4 MR-CV37K4 MR-CV45K4 MR-CV55K4 MR-CV75K4

30 A frame 5 A 480 1 600 1 600

Note. When having the converter unit comply with the IEC/EN/UL/CSA standard, refer to section 10.2.

(2) Drive unit

Drive unit Molded-case circuit breaker (Note) Fuse (Class T) Fuse (Class K5)

Frame, rated current Voltage AC [V] Current [A] Voltage AC [V] Current [A] Voltage AC [V] MR-J4-DU900B(-RJ) MR-J4-DU11KB(-RJ) MR-J4-DU15KB(-RJ) MR-J4-DU22KB(-RJ) MR-J4-DU30KB(-RJ) MR-J4-DU30KA(-RJ) MR-J4-DU37KB(-RJ) MR-J4-DU37KA(-RJ)

30 A frame 5 A 240 1 300 1 250

MR-J4-DU900B4(-RJ) MR-J4-DU11KB4(-RJ) MR-J4-DU15KB4(-RJ) MR-J4-DU22KB4(-RJ) MR-J4-DU30KB4(-RJ) MR-J4-DU30KA4(-RJ) MR-J4-DU37KB4(-RJ) MR-J4-DU37KA4(-RJ) MR-J4-DU45KB4(-RJ) MR-J4-DU45KA4(-RJ) MR-J4-DU55KB4(-RJ) MR-J4-DU55KA4(-RJ)

30 A frame 5 A 480 1 600 1 600

Note. When having the drive unit comply with the IEC/EN/UL/CSA standard, refer to section 10.2.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 30

(3) Passing wiring of the control circuit power supply

When the control circuit power supply is connected by passing wiring, wire L11 and L21 as follows. Use the 600 V grade heat-resistant polyvinyl chloride insulated wire (HIV wire) of 2 mm2 (AWG 14) for wiring. The units are shown with the terminal cover open.

Molded-case circuit breaker (MCCB) (Note)

MR-CV55K4 MR-J4-DU55KB4 MR-J4-DU22KB4 MR-J4-DU11KB4 Power supply

R S

Note. Install a molded-case circuit breaker dedicated to the control circuit power supply. Do not use a molded-case circuit breaker for the main circuit power supply.

(a) Molded-case circuit breaker

Use AWG 14 wire for wiring. Use a molded-case circuit breaker having the operation characteristics not activated with a inrush current.

Model

Number of drive units Voltage AC [V] 1 2 3 4 5

MR-CR55K 30 A frame 10 A

240

MR-CV11K 30 A frame 5 A 30 A frame 10 A

30 A frame 15 A

MR-CV18K MR-CV30K

30 A frame 10 A 30 A frame 15 A MR-CV37K MR-CV45K MR-CV55K MR-CR55K4 30 A frame 10 A

480

MR-CV11K4 30 A frame 5 A 30 A frame 10 A

30 A frame 10 A

MR-CV18K4 MR-CV30K4

30 A frame 10 A 30 A frame 15 A MR-CV37K4 MR-CV45K4 MR-CV55K4 MR-CV75K4

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 31

(b) Fuse

Use AWG 14 wire for wiring. Use a fuse having the fusing characteristics not blown with repeated inrush currents.

Model

Number of drive units Voltage AC [V] 1 2 3 4 5

MR-CR55K 30 A frame 3 A

250

MR-CV11K 30 A frame 2 A 30 A frame 2 A 30 A frame 3 A 30 A frame 3 A 30 A frame 4 A

MR-CV18K MR-CV30K

30 A frame 2 A 30 A frame 3 A 30 A frame 3 A 30 A frame 3 A 30 A frame 4 A MR-CV37K MR-CV45K MR-CV55K MR-CR55K4 30 A frame 5 A

600

MR-CV11K4 30 A frame 5 A 30 A frame 5 A 30 A frame 5 A 30 A frame 5 A 30 A frame 5 A

MR-CV18K4 MR-CV30K4

30 A frame 5 A 30 A frame 5 A 30 A frame 15 A 30 A frame 15 A 30 A frame 5 A MR-CV37K4 MR-CV45K4 MR-CV55K4 MR-CV75K4

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 32

8.6 Power factor improving DC reactor

POINT MR-DCL_ power factor improving DC reactor is for the MR-CR_ resistance regeneration converter unit. MR-DCL_ cannot be used with the MR-CV_ power regeneration converter unit.

The following shows the advantages of using power factor improving DC reactor.

It improves the power factor by increasing the form factor of the resistance regeneration converter unit's input current. It decreases the power supply capacity. The input power factor is improved to about 95%.

When connecting the power factor improving DC reactor to the resistance regeneration converter unit, be sure to remove the short bar across P1 and P2. If it remains connected, the effect of the power factor improving DC reactor is not produced. When used, the power factor improving DC reactor generates heat. To release heat, therefore, leave a 10 cm or more clearance at each of the top and bottom, and a 5 cm or more clearance on each side.

Resistance regeneration converter unit

Drive unit Power factor improving DC reactor

Variable dimensions [mm] Terminal screw

Mass [kg] W D H W1 X

MR-CR55K MR-J4-DU30K_(-RJ) MR-DCL30K

135

255 215 80 232 M12 9.5 MR-J4-DU37K_(-RJ) MR-DCL37K

MR-CR55K4

MR-J4-DU30K_4(-RJ) MR-DCL30K-4 205 200

75 175

M8

6.5 MR-J4-DU37K_4(-RJ) MR-DCL37K-4 225

80 197 7

MR-J4-DU45K_4(-RJ) MR-DCL45K-4 240 212 7.5 MR-J4-DU55K_4(-RJ) MR-DCL55K-4 260 215 232 9.5

[Unit: mm]

H o

r l es

s

X

D or less

Terminal cover Terminal screw

Terminal block (M3.5 screw) For thermal protector

P1 P2

Approx. W1

W or less Mounting hole for M8

+1.5 -1.5

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 33

8.7 AC reactor

POINT MR-AL_ AC reactor is for the MR-CV_ power regeneration converter unit. MR- AL_ cannot be used with the MR-CR_ resistance regeneration converter unit.

Power regeneration

converter unit AC reactor Variable dimensions [mm] Terminal

screw Mass [kg] W D H W1 X d

MR-CV11K MR-AL-11K 145 175 155 75 55 M6 M5 3.7 MR-CV18K MR-AL-18K 145 175 155 105 55 M6 M6 5.3 MR-CV30K MR-AL-30K 145 175 155 110 55 M6 M6 6.1 MR-CV37K MR-AL-37K 150 215 175 110 70 M6 M6 8.6 MR-CV45K MR-AL-45K 160 215 175 120 70 M6 M6 9.7 MR-CV55K MR-AL-55K 230 220 192 120 200 M8 M10 11.5 MR-CV11K4 MR-AL-11K4 145 175 155 75 55 M6 M5 3.7 MR-CV18K4 MR-AL-18K4 145 175 155 105 55 M6 M6 5.3 MR-CV30K4 MR-AL-30K4 145 175 155 110 55 M6 M6 6.0 MR-CV37K4 MR-AL-37K4 150 215 175 110 70 M6 M6 8.5 MR-CV45K4 MR-AL-45K4 160 215 175 120 70 M6 M6 9.8 MR-CV55K4 MR-AL-55K4 230 220 210 120 200 M8 M6 10.5 MR-CV75K4 MR-AL-75K4 230 250 215 143 230 M8 M6 13.0

20

4-d mounting hole

L22L12 L32

L31L21L11

Grounding terminal

X

H

W1

WD

Plate

Terminal plate

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 34

8.8 Noise reduction techniques

Noises are classified into external noises which enter the converter unit and drive unit to cause them to malfunction and those radiated by the converter unit and drive unit to cause peripheral equipment to malfunction. Since the converter unit and drive unit are electronic devices which handle small signals, the following general noise reduction techniques are required. Also, the drive unit can be a source of noise as its outputs are chopped by high carrier frequencies. If peripheral equipment malfunctions due to noise generation, take noise suppression measures. The measures will vary slightly with the routes of noise transmission. 8.8.1 Noise reduction techniques

(1) General reduction techniques Avoid bundling power lines (input/output) and signal cables of the converter unit/drive unit together or running them in parallel to each other. Separate the power lines from the signal cables. Use a shielded twisted pair cable for connection with the encoder and for control signal transmission, and connect the external conductor of the cable to the SD terminal. Ground the converter unit, drive unit and the servo motor, etc. together at one point. (Refer to section 3.4.8 and section 4.3.8.)

(2) Reduction techniques for external noises that cause the converter unit/drive unit to malfunction

If there are noise sources (such as a magnetic contactor, an electromagnetic brake, and many relays which make a large amount of noise) near the converter unit and drive unit and the converter unit/drive unit may malfunction, the following countermeasures are required.

Provide surge killers on the noise sources to suppress noises. Attach data line filters to the signal cables. Ground the shields of the encoder connecting cable and the control signal cables with cable clamp fittings. Although a surge absorber is built into the converter unit, to protect the converter unit, drive unit and other equipment against large exogenous noise and lightning surge, attaching a varistor to the power input section of the equipment is recommended.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 35

(3) Techniques for noises radiated by the converter unit/drive unit that cause peripheral equipment to

malfunction Noises produced by the converter unit and drive unit are classified into those radiated from the cables connected to the converter unit, drive unit and their main circuits (input and output circuits), those induced electromagnetically or statically by the signal cables of the peripheral equipment located near the main circuit cables, and those transmitted through the power supply cables.

Noises produced by converter unit and drive unit

Noises transmitted in the air

Noise radiated directly from converter unit and drive unit

Magnetic induction noise

Static induction noise

Noises transmitted through electric channels

Noise radiated from the power supply cable

Noise radiated from servo motor cable

Noise transmitted through power supply cable

Noise sneaking from grounding cable due to leakage current

Routes 4) and 5)

Route 1)

Route 2)

Route 3)

Route 7)

Route 8)

Route 6)

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 36

7)

ReceiverInstrument

Sensor power supply

Converter unit +

Drive unit

1)

3)

2)

4)

7)

6)

2)

3)

8)

5)

Servo motor M

7)

Sensor

Noise transmission route Suppression techniques

1) 2) 3)

When measuring instruments, receivers, sensors, etc. which handle weak signals and may malfunction due to noise and/or their signal cables are contained in a cabinet together with the converter unit and drive unit or run near the converter unit and drive unit, such devices may malfunction due to noises transmitted through the air. The following techniques are required. 1. Provide maximum clearance between easily affected devices and the converter unit/drive unit. 2. Provide maximum clearance between easily affected signal cables and the I/O cables of the

converter unit/drive unit. 3. Avoid wiring the power lines (input/output lines of the converter unit/drive unit) and signal lines

side by side or bundling them together. 4. Insert a line noise filter to the I/O cables or a radio noise filter on the input line. 5. Use shielded wires for signal and power lines or put lines in separate metal conduits.

4) 5) 6)

When the power lines and the signal lines are laid side by side or bundled together, magnetic induction noise and static induction noise will be transmitted through the signal cables and malfunction may occur. The following techniques are required. 1. Provide maximum clearance between easily affected devices and the converter unit/drive unit. 2. Provide maximum clearance between easily affected signal cables and the I/O cables of the

converter unit/drive unit. 3. Avoid wiring the power lines (input/output lines of the converter unit/drive unit) and signal lines

side by side or bundling them together. 4. Use shielded wires for signal and power lines or put lines in separate metal conduits.

7)

When the power supply of peripheral equipment is connected to the power supply of the converter unit/drive unit systems, noises produced by the converter unit and drive unit may be transmitted back through the power supply cable and the devices may malfunction. The following techniques are required. 1. Install the radio noise filter (FR-BIF(-H)) on the power lines (Input lines) of the converter unit/drive

unit. 2. Install the line noise filter (FR-BLF) on the power lines of the converter unit/drive unit.

8) If the grounding wires of the peripheral equipment and the servo amplifier make a closed loop circuit, leakage current may flow through, causing the equipment to malfunction. In this case, the malfunction may be prevented by the grounding wires disconnected from the equipment.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 37

8.8.2 Noise reduction techniques

This section explains how to use the line noise filter unique to the converter unit and drive unit. Other noise reduction products are the same as those for MR-J4-_(-RJ). When you use MR-J4-DU_A_(-RJ), refer to section 11.14 (2) of "MR-J4-_A_(-RJ) Servo Amplifier Instruction Manual". When you use MR-J4-DU_B_(- RJ), refer to section 11.14 (2) of "MR-J4-_B_(-RJ) Servo Amplifier Instruction Manual". (1) Line noise filter (FR-BLF)

This filter is effective in suppressing noises radiated from the power supply side and output side of the converter unit, drive unit and also in suppressing high-frequency leakage current (0-phase current). It especially affects the noises between 0.5 MHz and 5 MHz band. The filters are used with the main circuit power supply of the converter unit (L1/L2/L3) and the power output of the drive unit (U/V/W).

(a) Usage

Pass the 3-phase wires through four line noise filters. When you use the line noise filters with the power wires, passing the power wires together with the ground wire will reduce the filter effect. Run the ground wire separately from the power wires.

Use four FR-BLFs.

(b) Dimensions

[Unit: mm]

160 180

130 85

80 2.

3 35

31 .5

7

7

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 38

8.9 Earth-leakage current breaker

8.9.1 Selection method

High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits. Leakage currents containing harmonic contents are larger than those of the motor which is run with a commercial power supply. Select an earth-leakage current breaker according to the following formula, and ground the converter unit, drive unit, servo motor, etc. securely. To minimize leakage currents, make the input and output wires as short as possible, and keep a distance of 30 cm or longer between the wires and ground. Rated sensitivity current 10 {Igl + Ign + Iga + K (Ig2 + Igm)} [mA]

Ign

Noise filter Wire

Ig1

NV Converter

unit Drive unit

Wire

Iga Ig2 Igm

M

Earth-leakage current breaker K

Type Mitsubishi products

Models provided with harmonic and surge reduction techniques

NV-SV NV-SVF NV-SW NV-CV

NV-CVF NV-CW NV-HV

1

General models BV-C1 3

Igl: Leakage current on the electric channel from the earth-leakage current breaker to the input terminals of the drive unit (found from (1) in this section.) Ig2: Leakage current on the electric channel from the output terminals of the drive unit to the servo motor (found from (1) in this section.) Ign: Leakage current when a filter is connected to the input side (4.4 mA per one FR-BIF(-H)) Iga: Leakage current of the converter unit/drive unit (found from (2) in this section.) Igm: Leakage current of the servo motor (found from (3) in this section.)

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 39

(1) Example of leakage current per km (lg1, lg2) for CV cable run in metal conduit

(a) 200 V class

Le ak

ag e

cu rre

nt [m

A]

Cable size [mm ]2

120 100

80 60 40 20 0 2 5.5 14

3.5 8 38100

22 30

60150 80

(b) 400 V class 120 100

80 60 40 20

0 2 3.5

5.5 8 14

22 38

80 150

30 60

100

Le ak

ag e

cu rre

nt [m

A]

Cable size [mm ]2

(2) Converter unit/drive unit's leakage current example (Iga)

Converter unit Drive unit Leakage current [mA]

All series 5

(3) Servo motor leakage current example (lgm)

Servo motor output [kW] Leakage current [mA] 6 to 55 2.5

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 40

8.9.2 Selection example

Indicated below is an example of selecting an earth-leakage current breaker under the following conditions.

22 mm2 5 m

M

NV

Ig1 Ig2 Igm

Converter unit

Drive unit Servo motor

30 mm2 5 m

Iga

Use an earth-leakage current breaker designed for suppressing harmonics/surges. Calculate the terms of equation in section 8.9.1 from the figure.

Igl = 95 5

1000 = 0.475 [mA]

Ig2 = 105 5

1000 = 0.525 [mA]

Ign = 0 (not used)

Iga = 5 [mA]

Igm = 2.5 [mA]

Substitute these values in the equation in section 8.9.1.

Ig 10 {0.475 + 0 + 5 + 1 (0.525 + 2.5)} 85 [mA]

According to the result of calculation, use an earth-leakage current breaker having the rated sensitivity current (Ig) of 85 mA or more. Use an earth-leakage current breaker having Ig of 200 mA with the NV- SV/NV-SVF/NV-SW/NV-CV/NV-CVF/NV-CW/NV-HV series.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 41

8.10 EMC filter (recommended)

POINT When connecting multiple converter units to one EMC filter, refer to section 6.4 of "EMC Installation Guidelines".

It is recommended that one of the following filters be used to comply with EN EMC directive. Some EMC filters have a large leakage current. 8.10.1 Combinations with the converter unit

Converter unit

Recommended filter (Soshin Electric) Mass [kg] Model

Rated current [A]

Rated voltage [VAC]

Leakage current [mA]

MR-CV11K MR-CV18K

HF3100A-UN (Note) 100

250

6.5 12

MR-CV30K MR-CV37K MR-CV45K MR-CV55K MR-CR55K

HF3200A-UN (Note) 200 9 18

MR-CV11K4 TF3030C-TX 30

500 5.5

7.5 MR-CV18K4 TF3060C-TX 60 12.5 MR-CV30K4 MR-CV37K4 MR-CV45K4 MR-CV55K4 MR-CV75K4 MR-CR55K4

TF3150C-TX 150 31

Note. A surge protector is separately required to use any of these EMC filters.

Converter unit

Recommended filter (COSEL) Mass [kg] Model

Rated current [A]

Rated voltage [VAC]

Leakage current [mA]

MR-CV11K MR-CV18K

FTB-100-355-L (Note) 100 500 40 5.3

MR-CV11K4 MR-CV18K4

FTB-80-355-L (Note) 80 500 80 5.3

MR-CV30K4 MR-CV37K4 MR-CV45K4 MR-CV55K4 MR-CV75K4 MR-CR55K4

FTB-150-355-L (Note) 150 500 80 7.8

Note. A surge protector is separately required to use any of these EMC filters.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 42

8.10.2 Connection example

(1) For MR-CV_ power regeneration converter unit Power regeneration

converter unit

MC L1

L2

L3

L11

L21

EMC filter

1

2

3

4

5

6

E

(Note 1) Power supply

Drive unit

L11

L21

MCCB

Surge protector RSPD-250-U4 (Okaya Electric Industries) RSPD-500-U4 (Okaya Electric Industries)

(Note 2) 1 2 3

L22

L32

L21

L31

AC reactor L12L11

Note 1. For the power supply specifications, refer to section 1.4. 2. The example is when a surge protector is connected.

(2) MR-CR_ resistance regeneration converter unit

EMC filter

(Note 1) Power supply

MCCB

Surge protector RSPD-250-U4 (Okaya Electric Industries) RSPD-500-U4 (Okaya Electric Industries)

(Note 2)

1

2

3

4

5

6

E

L1

L2

L3

L11

L21

Resistance regeneration converter unit

Drive unit

L11

L21

MC

1 2 3

Note 1. For the power supply specifications, refer to section 1.4. 2. The example is when a surge protector is connected.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 43

8.10.3 Dimensions

(1) EMC filter (a) HF3100A-UN

[Unit: mm]

2-6.5 8

M8

2-6.5

14 5

1

16 5

3

M6380 1 400 5

16 0

3

M8

(b) HF3200A-UN [Unit: mm]

500 5

480 1

18 0

5

16 0

1

20 0

5

3-6.5 3-M10

M8

3-6.5 length: 8

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 44

(c) TF3030C-TX

[Unit: mm]

290 2

100 1 100 1

308 5

332 5

(1 2.

2)

3-M4

16 16

6-R3.25 length: 8 M4 M4

12 5

2

3-M4

14 0

1

15 5

2

IN

150 2

(67.5) 3

(160)

170 5

M4

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 45

(d) TF3060C-TX

[Unit: mm]

180 2

(91.5)

(190)

200 5

M6

390 2

100 1

412 5

438 5

(1 7)

3-M6

22 2

2

8-R3.25 length: 8 (for M6) M4 M4

14 5

2

3-M6

16 0

1

17 5

2

IN

100 1 100 1

(e) TF3150C-TX [Unit: mm]

150 1 150 1 150 1

27

1 27

1 23

1

452 5 500 3

20 0

2

22 5

1

24 5

2

25 8

3

3-M8 3-M8

M4

M8

M4 M4

8-R 4.25 length: 12 (for M8)

110 2 210 2 (227)

260 3

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 46

(f) FTB-80-355-L/FTB-100-355-L/FTB-150-355-L

The values in brackets are only for FTB-150-355-L.

[Unit: mm]

309 (359)

350 (400)

335 0.5 (385 0.5)

2-6.5

80

0 .5

20

14 3

10 0

26

6. 5

6. 5

20 28

14 3 17

0

3-M8 (option-S: hexagon socket head cap screw) Output

Input

Protective earth (PE)

3-M8 (option-S: hexagon socket head cap screw)

M6 (option-S: hexagon socket head cap screw) Terminal block coverTerminal block cover

Mounting hole

Mounting hole

Mounting plate

Model plate

(Note)

Protective earth (PE)

M6 (option-S: hexagon socket head cap screw)

Note. No heat radiation holes on the opposite side.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 47

(2) Surge protector (RSPD-250-U4/RSPD-500-U4)

41 1

28 .5

1

2 8

1

4.2 0.5 5. 5

1

11

1 +3

0 0

20 0

4. 5

0.

51 32

Lead

Case

Resin

[Unit: mm]

1 2 3

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 48

8.11 FR-BU2-(H) brake unit

POINT FR-BU2_ brake unit is for the MR-CR_ resistance regeneration converter unit. FR-BU2_ cannot be used with the MR-CV_ power regeneration converter unit. EM2 of the drive unit is the signal having the same contents as EM1 of the drive unit in torque control mode. Use a 200 V class brake unit and a resistor unit with a 200 V class resistance regeneration converter unit, and a 400 V class brake unit and a resistor unit with a 400 V class resistance regeneration converter unit. Combination of different voltage class units cannot be used. When a brake unit and a resistor unit are installed horizontally or diagonally, the heat dissipation effect diminishes. Install them on a flat surface vertically. The temperature of the resistor unit case will be higher than the ambient temperature by 100 C or over. Keep cables and flammable materials away from the case. Ambient temperature condition of the brake unit is between -10 C and 50 C. Note that the condition is different from the ambient temperature condition of the resistance regeneration converter unit (between 0 C and 55 C). Configure the circuit to shut down the power-supply with the alarm output of the brake unit and the resistor unit under abnormal condition. Use the brake unit with a combination indicated in section 8.11.1. Brake unit and regenerative options (Regenerative resistor) cannot be used simultaneously. When using the brake unit, set the parameters as follows.

Parameter Setting value [Pr. PA01] of the resistance regeneration converter unit _ _ 0 0

(Initial value)

[Pr. PA02] of the drive unit _ _ 0 1

Connect the brake unit to the bus of the resistance regeneration converter unit (L+ and L- of TE2-1) for use. As compared to the MR-RB regenerative option, the brake unit can return larger power. Use the brake unit when the regenerative option cannot provide sufficient regenerative capability. When using the brake unit, always refer to "FR-BU2 Brake Unit Instruction Manual". 8.11.1 Selection

Use a combination of resistance regeneration converter unit, brake unit and resistor unit listed below.

Brake unit Resistor unit Number of connected

units

Permissible continuous

power [kW]

Resultant resistance

[]

Resistance regeneration converter unit

200 V class FR-BU2-55K

FR-BR-55K 2 (parallel) 7.82 1 MR-CR55K

MT-BR5-55K 2 (parallel) 11.0 1 400 V class

FR-BU2-H55K FR-BR-H55K 2 (parallel) 7.82 4 MR-CR55K4

FR-BU2-H75K MT-BR5-H75K 2 (parallel) 15.0 3.25

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 49

8.11.2 Brake unit parameter setting

Normally, changing the FR-BU2-(H) parameter is not required. Whether a parameter can be changed or not is listed below.

Parameter Change possible/

impossible Remark

No. Name

0 Brake mode switchover Impossible Do not change the parameter. 1 Monitor display data selection Possible Refer to "FR-BU2 Brake Unit Instruction

Manual". 2 Input terminal function selection 1 Impossible Do not change the parameter. 3 Input terminal function selection 2

77 Parameter write selection

78 Cumulative energization time carrying-over times

CLr Parameter clear ECL Alarm history clear C1 For manufacturer setting

8.11.3 Connection example of combination with FR-BR-(H) resistor unit

POINT Connecting PR terminal of the brake unit to L+ terminal of the resistance regeneration converter unit results in a brake unit malfunction. Always connect the PR terminal of the brake unit to the PR terminal of the resistor unit. To use brake units with a parallel connection, use two sets of FR-BU2-(H) brake unit. Combination with other brake unit results in alarm occurrence or malfunction. Always connect the terminals for master/slave (MSG to MSG, SD to SD) between the two brake units. Do not connect as follows.

N/- P/+

Brake unit

Brake unit Resistance regeneration

converter unit

L+ L- N/-

P/+

Connecting two cables to L+ and L- terminals

N/- P/+

Brake unit

L+ L- N/-

P/+

Brake unit Resistance regeneration

converter unit

Passing wiring

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 50

(1) When magnetic contactor drive output is enabled

Drive unit Resistance regeneration

converter unit

L1

L2

L3

L11

L21

(Note 1) Power supply

L+

L-

L+

L-

EM2

3

20

SDPlate

DICOM10

DOCOM

5 DICOM

ALM15

CN3

CN1 1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

L11

L21

P1

P2 (Note 3)

L+

L- (Note 9)

24 V DC

24 V DC

B

B C

(Note 2) MC

RA2

N/- P/+

BUE SD

PR

A SD

MSG

(Note 4)

(Note 7)

FR-BU2-(H)

FR-BR-(H)

P PR

TH2 TH1(Note 6)

Terminal block

(Note 12) (Note 11)

(Note 10)

N/- P/+

BUE SD

PR

C

A SD

MSG

(Note 4)

(Note 7)

FR-BU2-(H)

TH2 TH1(Note 6)

FR-BR-(H)

P PR

(Note 11)

(Note 10)

(Note 8)

MCCB

RA1

(Note 13) Main circuit power supply

RA1

Drive unit malfunction Operation ready

OFF/ON MC

SK

TE2-2

TE2-1

1MC1

2MC2

CNP1 (Note 5)

(Note 14)

(Note 8)

Resistance regeneration converter unit malfunction

RA2 Emergency stop

switch

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 51

Note 1. For the power supply specifications, refer to section 1.4. 2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

3. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing the short bar across them. Refer to section 8.6 for details.

4. Connect P/+ and N/- terminals of the brake unit to a correct destination. Incorrect connection destination results in the resistance regeneration converter unit and brake unit malfunction.

5. For 400 V class, a step-down transformer is required. 6. Contact rating: 1b contact, 110 V AC, 5 A/220 V AC, 3 A

Normal condition: TH1-TH2 is conducting. Abnormal condition: TH1-TH2 is not conducting. 7. Contact rating: 230 V AC, 0.3 A/30 V DC, 0.3 A

Normal condition: B-C is conducting./A-C is not conducting. Abnormal condition: B-C is not conducting./A-C is conducting. 8. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section

8.5.) 9. Do not connect more than one cable to each L+ and L- terminals of TE2-1 of the resistance regeneration converter unit. 10. Always connect BUE and SD terminals. (factory-wired) 11. Connect MSG and SD terminals of the brake unit to a correct destination. Incorrect connection destination results in the

resistance regeneration converter unit and brake unit malfunction. 12. For connecting L+ and L- terminals of TE2-1 of the resistance regeneration converter unit to the terminal block, use the cable

indicated in (4) in this section. 13. Configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off to prevent an unexpected restart of

the drive unit. 14. The wiring is for MR-J4-DU_B_(-RJ). The connection for the interface of MR-J4-DU_(-RJ) is the same as in the case of MR-

J4-_(-RJ). Refer to each servo amplifier instruction manual.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 52

(2) When magnetic contactor drive output is disabled

L1

L2

L3

L11

L21

(Note 1) Power supply

L+

L-

L+

L-

1MC1

2MC2

CNP1

EM2

3

20

SDPlate

DICOM10

DOCOM

5 DICOM

ALM15

CN3

CN1 1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

L11

L21

P1

P2 (Note 3)

L+

L- (Note 9)

24 V DC

24 V DC

B

B C

(Note 2) MC

RA2

N/- P/+

BUE SD

PR

A SD

MSG

(Note 4)

(Note 7)

FR-BU2-(H)

FR-BR-(H)

P PR

TH2 TH1(Note 6)

Terminal block

(Note 12) (Note 11)

(Note 10)

N/- P/+

BUE SD

PR

C

A SD

MSG

(Note 4)

(Note 7)

FR-BU2-(H)

TH2 TH1(Note 6)

FR-BR-(H)

P PR

(Note 11)

(Note 10)

MCCB

RA1

(Note 13) Main circuit power supply

(Note 14)

TE2-2

TE2-1

(Note 8)

(Note 5)

(Note 8)

Resistance regeneration converter unit

Resistance regeneration converter unit malfunction

RA2 Emergency stop

switch

Drive unit

RA1

Drive unit malfunction

SK

OFF

MC

ON MC

Operation ready

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 53

Note 1. For the power supply specifications, refer to section 1.4. 2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

3. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing the short bar across them. Refer to section 8.6 for details.

4. Connect P/+ and N/- terminals of the brake unit to a correct destination. Incorrect connection destination results in the resistance regeneration converter unit and brake unit malfunction.

5. For 400 V class, a step-down transformer is required. 6. Contact rating: 1b contact, 110 V AC, 5 A/220 V AC, 3 A

Normal condition: TH1-TH2 is conducting. Abnormal condition: TH1-TH2 is not conducting. 7. Contact rating: 230 V AC, 0.3 A/30 V DC, 0.3 A

Normal condition: B-C is conducting./A-C is not conducting. Abnormal condition: B-C is not conducting./A-C is conducting. 8. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section

8.5.) 9. Do not connect more than one cable to each L+ and L- terminals of TE2-1 of the resistance regeneration converter unit. 10. Always connect BUE and SD terminals. (factory-wired) 11. Connect MSG and SD terminals of the brake unit to a correct destination. Incorrect connection destination results in the

resistance regeneration converter unit and brake unit malfunction. 12. For connecting L+ and L- terminals of TE2-1 of the resistance regeneration converter unit to the terminal block, use the cable

indicated in (4) in this section. 13. Configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off to prevent an unexpected restart of

the drive unit. 14. The wiring is for MR-J4-DU_B_(-RJ). The connection for the interface of MR-J4-DU_(-RJ) is the same as in the case of MR-

J4-_(-RJ). Refer to each servo amplifier instruction manual.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 54

8.11.4 Combination with MT-BR5-(H) resistor unit

POINT Connecting PR terminal of the brake unit to L+ terminal of the resistance regeneration converter unit results in a brake unit malfunction. Always connect the PR terminal of the brake unit to the PR terminal of the resistor unit.

(1) When connecting a brake unit to a resistance regeneration converter unit

(a) When magnetic contactor drive output is enabled

Resistance regeneration converter unit

Operation ready OFF/ON

Resistance regeneration converter unit malfunction

RA2 Emergency stop

switch

Drive unit

L1

L2

L3

L11

L21

(Note 1) Power supply

L+

L-

L+

L- 1MC1

2MC2

CNP1

EM2

3

20

SDPlate

DICOM10

DOCOM

5 DICOM

ALM15

CN3

CN1 1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

L11

L21

P1

P2 (Note 3)

L+

L- (Note 9)

24 V DC

24 V DC

N/- P/+

BUE SD

PR

B C

A SD

MSG

(Note 4)

(Note 7)

FR-BU2-(H)

MT-BR5-(H)

P PR

(Note 6)

(Note 10)

RA3

TH2 TH1

SK

(Note 2) MC

RA2

MCCB

RA1

(Note 11) Main circuit power supply

(Note 8)

TE2-2

TE2-1

(Note 12)

MC

RA3

SK

RA1

Drive unit malfunction

(Note 5)

(Note 8)

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 55

Note 1. For the power supply specifications, refer to section 1.4. 2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

3. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing the short bar across them. Refer to section 8.6 for details.

4. Connect P/+ and N/- terminals of the brake unit to a correct destination. Incorrect connection destination results in the resistance regeneration converter unit and brake unit malfunction.

5. For 400 V class, a step-down transformer is required. 6. Contact rating: 1a contact, 110 V AC, 5 A/220 V AC, 3 A

Normal condition: TH1-TH2 is not conducting. Abnormal condition: TH1-TH2 is conducting. 7. Contact rating: 230 V AC, 0.3 A/30 V DC, 0.3 A

Normal condition: B-C is conducting./A-C is not conducting. Abnormal condition: B-C is not conducting./A-C is conducting. 8. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section

8.5.) 9. Do not connect more than one cable to each L+ and L- terminals of TE2-1 of the resistance regeneration converter unit. 10. Always connect BUE and SD terminals. (factory-wired) 11. Configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off to prevent an unexpected restart of

the drive unit. 12. The wiring is for MR-J4-DU_B_(-RJ). The connection for the interface of MR-J4-DU_(-RJ) is the same as in the case of MR-

J4-_(-RJ). Refer to each servo amplifier instruction manual.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 56

(b) When magnetic contactor drive output is disabled

Drive unit

L1

L2

L3

L11

L21

(Note 1) Power supply

L+

L-

L+

L-

1MC1

2MC2

CNP1

EM2

3

20

SDPlate

DICOM10

DOCOM

5 DICOM

ALM15

CN3

CN1 1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

L11

L21

P1

P2 (Note 3)

L+

L- (Note 9)

24 V DC

24 V DC

N/- P/+

BUE SD

PR

B C

A SD

MSG

(Note 4)

(Note 7)

FR-BU2-(H)

MT-BR5-(H)

P PR

(Note 6)

(Note 10)

RA3

TH2 TH1

SK

(Note 2) MC

RA2

MCCB

RA1

(Note 11) Main circuit power supply

(Note 5) TE2-2

TE2-1

(Note 12)

SK

OFF

MC

ON MC

RA1

Drive unit malfunction

RA3

Operation ready

(Note 8) (Note 8)

Resistance regeneration converter unit

Resistance regeneration converter unit malfunction

RA2 Emergency stop

switch

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 57

Note 1. For the power supply specifications, refer to section 1.4. 2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

3. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing the short bar across them. Refer to section 8.6 for details.

4. Connect P/+ and N/- terminals of the brake unit to a correct destination. Incorrect connection destination results in the resistance regeneration converter unit and brake unit malfunction.

5. For 400 V class, a step-down transformer is required. 6. Contact rating: 1a contact, 110 V AC, 5 A/220 V AC, 3 A

Normal condition: TH1-TH2 is not conducting. Abnormal condition: TH1-TH2 is conducting. 7. Contact rating: 230 V AC, 0.3 A/30 V DC, 0.3 A

Normal condition: B-C is conducting./A-C is not conducting. Abnormal condition: B-C is not conducting./A-C is conducting. 8. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section

8.5.) 9. Do not connect more than one cable to each L+ and L- terminals of TE2-1 of the resistance regeneration converter unit. 10. Always connect BUE and SD terminals. (factory-wired) 11. Configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off to prevent an unexpected restart of

the drive unit. 12. The wiring is for MR-J4-DU_B_(-RJ). The connection for the interface of MR-J4-DU_(-RJ) is the same as in the case of MR-

J4-_(-RJ). Refer to each servo amplifier instruction manual.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 58

(2) When connecting two brake units to a resistance regeneration converter unit

POINT To use brake units with a parallel connection, use two sets of FR-BU2-(H) brake unit. Combination with other brake unit results in alarm occurrence or malfunction. Always connect the terminals for master/slave (MSG to MSG, SD to SD) between the two brake units. Do not connect as follows.

N/- P/+

Brake unit

Brake unit Resistance regeneration

converter unit

L+ L- N/-

P/+

Connecting two cables to L+ and L- terminals

N/- P/+

Brake unit

Brake unit Resistance regeneration

converter unit

L+ L- N/-

P/+

Passing wiring

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 59

(a) When magnetic contactor drive output is enabled

Resistance regeneration converter unit

Operation ready OFF/ON

Resistance regeneration converter unit malfunction

RA2 Emergency stop

switch

N/- P/+

BUE SD

PR

B C

A SD

MSG

(Note 4)

(Note 7)

FR-BU2-(H)

MT-BR5-(H)

P PR

(Note 6)

(Note 10)

RA3

TH2 TH1

(Note 11)(Note 12)

Terminal block

(Note 7)

N/- P/+

BUE SD

PR

B C

A SD

MSG

(Note 4)

FR-BU2-(H)

TH2 TH1(Note 6)

MT-BR5-(H)

P PR

(Note 11)

(Note 10)

RA4

SK

SK

Drive unit

L1

L2

L3

L11

L21

(Note 1) Power supply

L+

L-

L+

L- 1MC1

2MC2

CNP1

EM2

3

20

SDPlate

DICOM10

DOCOM

5 DICOM

ALM15

CN3

CN1 1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

L11

L21

P1

P2 (Note 3)

L+

L- (Note 9)

24 V DC

24 V DC

(Note 2) MC

RA2

MCCB

RA1

(Note 13) Main circuit power supply

TE2-2

TE2-1

(Note 14)

RA3 RA4RA1

Drive unit malfunction

MC

SK

(Note 5)

(Note 8) (Note 8)

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 60

Note 1. For the power supply specifications, refer to section 1.4. 2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

3. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing the short bar across them. Refer to section 8.6 for details.

4. Connect P/+ and N/- terminals of the brake unit to a correct destination. Incorrect connection destination results in the resistance regeneration converter unit and brake unit malfunction.

5. For 400 V class, a step-down transformer is required. 6. Contact rating: 1a contact, 110 V AC, 5 A/220 V AC, 3 A

Normal condition: TH1-TH2 is not conducting. Abnormal condition: TH1-TH2 is conducting. 7. Contact rating: 230 V AC, 0.3 A/30 V DC, 0.3 A

Normal condition: B-C is conducting./A-C is not conducting. Abnormal condition: B-C is not conducting./A-C is conducting. 8. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section

8.5.) 9. Do not connect more than one cable to each L+ and L- terminals of TE2-1 of the resistance regeneration converter unit. 10. Always connect BUE and SD terminals. (factory-wired) 11. Connect MSG and SD terminals of the brake unit to a correct destination. Incorrect connection destination results in the

resistance regeneration converter unit and brake unit malfunction. 12. For connecting L+ and L- terminals of the resistance regeneration converter unit to the terminal block, use the cable indicated

in (4) in this section. 13. Configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off to prevent an unexpected restart of

the drive unit. 14. The wiring is for MR-J4-DU_B_(-RJ). The connection for the interface of MR-J4-DU_(-RJ) is the same as in the case of MR-

J4-_(-RJ). Refer to each servo amplifier instruction manual.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 61

(b) When magnetic contactor drive output is disabled

Resistance regeneration converter unit

Resistance regeneration converter unit malfunction

RA2 Emergency stop

switch

N/- P/+

BUE SD

PR

B C

A SD

MSG

(Note 4)

(Note 7)

FR-BU2-(H)

MT-BR5-(H)

P PR

(Note 6)

(Note 10)

RA3

TH2 TH1

(Note 11) (Note 12)

Terminal block

(Note 7)

N/- P/+

BUE SD

PR

B C

A SD

MSG

(Note 4)

FR-BU2-(H)

TH2 TH1(Note 6)

MT-BR5-(H)

P PR

(Note 11)

(Note 10)

RA4

SK

SK

Drive unit

L1

L2

L3

L11

L21

(Note 1) Power supply

L+

L-

L+

L-

1MC1

2MC2

CNP1

EM2

3

20

SDPlate

DICOM10

DOCOM

5 DICOM

ALM15

CN3

CN1 1 DICOM

5 DOCOM

6 DICOM

2 ALM

7 EM1

9 DOCOM

L11

L21

P1

P2 (Note 3)

L+

L- (Note 9)

24 V DC

24 V DC

(Note 2) MC

RA2

MCCB

RA1

(Note 13) Main circuit power supply

SK

OFF

MC

ON MC

RA1

Drive unit malfunction

RA3 RA4

(Note 5) TE2-2

TE2-1

(Note 14)

Operation ready

(Note 8) (Note 8)

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 62

Note 1. For the power supply specifications, refer to section 1.4. 2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of

contacts) of 80 ms or less. Depending on the main circuit voltage and operation pattern, bus voltage decreases, and that may cause the forced stop deceleration to shift to the dynamic brake deceleration. When dynamic brake deceleration is not required, slow the time to turn off the magnetic contactor.

3. P1 and P2 are connected by default. When using the power factor improving DC reactor, connect P1 and P2 after removing the short bar across them. Refer to section 8.6 for details.

4. Connect P/+ and N/- terminals of the brake unit to a correct destination. Incorrect connection destination results in the resistance regeneration converter unit and brake unit malfunction.

5. For 400 V class, a step-down transformer is required. 6. Contact rating: 1a contact, 110 V AC, 5 A/220 V AC, 3 A

Normal condition: TH1-TH2 is not conducting. Abnormal condition: TH1-TH2 is conducting. 7. Contact rating: 230 V AC, 0.3 A/30 V DC, 0.3 A

Normal condition: B-C is conducting./A-C is not conducting. Abnormal condition: B-C is not conducting./A-C is conducting. 8. Install an overcurrent protection device (molded-case circuit breaker or fuse) to protect the branch circuit. (Refer to section

8.5.) 9. Do not connect more than one cable to each L+ and L- terminals of TE2-1 of the resistance regeneration converter unit. 10. Always connect BUE and SD terminals. (factory-wired) 11. Connect MSG and SD terminals of the brake unit to a correct destination. Incorrect connection destination results in the

resistance regeneration converter unit and brake unit malfunction. 12. For connecting L+ and L- terminals of the resistance regeneration converter unit to the terminal block, use the cable indicated

in (4) in this section. 13. Configure a circuit to turn off EM2 in the drive unit when the main circuit power is turned off to prevent an unexpected restart of

the drive unit. 14. The wiring is for MR-J4-DU_B_(-RJ). The connection for the interface of MR-J4-DU_(-RJ) is the same as in the case of MR-

J4-_(-RJ). Refer to each servo amplifier instruction manual.

8.11.5 Connection instructions

Keep the wires between the resistance regeneration converter unit and the brake unit, and between the resistor unit and the brake unit as short as possible. For wires longer than 5 m, twist the wires five times or more per meter. The wires should not exceed 10 m even when the wires are twisted. If wires exceeding 5 m without twisted or exceeding 10 m with or without twisted are used, the brake unit may malfunction.

Resistance regeneration converter unit

Brake unit

5 m or less 5 m or less

Resistance regeneration converter unit

Brake unit

10 m or less 10 m or less

L+ L-

P/+ N/-

P PR

P PR

P/+ N/-

P PR

P PR

Twist Twist

Resistor unit Resistor unit

L+ L-

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 63

8.11.6 Wires

(1) Wires for the brake unit For the brake unit, HIV wire (600 V Grade heat-resistant polyvinyl chloride insulated wire) is recommended.

(a) Main circuit terminal

N/- P/+ PR

Terminal block

Brake unit

Main circuit

terminal screw size

Crimp terminal Tightening

torque [Nm]

Wire size

N/-, P/+, PR,

N/-, P/+, PR, HIV wire

[mm2] AWG

200 V class FR-BU2-55K M6 14-6 4.4 14 6

400 V class

FR-BU2-H55K M5 5.5-5 2.5 5.5 10 FR-BU2-H75K M6 14-6 4.4 14 6

(b) Control circuit terminal

POINT

Under tightening can cause a cable disconnection or malfunction. Over tightening can cause a short circuit or malfunction due to damage to the screw or the brake unit.

A RESPC

B SDBUE

C MSGSD MSG SD SD

Jumper

Insulator Core

6 mm

Wire the stripped cable after twisting to prevent the cable from becoming loose. In addition, do not solder it. Screw size: M3 Tightening torque: 0.5 Nm to 0.6 Nm Wire size: 0.3 mm2 to 0.75 mm2 Screw driver: Small flat-blade screwdriver (Tip thickness: 0.4 mm/Tip width 2.5 mm) (2) Cables for connecting the resistance regeneration converter unit and a distribution terminal block when

connecting two sets of the brake unit

Brake unit Wire size

HIV wire [mm2] AWG 200 V class FR-BU2-55K 38 2

400 V class

FR-BU2-H55K 14 6 FR-BU2-H75K 38 2

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 64

8.11.7 Crimp terminals for L+ and L- terminals of TE2-1 of resistance regeneration converter unit

(1) Recommended crimp terminals

POINT Some crimp terminals may not be mounted depending on their sizes. Make sure to use the recommended ones or equivalent ones.

Resistance regeneration converter

unit Brake unit Number of connected

units Crimp terminal (Manufacturer)

(Note 1) Applicable

tool 200 V class

MR-CR55K FR-BU2-55K 2 38-S6 (JST) (Note 2) R38-6S (NICHIFU) (Note 2)

a

400 V class

MR-CR55K4 FR-BU2-H55K 2 FVD14-6 (JST)

b

FR-BU2-H75K 2 38-S6 (JST) (Note 2) R38-6S (NICHIFU) (Note 2)

a

Note 1. Symbols in the applicable tool field indicate applicable tools in (5) (b) in this section. 2. Coat the crimping part with an insulation tube.

(2) Applicable tool

Symbol Resistance regeneration converter unit-side crimp terminal

Crimp terminal Applicable tool

Manufacturer Body Head Dice

a 38-S6

YPT-60-21 TD-124 TD-112

JST YF-1 E-4

YET-60-1

R38-6S NOP60 NOM60

NICHIFU

b FDV14-6 YF-1 E-4

YNE-38 DH-112 DH-122

JST

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 65

8.11.8 Dimensions

(1) FR-BU2-(H) brake unit FR-BU2-55K/FR-BU2-H55K/FR-BU2-H75K

[Unit: mm]

18.5

Rating plate

52 72

5

142.5

12 8

11 8

5 5

5 61586

170

2-5 hole (Screw size: M4)

(2) FR-BR-(H) resistor unit

[Unit: mm]

H 3

1

H 1

3

Ap pr

ox .

H 2

Ap pr

ox .

40

33 Ap

pr ox

. H

2

D 1

H

5

2-C

Control circuit terminal

Main circuit terminal

W1 1Approx. 35 Approx. 35

204 Eyebolt

C C

W 5

D

5 (Note)

(Note)

Two eyebolts are attached. (Refer to the following diagram.)

Note. Ventilation ports are provided on both sides and the top. The bottom is open.

Resistor unit W W1 H H1 H2 H3 D D1 C Approximate mass [kg]

200 V class FR-BR-55K 480 410 700 620 40 670 450 3.2 12 70

400 V class FR-BR-H55K 480 410 700 620 20 670 450 3.2 12 70

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 66

(3) MT-BR5-(H) resistor unit

[Unit: mm]

415 mounting hole 30075 75 4507.5 7.5

M6 M4

193 189

480 510

85

85 80

0

37 60 2110

40 30

NP

Resistor unit Resistance Approximate mass [kg]

200 V class

MT-BR5-55K 2.0 50

400 V class MT-BR5-H75K 6.5 70

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 67

8.12 MR-DCBAR_ bus bar

When one drive unit is connected to one power regeneration converter unit, the drive unit is driven at the rated output with the following combinations. Use the bus bars for the connection of the L+/L- terminals between the converter unit and the drive unit, and between the drive units. The bus bars vary depending on the units to be connected. Be sure to use the bus bars listed in this section. 8.12.1 Bus bar

(1) 200 V class

Unit mounted on the left side (Note 1) Unit mounted on the right side (Note 1) Bus bar model

Number contained

in a set MR-CR55K MR-J4-DU30K_(-RJ)/MR-J4-DU37K_(-RJ) MR-DCBAR106-C04 (Note 2) 2

MR-CV11K MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ) MR-DCBAR137-B52 1 (assembled)

MR-CV18K MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ) MR-DCBAR137-B52 1

(assembled)

MR-J4-DU15KB(-RJ) MR-DCBAR235-B52 1 (assembled)

MR-CV30K

MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ) MR-DCBAR159-B52 1 (assembled)

MR-J4-DU15KB(-RJ)/MR-J4-DU22KB(-RJ) MR-DCBAR255-B52 1 (assembled)

MR-J4-DU30KB(-RJ) MR-DCBAR105-C03 2

MR-CV37K MR-CV45K

MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ) MR-DCBAR159-B52 1 (assembled)

MR-J4-DU15KB(-RJ)/MR-J4-DU22KB(-RJ) MR-DCBAR255-B52 1 (assembled)

MR-J4-DU30KB(-RJ)/MR-J4-DU37KB(-RJ) MR-DCBAR105-C03 2

MR-CV55K

MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ) MR-DCBAR159-B53 1 (assembled)

MR-J4-DU15KB(-RJ)/MR-J4-DU22KB(-RJ) MR-DCBAR257-B53 1 (assembled)

MR-J4-DU30KB(-RJ)/MR-J4-DU37KB(-RJ) MR-DCBAR106-C04 (Note 2) 2

MR-J4-DU900B MR-J4-DU900B(-RJ) MR-DCBAR170-B52 1 (assembled)

MR-J4-DU11KB MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ) MR-DCBAR170-B52 1 (assembled)

MR-J4-DU15KB MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ) MR-DCBAR137-B52 1

(assembled)

MR-J4-DU15KB(-RJ) MR-DCBAR235-B52 1 (assembled)

MR-J4-DU22KB MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ) MR-DCBAR137-B52 1

(assembled)

MR-J4-DU15KB(-RJ)/MR-J4-DU22KB(-RJ) MR-DCBAR235-B52 1 (assembled)

MR-J4-DU30KB

MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ) MR-DCBAR159-B53 1 (assembled)

MR-J4-DU15KB(-RJ)/MR-J4-DU22KB(-RJ) MR-DCBAR257-B53 1 (assembled)

MR-J4-DU30KB(-RJ) MR-DCBAR106-C04 (Note 2) 2

MR-J4-DU37KB

MR-J4-DU900B(-RJ)/MR-J4-DU11KB(-RJ) MR-DCBAR159-B53 1 (assembled)

MR-J4-DU15KB(-RJ)/MR-J4-DU22KB(-RJ) MR-DCBAR257-B53 1 (assembled)

MR-J4-DU30KB(-RJ)/MR-J4-DU37KB(-RJ) MR-DCBAR106-C04 (Note 2) 2 Note 1. "Unit mounted on the left side" and "Unit mounted on the right side" indicate the position when the units are seen from the

front. Install the power regeneration converter unit on the left side of the drive unit. 2. This is supplied with the drive unit.

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 68

(2) 400 V class

Unit mounted on the left side (Note 1) Unit mounted on the right side (Note 1) Bus bar model

Number contained

in a set

MR-CR55K4 MR-J4-DU30K_4(-RJ)/MR-J4-DU37K_4(-RJ) MR-DCBAR085-C03 (Note 2) 2 MR-J4-DU45K_4(-RJ)/MR-J4-DU55K_4(-RJ) MR-DCBAR106-C04 (Note 2) 2

MR-CV11K4 MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR137-B52 1 (assembled)

MR-CV18K4 MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR137-B52 1

(assembled)

Model MR-J4-DU_(-RJ) MR-DCBAR235-B52 1 (assembled)

MR-CV30K4

MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR159-B52 1 (assembled)

MR-J4-DU15KB4(-RJ)/MR-J4-DU22KB4(-RJ) MR-DCBAR255-B52 1 (assembled)

MR-J4-DU30KB4(-RJ) MR-DCBAR082-C02 2

MR-CV37K4

MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR159-B52 1 (assembled)

MR-J4-DU15KB4(-RJ)/MR-J4-DU22KB4(-RJ) MR-DCBAR255-B52 1 (assembled)

MR-J4-DU30KB4(-RJ)/MR-J4-DU37KB4(-RJ) MR-DCBAR082-C02 2

MR-CV45K4

MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR159-B52 1 (assembled)

MR-J4-DU15KB4(-RJ)/MR-J4-DU22KB4(-RJ) MR-DCBAR255-B52 1 (assembled)

MR-J4-DU30KB4(-RJ)/MR-J4-DU37KB4(-RJ) MR-DCBAR082-C02 2 MR-J4-DU45KB4(-RJ) MR-DCBAR105-C03 2

MR-CV55K4 MR-CV75K4

MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR159-B53 1 (assembled)

MR-J4-DU15KB4(-RJ)/MR-J4-DU22KB4(-RJ) MR-DCBAR257-B53 1 (assembled)

MR-J4-DU30KB4(-RJ)/MR-J4-DU37KB4(-RJ) MR-DCBAR085-C03 (Note 2) 2 MR-J4-DU45KB4(-RJ)/MR-J4-DU55KB4(-RJ) MR-DCBAR106-C04 (Note 2) 2

MR-J4-DU900B4 MR-J4-DU900B4(-RJ) MR-DCBAR170-B52 1 (assembled)

MR-J4-DU11KB4 MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR170-B52 1 (assembled)

MR-J4-DU15KB4 MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR137-B52 1

(assembled)

MR-J4-DU15KB4(-RJ) MR-DCBAR235-B52 1 (assembled)

MR-J4-DU22KB4 MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR137-B52 1

(assembled)

MR-J4-DU15KB4(-RJ)/MR-J4-DU22KB4(-RJ) MR-DCBAR235-B52 1 (assembled)

MR-J4-DU30KB4

MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR310-B52 1 (assembled)

MR-J4-DU15KB4(-RJ)/MR-J4-DU22KB4(-RJ) MR-DCBAR409-B52 1 (assembled)

MR-J4-DU30KB4(-RJ) MR-DCBAR235-B52 1 (assembled)

MR-J4-DU37KB4

MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR310-B52 1 (assembled)

MR-J4-DU15KB4(-RJ)/MR-J4-DU22KB4(-RJ) MR-DCBAR409-B52 1 (assembled)

MR-J4-DU30KB4(-RJ)/MR-J4-DU37KB4(-RJ) MR-DCBAR235-B52 1 (assembled)

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 69

Unit mounted on the left side

(Note 1) Unit mounted on the right side (Note 1) Bus bar model Number

contained in a set

MR-J4-DU45KB4

MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR159-B53 1 (assembled)

MR-J4-DU15KB4(-RJ)/MR-J4-DU22KB4(-RJ) MR-DCBAR257-B53 1 (assembled)

MR-J4-DU30KB4(-RJ)/MR-J4-DU37KB4(-RJ) MR-DCBAR085-C03 (Note 2) 2 MR-J4-DU45KB4(-RJ) MR-DCBAR106-C04 (Note 2) 2

MR-J4-DU55KB4

MR-J4-DU900B4(-RJ)/MR-J4-DU11KB4(-RJ) MR-DCBAR159-B53 1 (assembled)

MR-J4-DU15KB4(-RJ)/MR-J4-DU22KB4(-RJ) MR-DCBAR257-B53 1 (assembled)

MR-J4-DU30KB4(-RJ)/MR-J4-DU37KB4(-RJ) MR-DCBAR085-C03 (Note 2) 2 MR-J4-DU45KB4(-RJ)/MR-J4-DU55KB4(-RJ) MR-DCBAR106-C04 (Note 2) 2

Note 1. "Unit mounted on the left side" and "Unit mounted on the right side" indicate the position when the units are seen from the

front. Install the power regeneration converter unit on the left side of the drive unit. 2. This is supplied with the drive unit.

8.12.2 Adjustment bar

When the total number of MR-J4-DU900(4)(-RJ) and MR-J4- DU11KB(4)(-RJ) drive units connected to the power regeneration convert unit is even, there is a gap of bar thickness between the bus bar and TE2 terminal block of the final drive unit (right end). Place adjustment bars in the gap and screw them together. (Refer to section 3.3.1 (3).)

Bus bar Number contained MR-DCBAR035-B05 2

8. OPTIONS AND PERIPHERAL EQUIPMENT

8 - 70

MEMO

9. COMPLIANCE WITH SEMI-F47 STANDARD

9 - 1

9. COMPLIANCE WITH SEMI-F47 STANDARD

POINT A combination of the MR-CV_ power regeneration converter unit and drive unit does not comply with SEMI-F47 standard. The control circuit power supply of the resistance regeneration converter unit and drive unit can comply with SEMI-F47 standard. However, a back-up capacitor may be necessary for instantaneous power failure in the main circuit power supply depending on the power impedance and operating situation. The external dynamic brake cannot be used for compliance with SEMI-F47 standard. Do not assign DB (Dynamic brake interlock). Doing so will cause the drive unit to become servo-off when an instantaneous power failure occurs. Be sure to perform actual machine tests and detail checks for power supply instantaneous power failure of SEMI-F47 standard with your equipment.

The following explains the compliance with "SEMI-F47 semiconductor process equipment voltage sag immunity test" of MR-J4 series. This function enables to avoid triggering [AL. 10 Undervoltage] using the electrical energy charged in the capacitor in case that an instantaneous power failure occurs during operation.

9. COMPLIANCE WITH SEMI-F47 STANDARD

9 - 2

9.1 Parameter setting

Setting parameters of the drive unit and resistance regeneration converter unit as follows will enable SEMI- F47 function.

Parameter Setting value Description [Pr. PA20] of the drive unit _ 1 _ _ SEMI-F47 function selection [Pr. PF25] of the drive unit 200 Set the time [ms] until the occurrence of [AL. 10.1 Voltage drop in the control

circuit power]. [Pr. PA17] of the resistance regeneration converter unit

_ _ 1 _ SEMI-F47 function selection

[Pr. PA18] of the resistance regeneration converter unit

200 Set the time [ms] until the occurrence of [AL. 10 Undervoltage].

Enabling SEMI-F47 function will change operation as follows. (1) The voltage will drop in the control circuit power at "Rated voltage 50% or less". After 200 ms, [AL.

10.1 Voltage drop in the control circuit power] will occur. (2) [AL. 10.2 Voltage drop in the main circuit power] will occur when bus voltage is as follows.

Voltages which trigger [AL. 10.2 Voltage drop in the main circuit power] Drive unit Bus voltage which triggers alarm

MR-J4-DU30KB(-RJ) MR-J4-DU30KA(-RJ) MR-J4-DU37KB(-RJ) MR-J4-DU37KA(-RJ)

200 V DC

MR-J4-DU30KB4(-RJ) MR-J4-DU30KA4(-RJ) MR-J4-DU37KB4(-RJ) MR-J4-DU37KA4(-RJ) MR-J4-DU45KB4(-RJ) MR-J4-DU45KA4(-RJ) MR-J4-DU55KB4(-RJ) MR-J4-DU55KA4(-RJ)

380 V DC

(3) MBR (Electromagnetic brake interlock) will turn off when [AL. 10.1 Voltage drop in the control circuit

power] occurs.

9. COMPLIANCE WITH SEMI-F47 STANDARD

9 - 3

9.2 Requirement of SEMI-F47 standard

The following shows the permissible time of instantaneous power failure for instantaneous power failure voltage of SEMI-F47 standard.

Requirement of SEMI-F47 standard

Instantaneous power failure voltage

Permissible time of instantaneous power

failure [s] Rated voltage 80% 1 Rated voltage 70% 0.5 Rated voltage 50% 0.2

9.3 Calculation of tolerance against instantaneous power failure

The following shows tolerance against instantaneous power failure when instantaneous power failure voltage is "rated voltage 50%" and instantaneous power failure time is 200 ms.

Tolerance against instantaneous power failure (instantaneous power failure voltage = rated voltage 50%, instantaneous power failure time = 200 ms)

Drive unit model Instantaneous maximum output [W]

Tolerance against instantaneous power failure [W]

(voltage drop between lines) MR-J4-DU30K_ 79000 7500 MR-J4-DU37K_ 103000 10000

MR-J4-DU30K_4 79000 7500 MR-J4-DU37K_4 103000 7500 MR-J4-DU45K_4 110000 7500 MR-J4-DU55K_4 135000 7500

Instantaneous maximum output means power which drive unit can output in maximum torque at rated speed. You can examine margins to compare the values of following conditions and instantaneous maximum output. Even if driving at maximum torque with low speed in actual operation, the motor will not drive with the maximum output. This can be handled as a margin. The following shows the conditions of tolerance against instantaneous power failure. 9.3.1 Delta connection

For the 3-phase (L1/L2/L3) delta connection, an instantaneous power failure occurs in the voltage between a pair of lines (e.g. between L1 and L2) among voltages between three pairs of lines (between L1 and L2, L2 and L3, or L3 and L1). 9.3.2 Star connection

For the 3-phase (L1/L2/L3/neutral point N) star connection, an instantaneous power failure occurs in the voltage between a pair of lines (e.g. between L1 and N) among voltages at six locations, between three pairs of lines (between L1 and L2, L2 and L3, or L3 and L1) and between one of the lines and the neutral point (between L1 and N, L2 and N, or L3 and N).

9. COMPLIANCE WITH SEMI-F47 STANDARD

9 - 4

MEMO

10. APPENDIX

10 - 1

10. APPENDIX

10.1 Peripheral equipment manufacturer (for reference)

Names given in the table are as of Jun. 2018.

Manufacturer Contact information DDK DDK Ltd. Phoenix Contact Phoenix Contact GmbH & Co. KG JST J.S.T. Mfg. Co., Ltd. Honda Tsushin Kogyo HONDA TSUSHIN KOGYO CO., LTD. 3M 3M NICHIFU NICHIFU CO., LTD. Soshin Electric Soshin Electric Co., Ltd. Okaya Electric Industries OKAYA ELECTRIC INDUSTRIES CO., LTD.

10.2 Compliance with global standards

Converter units and drive units are written as servo amplifiers in app. 2 under certain circumstances. 10.2.1 Terms related to safety

(1) IEC 61800-5-2 Stop function STO function (Refer to IEC 61800-5-2: 2007 4.2.2.2 STO.) MR-J4 servo amplifiers have the STO function. The STO function shuts down energy to servo motors, thus removing torque. This function electronically cuts off power supply in the servo amplifier.

10.2.2 About safety

This chapter explains safety of users and machine operators. (1) Professional engineer

Only professional engineers should mount MR-J4 servo amplifiers. Here, professional engineers should meet all the conditions below.

(a) Persons who took a proper training of related work of electrical equipment or persons who can avoid

risk based on past experience.

(b) Persons who have read and familiarized himself/herself with this installation guide and operating manuals for the protective devices (e.g. light curtain) connected to the safety control system.

(2) Applications of the devices

MR-J4 servo amplifiers comply with the following standards. ISO/EN ISO 13849-1 Category 3 PL e, IEC/EN 62061 SIL CL 3, IEC/EN 61800-5-2 (STO), IEC/EN 61800-5-1, IEC/EN 61800-3, IEC/EN 60204-1 MR-J4 servo amplifiers can be used with the MR-J3-D05 safety logic unit, or safety PLCs.

10. APPENDIX

10 - 2

(3) Correct use

Use the MR-J4 servo amplifiers within specifications. Refer to section 1.4 for specifications such as voltage, temperature, etc. Mitsubishi Electric Co. accepts no claims for liability if the equipment is used in any other way or if modifications are made to the device, even in the context of mounting and installation.

WARNING

If you need to get close to the moving parts of the machine for inspection or others, ensure safety by confirming the power off, etc. Otherwise, it may cause an accident. It takes 20 minutes maximum for capacitor discharging. Do not touch the unit and terminals immediately after power off.

(a) Selection of peripheral equipment and wire

The followings are selected based on IEC/EN 61800-5-1, UL 508C, and CSA C22.2 No. 14.

1) Local wiring The following table shows the stranded wire sizes [AWG] and the crimp terminal symbols rated at 75 C/60 C.

Table App. 1 Recommended wire

Converter unit 75 C/60 C stranded wire [AWG] (Note 2)

L1/L2/L3 (Note 3) L11/L21 L+/L- MR-CV11K (Note 1) 8: h/6: i MR-CV18K (Note 1) 4: q/2: - MR-CV30K (Note 1) 2: n/1/0: j MR-CV37K (Note 1) 1/0: j/1/0: j MR-CV45K (Note 1) 1/0: j/-: - MR-CV55K (Note 1) 3/0: k/-: - MR-CV11K4 (Note 1) 10: l/10: l MR-CV18K4 (Note 1) 8: h/6: i 14: g/14: g Exclusive Bus Bar MR-CV30K4 (Note 1) 6: m/4: e MR-CV37K4 (Note 1) 4: e/2: n MR-CV45K4 (Note 1) 4: e/2: n MR-CV55K4 (Note 1) 2: n/1/0 :- MR-CV75K4 (Note 1) 1/0: j/-: - MR-CR55K (Note 1) 2 2/0: d (Note 4)/2 2/0: - MR-CR55K4 (Note 1) 2: c/1/0: -

10. APPENDIX

10 - 3

Drive unit 75 C/60 C stranded wire [AWG] (Note 2)

L11/L21 L+/L- U/V/W/ (Note 3) MR-J4-DU700 (Noe 1) 8: o/6: m MR-J4-DU900 (Note 1) 4: e/2: n MR-J4-DU11K (Note 1) 4: e/2: n MR-J4-DU15K (Note 1) 2: n/1/0: j MR-J4-DU22K (Note 1) 1/0: j/-: - MR-J4-DU30K (Note 1) 2/0: d/2/0: - MR-J4-DU37K (Note 1)

Exclusive Bus Bar

2 2/0: d (Note 4)/-: - MR-J4-DU700_4 (Note 1) 14: g/14: g 10: p/10: p MR-J4-DU900_4 (Note 1) 8: o/6: m MR-J4-DU11K_4 (Note 1) 8: o/6: m MR-J4-DU15K_4 (Note 1) 6: m/6: m MR-J4-DU22K_4 (Note 1) 4: e/2: n MR-J4-DU30K_4 (Note 1) 3: f/2: f MR-J4-DU37K_4 (Note 1) 2: f/1: c MR-J4-DU45K_4 (Note 1) 1/0: d/1/0: - MR-J4-DU55K_4 (Note 1) 1/0: d/2/0: -

Note 1. To connect these models to a terminal block, be sure to use the screws that come with the

terminal block. 2. Alphabets in the table indicate crimping tools. For crimp terminals and applicable tools, refer

to (3) (a) 3) in this section. 3. Select wire sizes depending on the rated output of the servo motors. The values in the table

are sizes based on rated output of the servo amplifiers. 4. When the rated current is less than 175 A, 2/0: d can also be used.

2) Crimping tool

Symbol Servo amplifier-side crimp terminals

Manufacturer Crimp terminal (Note 2) Applicable tool

a FVD5.5-10 YNT-1210S

JST (J.S.T. Mfg. Co., Ltd.)

b FVD22-10 YF-1/E-4

c (Note 1) R38-10 YPT-60-21 YF-1/E-4

d (Note 1) R60-10 YPT-60-21 YF-1/E-4

e FVD22-8 YF-1/E-4

f (Note 1) R38-8 YPT-60-21 YF-1/E-4

g FVD2-4 YNT-1614 h FVD8-5 YF-1/E-4 i FVD14-5 YF-1/E-4

j (Note 1) 60-S8 YF-1/E-4 k (Note 1) 80-10 YF-1/E-4

l FVD5.5-5 YNT-1210S m FVD14-8 YF-1/E-4 n FVD38-8 YF-1/E-4 o FYD8-8 YF-1/E-4 p FVD5.5-8 YNT-1210S

q (Note 1) 22-S5 YF-1/E-4

Note 1. Coat the crimping part with an insulation tube. 2. Some crimp terminals may not be mounted depending on their sizes. Make sure

to use the recommended ones or equivalent ones.

10. APPENDIX

10 - 4

3) Selection example of MCCB and fuse

Use a fuse (T class) or the molded-case circuit breaker (UL 489 Listed MCCB) indicated in the table below. The T class fuses and molded-case circuit breakers in the table are selected examples based on rated I/O of the servo amplifiers. When you select a smaller capacity servo motor to connect it to the servo amplifier, you can also use smaller capacity T class fuses or molded-case circuit breaker than ones in the table. For selecting ones other than Class T fuses and molded-case circuit breakers below, refer to section 1.4.

Converter unit Molded-case circuit breaker (240 V AC) Fuse (300 V)

MR-CV11K NF100-CVFU-60A (100 A frame 60 A) 80 A MR-CV18K NF100-CVFU-100A (100 A frame 100 A) 150 A MR-CV30K NF225-CVFU-150A (225 A frame 150 A) 225 A MR-CV37K NF225-CVFU-200A (225 A frame 200 A) 300 A MR-CV45K NF225-CWU-225A (225 A frame 225 A) 350 A MR-CV55K NF400-SKW-300A (400 A frame 300 A) 400 A MR-CR55K NF225-CWU-175A (225 A frame 175 A) 300 A

Converter unit Molded-case circuit breaker (480 V AC) Fuse (600 V) MR-CV11K4 NF100-HRU-30A (100 A frame 30 A) 40 A MR-CV18K4 NF100-HRU-50A (100 A frame 50 A) 80 A MR-CV30K4 NF100-HRU-80A (100 A frame 80 A) 150 A MR-CV37K4 NF100-HRU-100A (100 A frame 100 A) 150 A MR-CV45K4 NF250-SVU-125A (250 A frame 125 A) 200 A MR-CV55K4 NF250-SVU-150A (250 A frame 150 A) 225 A MR-CV75K4 NF250-SVU-200A (250 A frame 200 A) 300 A MR-CR55K4 NF125-SVU-125A (125 A frame 125 A) 200 A

4) Power supply

This servo amplifier can be used on the condition of overvoltage category III set forth in IEC/EN 60664-1. For the interface power supply, use an external 24 V DC power supply with reinforced insulation on I/O terminals.

5) Grounding

To prevent an electric shock, always connect the protective earth (PE) terminal (marked ) of the servo amplifier to the protective earth (PE) of the cabinet. Do not connect two grounding cables to the same protective earth (PE) terminal. Always connect cables to the terminals one-to- one. This product can cause a DC current in the protective earthing conductor. Where a residual current-operated protective (RCD: earth-leakage current breaker) device is used for protection in case of direct or indirect contact, only an RCD of Type B is allowed on the supply side of this product.

PE terminal PE terminal

10. APPENDIX

10 - 5

(b) EU compliance

The EC directives were issued to standardize the regulations of the EU countries and ensure smooth distribution of safety-guaranteed products. The CE marking proves the compliance of the manufacturer with the EC directives, and this marking also applies to machines and equipment incorporating servos.

1) EMC requirement

MR-J4 servo amplifiers comply with category C3 in accordance with EN 61800-3. As for I/O wires (max. length 10 m. However, 3 m for STO cable for CN8.) and encoder cables (max. length 50 m), use shielded wires and ground the shields. Install an EMC filter and surge protector on the primary side of the servo amplifier. In addition, use a line noise filter for outputs of the servo amplifiers. The following shows recommended products.

EMC filter: Soshin Electric HF3000A-UN series, TF3000C-TX series, COSEL FTB series Surge protector: Okaya Electric Industries RSPD series Line noise filter: Mitsubishi Electric FR- BIF

MR-J4 Series are not intended to be used on a low-voltage public network which supplies domestic premises; Radio frequency interference is expected if used on such a network. The installer shall provide a guide for Installation and use, including recommended mitigation devices. To avoid the risk of crosstalk to signal cables, the installation instructions shall either recommend that the power interface cable be segregated from signal cables.

2) For Declaration of Conformity (DoC)

Hereby, MITSUBISHI ELECTRIC EUROPE B.V. declares that the optional unit is in compliance with EC directives (EMC directive (2014/30/EU) and RoHS directive (2011/65/EU)). For the copy of Declaration of Conformity, contact your local sales office.

(c) USA/Canada compliance

This servo amplifier is designed in compliance with UL 508C and CSA C22.2 No. 14.

1) Installation The minimum cabinet size is 150% of each MR-J4 servo amplifier's volume. Also, design the cabinet so that the ambient temperature in the cabinet is 55 C or less. The servo amplifier must be installed in a metal cabinet. Additionally, mount the servo amplifier on a cabinet that the protective earth based on the standard of IEC/EN 60204-1 is correctly connected. For environment, the units should be used in open type (UL 50) and overvoltage category shown in table in section 10.2.8. The servo amplifier needs to be installed at or below pollution degree 2. Use only copper wires or copper bus bars for wiring.

2) Short-circuit current rating (SCCR)

Suitable For Use On A Circuit Capable Of Delivering Not More Than 100 kA rms Symmetrical Amperes, 500 Volts Maximum.

3) Overload protection characteristics

The MR-J4 servo amplifiers have servo motor overload protective function. (It is set on the basis (full load current) of 120% rated current of the servo amplifier.)

4) Over-temperature protection for motor

Motor Over temperature sensing is not provided by the drive. Integral thermal protection(s) is necessary for motor and refer to section 10.2.8. for the proper connection.

10. APPENDIX

10 - 6

5) Branch circuit protection

For installation in United States, branch circuit protection must be provided, in accordance with the National Electrical Code and any applicable local codes. For installation in Canada, branch circuit protection must be provided, in accordance with the Canada Electrical Code and any applicable provincial codes.

(d) South Korea compliance (MR-CR55K(4) and 30 kW or more of MR-J4-DU)

This product complies with the Radio Wave Law (KC mark) Please note the following to use the product. (A) ,

.

(The product is for business use (Class A) and meets the electromagnetic compatibility requirements. The seller and the user must note the above point, and use the product in a place except for home.) In addition, use an EMC filter, surge protector, ferrite core, and line noise filter on the primary side for inputs. Use a ferrite core and line noise filter for outputs. Use a distance greater than 30 m between the product and third party sensitive radio communications.

(4) General cautions for safety protection and protective measures

Observe the following items to ensure proper use of the MR-J4 servo amplifiers.

(a) For safety components and installing systems, only qualified personnel and professional engineers should perform.

(b) When mounting, installing, and using the MR-J4 servo amplifier, always observe standards and

directives applicable in the country.

(c) The item about noises of the test notices in the manuals should be observed. (5) Residual risk

(a) Be sure that all safety related switches, relays, sensors, etc., meet the required safety standards.

(b) Perform all risk assessments and safety level certification to the machine or the system as a whole.

(c) If the upper and lower power modules in the servo amplifier are shorted and damaged simultaneously, the servo motor may make a half revolution at a maximum.

(d) Only qualified personnel are authorized to install, start-up, repair or adjust the machines in which

these components are installed. Only trained engineers should install and operate the equipment. (ISO 13849-1 Table F.1 No. 5)

(e) Separate the wiring for safety observation function from other signal wirings. (ISO 13849-1 Table F.1

No. 1)

(f) Protect the cables with appropriate ways (routing them in a cabinet, using a cable guard, etc.).

(g) Keep the required clearance/creepage distance depending on voltage you use.

10. APPENDIX

10 - 7

(6) Disposal

Disposal of unusable or irreparable devices should always occur in accordance with the applicable country-specific waste disposal regulations. (Example: European Waste 16 02 14)

(7) Lithium battery transportation

To transport lithium batteries, take actions to comply with the instructions and regulations such as the United Nations (UN), the International Civil Aviation Organization (ICAO), and the International Maritime Organization (IMO). The batteries (MR-BAT6V1SET, MR-BAT6V1, and MR-BAT6V1BJ) are assembled batteries from two batteries (lithium metal battery CR17335A) which are not subject to the dangerous goods (Class 9) of the UN Recommendations.

10.2.3 Installation direction and clearances

CAUTION The devices must be installed in the specified direction. Not doing so may cause a malfunction. Mount the servo amplifier on a cabinet which meets IP54 in the correct vertical direction to maintain pollution degree 2.

80 mm or more

SideFront

100 mm or more

120 mm or more

30 mm or more

30 mm or more

Top

Bottom

Converter unit Drive unit

Converter unit +

Drive unit

10. APPENDIX

10 - 8

10.2.4 Electrical Installation and configuration diagram

WARNING Turn off the molded-case circuit breaker (MCCB) to avoid electrical shocks or damages to the product before starting the installation or wiring.

CAUTION

Securely connect the cables in the specified method and tighten them with the specified torque. Otherwise, the servo motor may operate unexpectedly. The installation complies with IEC/EN 60204-1. The voltage supply to machines must be 20 ms or more of tolerance against instantaneous power failure as specified in IEC/EN 60204-1. Connecting a servo motor of the wrong axis to U, V, W, or CN2_ of the servo amplifier may cause a malfunction.

10. APPENDIX

10 - 9

The following shows representative configuration examples to conform to the IEC/EN/UL/CSA standards.

Connection with resistance regeneration converter unit

Drive unit

STO

Controller

Encoder cable Cabinet sides Machine side

CN8

CN1

CN2

U/V/W/PE

L+ L-

CN40A

PE L11

L- P1 P2 C

CN40

L1L2L3

L21

L11 L21 PE

Resistance regeneration converter unit(3-Phase 240 V AC)

MCCB or

fuse

MCCB or

fuse

MCCB or

fuse

(3-Phase 400 V AC)

To protective equipment (Thermal signal) (Note)

Servo motor Encoder

L+MC CNP1

Connection with power regeneration converter unit

Drive unit

STO

Controller

Encoder cable Cabinet sides Machine side

CN8

CN1

CN2

U/V/W/PE

L+ L-

CN40A

PE L11

L- L1L2L3

L21

L11 L21 PE

(3-Phase 240 V AC)

MCCB or

fuse

MCCB or

fuse

MCCB or

fuse

(3-Phase 400 V AC)

To protective equipment (Thermal signal) (Note)

Servo motor Encoder

L+MC

CN4

Power regeneration converter unit

MC1 MC2

AC reactor

Note. Please use a thermal sensor, etc. for thermal protection of the servo motor.

The connectors described by rectangles are safely separated from the main circuits described by circles. The connected motors will be limited as follows.

HG/HF/HC/HA series servo motors (Mfg.: Mitsubishi Electric) Using a servo motor complied with IEC 60034-1 and Mitsubishi Electric encoder (OBA, OSA)

10. APPENDIX

10 - 10

10.2.5 Signals

(1) Signal The following shows MR-J4-DU30KB signals as a typical example.

CN3

1 2

3

5

4

6

7

9

8

10

11 12

13 14

15 16

17 18

19 20

DI1

MO1

DICOM

LG

DOCOM

DICOM

LZ

DI2

MO2

EM2

LG

MBR

LBR

LA

LB LZR

LAR ALM

DI3INP

TOFB2

STO2TOFB1

STO1 STOCOM

2

CN8

1

4 3

6 5

8 7 TOFCOM

STO I/O signal connector

(2) I/O device Input device

Symbol Device Connector Pin No. EM2 Forced stop 2 CN3 20

STOCOM Common terminal for input signals STO1/STO2 3 STO1 STO1 state input CN8 4 STO2 STO2 state input 5

Output device

Symbol Device Connector Pin No. TOFCOM Common terminal for monitor output signal in STO state 8

TOFB1 Monitor output signal in STO1 state CN8 6 TOFB2 Monitor output signal in STO2 state 7

Power supply

Symbol Device Connector Pin No. DICOM Digital I/F power supply input 5, 10 DOCOM Digital I/F common CN3 3

SD Shield Plate

10. APPENDIX

10 - 11

10.2.6 Maintenance and service

WARNING To avoid an electric shock, only qualified personnel should attempt inspections. For repair and parts replacement, contact your local sales office.

(1) Inspection items

It is recommended that the following points periodically be checked.

(a) Check for loose terminal block screws. Retighten any loose screws.

Drive unit/converter unit Tightening torque: [Nm]

L1 L2 L3 P1 P2 C L+ L- L11 L21 U V W PE MR-J4-DU700_/MR-J4-DU900_/ MR-J4-DU11K_/MR-J4-DU15K_/ MR-J4-DU22K_/MR-J4-DU700_4/ MR-J4-DU900_4/MR-J4-DU11K_4/ MR-J4-DU15K_4/MR-J4-DU22K_4/ MR-J4-DU30K_4/MR-J4-DU37K_4

3.0 1.2

6.0

MR-J4-DU30K_/MR-J4-DU37K_/ MR-J4-DU45K_4/MR-J4-DU55K_4 12.0

MR-CV11K_/MR-CV18K_/MR-CV11K_4/ MR-CV18K_4

2.0

2.0

MR-CV30K_/MR-CV37K_/MR-CV45K_/ MR-CV30K_4/MR-CV37K_4/MR-CV45K_4/ MR-CV55K_4/MR-CV75K_4

6.0 6.0

MR-CV55K 12.0 12.0

MR-CR55K/MR-CR55K4 12.0

(b) Check servo motor bearings, brake section, etc. for unusual noise.

(c) Check the cables and the like for scratches or cracks. Perform periodic inspection according to

operating conditions.

(d) Check that the connectors are securely connected to the servo motor.

(e) Check that the wires are not coming out from the connector.

(f) Check for dust accumulation on the servo amplifier.

(g) Check for unusual noise generated from the servo amplifier.

(h) Check the servo motor shaft and coupling for connection.

(i) Make sure that the emergency stop circuit operates properly such that an operation can be stopped immediately and a power is shut off by the emergency stop switch.

10. APPENDIX

10 - 12

(2) Parts having service life

Service life of the following parts is listed below. However, the service life varies depending on operating methods and environment. If any fault is found in the parts, they must be replaced immediately regardless of their service life. For parts replacement, please contact your local sales office.

Part name Life guideline

Smoothing capacitor 10 years (Note 3)

Relay Number of power-on, forced stop and controller forced stop times: 100,000 times

Number of on and off for STO: 100,000 times Cooling fan 10,000 hours to 30,000 hours (2 years to 3 years)

Battery backup time (Note 1) Approximately 20,000 hours

(equipment power supply: off, ambient temperature: 20 C) Battery life (Note 2) 5 years from date of manufacture

Note 1. The time is for using MR-J4 servo amplifier with a rotary servo motor using MR-BAT6V1SET or MR-BAT6V1BJ. For details

and other battery backup time, refer to each servo amplifier instruction manual. 2. Quality of the batteries degrades by the storage condition. The battery life is 5 years from the production date regardless of the

connection status. 3. The characteristic of smoothing capacitor is deteriorated due to ripple currents, etc. The life of the capacitor greatly depends

on ambient temperature and operating conditions. The capacitor will be the end of its life in 10 years of continuous operation in air-conditioned environment (ambient temperature of 40 C or less for use at the maximum 1000 m above sea level, 30 C or less for over 1000 m to 2000 m).

10.2.7 Transportation and storage

CAUTION

Transport the products correctly according to their mass. Stacking in excess of the limited number of product packages is not allowed. For detailed information on transportation and handling of the battery, refer to the servo amplifier instruction manual. Install the product in a load-bearing place of servo amplifier and servo motor in accordance with the instruction manual. Do not put excessive load on the machine. Do not hold the front cover, cables, or connectors when carrying the servo amplifier. Otherwise, it may drop.

When you keep or use it, please fulfill the following environment.

Item Environment

Ambient temperature

Operation [C] 0 to 55 Class 3K3 (IEC/EN 60721-3-3) Transportation (Note) [C] -20 to 65 Class 2K4 (IEC/EN 60721-3-2) Storage (Note) [C] -20 to 65 Class 1K4 (IEC/EN 60721-3-1)

Ambient humidity

Operation, transportation, storage 5 %RH to 90 %RH

Vibration resistance

Test condition 10 Hz to 57 Hz with constant amplitude of 0.075 mm

57 Hz to 150 Hz with constant acceleration of 9.8 m/s2 to IEC/EN 61800-5-1 (Test Fc of IEC 60068-2-6)

Operation 5.9 m/s2 Transportation (Note) Class 2M3 (IEC/EN 60721-3-2) Storage Class 1M2 (IEC/EN 60721-3-2)

Pollution degree 2

IP rating IP20 (IEC/EN 60529), Terminal block IP00 Open type (UL 50)

Altitude Operation, storage Max. 2000 m above sea level Transportation Max. 10000 m above sea level

Note. In regular transport packaging

10. APPENDIX

10 - 13

10.2.8 Technical data

(1) Converter unit

Item MR-_

CR_ CV_ CR_ CV_ 55K 11K 18K 30K 37K 45K 55K 55K4 11K4 18K4 30K4 37K4 45K4 55K4 75K4

Output Rated voltage 270 V DC to 324 V DC 513 V DC to 648 V DC Rated current [A] 215.9 41 76 144 164 198 238 113.8 21 38 72 82 99 119 150

Power supply

Main circuit (line voltage)

Voltage, Frequency 3-phase 200 V AC to 240 V AC, 50 Hz/60 Hz 3-phase 380 V AC to 480 V AC, 50 Hz/60 Hz

Current [A] 191.3 35 65 107 121 148 200 100.7 18 35 61 70 85 106 130 Control circuit (line voltage)

1-phase 200 V AC to 240 V AC, 50 Hz/60 Hz, 0.3 A 1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz, 0.2 A

Interface (SELV) 24 V DC 10% (required current capacity: MR-CR_, 150 mA; MR-CV_, 350 mA) Pollution degree 2 (IEC/EN 60664-1) Overvoltage category 3-phase 200 V AC/400 V AC: III (IEC/EN 60664-1) Protective class I (IEC/EN 61800-5-1) Short-circuit current rating (SCCR) 100 kA

(2) Drive unit

Item MR-J4-DU_

700_ 900_ 11K_ 15K_ 22K_ 30K_ 37K_ 700_4 900_4 11K_4 15K_4 22K_4 30K_4 37K_4 45K_4 55K_4

Output Rated voltage 3-phase 170 V AC, 360 Hz 3-phase 323 V AC, 360 Hz Rated current [A] 37 54 68 87 126 174 204 17 25 32 41 63 87 102 131 143

Power supply

Main circuit The main circuit power of the drive unit is supplied by the converter unit. Control circuit (line voltage)

1-phase 200 V AC to 240 V AC, 50 Hz/60 Hz, 0.3 A

1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz, 0.2 A

Interface (SELV) 24 V DC 10% (required current capacity: MR-J4-DU_A_, 500 mA; MR-J4-DU_B_, 300 mA) Control method Sine-wave PWM control, current control method Safety observation function (STO) IEC/EN 61800-5-2 (Note)

EN ISO 13849-1 category 3 PL e, IEC 61508 SIL 3, EN 62061 SIL CL 3, and EN 61800-5-2

Mean time to dangerous failure MTTFd 100 [years] (314a) Effectiveness of fault monitoring of a system or subsystem DC = Medium, 97.6 [%]

Probability of dangerous Failure per Hour PFH = 6.4 10-9 [1/h]

Mission time TM = 20 [years] Response performance 8 ms or less (STO input off energy shut off) Pollution degree 2 (IEC/EN 60664-1) Overvoltage category 3-phase 200 V AC/400 V AC: III (IEC/EN 60664-1) Protective class I (IEC/EN 61800-5-1) Short-circuit current rating (SCCR) 100 kA

Note. Servo amplifiers manufactured in August 2015 or later comply with SIL 3 requirements.

10. APPENDIX

10 - 14

(3) Dimensions/mounting hole process drawing

W D

H Front Side

Converter unit/drive unit Variable dimensions [mm]

Mass [kg] W H D

MR-CR55K/MR-CR55K4 300 380 300 22 MR-CV11K/MR-CV18K/ MR-CV11K4/MR-CV18K4 90 380 270 7.0

MR-CV30K/MR-CV37K/MR-CV45K/ MR-CV30K4/MR-CV37K4/MR-CV45K4 150 380 300 10.7

MR-CV55K/MR-CV55K4/MR-CV75K4 300 380 300 26.5 MR-J4-DU700_/MR-J4-DU900_/ MR-J4-DU11K_/MR-J4-DU700_4/ MR-J4-DU900_4/MR-J4-DU11K_4

150 380 300 9.9

MR-J4-DU15K_/MR-J4-DU22K_ MR-J4-DU15K_4_/MR-J4-DU22K_4

240 380 300 15.2

MR-J4-DU30K_/MR-J4-DU37K_ 300 380 300 21 MR-J4-DU30K_4/MR-J4-DU37K_4 240 380 300 16 MR-J4-DU45K_4/MR-J4-DU55K_4 300 380 300 19

Approx. W5 Approx. W3

1910 34

2 36

0 38

0

Approx. 10

36 0

34 2

1019

Converter unit/ Drive unit

Opening

4-A screw Approx. 19

Approx. 19 Approx. 10

W1 W4 W2

W5 W3

Converter unit/Drive unit Variable dimensions [mm] Screw

size W1 W2 W3 W4 W5 A

MR-CR55K/MR-CR55K4/ MR-J4-DU30K_/MR-J4-DU37K_/ MR-J4-DU45K_4/MR-J4-DU55K_4

300 260 20 281 9.5 M6

MR-CV11K/MR-CV18K/MR-CV11K4/ MR-CV18K4 90 - 45 82 4 M5

MR-CV30K/MR-CV37K/MR-CV45K/ MR-CV30K4/MR-CV37K4/ MR-CV45K4/MR-J4-DU700_/ MR-J4-DU900_/MR-J4-DU11K_/ MR-J4-DU700_4/MR-J4-DU900_4/ MR-J4-DU11K_4

150 60 45 142 4 M5

MR-CV55K/MR-CV55K4/MR-CV75K4 300 180 60 282 9 M5 MR-J4-DU15K_/MR-J4-DU22K_/ MR-J4-DU15K_4/MR-J4-DU22K_4/ MR-J4-DU30K_4/MR-J4-DU37K_4

240 120 60 222 9 M5

10.2.9 Check list for user documentation

MR-CV/MR-CR/MR-J4-DU installation checklist for manufacturer/installer The following items must be satisfied by the initial test operation at least. The manufacturer/installer must be responsible for checking the standards in the items. Maintain and keep this checklist with related documents of machines to use this for periodic inspection.

1. Is it based on directive/standard applied to the machine? Yes [ ], No [ ] 2. Is directive/standard contained in Declaration of Conformity (DoC)? Yes [ ], No [ ] 3. Does the protection instrument conform to the category required? Yes [ ], No [ ] 4. Are electric shock protective measures (protective class) effective? Yes [ ], No [ ] 5. Is the STO function checked (test of all the shut-off wiring)? Yes [ ], No [ ]

Checking the items will not be instead of the first test operation or periodic inspection by professional engineers.

10. APPENDIX

10 - 15

10.3 Special coating-specification product (IEC 60721-3-3 Class 3C2)

10.3.1 Summary

This section explains servo amplifiers with a special coating specification. 10.3.2 Specifications

(1) Special coating Using the MR-J4 series in an atmosphere containing a corrosive gas may cause its corrosion with time, resulting in a malfunction. For the printed circuit board of the servo amplifiers with a special coating specification, a urethane coating agent is applied to some parts capable of being coated technically (except LEDs, connectors, terminal blocks, etc.) to improve the resistance to corrosive gases. Use a servo amplifier with a special coating specification specifically for applications susceptible to corrosive gases, including tire manufacturing and water treatment. Although the special coating-specification products have the improved resistance to corrosive gases, proper operations in environments mentioned above are not guaranteed. Therefore, perform periodic inspections for any abnormality.

(2) Standard for corrosive gases

In IEC 60721-3-3, corrosive gases refer to sea salt, sulfur dioxide, hydrogen sulfide, chlorine, hydrogen chloride, hydrogen fluoride, ammonia, ozone, and nitrogen oxides shown in the environmental parameter column of the table below. The table also shows the corrosive gas concentrations defined in IEC 60721-3-3, Class 3C2.

Environmental parameter Unit

3C2 Mean value Maximum value

a) Sea salt None Salt mist b) Sulfur dioxide cm3/m3 0.11 0.37 c) Hydrogen sulfide cm3/m3 0.071 0.36 d) Chlorine cm3/m3 0.034 0.1 e) Hydrogen chloride cm3/m3 0.066 0.33 f) Hydrogen fluoride cm3/m3 0.012 0.036 g) Ammonia cm3/m3 1.4 4.2 h) Ozone cm3/m3 0.025 0.05 i) Nitrogen oxides cm3/m3 0.26 0.52

The special coating-specification products have the improved corrosion resistance in environments with corrosive gas concentrations conforming to IEC 60721-3-3, Class 3C2. We tested typical models and confirmed that their corrosive gas resistance was improved, compared with the standard models.

10. APPENDIX

10 - 16

10.4 EC declaration of conformity

The MR-J4-_DU series drive units comply with the safety component laid down in the Machinery directive.

10. APPENDIX

10 - 17

10.5 Status of general-purpose AC servo products for compliance with the China RoHS directive

10.5.1 Summary

The China RoHS directive: (Management Methods for Controlling Pollution by Electronic Information Products) came into effect on March 1, 2007. The China RoHS directive was replaced by the following China RoHS directive: (Management Methods for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products). The succeeding China RoHS directive has been in effect since July 1, 2016. The China RoHS directive restricts the use of six hazardous substances (lead, mercury, cadmium, hexavalent chromium, polybrominated biphenyls (PBB), and polybrominated diphenyl ethers (PBDE)) and other hazardous substances specified by the State (currently no applicable substances). The EU RoHS directive (2011/65/EU) also restricts the use of the above six hazardous substances. 10.5.2 Status of our products for compliance with the China RoHS directive

The following tables show the content of six hazardous substances in our products and Environment-Friendly Use Period marks. This table is created based on the standard SJ/T11364.

Substance name Threshold standard

Part name

Hazardous substance (Note 1)

Environment- Friendly Use Period mark

(Note 2) Remark

Lead (Pb)

Mercury (Hg)

Cadmium (Cd)

Hexavalent chromium (Cr(VI))

PBB PBDE

Threshold of cadmium: 0.01 wt% (100 ppm), Threshold of substances other than cadmium: 0.1 wt% (1000 ppm)

Servo amplifier Servo system controller

Mounting board

Heat sink

Resin cabinet

Plate and screw

Servo motor Bracket

Mounting board

Resin cabinet

Core and cable

Cable product Cable Including connector set Connector

Optional unit Mounting board

Resin cabinet

Plate and screw Note 1. : Indicates that said hazardous substance contained in all of the homogeneous materials for this part is below the limit

requirement of GB/T26572. : Indicates that said hazardous substance contained in at least one of the homogeneous materials for this part is above the

limit requirement of GB/T26572. 2. Indications based on "Marking for the restriction of the use of hazardous substances in electrical and electronic product"

[SJ/T11364-2014]

Indicates that a certain hazardous substance is contained in the product manufactured or sold in China. Observe safety and usage precautions for the product, and use it within a limited number of years from the production date. Thereby, any of the hazardous substances in the product does not cause environmental pollution, or seriously affect human health or property.

Indicates that no certain hazardous substance is contained in the product.

10. APPENDIX

10 - 18

10.5.3 Difference between the China RoHS directive and the EU RoHS directive

The China RoHS directive allows no restriction exemption unlike the EU RoHS directive. Although a product complies with the EU RoHS directive, a hazardous substance in the product may be considered to be above the limit requirement (marked " ") in the China RoHS directive. The following shows some restriction exemptions and their examples according to the EU RoHS directive.

Lead as an alloying element in steel for machining purposes and in galvanized steel containing up to 0.35% lead by weight, lead as an alloying element in aluminum containing up to 0.4% lead by weight, and copper alloy containing up to 4% lead by weight, e.g. brass-made insert nuts Lead in high melting temperature type solders (i.e. lead-based alloys containing 85% by weight or more lead) Electrical and electronic components containing lead in a glass or ceramic other than dielectric ceramic in capacitors, e.g. piezoelectronic devices Electrical and electronic components containing lead in a glass or ceramic matrix compound, e.g. chip resistors

10.5.4 Status of our products for compliance with the China RoHS directive (Chinese)

The following shows the table in Chinese according to "Management Methods for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products".

(1)

(2)

(Pb)

(Hg)

(Cd)

(Cr(VI)) PBB PBDE

0.01wt%(100ppm)

0.1wt%(1000ppm)

1. : GB/T26572

: GB/T26572

2. [SJ/T11364-2014]

/

REVISION

*The manual number is given on the bottom left of the back cover. Print Data *Manual Number Revision Jan. 2015 SH(NA)030153ENG-A First edition Aug. 2015 SH(NA)030153ENG-B Altitude of 2000 m above sea level is disclosed.

Safety Instructions 4. Additional instructions Relevant manuals Section 1.1.1 Section 1.1 Section 1.2.1 Section 1.2.2 (1) (a) Section 1.2.2 (1) (b) Section 1.2.2 (2) (a) Section 1.2.2 (2) (b) Section 1.4 (2) (b) Section 1.5.1 (1) Section 1.5.1 (2) (a) 1) a) Section 1.5.1 (2) (a) 2) a) Section 1.6 Section 2.5 Section 3.1.2 (1) (a) Section 3.1.2 (1) (b) Section 3.1.2 (2) (a) Section 3.1.2 (2) (b) Section 3.3.2 (1) Section 6.2 Section 6.2.1 (2) Section 6.2.2 Section 6.2.3 Section 9.3.2 Section 9.5 (1) Section 9.5 (2) Section 9.10.3 (1) (a) Section 9.10.3 (1) (b) Section 9.10.3 (2) (a) 1) Section 9.10.3 (2) (a) 2) Section 9.10.3 (2) (b) 1) Section 9.10.3 (2) (b) 2) Section 9.10.3 (3) App. 2

The environment is changed. The part of table is changed. The diagram is partially changed. The note is partially changed. The part of table is changed. The table and the note are partially changed. The table and the note are partially changed. The table and the note are partially changed. The table and the note are partially changed. The diagram is changed. The part of table is changed. The part of table is changed. The part of table is changed. The note is changed. Added. The note is partially changed. The note is partially changed. The note is partially changed. The note is partially changed. The diagram is partially changed. The sentences are partially changed. The sentences are partially changed. The table and the note are partially changed. The part of table is changed. The note is partially changed. The caution and the note are added. The sentences are changed. The note is partially changed. The note is partially changed. The note is partially changed. The note is partially changed. The note is partially changed. The note is partially changed. The diagram is partially changed. Partially changed.

Feb. 2017 SH(NA)030153ENG-C MR-CV_ is added. MR-J4-DU900B_ to MR-J4-DU22KB_ are added. MR-D30 is supported. MR-CR55_ and MR-J4-DU_ with a special coating specification are added.

Safety Instructions 4. Additional instructions The environment is changed. Relevant manuals The part of table is changed. Chapter 1 to Chapter 9 The contents are entirely changed. App. 3 Added. App. 4 Added. App. 5 Added.

May 2017 SH(NA)030153ENG-D Maximally increased torque function for MR-J4-DU900B is added. 4. Additional instructions (3) Sentences in test run and adjustment are changed. Section 1.1 The part of table is changed.

Print Data *Manual Number Revision May 2017 SH(NA)030153ENG-D Section 1.3.3 The part of table is changed.

Section 1.4.1 (2) The part of table is changed. Section 1.4.3 (1) The part of table is changed. Section 1.6.1 Note 8 is added. Section 3.1 Note 4 is added. Section 3.3.1 (2) Note 1 is changed. Section 3.3.4 (1) Sentences in RDYB (Operation permission) are changed. Section 3.6 Note 1 is changed. Section 5.1 (1) (a) Note 2 is changed. Section 5.3.1 PC23 is added. Section 5.4.1 Note 3 is changed. Section 6.1.1 (2) The sentences and table are changed. Section 6.1.2 (2) Note 2 is changed. Section 6.2.1 (2) The sentences and table are changed. Section 6.2.2 (2) Note 2 is changed. Section 6.3.1 (2) The sentences and table are changed. Section 8.3.1 The table is changed. Section 8.3.2 Note 8 is added and changed. Section 8.5 (1) Changed note 3 for the table of MR-CR_. App.2.3 The item name is changed.

Jun. 2018 SH(NA)030153ENG-E The passing wiring of the control circuit power supply is added. 3. To prevent injury, note

the following The sentences are added.

4. Additional instructions The sentences are added and changed. Section 1.6 Note is added. 2. INSTALLATION CAUTION is added. Section 3.3.1 (2) Note is added. Section 3.3.3 (2) Added. Section 3.4 Caution and Note are added. Section 4.3.1 (2) Note is added. Section 5.1.1 (1) (a) The sentences in the table are partially deleted. Section 5.1.1 (1) (c) The sentences in the table are partially deleted. Section 5.1.1 (2) (a) The sentences in the table are partially deleted. Section 5.1.1 (2) (c) The sentences in the table are partially deleted. Section 5.1.2 (1) (a) The sentences in the table are partially deleted. Section 5.1.2 (2) (a) The sentences in the table are partially deleted. Section 5.1.1 (2) (c) The sentences in the table are partially deleted. Section 5.2 CAUTION is added. Section 5.4.2 CAUTION is added. Section 5.4.3 (1) The sentences are changed. Section 5.4.3 (2) The sentences are changed. Section 5.5 Added. Section 8.2.2 (1) The contents are entirely changed. Section 8.3 POINT is changed. Section 8.3.2 Note is added. Section 8.4.2 Added. Section 8.5.2 (3) Added. Section 8.11.3 POINT is added. Section 8.11.4 POINT is added. Section 10.2.2 (1) (b) The sentences are changed. Section 10.2.7 CAUTION is added.

Print Data *Manual Number Revision Nov. 2020 SH(NA)030153ENG-F The dimensions are changed.

Section 7.1 The diagrams are changed. Section 7.2 The diagrams are changed. Section 7.3 The diagrams are changed.

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.

2015 MITSUBISHI ELECTRIC CORPORATION

MEMO

MELSERVO is a trademark or registered trademark of Mitsubishi Electric Corporation in Japan and/or other countries. All other product names and company names are trademarks or registered trademarks of their respective companies.

Warranty 1. Warranty period and coverage

We will repair any failure or defect hereinafter referred to as "failure" in our FA equipment hereinafter referred to as the "Product" arisen during warranty period at no charge due to causes for which we are responsible through the distributor from which you purchased the Product or our service provider. However, we will charge the actual cost of dispatching our engineer for an on-site repair work on request by customer in Japan or overseas countries. We are not responsible for any on-site readjustment and/or trial run that may be required after a defective unit are repaired or replaced.

[Term] For terms of warranty, please contact your local FA center.

[Limitations] (1) You are requested to conduct an initial failure diagnosis by yourself, as a general rule.

It can also be carried out by us or our service company upon your request and the actual cost will be charged. However, it will not be charged if we are responsible for the cause of the failure.

(2) This limited warranty applies only when the condition, method, environment, etc. of use are in compliance with the terms and

conditions and instructions that are set forth in the instruction manual and user manual for the Product and the caution label affixed to the Product.

(3) Even during the term of warranty, the repair cost will be charged on you in the following cases;

(i) a failure caused by your improper storing or handling, carelessness or negligence, etc., and a failure caused by your hardware or software problem

(ii) a failure caused by any alteration, etc. to the Product made on your side without our approval

(iii) a failure which may be regarded as avoidable, if your equipment in which the Product is incorporated is equipped with a safety device required by applicable laws and has any function or structure considered to be indispensable according to a common sense in the industry

(iv) a failure which may be regarded as avoidable if consumable parts designated in the instruction manual, etc. are duly maintained and replaced

(v) any replacement of consumable parts (battery, fan, smoothing capacitor, etc.)

(vi) a failure caused by external factors such as inevitable accidents, including without limitation fire and abnormal fluctuation of voltage, and acts of God, including without limitation earthquake, lightning and natural disasters

(vii) a failure generated by an unforeseeable cause with a scientific technology that was not available at the time of the shipment of the Product from our company

(viii) any other failures which we are not responsible for or which you acknowledge we are not responsible for

2. Term of warranty after the stop of production (1) We may accept the repair at charge for another seven (7) years after the production of the product is discontinued. The

announcement of the stop of production for each model can be seen in our Sales and Service, etc.

(2) Please note that the Product (including its spare parts) cannot be ordered after its stop of production.

3. Service in overseas countries Our regional FA Center in overseas countries will accept the repair work of the Product. However, the terms and conditions of the repair work may differ depending on each FA Center. Please ask your local FA center for details.

4. Exclusion of loss in opportunity and secondary loss from warranty liability

Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:

(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.

(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.

(3) Special damages and secondary damages whether foreseeable or not, compensation for accidents, and compensation for damages to products other than Mitsubishi products.

(4) Replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.

5. Change of Product specifications

Specifications listed in our catalogs, manuals or technical documents may be changed without notice.

6. Application and use of the Product (1) For the use of our AC Servo, its applications should be those that may not result in a serious damage even if any failure or

malfunction occurs in AC Servo, and a backup or fail-safe function should operate on an external system to AC Servo when any failure or malfunction occurs.

(2) Our AC Servo is designed and manufactured as a general purpose product for use at general industries.

Therefore, applications substantially influential on the public interest for such as atomic power plants and other power plants of electric power companies, and also which require a special quality assurance system, including applications for railway companies and government or public offices are not recommended, and we assume no responsibility for any failure caused by these applications when used In addition, applications which may be substantially influential to human lives or properties for such as airlines, medical treatments, railway service, incineration and fuel systems, man-operated material handling equipment, entertainment machines, safety machines, etc. are not recommended, and we assume no responsibility for any failure caused by these applications when used. We will review the acceptability of the abovementioned applications, if you agree not to require a specific quality for a specific application. Please contact us for cons

Manualsnet FAQs

If you want to find out how the MR-J4-DU-B-RJ Mitsubishi works, you can view and download the Mitsubishi MR-J4-DU-B-RJ Drive Unit Instruction Manual on the Manualsnet website.

Yes, we have the Instruction Manual for Mitsubishi MR-J4-DU-B-RJ as well as other Mitsubishi manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Instruction Manual should include all the details that are needed to use a Mitsubishi MR-J4-DU-B-RJ. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Mitsubishi MR-J4-DU-B-RJ Drive Unit Instruction Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Mitsubishi MR-J4-DU-B-RJ Drive Unit Instruction Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Mitsubishi MR-J4-DU-B-RJ Drive Unit Instruction Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Mitsubishi MR-J4-DU-B-RJ Drive Unit Instruction Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Mitsubishi MR-J4-DU-B-RJ Drive Unit Instruction Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.