Mitsubishi EMU-CT100 Current Sensor User's Manual PDF

1 of 1
1 of 1

Summary of Content for Mitsubishi EMU-CT100 Current Sensor User's Manual PDF

CURRENT SENSOR MODEL EMU-CT50, EMU-CT100, EMU-CT250 If you are considering using this unit for special

purpose such as nuclear power plants, aerospace, medical care, or passenger vehicles, please refer to our sales representative.

1.7 Precautions concerning disposal Dispose this product appropriately in accordance with the national or community rule.

2 Installation Installation

1)Open the moving core as shown Figure 1. Slowly lift the moving core locking claws on both sides of the moving core to open and remove them from the stoppers. Before inserting the cable, check the symbols K and L to fit the current sensor in the correct direction. (The direction from the power supply side to the load side is indicated with .)(Figure 3)

2) After checking that the core parting faces are free from dirt, close the moving core. Push up the moving core until the stoppers aresecurely locked. (When the moving core securing claws on both sides catch on the stoppers, you hear two clicks.)(Figure 2)

3) Pass the tying bands into the current sensor locking holes to secure the sensor with the cable.(Figure 3) For the details, see the manual for combination measurement unit. Applicable wire size in the table of specification is the normal sectional areas of 600V vinyl-coated cable.These values are the standard nominal sectional

areas.These electric wires may not pass through the sensor owing to the error of the outer diameters of vinyl insulators finished by manufacturers or deformation (bending) of the wires.Check the wire on site.

Connection For the details,

see the manual for the combination measurement unit.

3 Specification

Locking hole 32

Moving core

Primary Cable

(Figure 1)

Moving core parting face

Primary Cable

(Figure 2)

Moving core locking claw

Stopper

Moving core locking claw

Direction of current

(Figure 3)

*Buy the tying bands.

Direction of current

Protective cover

Tying bnd

K side set CAUTION!

LINE side

(LINE side) (LOAD side)

Use in the environment with the pollution degree 2 or less. Install the current sensor to the secondary of the circuit breaker. Install the current sensor in the cabinet. Use the PVC insulation electric wire.(less than heat-resistant temperature +70C,the rating voltage 300V class.)

4 Contained harmful substances

Caution

5 Customer Service

Please refer to "catalog" or users manual (Details) for more detail. HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, Japan

See the manual, please wire the polarity (Power supply side, Load side), 1 side (R phase), 2 side (S phase), 3 side (T phase) and the polarity (k, l) of the secondary side of the CT to the k, l terminal of the measuring unit.

Model EMU-CT50 EMU-CT100 EMU-CT250 Rated primary current 50A AC 100A AC 250A AC

Maximum voltage* (voltage to groundline voltage) 266V/460V AC

Frequency 45 to 65Hz Ratio error 1%5% to 100% of ratingRL10

Phase displacement 0.9 c rad5% to100% of ratingRL10 Measurement(installation)category CAT

Pollution degree 2 Applicable wire

size (reference) IV wire 60mm2 or less 150mm2 or less CV wire 38mm2 or less 150mm2 or less

Working temperature range -5C to +55C (daily mean temperature: +35C or less) Working humidity range 5% to 95%RH (no condensation)

CE marking conformity standard EN61010-2-032 ULc-UL conformity

combination unit Unit combinaison conforme

au UL/c-UL standard

This sensor confirm UL/c-UL in a condition to make combination use with Mitsubishi MELSEC-Q series programmable controllers Energy Measuring Unit (Models QE81WH,QE81WH4W,QE84WH and QE83WH4W). When EMU-CT50/100/250 is combined with EcoMonitorLight (Model:EMU4-BD1-MB, EMU4-HD1-MB), EcoMonitorPlus(Model:EMU4-BM1-MB,EMU4-HM1-MB,EMU4-A2,EMU4-VA2),and Mitsubishi MELSEC iQ-R series programmable controllers Energy Measuring Unit(Model RE81WH), it is necessary to confirm compatibility with an end product. Ce dtecteur est conform auUL/c-UL standard sous conditiond'tre utilis et combinavec srie MELSEC-Q de Mitsubishi,appareilde contrle et programmable,Unit d'Energie Mesurage(Modle QE81WH, QE81WH4W,QE84WH etQE83WH4W). Lorsque EMU-CT50/100/250 est combin avec EcoMonitorLight (Modle:EMU4-BD1-MB, EMU4-HD1-MB), et EcoMonitorPlus(Modle:EMU4-BM1-MB,EMU4-HM1-MB,EMU4-A2,EMU4-VA2),et MELSECiQ-R de Mitsubishi,appareil de contrle et programmable,Unitd'EnergieMesurage (Modle:RE81WH), il est ncessaire de confirmer la compatibilit avec le produit final.

* Please check the maximum voltage for the combination measurement unit.

INSTRUCTION MANUAL

1 Safety Precautions 1.1 Precautions concerning working environment and conditions

Do not use the unit in any of the following places. Doing so may cause malfunctions or a reduction in service life.

1.2 Precautions concerning preparations before using the equipment Use the unit in the specified usage environment and conditions. Check the current and voltage ratings of the equipment.

1.3 Precautions concerning installation and connection

1.4 Precautions concerning maintenance Protect the unit from a power failure. Failure to do so can cause unit failures, fires, or electric shocks. Wipe off thesurface dirt with tender cloth. Dont let chemical cloths touch it for a long time, and do not wipe it with benzine or thinner.

1.5 Precautions concerning inspection Perform the check in the state that does not turn on electricity by all means. Check out the following. a) Does not this product have the damage? b) Are not there an abnormal sound, bad-smelling fever?c) Are not there installation, the slack of the screw?

1.6 Precautions concerning storage When storing the unit, turn off power, disconnect cables and wires, and put them in vinyl bags or the like. When storing the unit for a long time, avoid keeping it in the places shown below.

Caution

Caution

Perform installation, disassembly, the wiring work after intercepting a power supply by all means. There might be the damage of an electric shock or the product.( ) Do not install around non-insulated dangerous electric shock conductors that can cause electric shock, electric burn or arc flash. ( )

Danger

Make sure to use the module by following cautions of this section.

Any person who is involved in the installation and the wiring of this Programmable Controller should be fully competent to do the work. Use an electric wire of the size of penetrating this current sensor for a primary side cable, do not use a non-insulation electric wire or a metal for a primary cable.

When threading and wiring, take utmost care that cuttings and wire pieces do not enter the equipment. Connect the wires carefully, checking the wiring diagram. Incorrect wiring can cause unit failures, fires, and electric shocks.

Perform wiring work with current off and do not perform live wire operations. Doing so can cause electric shocks, unit failures, and fires. After tightening, be sure to check that all screws have been tightened. Failure to tighten any screw can cause unit malfunctions, fires, and electric shocks.

Use the M3.5 screws crimp type terminals (less than external form 7.2mm) appropriate for for which is suitable for electric wire size(1.25mm2). The use of the infelicity causes malfunction of the machinery, trouble, a damage by a fire, the fire by outbreak of the poor disconnection and contact. ULc-UL listed corresponds, use the wires according to the following conditions and UL-listed crimp type terminals. Single wire AWG24 to AWG18Stranded wireAWG20 to AWG18

+75 copper conductor only. Confirm that a terminal is closed surely. The lack of clamping causes malfunction of the machinery, a fire, the electric shock. Carry out the clamping of the crimp-type terminal lugs by prescribed torque (0.49 to 0.78Nm). The excessive clamping becomes the ruination of a terminal and the screw. Keep the second terminals 1cm or more away from the panel and the first conductor. Read the manual of measuring units which is used with this current sensor , and is used well, and follow it. Use this current sensor in cabinet certainly. As for the panel, it be assumed that it was given the following matters.

a)It is necessary to attach a key to the cabinet. b)The structure that a power supply is intercepted automatically is necessary when opening a cabinet.

Degrees of protection(IP code)needs to higher than IP2X level. Dust or rust on the split part can degrade the performance of the current transformer . Wipe the dirt from the surface with soft dry cloth. Use the unit within the rated range stated here. Using the unit out of the rated range may cause not only malfunctions or unit failure,but also fires or burnout. The secondary side of the current sensor has a built-in protective circuit against opening of the secondary terminal. No problem occurs by

opening the terminal during wiring work. However, for safety,do not continuously apply current while the terminal is open.

Caution

EMU-CT50 / EMU-CT100/ EMU-CT250 is split current sensor for energy measuring unit. Read this manual thoroughly before using the equipment for proper handling. This manual should be retained for the future reference. Be sure that the manual is delivered to the end users. The following items for this device are included in package. Check that no items are missing. (1)Split current sensor x1 (2)Instruction manual x1

SJ/T11364

(2)

6

GB/T 26572

GB/T26572

RoHS

(1)

)

Places where the ambient temperature exceeds the working temperature range(5C to +55C). Places where the humidity exceeds the humidity range (5% to 95%RH) or where condensation occurs. Places with a lot of dust, corrosive gas, salt or oily smoke. Places where the unit may be exposed to rain or drops of water. Places where metal pieces or inductive substances are laying around.

Places where the daily average temperature exceeds +35C. Places with a lot of vibration or impacts. Places exposed to direct sunlight. Places where the out of the cabinet. Places with strong electromagnetic field or noise. Place where the altitude exceeds 2000m.

Places where the ambient temperature is out of the range from 10C to +60C. Places where the humidity exceeds the humidity range(5% to 95%RH) or where condensation occurs. Places where metallic particles or inductive substances are laying around.

Places where the unit is exposed directly to rain, water droplets. Places where the daily average temperature exceeds +35C. Places with a lot ofvibration or impact. Places with a lot of dust, corrosive gas, salt or oily smoke.

Pb

Hg

Cd

Cr(VI) PBB

PBDE

Manualsnet FAQs

If you want to find out how the EMU-CT100 Mitsubishi works, you can view and download the Mitsubishi EMU-CT100 Current Sensor User's Manual on the Manualsnet website.

Yes, we have the User's Manual for Mitsubishi EMU-CT100 as well as other Mitsubishi manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The User's Manual should include all the details that are needed to use a Mitsubishi EMU-CT100. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Mitsubishi EMU-CT100 Current Sensor User's Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Mitsubishi EMU-CT100 Current Sensor User's Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Mitsubishi EMU-CT100 Current Sensor User's Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Mitsubishi EMU-CT100 Current Sensor User's Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Mitsubishi EMU-CT100 Current Sensor User's Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.