CC-Link IE Field Network Data Collector (MELIPC MI5122-VW) User's Manual

-SW1DNN-DCCCIEFM-M

1

SAFETY PRECAUTIONS (Read these precautions before using this product.)

Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle

the product correctly.

The precautions given in this manual are concerned with this product only. For the safety precautions of the programmable

controller system, refer to the user's manual for the CPU module used.

In this manual, the safety precautions are classified into two levels: " WARNING" and " CAUTION".

Under some circumstances, failure to observe the precautions given under " CAUTION" may lead to serious

consequences.

Observe the precautions of both levels because they are important for personal and system safety.

Make sure that the end users read this manual and then keep the manual in a safe place for future reference.

[Design Precautions]

[Design Precautions]

WARNING To perform an operation, such as data change or operating status change, to running devices, such as

a programmable controller, servo, robot, or server, from an industrial PC equipped with this product,

configure an interlock circuit outside of the devices so that the entire system always operates to the

safety side. Additionally, read this manual carefully and ensure the safety before operations.

Especially, in the above mentioned operations that are performed from external devices through

network, any problems on devices may not be dealt with promptly due to an abnormal data

communication.

Configure a safety circuit outside of an industrial PC equipped with this product so that the entire

system operates to the safely side even when a fault occurs in the PC.

Failure to do so may result in an accident due to an incorrect output or malfunction.

CAUTION During application of each setting, do not perform the operation that forcibly turns the industrial PC

equipped with this product OFF.

Otherwise, the data will be undefined and resetting and re-registering data will be required.

Additionally, doing so may cause the malfunction of this product.

WARNING Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.

CAUTION Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury or property damage.

2

CONDITIONS OF USE FOR THE PRODUCT (1) This software shall be used under the following conditions:

i) that any failure occurred in this software, if any, shall not lead to any serious accident. ii) that the backup and/or fail-safe functions are systematically performed outside the devices in the cases of any failure occurred in this software.

(2) Mitsubishi assumes no responsibility and liability (including but not limited to, default liability, defect liability, quality assurance responsibility, tort liability, product liability) for the quality, performance, and safety of both this software and products using this software.

3

INTRODUCTION Thank you for purchasing CC-Link IE Field Network Data Collector.

This manual describes the specifications, procedures before operation, and troubleshooting of this product.

Before using this product, please read this manual and the relevant manuals carefully, and develop familiarity with the

functions and performance of this product to handle correctly.

Please make sure that the end users read this manual.

4

CONTENTS SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

CONDITIONS OF USE FOR THE PRODUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

RELEVANT MANUALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

TERMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

CHAPTER 1 CC-Link IE Field Network Data Collector 7

CHAPTER 2 SPECIFICATIONS 9

2.1 Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

2.2 Operational Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Behavior when an error occurs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.3 Accessible devices (locations) and range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Accessible devices (locations). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

CHAPTER 3 PROCEDURE BEFORE OPERATION 13

CHAPTER 4 FUNCTIONS 15

4.1 Data Collection Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Cyclic transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

4.2 Data Reading Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Cyclic transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

4.3 Data Writing Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Cyclic transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

4.4 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

CHAPTER 5 PARAMETER SETTING 23

5.1 Communication Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

5.2 Collection Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

5.3 Location Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

CHAPTER 6 TROUBLESHOOTING 25

6.1 Checking Method for Error Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Error type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

6.2 Troubleshooting by Symptom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Troubleshooting on the CC-Link IE Field Network Data Collector startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Troubleshooting on data collection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Troubleshooting on data reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Troubleshooting on data writing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Troubleshooting on Edgecross Basic Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Troubleshooting on screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

6.3 Error Code List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

6.4 Event Code List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

APPENDIX 39

Appendix 1 Processing Performance and Processing Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Processing performance in data collection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

5

C O

N T

E N

T S

Processing performance in read processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Appendix 2 Data Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Data assignment availability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Number of points for data assignment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Appendix 3 Buffer Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Buffer memory list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Buffer memory details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Appendix 4 Software Licenses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Software information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Appendix 5 Supported Edgecross Basic Software Version. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Appendix 6 Added and Changed Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

INDEX 49

REVISIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51

TRADEMARKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52

6

RELEVANT MANUALS

e-Manual refers to the Mitsubishi Electric FA electronic book manuals that can be browsed using a dedicated

tool.

e-Manual has the following features:

Required information can be cross-searched in multiple manuals.

Other manuals can be accessed from the links in the manual.

Hardware specifications of each part can be found from the product figures.

Pages that users often browse can be bookmarked.

Sample programs can be copied to an engineering tool.

TERMS Unless otherwise specified, this manual uses the following terms.

Manual name [manual number] Description Available form

CC-Link IE Field Network Data Collector (MELIPC

MI5122-VW) User's Manual

[SH-081923ENG] (this manual)

Explains the specifications, procedure before operation, and troubleshooting

of CC-Link IE Field Network Data Collector.

e-Manual

PDF

Term Description

Cyclic transmission A function to exchange data periodically between stations on network by using link devices.

Data model management A function that abstracts devices, equipment, and lines in the production site and hierarchically manages them.

Edge application Software that performs various processing for data utilization in production sites using the functions provided by

Edgecross in the edge computing area.

Edge computing An information processing method and area, for not only collecting and analyzing data in production sites in real-time,

and feed backing the data, but summarizing the production site data and sharing information with IT systems efficiently

with the hardware and software in production sites.

Edgecross A software platform that implements specifications and concepts for realizing manufacturing solutions by the FA-IT

collaboration centering on the edge computing.

Edgecross Basic Software The name of the software product that implements the Edgecross function.

Industrial PC A PC specialized for industrial use with features such as high reliability, environmental resistance, and long-term supply.

Link device A device (RX, RY, RWr, and RWw) in modules on CC-Link IE Field Network.

Management Shell The name of the Windows version product that implements the model management function.

Management Shell Explorer Software that sets and refers to data models managed by Management Shell.

MI Configurator A product name for SWnDNN-MICONF. ("n" indicates its version.)

Real-time data processing A function that realizes the real-time diagnosis and feedback of the production site data.

Real-time Flow Designer The name of the software component that performs operation setting of Real-time Flow Manager.

Real-time Flow Manager The name of the Windows version software component that implements the real-time data processing.

1 CC-Link IE Field Network Data Collector 7

1 1 CC-Link IE Field Network Data Collector

CC-Link IE Field Network Data Collector (SW1DNN-DCCCIEFM-M) is a software component that performs the data

collection, data reading, and data writing functions in cyclic transmission via CC-Link IE Field Network.

Data in a device can be collected and updated by using CC-Link IE Field Network Data Collector in combination with

Edgecross Basic Software.

For details on Edgecross Basic Software, refer to the following manual.

Edgecross Basic Software for Windows User's Manual

CC-Link IE Field Network Data Collector (SW1DNN-DCCCIEFM-M) is designed for MI5122-VW.

For MI5122-VW, refer to the following manual.

MELIPC MI5000 Series User's Manual (Startup)

CC-Link IE Field Network Data Collector runs by using a routine performed when a link scan of CC-Link IE

Field Network is completed.

Therefore, do not use the function (CCPU_EntryLinkScanEndFunc function) used for registering the routine

in a user program of MI5122-VW.

If the function is used, some problems such as data collection failure, no change in collected data, and no

feedback will occur.

When running CC-Link IE Field Network Data Collector and a user program of MI5122-VW at the same

time, the data collection timing of the Data Collector will be unstable.

Lower the priority of the user program of MI5122-VW.

CC-Link IE Field Network Data Collector may use up to 50 percent of the CPU for the interrupt processing.

This must be considered when including the interrupt processing in a user program of MI5122-VW to avoid

a system WDT error.

8 1 CC-Link IE Field Network Data Collector

MEMO

2 SPECIFICATIONS 2.1 Functional Specifications 9

2

2 SPECIFICATIONS

This chapter shows the functional specifications, operational specifications, and accessible devices (locations) and range of

CC-Link IE Field Network Data Collector.

2.1 Functional Specifications This section shows the functional specifications of CC-Link IE Field Network Data Collector.

Item Specification

Connectable route CC-Link IE Field Network with built-in MI5122-VW

(Cyclic transmission)

Supported type by a data collector Data collection function

Data reading function/Data writing function

Data collection function Maximum number of flow settings 64 including the settings in Data reading function/Data

writing function*1

Maximum number of units of data for one flow 256

Maximum collectible size for one flow 8192 (word)

Collection interval Cyclic transmission 5 to 999 (ms)

1 to 10 (s)

Each link scan time

Input data type*2 BOOL (Bit value)

INT (Signed 16-bit integer value)

UINT (Unsigned 16-bit integer value)

DINT (Signed 32-bit integer value)

UDINT (Unsigned 32-bit integer value)

LINT (Signed 64-bit integer value)

ULINT (Unsigned 64-bit integer value)

REAL (32-bit real number value)

LREAL (64-bit real number value)

STRING (Character string: UTF-8 (1 to 32 characters))

WSTRING (Wide-character string: Unicode (UTF-16LE)

(1 to 16 characters))

Accessible device

(Location)

Cyclic transmission RX, RY, RWr, RWw*3

Data reading function/

Data writing function

Maximum number of settings 64 including the settings in Data collection function*1

Maximum number of units of data for one setting 256

Maximum collectible size for one setting 8192 (word)

Input and output data type*2 BOOL (Bit value)

INT (Signed 16-bit integer value)

UINT (Unsigned 16-bit integer value)

DINT (Signed 32-bit integer value)

UDINT (Unsigned 32-bit integer value)

LINT (Signed 64-bit integer value)

ULINT (Unsigned 64-bit integer value)

REAL (32-bit real number value)

LREAL (64-bit real number value)

STRING (Character string: UTF-8 (1 to 32 characters))

WSTRING (Wide-character string: Unicode (UTF-16LE)

(1 to 16 characters))

Accessible device

(Location)

Cyclic transmission RX, RY, RWr, RWw*4

10 2 SPECIFICATIONS 2.1 Functional Specifications

*1 For details, refer to the following: Edgecross Basic Software for Windows User's Manual

*2 For details on data types, refer to the following manual. Edgecross Basic Software for Windows User's Manual

*3 When MI5122-VW is set as the master station, RY and RWw cannot be accessed. *4 When MI5122-VW is set as the master station and if the data reading function is performed, RY and RWw cannot be accessed. *5 Before using CC-Link IE Field Network Data Collector, only the start-up monitor task is performed. *6 When CC-Link IE Field Network Data Collector is not working, the priority of each task will be '255'. *7 It is not registered when CC-Link IE Field Network Data Collector is not running.

Resource used for the

VxWorks part

Number of tasks 3*5,*6

Start-up monitor task (Priority: 120)

Task for monitoring whether the Windows part of a data

collector is started up

Periodic monitor task (Priority: 46)

Task for monitoring the time interval to perform the

periodic processing

Cyclic access task (Priority: 100)

Task for a cyclic access

Maximum number of settings for a data collector 64

Routine called when a link scan of the CC-Link IE field Network is

completed

Registered*7

Buffer memory 1024 (point)

Memory RAM 4 MB

ROM 1 MB

Item Specification

2 SPECIFICATIONS 2.2 Operational Specifications 11

2

2.2 Operational Specifications This section shows the operational specifications of CC-Link IE Field Network Data Collector.

Operating status The status of CC-Link IE Field Network Data Collector varies for each access target and is determined according to the

communication status with the targets.

The communication status with access targets can be checked in Edgecross Basic Software.

Behavior when an error occurs When CC-Link IE Field Network Data Collector detects an error, it performs the following operations depending on the error

type.

The type of errors reported to Edgecross Basic Software are as follows:

Data collector operation stop error: Moderate error

Data collector operation continuation error: Minor error

Status of CC-Link IE Field Network Data Collector Description Communication status with an access target

Data is being read from or written to an access target. Data Collector and the access target are connected

normally. (It will be in this state when the connection

processing succeeds.)

Connected

Data is not read from or written to an access target.

(Reconnection is being performed.)

Data Collector and the access target is disconnected.

(It will be in this state when the connection processing

fails.)

Disconnected

Error type Status of CC-Link IE Field Network Data Collector

Behavior of CC-Link IE Field Network Data Collector

Data collector operation stop error Operations according to the specifications cannot be

guaranteed due to a hard disk error in MI5122-VW of

the installation destination or a failure of resource

securing.

A error cannot be corrected even by changing the

network configuration due to an incorrect parameter

setting (device type out of range, for example).

Discards collected data when this error occurs during

data collection.

Stops the data collection, data reading, or data

writing function and reports this error to Edgecross

Basic Software.

Data collector operation continuation error Operations such as a program execution or data

communication cannot be continued due to

temporary network failure.

An error may be corrected by changing the network

configuration even though there is no

communication due to a mismatch between the

parameter settings and the network configuration.

Discards collected data when this error occurs during

data collection.

Continues the data collection, data reading, or data

writing function even after reporting this error to

Edgecross Basic Software.

12 2 SPECIFICATIONS 2.3 Accessible devices (locations) and range

2.3 Accessible devices (locations) and range This section shows the accessible devices (locations) and range.

Accessible devices (locations) The following table shows the accessible devices (locations).

Cyclic transmission : Accessible

Device name (device) Range Accessibility

Remote input (RX) 0 to 3FFF

Remote output (RY) 0 to 3FFF

Remote register (RWw) 0 to 1FFF

Remote register (RWr) 0 to 1FFF

3 PROCEDURE BEFORE OPERATION 13

3

3 PROCEDURE BEFORE OPERATION

This chapter shows the procedure from start-up to operation of CC-Link IE Field Network Data Collector.

Operating procedure

1. Set the setting of a device and wire and connect it to MI5122-VW.

For the setting, wiring, and connection methods, refer to the manuals of the device and MI5122-VW to use.

Manual of the MELSEC device to use

MELIPC MI5000 Series User's Manual (Startup)

2. Set the parameters of CC-Link IE Field Network necessary for the Data Collector.

For the setting method of parameters, refer to the following manual.

MI Configurator Operating Manual

3. Set parameters of the Data Collector.

Page 23 PARAMETER SETTING

Precautions

When running a data collector on an industrial PC where an antivirus software is installed, an exceeded collection cycle or

data missing may occur due to an operation of the antivirus software. Exclude the following folders from the monitoring targets

in the antivirus software settings. For the setting methods, refer to the manual for each antivirus software.

Installation destination folder of a data collector

Following files and folders of Windows

Pagefile.sys

*.pst

%systemroot%\System32\Spool

%systemroot%\SoftwareDistribution\Datastore

%windir%\Security\Database

%allusersprofile%\NTUser.pol

%systemroot%\system32\GroupPolicy\Machine\registry.pol

%systemroot%\system32\GroupPolicy\User\registry.pol

14 3 PROCEDURE BEFORE OPERATION

MEMO

4 FUNCTIONS 4.1 Data Collection Function 15

4

4 FUNCTIONS

This chapter shows the functions of CC-Link IE Field Network Data Collector.

4.1 Data Collection Function This function collects data in the interval of the set collection cycle.

Data can be collected in the following transmission method:

Cyclic transmission (Page 15 Cyclic transmission)

Cyclic transmission This is the method for collecting the link devices, RX, RY, RWr, and RWw, which are sent from a device connected via CC-

Link IE Field Network in cyclic transmission.

The collection methods which can be set for the cyclic transmission are as follows:

Collection method Overview Reference

Collection at a time interval This method is for collecting data by accessing link devices periodically every

set interval.

Data is collected at the specific intervals, so the collected data is suitable for

waveform analysis.

Page 16 Collection at a time interval

Collection for each link scan This method is for collecting data by synchronizing with the link scan and

accessing to link devices.

Data is collected for each link scan, so data will be collected without missing a

data change even in the cyclic transmission in which data is transmitted and

received at high speed.

Page 17 Collection for each link scan

16 4 FUNCTIONS 4.1 Data Collection Function

Collection at a time interval This is the method for collecting data of link devices at the set interval.

Time information added to collected data is the time of the VxWorks part when accessing to link devices.

Ex.

The following shows the timing of a data collection by collection at a time interval.

Time interval: 18 milliseconds

: Link scan in which data is collected

: Link scan in which data is not collected

: Link scan time

: Collection interval

Data is collected at 10:24:20.010.

Data is collected at 10: 24: 20.028 - 18 milliseconds later.

Data is collected at 10:24:20.046 - 18 milliseconds later.

Data is collected at 10:24:20.064 - 18 milliseconds later.

Data is collected at 10:24:20.082 - 18 milliseconds later.

Setting for MI5122-VW Set the following parameters of MI5122-VW in MI Configurator.

For MI Configurator, refer to the following manual.

MI Configurator Operating Manual

Data missing If data collection is not started even after the allowable collection processing delay time (the set collection cycle 2) elapses,

an exceeded collection cycle is detected and the data for which data collection is not started will be missing.

Effects of time change When changing the time of MI5122-VW, collection time interval added to collected data is not fixed but the collection cycle is

fixed.

Item Setting content

Basic Parameter Operation

Related Setting

Time Setting Clock Data

Synchronization

Settings

To Use or Not to

Clock Data

Synchronization

Settings

Select "Enable".

Synchronous

Source

Select "VxWorks part".

Clock Related

Setting

Time Zone Set the same contents as the clock setting in the

Windows part.Setting to Adjust Clock for Daylight

Saving Time

22ms 12ms 14ms 24ms

18ms 18ms 18ms 18ms

10:24:20.010 10:24:20.028 10:24:20.046 10:24:20.064 10:24:20.082

4 FUNCTIONS 4.1 Data Collection Function 17

4

Collection for each link scan This is the method for collecting data of link devices for each link scan.

The features of the data collection for each link scan are as follows:

Data can be collected for each link scan if the link scan time differs every time.

Data can be collected in a single link scan without spanning multiple link scans.

Ex.

The following shows the timing of a data collection by collection for each link scan.

: Link scan in which data is collected

: Link scan time

Data is collected at 10:24:20.010.

Data is collected at 10:24:20.032 - 22 milliseconds later.

Data is collected at 10:24:20.044 - 12 milliseconds later.

Data is collected at 10:24:20.058 - 14 milliseconds later.

Data is collected at 10:24:20.082 - 24 milliseconds later.

Data missing Data missing occurs when a data collection is not completed within the set collection cycle. (It is registered as an event.)

Cyclic transmission cancellation When MI5122-VW is set as a local station, data is not collected when cyclic transmission is not performed.

Whether cyclic transmission is being performed can be checked according to any of the following methods.

Check the status of 'D LINK LED' on the front of MI5122-VW.

For details on MI5122-VW, refer to the following manual.

MELIPC MI5000 Series User's Manual (Startup)

Perform a CC-Link IE Field diagnosis of MI Configurator.

For details on MI Configurator, refer to the following manual.

MI Configurator Operating Manual

22ms 12ms 14ms 24ms

10:24:20.010 10:24:20.032 10:24:20.044 10:24:20.058 10:24:20.082

18 4 FUNCTIONS 4.1 Data Collection Function

Collection processing time report When an enable data collection setting is included in Edgecross Basic Software and the operating status of the software is

changed from RUN to STOP, the maximum and minimum collection processing times when the software was in the RUN state

are reported to the software.

The collection processing time is reported according to the following.

Unit: Microsecond

Range: 0 to 4294967295

When no data is collected while Edgecross Basic Software is in the RUN state, the maximum and minimum

collection processing times are reported as '0'.

In a report, the unit is changed to millisecond (three decimal places).

Precautions

The operations when collecting the WSTRING type data are as follows:

For non-surrogate characters, one word is collected from a target device.

For surrogate characters, two words are collected from a target device.

Ex.

Setting of data to be collected

WSTRING type data [Number of characters = 4] (D0-D7)

Setting of a value to be collected

D0: 'A'

D1: 'B'

D2-D3: ''

D4:'C'

D5:'D'

D6:'E'

D7:'F'

Collection result

"ABC"

indicates a surrogate character.

4 FUNCTIONS 4.1 Data Collection Function 19

4

Features The following shows the features of the data collection function in cyclic transmission.

High-speed data collection Data can be collected at high-speed by using the VxWorks part of MI5122-VW to collect data from link devices in cyclic

transmission.

Unit (block) of data collection In cyclic transmission, the link device area is divided for each block*1 for collecting data efficiently and collect data from blocks

in use.

*1 The unit divided by 64 words from the start device memory number in each device type is referred to "block".

Bit device (RX/RY)

Word device (RWr/RWw)

If one device in a block is used, the block is considered to be used.

Ex.

The number of used blocks is two when data is collected from RX0, RX1, RX3FF, and RX400.

: Used device

: Unused device

Bit device (RX)

Ex.

The number of used blocks is three when data is collected from RX0, RY0, and RWr0.

: Used device

: Unused device

Bit device (RX)

Bit device (RY)

Word device (RWr)

0H 1H 2H 3FDH

64 words

3FEH 3FFH 400H 401H 402H 7FDH 7FEH 7FFH 800H 801H

64 words

0H 1H 2H 3DH

64 words

3EH 3FH 40H 41H 42H 7DH 7EH 7FH 80H 81H

64 words

0H 1H 2H 3FDH

64 words

3FEH 3FFH 400H 401H 402H 7FDH 7FEH 7FFH 800H 801H

64 words

0H 1H 2H 3FDH

64 words

3FEH 3FFH 400H 401H 402H 7FDH 7FEH 7FFH 800H 801H

64 words

0H 1H 2H 3FDH

64 words

3FEH 3FFH 400H 401H 402H 7FDH 7FEH 7FFH 800H 801H

64 words

0H 1H 2H 3DH

64 words

3EH 3FH 40H 41H 42H 7DH 7EH 7FH 80H 81H

64 words

20 4 FUNCTIONS 4.1 Data Collection Function

Considerations The following shows the considerations for the data collection function in cyclic transmission.

Data transmission delay Transmission delay occurs in cyclic transmission, so the collected values are ones that has been sent from the collection

destination before the collection time added in the collected data.

Data inconsistency In cyclic transmission, it is guaranteed by CC-Link IE Field Network that data inconsistency will not occur in 32-bit data.

However, data inconsistency may occur in collected data exceeding 32-bits if a link scan occurs during data copy.

By using the data inconsistency prevention function, data inconsistency in cyclic transmission can be prevented.

For using the function, enable the setting of the block data assurance per station in the master station.

For the setting, refer to the manual of a device used as a master station.

Setting change during data collection When the collection setting is changed and updated from Edgecross Basic Software during data collection, the data collection

being performed is stopped and it is restarted according to the new setting.

4 FUNCTIONS 4.2 Data Reading Function 21

4

4.2 Data Reading Function This function sends a data reading request to a device according to a request from Edgecross Basic Software and reads data.

Cyclic transmission It reads data of link devices according to a request from Edgecross Basic Software.

Read processing time report When reconnecting to an access target device in Edgecross Basic Software, the maximum and minimum read processing

times during the operation are reported to the software.

Unit: Microsecond

Range: 0 to 4294967295

When no data is read during the operation, the maximum and minimum read processing times are reported

as '0'.

In a report, the unit is changed to millisecond (three decimal places).

Precautions

The operations when reading the WSTRING type data are as follows:

For non-surrogate characters, one word is read from a target device.

For surrogate characters, two words are read from a target device.

Ex.

Setting of data to be read

WSTRING type data [Number of characters = 4] (D0-D7)

Setting of a value to be read

D0: 'A'

D1: 'B'

D2-D3: ''

D4:'C'

D5:'D'

D6:'E'

D7:'F'

Reading result

"ABC"

indicates a surrogate character.

22 4 FUNCTIONS 4.3 Data Writing Function

4.3 Data Writing Function This function sends a data writing request to a device according to a request from Edgecross Basic Software and writes data.

Cyclic transmission It writes data to link devices according to a request from Edgecross Basic Software.

Precautions

The operations when writing the WSTRING type data are as follows:

For non-surrogate characters, one word is written to a target device.

For surrogate characters, two words are written to a target device.

Ex.

Setting of data to be written

WSTRING type data [number of characters = 4] (RWw0-RWw7)

Setting of a value to be written

ABC

indicates a surrogate character.

Writing result

RWw0: 'A'

RWw1: 'B'

RWw2: 'C'

RWw3-RWw4: ''

RWw5-RWw7: '\0'

4.4 Considerations The following shows the considerations for the functions of CC-Link IE Field Network Data Collector.

Cyclic data assurance During cyclic data assurance, the update of the input and output status of link devices is stopped.

Therefore, during that time, collected data will not be changed and also the feedback will not be provided.

Consider these above when using the following functions for assuring data in a user program.

CCPU_StartLinkDeviceAssurance

CCPU_EndLinkDeviceAssurance

For details on functions, refer to the following manual.

MELIPC MI5000 Series Programming Manual (VxWorks)

Operation when a data link error occurs in the own station The following table shows the operations when a data link error occurs in the own station on CC-Link IE Field Network during

the data collection, reading, or writing.

Function Cycle System Station type Operational specification

Error registration content

Data

collection

Specify Cycle Master/local station Collects data. The error code '1007H' is registered in

Edgecross Basic Software.

Each Link Scan Master station Collects data. The error code '1007H' is registered in

Edgecross Basic Software.

Local station Does not collect data. The error code '1007H' is registered in

Edgecross Basic Software.

Data reading Master/local station Does not read data. The error code '1007H' is registered in

Edgecross Basic Software.

Data writing Master/local station Does not write data. The error code '1008H' is registered in

Edgecross Basic Software.

5 PARAMETER SETTING 5.1 Communication Parameter 23

5

5 PARAMETER SETTING

The parameter settings for CC-Link IE Field Network Data Collector can be set in Edgecross Basic Software.

For the display of the setting screens for each parameter, refer to Edgecross Basic Software User's Manual.

Edgecross Basic Software for Windows User's Manual

5.1 Communication Parameter Set the setting on the connection between CC-Link IE Field Network Data Collector and a device.

Window

The "Target Device Setting" screen of Real-time Flow Designer

The "Target Device Setting" screen of Management Shell Explorer

Displayed items

Item Description

Initial Access Delay Time Set the waiting time from when the initialization processing of an access target device is completed until data collection

can be performed (0 to 255 seconds).

User Name Set a user name registered in the user authentication setting of MI5122-VW.

Password Set a password registered in the user authentication setting of MI5122-VW.

24 5 PARAMETER SETTING 5.2 Collection Parameter

5.2 Collection Parameter Set the setting on data collection in CC-Link IE Field Network Data Collector.

Window

The [Collection Option] tab in the "Data Collection Setting" screen of Real-time Flow Designer

Displayed items

*1 It cannot be set when "Each Link Scan" is selected for "Cycle System".

5.3 Location Parameter In CC-Link IE Field Network Data Collector, a screen for setting location parameters is not included.

Enter accessible devices (locations) shown in the following section directly.

Page 12 Accessible devices (locations)

Item Description

Cycle System Select a cycle to collect data.

Collection Interval*1 Set an interval and the unit for collecting data.

6 TROUBLESHOOTING 6.1 Checking Method for Error Descriptions 25

6

6 TROUBLESHOOTING

This chapter explains the errors which may occur when using CC-Link IE Field Network Data Collector and the

troubleshooting.

6.1 Checking Method for Error Descriptions The following are the methods for checking error descriptions.

Error type There are two types of errors for CC-Link IE Field Network Data Collector; moderate error and minor error.

Checking method Details

Real-time Flow Designer Error codes can be checked in the "Real-time Flow Manager Diagnostics" screen of Real-time Flow Designer.

For details, refer to the following:

Edgecross Basic Software for Windows User's Manual

Management Shell Explorer Error codes can be checked in the "Error Information List" screen of Management Shell Explorer.

For details, refer to the following:

Edgecross Basic Software for Windows User's Manual

26 6 TROUBLESHOOTING 6.2 Troubleshooting by Symptom

6.2 Troubleshooting by Symptom If a function of CC-Link IE Field Network Data Collector does not perform properly, check the applicable items in the following

and troubleshoot the error.

For the troubleshooting by symptom for MI5122-VW, refer to the following:

MELIPC MI5000 Series User's Manual (Application)

Troubleshooting on the CC-Link IE Field Network Data Collector startup

The data collector is not recognized at the Edgecross Basic Software start.

Troubleshooting on data collection

Data collection cannot be performed.

There is no change in collected data.

Data inconsistency occurs in collected data.

Data missing has occurred in collected data.

Check point Corrective action

Does a signed-in user who started Edgecross Basic

Software have the access right to a folder in which

CC-Link IE Field Network Data Collector is stores?

Sign in as a user with the access right to the folder in which CC-Link IE Field Network Data Collector

is stored, and start Edgecross Basic Software.

Grant the user access to the folder in which CC-Link IE Field Network Data Collector is stored.

Check point Corrective action

Does the data link error occur on CC-Link IE Field

Network?

Solve the data link error by performing a CC-Link IE Field diagnosis of MI Configurator.

(MI Configurator Operating Manual)

Is the station type of the network parameter in CC-

Link IE Field Network set to a master station, the VX

RDY LED on a MELIPC (MI5122-VW) turned OFF,

and the MAIN ERR LED turned ON?

Delete the RY and RWw devices in the collection data setting.

Check point Corrective action

Does the data link error occur on CC-Link IE Field

Network?

Solve the data link error by performing a CC-Link IE Field diagnosis of MI Configurator.

(MI Configurator Operating Manual)

Is a slave station on CC-Link IE Field Network

disconnected?

Restore the connection with the slave station on CC-Link IE Field Network.

Is a value other than '0' set for the number of times of

the un-executed interrupt processing in the buffer

memory?

Review the number of collection points and the processing contents to lower the load.

Check point Corrective action

Is "Disable" set for "Station-based Block Data

Assurance" in the network parameter of CC-Link IE

Field Network?

Change the network parameter of CC-Link IE Field Network and set "Enable" for "Station-based Block

Data Assurance" in MI Configurator.

(MI Configurator Operating Manual)

Check point Corrective action

Is the event code '8000H' registered and "Cycle

System" of the collection parameter set to "Specify

Cycle"?

Review the collection interval of the collection parameter.

Restart the MELIPC running this product.

Lower the load on the Windows part.

Lower the load of the VxWorks part.*1

Review the number of collection points and the processing contents to lower the load.

6 TROUBLESHOOTING 6.2 Troubleshooting by Symptom 27

6

*1 Perform the following to reduce the load. Review the user program processing to reduce the CPU usage rate and the load of file I/O. Reduce the frequency of file reading and writing from/to the VxWorks part using the file sharing function. Reduce the frequency of parameter reading and writing using MI Configurator. Reduce the frequency of event history acquisition using MI Configurator. Reduce the frequency of access to the VxWorks part using Telnet. Reduce the frequency of access to the VxWorks part using FTP.

*2 The link scan time of CC-Link IE Field Network can be checked by performing a CC-Link IE Field diagnosis of MI Configurator. MI Configurator Operating Manual

Is the event code '8000H' registered and "Cycle

System" of the collection parameter set to "Each Link

Scan"?

Change the setting for "Cycle System" of the collection parameter to "Specify Cycle".

Restart the MELIPC running this product.

Lower the load on the Windows part.

Lower the load of the VxWorks part.*1

Review the number of collection points and the processing contents to lower the load.

Review the setting of CC-Link IE Field Network to increase the link scan time of the network.*2

Check point Corrective action

28 6 TROUBLESHOOTING 6.2 Troubleshooting by Symptom

Troubleshooting on data reading

Data cannot be read.

Troubleshooting on data writing

Data cannot be written.

Troubleshooting on Edgecross Basic Software

An error caused by this product has been detected in Edgecross Basic Software.

Troubleshooting on screens

Contents in the screen may not be displayed properly.

*1 The Windows version can be checked by the following procedure. Press Windows key + , or select [Windows System] [Run] from Windows Start. Enter 'winver' in the "Run" screen. Check the version in the displayed screen.

*2 The display will be blurred by enlarging. The following lists the setting values for "Change the size of text, apps, and other items" and the recommended display resolution for each setting value in Windows 10. Setting value: 100%, display resolution: 1024 768 dots or more Setting value: 125%, display resolution: 1900 1200 dots or more Setting value: 150%, display resolution: 1900 1200 dots or more Setting value: 175%, display resolution: 2880 1620 dots or more Setting value: 200%, display resolution: 2880 1620 dots or more Setting value: 225%, display resolution: 3840 2160 dots or more Setting value: 250%, display resolution: 3840 2160 dots or more

*3 'ProcessDesigner.exe' is stored in the folder in which Edgecross Basic Software is installed. The following is an example of a storage location. (Example) When starting the operating system on the C drive and setting the installation destination folder as the default C:\Edgecross\Edgecross Basic Software\Real-timeFlowDesigner\ProcessDesigner.exe

Check point Corrective action

Is the initial access delay time set? Wait until the set initial access delay time elapses.

Set the initial access delay time shorter.

Check point Corrective action

Is the initial access delay time set? Wait until the set initial access delay time elapses.

Set the initial access delay time shorter.

Check item Corrective action

Has a data collector startup error been detected in Edgecross Basic

Software?

Reinstall this product since the file may have been moved or deleted.

Check item Corrective action

Is a value other than 100% set for "Change the size of text, apps, and other

items" in Windows?

Change the value to 100% for "Change the size of text, apps, and other

items".

For Windows 10 (version 1703 or later)*1, the display of a screen can be

enlarged with high DPI scaling by using a Windows 10 function*2.

Select 'ProcessDesigner.exe'*3, then select [Properties] on the right-click

menu.

Select the checkbox of "Override high DPI scaling behavior. Scaling

performed by:" in the [Compatibility] tab, then select "System" from the pull-

down list.

Click the [OK] button.

6 TROUBLESHOOTING 6.3 Error Code List 29

6

6.3 Error Code List This section shows the codes for errors that occur in CC-Link IE Field Network Data Collector.

Error code

Error name Error description Corrective action

1000H Communication

parameter setting error

There is an error in the communication parameter. Please review the communication parameter because

there is an error.

1001H Collection parameter

setting error

There is an error in the collection parameter. Please review the collection parameter because there is

an error.

1002H Location parameter

setting error

There is an error in the location parameter. Please review the location parameter because there is an

error.

1003H Device memory No.

error

A device memory No. which does not exist is specified. Please review the device memory No. specified in the

location parameter.

1004H Insufficient memory error There is not enough memory available to running the

Windows part.

Please restart the MELIPC running this product.

Please close the unnecessary Windows applications

and lower the load on the Windows part.

1005H Data Collector internal

error

An unexpected error caused by the Windows part

occurred inside this product.

If Real-time Flow Manager is used, please write the

Real-time Flow Manager parameter again.

Please restart the MELIPC running this product.

Please reinstall this product.

Please consult your local Mitsubishi representative if

the same error occurs again.

1006H Data Collector internal

error

Communication between tasks inside the VxWorks part

failed.

Please restart the MELIPC running this product.

Please close the unnecessary VxWorks applications

and lower the load on the VxWorks part.

Please reinstall this product.

1007H Data reading error Reading of data failed because data link is stopped. Please check if there is any device which is

disconnected from the CC-Link IE field network.

Please check if there is any problem of the CC-Link IE

field network with the CC-Link IE field diagnosis by MI

Configurator.

Please review the network parameter of the CC-Link IE

field network.

1008H Data writing error Writing of data failed because data link is stopped. Please check if there is any device which is

disconnected from the CC-Link IE field network.

Please check if there is any problem of the CC-Link IE

field network with the CC-Link IE field diagnosis by MI

Configurator.

Please review the network parameter of the CC-Link IE

field network.

1700H Communication error

between Windows and

VxWorks operating

system

The data received from VxWorks part is incorrect. Please restart the MELIPC running this product.

Please close the unnecessary VxWorks applications

and lower the load on the VxWorks part.

Please close the unnecessary Windows applications

and lower the load on the Windows part.

Please reinstall this product.

1701H Number of Data

Collector configurations

is exceeded

The number of Data Collector configurations using

VxWorks part has exceeded its maximum number.

Please review the number of Data Collector

configurations using VxWorks part.

1702H System error An unexpected error caused by common functions of

the MELIPC occurred inside this product.

If Real-time Flow Manager is used, please write the

Real-time Flow Manager parameter again.

Please restart the MELIPC running this product.

Please reinstall this product.

Please consult your local Mitsubishi representative if

the same error occurs again.

1703H Data Collector (Windows

part) stop error

Data Collector (Windows part) is stopped. Please restart the MELIPC running this product.

Please close the unnecessary Windows applications

and lower the load on the Windows part.

Please reinstall this product.

1705H Resource contention

error

Resource contention has occurred between this product

and other applications.

Please restart the MELIPC running this product.

Please close the unnecessary Windows applications

and lower the load on the Windows part.

Please reinstall this product.

30 6 TROUBLESHOOTING 6.3 Error Code List

1706H Insufficient memory error There is not enough memory available to common

functions of the MELIPC.

If Real-time Flow Manager is used, please write the

Real-time Flow Manager parameter again.

Please restart the MELIPC running this product.

Please close the unnecessary VxWorks applications

and lower the load on the VxWorks part.

Please close the unnecessary Windows applications

and lower the load on the Windows part.

Please review the collection cycle, number of collected

data, and processing contents to lower the load.

Please reinstall this product.

1707H*1 Data buffer overflow Data buffering has overflowed. Data cannot be

transmitted fast enough from the VxWorks part to

Windows part.

Please restart the MELIPC running this product.

Please close the unnecessary Windows applications

and lower the load on the Windows part.

Please review the collection cycle, number of collected

data, and processing contents to lower the load.

170AH Data Collector (VxWorks

part) stop error

Data Collector (VxWorks part) is stopped. Please restart the MELIPC running this product.

Please close the unnecessary VxWorks applications

and lower the load on the VxWorks part.

Please close the unnecessary Windows applications

and lower the load on the Windows part.

Please reinstall this product.

170BH Communication error

between Windows and

VxWorks operating

system

The data received from Windows part is incorrect. Please restart the MELIPC running this product.

Please close the unnecessary Windows applications

and lower the load on the Windows part.

Please reinstall this product.

170CH*1 Data buffer overflow Data buffering has overflowed. Data cannot be

transmitted fast enough from Windows part to the

VxWorks part.

Please restart the MELIPC running this product.

Please close the unnecessary VxWorks applications

and lower the load on the VxWorks part.

Please close the unnecessary Windows applications

and lower the load on the Windows part.

Please review the collection cycle, number of collected

data, and processing contents to lower the load.

170DH VxWorks part file access

error

The /ROM/MELAPP folder of the VxWorks part cannot be

accessed.

Please check if the /ROM/MELAPP folder is

accessible.

Please set the user access level of MELIPC to

Administrators.

Please restart the MELIPC running this product.

Please reset the virtual Ethernet to the factory settings.

170EH VxWorks part FTP

access error

The FTP server of the VxWorks part cannot be accessed. Please set the FTP server setting of the VxWorks part

to use.

Please set the user name or the password correctly in

the communication parameter.

If it is locked out, please re-execute after the lockout

time.

Please set the user access level of MELIPC to

Administrators.

Please restart the MELIPC running this product.

Please reset the virtual Ethernet to the factory settings.

170FH VxWorks part file access

error

The /ROM/MELAPP/DATACOLLECTOR folder of the

VxWorks part cannot be accessed.

Please check if the /ROM/MELAPP/

DATACOLLECTOR folder is accessible.

Please set the user access level of MELIPC to

Administrators.

Please restart the MELIPC running this product.

Please reset the virtual Ethernet to the factory settings.

1710H VxWorks part file access

error

A file transfer to the VxWorks part failed. Please set the user name or the password correctly in

the communication parameter.

Please set the user access level of MELIPC to

Administrators.

Please restart the MELIPC running this product.

Please reset the virtual Ethernet to the factory settings.

Please reinstall this product.

1711H Environment variable

reference error

Reference to the environment variable failed. Please restart the MELIPC running this product.

Please reinstall this product.

1712H VxWorks part Telnet

access error

The Telnet server of the VxWorks part cannot be

accessed.

Please disconnect the client connected to the Telnet

server of the VxWorks part.

Please restart the MELIPC running this product.

Please reset the virtual Ethernet to the factory settings.

Error code

Error name Error description Corrective action

6 TROUBLESHOOTING 6.3 Error Code List 31

6

1713H VxWorks part Telnet

access error

The Telnet server of the VxWorks part cannot be

accessed.

Please set the Telnet server setting of the VxWorks

part to use.

Please restart the MELIPC running this product.

Please reset the virtual Ethernet to the factory settings.

1715H VxWorks part Telnet

access error

The Telnet server of the VxWorks part cannot be

accessed.

Please set the user name or the password correctly in

the communication parameter.

Please restart the MELIPC running this product.

Please reset the virtual Ethernet to the factory settings.

1716H VxWorks part file access

error

The /ROM folder of the VxWorks part cannot be

accessed.

Please check if the /ROM folder exists.

Please set the user access level of MELIPC to

Administrators.

Please restart the MELIPC running this product.

Please reset the virtual Ethernet to the factory settings.

1717H Communication error

between Windows and

VxWorks operating

system

Communication between Windows and VxWorks

operating system failed.

If Real-time Flow Manager is used, please write the

Real-time Flow Manager parameter again.

Please restart the MELIPC running this product.

Please close the unnecessary VxWorks applications

and lower the load on the VxWorks part.

Please close the unnecessary Windows applications

and lower the load on the Windows part.

Please review the collection cycle, number of collected

data, and processing contents to lower the load.

Please reinstall this product.

Please consult your local Mitsubishi representative if

the same error occurs again.

F001H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F002H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F003H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F004H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F005H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F006H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F007H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F008H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F009H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F00AH Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

Error code

Error name Error description Corrective action

32 6 TROUBLESHOOTING 6.3 Error Code List

F00BH Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F00CH Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F00DH Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F00EH Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F00FH Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Carry out review to lower the load caused by collection

cycle, number of collections, and contents of

processing.

Lower the load on Windows by closing other

applications or by other means.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F010H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F011H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F012H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F013H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F100H Error in the initialization

process of Data

Collector

An error occurred in the initialization process. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F104H Error in the initialization

process of Data

Collector

An error occurred in the initialization process. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F105H Error in the initialization

process of Data

Collector

An error occurred in the initialization process. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F106H Error in the collection

process of Data

Collector

An error occurred in the collection process. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F107H Error in the read process

of Data Collector

An error occurred in the read process. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F108H Error in the write process

of Data Collector

An error occurred in the write process. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

Error code

Error name Error description Corrective action

6 TROUBLESHOOTING 6.3 Error Code List 33

6

F109H Error in the read process

of Data Collector

An error occurred in the read process. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F10AH Error in the write process

of Data Collector

An error occurred in the write process. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F200H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F205H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F207H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F20AH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F20BH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F20CH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F20DH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F20EH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F20FH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F212H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F217H Error in module

reference

An error occurred when the module (JSON parser) was

referenced.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F218H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F219H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F21AH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

Error code

Error name Error description Corrective action

34 6 TROUBLESHOOTING 6.3 Error Code List

F21BH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F21CH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F21EH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F221H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F223H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F227H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F228H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F229H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F22AH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F22BH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F22DH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F22FH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F232H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F233H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F234H Data Collector I/F error An error occurred during the access to Edgecross Basic

Software.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F240H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

Error code

Error name Error description Corrective action

6 TROUBLESHOOTING 6.3 Error Code List 35

6

F242H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F244H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F245H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F247H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F248H Data reference error in

Data Collector

An error occurred when the argument of the

communication parameter acquisition was referenced.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F249H Data reference error in

Data Collector

An error occurred when the argument of the collection

parameter acquisition was referenced.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F24AH Data reference error in

Data Collector

An error occurred when the argument of the data

parameter acquisition was referenced.

Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F24CH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F24DH Process data buffer

overflow in Data

Collector

Data buffering has overflowed. Carry out review to lower the load caused by collection

cycle, number of collections, and contents of

processing.

Lower the load on Windows by closing other

applications or by other means.

F24EH Process data buffer

overflow in Data

Collector

Data buffering has overflowed. Carry out review to lower the load caused by collection

cycle, number of collections, and contents of

processing.

Lower the load on Windows by closing other

applications or by other means.

F260H Error: Character is out of

range

The character string acquired from the Data Collector

contains characters out of range.

Please do not set characters out of range to collected

STRING type character string.

F261H Error: Character is out of

range

The character string acquired from the Data Collector

contains characters out of range.

Please do not set characters out of range to read

STRING type character string.

F262H Error: Number of

characters exceeded

It exceeds the maximum number of character string

acquired from the Data Collector.

Please review the location parameter so that the

number of characters in the collected STRING type

character string does not exceed the maximum

number.

Please review the target device value so that the

number of characters in the collected STRING type

character STRING does not exceed the maximum

number.

F263H Error: Number of

characters exceeded

It exceeds the maximum number of character string

acquired from the Data Collector.

Please review the location parameter so that the

number of characters in the read STRING type

character string does not exceed the maximum

number.

Please review the target device value so that the

number of characters in the read STRING type

character STRING does not exceed the maximum

number.

F264H Error: Character is out of

range

The character string acquired from the Data Collector

contains characters out of range.

Please do not set characters out of range to collected

WSTRING type character string.

Error code

Error name Error description Corrective action

36 6 TROUBLESHOOTING 6.3 Error Code List

F265H Error: Character is out of

range

The character string acquired from the Data Collector

contains characters out of range.

Please do not set characters out of range to read

WSTRING type character string.

F266H Error: Number of

characters exceeded

It exceeds the maximum number of character string

acquired from the Data Collector.

Please review the location parameter so that the

number of characters in the collected WSTRING type

character string does not exceed the maximum

number.

Please review the target device value so that the

number of characters in the collected WSTRING type

character STRING does not exceed the maximum

number.

F267H Error: Number of

characters exceeded

It exceeds the maximum number of character string

acquired from the Data Collector.

Please review the location parameter so that the

number of characters in the read WSTRING type

character string does not exceed the maximum

number.

Please review the target device value so that the

number of characters in the read WSTRING type

character STRING does not exceed the maximum

number.

F268H Invalid real number data The real number acquired from the Data Collector is

invalid(NaN, ).

Please do not set invalid value(NaN, ) to read REAL

type real number.

F269H Invalid real number data The real number acquired from the Data Collector is

invalid(NaN, ).

Please do not set invalid value(NaN, ) to read LREAL

type real number.

F280H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F281H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F282H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F283H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F284H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F2C5H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F2C6H Process data buffer

overflow in Data

Collector

Data buffering has overflowed. Carry out review to lower the load caused by collection

cycle, number of collections, and contents of

processing.

Lower the load on Windows by closing other

applications or by other means.

F300H Error: Not enough

memory

There is not enough memory available to execute this

operation.

Please close other applications.

Please restart the Industrial PC.

F303H Error: Not enough

memory

There is not enough memory available to execute this

operation.

Please close other applications.

Please restart the Industrial PC.

F306H Error: Not enough

memory

There is not enough memory available to execute this

operation.

Please close other applications.

Please restart the Industrial PC.

F30EH Error: Not enough

memory

There is not enough memory available to execute this

operation.

Please close other applications.

Please restart the Industrial PC.

F380H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

Error code

Error name Error description Corrective action

6 TROUBLESHOOTING 6.3 Error Code List 37

6

*1 For details on the number of points, refer to the following: Page 42 Number of points for data assignment

F382H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F383H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F386H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F387H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F388H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F389H Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F38AH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F38BH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F38DH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

F38FH Data Collector internal

error

An unexpected error occurred inside this product. Please restart the Industrial PC.

Please reinstall Data Collector.

Please consult your local Mitsubishi representative if

the same error occurs again.

Error code

Error name Error description Corrective action

38 6 TROUBLESHOOTING 6.4 Event Code List

6.4 Event Code List This section shows the codes for events that occur in CC-Link IE Field Network Data Collector.

Event code

Event status Event name Event description

8000H Warning Exceeded collection

cycle

Collection process was not completed within the collection cycle.

Page 26 Data missing has occurred in collected data.

8001H Information Collection processing

time

Measurement of collection processing time has been completed.

8002H Information Read processing time Measurement of Read processing time has been completed.

F800H Warning Exceeded collection

cycle

Collection process was not completed within the collection cycle.

Page 26 Data missing has occurred in collected data.

APPX Appendix 1 Processing Performance and Processing Time 39

A

APPENDIX Appendix 1 Processing Performance and Processing

Time This section shows the processing performance and processing time in data collection by cyclic transmission of CC-Link IE

Field Network Data Collector.

The processing performance refers the performance that can be collected all data at the set collection cycle.

The processing performance is the same regardless of the station type (master station or local station).

The processing performance is the same regardless of the cyclic transmission mode (normal mode or high

speed mode).

Processing performance in data collection

Measurement conditions

Parameters of Real-time Flow Manager

Parameters of a data collector The following table shows the setting values of parameters affecting to the processing performance among the parameters of

a data collector used for measurement.

Parameters of MI5122-VW

Parameter type Setting item Setting content

File saving setting File format CSV file

Output data All collected data

Output name of the date/time column TIME

Data row output format YYYY/MM/DD hh:mm:ss.sss

Save destination folder Local path

File name prefix LOG

Number of record rows for switching 1000

Maximum number of files to be saved 100

Parameter type Setting item Setting content

Collection parameter Cycle system Specify Cycle

Collection interval 100 (ms)

Parameter type Setting item Setting content

CC-Link IE Field Network parameter Required setting Station type Local station

40 APPX Appendix 1 Processing Performance and Processing Time

Processing performance The following table shows the processing performance capable of collecting all data in a specified cycle per collection

processing time (single collection cycle).

Precautions

Processing of CC-Link IE Field Network Data Collector may be delayed if interrupted by processing of other software or an

operating system of Windows.

Number of word device collection points Performance value [ms]

16 0.111

32 0.121

64 0.132

128 0.138

256 0.147

512 0.165

1024 0.188

2048 0.220

APPX Appendix 1 Processing Performance and Processing Time 41

A

Processing performance in read processing

Measurement conditions

Parameters of Real-time Flow Manager

Parameters of MI5122-VW

Processing performance The following table shows the read processing performance of CC-Link IE Field Network Data Collector.

Setting item Setting content

Current Value Update Interval 1 second

Access target device Initial Access Delay Time 0

Registration target for data tag resource monitoring Device setting according to the number of word device read points (all INT

type)

Parameter item Setting item Setting content

CC-Link IE Field Network parameter Required item Station type Local station

Number of word device read points Performance value

256 63

512 78

1024 188

2560 390

5120 766

42 APPX Appendix 2 Data Assignment

Appendix 2 Data Assignment This section shows the assignment availability and the number of points for data assignment.

Data assignment availability The following table shows the assignment availability of data for each data type.

: Available, : Not available

Number of points for data assignment The following table shows the number of points for data assignment for each data type.

Number: Fixed number of points for data assignment, : calculation formula, Not available

*1 Round up digits after a decimal points of a value obtained by division.

Setting value Data type

BOOL UINT UDINT ULINT INT DINT LINT REAL LREA L

STRING WSTRING

Bit device

Word device

Setting value Data type

1 bit 16 bit 32 bit 64 bit Character string

BOOL UINT INT UDINT DINT REAL ULINT LINT LREA L

STRING WSTRING

Bit device 1

Word device 1 1 2 2 2 4 4 4 (Number of

characters

2)*1

((Number

of characters

4) 2)*1

APPX Appendix 3 Buffer Memory 43

A

Appendix 3 Buffer Memory This section shows the buffer memory of CC-Link IE Field Network Data Collector.

Buffer memory list This section shows the list of the buffer memory of CC-Link IE Field Network Data Collector.

*1 Initialized to '0'.

Address in decimal (hexadecimal)

Purpose Name Initialization timing*1 Reading or writing

90000

(15F90H)

Task status Task priority When the power of a MELIPC is turned OFF

and ON

Reading

90001

(15F91H)

Free-run counter for task operation

check

When the power of a MELIPC is turned OFF

and ON

Reading

90002 to 90063

(15F92H to 15FCFH)

System area

90064

(15FD0H)

Task operation status Periodic monitoring task priority When the power of a MELIPC is turned OFF

and ON

Reading

90065

(15FD1H)

Free-run counter for periodic

monitoring task operation check

When the power of a MELIPC is turned OFF

and ON

Reading

90066

(15FD2H)

Cyclic access task priority When the power of a MELIPC is turned OFF

and ON

Reading

90067

(15FD3H)

Free-run counter for cyclic access

task operation check

When the power of a MELIPC is turned OFF

and ON

Reading

90068 to 90071

(15FD4H to 15FD7H)

System area

90072 to 90073

(15FD8H to 15FD9H)

Processing time Maximum When the power of a MELIPC is turned OFF

and ON

Reading

90074 to 90075

(15FDAH to 15FDBH)

Minimum When the power of a MELIPC is turned OFF

and ON

Reading

90076 to 90077

(15FDCH to 15FDDH)

Latest When the power of a MELIPC is turned OFF

and ON

Reading

90078

(15FDEH)

Number of times of the

unperformed interrupt

processing

Number of times of the unperformed

interrupt processing

When the power of a MELIPC is turned OFF

and ON

Reading

90079 to 91023

(15FDFH to 1638FH)

System area

44 APPX Appendix 3 Buffer Memory

Buffer memory details The following shows the details of the buffer memory of CC-Link IE Field Network Data Collector.

Task status (90000 to 90001)

Task operation status (90064 to 90067)

Processing time (90072 to 90077)

Number of times of the unperformed interrupt processing (90078)

Address Name Description

90000 Task priority 0 to 255

0: No task is started.

90001 Free-run counter for task operation

check

0 to 65535

When it reaches the upper limit of a numerical value, it is counted from '0' again.

Address Name Description

90064 Periodic monitoring task priority 0 to 255

0: No task is started.

90065 Free-run counter for periodic

monitoring task operation check

0 to 65535

When it reaches the upper limit of a numerical value, it is counted from '0' again.

90066 Cyclic access task priority 0 to 255

0: No task is started.

90067 Free-run counter for cyclic access

task operation check

0 to 65535

When it reaches the upper limit of a numerical value, it is counted from '0' again.

Address Name Description

90072 to 90073 Maximum The maximum processing time is stored (in microseconds, 32 bit).

90074 to 90075 Minimum The minimum processing time is stored (in microseconds, 32 bit).

90076 to 90077 Latest The latest processing time is stored (in microseconds, 32 bit).

Address Name Description

90078 Number of times of the unperformed

interrupt processing

0 to 65535

The number of times of the interrupt processing which is not performed due to high-load is

incremented to the upper limit.

If CC-Link IE Field Network Data Collector is restarted, the number is incremented from '0'

again.

APPX Appendix 4 Software Licenses 45

A

Appendix 4 Software Licenses This software consists of multiple software components. Each of them is copyrighted by Mitsubishi and/or third parties.

The following types of software are contained:

Software copyrighted by third parties and distributed as free software

Source codes are not distributed for the software that Mitsubishi and/or third parties have copyrights to.

Please refrain from inquiring about the source codes of this open source.

Software information This product contains the following software:

RapidJSON (Page 45 RapidJSON)

msinttypes (Page 46 msinttypes)

RapidJSON This product uses RapidJSON licensed under the MIT License.

The copyright and permission notices of RapidJSON are described below. Tencent is pleased to support the open source community by making RapidJSON available.

Copyright (C) 2015 THL A29 Limited, a Tencent company, and Milo Yip. All rights reserved.

If you have downloaded a copy of the RapidJSON binary from Tencent, please note that the RapidJSON binary is licensed under the MIT License.

If you have downloaded a copy of the RapidJSON source code from Tencent, please note that RapidJSON source code is licensed under the MIT License,

except for the third-party components listed below which are subject to different license terms. Your integration of RapidJSON into your own projects may

require compliance with the MIT License, as well as the other licenses applicable to the third-party components included within RapidJSON. To avoid the

problematic JSON license in your own projects, it's sufficient to exclude the bin/jsonchecker/ directory, as it's the only code under the JSON license.

A copy of the MIT License is included in this file.

Permission is hereby granted, free of charge, to any person obtaining a copy of this software and associated documentation files (the "Software"), to deal in the

Software without restriction, including without limitation the rights to use, copy, modify, merge, publish, distribute, sublicense, and/or sell copies of the Software,

and to permit persons to whom the Software is furnished to do so, subject to the following conditions:

The above copyright notice and this permission notice shall be included in all copies or substantial portions of the Software.

THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE

WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT. IN NO EVENT SHALL THE AUTHORS OR

COPYRIGHT HOLDERS BE LIABLE FOR ANY CLAIM, DAMAGES OR OTHER LIABILITY, WHETHER IN AN ACTION OF CONTRACT, TORT OR

OTHERWISE, ARISING FROM, OUT OF OR IN CONNECTION WITH THE SOFTWARE OR THE USE OR OTHER DEALINGS IN THE SOFTWARE.

46 APPX Appendix 4 Software Licenses

msinttypes This product uses msinttypes licensed under the BSD License.

The copyright and permission notices of msinttypes are described below. The msinttypes r29

Copyright (c) 2006-2013 Alexander Chemeris

All rights reserved.

Redistribution and use in source and binary forms, with or without

modification, are permitted provided that the following conditions are met:

* Redistributions of source code must retain the above copyright notice, this list of conditions and the following disclaimer.

* Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the following disclaimer in the documentation and/or other

materials provided with the distribution.

* Neither the name of copyright holder nor the names of its contributors may be used to endorse or promote products derived from this software without specific

prior written permission.

THIS SOFTWARE IS PROVIDED BY THE REGENTS AND CONTRIBUTORS ``AS IS'' AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT

NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT

SHALL THE REGENTS AND CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL

DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR

BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT

(INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY

OF SUCH DAMAGE.

APPX Appendix 5 Supported Edgecross Basic Software Version 47

A

Appendix 5 Supported Edgecross Basic Software Version

The following table shows the version of Edgecross Basic Software supported by CC-Link IE Field Network Data Collector.

*1 It can be checked in the screen displayed by selecting [Windows System] [Control Panel] [Programs] [Programs and Features] from Windows Start.

*2 The version 1.03D is recommended when using this product in Management Shell. *3 For the checking method, refer to the following:

Edgecross Basic Software for Windows User's Manual

CC-Link IE Field Network Data Collector version*1,*2

Data collector Version*3 Data collector specifications version*3

Supporting Edgecross Basic Software version*3

1.00A 1 1.00 1.00 or later

1.01B 2

1.02C 3

1.03D 4

48 APPX Appendix 6 Added and Changed Functions

Appendix 6 Added and Changed Functions This section shows the added and changed function of CC-Link IE Field Network Data Collector.

Added/changed contents Version Reference

Management Shell added in Edgecross Basic Software

Ver.1.10 is supported.

1.02C

49

I

INDEX

A

Accessible device (location) . . . . . . . . . . . . . . . . 12

C

Collection at a time interval . . . . . . . . . . . . . . . . 15 Collection for each link scan. . . . . . . . . . . . . . . . 15 Collection parameter . . . . . . . . . . . . . . . . . . . . . 24 Communication parameter . . . . . . . . . . . . . . . . . 23

D

Data collection function . . . . . . . . . . . . . . . . . . . 15 Data Reading Function . . . . . . . . . . . . . . . . . . . 21 Data writing function . . . . . . . . . . . . . . . . . . . . . 22

E

Error code list . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Event code list . . . . . . . . . . . . . . . . . . . . . . . . . 38

F

Functional specifications . . . . . . . . . . . . . . . . . . . 9

N

Number of points . . . . . . . . . . . . . . . . . . . . . . . 42

O

Operational specifications . . . . . . . . . . . . . . . . . 11

T

Troubleshooting by symptom . . . . . . . . . . . . . . . 26

50

MEMO

51

REVISIONS *The manual number is given on the bottom left of the back cover.

Japanese manual number: SH-081922-G

2018 MITSUBISHI ELECTRIC CORPORATION

Revision date *Manual number Description

May 2018 SH(NA)-081923ENG-A First edition

May 2018 SH(NA)-081923ENG-B Partial correction

September 2018 SH(NA)-081923ENG-C Added or modified parts

Section 6.2

March 2019 SH(NA)-081923ENG-D Added or modified parts

Chapter 1, Section 2.1, Section 4.1, Section 4.2, Section 4.4, Section 5.1, Section 5.2, Section 6.2,

Section 6.3, Section 6.4, Appendix 1, Appendix 3, Appendix 5, Appendix 6

June 2019 SH(NA)-081923ENG-E Partial correction

December 2019 SH(NA)-081923ENG-F Added or modified parts

Section 6.2

This manual confers no industrial property rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held

responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.

52

TRADEMARKS Microsoft and Windows are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or

other countries.

The company names, system names and product names mentioned in this manual are either registered trademarks or

trademarks of their respective companies.

In some cases, trademark symbols such as '' or '' are not specified in this manual.

SH(NA)-081923ENG-F(1912)

MODEL: SW1DNN-DCCCIEFM-U-E

Specifications subject to change without notice.

When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.

HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-K

Manualsnet FAQs

If you want to find out how the CC-Link IE Field Network Data Collector Mitsubishi Electric works, you can view and download the Mitsubishi Electric CC-Link IE Field Network Data Collector User's Manual on the Manualsnet website.

Yes, we have the User's Manual for Mitsubishi Electric CC-Link IE Field Network Data Collector as well as other Mitsubishi Electric manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The User's Manual should include all the details that are needed to use a Mitsubishi Electric CC-Link IE Field Network Data Collector. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Mitsubishi Electric CC-Link IE Field Network Data Collector User's Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Mitsubishi Electric CC-Link IE Field Network Data Collector User's Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Mitsubishi Electric CC-Link IE Field Network Data Collector User's Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Mitsubishi Electric CC-Link IE Field Network Data Collector User's Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Mitsubishi Electric CC-Link IE Field Network Data Collector User's Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.