Mitsubishi AE1000-SS Breaker Instruction Manual PDF

1 of 39
1 of 39

Summary of Content for Mitsubishi AE1000-SS Breaker Instruction Manual PDF

MITSUBISHI Low-Voltage Air Circuit Breakers type AE

Field test device Y-2005

INSTRUCTION MANUAL

Contents

1. Specification ..................................................................................................... 2

2. Part names and functions (for AE-SW) ............................................... 3

3. Connection (for AE-SW) ............................................................................. 5

4. Initial setting and operation (for AE-SW) ............................................ 6

5. Tests (for AE-SW) ......................................................................................... 8

6. Settings and accuracy (for AE-SW) ................................................... 15

7. Inspection form (for AE-SW) ................................................................. 20

8. Part names and functions (for AE-SS/SH) .................................... 23

9. Connection (for AE-SS/SH) .................................................................. 25

10. Initial setting and operation (for AE-SS/SH) ............................... 26

11. Tests (for AE-SS/SH) ........................................................................... 28

12. Settings and accuracy (for AE-SS/SH) ......................................... 33

13. Inspection form (for AE-SS/SH) ....................................................... 36

14. Service network ......................................................................................... 37

AE630-SW AE1000-SW AE1250-SW AE1600-SW

AE2000-SWA

AE2000-SW AE2500-SW AE3200-SW

AE4000-SWA

AE4000-SW AE5000-SW AE6300-SW

AE630-SH AE1000-SH AE1250-SH AE1600-SH AE2000-SH AE2500-SH AE3200-SH

AE630-SS AE1000-SS AE1250-SS AE1600-SS

AE2000-SS AE2500-SS AE3200-SS

AE4000-SSC

AE4000-SSA

AE4000-SS AE5000-SS AE6300-SS

IMPORTANT NOTE: Before using this device, please read this instruction manual carefully,

and make sure that final user receives this manual.

E-1

OBSERVE THE FOLLOWING FOR SAFETY:

Before using this device, make sure to read this Instruction manual thoroughly. The cautionary items noted

herein are of the utmost importance for the safe use of this device, and should always be strictly followed.

Store this instruction manual together with the device so that it can be read anytime during use.

Also read the instruction manual for AE-SW to be tested, and take care not to damage the air circuit

breaker.

These safety precautions and Instruction manual is prepared for an electrical expert.

The following symbols have been used:

DANGER

Failure to follow these instructions

may result in dangerous conditions,

which in turn could lead to severe

personal injury or even death.

CAUTION

Failure to follow these instructions

may result in dangerous conditions,

which could result in moderate to

slight personal injury or damage to

equipment and facilities

Warning for possible electrification

under certain conditions.

This means prohibition. Never ignore

this indication.

Warning for possible outbreak of a

fire under certain conditions.

Be sure to follow these instructions

without fail.

DANGER

Do not use this device on the conditions over ratings. Otherwise ground-fault, short circuit fault or fire

may occur due to dielectric breakdown.

Do not touch the terminals of Breaker and Y-2005. There is a risk of electrical shock.

CAUTION

Test should be performed by an electrical expert.

Test should be performed only after shutting off the electric power and verifying that there is no voltage

present. Failure to do so may result in an electrical shock.

Connect for tests in accordance with the description given in this instruction manual. Otherwise, electric

shocks or malfunction may occur.

Do not install in areas subject to high temperatures, high humidity, dust, corrosive gas, vibrations,

shocks, etc. To do so may result in malfunction or fire.

This tester is for 100-240VAC 50/60Hz. Using it at other specifications may cause fires or malfunction.

After testing, remove the wiring used for testing and restore the circuit breaker to its original condition.

Any other conditions may cause fires or malfunction.

When discard products, dispose of as industrial waste.

E-2

The Y-2005 breaker tester is a light-weight portable

tester for MITSUBISHI Low-Voltage Air Circuit

Breakers series AE-SW, AE-SS and AE-SH.

The characteristics of electronic trip relay can be

checked in the field without applying a current to

circuit breaker.

Input voltage 100-240V AC 50/60Hz

(available voltage range: AC85-264V)

Power consumption VA 100VA or less

Range of signal output

Voltage signal equivalent to 1%2500% of Rated current In (CT rating)

(continuously adjustable).

*The output at 100% of CT rating is 141mV at 50Hz or 170mV at 60Hz.

Test power output and trip

check power output DC30V 5W

Terminal for checking the

signal output

The same signal as the signal output is output to the terminal on the

back side (load impedance: 100k or more).

Stop signal input "a" contact, "b" contact or test terminal (ETR)

Test items LTD, STD, INST/MCR, GFR, PAL, PAL2 and Trip check

*ER check is not available.

Signal level Max. 2500% of Rated current setting (Ir) (accuracy: 2.5% at CT rating)

Time counter 0.000s2ms999.999s1%

Working temperature range 040 (humidity: 85%Rh or less)

Storage temperature range -1050(humidity: 85%Rh or less)

Dimensions 220mm (W) X 150mm (H) X 340mm (D) (excluding protruding portions)

Weight 4.5kg

Attachments AC power cord, test cable, carry case

Earth leakage protection (ER) check is not available with this tester. Please make a

reference separately about the ER operating check method.

When carrying out ETR check of Type WD,Please make inquiries.

Power plug of AC power cord is equipped with grounding pin. Please use the outlet with

grounding for the electric shock prevention.

1. Specification

E-3

The ratio to CT rating RATIO indicated on the front face of Y-2005 is a ratio of

Current setting Ir at AE-SW Electronic trip relay (ETR) to Rated current In(CT rating).

Be careful in testing or operating.

Front view

Signal setting keypad The signal level can be set to the desired value.

C 2 0 SET

Signal level indicator The indication varies depending on the decimal point position as follows: H 0.000: Ratio to CT rating RATIO 00000.0: Test signal level TEST SIGNAL(%)

OUTPUT pin indicating LED S1: Overcurrent tripping

(L/C/R-pole) S2: Ground fault tripping S3: N-pole overcurrent tripping

Trip check mode indicating LED

Output frequency indicating LED

TRIP indicating LED

Test power indicating LED

Output pin switch

Output frequency switch Stop signal input switch

Time counter LED (Indicates operating time)

Signal level mode switch

TRIP CHECK mode switch

Test power manual connecting switch (auxiliary function)

STOP switch Use this switch to stop testing

START switch The test signal is output, and the time counter starts.

RESET switch The time counter and trip indicating LED are reset.

Signal adjusting switches The signal level can be changed continuously with three digits even during testing.

Stop signal indicating LED a: The trip signal is made by the "a" (make) contact. b: The trip signal is made by the "b" (break) contact. ETR: The trip signal is input from ETR through the test connector.

TESTING mode indicating LED Lights with START and goes out with STOP or TRIP.

2. Part names and functions (for AE-SW)

E-4

Back view

Signal output checking terminal

(usually not in use)

Power switch (With overcurrent protective function) AC Power input connector

Available in the range from 100VAC to 240VAC.

Test signal output connector (With reverse insertion prevention.)

Stop signal input terminals To be connected with the "a" contact or "b" contact of a trip indicator, main contact, auxiliary switch or the like.

For calibration, inquire at any of our branch offices or service centers.

The test signal output can be checked by connecting an AC voltmeter.

DANGER

When using the Stop signal input terminals, check that no power is supplied and that there is no interference with other wiring in the panelboad. Otherwise, electric shocks or short circuits may occur.

E-5

Electronic trip relay (ETR)

Breaker tester Y-2005

Test connector

(With reverse

insertion prevention)

AC plug (with earth pin)

These are used when the stop signal is input from other than the test cable (test connector of ETR).

When using the main contact of breaker. Set the Stop signal input switch on the front face to [b].

When using the "a" contact of auxiliary switch (AX). Set the Stop signal input switch to [b].

When using the "b" contact of auxiliary switch (AX). Set the Stop signal input switch to [a].

When using the OCR alarm switch (AL). Set the Stop signal input switch to [a].

*Connect to the circuit breaker's control circuit terminal block ( 97 and 98 ).

When using the alarm contacts. Set the Stop signal input switch to [a].

*Connect to the circuit breaker's control circuit terminal block ( 524 564 and 513 ).

*For using these alarm contacts, the Power supply module with alarm contact (type: P3, P4 OR P5) is

required.

DANGER Do not touch the terminals. Otherwise, electric shocks may occur.

When checking a dielectric voltage test or insulation resistance measurement of the circuit breaker and panelboad, remove all wiring for Y-2005. Otherwise, trouble may occur.

Test cable

3. Connection (for AE-SW)

Note) This figure includes Display (*option) and MCR switch (*option).

E-6

Start the setting and operation after carefully reading an instruction

manual for AE-SW (IB63366) and 6. Settings and accuracy in this

instruction manual to understand the characteristics of ETR.

4.1 Setting of rated current

1Open the front cover of ETR.

2Connect a test cable to ETR as described in Chapter 3.

3Turn on the Power switch on the back panel.

4Set a mode with the corresponding switches described below. The settings are changed in turn by pushing the switches. As for

function of each setting, see chapter 2.

Output frequency 50Hz / 60Hz

Stop signal a / b / ETR

Output pin S1 / S2 / S3

Test mode usual test / TRIP CHECK

*When power is turned on, each item is set to the marked position.

5Setting of Rated current

This tester outputs a signal at the ratio of Current setting Ir at ETR to Rated current In(CT rating). Therefore, at the beginning,

the ratio to CT rating should be set in % of Rated current In(CT rating).

Set a mode to H . with Signal level mode switch TEST SIGNAL(%) / RATIO .

(When power is turned on, the rated current is set to H 1.000 ).

Input a value of the rated current to H . with Signal adjusting switches or Signal setting keypad.

When testing the Overcurrent tripping or pre-alarm characteristics.

iIn case of WS or WB type relay;

Input a value of Ir setting dial of ETR.

Example) In case that Ir is set to 0.8: Input H 0.800 .

iiIn case of WM type relay;

Input a value calculated by (Ir [A]In [A]).

Example) In case that In=1600A and Ir=1283A: 1283A1600A=0.802, therefore input H 0.802 .

When testing the ground fault characteristics.

Set to H 1.000 even if Ir setting dial of ETR is not set to 1.0.

4. Initial setting and operation (for AE-SW)

E-7

4.2 How to operate

DANGER

Test should be performed only after shutting off the electric power and

verifying that there is no voltage present. Failure to do so may result in an

electrical shock.

When current is flowing in the main circuit of breaker, it is combined with the

test signal of Y-2005, consequently does not become correct characteristic.

The operating test should be performed in the state that load current does

not flow in the main circuit.

1Set the Signal level indicator to . by pushing the Signal level mode switch TEST SIGNAL(%) / RATIO .

2Set a signal level in % of Ir by using the Signal adjusting switches or Signal setting keypad.

When using the Signal adjusting switches:

When using the Signal setting keypad:

Push a clear key C .

Since figures are shifted to left every time you

push numerical keys, enter the desired values.

Push a set key SET .

3Push START switch, and the test signal is output. Then the time counter starts from 000.000 , and also the TESTING

mode indicating LED lights.

4Push STOP switch, and the test signal is stopped. Then the time counter stops, and the TESTING mode indicating LED

goes off.

In case of tripping, the TRIP indicating LED lights and the time counter stops automatically.

5Push RESET switch to reset the TRIP indicating LED and the time counter. This switch is used for retesting.

Continuing to push the switches increases or decreases the signal level continuously.

To set to 200%Ir, push C 2 0 0 0 SET ,

and 00200.0 is set.

10% 1% 0.1%

E-8

It is possible to display a trip current value on LCD by supplying control power to ETR, if Display (DP1

or DP2) (*option) is equipped. However, this value may become somewhat larger than the value

displayed by Y-2005, especially in case of STD and INST trip. Furthermore, since the test signal from

Y-2005 is not input into the Extension module (EX1), even if it supplies the test current to ETR, the

measuring current value displayed on LCD will be as 0.

5.1 LTD Pick-up current test

1Set the signal level to approximately 90% of LTD pick-up current.

2Push START switch.

3Increase the signal level with Signal adjusting switch, and take a reading of pick-up value.

iIn case of WS type relay

The pick-up value is calculated by;

(Pick-up level at a point where ETR turns a [OVER] LED on)Iu.

Example) When the [OVER] LED lights at 94% with Iu=0.8, the pick-up value is 94%0.8=117.5%.

iiIn case of WM type relay

The LTD pick-up level can be taken at a point where ETR turns a [100%] LED on.

4Push STOP switch.

5Push RESET switch and start at (1), if testing again.

5.2 LTD operating time test

1Set a desired signal level.

iIn case of WS type relay

The operating time is to be taken at 200%Iu, therefore, if Iu is set to 1.0, set the signal level to 00200.0 .

In case that Iu is not set to 1.0, for example, if Iu is 0.9, since 0.9200%=180%, set the signal level to 00180.0 .

iiIn case of WM type relay

The operating time is to be taken at 120%IL, therefore, if IL is set to 1.05, since 1.05120%=126%,

set the signal level to 00126.0 .

2The Isd (short-time-delay pick-up current) and Ii (instantaneous pick-up current) setting dial of ETR should be set to 1.2 times

or more the above-mentioned signal level.

3Push START switch.

4After tripping, the operating time is indicated.

5Push RESET switch and start at (3), if testing again.

Since ETR has a memory effect for overcurrent state, when the operating time test is interrupted on

the way, the operating time at the next test becomes short. This memory effect can be reset by

tripping. Therefore, if operating time test is interrupted on the way, perform the next test after tripping

ETR one-time. To trip, perform the trip check in accordance with 5.12.

Hint In section 5.1 and 5.2, if Iu of WS type relay is not set to 1.0, the reading value of the signal level can be regarded as

the LTD pick-up current (%) by setting the value of H . to IrIu. Also, when measuring the LTD operating time,

test can be performed with the signal level 00200.0 . However, when checking the STD or INST characteristics, return the

setting of H . to a former value.

5. Test (for AE-SW)

Signal adjusting switches

Increase the signal level with this 1% step key.

E-9

5.3 STD Pick-up current test

1Set Ii (instantaneous pick-up current) setting dial of ETR to the maximum,

and set Tsd (short-time-delay operating time) to the minimum (0.06s).

* If the setting value of Tg is large, exact measurement cannot be

performed in the following (5).

2Set the signal level to approximately 80% of Isd.

3Push START switch, and immediately increase the signal level with a

10% signal adjusting switch until ETR trips and Time counter LED stops.

Increase the signal level by using 10% step key. Since it takes a long time to test in case of 1% or

0.1% step, the LTD pick-up may operate before STD. If LTD pick-up operates even the 10% step,

start again at approximately 95% of Isd.

4Read the signal level indicated at the time.

5Furthermore, measure the operating time near the pick-up current measured in (3) by using 1% step key. The point where the

operating time becomes short suddenly serves as accurate measured value of Isd.

6Push RESET switch and start at (2), if testing again.

5.4 STD operating time test

1Set Ii setting dial of ETR to the maximum.

2Set a desired signal level.

For example, if Isd setting dial is set to 4, since 400%1.5=600%, set the signal level to 00600.0 .

*Where, 1.5 is a value that the operating time becomes flat.

3Push START switch.

4After tripping, the operating time is indicated.

When the stop signal is made by the main contact, auxiliary switch (AX) or OCR alarm switch (AL).

Take the reading of the counter as it is.

When the stop signal is made through the test connector of ETR or alarm contacts of Power supply module (type: P3, P4 or P5).

Add 20ms (mechanical operating time) to the reading of the counter.

5Push RESET switch and start at (3), if testing again.

If ETR operates as LTD or INST in checking STD pick-up current, change the set value of INST/LTD,

or change the test current. Moreover, ETR may operate as INST when checking STD operating time at

Isd=10. In this case, lower the test current to near 140%Isd, or lower the test current after setting Tsd

to I2t OFF temporarily.

Signal adjusting switches

Increase the signal level with this 10% step key.

T im

e

Tsd

Isd Isd1.5 Current

E-10

5.5 INST Pick-up current test

1When the MCR switch (*option) is equipped,

set Ii setting dial to "INST side (See right figure).

2Set the signal level to approximately 90% of Ii.

3Push START switch while continuing to push a [L/S LOCK] button

of ETR, then increase the signal level by using the Signal adjusting switch

until ETR trips and Time counter LED stops.

4Read the signal level indicated at the time.

5Push RESET switch and start at (2), if testing again.

5.6 INST operating time test

1Set a desired signal level.

For example, if Ii setting dial is set to 10, since 1000%1.5=1500%,

set the signal level to 01500.0 .

*Where, 1.5 is a value that the operating time becomes flat.

2Push START switch while continuing to push the [L/S LOCK] button of ETR.

3After tripping, the operating time is indicated.

When the stop signal is made by the main contact, auxiliary switch (AX) or OCR alarm switch (AL).

Take the reading of the counter as it is.

When the stop signal is made through the test connector of ETR or alarm contacts of Power supply module (type: P3, P4 or P5).

Add 20ms (mechanical operating time) to the reading of the counter.

4Push RESET switch and start at (2), if testing again.

When checking the short time operation such as INST operating time test, in order to measure the

operating time with accuracy, push the Test power manual connecting switch VT , and push

START switch after the Test power indicating LED lighting. If do not pushing the Test power

manual connecting switch VT , exact measurement cannot be performed.

5.7 MCR function check (*Only when MCR switch is equipped)

1Set Ii setting dial of ETR to "MCR" side.

2When the state of circuit breaker is off, ETR operates as INST.

Check the INST operation in accordance with section 5.5 and 5.6.

* This test is checking that instantaneous characteristics is effective

during breaker closing operation ( from open to close ) .

3Confirms that the breaker does not operate as INST even when the same test as section 5.5 and 5.6 is carried out. In this case,

it operates as STD in case of WS or WM type relay. In case of WB type relay, it does not trip.

Signal adjusting switches

Increase the signal level with this 10% step key.

INST (standard) MCR (*option) (INST/MCR selectable)

Current

T im

e

Ii

Ti

I i1.5

INST (standard) MCR (*option) (INST/MCR selectable)

E-11

5.8 GFR Pick-up current test (TRIP mode) (*Only when G1 module is equipped)

1Set Tg (ground fault operating time) setting dial of ETR to the minimum (0.10s) of TRIP side.

* If the setting value of Tg is large, exact measurement cannot be performed in the following (4).

2Set the Signal output pin to [S2] and the rated current to H 1.000 in accordance with section 4.1(5).

3Set the signal level to approximately 80% of Ig (ground fault pick-up current).

4Push START switch, and immediately increase the signal level with

the Signal adjusting switch until ETR trips and Time counter LED stops.

5Read the signal level indicated at the time.

6Push RESET switch and start at (3), if testing again.

5.9 GFR operating time test (TRIP mode) (*Only when G1 module is equipped)

1Set Tg setting dial of ETR to TRIP side.

2Set the Signal output pin to [S2] and the rated current to H 1.000 in accordance with section 4.1(5).

3Set the Signal level indicator to . by pushing the Signal level mode switch TEST SIGNAL(%) / RATIO .

4Set a desired signal level.

For example, if Ig setting dial is set to 0.3, since 30%1.5=45%,

set the signal level to 00045.0 .

* Where, 1.5 is a value that the operating time becomes flat.

5Push START switch.

6After tripping, the operating time is indicated.

When the stop signal is made by the main contact, auxiliary switch (AX) or OCR alarm switch (AL).

Take the reading of the counter as it is.

When the stop signal is made through the test connector of ETR or alarm contacts of Power supply module (type: P3, P4 or P5).

Add 20ms (mechanical operating time) to the reading of the counter.

8Push RESET switch and start at (5), if testing again.

When checking the short time operation such as GFR operating time test, in order to measure the

operating time with accuracy, push the Test power manual connecting switch VT , and push the

START switch after the Test power indicating LED lighting. If do not pushing the Test power

manual connecting switch VT , exact measurement cannot be performed.

Signal adjusting switches

Increase the signal level with this 1% step key.

T im

e

Tg

Ig1.5 Ig Current

E-12

5.10 GFR Pick-up current test (ALARM mode) (*Only when G1 module is equipped)

1Set Tg (ground fault operating time) setting dial of ETR to the minimum (0.10s) of ALARM side.

* If the setting value of Tg is large, exact measurement cannot be performed in the following (5).

2Set the Signal output pin to [S2] and the rated current to H 1.000 in accordance with section 4.1(5).

3Set the signal level to approximately 80% of Ig (ground fault pick-up current).

4Push START switch.

5Increase the signal level using the "Signal adjusting switch",

and take a reading of the counter at a point where ETR turns a [GFR] LED on.

6Push RESET switch and start at (3), if testing again.

5.11 GFR operating time test (ALARM mode) (*Only when type P3, P4 or P5 module and G1 module are equipped)

1Set Tg setting dial of ETR to ALARM side.

2Supply power to ETR (between P1 and P2 of the circuit breaker's control circuit terminal block).

3Connect the "Stop signal input" on the back of tester and the contact terminal for GFR (between 544 and 513 of the

circuit breaker's control circuit terminal block). Then set the "Stop signal input switch" to [a].

*The terminal allocation for GFR ( 544 and 513 ) described in above is the assignment at the factory shipments. If this

allocation is changed by using the display (DP1 or DP2), it differs from the above allocation.

4Set a desired signal level (See section 5.9).

5Push START switch.

6After operation, the operating time is indicated.

7Push RESET switch and start at (4), if testing again.

Signal adjusting switches

Increase the signal level with this 1% step key.

E-13

5.12 Trip check

This function enables the circuit breaker to operate instantaneously. It is effective when checking panel sequence, resetting the

memory effect for overcurrent and the like.

1Set a test mode to [TC] (trip check).

2In case of WM type relay, if MCR switch (*option) is equipped, set Ii setting dial to "INST" side.

*In case of WB type relay, unless Ii setting dial is set to "INST" side, ETR does not trip.

3Push START switch.

4Confirms that the circuit breaker trips instantaneously.

5Push RESET switch and start at (3), if testing again.

When checking the circuit breaker operating time, push the Test power manual connecting switch

VT , and push START switch after the Test power indicating LED lighting. If do not pushing

the Test power manual connecting switch VT , exact measurement cannot be performed.

5.13 PAL pick-up current test

1Set the signal level to approximately 80% of Ip.

2Push START switch.

3Increase the signal level using the "Signal adjusting switch",

and take a reading of the counter at a point where [PAL] LED of ETR blinks.

4Push STOP switch.

5Push RESET switch and start at (1), if testing again.

5.14 PAL operating time test (*Only when type P3, P4 or P5 of Power supply module is equipped)

1Supply power to ETR (between P1 and P2 of the circuit breaker's control circuit terminal block).

2Connect the "Stop signal input" on the back of tester and the contact terminal for PAL OUT (between 554 and 513 of

the circuit breaker's control circuit terminal block). Then set the "Stop signal input switch" to [a].

*The terminal allocation for PAL OUT ( 554 and 513 ) described in above is the assignment at the factory shipments. If

this allocation is changed by using the display (DP1 or DP2), it differs from the above allocation.

3Set a desired signal level (See section 5.2).

4Push START switch.

5After operation, the operating time is indicated.

6Push RESET switch and start at (3), if testing again.

Since ETR has a memory effect for overcurrent state, when the operating time test is interrupted on

the way, the operating time at the next test becomes short. This memory effect can be reset by

tripping. Therefore, if operating time test is interrupted on the way, perform the next test after tripping

ETR one-time. To trip, perform the trip check in accordance with 5.12.

Signal adjusting switches

Increase the signal level with this 1% step key.

E-14

5.15 PAL2 pick-up current test (*Only when AP module is equipped)

1Set the signal level to approximately 80% of Ip2.

2Push START switch.

3Increase the signal level using the "Signal adjusting switch",

and take a reading of the counter at a point where [PAL2] LED of ETR blinks.

4Push STOP switch.

5Push RESET switch and start at (1), if testing again.

5.16 PAL2 operating time test (*Only when P3, P4 or P5 module and AP module are equipped)

1Supply power to ETR (between P1 and P2 of the circuit breaker's control circuit terminal block).

2Connect the "Stop signal input" on the back of tester and the contact terminal for PAL2 OUT (between 544 and 513 of

the circuit breaker's control circuit terminal block). Then set the "Stop signal input switch" to [a].

*The terminal allocation for PAL2 OUT ( 544 and 513 ) described in above is the assignment at the factory shipments. If

this allocation is changed by using the display (DP1 or DP2), it differs from the above allocation.

3Set a desired signal level (See section 5.2).

4Push START switch.

5After operation, the operating time is indicated.

6Push RESET switch and start at (3), if testing again.

Since ETR has a memory effect for overcurrent state, when the operating time test is interrupted on

the way, the operating time at the next test becomes short. This memory effect can be reset by

tripping. Therefore, if operating time test is interrupted on the way, perform the next test after tripping

ETR one-time. To trip, perform the trip check in accordance with 5.12.

5.17 OCR alarm switch (AL) check

The OCR alarm switch (AL) is a contact (a contact) of short time operation (30-50ms) Note). This time can be measured with the

oscilloscope, the millisecond counter or the like.

Note): In case of the manual reset type (MRE) (*option), AL is output continuously. This contact output is not reset until pushing

the manual reset button of breaker.

Y-2005 enables a check of operation even if breaker is in the state of OFF. However, as for AL

checking, since AL is included in the trip mechanism, AL is output only when tripping from ON state.

(AL cannot be output unless tripping actually).

Signal adjusting switches

Increase the signal level with this 1% step key.

E-15

6.1 Settings and accuracy of type WS relay

No. Setting item Mark

Adjustable setting range

Accuracy AE630-SWAE1600-SW AE2000-SWAE3200-SW

AE4000-SW

AE2000-SWA AE4000-SWA AE5000-SW

AE6300-SW

Rated current setting Ir 0.51.0(0.05step) In (CT rating)

Uninterrupted current Iu 0.81.0Ir(0.02step), Pick-up current: 1.15xIu 1.05IuNon pick-up

1.25IuPick-up

LTD time T 12-25-50-100-150s at Iu2 20%

STD Pick-up current Isd 1.5-2-2.5-3-4-5-6-7-8-9-10 Ir 15%

STD time Tsd 0.5-0.4-0.3-0.2-0.1-0.06- 0.06-0.1-0.2-0.3-0.4-0.5s

(I2t ON) (I2t OFF) 20%

(0.060.02s)

INST. Pick-up current Ii 162 - 216 Ir 122 - 212 Ir 102 - 210 Ir

15% (INST) (MCR) WS1 (INST) (MCR) WS2 (INST) (MCR) WS3

Pre-alarm current Ip Iu0.681.0(0.04step)-OVER 10%

Pre-alarm time Tp 1/2 TL (after 1/2TL, PAL output contact turns on) 20%

*Note): The table shows data obtained on the breakers provided with MCR (*option). For breakers without MCR, the setting position for MCR is not provided.

3

3

The figure includes optional G1 setting module, Display and MCR.

6. Settings and accuracy (for AE-SW)

Ig see page18

Relation of setting dial

Ii

Ip

Ip2 (see page19)

In (CT rating) Ir Iu

Isd

Load current LED60, 80, 100, OVER

*Note)

*Note): In case of AE4000-SWAE6300-SW, the max. breaking time is 0.05s.

E-16

6.2 Settings and accuracy of type WM relay

No. Setting item Mark

Adjustable setting range

Accuracy AE630-SWAE1600-SW AE2000-SWAE3200-SW

AE4000-SW

AE2000-SWA AE4000-SWA AE5000-SW

AE6300-SW

Rated current setting Ir 0.63 1.0In (*Set to specified current value before shipment (fixed))

LTD pick-up current I 1.0-1.05-1.1-1.15-1.2 Ir 5%

LTD time T 15-20-25-30-40-60s at IL1.2 20%

STD pick-up current Isd 1.5-2-2.5-3-3.5-4-4.5-5 Ir 15%

STD time Tsd 0.5-0.4-0.3-0.2-0.1-0.06- 0.06-0.1-0.2-0.3-0.4-0.5s (I2t ON) (I2t OFF)

20% (0.060.02s)

INST. pick-up current Ii 162 216 Ir 122 212 Ir 102 210 Ir

15% (INST) (MCR) WM1 (INST) (MCR) WM2 (INST) (MCR) WM3

Pre-alarm current Ip IL0.681.0(0.04step)-OVER 5%

Pre-alarm time Tp 1/2 TL (after 1/2TL, PAL output contact turns on) 20%

*Note1): The table shows data obtained on the breakers provided with MCR (*option). For breakers without MCR, the setting position for MCR is not provided. *Note2): When the WM type relay is used, the pre-alarm current at the setting, OVER , is the same as that at 1.0.

3

3

The figure includes optional G1 setting module, Display and MCR.

Ig see page18

Relation of setting dial

Ii

Ip

Ip2 (see page19)

In (CT rating) Ir (Fixed) IL

Isd

Load current LED40, 60, 80, 100

*Note)

*Note): In case of AE4000-SWAE6300-SW, the max. breaking time is 0.05s.

E-17

6.3 Settings and accuracy of type WB relay

No. Setting item Mark

Adjustable setting range

Accuracy AE630-SWAE1600-SW AE2000-SWAE3200-SW

AE4000-SW

AE2000-SWA AE4000-SWA AE5000-SW

AE6300-SW

Rated current setting Ir 0.5 1.0(0.05step) In (CT rating)

INST. pick-up current Ii 162 - 216 Ir 122 - 212 Ir 102 - 210 Ir

15% (INST) (MCR) WB1 (INST) (MCR) WB2 (INST) (MCR) WB3

Pre-alarm current Ip Ir0.681.0(0.04step)-OVER 5%

Pre-alarm time Tp 75s at Ir2 (after 1/2TL, PAL output contact turns on) 20%

*Note): The table shows data obtained on the breakers provided with MCR (*option). For breakers without MCR, the setting position for MCR is not provided.

The figure includes MCR function.

Ig see page18

Relation of setting dial

In (CT rating) Ir Ii

Ip

Load current LED60, 80, 100, OVER

Ip2

*Note)

*Note): In case of AE4000-SWAE6300-SW, the max. breaking time is 0.05s.

E-18

6.4 Settings and accuracy of G1 module

Ground fault protection characteristics

Pick-up currentIg

Ground fault timeTg

0.1 (0.040.1s)

0.1520%

3.020%

1.0 0.1

% of rated current In (CT rating)

O pe

ra ti o n t

im e ( s)

No. Setting item Mark Adjustable setting range Accuracy

Ground fault Pick-up Ig 0.11.0In (0.1step) 20%

Ground fault time Tg 3.0-1.5-0.8-0.5-0.3-0.15-0.1 - 0.1-0.15-0.3-0.5-0.8-1.5-3.0 s (Trip) (Alarm)

20%

3

3

E-19

6.5 Settings and accuracy of AP module

No. Setting items Mark Adjustable setting range Accuracy

2nd pre-alarm current Ip2 0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 Iu 10%

0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 IL 5%

2nd pre-alarm

operating time Tp2

0.9-0.8-0.7-0.6-0.5-0.4-0.3TL 5-10-15-20-30-40-60s

(TL) (FLAT) 20%

2nd pre-alarm currentIp2

Current (% of Iu)

LTD operating timeTL

12-25-50-100-150s (at Iu2)

2nd pre-alarm operating timeTp2 (FLAT)

2nd pre-alarm operating timeTp2 (TL)

For type WS relay

Current (% of IL)

For type WM relay

2nd pre-alarm currentIp2

LTD operating timeTL

15-20-25-30-40-60s (at IL1.2)

2nd pre-alarm operating timeTp2 (FLAT)

2nd pre-alarm operating timeTp2 (TL)

O pe

ra ti on

t im

e (s

)

O pe

ra ti on

t im

e (s

)

WS

WM

3

3

WS

WM

E-20

Inspection report form for WS type relay Date: Checked person:

Name of Panel/Distribution system:

ACB Type CT rating (In) Serial number ETR type ETR serial number

External appearance

There must be no breakage of ETR. There must be no breakage. There must be no loosening of terminal screws of Control circuit terminal block.

There must be connected securely.

Confirmation of settings

Rated current setting (Ir)

Fill in the setting values. If setting was changed during check, reset the value to the previous settings at the completion of check.

LTD Uninterrupted current (Iu) Operating time (TL)

STD Pickup current (Isd) Operating time (Tsd) I2t ON/OFF settings

INST Pickup current (Ii) INST/MCR settings

PAL Pickup current (Ip) Operating time (Tp)

GFR 3) Pickup current (Ig) Operating time (Tg) TRIP/ALARM settings

ER 3) Pickup current (In) Operating time (Te) TRIP/ALARM settings

PAL2 3) Pickup current (Ip2) Operating time (Tp2)

Pickup/ Operating time

LTD Pickup current (%) 105% - 125%Iu Operating time (s) TL20% at 200%Iu

STD 2) Pickup current (%) Isd15% Operating time (s) Tsd20% at 150%Isd

INST 1)

Pickup current (%) Ii15% Operating time (s) Max. breaking time at 150%Ii

PAL

Pickup current (%) Ip10% Operating time (s) TL/220% at 200%Iu

GFR 3)

Pickup current (%) Ig20% Operating time (s) Tg20% at 150%Ig

ER 3), 4) Pickup current (%) In+0%-30% Operating time (s) Te20% at 150%In

PAL2 3) Pickup current (%) Ip210% Operating time (s) Tp220% at 200%Iu

Outputs

Trip indicator LED (L, S, I, PAL, GFR 3), ER 3), 4), PAL2 3))

Trip indicator contact output (L, S/I, PAL, GFR 3)/ER 3), 4)/PAL2 3))

Only if Power supply with alarm contact (type: P3/P4/P5) is equipped.

OCR alarm switch (AL) output 5) AL (*standard): 30ms (1pulse) MRE (*option): continuously

Result Other items to be checked.

Note1): If ETR operates as LTD or STD in checking INST pick-up current, use the L/S LOCK (LTD/STD LOCK) button of ETR. Note2): If ETR operates as LTD or INST in checking STD pick-up current, change the set value of INST/LTD, or change the test current.

Moreover, ETR may operate as INST when checking STD operating time at Isd=10. In this case, lower the test current to near 140%Isd, or lower the test current after setting Tsd to I2t OFF temporarily.

Note3): Check and fill in the blanks only if any Optional setting module (G1/E1/AP) is equipped. Note4): Please make a reference separately about the ER operating check method. Note5): Since AL is included in the trip mechanism, AL is output only when tripping from ON state. (AL cannot be output unless tripping actually).

7. Inspection form (for AE-SW)

E-21

Inspection report form for WM type relay Date: Checked person:

Name of Panel/Distribution system:

ACB Type CT rating (In) Serial number ETR type ETR serial number

External appearance

There must be no breakage of ETR. There must be no breakage. There must be no loosening of terminal screws of Control circuit terminal block.

There must be connected securely.

Confirmation of settings

Rated current setting (Ir)

Fill in the setting values. If setting was changed during check, reset the value to the previous settings at the completion of check.

LTD Pickup current (IL) Operating time (TL)

STD Pickup current (Isd) Operating time (Tsd) I2t ON/OFF settings

INST Pickup current (Ii) INST/MCR settings

PAL Pickup current (Ip) Operating time (Tp)

GFR 3) Pickup current (Ig) Operating time (Tg) TRIP/ALARM settings

ER 3) Pickup current (In) Operating time (Te) TRIP/ALARM settings

PAL2 3) Pickup current (Ip2) Operating time (Tp2)

Pickup/ Operating time

LTD Pickup current (%) IL5% Operating time (s) TL20% at 120%IL

STD 2) Pickup current (%) Isd15% Operating time (s) Tsd20% at 150%Isd

INST 1)

Pickup current (%) Ii15% Operating time (s) Max. breaking time at 150%Ii

PAL

Pickup current (%) Ip5% Operating time (s) TL/220% at 120%IL

GFR 3)

Pickup current (%) Ig20% Operating time (s) Tg20% at 150%Ig

ER 3), 4) Pickup current (%) In+0%-30% Operating time (s) Te20% at 150%In

PAL2 3) Pickup current (%) Ip25% Operating time (s) Tp220% at 120%IL

Outputs

Trip indicator LED (L, S, I, PAL, GFR 3), ER 3), 4), PAL2 3))

Trip indicator contact output (L, S/I, PAL, GFR 3)/ER 3), 4)/PAL2 3))

Only if Power supply with alarm contact (type: P3/P4/P5) is equipped.

OCR alarm switch (AL) output 5) AL (*standard): 30ms (1pulse) MRE (*option): continuously

Result Other items to be checked.

Note1): If ETR operates as LTD or STD in checking INST pick-up current, use the L/S LOCK (LTD/STD LOCK) button of ETR. Note2): If ETR operates as LTD or INST in checking STD pick-up current, change the set value of INST/LTD, or change the test current.

Moreover, ETR may operate as INST when checking STD operating time at Isd=10. In this case, lower the test current to near 140%Isd, or lower the test current after setting Tsd to I2t OFF temporarily.

Note3): Check and fill in the blanks only if any Optional setting module (G1/E1/AP) is equipped. Note4): Please make a reference separately about the ER operating check method. Note5): Since AL is included in the trip mechanism, AL is output only when tripping from ON state. (AL cannot be output unless tripping actually).

E-22

Inspection report form for WB type relay Date: Checked person:

Name of Panel/Distribution system:

ACB Type CT rating (In) Serial number ETR type ETR serial number

External appearance

There must be no breakage of ETR. There must be no breakage. There must be no loosening of terminal screws of Control circuit terminal block.

There must be connected securely.

Confirmation of settings

Rated current setting (Ir)

Fill in the setting values. If setting was changed during check, reset the value to the previous settings at the completion of check.

INST Pickup current (Ii) INST/MCR settings

PAL Pickup current (Ip) Operating time (Tp)

GFR 1) Pickup current (Ig) Operating time (Tg) TRIP/ALARM settings

ER 1) Pickup current (In) Operating time (Te) TRIP/ALARM settings

PAL2 1) Pickup current (Ip2) Operating time (Tp2)

Pickup/ Operating time

INST

Pickup current (%) Ii15% Operating time (s) Max. breaking time at 150%Ii

PAL

Pickup current (%) Ip10% Operating time (s) 75s20% at 200%Ir

GFR 1)

Pickup current (%) Ig20% Operating time (s) Tg20% at 150%Ig

ER 1), 2) Pickup current (%) In+0%-30% Operating time (s) Te20% at 150%In

PAL2 1) Pickup current (%) Ip210% Operating time (s) Tp220% at 200%Ir

Outputs

Trip indicator LED (I, PAL, GFR 1), ER 1), 2), PAL2 1))

Trip indicator contact output (I, PAL, GFR 1)/ER 1), 2)/PAL2 1))

Only if Power supply with alarm contact (type: P3/P4/P5) is equipped.

OCR alarm switch (AL) output 3) AL (*standard): 30ms (1pulse) MRE (*option): continuously

Result Other items to be checked.

Note1): Check and fill in the blanks only if any Optional setting module (G1/E1/AP) is equipped. Note2): Please make a reference separately about the ER operating check method. Note3): Since AL is included in the trip mechanism, AL is output only when tripping from ON state. (AL cannot be output unless tripping actually).

E-23

The ratio to CT rating RATIO indicated on the front face of Y-2005 is a ratio of RATED

CURRENT In at AE-SS Electronic trip relay to RATED CURRENT MAX In max(CT rating).

Be careful in testing or operating.

Front view

Signal setting keypad The signal level can be set to the desired value.

C 2 0 SET

Signal level indicator The indication varies depending on the decimal point position as follows: H 0.000: Ratio to CT rating RATIO 00000.0: Test signal level TEST SIGNAL(%)

OUTPUT pin indicating LED C/S/SL type relay M type relay

S1: Overcurrent tripping S1: L-pole test (L/C/R-pole) S2: C-pole test/

S2: Ground fault tripping Ground fault tripping S3: N-pole overcurrent tripping S3: R-pole test

Trip check mode indicating LED

Output frequency indicating LED

TRIP indicating LED

Test power indicating LED

Output pin switch

Output frequency switch Stop signal input switch

Time counter LED (Indicates operating time)

Signal level mode switch

TRIP CHECK mode switch

Test power manual connecting switch (auxiliary function)

STOP switch Use this switch to stop testing

START switch The test signal is output, and the time counter starts.

RESET switch The time counter and trip indicating LED are reset.

Signal adjusting switches The signal level can be changed continuously with three digits even during testing.

Stop signal indicating LED a: The trip signal is made by the "a" (make) contact. b: The trip signal is made by the "b" (break) contact. ETR: The trip signal is input from ETR through the test connector.

TESTING mode indicating LED Lights with START and goes out with STOP or TRIP.

8. Part names and functions (for AE-SS/SH)

E-24

Back view

Signal output checking terminal

(usually not in use)

Power switch (With overcurrent protective function) AC Power input connector

Available in the range from 100VAC to 240VAC.

Test signal output connector (With reverse insertion prevention.)

Stop signal input terminals To be connected with the "a" contact or "b" contact of a trip indicator, main contact, auxiliary switch or the like.

For calibration, inquire at any of our branch offices or service centers.

The test signal output can be checked by connecting an AC voltmeter.

DANGER

When using the Stop signal input terminals, check that no power is supplied and that there is no interference with other wiring in the panelboad. Otherwise, electric shocks or short circuits may occur.

E-25

9. Connection (for AE-SS/SH)

Breaker tester Y-2005

Test connector

(Prevents inserting in

the reverse direction.)

AC plug (with earth) When measuring the operating time including that of the circuit breaker,

connect with the "a" contact or "b" contact of the auxiliary switch (AX).

"a" contact of the auxiliary switch (AX) ... Set the stop signal to [b].

"b" contact of the auxiliary switch (AX) ... Set the stop signal to [a].

When measuring the pre-alarm operating time, connect with the PAL OUT

contact.

"a" contact between PAL OUT T0+ and T4 ... Set the stop signal to [a].

To operate the PAL OUT contact, control power is required for the

trip relay.

Do not touch the terminals.

Otherwise, electric shocks may occur.

When conducting a withstand voltage

test or insulation resistance

measurement of the circuit breaker,

remove the wiring of Y-2005.

Otherwise, trouble may occur.

Test cable

DANGER

E-26

Start the setting and operation after carefully reading an instruction

manual for AE-SS/SH and 12. Settings and accuracy in this instruction

manual to understand the characteristics of Electronic trip relay.

10.1 Setting of rated current

(1) Open the front cover of Electronic trip relay.

(2) Connect as described in paragraph 9.

(3) Turn on the power switch on the back panel, and the time counter and other indicator lights at the front.

(4) Set the following with the corresponding switches. The settings are changed in turn by pushing the switches.

(The function of each setting, see paragraph 8).

Output frequency 50Hz , 60Hz

Stop signal a , b, ETR

Output pin S1 , S2, S3

Test mode usual test , TRIP CHECK

When the power is turned on, each item is set to the marked position.

(5) Setting of the rated current

First, set the ratio to CT rating because this tester is designed so that signals are output in percentages (%) of

RATED CURRENT In at Electronic trip relay to RATED CURRENT MAX In max(CT rating).

When the power is turned on, the rated current is set to H1.000 (IN=1.000INMAX).

In the case of a C type or S type relay, set the mode to H with the TEST SIGNAL(%) / RATIO

signal level mode switch.

Set to the value of the rated current setting dial of the trip relay with the signal adjusting switches or signal

setting switches.

Example: In the case where the rated current (IN) is set to 0.8,

set to H0.800 .

In the case of an M type relay, set as follows:

Example: In the case where INMAX=1600A and IN=1283A,

1283A1600A=0.802, therefore set to H0.802.

In the case of measuring the ground fault tripping characteristics, set to H1.000 (even if the rated current is not

set to 1.0).

10. Initial setting and operation (for AE-SS/SH)

E-27

10.2 How to operate

DANGER

Test should be performed only after shutting off the electric power and

verifying that there is no voltage present. Failure to do so may result in an

electrical shock.

When current is flowing in the main circuit of breaker, it is combined with the

test signal of Y-2005, consequently does not become correct characteristic.

The operating test should be performed in the state that load current does

not flow in the main circuit.

(1) Set the signal level indicator to . by pushing the TEST SIGNAL(%) / RATIO signal level mode switch.

(2) Set the signal level with the signal adjusting switches or signal setting switches in % of IN set in 10.1 (5).

When using the signal adjusting switches

When using the signal setting switches

Push the C (clear) key.

Since figures are shifted to the left every

time you push the numeral keys, indicate

the desired value.

Push the SET key.

(3) START Push the [START] switch, and the test signal is output, the time counter starts from 000.000, and also

the [TESTING] mode indicating LED lights.

(4) STOP To stop testing, push the [STOP] switch, and the test signal is stopped, the time counter stops, and

also the [TESTING] mode indicating LED goes out.

(5) With tripping, the TRIP indicating LED lights, and the time counter stops. Read the operating time at the time counter.

(6) RESET Push the [RESET] switch to reset the TRIP indicating LED and the time counter, so that testing can

be restarted.

To set 200%, push C 2 0 0 0 SET, and

0200.0 is set.

Continuing to push the switches

increases or decreases the signal

level continuously.

10% 1% 0.1%

E-28

11.1 LTD Pick-up current test

(1) If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM".

(2) Set the signal level to approximately 90% of the pick-up current.

(3) Push the START switch.

(4) Increase the signal with the signal adjusting switch, and measure the pick-up value.

In the case of a C type or S type relay, the long-time-delay pick-up current is to be taken when the [OVER]

LED of the trip relay lights.

In the case where IU of the S relay is not set to 1.0,

for example, if IU is 0.8 and the [OVER] LED lights are at 94%,

the pick-up value is 94%0.8=117.5%.

In the case of an M type relay, the long-time-delay pick-up current is to be taken when the [100%] LED lights.

(5) Push the STOP switch.

(6) Return the trip relay setting changed in (1) to the initial condition.

11.2 LTD operating time test

(1) Set the signal level to be tested.

In the case of a C type or S type relay, the operating time is to be taken at 200%, therefore set the signal level

to 00200.0.

In the case where IU of the S relay is not set to "1.0",

for example, if IU is 0.9,

0.9200%=180%, therefore set the signal level to 00180.0.

In the case of an M relay,

for example, if the long-time-delay pick-up current (IL) is set to "1.05",

1.05120%=126%, therefore set the signal level to 00126.0.

(2) Set the short-time-delay pick-up current (IS) setting dial and the instantaneous pick-up current (I) setting dial of the

trip relay to 1.2 times the above-mentioned signal level or more.

If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM."

(3) Push the START switch.

(4) After tripping, the operating time is indicated.

(5) Push the RESET switch.

(6) Return the trip relay settings changed in (2) to the initial conditions.

Since Electronic trip relay has a memory effect for overcurrent state, when the operating time test is

interrupted on the way, the operating time at the next test becomes short. This memory effect can be

reset by tripping. Therefore, if operating time test is interrupted on the way, perform the next test

after tripping Electronic trip relay one-time. To trip, perform the trip check in accordance with 11.10.

Hint In 11.1 and 11.2, if IU of the S relay is not set to "1.0", the reading of the signal level is regarded as the long-time-delay

pick-up current (%) by setting the value of H. to INIU.

When measuring the long-time-delay operating time, measurement can be performed with the signal level 00200.0.

When performing the short-time-delay or instantaneous tests, return the setting of H. to the initial value.

11. Test (for AE-SS/SH)

E-29

11.3 STD Pick-up current test

(1) Set the instantaneous pick-up current (II) setting dial of the trip relay to the maximum.

Set the short-time-delay operating time (TS) to 0s. (minimum).

If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM."

(2) Set the signal level to approximately 80% of the short-time-delay pick-up current.

(3) Push the START switch, immediately increase the signal with the

signal adjusting switch until Electronic trip relay trips and Time counter

LED stops.

(4) Read the signal level indicated at the time.

(5) In addition, measure the operating times before and after the short-time-delay pick-up current measured above, and

take the point where the operating time shortens suddenly as the measured value of the short-time-delay pick-up

current (IS).

(6) Return the trip relay settings changed in (1) to the initial conditions.

* If there is a long delay in increasing the signal, long-time-delay operation may be performed before reaching the

short-time-delay pick-up current. In this case, start again from approximately 95% of the short-time-delay pick-

up current.

11.4 STD operating time test

(1) Set the instantaneous pick-up current (II) of the trip relay to the maximum. If the trip relay has the ground fault

function (GFR), set the ground fault alarm switch to "ALARM."

(2) Set the signal level to be tested.

For example, if the short-time-delay pick-up current (IS) setting dial is set to 4.5,

450%1.5=675%, therefore set the signal level to 00675.0.

* Here, 1.5 is the value with which the operating time becomes flat.

(3) Push the START switch.

(4) After tripping, the operating time is indicated.

When the stop signal is made by the main

contact or auxiliary switch (AX) Take the reading of the counter as it is.

When the stop signal is made through the test

connector of Electronic trip relay

Add 20ms. (mechanical operating time) to the

reading of the counter.

(5) Push the RESET switch.

(6) Return the trip relay settings changed in (1) to the initial conditions.

(7) Be aware that instantaneous operation may be performed near the instantaneous pick-up current (II) due to the

influence of the signal making phase.

T im

e

Ts

Is Is1.5 Current

Signal adjusting switches

Increase the signal with this key

E-30

11.5 INST Pick-up current test

(1) Set the long-time-delay operating time (TL) setting dial of the trip relay to the maximum.

If the INST/MCR switch is provided, set the switch to "INST."

If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM."

(2) Set the signal level to approximately 80% of the instantaneous pick-up current (I).

(3) Push the START switch with the [STD LOCK] switch of the trip relay pushed, immediately increase the signal with

the signal adjusting switch until Electronic trip relay trips

and Time counter LED stops.

(4) Read the signal level.

(5) Push the RESET switch.

(6) Return the trip relay settings changed in (1) to the initial

conditions.

* If there is a long delay in increasing the signal, long-time-delay operation may be performed before reaching the

instantaneous pick-up current. In this case, start again from approximately 95% of the instantaneous pick-up

current.

* If the MCR/INST switch of the trip relay is set to MCR when the circuit breaker is on, instantaneous operation

is not performed but short-time-delay or long-time-delay operation is performed.

11.6 INST operating time test

(1) Set the signal level to be tested.

For example, if the instantaneous pick-up current (I)

setting dial is set to "10",

1000%1.5=1500%, therefore set the signal level to

01500.0.

* Here, 1.5 is the value with which the operating

time becomes flat.

(2) Push the START switch with the [STD LOCK] switch of the trip relay pushed.

(3) After tripping, the operating time is indicated.

When the stop signal is made by the main

contact or auxiliary switch (AX) Take the reading of the counter as it is.

When the stop signal is made through the test

connector of Electronic trip relay

Add 20ms. (mechanical operating time) to the

reading of the counter.

(4) Push the [RESET] switch.

When checking the short time operation such as INST operating time test, in order to measure the

operating time with accuracy, push the Test power manual connecting switch VT , and push

START switch after the Test power indicating LED lighting. If do not pushing the Test power

manual connecting switch VT , exact measurement cannot be performed.

11.7 MCR function check

(1) Set the INST/MCR switch of the trip relay to MCR.

Set the stop signal of Y-2005 to ETR.

(2) Instantaneous operation is performed with the circuit breaker off.

Check the instantaneous operation in accordance with 11.5 and 11.6.

* This test is checking that instantaneous characteristics is effective during breaker closing operation (from open to close).

(3) Instantaneous tripping characteristics disappear with the circuit breaker on.

Set the signal level exceeding the instantaneous pick-up current (I), and check that instantaneous operation is not performed.

Current

T im

e

II

TI

I I1.5

Signal adjusting switches

Increase the signal level with this 10% step key.

E-31

11.8 GFR Pick-up current test

(1) Set the ground fault alarm switch of the trip relay to "TRIP," and set the ground fault operating time (TG) to "0.3"s.

(minimum).

(2) Set the signal output pin to [S2], and set the rated current to H1.000 in accordance with paragraph 10.

(3) Set the rated current of the tester to IN=1INMAX. (See 10.1 (5) ).

(4) Set the signal level to approximately 80% of the ground fault pick-up current (IG).

(5) Push the START switch, immediately increase the signal with the signal adjusting switch until Electronic trip relay

trips and Time counter LED stops.

(6) Read the signal level indicated at the time.

(7) In addition, push the START switch at several points before and after the ground fault pick-up current measured in

(6), and take the minimum value with which the trip relay trips as the measured value of the ground fault pick-up

current (IG).

(8) Return the trip relay settings changed in (1) to the initial conditions.

11.9 GFR operating time test

(1) Set the signal level to be tested.

(2) Set the ground fault alarm switch of the trip relay to "TRIP."

(3) Set the signal output pin to [S2], and set the rated current to H1.000 in accordance with paragraph 10.

For example, if the ground fault pick-up current (IG) is set to "0.3",

30%1.5=45%, therefore set the signal level to 00045.0.

* Here, 1.5 is the value with which the operating time becomes flat.

(4) Push the START switch.

(5) After tripping, the operating time is indicated.

When the stop signal is made by the main

contact or auxiliary switch (AX) Take the reading of the counter as it is.

When the stop signal is made through the test

connector of Electronic trip relay

Add 20ms. (mechanical operating time) to the

reading of the counter.

(6) Push the RESET switch.

(7) Return the trip relay setting changed in (2) to the initial condition.

When checking the short time operation such as GFR operating time test, in order to measure the

operating time with accuracy, push the Test power manual connecting switch VT , and push the

START switch after the Test power indicating LED lighting. If do not pushing the Test power

manual connecting switch VT , exact measurement cannot be performed.

T im

e

TG

IG1.5 IG Current

E-32

11.10 Trip check

The circuit breaker can be tripped instantaneously with this trip check, which is effective when checking the panel

sequence and resetting the memory effect in 11.2 (7).

(1) Set the test mode to "TC" (trip check).

(2) If the INST/MCR switch is provided for the trip relay, set the switch to "INST."

(3) Push the START switch.

(4) Check that the circuit breaker is tripped instantaneously.

(5) Push the RESET switch.

(6) Return the trip relay setting changed in (2) to the initial condition.

When checking the circuit breaker operating time, push the Test power manual connecting switch

VT , and push START switch after the Test power indicating LED lighting. If do not pushing

the Test power manual connecting switch VT , exact measurement cannot be performed.

11.11 PAL pick-up current test

(1) If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM."

(2) Set the signal level to approximately 80% of the pre-alarm pick-up current (IP).

(3) Push the START switch.

(4) Increase the signal with the signal adjusting switch, and take the value with which the [PAL] LED of the trip relay

lights as the measured value of the pre-alarm pick-up current.

(5) Push the STOP switch.

(6) Return the trip relay setting to the initial condition.

11.12 PAL operating time test

(1) Input control power to the trip relay (between R+ and R1- or between R+ and R2- of the circuit breaker's control

circuit terminal block).

(2) If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM."

(3) Set the stop signal input of the tester to [a], and connect the PAL OUT contacts (T0+ and T4-) of the circuit

breaker with the input terminals on the back of the tester.

(4) Set the signal level to be tested. (See 11.2 LTD operating time test).

(5) Push the START switch.

(6) After operation, the operating time is indicated.

(7) Push the RESET switch.

(8) Return the trip relay setting to the initial condition.

11.13 OCR alarm switch (AL) check

Measure the AL operating time with an oscilloscope, millisecond counter or the like.

The minimum AL operating time is 30 ms., however, when measured with Y-2005, the operating time is

approximately 5 ms. shorter than that taken when tripping at the actual current.

E-33

12.1 Settings and accuracy of type C relay

No. Item Mark

Setting range [tolerance]

AE6304000-SS

/AE-SH AE5000-SS AE6300-SS

Rated current IN

0.5-0.6-0.7-0.8-0.9-1.0INMAX

[The LTD pick-up current ranges from 105% to 125% of the

rated current.]

LTD time TL 150 s. at 2IN (fixed) [20%]

STD Pick-up current IS 2-3-4-6-8-10IN [15]

STD time TS 0-0.1-0.2-0.3-0.4-0.5s. at 1.5IS [20%]

INST pick-up current II 4-6-8-10-12-16IN

[15]

4-6-8-10-12IN

[15]

4-6-8-10IN

[15]

Pre-alarm pick-up current IP 0.7-0.8-0.9-1.0-OVERIN [10]

12. Settings and accuracy (for AE-SS/SH)

STD LOCK switch

Maximum rated current INMAX (CT rating)

E-34

12.2 Settings and accuracy of type S/SL relay

No. Item ark

Setting range [tolerance]

AE6304000-SS

/AE-SH AE5000-SS AE6300-SS

Rated current IN 0.5-0.6-0.7-0.8-0.9-1.0INMAX

Uninterrupted current IU

0.81.0IN

[The LTD pick-up current ranges from 105% to 125% of the uninterrupted

current.]

LTD time TL S series: 50-100-150s. at 2IU [20%]

SL series: 10-15-20-25-30s. at 5IU [20%]

STD Pick-up current IS 2-3-4-6-8-10 [15]

STD time TS 0-0.1-0.2-0.3-0.4-0.5s. at 1.5IS [20%]

INST pick-up current II 4-6-8-10-12-16IN

[15]

4-6-8-10-12IN

[15]

4-6-8-10IN

[15]

(INST/MCR) switch (Note 2) - Switch to select instantaneous tripping characteristics or MCR.

Pre-alarm pick-up current IP 0.7-0.8-0.9-1.0-OVERU [10]

Ground fault pick-up current

(Note 1) IG

0.1-0.2-0.3-0.5INMAX

[20] 0.2-0.3-0.5INMAX [20]

Ground fault operating time TG 0.3-0.8-1.5-3 s. at 1.5IG [20%]

Ground fault alarm switch - Switch to select tripping or only alarm with a ground fault.

STD LOCK switch

(Note 1) The setting for AE4000-SS is the same as that for AE5000-SS and AE6000-SS.

(Note 2) "MCR" is an abbreviation for "making current release", which has INST characteristics only when the circuit breaker is

turned on (make). After the circuit breaker is turned on (make), the INST characteristics disappear.

Maximum rated current INMAX (CT rating)

E-35

12.3 Settings and accuracy of type M relay

No. Item Symbol

Setting range [tolerance]

AE6304000-SS

/AE-SH AE5000-SS AE6300-SS

Rated current IN Set at the factory within the range of 0.51.0INMAX

LTD Pick-up current IL 1.0-1.05-1.1-1.15-1.2IN [5]

LTD time YL 15-20-25-30-40-60s. at 1.2IL [20%]

LTD Pick-up time fine

adjustment - 0.81.01.2TL

STD Pick-up current IS 2-2.5-3-3.5-4-4.5IN [15]

STD time TS 0-0.1-0.2-0.3-0.4-0.5s. at 1.5IS [20]

INST pick-up current II 4-6-8-10-12-16IN

[15]

4-6-8-10-12IN

[15]

4-6-8-10IN

[15]

Pre-alarm pick-up current IP 0.84-0.88-0.92-0.96-1.0IL [5%]

Ground fault pick-up current

(Note) IG

0.1-0.2-0.3-0.5

INMAX [20] 0.2-0.3-0.5INMAX [20]

Ground fault operating time TG 0.3-0.8-1.5-3s. at 1.5IG [20]

Ground fault alarm switch - Switch to select tripping or only alarm with a ground fault.

STD LOCK switch

(Note) The setting for AE4000-SS is the same as that for AE5000-SS and AE6300-SS.

Maximum rated current INMAX (CT rating)

E-36

Inspection report form for S type relay Date: Checked person:

13. Inspection form (for AE-SS/SH)

E-37

14. SERVICE NETWORK

AE MITSUBISHI Low-Voltage Air Circuit Breakers type AE

Y-2005

Field test devise Y-2005

LN338A475H01 <

Manualsnet FAQs

If you want to find out how the AE1000-SS Mitsubishi works, you can view and download the Mitsubishi AE1000-SS Breaker Instruction Manual on the Manualsnet website.

Yes, we have the Instruction Manual for Mitsubishi AE1000-SS as well as other Mitsubishi manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Instruction Manual should include all the details that are needed to use a Mitsubishi AE1000-SS. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Mitsubishi AE1000-SS Breaker Instruction Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Mitsubishi AE1000-SS Breaker Instruction Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Mitsubishi AE1000-SS Breaker Instruction Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Mitsubishi AE1000-SS Breaker Instruction Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Mitsubishi AE1000-SS Breaker Instruction Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.