- Manuals
- Brands
- Mitsubishi
- Drive Unit
- MD-AX520-2.0K
- Instruction Manual
Mitsubishi MD-AX520-2.0K Drive Unit Instruction Manual PDF
Summary of Content for Mitsubishi MD-AX520-2.0K Drive Unit Instruction Manual PDF
1/16 BCN-C22005-560
MD-AX520-5.0K, 7.0K Instruction Manual Supplement This Instruction Manual Supplement provides the dedicated specification for the magnet motor drive unit MD-AX520-5.0K and 7.0K. For the information not found in this Instruction Manual Supplement, please refer to the Instruction Manual of the MD-AX520 series.
1. Drive units to be used with motors Refer to: Chapter 1 of the Specifications/Instruction Manual, 1.1.3 Drive units to
be used with motors Use the drive units and motors in the following combinations. (The drive unit and motor of the same capacity are used together.)
Drive Unit Motor MD-AX520-0.5K MM-CF52 MD-AX520-1.0K MM-CF102 MD-AX520-1.5K MM-CF152 MD-AX520-2.0K MM-CF202 MD-AX520-3.5K MM-CF352 MD-AX520-5.0K MM-CF502 MD-AX520-7.0K MM-CF702
2. Installation in control box
Refer to: Chapter 2 of the Specifications/Instruction Manual, 2.1.2 Installation in control box
When installing the drive unit in a control box, the internal temperature of the control box must not exceed the permissible value due to drive-unit generated heat and peripheral-generated heat. Placing a heat sink outside the control box can reduce the heat generated inside the control box Refer to: Chapter 7 of the Specifications/Instruction Manual, 7.1.3 Option
list (External heat sink mounting attachment)
Measurement positions of ambient temperatures
5cm 5cm
5cm Measurement position
Drive unit Measurement position
2/16 BCN-C22005-560
Layout of drive units within control box
Ventilation fan
Drive unit
(Correct example) (Incorrect example)
Drive unit
Position of ventilation fan
Built-in cooling fans
Accommodation of two or more drive units
Drive unit Drive unit Drive unit
Drive unit
(Incorrect example)(Correct example)
NOTICE
Leave the specified clearances between the drive unit and control box walls or other equipment. Not doing so can cause a failure. In addition, improper convection of air in the control box will reduce the heat dissipation effect. Fully consider the equipment layout in the control box and the use of a cooling fan for ventilation, for example.
10cm or more
5cm or more
Drive unit 5cm or more
1cm or more for 3.5K or less. These clearances are also required for replacement of the cooling fan.
Leave sufficient clearances above and under the drive unit to ensure adequate ventilation.
Cooling fan built in the drive unit
Cooling air
10cm or more
3/16 BCN-C22005-560
Installation in enclosed control box The following is the relationship between the internal temperature rise and heat dissipation area of an enclosed control box (hereafter referred to as the enclosure) which accommodates the drive unit.
P A = K T
A: Heat dissipation area (m2) P: All losses produced in enclosure (W) T: Difference between enclosure inside and outside-air temperatures (C) K: Heat dissipation factor
The heat dissipation area A does not include the area in contact with a structures which interfere with heat dissipation, e.g. floor and walls. The heat dissipation factor K used is normally 5 to 6, which depends on the enclosure structure, the layout of parts in the enclosure, and the outside-air temperature.
Produced losses The following table indicates the losses produced during rated load operation of the drive unit.
Unit (W)
Capacity Drive Unit-Produced Loss during
Continuous Rated Load Operation
Loss Produced in Enclosure when Drive Unit Heat Sink Is Placed Outside
of Enclosure 0.5K 55 1.0K 70 1.5K 110 33 2.0K 150 45 3.5K 230 69 5.0K 310 93 7.0K 420 126
4/16 BCN-C22005-560
3. Selection of peripheral devices Refer to: Chapter 2 of the Specifications/Instruction Manual, 2.2.2 Selection of
peripheral devices (1) Wire size
AC power input terminals R, S, T, motor connection terminals U, V, W, DC reactor connection terminals P/+, P1, DC terminals P/+, N/-, ground terminals
Wire Sizes, Unit: mm2 Capacity (K)
Terminal Screw Size R, S, T U, V, W P/+, P1, N/- Connection
Wire Type
0.5 1.0 1.5 2.0
2 to 5.5 2 to 5.5 2 to 5.5 2 to 5.5
3.5
M4
3.5 to 5.5 3.5 to 5.5 3.5 to 5.5 3.5 to 5.5 5.0 5.5 to 14 5.5 to 14 5.5 to 14 7.0
M5 14 8 to 14 14
5.5 to 14
Power cable 600V vinyl
wire or equivalent
Control circuit power supply terminals R1, S1
Capacity Terminal Screw Size Wire Size, Unit: mm2 Wire Type
All capacities
M4 2 to 5.5 Power cable 600V vinyl wire or equivalent
Control circuit terminals (all terminals)
Capacity Terminal Screw Size Wire Size, Unit: mm2 Wire Type
All capacities
M3.5 0.5 to 2
Twisted shielded wire, polyethylene insulated vinyl wire for instrumentation or equivalent
MEMO Refer to the corresponding instruction manual for wires connection of a stand- alone option connected to the DC terminals P/+, N/-.
5/16 BCN-C22005-560
NOTICE
Choose the size of the wires connected to the motor connection terminals so that a voltage drop due to the wires is less than 4V. The minimum wire size in the above selection table assumes that the wiring length is less than 20m. A voltage drop can be found by the following expression: Line voltage drop (mV) = 3 wire resistance (/km) wiring length (m) current (A)
Use the ground cable which is as thick as possible. We recommend you to use the 0.75mm2 or less wire size for the control circuit terminals. Using the wire size of 1.25mm2 or more may cause the front cover to bulge, leading to a contact fault in the operation panel or parameter unit, when there are many cables wired, for example.
(2) Crimping terminals
Wire Size, Unit: mm2 Terminal Screw Size Crimping Terminal Size 0.5 M3.5 1.25-3.5 0.75 M3.5 1.25-3.5 1.25 M3.5 1.25-3.5
M3.5 2-3.5 2
M4 2-4 M4 5.5-4
3.5/5.5 M5 5.5-5
8 M5 8-5 14 M5 14-5
(3) No-fuse breakers, magnetic contactors
No-Fuse Breaker Capacity (K) With power factor
improving reactor Without power factor
improving reactor Magnetic Contactor
0.5 30AF/5A 1.0 30AF/10A 1.5 30AF/15A
S-N10
2.0 30AF/15A 30AF/20A S-N11, S-N12 3.5 30AF/30A S-N20 5.0 50AF/40A 50AF/50A S-N25 7.0 50AF/50A 100AF/60A S-N35
6/16 BCN-C22005-560
NOTICE
Select the no-fuse breaker according to the power supply capacity. Install one no-fuse breaker per drive unit. When the breaker on the drive unit primary side trips, check for the wiring fault (short circuit), damage to internal parts of the drive unit, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
(4) Earth leakage circuit breakers
Selection method Use the earth leakage circuit breaker which has harmonic/surge suppression. Our product: Progressive Super Series NV-SF, NV-CF
Earth Leakage Circuit Breaker Capacity (K)
With power factor improving reactor Without power factor improving reactor 0.5 30AF/5A 1.0 30AF/10A 1.5 30AF/15A 2.0 30AF/15A 30AF/20A 3.5 30AF/30A 5.0 50AF/40A 50AF/50A 7.0 50AF/50A 100AF/60A
MEMO
Leakage currents from the wiring and motor include frequency components of a higher degrees than those from the commercial power supply. Therefore, the earth leakage circuit breaker which is not a harmonic/surge suppression product can cause unnecessary operations.
7/16 BCN-C22005-560
Setting of rated current sensitivity Rated current sensitivity 10 {lg1 + lgn + K (lg2 + lgm)}
K: Constant in consideration of harmonics
Earth Leakage Circuit Breaker Type Our product
K
Harmonic/ surge
suppression product
NV-C/NV-S/MN series, NV30-FA, NV50-FA, BV-C2, earth leakage alarm
breaker (NF-Z), NV-ZHA, NV-H 1
NV
Ig1 Ign Ig2 Igm
MDrive unit
Noise filter
General product
BV-C1, BC-V, NVB, NV-L, NV-G2N, NV-G3NA and NV-2F earth leakage relay (except NV-ZHA), NV with AA neutral wire open-phase protection
3
lg1: Leakage current in cable path between earth
leakage circuit breaker and drive unit (see Fig. 2- 2)
lg2: Leakage current in cable path between drive unit and motor (see Fig. 2-2)
lgn: Leakage current of filter connected on input side Refer to Chapter 7 of the Specifications/ Instruction Manual, 7.1.3 Option list for our dedicated filters.
lgm: Leakage current of motor (see Fig. 2-3)
0
20
40
60
80
100
120
2 3.5 5.5
8 1422 30 38
60 80 100
150
(200V 60Hz)
Fig. 2-2 Example of Leakage Current per 1km of Cable Path When CV Cable Is Routed in Metal Conduit
Wire size (mm )
Le ak
ag e
cu rre
nt (m
A )
2
0.1 1.5 3.7 2.2
7.5 15 22 11
37 30
55 45
0.2 0.3
0.5 0.7 1.0
2.0
5.5 18.5
Fig. 2-3 Leakage current example of three-phase induction motor during the commercial power supply operation (200V 60Hz)
Le ak
ag e
cu rre
nt (m
A )
Motor capacity (kW)
NOTICE
Install the leakage current circuit breaker on the input side (power supply side) of the drive unit. Installation on the output side will cause the earth leakage circuit breaker to overheat or malfunction.
MEMO A leakage current may flow into the other lines through the ground cables, etc.
8/16 BCN-C22005-560
4. Terminal layout and connection specifications Refer to: Chapter 3 of the Specifications/Instruction Manual, 3.2.2 Terminal layout
and connection specifications
AX520-0.5, 1.0K AX520-1.5K to 3.5K
Layout R
R1
S T U V W PR
S1 P1 PXP/ +N/ -
Charge lamp Jumper
Layout R
R1
S T U V W PR
S1
P1
PX
N/ - P/+
Charge lamp
Jumper
Screw size M4
Tightening torque 1.5Nm
Screw size M4
Tightening torque 1.5Nm
MD-AX520-5.0K, 7.0K Layout
R
N/-
S T U V W
P1 P/+ PR PX
R1
R
S1
S
Charge lamp
Jumper Screw size
M5 Tightening torque
2.5Nm
CAUTION Tighten the terminal screws to the specified torque. Undertightening can cause an inter- terminal short circuit or malfunction. Overtightening can cause the screws and unit to be damaged, resulting in a short circuit malfunction or the like.
9/16 BCN-C22005-560
5. Wiring of the control circuit power supply terminals R1, S1
Refer to: Chapter 3 of the Specifications/Instruction Manual, 3.2.4 Wiring of the control circuit power supply terminals R1, S1
Wire these terminals when you want to supply the control circuit power of the drive unit to retain the alarm signal if the magnetic contactor (MC) on the power supply side is opened to switch off main circuit power when the protective circuit is activated.
1) Remove the jumpers across the terminals R-R1, S-S1. 2) Wire the terminals R1, S1 from the primary side of the magnetic contactor.
MD-AX520-0.5K to 3.5K MD-AX520-5.0K, 7.0K
1) Loosen the upper screws. 2) Remove the lower screws.
R S T
Main circuit terminal block
R1 S1
3) Remove the jumper
4) Connect the separate
power supply cable for the
control circuit to the lower
terminals (R1, S1).
Power supply terminal block
for the control circuitR S T
MC
R1 S1
Power supply
terminal block
for the control circuit
Main power supply
1) Loosen the upper screws. 2) Remove the lower screws. 3) Pull the jumper toward you
to remove.
4) Connect the separate
power supply cable for the
control circuit to the upper
terminals (R1, S1).
MEMO An error display (E.OC1) will be provided if you turn on the start signal with power supplied to only the R1 and S1 terminals.
CAUTION
When you have energized the AC power input terminals R, S, T, always energize the control circuit power supply terminals R1, S1, too. The drive unit may be damaged if you energize the AC power input terminals without the control circuit power supply terminals being energized.
Before wiring the control circuit power supply terminals, always remove the jumpers across the terminals R-R1 and across the terminals S-S1. Not doing so can cause a power supply short circuit.
When using MD-AX520-5.0K and 7.0K, connecting the power supply cable to the lower terminals may break the drive unit. Do not connect the power supply cable to those terminals.
10/16 BCN-C22005-560
6. Wiring of the brake resistor connection terminals P/+, PR Refer to: Chapter 3 of the Specifications/Instruction Manual, 3.2.8 Wiring of the
brake resistor connection terminals P/+, PR These terminals are designed for connection of the heavy-duty brake resistor.
1) Remove the screws in the terminals PR and PX and disconnect the jumper.
MD-AX520-0.5K to 3.5K MD-AX520-5.0K, 7.0K
Terminal PX
Terminal PR
Jumper
Jumper Terminal PX
Terminal PR
2) Connect the brake resistor to the terminals P/+, PR.
MD-AX520-0.5K, 1.0K MD-AX520-1.5K to 3.5K MD-AX520-5.0K, 7.0K
Terminal P/+
Terminal PR
Terminal PR Terminal P/+
Terminal P/+ Terminal PR
3) Change the Pr. 30 and Pr. 70 settings.
NOTICE Always remove the jumper across the terminals PR-PX. Connect only the specified brake resistor.
11/16 BCN-C22005-560
7. Standard specifications Refer to: Chapter 7 of the Specifications/Instruction Manual, 7.1.1 Standard
specifications (1) Rating specifications
MD-AX520- 0.5K 1.0K 1.5K 2.0K 3.5K 5.0K 7.0K Applicable motor capacity (kW) 0.5 1.0 1.5 2.0 3.5 5.0 7.0
Overload capacity 150% 60s (inverse-time characteristics)
Max. value/time 150% 5s 100% 5s
O ut
pu t
Regenerative
braking torque Permissible duty 3%ED 2%ED
Rated input AC voltage Three phase, 200V to 220V 50Hz, 200 to 230V 60Hz
Permissible AC voltage fluctuation 170 to 242V 50Hz, 170 to 253V 60Hz
Permissible frequency fluctuation 5%
P ow
er s
up pl
y
Power supply system capacity (kVA) 1.1 2.2 3.1 4.3 7.3 11.7 15.4
Protective structure Enclosed type (IP20)
Cooling system Self-cooling Air cooling
Approx. weight (kg) 2.0 2.5 3.5 3.5 3.5 6.0 6.0
MEMO
The rated output capacity and rated speed of the motor used with the drive unit assume the rated input AC voltage indicated above. They cannot be guaranteed when the power supply voltage drops.
The overload capacity indicated in % is the ratio of the overload current to the motor's rated output.
The power supply system capacity varies with the values of the power supply side impedances (including those of the input reactor and cables).
The drive unit cannot run multiple motors.
12/16 BCN-C22005-560
8. Outline drawings
Refer to: Chapter 7 of the Specifications/Instruction Manual, 7.1.2 Outline drawings
MD-AX520-0.5K, 1.0K MD-AX520-1.5K to 3.5K 110
26 0
D
95 6
5
24 5
2- 6 hole
Drive Unit Type D
0.5K 110
1.0K 125
150
26 0
140
143
125 6
5
24 549.5
2- 6 hole
(Unit: mm) (Unit: mm) MD-AX520-5.0K, 7.0K
220
2 6
0
170
211
195 6
2 4
5
10.5 2-6 hole
84
(Unit: mm)
13/16 BCN-C22005-560
9. Option list Refer to: Chapter 7 of the Specifications/Instruction Manual, 7.1.3 Option list
Name Type Applicable Capacity Application, Specifications, Etc.
Heat sink external mounting attachment
FR-A5CN01 FR-A5CN02
1.5K to 3.5K 5.0K, 7.0K
Used to place only the heat sink section of the drive unit in the outside of the control box.
Power factor improving DC reactor
FR-BEL-0.4K FR-BEL-0.75K FR-BEL-1.5K FR-BEL-2.2 FR-BEL-3.7K FR-BEL-5.5K FR-BEL-7.5K
0.5K 0.1K 1.5K 2.0K 3.5K 5.0K 7.0K
Used to improve the input power factor (overall power factor about 95%) and cooperate with the power supply.
Power factor improving AC reactor
FR-BAL-0.4K FR-BAL-0.75K FR-BAL-1.5K FR-BAL-2.2K FR-BAL-3.7K FR-BAL-5.5K FR-BAL-7.5K
0.5K 1.0K 1.5K 2.0K 3.5K 5.0K 7.0K
Used to improve the input power factor (overall power factor about 90%) and cooperate with the power supply.
High-duty brake resistor FR-ABR-0.4K FR-ABR-0.75K FR-ABR-2.2K FR-ABR-3.7K FR-ABR-5.5K FR-ABR-7.5K
0.5K 1.0K 1.5K, 2.0K 3.5K 5.0K 7.0K
Used to improve the braking capability of the drive unit. (Permissible duty: 10%ED)
S ta
nd -a
lo ne
ty pe
BU brake unit BU-1500 BU-3700 BU-7.5K BU-15K
0.5K, 1.0K 1.5K, 2.0K, 3.5K 2.0K, 3.5K, 5.0K, 7.0K 5.0K, 7.0K
Used with a discharge resistor to improve the braking capability of the drive unit.
14/16 BCN-C22005-560
10. Motor Specifications
Refer to: Chapter 7 of the Specifications/Instruction Manual, 7.2 Motor Specifications
2000r/min Series Motor Item MM-
CF52 MM-
CF102 MM-
CF152 MM-
CF202 MM-
CF352 MM-
CF502 MM-
CF702 Compatible drive unit
MD-AX520- MD-CX520-
0.5K 1.0K 1.5K 2.0K 3.5K 5.0K 7.0K
Rated output [kW] 0.5 1.0 1.5 2.0 3.5 5.0 7.0 Continuous characteristics (Note 1) Rated torque [Nm] 2.39 4.78 7.16 9.55 16.70 23.86 33.41
Rated speed (Note 1) [r/min] 2000 Maximum speed [r/min] 3000 Permissible instantaneous speed [r/min] 3450
Maximum torque [Nm] 4.78 9.56 14.32 19.09 33.41 47.73 66.82 Inertia moment J [10-4kgm2] 6.6 13.7 20.0 45.5 85.6 120.0 160.0 Permissible ratio of load inertia moment to motor shaft inertia moment (Note 2)
100 times max. 50 times max.
Rated current [A] 1.81 3.70 5.22 7.70 12.50 20.5 27.0 Insulation class Class F Structure Totally closed, self-cooling (protection system: IP44 (Note 3))
Ambient temperature -10C to +40C (non-freezing) Ambient humidity 90%RH or less (non-condensing) Storage temperature -20C to +70C (non-freezing) Storage humidity 90%RH or less (non-condensing)
Ambience Indoors (no exposure to direct sunlight), no corrosive and flammable gases, oil mist, dust and dirt.
Altitude Max. 1000m above sea level
Environmental conditions (Note 4)
Vibration X: 9.8m/s2, Y: 24.5m/s2 Weight [kg] 5.1 7.2 9.3 13.0 19.0 27.0 36.0 Note 1. When the power supply voltage drops, the output and rated speed cannot be guaranteed.
2. This value assumes that the load torque is about 20% of the rated motor torque. If the load torque is larger, the permissible ratio of load inertia moment to motor shaft inertia moment is smaller. Consult Mitsubishi if the ratio of load inertia moment to motor shaft inertia moment exceeds the indicated value.
3. Except the shaft through portion. 4. When the motor is to be operated in a place where it will be exposed to oil and/or water,
e.g. machine field, consult us since a motor of optional features is needed.
15/16 BCN-C22005-560
Torque characteristics
200
150
100
50
0 100 1000 2000 3000 Speed [r/min]
To rq
ue [%
]
Instantaneous operation region
Short-duration (60s) operation region
Continuous operation region
11. Control Parameters
Refer to: Chapter 8 of the Specifications/Instruction Manual, 8.8 Control Parameters
Do not change the settings of these parameters since they have been factory-set to the optimum values. When changing their settings, you need to set 801 in Pr. 77.
Initial value
Pr. 80 "motor capacity" Pr. Setting Range Unit Operation
80 0
Related manuals for Mitsubishi MD-AX520-2.0K Drive Unit Instruction Manual
Manualsnet FAQs
If you want to find out how the MD-AX520-2.0K Mitsubishi works, you can view and download the Mitsubishi MD-AX520-2.0K Drive Unit Instruction Manual on the Manualsnet website.
Yes, we have the Instruction Manual for Mitsubishi MD-AX520-2.0K as well as other Mitsubishi manuals. All you need to do is to use our search bar and find the user manual that you are looking for.
The Instruction Manual should include all the details that are needed to use a Mitsubishi MD-AX520-2.0K. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.
The best way to navigate the Mitsubishi MD-AX520-2.0K Drive Unit Instruction Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.
This Mitsubishi MD-AX520-2.0K Drive Unit Instruction Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.
You can download Mitsubishi MD-AX520-2.0K Drive Unit Instruction Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.
To be able to print Mitsubishi MD-AX520-2.0K Drive Unit Instruction Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Mitsubishi MD-AX520-2.0K Drive Unit Instruction Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.