Electronic Multi-Measuring Instrument

MODEL

ME96SSRA-MB User's Manual: Detailed Edition

Before operating the instrument, you should first read thoroughly

this operation manual for safe operation and optimized performance of the product. Deliver this user's manual to the end user.

1

Check on your delivery

Check the following point as soon as you receive Mitsubishi Electronic Multi-Measuring Instrument

Parts name Quantity Specifications

Users Manual

(Simplified)

1

A3 size

Attachment lug

(with screw)

2

About the optional plug-in module sold separately

This product has the following optional plug-in module. It is possible to correspond to various I/O by installing the optional plug-in module. We hope that you will order to us.

Type name of

optional plug-in module

I/O specifications

Analog

output

Pulse/Alarm

output

Digital

input

Digital

output Communication

Logging

function

ME-4210-SS96 4 circuits 2 points 1 point

ME-0040C-SS96 4 points CC-Link

ME-0052-SS96 5 points 2 points

ME-0000MT-SS96 MODBUS

TCP

ME-0000BU-SS96 6 items

Note ME-4201-NS96, ME-0052-NS96 and ME-0040C-NS96 can not use in the ME96SSRA-MB. They can use for ME96NSR, ME96NSR-MB only.

I/O Parts Specifications Type name of

optional plug-in module

Analog output Output :4 to 20mA

Load resistance :600 or less ME-4210-SS96

Pulse/Alarm output No-voltage a contact

Contact Capacity :DC35V, 0.1A or less ME-4210-SS96

Digital input Contact Capacity :DC24V(DC19 to 30V),7mA or less

Input Pulse Width :30ms or more

ME-4210-SS96

ME-0040C-SS96

ME-0052-SS96

Digital output No-voltage a contact

Contact Capacity :DC35V, 0.2A or less ME-0052-SS96

In this manual, when the optional plug-in module is installed, it explains.

2

Features

This instrument measures the load status by inputting the secondary side of the VT and CT, and displays various

measurement values.

This instrument supports active energy: class 0.5S and harmonic measurement up to 19th.

This instrument enables measurement of integrated active energy divided into two time segments such as

peak/off-peak and day/night. (Periodic Active Energy)

This instrument enables measurement of the active energy in a block of any period (interval).( Rolling

Demand)

The password protection setting avoids undesired change of settings or deletion of measured data.

The instruments with transmission functions (MODBUSRTU communication, CC-Link communication,

MODBUS TCP communication) are able to transmit the measured data to superior monitoring devices.

(CC-Link communication: When the ME-0040C-SS96 optional plug-in module is installed)

(MODBUS TCP communication: When the ME-0000MT-SS96 optional plug-in module is installed)

Using the logging function, measurement data can be backup even when the MODBUSRTU

communication fails.

(Logging function: When the ME-0000BU-SS96 optional plug-in module is installed)

The instruments with analog/pulse output function are able to output key measurement factors (current,

voltage, active power, power-factor, and Active Energy) of the power receiving point alone and are optimum

for remote monitoring.(When the ME-4210-SS96 optional plug-in module is installed)

This instrument complies with the requirements of the CE marking, UL standards, KC mark, and FCC/IC.

MODBUS is a registered trademark of SCHNEIDER ELECTRIC USA, INC in the United States.

3

Table of Contents

Check on your delivery ............................................................................................................................................ 1

About the optional plug-in module sold separately .................................................................................................. 1

Features ................................................................................................................................................................... 2

Table of Contents ..................................................................................................................................................... 3

Safety Precaution .................................................................................................................................................... 5

EMC Directive Instruction ........................................................................................................................................ 9

Precautions for KC mark.......................................................................................................................................... 9

Instructions for Handling

1. Display and Button Functions of Each Parts .................................................................................................... 10

2. Function Modes ................................................................................................................................................ 15

3. Setting ............................................................................................................................................................... 16 3.1. Setting flow ............................................................................................................................................. 16 3.2. Setting Menu 1: Basic Settings (Setting the Phase Wire System, Display Pattern, VT/Direct

Voltage, CT Primary Current, etc.) ......................................................................................................... 22 3.3. Setting Menu 2: Communication Settings (Setting the MODBUSRTU communication) ...................... 26 3.4. Setting Menu 2: Communication Settings (Setting the CC-Link communication) .................................. 27 3.5. Setting Menu 2: Communication Settings (Setting the MODBUSTCP communication) ...................... 29 3.6. Setting Menu 3: Display Settings (Setting Maximum Scale, Active Energy Measurement, and

Harmonic Display, etc.) .......................................................................................................................... 31 3.7. Setting Menu 4: LCD Settings (Setting Model Display, Version Display, Backlight, and Display

Update Time) .......................................................................................................................................... 33 3.8. Setting Menu 5: Pulse and Alarm Settings (Setting Upper/Lower Limit Alarm, Motor Starting

Current Mask Function, Pulse Output, etc.) ........................................................................................... 34 3.9. Setting Menu 6: Setting the Analog Output ............................................................................................ 39 3.10. Setting Menu 6: Setting the Logging function ........................................................................................ 42 3.11. Setting Menu 7: Setting Periodic Active Energy, Rolling Demand, and Digital Input/Output ............ 44 3.12. Setting Menu 8:Special Settings (Setting Operation Time, Phase Display, IEC Mode) ......................... 46 3.13. Setting Menu CL: Present Time Settings for Data Logging ................................................................... 48 3.14. Setting Value Confirmation Menus 1-9: Confirming the Settings in the Setting Menus 1-8 and

Test Mode in Setting Menu 9 .................................................................................................................. 50 3.15. Initializing Related Items by Changing Settings ..................................................................................... 51 3.16. Initializing All Settings............................................................................................................................. 52 3.17. Setting the Special Display Pattern P00 ................................................................................................ 53 3.18. Examples of Simple Settings ................................................................................................................. 55

4. Using Test Mode ............................................................................................................................................... 57 4.1. Test Menu 1: Communication Test ......................................................................................................... 58 4.2. Test Menu 2: Alarm Output/Digital Output Operation Test ..................................................................... 59 4.3. Test Menu 3: Zero Span Adjustment for Analog Output ........................................................................ 60 4.4. Test Menu 4: Analog Output Operation Test .......................................................................................... 61 4.5. Test Menu 5: Pulse Output Operation Test ............................................................................................ 62

5. Operation .......................................................................................................................................................... 63 5.1. Basic Operation ...................................................................................................................................... 63 Switch display ......................................................................................................................................... 63 Switch phase .......................................................................................................................................... 63 Bar graph display ................................................................................................................................... 64 Switching measurement factors displayed on bar graphs ..................................................................... 64 Cyclic Display ......................................................................................................................................... 65 Harmonics display .................................................................................................................................. 65 Maximum value and minimum value display ......................................................................................... 67 Display of maximum value and minimum value ..................................................................................... 67 Clear the maximum/minimum value ....................................................................................................... 67 Active Energy / Reactive Energy / Apparent Energy Display ................................................................. 68 How to change the unit of Wh, varh and VAh ........................................................................................ 68 Wh, varh and VAh zero reset ................................................................................................................. 68 Reactive energy counting method (2 quadrant counting / 4 quadrant counting) ................................... 69 Each measurement item display during power transmission ................................................................. 69 Demand time and demand value of current demand ............................................................................. 70

4

Table of Contents

5.2. Usage According to Purpose (Alarm, Periodic Active Energy, Rolling Demand, Operating Time,

Password, etc.) ....................................................................................................................................... 71 Display and operation of the upper/lower limit alarm ............................................................................. 71 Canceling the upper/lower limit alarm .................................................................................................... 72 Stopping backlight flickering caused by upper/lower limit alarm generation.......................................... 72 Upper/lower limit alarm items on the alarm contacts ............................................................................. 72 Display of periodic active energy ........................................................................................................... 72 Resetting periodic active energy to zero ................................................................................................ 72 Display and calculation of rolling demand .............................................................................................. 73 Adjusting rolling demand time ................................................................................................................ 74 Resetting the peak value of rolling demand ........................................................................................... 74 Display of operation time ........................................................................................................................ 74 Resetting the operation time to zero ...................................................................................................... 74 Display and operation of digital input/output status ............................................................................... 75 Releasing the digital input latch ............................................................................................................. 75 Preventing maximum value update by motor starting current ............................................................... 75 Password protection setting ................................................................................................................... 76

6. Other ................................................................................................................................................................. 77 6.1. Display Pattern Contents ....................................................................................................................... 77 6.2. Maximum Scale Value............................................................................................................................ 79 6.3. Possible Setting Range for Maximum Scale .......................................................................................... 80 6.4. Measurement Items and Correspondence between Display and Output .............................................. 83 6.5. Measurement Characteristic .................................................................................................................. 84 6.6. Troubleshooting ...................................................................................................................................... 85

Installation

Installation 1. Dimensions ...................................................................................................................................... 87

Installation 2. Mounting .......................................................................................................................................... 89

Installation 3. Wiring .............................................................................................................................................. 90

Installation 4. Wiring Diagram ................................................................................................................................ 92

Installation 5. How to insert and eject the SD memory card (ME-0000BU-SS96) .............................................. 100

Specifications

Specifications ....................................................................................................................................................... 101 1. Specification ............................................................................................................................................... 101 2. Applicable Standards .................................................................................................................................. 102 3. Specifications of MODBUS RTU Communication ..................................................................................... 102 4. Specifications of CC-Link Communication ................................................................................................. 102 5. Specifications of MODBUS TCP Communication ..................................................................................... 103 6. Specifications of Logging ............................................................................................................................ 103 7. Setting Table (Factory Settings and Customer Setting Note) ..................................................................... 104

Appendix .............................................................................................................................................................. 106

1. Calculation methods of ME96SS (for 3 phase unbalanced system with neutral) ...................................... 106 2. Optional part (Available part) ...................................................................................................................... 107

5

Safety Precaution

(Always read these instructions before using this equipment)

For personnel and product safety please read the contents of these operating instructions carefully before using.

Make sure that the end users read this manual and then keep the manual in a safe place for future reference.

Make sure to deliver this manual to the end-user.

If you are considering using this instrument for special purpose such as nuclear power plants, aerospace,

medical care or passenger vehicles please refer to our sales representative.

HAZARD SYMBOLS Read these instructions carefully and look at the equipment to become familiar with the device before trying

to install, operate, service or maintain it. Terminal of control power (MA, MB) and voltage inputs (P1, P2, P3,

PN) have hazards of electric shock, explosion, or arc flash. Turn off power supplying this device and the

equipment in which it is installed before working on it.

CAUTION

The above Indicates that incorrect handling may cause hazardous conditions. Always follow the instructions

because they are important to personal safety. Otherwise, it could result in electric shock, fire, erroneous

operation, and damage of the instrument. If the equipment is used in a manner not specified by the

manufacturer, the protection provided by the equipment may be impaired.

Normal service conditions

Use the instrument in an environment that meets the Normal service conditions as following points:

Ambient temperature: -5 to +55C

Average day temperature: 35C or less

Humidity: 0 to 85%RH, non condensing.

Altitude: 2000m or less

Pollution Degree: 2 or less (Note 1)

Atmosphere without corrosive gas, dust, salt, oil mist.

Indoor use

Transient over voltage: 4000V or less (Note 1)

A place without excessive shocks or vibration.

Do not expose to rain and water drips.

Do not expose to direct sunlight.

An area in where no pieces of metal and an inductive substance disperse.

Do not expose to strong electromagnetic field and ambient noises.

Note 1For the definition of the Pollution Degree and the Transient over voltage category, refer to

EN61010-1:2010.

Installation instructions

Make sure to read this manual carefully before Installation and Wiring.

CAUTION

This instrument should be installed and used by a qualified electrician.

The instrument must not be powered and used until its definitive assembly on the

cabinets door.

The instrument is to be mounted on a panel. All connections must be kept inside the

cabinet.

Verify the following points:

Auxiliary power supply and measuring ratings.

Auxiliary power

supply

AC100-240V(15%) 50-60Hz 8VA

DC100-240V(-30% 15%) 5W MA,MB terminals

Ratings

Voltage

3-PHASE 4-WIREmax AC277/480V

3-PHASE 3-WIRE(DELTA)max AC220V,

(STAR)max AC440V

1-PHASE 3-WIREmax AC220/440V

1-PHASE 2-WIRE(DELTA)max AC220V,

(STAR)max AC440V

Category P1,P2,P3,PN terminals

Current 5A(via current transformer),maxAC30V Category +C1,C1,+C2,C2,+C3,C3

terminals

Frequency 50-60Hz

Provide the basic insulation externally at the current input terminals.

Voltage-measuring and current-measuring circuit terminals should be permanently

connected.

6

Safety Precaution

CAUTION

Others MODBUSRTU communication

T/R+,T/R-,SG,Ter terminals

maxDC35V

MODBUSTCP communication

Ethernet terninals

CC-Link communication

DA,DB,DG terminals

Digital input DI1,DI2,DI3,DI4,DI COM,DI+,DI-, DI1+,DI1-,DI2+,DI2-,DI3+,DI3-,DI4+,DI4-,DI5+,DI5- terminals

Digital output DO1+,DO1-,DO2+,DO2- terminals

Analog output CH1+,CH1-,CH2+,CH2-,CH3+,CH3-,CH4+,CH4- terminals

Pulse/ Alarm output C1A/A1,C1B/COM1,C2A/A2,C2B/COM2 terminals

Do not drop this instrument from high place. If you drop it and the display is cracked,

do not touch the liquid crystal or get it in your mouth. If the liquid crystal is touched,

wash it away at once.

Work under the electric outage condition when installing and wiring. It may cause

electric shock, electric burn injury or damage of the device.

When tapping or wiring, take care not to entering any foreign objects such as chips

and wire pieces into this instrument.

If the terminal wiring is pulled with a strong force, the terminals may detach. (Tensile

load: 39.2N or less)

When wiring in this instrument, be sure that it is done correctly by checking the

instruments wiring diagram. Wrong wiring may cause failure of the instrument, a fire

or electric shock.

Use electrical wire sizes compatible with the rated current. Use of unsuitable sizes

may cause heat generation, which may lead to a fire.

Tighten the terminal screws with the specified torque and use the suitable pressure

connectors and suitable wire size. (Refer to page 90)

In order to prevent invasion of noise, do not bunch the control wires or communication

cables with the main circuit or power wire, or install them close to each other. The

distance between communicational signal lines, input signal lines and power lines, and

high voltage lines when running parallel to each other are shown below.

Conditions Length

Below 600V, or 600A power lines 30cm or more

Other power lines 60cm or more

Protective conductor terminals for mains circuits shall be at least equivalent in

current-carrying capacity to the mains supply terminals.

If the protective conductor terminals are also used for other bonding purposes, the

protective conductor shall be applied first and secured independently of other

connections.

Matters concerning the precaution before use

Use the instrument in the specified usage environment and conditions.

The setting of this instrument is necessary before use it. Please read this manual carefully to ensure

correct setting.

Confirm the rating of this instrument, and supply power voltage within the specified range.

7

Safety Precaution

Operation instructions

Before operating the product, check that active bare wire and so on does not exist around the product. If

any bare wire exists, stop the operation immediately, and take an appropriate action such as isolation

protection.

In the event of a power outage during the setting, the instrument is not set correctly. Please set again

after power recovery.

CAUTION

Do not disassemble or modify this instrument. It may cause failure, malfunction, injury or

fire.

Use this instrument within the ratings specified in this manual. If it is used outside the

ratings, it may cause not only malfunction or failure but also fire burnout.

Do not open the secondary side of the CT circuit. If the CT is not connected properly or if

the secondary side of the CT is open, it may result in high voltage on the secondary side

of the CT, the insulation of the secondary winding wire may be damaged, and burnout

may be caused.

When the external terminals are connected to the external equipment, the instrument and

the external equipment must not be powered and used until its definitive assembly on the

cabinets door.

The rating of the terminal of the external equipment should satisfy the rating of the

external terminal of this instrument.

Maintenance instructions

Wipe dirt off the surface with a soft dry cloth.

Do not contact a chemical dust cloth to the instrument for a long time, or do not wipe it with benzene,

thinner, alcohol.

Check for the following items to use this instrument properly for long time.

(1)Daily maintenance

No damage on this instrument

No abnormality with LCD indicators

No abnormal noise, smell or heat

(2)Periodical maintenance (Once every 6 months to 1 year)

No looseness with installation and wire connection

CAUTION Do periodical maintenance under the electric outage condition. Failure to do so may cause electric

shock, failure of the instrument or a fire. Tighten the terminal regularly to prevent a fire.

Storage conditions

To store this instrument, turn off the power and remove wires, and put it in a plastic bag.

For long-time storage, store at the following places. Failure to follow the instruction may cause a failure

and reduced life of the instrument.

Ambient temperature the: -25 to +75C

average day temperature: 35C or less

Humidity range 0 to 85%RH, non-condensing.

Atmosphere without corrosive gas, dust, salt, oil mist.

A place without excessive shocks or vibration.

Do not expose to rain and water drips.

Do not expose to direct sunlight.

An area in where no pieces of metal and an inductive substance disperse.

8

Safety Precaution

Guarantee

Gratis warranty is effective until the earlier of 1 year after the date of your purchase or 18 months after

manufacturing.

The gratis warranty shall apply if the product fails even though it is being used properly in the

conditions, with the methods and under the environments in accordance with the terms and

precautions described in the catalogs, the instruction manual, caution label on the product, etc.

Repair shall be charged for the following cases even during the gratis warranty period.

Failures occurring due to your improper storage or handling, carelessness or fault.

Failures due to faulty workmanship

Failures due to faults in use and undue modification

Failures due to accidental force such as a fire, abnormal voltage, etc. and force majeure

such as an earthquake, wind, flood, etc.

Failures due to matters unpredictable based on the level of science technology at the time of

product.

Our company shall not be liable to compensate for any loss arising from events not attributable to our

company, opportunity loss and lost earning of the customer due to failure of the product, and loss,

secondary loss, accident compensation, damage to other products besides our products and other

operations caused by a special reason regardless of our companys predictability

Replacement Cycle

Although it depends on the status of use, 10 years is the guideline for renewal.

Disposal

When disposing of this product, treat it as industrial waste.

A lithium battery is embedded in the optional plug-in module: ME-0000BU-SS96. Lithium batteries

are disposed of according to local regulation.

In EU member states, there is a separate collection system for waste batteries. Dispose of batteries

properly at the local community waste collection/recycling center.

The symbol shown below is printed on the packaging of ME-0000BU-SS96.

Note: This symbol is for EU member states only.

The symbol is specified in the new EU Battery Directive (2006/66/EC) Article 20 "Information for

end-users" and Annex II.

The symbol indicates that batteries need to be disposed of separately from other wastes.

CAUTION

A lithium battery is embedded in the optional plug-in module: ME-0000BU-SS96.

Therefore, if it will be thrown in fire, evolution of heat, burst or ignition may occur. Lithium

batteries are disposed of according to local regulation.

About packaging materials and this manual

For reduction of environment load, packaging materials are produced with cardboard, and this manual

is printed on recycled paper.

9

EMC Directive Instruction

This section summarizes the precautions on conformance to the EMC Directive of the cabinet constructed

using this instrument.

However, the method of conformance to the EMC Directive and the judgment on whether or not the cabinet

conforms to the EMC Directive has to be determined finally by the manufacturer.

This instrument complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)

This instrument may not cause harmful interference, and (2) this instrument must accept any interference

received, including interference that may cause undesired operation.

1EMC Standards

EN 61326-1

EN 61000-3-2

EN 61000-3-3

2Installation (EMC directive)

The instrument is to be mounted on panel of a cabinet.

Therefore, the construction of a cabinet is important not only for safety but also for EMC.

The instrument is examined by the following conditions.

Conductive cabinet is used.

Six faces of a cabinet have to be ensured conductivity for each other.

A cabinet has to be connected to earth by a thick wire of low impedance.

Holes on faces of cabinet have to be 10 cm or less in diameter.

The terminals for protective earth and functional earth have to be connected to earth by a thick wire of

low impedance. (A terminal for protective earth is important not only for safety but also for EMC.)

All connections must be kept inside the cabinet.

Wirings outside the cabinet have to be used with the shielded cable.

The following diagram shows how to provide good contact of the shielded cable.

Remove part of the outer cover.

Remove part of the paint musk on the cabinet.

Connect those parts with the clamp.

Precautions for KC mark

Precautionary note written in Korean

Distributors and users must understand that this product meets the electromagnetic compatibility requirements and is designed for industrial use (Class A). Do not use the product in a residential area.

Applicant for KC mark : MITSUBISHI ELECTRIC AUTOMATION KOREA CO.,LTD

Manufacturer : MITSUBISHI ELECTRIC CORPORATION

Note 1: This is the notification for the KC mark (Korea Certification)

10

1. Display and Button Functions of Each Parts

Part names

Operation buttons (For details, refer to page 13.)

LCD with backlight

Current Input terminals +C1, C1: Input a circuit current. +C2, C2: Input a circuit current. +C3, C3: Input a circuit current.

MODBUS RTU communication terminal

T/R+: MODBUS RTU communication transmission terminal

T/R-: MODBUS RTU communication transmission terminal

SG: Signal Ground. Ter: Termination terminal

(120 termination when short-circuited to the terminal T/R-) SLD: Shielded wire terminal (Ground resistance 100 or less)

Optional cover By removing the optional cover, you can install each optional plug-in module in the main unit. See illustration of next page for the terminals name of the optional plug-in module.

Voltage Input terminals P1, P2, P3, PN: Input a circuit voltage.

Auxiliary power input terminals MA, MB: Connect to an auxiliary power. : Ground terminal (Ground resistance: 100 or less)

Terminal cover

Front view

Rear view (main unit)

11

1. Display and Button Functions of Each Parts

Part names

Rear view (Optional plug-in module: ME-4210-SS96, ME-0040C-SS96, ME-0052-SS96)

Side/Rear view (Optional plug-in module: ME-0000MT-SS96)

Side/Rear view (Optional plug-in module: ME-0000BU-SS96)

Input/ output terminals (ME-4210-SS96) CH1+, CH1-: Analog output terminal CH2+, CH2-: Analog output terminal CH3+, CH3-: Analog output terminal CH4+, CH4-: Analog output terminal C1A/A1, C1B/COM1: Pulse/ Alarm output C2A/A2, C2B/COM2: Pulse/ Alarm output DI+, DI-: Digital input terminal

Input/ output terminals (ME-0040C-SS96) DA: CC-Link communication terminal DB: CC-Link communication terminal DG: CC-Link communication terminal SLD: Shielded terminal FG: Ground terminal (Ground resistance 100 or less) DI1, DI2, DI3, DI4, DI COM: Digital input terminal

Input/ output terminals (ME-0052-SS96) DI1+, DI1-: Digital input terminal DI2+, DI2-: Digital input terminal DI3+, DI3-: Digital input terminal DI4+, DI4-: Digital input terminal DI5+, DI5-: Digital input terminal DO1+, DO1-: Digital output terminal DO2+, DO2-: Digital output terminal

10BASE-T/100BASE-TX connector (RJ45)

Indicator LEDs (Refer to page 14) ERR. (Red) 10/100 (Green) LINK/ACT (Green)

Indicator LEDs (Refer to page 14) LOG. (Red) SD C. (Red) BAT. (Red)

SD memory card slot

12

1. Display and Button Functions of Each Parts

Display

Note: The above display is an example for explanation.

No. Segment Name Description

1 LEAD status They show direction of Power Factor or Reactive Power on bar graph.

They show the type of counting of Reactive Energy on Reactive Energy Display. 2 LAG status

3 Scale of the bar graph They show the scales of the bar graph.

4 Under scale input Turns on when measuring values fall below the minimum scale.

5 Over scale input Turns on when measuring values exceed the maximum scale.

6 Index indicator When upper/lower limit alarm set, flickers at the limit setting value.

7 Bar graph status

They show the item expressed with the bar graph.

When the item is the same as a digital displayed item, indicated with ,

otherwise indicated with

8 Phase status They show the phase for each of the digital displays.

9 Digital display Measured values displayed in digital.

10 Unit Units of measuring value displayed.

11 Metering status Flickers when counting active energy.(Note.1)(only active energy imported display)

12 Harmonics Turns on when harmonics displayed.

13 Setup status Turns on at setting mode. ( )

Flickers at setting value confirmation mode. ( )

14 Test mode status Turns on at the test mode.

15 Clock status Turns on when Operation time displayed.

16 Upper/lower limit alarm

status Flickers when upper/lower limit alarm is generated.

17 Communication or Logging

status

Specification On Blinking Off

CC-Link communication Normal CC-Link version mismatch Hardware error

Hardware error

MODBUSRTU communication MODBUSTCP communication

Normal Communication error (Such as wrong address)*1

Hardware error

Logging function Normal Error such as incorrect setting, SD memory card error, low battery voltage)*1

Hardware error

*1. For details, refer to Section 6.6.(page86).

Note 1. The blinking cycle is constant regardless of the size of the measured input.

4

7

8

6

11

10

3

5

3

9

16

1 2

13 14 15 17 12

13

1. Display and Button Functions of Each Parts

Functions of operation buttons

The operation buttons have various functions According to how they are pressed down.

Meaning of code:(press),(press on over 1 second),(press on over 2 seconds), (press simultaneously)

Operation

Mode

Button Function

SET RESET MAX/MIN PHASE DISPLAY

O p e ra

ti o

n m

o d e

D is

p la

y c

h a n g e s o

p e ra

ti o

n

Display changes.

Display changes.(reverse direction)

Phase changes.

Mode changes to the max./min. display and the instantaneous display

The item expressed with the bar graph is changed.

Harmonics number changes when harmonics displayed.

Displays change cyclically. (Refer to page 65)

Phases change cyclically. (Refer to page 65)

Change the unit of Wh, varh and VAh, etc. (Refer to page 68)

M e a s u re

d v

a lu

e i s r

e s e t/ C

a n c e lin

g t

h e

a la

rm ,

e tc

Maximum values and minimum values on

the display are reset to the present value. Only available for

maximum/minimum

value display All of the Maximum values and minimum

values are reset to the present value.

Wh, varh, VAh are zero reset. (All of the counting values are zero reset.)

Periodic active energy is zero reset. (Only effective in Periodic active

energy display)

Adjusting rolling demand time(Only effective in rolling demand display)

Resetting the peak value of rolling demand (Only effective in rolling

demand display)

The operation time is zero reset (Screen operation time only)

An alarm condition is canceled.

(Screen element is canceled) Available only when

manual cancelation is

set All alarm conditions are canceled.

(Element is canceled for all screens)

Stopping backlight flickering alarm. (Only effective in setting backlight

flicker)

The latching data of digital input on the display is canceled.

(Available only for contact point input screen)

M

o d e

c h a n g e s The display of Setting mode appears.

The display of Set value confirmation mode appears.

The display of password protection mode appears.

S e tt in

g / S

e tt in

g v

a lu

e c

o n fi rm

a ti o

n m

o d e

S e tt in

g o

p e ra

ti o

n

The setting items are saved, and setting item is changed to next item.

Back to the previous item.

The values of setting are changed.

(If it presses for 1 sec or more fast forward or fast return.)

Back to the setting display.

Save the settings(Only effective in End display)

Cancel the settings(Only effective in CANCEL display)

S p e c ia

l o p e ra

ti o

n

Meter restart(Only effective in CANCEL display)

Returns set contents to the default settings (the default values, Only

effective in CANCEL display) (Refer to page 52)

Note: While the back light is off, if the operation button is pressed, the back light is always lit. If the operation button is pressed once again, the function in the above table appears.

CAUTION

If the function of maximum value and minimum value reset and Wh, varh, VAh zero reset are done, data will be lost. If this data is needed, please record the data before the reset operation. If the function of meter restart is done, the entire measurement(measurement display, alarm, analog output, pulse) stops.

SET RESET MAX/MIN PHASE DISPLAY

Set button Reset button Phase button

/button Maximum/Minimum button Display button

14

1. Display and Button Functions of Each Parts

LEDs of the Optional plug-in module

LEDs of ME-0000MT-SS96

LEDs of ME-0000BU-SS96

No. Name Function

1) ERR. LED This indicates a communication error state of ME-0000MT-SS96

OFF Normal

Blink MODBUS TCP communication error as follows was detected. MODBUS TCP application protocol header was incorrect.

Function code was incorrect(Serial only code was received),

etc. When correct request is received, this LED turns off.

2) 10/100 LED This indicates the transmission speed.

ON 100Mbps or not connected.

OFF 10Mbps

3) LINK/ACT LED This indicates the link status.

ON Link is good.

Blink Blinks when data send or receive.

OFF Not linked

No. Name Function

1) LOG. LED This indicates a state of logging operation.

ON Logging is running.

OFF Logging is stopped.

Blink slowly (0.5s:on/ 0.5s:off)

Change of logging condition settings finished. Blink of LED lasts 5 second.

Blink quickly (0.25s:on/ 0.25s:off)

When Setting of Logging-item pattern is LP00, Setting data file needed to store in SD memory card was incorrect. LED blinks until correct setting is done.

2) SD C. LED This indicates a state of communication with the SD memory card.

ON Communicating

OFF Stop communicating

Blink quickly (0.25s:on/ 0.25s:off)

SD memory card error. Check whether the SD memory card is write-protect and SD memory card capacity is sufficient or not.

3) BAT. LED This indicates a state of battery voltage.

OFF Normal

ON The battery is low voltage.

1) ERR.

2) 10/100

3) LINK/ACT

1) LOG.

2) SD C.

3) BAT.

15

2. Function Modes

The following function modes are available for this Multi-Measuring instrument. Operation mode is displayed after auxiliary power turns on. It is then possible to switch to the desired mode.

Mode Description Reference

Pages

Operation

Mode

This mode is for displaying each measured value using digital numerical values and

bar graphs.

Operation mode contains "Current Value Display" that displays the current value, and

"Maximum/Minimum Value Display" that displays old maximum/minimum values.

In addition, for each display, the cyclic display function can be used to switch between the

screens every 5 seconds.

P.63 to P.76

Setting Mode This mode is for changing the setting values related to measurement and output functions.

The following special operations can be executed from the "CANCEL Display" for

changing/cancelling setting values.

The instrument is reset.

Reset the settings to the factory defaults

P.16 to P.49

P.51 to P.56

Setting Value

confirmation

mode

(Test Mode)

This mode is for confirming the setting values for each setting item.(In this mode, settings

cannot be changed in order to prevent accidental changing of settings.)

This mode contains test functions that can be used for equipment startup.

Analog Output Adjustment: Analog output can be adjusted (zero adjustment and span

adjustment).

Output Test: Analog output can be switched, pulse output can be executed,

and alarm contact points can be opened/closed without

measurement input (voltage/current).

Communication Test: Fixed numerical data can be returned without measurement

input (voltage/current).

P.50,

P.57 to P.62

Diagram of Each Mode

SET

Operation mode

Current value

display

Maximum/minimum

value display

Setting mode

Setting value confirmation mode

Test mode

SET

SET SET

SET

SET RESET

End Display

CANCEL

Display

Save the settings

Cancel the settings

Pressing simultaneously for 2 seconds

When "End" is selected from the menu

When "End" is selected

from the menu

Press for 2 seconds

16

3. Setting

3.1. Setting flow

To measure, it is necessary to use Setting mode to set the phase wire system, VT / direct voltage, and CT primary current. From Operation mode, move to Setting mode and then set necessary items. Factory default settings will be used for items that you do not set. Only the settings in Setting menu 1 (basic setting) are needed for normal use. For more information about the settings, refer to page 22 and after. For more information about the factory default settings, refer to the setting table on page 104.

Setting flow when without optional plug-in module, with ME-4210-SS96, with ME-0040C-SS96 or with ME-0052-SS96,

CAUTION

Keep in mind that when a setting is changed, the related setting items and measurement data

will be reset to the default settings. (Refer to page 51.)

Measurement Display Setting Menu End

End Display

CANCEL Display

Automatic migration.

Time constant for

current demand

Time constant for

rolling demand

Frequency

CT current

VT/direct

voltage

Display

Pattern

Phase

wire system

Setting Menu 1 Setting Menu 2 Setting Menu 3

Cancel the settings.

Save the setting.

Instrument restart

or

Factory default setting

Operation Mode

2

1

Password Protection Display

Example of Setting Mode Example of Setting Value Confirmation Mode

Harmonics

display

Reactive

power scale

Active power

scale

Voltage scale

Current scale

Power factor

scale

Expanded

counting

Changes Password

MODBUSRTU

address

MODBUSRTU

baud rates

MODBUSRTU

parity

MODBUSRTU

stop bit

CC-Link

baud rates

CC-Link

version

CC-Link

Reset

CC-Link

Station number

With ME-0040C-SS96 only

Communication

setting selection

ON Blinking

3. Setting

17

3.1. Setting flow

Press and simultaneously for 2 After completion of setting, select End in the setting

seconds to get in the setting mode. menu and press .

Select a setting menu number by or . When the End display appears, press once again.

Use the button to select a setting menu number.

Set each setting item. (Refer to page 22 and later

pages.)

SET

SET

SET

SET

RESET

Analog output 1

Alarm value

Alarm delay

time

Alarm cancel

method

Back light flickers

during alarms

Motor starting

current delay time

Alarm item Model +

option code

Version

display

Backlight

brightness

Backlight

auto off

Display

update time Output Limit

Analog output 4

Analog output 3

Analog output 2

Digital input

reset method

Digital input/

output display

Periodic active energy setting

Periodic active

energy display

Phase display

setting

Operation time

threshold

Target for

counting operation

time setting

Operation time

display

Setting Value

Confirmation Menu 9 Setting Menu 4 Setting Menu 5 Setting Menu 6 Setting Menu 7 Setting Menu 8

Setting Mode or Setting Value Confirmation Mode

Arrow in Figure Action Button operation

Shift from the operation mode to the setting mode. Press them simultaneously

Shift from the operation mode to the set value confirmation mode. Press it for 2 seconds.

Select the menu number to set or End . or Press it several times.

Get into each setting screen. Shift to the next setting item. Press it.

Go back to the previous setting item. Press it.

Omitted in figure Select a set value. or Press it several times.

Shift to the End screen. Press it.

Memorize the setting contents, and go back to the operation mode. Press it.

Select "CANCEL." or Press it.

Cancel the settings. Press it.

Skip remaining setting items during setting. Press it for 1 second.

Set values return to the factory default value. Press it for 2 seconds.

Shift from the operation mode to the password protection mode. Press it for 2 seconds.

DISPLAY

RESET

SET

PHASERESET

SET

SET

SET

SET

SET

SET

Pulse output

1 If the password protection setting is enabled, it is

necessary to enter the password in shift from the

operation mode to the setting mode.

2For Setting Value Confirmation, it returns to Operation

Mode.

3This is not display in Setting Mode.

Test Mode 3

PHASERESET

Pulse / Alarm

output

Set IEC

mode

Rolling demand

time setting

Rolling demand

display

3

With ME-4210-SS96 only

With ME-4210-SS96 only

With Optional pug-in module only

3. Setting

18

3.1. Setting flow

Setting flow when with ME-0000MT-SS96

CAUTION

Keep in mind that when a setting is changed, the related setting items and measurement data

will be reset to the default settings. (Refer to page 51.)

Measurement Display Setting Menu End

End Display

CANCEL Display

Automatic migration.

Time constant for

current demand

Time constant for

rolling demand

Frequency

CT current

VT/direct

voltage

Display

Pattern

Phase

wire system

Setting Menu 1 Setting Menu 2 Setting Menu 3

Cancel the settings.

Save the setting.

Instrument restart

or

Factory default setting

Operation Mode

2

1

Password Protection Display

Example of Setting Mode Example of Setting Value Confirmation Mode

Harmonics

display

Reactive

power scale

Active power

scale

Voltage scale

Current scale

Power factor

scale

Expanded

counting

Changes Password

MODBUSRTU

address

MODBUSRTU

baud rates

MODBUSRTU

parity

MODBUSRTU

stop bit

MODBUSTCP

Subnet mask

MODBUSTCP Default G/W

existence

MODBUSTCP

Default G/W

MODBUSTCP

IP address

Communication

setting selection

MODBUSTCP

Reset

ON Blinking

3. Setting

19

3.1. Setting flow

non

Alarm value

Alarm delay

time

Alarm cancel

method

Back light flickers

during alarms

Motor starting

current delay time

Alarm item Model +

option code

Version

display

Backlight

brightness

Backlight

auto off

Display

update time

Periodic active energy setting

Periodic active

energy display

Phase display

setting

Operation time

threshold

Target for

counting operation

time setting

Operation time

display

Setting Value

Confirmation Menu 9 Setting Menu 4 Setting Menu 5 Setting Menu 6 Setting Menu 7 Setting Menu 8

Setting Mode or Setting Value Confirmation Mode

Arrow in Figure Action Button operation

Shift from the operation mode to the setting mode. Press them simultaneously

Shift from the operation mode to the set value confirmation mode. Press it for 2 seconds.

Select the menu number to set or End . or Press it several times.

Get into each setting screen. Shift to the next setting item. Press it.

Go back to the previous setting item. Press it.

Omitted in figure Select a set value. or Press it several times.

Shift to the End screen. Press it.

Memorize the setting contents, and go back to the operation mode. Press it.

Select "CANCEL." or Press it.

Cancel the settings. Press it.

Skip remaining setting items during setting. Press it for 1 second.

Set values return to the factory default value. Press it for 2 seconds.

Shift from the operation mode to the password protection mode. Press it for 2 seconds.

DISPLAY

RESET

SET

PHASERESET

SET

SET

SET

SET

SET

SET

1 If the password protection setting is enabled, it is

necessary to enter the password in shift from the

operation mode to the setting mode.

2For Setting Value Confirmation, it returns to Operation

Mode.

3This is not display in Setting Mode.

Test Mode 3

PHASERESET

Set IEC

mode

Rolling demand

display

3

Automatic migration

3. Setting

20

3.1. Setting flow

Setting flow when with ME-0000BU-SS96

CAUTION

Keep in mind that when a setting is changed, the related setting items and measurement data

will be reset to the default settings. (Refer to page 51.)

Measurement Display Setting Menu End

End Display

CANCEL Display

Automatic migration.

Time constant for

current demand

Time constant for

rolling demand

Frequency

CT current

VT/direct

voltage

Display

Pattern

Phase

wire system

Setting Menu 1 Setting Menu 2 Setting Menu 3

Cancel the settings.

Save the setting.

Instrument restart

or

Factory default setting

Operation Mode

2

1

Password Protection Display

Example of Setting Mode Example of Setting Value Confirmation Mode

Harmonics

display

Reactive

power scale

Active power

scale

Voltage scale

Current scale

Power factor

scale

Expanded

counting

Changes Password

MODBUSRTU

address

MODBUSRTU

baud rates

MODBUSRTU

parity

MODBUSRTU

stop bit

Present time

setting (Month)

Setting Menu CL

Present time setting (Day)

Present time setting (Year)

Present time setting (Hour)

Present time setting

(Minute)

ON Blinking

3. Setting

21

3.1. Setting flow

Alarm value

Alarm delay

time

Alarm cancel

method

Back light flickers

during alarms

Motor starting

current delay time

Alarm item Model +

option code

Version

display

Backlight

brightness

Backlight

auto off

Display

update time

Periodic active energy setting

Periodic active

energy display

Phase display

setting

Operation time

threshold

Target for

counting operation

time setting

Operation time

display

Setting Value

Confirmation Menu 9 Setting Menu 4 Setting Menu 5 Setting Menu 6 Setting Menu 7 Setting Menu 8

Setting Mode or Setting Value Confirmation Mode

Arrow in Figure Action Button operation

Shift from the operation mode to the setting mode. Press them simultaneously

Shift from the operation mode to the set value confirmation mode. Press it for 2 seconds.

Select the menu number to set or End . or Press it several times.

Get into each setting screen. Shift to the next setting item. Press it.

Go back to the previous setting item. Press it.

Omitted in figure Select a set value. or Press it several times.

Shift to the End screen. Press it.

Memorize the setting contents, and go back to the operation mode. Press it.

Select "CANCEL." or Press it.

Cancel the settings. Press it.

Skip remaining setting items during setting. Press it for 1 second.

Set values return to the factory default value. Press it for 2 seconds.

Shift from the operation mode to the password protection mode. Press it for 2 seconds.

DISPLAY

RESET

SET

PHASERESET

SET

SET

SET

SET

SET

SET

1 If the password protection setting is enabled, it is

necessary to enter the password in shift from the

operation mode to the setting mode.

2For Setting Value Confirmation, it returns to Operation

Mode.

3This is not display in Setting Mode.

Test Mode 3

PHASERESET

Set IEC

mode

Rolling demand

display

3

Logging ID

Logging Data

Clear

Logging-item

pattern

Detailed data

Logging cycle

3. Setting

22

Basic Operations for setting

Function Operation Remarks

Select a set value Press or . Fast-forward when pressed over 1 sec.

Setting items are saved Press . Setting item will be cared and shift to the next item.

Go back to the previous setting item Press . The set value for the setting item just before Skip removing setting items returning is still available.

Skip removing setting items during setting

Press and hold for 1 sec.

3.2. Setting Menu 1: Basic Settings (Setting the Phase Wire System, Display Pattern,

VT/Direct Voltage, CT Primary Current, etc.)

Set the phase wire method, display pattern, VT/direct voltage, CT primary current, etc.

In the operation mode, after pressing and simultaneously for 2 seconds or more, the following operation becomes available.

SET

DISPLAY

RESET

SET

SET

Set the phase wire system.

Supplemental Information:

Underlined portions indicate

the default values.

(Same from here.) Phase Wire system

3P4 : 3-phase 4-wire

3P32CT : 3-phase 3-wire2CT

3P33CT : 3-phase 3-wire3CT

1P31N2 : 1-phase 3-wire1N2 display

1P31N3 : 1-phase 3-wire1N3 display

1P2 : 1-phase 2 -wire

Set the setting menu number to 1. (as shown in the right figure)

Setting Menu

SETDISPLAY

SETDISPLAY

SETDISPLAY

Display Pattern

Set the display pattern. The following table shows the measurement elements that can be displayed by each display pattern. (For more details about display patterns, refer to page 77,78.) In addition, if there is no display pattern that you want from P01 to P13), select the special display pattern P00 to configure the screen freely. ( For more information about setting the special display pattern P00,

refer to page53,54)

Displayable at this display setting.

Set at other additional settings.

Select "P00" and set the display order and display position.

(1)For 3-phase 4-wire

D is

p la

y P

a tt

e rn

C u rr

e n t

N P

h a s e C

u rr

e n t

C u rr

e n t

D e m

a n d

N P

h a s e C

u rr

e n t

D e m

a n d

V o lt a g e

A c ti v e P

o w

e r

P o w

e r

F a c to

r

R e a c ti v e P

o w

e r

A p p a re

n t

P o w

e r

F re

q u e n c y

A c ti v e E

n e rg

y (I

m p o rt

e d )

A c ti v e E

n e rg

y (E

x p o rt

e d )

R e a c ti v e E

n e rg

y

(I m

p o rt

e d L

A G

)

A p p a re

n t

E n e rg

y

Additional display

A c ti v e E

n e rg

y (

Im p o rt

e d )

A c ti v e E

n e rg

y (E

x p o rt

e d )

R e a c ti v e E

n e rg

y

(S p e c ia

l)

A p p a re

n t

E n e rg

y

P e ri o d ic

A c ti v e E

n e rg

y

R o lli

n g D

e m

a n d

H a rm

o n ic

C u rr

e n t/

V o lt a g e

D ig

it a l In

p u t/

O u tp

u t

O p e ra

ti o n t

im e

P01

P02

P03

P04

P05

P06

P07

P08

P09

P10

P11

P12

P13

P00

Note: The following settings are required for displaying elements on an additional display.

Measurement element on additional display Setting item Reference

Pages

Active energy Exported /reactive energy Special(*)

Setting Menu 3 Active energy measurement Page 32

Harmonic current/ Harmonic voltage Setting Menu 3 Harmonics display Page 32

Periodic Active Energy Setting Menu 7 Periodic Active energy display Page 44

Rolling Demand Setting Menu 7 Rolling demand display Page 44

Digital input / output status Setting Menu 7 Digital input / output display Page 45

Operation time Setting Menu 8 Operation time display Page 46

When display elements does not set active energy/ reactive energy/ apparent energy, P00 of active

energy/ reactive energy/ apparent energy on additional display does not appear.

3. Setting

23

3.2 Setting menu 1: Basic Settings (Setting the Phase Wire System, Display Pattern,

VT/Direct Voltage, CT Primary Current, etc.)

Set the VT

When direct input (without VT) Select no, and then press , shift to following (1).

When using VT Select yES, and then press , shift to following (2)

1. For 3-phase 4-wire

2. For 3-phase 3-wire or 1-phase 2-wire

Note. VT is voltage transformers.

(1)For direct input (without VT)Set the direct voltage.

aFor 3-phase 4-wire

(phase to neutral voltage / phase to phase voltage)

bFor 3-phase 3-wire (2CT, 3CT) or 1-phase 2-wire

cFor 1-phase 3-wire1N2, 1N3(phase to neutral voltage / phase to phase voltage)

VT / direct voltage

Use only for direct input. This setting will be skipped.

SET

SET

110V 220V 440V

yES no

110/220V 220/440V

no yES

63.5/110V 100/173V 110/190V 220/380V 230/400V 240/415V

277/480V 254/440V

SETDISPLAY

2For other phase wire system except 3-phase 4-wire

D is

p la

y P

a tt

e rn

C u rr

e n t

C u rr

e n t

D e m

a n d

V o lt a g e

A c ti v e P

o w

e r

P o w

e r

F a c to

r

R e a c ti v e P

o w

e r

F re

q u e n c y

A c ti v e E

n e rg

y (I

m p o rt

e d )

A c ti v e E

n e rg

y (E

x p o rt

e d )

R e a c ti v e E

n e rg

y y

(I

m p o rt

e d L

A G

)

Additional display

A c ti v e E

n e rg

y (

Im p o rt

e d )

A c ti v e E

n e rg

y (E

x p o rt

e d )

R e a c ti v e E

n e rg

y

(S p e c ia

l)

P e ri o d ic

A c ti v e E

n e rg

y

R o lli

n g D

e m

a n d

H a rm

o n ic

C u rr

e n t/

V

o lt a g e

D ig

it a l In

p u t/

O u tp

u t

O p e ra

ti o n t

im e

P01

P02

P03

P04

P05

P06

P07

P08

P09

P10

P11

P12

P13

P00

Note: The following settings are required for displaying elements on an additional display. Measurement element on additional

display Setting item

Reference Pages

Active energy Exported /reactive energy Special(*)

Setting Menu 3 Active energy measurement Page 32

Harmonic current/ Harmonic voltage Setting Menu 3 Harmonics display Page 32

Periodic Active Energy Setting Menu 7 Periodic Active energy display Page 44

Rolling Demand Setting Menu 7 Rolling demand display Page 44

Digital input / output status Setting Menu 7 Digital input / output display Page 45

Operation time Setting Menu 8 Operation time display Page 46

When display elements does not set active energy/ reactive energy, P00 of active energy/ reactive

energy on additional display does not appear.

3. Setting

24

3.2 Setting menu 1: Basic Settings (Setting the Phase Wire System, Display Pattern,

VT/Direct Voltage, CT Primary Current, etc.)

Set the CT.

Primary / secondary Current Setting

Set the secondary current

Note. CT is current transformers.

Set the primary current

Default Setting5.0A

CT current

From top digit, select the value of the flickering digit by and .

The setting digit can be moved to right by the .

The setting digit can be moved to left by the .

Setting is available in range from 1.0A to 30000.0A Less than 10A : Upper 2 digits setting Over 10A : Upper 3 digits setting

Error display (E05) appears when set out of 1.0 to 30000.0A

range. After that, please press , review the setting value and set it once again.

When over 10A set over upper 3 digits setting, the display appear switching

upper 3 digits setting.

Press at the lowest digit, the setting step will shift to the next one.

1A 5A

DISPLAY

SET

SET

SET

Continued form the previous page 2 When using VT

Set the secondary and primary voltages of the VT.

aFor 3-phase 4-wire(Phase to phase Voltage)

bFor 3-phase 3-wire (2CT, 3CT) or 1-phase 2-wirephase to neutral voltage

Primary Voltage Settings Default value

For 3-phase 4-wire 200V(Phase to phase Voltage)

For 3-phase 3-wire or 1-phase 2-wire10000V

phase to neutral voltage

From top digit, select the value of the flickering digit by and

The setting digit can be moved to right by

The setting digit can be moved to left by

Setting is available in range from 60V to 750000V

Less than 100V : Upper 2 digits setting

Over 100V : Upper 3 digits setting

Error display (E05) appears when set out of 60Vto750000V range.

After that, please press , review the setting value and set it once Again.

When over 100V set over upper 3 digits setting, the display appear switching

upper 3 digits setting.

Press at the lowest digit, the setting step will shift to the next one.

63.5V 100V 110V 115V 120V

100V 110V 220V

SET

DISPLAY

SET

SET

SETDISPLAY

3. Setting

25

3.2 Setting menu 1: Basic Settings (Setting the Phase Wire System, Display Pattern,

VT/Direct Voltage, CT Primary Current, etc.)

In the case of use only by the Setting menu 1, please go to 5. Operation (from page 63). In the case to use additional functions, please go to Setting Menus 2 - 8 (from page 26).

Note

If the contents in the setting menu 1 are changed, the maximum value, minimum value,

demand value of related measurement items will be reset.

(However, active energy, reactive energy and Apparent energy will not be reset.)

For detail, refer to section 3.15.

SETDISPLAY

SETDISPLAY

SET

Set the frequency.

Frequency 50Hz 60Hz

Note1.The scale value of the frequency of the bar graph display is changed, too. Note2.Scale of the analog output is changed, too.

Set the interval time constant for the rolling demand. (For the rolling demand, refer to page 73.)

(1)Interval time constant

Setting range Setting step

1 to 15 to 60min 1min

(2)Subinterval time constant

Setting range Setting step

1 to 60min 1min

Error display (E05) appears when the interval time constant

is set to a value that is not dividable by the subinterval time

period. After that, please press , review the setting value

and it once again.

Even when the display pattern not display the rolling

demand, this screen appears. If the rolling demand is not

necessary, press the as it is.

Time constant for

rolling demand

SET

SET

Set the time constant for current demand. (For the demand time period, refer to page 70.)

Note) Even when the display pattern not display the current demand, this screen appears. If the current demand is not necessary, press the as it is.

Time constant

for current demand

SET

0 s 10 s 20 s 30 s

40 s 50 s

1 min 2 min

3 min 4 min 5 min 6 min

7 min 8 min 9 min

10 min

15 min 20 min 25 min 30 min

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu.

Setting Menu

3. Setting

26

3.3. Setting Menu 2: Communication Settings (Setting the MODBUSRTU communication)

In the operation mode, press + simultaneously for 2 seconds or more, and the following operation

becomes available.

SET RESET

Set the MODBUS RTU parity.

MODBUS RTU

parity

non

odd

evenEVEn

Set the MODBUS RTU baud rate.

MODBUS RTU

baud rates

2400bps

4800bps

9600bps

19.2kbps

38.4kbps

Set the MODBUS RTU address number.

Selectable addresses: 1 to 255

MODBUS RTU

address

Set the MODBUS RTU stop bit.

MODBUS

RTU

stop bit Stop bit 1 Stop bit 2

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

Set the setting menu number to 2. (as shown in the right figure)

Setting Menu

SET

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu.

Setting Menu

3. Setting

27

3.4. Setting Menu 2: Communication Settings (Setting the CC-Link communication)

In the operation mode, press + simultaneously for 2 seconds or more, and the following operation

becomes available.

SET RESET

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

Set the setting menu number to 2. (as shown in the right figure)

Setting Menu

Set the CC-Link station number.

Selectable station number: 1 to 64 CC-Link station

number

Set the CC-Link baud rate.

CC-Link baud rates

156kbps

625bps

2.5Mbps

5Mbps

10Mbps

Set the CC-Link version according to the configuration of the used CC-Link system.

CC-Link version Version 1.10 Version 2.00

Select either of Setting of CC-Link communication or Setting of MODBUSRTU communication.

CC Mb.rtu

(CC-Link communication) (MODBUSRTU communication)

When MODBUS RTU communication is selected,

refer to MODBUSRTU Address at page 26.

Hereafter, CC-Link communication setting describes.

Communication

setting selection

3. Setting

28

3.4. Setting Menu 2: Communication Settings (Setting the CC-Link communication)

When the changed above settings are enabled, set to "on." When it is not set to on, the changed settings of CC-Link do not

become effective.

Communication

reset oFF on

SET

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu. If it is needed to set the MODBUSRTU communication setting, Select the menu number 2 again, and select Mb.rtu at

Communication setting selection.

Setting Menu

3. Setting

29

3.5. Setting Menu 2: Communication Settings (Setting the MODBUSTCP communication)

In the operation mode, press + simultaneously for 2 seconds or more, and the following operation

becomes available.

SET RESET

Set the subnet mask.

Select the subnet mask from the below table.

(1) 128.0.0.0 (9) 255.128.0.0 (17) 255.255.128.0 (25) 255.255.255.128

(2) 192.0.0.0 (10) 255.192.0.0 (18) 255.255.192.0 (26) 255.255.255.192

(3) 224.0.0.0 (11) 255.224.0.0 (19) 255.255.224.0 (27) 255.255.255.224

(4) 240.0.0.0 (12) 255.240.0.0 (20) 255.255.240.0 (28) 255.255.255.240

(5) 248.0.0.0 (13) 255.248.0.0 (21) 255.255.248.0 (29) 255.255.255.248

(6) 252.0.0.0 (14) 255.252.0.0 (22) 255.255.252.0 (30) 255.255.255.252

(7) 254.0.0.0 (15) 255.254.0.0 (23) 255.255.254.0

(8) 255.0.0.0 (16) 255.255.0.0 (24) 255.255.255.0

MODBUS TCP

Subnet mask

Set the local station IP address for MODBUS TCP by each octet.

000.000.000.000 to 192.168.3.10 to 255.255.255.255

MODBUS TCP

IP address

* If invalid IP address is set, error code E05 is appears.

If that happens, press and set again after review

the IP address.

[Range of configurable IP address]

1.0.0.0 to 126.255.255.255

128.0.0.0 to 191.255.255.255

192.0.0.0 to 223.255.255.255

The following IP addresses cannot be configured.

0.0.0.0

xxx.xxx.xxx.255 (xxx are any values)

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

Set the setting menu number to 2. (as shown in the right figure)

Setting Menu

SET

Select either of MODBUSTCP communication or MODBUSRTU communication.

Mb. tcP Mb.rtu

(MODBUSTCP communication) (MODBUSRTU communication)

When MODBUS RTU communication is selected,

refer to MODBUSRTU Address at page 26.

Hereafter, MODBUSTCP communication setting describes.

Communication

setting selection

3. Setting

30

3.5. Setting Menu 2: Communication Settings (Setting the MODBUSTCP communication)

Set the Default gateway existence.

If the default gateway exists on the Ethernet,

select on to communicate with other network.

oFF on

MODBUSTCP

Default gateway

existence

SETDISPLAY

When the changed above settings of MODBUS TCP are enabled, set to "on." When it is not set to on, the changed settings of MODBUSTCP

do not become effective.

Communication

reset

oFF on

SETDISPLAY

SET

Set the Default gateway address.

If select oFF in MODBUSTCP Default gateway existence,

this display will be skipped.

MODBUS

TCP

Default gateway

address * If invalid default gateway address is set, error code E05

is appears.

If that happens, press and set again after review

the default gateway address.

The following default gateway addresses cannot be configured.

0.0.0.0

xxx.xxx.xxx.255 (xxx are any values)

000.000.000.000 to 127.0.0.1 to 255.255.255.255

SET

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu. If it is needed to set the MODBUSRTU communication setting, Select the menu number 2 again, and select Mb.rtu at

Communication setting selection.

Setting Menu

3. Setting

31

3.6. Setting Menu 3: Display Settings (Setting Maximum Scale, Active Energy Measurement,

and Harmonic Display, etc.)

This section shows how to set maximum scale in the bar graph, expanded counting, and harmonics display.

In the operation mode, press and simultaneously for 2 seconds or more, and the following operation

becomes available.

SET RESET

Set the setting menu number to "3".

(as shown in the right figure) Setting menu

Set the maximum scale of Reactive power. If you have not set reactive power to Display pattern, this display will be skipped.

The setting method is the same as active power maximum scale.

Reactive power is only double deflection.

Reactive power

maximum scale

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

Set the current maximum scale. If you have not set current to Display pattern, this display menu will be skipped.

(1)Maximum scale value

Primary Current

(1.4.1Primary Current Setting value)

SP.(Special Setting) (2)Special current maximum scale This display is displayed when you set the "SP" in 3.1.

+ 3 STEP (About 120%) to 0 STEP (100% : Rating) to -10 STEP (About 40%)

Note: The maximum scale value becomes the value in the table on Section 6.3.(page 80 and after).

Current maximum

scale

Set the voltage maximum scale. If you have not set voltage to Display pattern, this display menu will be skipped.

Maximum scale value

+10 STEP (About 250%) to 0 STEP (100% : Standard maximum scale value) to -18 STEP (About 20%)

Note: The maximum scale value becomes the value in the table on Section 6.3.(page 80 and after).

Voltage maximum

scale

Set the maximum scale of Active power, Rolling demand. If you have not set active power and rolling demand to Display pattern,

this display will be skipped. And, if selected not Active power but rolling demand, (2)single deflection/ double deflection will be skipped.

(1)Maximum scale value

+3 STEP (About 120%) to 0 STEP (100% : Rating) to -18 STEP (About 20%)

Note: The maximum scale value becomes the value in the table on Section 6.3.(page 80 and after).

(2)single deflection / double deflection

Active power

maximum scale

single deflection double deflection

SETDISPLAY

3. Setting

32

3.6. Setting Menu 3: Display Settings (Setting Maximum Scale, Active Energy Measurement,

and Harmonic Display, etc.)

Note

Accuracy is defined to rated current. Although the maximum scale may display 120% or more of rated current and rated voltage in order to make a scale easy to read depending on the settings of VT/direct voltage and CT primary current, current input is within 100% of rated current.

Even if a display pattern is selected that cannot display active power, reactive power, active energy, and reactive energy, it is possible to display the sign according to 2 quadrant / 4 quadrant

measurement of the power factor and reactive power due to Expanded counting , so setting

items for Expanded counting will be displayed.

Set the power factor scale. If you have not set power factor to Display pattern, this display will be skipped.

Power factor scale

-0.5 to 1 to 0.5 -0 to 1 to 0

Set on or off of the harmonic measurement display.

When the display is set to "on," the harmonic measured value can be displayed on an additional screen of the display pattern.

Harmonics

oFF on

(Not displayed) (Displayed)

SETDISPLAY

SETDISPLAY

SET

Set the combinations of imported / exported and lag / lead for active energy and reactive energy you want to display, and set the measurement method for reactive energy.

Combination (Setting value)

Display Reactive energy measurement

method Wh varh

Imported Exported Imported Exported

lag lead lag lead

2 quadrant measurement

4 quadrant measurement

Note: For more information about the measurement method for reactive energy, refer to page 69.

Combination I, II It is suitable for the counting of equipment without the private

electric generator and the reactive power of the capacitor load at the power factor = 0, generally.

Combination III, IVIt is suitable for the counting of equipment with the private electric

generator.

Depending on the above combination and the measurement element which

set in Display pattern of the setting menu 1, the energies displayed at the

additional screen are as below.

Additional Screen

Wh Wh -Wh

-Wh

varh varh varh(imported LEAD) varh(exported LAG) varh(exported LEAD)

VAh VAh

Note: Wh:Wh(imported), -Wh:Wh(exported), varh:varh(imported LAG)

Expanded counting

:Imported :Exported lead varh lag varh

Combination I Combination II Combination III Combination IV

Example Screen

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu.

Setting Menu

3. Setting

33

3.7. Setting Menu 4: LCD Settings (Setting Model Display, Version Display, Backlight, and

Display Update Time)

This section is for confirming the model, option code and the product version, and also set the backlight and the display update time. In the operation mode, press + simultaneously for 2 seconds or more, and the following operation becomes available.

SET RESET

Set the setting menu number to 4.

(as shown in the right figure) Setting menu

The display update time for the measured value can be change. If the display switches too quickly for you to read the displayed value, set it to 1.0 second. (Normally, leave this setting to 0.5 second.)

0.5second 1second

Display update time

The backlight can be set to continuous on (HoLd)

or auto off (Auto).

Backlight auto off

Auto HoLd

No button operation for 5 minutes the backlight turns off

Button operation during off (Note) the backlight turns on

for 5 minutes

Note: When the backlight is off, pressing any button once does not switch the display but only turns on the backlight. Pressing any button again switches the display.

(Auto off) (Continuous on)

The backlight brightness can be adjusted.

Backlight brightness 1 2 3 4 5

Dark Bright

The product version can be checked.

(The product version is displayed, but cannot be changed.) Version display

The model can be confirmed. (This is only display, and settings cannot be changed.)

1Middle Line Model

ME96SSRA-MB

2Lower Line

Option code

Blank

ME-4210-SS96

ME-0040C-SS96

ME-0052-SS96

ME-0000MT-SS96

ME-0000BU-SS96

Model + option code

*1 If E90xx appears, MODBUSTCP communication

error will be occurred.

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

SET

SETDISPLAY

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu.

Setting Menu

3. Setting

34

3.8. Setting Menu 5: Pulse and Alarm Settings (Setting Upper/Lower Limit Alarm, Motor

Starting Current Mask Function, Pulse Output, etc.)

This section shows how to set the upper/lower limit alarm, backlight flickering during alarm, motor starting current delay time, and

pulse output.

In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.

For more details about each function, refer to the corresponding pages. Upper/lower limit alarm Pages 71 and 72, Motor startup current Page 75

SET RESET

Set the Alarm item 1 to be allowed to measurement items. The upper/lower limit measurement values can be monitored by this setting.

(1)For 3-phase 4-wire (2)For other phase wire system except 3-phase 4-wire

Alarm item 1

Note 1. Measurement items that are not selected in the display pattern can be selected. Note 2. DA: Current demand, DAN: N-phase current demand,

V (L-N): Phase to neutral voltage, V (L-L): phase to phase voltage, DW: Active power rolling demand, Dvar: Reactive power rolling demand, DVA: Apparent power rolling demand

Display when "non" is selected

Display when "A upper limit" is selected

DW upper limit var upper limit var lower limit Dvar upper limit DVA upper limit PF upper limit PF lower limit Hz upper limit Hz lower limit Harmonic current total RMS Value N-phase harmonic current total RMS value

Harmonic voltage total distortion ratio

non A upper limit A lower limit AN upper limit DA upper limit DA lower limit DAN upper limit V (L-N) upper limit V (L-N) lower limit V (L-L) upper limit V (L-L) lower limit W upper limit W lower limit

non A upper limit A lower limit DA upper limit DA lower limit V upper limit V lower limit W upper limit W lower limit

DW upper limit var upper limit var lower limit Dvar upper limit DVA upper limit PF upper limit PF lower limit Hz upper limit Hz lower limit Harmonic current total RMS value Harmonic voltage total distortion ratio

Set the setting menu number to 5. (as shown in the right figure)

Setting menu

SETDISPLAY

SETDISPLAY

3. Setting

35

3.8. Setting Menu 5: Pulse and Alarm Settings (Setting Upper/Lower Limit Alarm, Motor

Starting Current Mask Function, Pulse Output, etc.)

Set the alarm value for the upper/lower limit alarm items 2 to 4.

The setting method is the same as Alarm value 1 .

Alarm value 2 to 4

Set the measurement element assigned to the upper/lower limit alarm items 2 to 4.

Elements that are set elsewhere cannot be set.

The setting method is the same as Alarm item 1 .

Alarm item 2 to 4

Set the alarm value for upper/lower limit alarm element 1. The following table shows

the setting range.

Measuring element Setting range Setting

step(Note)

A, AN, DA, DAN upper limit 5 to 100 to 120(%) 1%

A, DA lower limit 3 to 10 to 95(%) 1%

V (L-N), V (L-L) upper limit 25 to 110 to 135(%) 1%

V (L-N), V (L-L) lower limit 20 to 70 to 95(%) 1%

W, var upper limit -95 to 100 to 120(%) 1%

W, var lower limit -120 to 3 to 95(%) 1%

DW, Dvar, DVA upper limit 5 to 100 to 120(%) 1%

PF upper limit -0.05 to 1 to 0.05 0.05

PF lower limit -0.05 to -0.5 to 0.05 0.05

Hz upper limit 45 to 65(Hz) 1Hz

Hz lower limit 45 to 65(Hz) 1Hz Harmonic current total RMS value 1 to 35 to 120(%) 1% N-phase harmonic current total RMS value

1 to 35 to 120(%) 1%

Harmonic voltage total distortion ratio

0.5 to 3.5 to 20.0(%) 0.5%

Note:W, var, DW, Dvar,DVA and var show the percentage for the maximum scale value (0 step). A, AN, DA, DAN, Harmonic current total RMS value, N-phase harmonic current total RMS value shows the percentage for the CT primary current. "V" shows the percentage for the VT primary voltage (or direct voltage). (The "V" for 1-phase 3-wire is the percentage for phase to neutral voltage. Alarm monitoring is executed using twice the value which set upper/lower limit alarm for the 12-phase and 13-phase.)

Alarm value 1

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

Set the alarm mask time for when you want to prevent a momentary overload or noise alarm. When this is set, an alarm is generated only when the alarm value over the upper/lower limit alarm value for a longer time than the delay time. On the setting screen, seconds are indicated by s and minutes are indicated by min.

Alarm delay time

0s

5s

10s

20s

30s

40s

50s

1min

2min

3min

4min

5min

Note

When all settings for Alarm item 1

and Alarm item 2 to 4 are set to non,

this setting will be skipped.

Set the alarm cancel method at generation of alarm. (screen, relay)

Reset method (Setting value)

Description (Refer to pages 71 and72)

Automatic (Auto)

When there is no alarm generation

condition, alarm is automatically reset.

Manual (HoLd)

The alarm will continue even when the alarm generated conditions no longer exist. It is necessary to execute button operation to cancel the alarm.

Note: When all settings for Alarm item 1 and Alarm item 2 to 4

are set to "non," this setting will be skipped.

Alarm cancel method

3. Setting

36

3.8. Setting Menu 5: Pulse and Alarm Settings (Setting Upper/Lower Limit Alarm, Motor

Starting Current Mask Function, Pulse Output, etc.)

By using this setting for motor current monitoring delay time, it is possible to prevent

unnecessary maximum value updating and unnecessary alarms caused by the motor startup

current.

When this setting is not needed Select "oFF" and press , and return to the Setting Menu

or go to menu 5.9(ME-4210-SS96)

When this setting is executed Select "on" and press , and go to (1) below.

1 Motor starting current value.

Set the value for detecting the motor starting current.

Setting range Setting step (Note)

3 to 5 to 120 (%) 1% * This is the percentage for the maximum scale value for

the current (0 step).

2 Motor starting current delay time

After the motor starting current is detected, maximum value update is not executed and an alarm is not generated for the delay time.

Motor starting current delay time

oFF on

1s

3s

5s

10s

15s

20s

30s

45s

4min

5min

SET

SET

SETDISPLAY

1min

1.5min

2min

3min

It is possible to make the backlight to flicker when an alarm is generated.

Backlight flickers

during alarms

oFF on

(Not flicker) (Flicker)

Note: When all settings for Alarm item 1 and Alarm item 2 to 4

are set to "non," this setting will be skipped.

SETDISPLAY

SETDISPLAY

3. Setting

37

3.8. Setting Menu 5: Pulse and Alarm Settings (Setting Upper/Lower Limit Alarm, Motor

Starting Current Mask Function, Pulse Output, etc.)

Set the pulse value of pulse output 1.

Pulse value is selected from the table below, according to total load power[kW]. In the following cases, this display will be skipped.

ME-4210-SS96 optional plug-in module is not installed.

Not set PULSE to Pulse/Alarm output 1.

Set non to Pulse output 1 output item.

Total load power[kW] = x (VT primary voltage) x (CT primary current)

1000

*1: For 3-phase 4-wire setting, the VT primary voltage is calculated using the phase to neutral voltage. *2: For 1-phase 3-wire setting, the VT primary voltage is calculated using the phase to neutral voltage. *3: For direct voltage setting, the direct voltage is used for calculation instead of the VT primary voltage.

Total load [kW] Possible pulse unit settings

Less than 10 1 0.1 0.01 0.001

kWh/pulse 10 or higher but less than 100 10 1 0.1 0.01

100 or higher but less than 1000 100 10 1 0.1

1000 or higher but less than 10000 1 0.1 0.01 0.001

MWh/pulse 10000 or higher but less than 100000 10 1 0.1 0.01

100000 or higher 100 10 1 0.1

Note 1: When Pulse output 1 output item is set to "non", this setting will be skipped.

Note 2: The factory default setting values are minimum values for the pulse unit that can be set.

Note 3: For reactive power, kW in the above table needs to be read as kvar, kWh needs to

be read as kvarh, and MWh needs to be read as Mvarh.

Note 4: For apparent power, kW in the above table needs to be read as kVA, kWh needs to

be read as kVAh, and MWh needs to be read as MVAh.

Pulse output 1

pulse unit

1 1-phase 2-wire

2 1-phase 3-wire 3 3-phase 3-wire 3 3-phase 4-wire

SETDISPLAY

SETDISPLAY

SETDISPLAY

Set the output function of Pulse/Alarm output 1.

When the ME-4210-SS96 optional plug-in module is not installed, this display will be skipped. Please refer to page 57 for the correspondence between Alarm output and Alarm item.

Pulse/Alarm

output 1

Pulse output Alarm output

PULSE AL

Set the item that is output to pulse output 1. In the following cases, this display will be skipped.

ME-4210-SS96 optional plug-in module is not installed.

Not set PULSE to Pulse/Alarm output 1.

Setting value Display

Section (A) Section (B) Section (C)

Active energy (Imported) OFF

Active energy (Exported) OFF

Reactive energy (Imported, Lag)

Reactive energy (Imported, Lead)

Reactive energy (Exported, Lag)

Reactive energy (Exported, Lead)

Apparent energy OFF

Periodic active energy 1 OFF

Periodic active energy 2 OFF

non (No output) OFF OFF

Pulse output 1

output item Note: The segment shown in The left table flickers according to the selected element.

Section (C)

Section (A) Section (B)

3. Setting

38

3.8. Setting Menu 5: Pulse and Alarm Settings (Setting Upper/Lower Limit Alarm, Motor

Starting Current Mask Function, Pulse Output, etc.)

Set the pulse width for output pulse. Set according to the input pulse conditions for the receiver.

In the following cases, this display will be skipped.

ME-4210-SS96 optional plug-in module is not installed.

Not set PULSE to Pulse/Alarm output 1 and Pulse/Alarm output 2.

Set non to Pulse output 1 output item and

Pulse output 2 output item.

Note When the pulse unit is set to the minimum value and the pulse width is set to 0.500s or 1.000s, the pulse output cannot follow if the load is too large, which can result in a decrease in the pulse output number.

Pulse width

0.125s 0.500s 1.000s

Set a pulse unit for pulse output 2. In the following cases, this display will be skipped.

ME-4210-SS96 optional plug-in module is not installed.

Not set PULSE to Pulse/Alarm output 2.

Set non to Pulse output 2 output item.

The setting method is the same as for Pulse output 1 pulse unit .

(Factory default setting values: Minimum possible value for pulse unit)

Pulse output 2

pulse unit

Set the element that is output to pulse output 2.

The same elements as pulse output 1 can be set. In the following cases, this display will be skipped.

ME-4210-SS96 optional plug-in module is not installed.

Not set PULSE to Pulse/Alarm output 2.

The setting method is the same as Pulse output 1 output item .

(Factory default setting value: Reactive energy (Imported, Lag))

Pulse output 2

output item

SETDISPLAY

SETDISPLAY

SETDISPLAY

SET

Set the output function of Pulse/Alarm output 2.

When the ME-4210-SS96 optional plug-in module is not installed, this display will be skipped. Please refer to page 72 for the correspondence between Alarm output and Alarm item.

Plulse/Alarm

output2

AL PULSE (Alarm output) (Pulse output)

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu.

Setting Menu

3. Setting

39

3.9. Setting Menu 6: Setting the Analog Output

This section shows how to set analog output. When the ME-4210-SS96 optional plug-in module is not installed, this test menu will be skipped. In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.

SET RESET

Set the measurement item to be output to analog output CH1. Select a measurement item for output from the following table.

(1)For 3-phase 4-wire 3-phase 4-wire

non

A1

A2

A3

AN

AAVG(CH1)

Demand A1

Demand A2

Demand A3

Demand AN

Demand AAVG

V1N

V2N

V3N

VAVG(L-N)(CH2)

V12

V23

V31

VAVG(L-L)

W1

W2

W3

W(CH3)

var1

var2

var3

var

VA1

VA2

VA3

VA

PF1

PF2

PF3

PF(CH4)

Hz

Harmonic A1

Harmonic A2

Harmonic A3

Harmonic AN

Harmonic V1N

Harmonic V2N

Harmonic V3N

AVGAverage, Total RMS Value

(2)For other phase wire system except 3-phase 4-wire

3-phase 3-wire 1-phase 3-wire (1N2 display)

1-phase 3-wire (1N3 display) 1-phase 2-wire

non

A1(CH1) A2 A3 AAVG Demand A1 Demand A2 Demand A3 Demand AAVG

V12(CH2) V23 V31 VAVG W(CH3) var VA PF(CH4) Hz Harmonic A1 Harmonic A3 Harmonic V12 Harmonic V23

non

A1(CH1) AN A2 AAVG Demand A1 Demand AN Demand A2 Demand AAVG

V1N(CH2) V2N V12 VAVG W(CH3) var VA PF(CH4) Hz Harmonic A1 Harmonic A2 Harmonic V1N Harmonic V2N

non

A1(CH1) AN A3 AAVG Demand A1 Demand AN Demand A3 Demand AAVG

V1N(CH2) V3N V13 VAVG W(CH3) var VA PF(CH4) Hz Harmonic A1 Harmonic A3 Harmonic V1N Harmonic V3N

non A(CH1) Demand A V(CH2) W(CH3) var VA PF(CH4) Hz Harmonic A Harmonic V

AVGAverage, Total RMS Value

Analog output CH1

output item

Note 1:The same measurement item can be set for each analog output. Note 2:It is possible to select measurement item that are not included in the set display pattern. Note 3:Setting to "non" are minimum output. In addition, it moves to the next analog output setting. Note 4:Underlined portions are the factory default settings for measurement elements assigned to each

analog output. Note 5:VA is output by scaling 0 to 100% of the rating. Note 6:When Frequency(Setting menu 1.5) is set to 50Hz, Hz is output by a scale form 45Hz to 55Hz. When Frequency(Setting menu 1.5) is set to 60Hz, Hz is output by a scale form 55Hz to 65Hz. Note 7:For the harmonic current, the total RMS value is output by a scale from 0 to 60%of the rating. For the harmonic voltage, the total distortion ratio is output by scaling 0 to 20%.

SETDISPLAY

SETDISPLAY

Set the setting menu number to 6. (as shown in the right figure)

Setting menu

3. Setting

40

3.9. Setting Menu 6: Setting the Analog Output

Analog output CH2-CH4 detailed setting

The setting method is the same as Analog output CH1 detailed setting .

CH1

Analog output CH2 to CH4 detailed settings

Set the measurement item that is output to analog output CH2 to CH4.

The setting method is the same as Analog output CH1 output item .

Analog output CH2 to CH4

measurement item

SETDISPLAY

SETDISPLAY

SETDISPLAY

Analog output CH1 detailed setting

(The following setting can be made separately from the measurement items included in the display pattern.) (1)Set the current / current demand / voltage / active power / reactive power /

power factor for analog output.(Setting menu 6.1.1)

Output item Setting range *2

A Demand A

Primary Current (1.4.1 Primary Current Setting value)

SP.(Special Setting)

V

W var

PF -0.5 to 1 to 0.5 -0 to 1 to 0

(2)Set the current / current demand / active power for analog output.

(Setting menu 6.1.2)

Output item Setting range *2

A Demand A

W Single deflection Double deflection

Analog output CH1 detailed setting

*1. When var or PF are set as output items, it moves to the next analog output settings. *2. Detailed setting values are according to the values shown in the table on Section 6.3.

0 STEP (100% Rating)

-10 STEP (About 40%)

+3 STEP (About 120%)

0 STEP (100% Rating)

-18 STEP (About 20%)

+ 3 STEP (About 120%)

mA

4

12

20

-40kW 40kW 0

Double deflection

mA

4

20

40kW 0

Single deflection

To next CH settings

1

mA

4

12

20

-0.5 0.5 1

mA

4

12

20

-0 0 1

0 STEP (100% standard maximum scale value)

-18 STEP (About 20%)

+10 STEP (About 250%)

SETDISPLAY

SETDISPLAY

3. Setting

41

3.9. Setting Menu 6: Setting the Analog Output

Set analog output for when full scale is over the limit.The same in all the CH

Setting value Description

oFF (No limit)

For the span value, the maximum output is +5% and the minimum output is -5%.

on (Limited)

For the span value, the maximum output is +1% and the minimum output is -1%.

Note: When the output items for all analog output are set to "non," this setting is skipped.

Analog output limit

20 mA

oFF5%

on 1%

oFF5%

on 1%

4 mA

SET

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu.

Setting Menu

3. Setting

42

3.10. Setting Menu 6: Setting the Logging function

This section shows how to set the logging function. When the ME-0000BU-SS96 optional plug-in module is not installed, this menu will be skipped.

In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.

SET RESET

Set the ID number of the optional plug-in module: ME-0000BU-SS96.

Settable ID 001 to 255

When ID number installed of the optional plug-in module is set, that ID number is appeared as the initial value.

Note If ME96SS cannot receive the setting value of logging ID from ME-0000BU-SS96, the screen does not appear. Just wait there for a moment.

Logging ID

SETDISPLAY

Set the setting menu number to 6. (as shown in the right figure)

Setting Menu

Clears logging data memorized in optional plug-in module: ME-0000BU-SS96.

no yES (Not clear) (Clear) When yES(Clear) is selected at the above setting, the confirmation screen appears in order to reconfirm whether the logging data can be cleared or not.

no yES (Not clear) (Clear)

Logging Data Clear

Set the Logging-item pattern to select the logging items.

Settable pattern LP01 LP02 LP00

When LP00 is set, you can choose any 6-item. (For details of LP00, refer to following manual: ME-0000BU-SS96:Logging specifications ............ LSPM-0092)

The logging-item pattern of LP01 and LP02 is defined as follows. Detailed data is memorized shorter cycle than One-hour data.

Logging cycle of Detailed data is set in Detailed data logging cycle .

Phase-wire setting: 3P4W Logging-item

pattern

LP01 LP02

Detailed data One-hour data Detailed data One-hour data

Data 1 Wh(import) Wh(import) Wh(import) Wh(import)

Data 2 varh(import LAG) Wh(export) AAVG Wh(export)

Data 3 VAh varh(import LAG) VAVG(L-L) varh(import LAG)

Data 4 DW varh(import LEAD) W varh(import LEAD)

Data 5 Dvar VAh PF VAh

Data 6 DVA - Hz -

Phase-wire setting 3P3W_2CT, 3P3W_3CT, 1P3W

Logging-item pattern

LP01 LP02

Detailed data One-hour data Detailed data One-hour data

Data 1 Wh(import) Wh(import) Wh(import) Wh(import)

Data 2 varh(import LAG) Wh(export) AAVG Wh(export)

Data 3 VAh varh(import LAG) VAVG varh(import LAG)

Data 4 DW varh(import LEAD) W varh(import LEAD)

Data 5 Dvar VAh PF VAh

Data 6 DVA - Hz -

Logging-item

pattern

SETDISPLAY

SETDISPLAY

SETDISPLAY

3. Setting

43

3.10. Setting Menu 6: Setting the Logging function

LP01LP02

1min 5min 10min 15min 30min

Continued from the previous.

Phase-wire setting 1P2W

Logging-item pattern

LP01 LP02

Detailed data One-hour data Detailed data One-hour data

Data 1 Wh(import) Wh(import) Wh(import) Wh(import)

Data 2 varh(import LAG) Wh(export) A Wh(export)

Data 3 VAh varh(import LAG) V varh(import LAG)

Data 4 DW varh(import LEAD) W varh(import LEAD)

Data 5 Dvar VAh PF VAh

Data 6 DVA - Hz -

Set the logging cycle of detailed data when Logging-item pattern is LP01 or LP02.

1min 5min 10min 15min 30min

Detailed data

Logging cycle

SET

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu.

Setting Menu

3. Setting

44

3.11. Setting Menu 7: Setting Periodic Active Energy, Rolling Demand, and Digital

Input/Output Set the periodic active energy, rolling demand, and digital input/output. In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.

For more details about each function, refer to the corresponding pages.

Periodic Active Energy page 72, Rolling Demand page 73, digital input/ output page 75

Set the setting menu number to 7.

(as shown in the right figure) Setting menu

SET RESET

Set on or off of the periodic active energy display that enables

display of the electric energy divided into two time segments.

oFF on

Not displayed Displayed

Periodic Active

energy display

Set the control method to switch between time segments of periodic active energy.

When without the optional plug-in module, with ME-0000MT-SS96 or ME-0000BU-SS96, no item related to DI is displayed.

Control setting for

switching time segments of periodic active energy

Non:Not switched, COM.:Communication control,

d.in1:Digital input DI1, d.in2:Digital input DI2

non COM. d.in1 d.in2

Note1When the ME-4210-SS96 optional plug-in module is installed, d.in2 will be skipped.

The d.in1 set Rolling demand time setting, no item related to DI is displayed.

Note2When the ME-0040C-SS96 and ME-0052-SS96 the optional plug-in module is installed,

this display will be skipped of Rolling demand time setting set DI.

Set on or off of the rolling demand display.

oFF on

Not displayed Displayed

Rolling demand

display

Set the rolling demand time. When without the optional plug-in module, with ME-0000MT-SS96 or ME-0000BU-SS96, this display will be skipped.

Rolling demand

time setting

Manual Digital input DI1 Digital input DI2

oFF d.in1 d.in2

Note1When the ME-4210-SS96 optional plug-in module is installed, d.in2 will be skipped.

The d.in1 set Control setting for switching time segments of periodic active energy,

this display will be skipped.

Note2When the ME-0040C-SS96 and ME-0052-SS96 the optional plug-in module is installed,

this display will be skipped of Control setting for switching time segments of periodic

active energy set DI.

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

3. Setting

45

3.11. Setting Menu 7: Setting Periodic Active Energy, Rolling Demand, and Digital

Input/Output

SETDISPLAY

SET

Set on or off of the digital input/output display. When without the optional plug-in module, with ME-0000MT-SS96 or ME-0000BU-SS96, this display will be skipped.

oFF on

Not displayed Displayed

Digital

input/output display

Set the method to reset the digital input. When without the optional plug-in module, with ME-0000MT-SS96 or ME-0000BU-SS96, this display will be skipped.

Reset method

(Setting value)

Description (For details, refer to page 75.)

Auto (Auto)

When the digital input is turned to OFF (opened), the digital input state is automatically turned to OFF (opened).

Latch (HoLd)

When the digital input detects ON (closed) once, even if the digital input is turned to OFF (opened), the digital input state is retained as ON (closed) until the operation of releasing the latch is performed.

Note

When the ME-4210-SS96 optional plug-in module is installed, the d.in1

set Control setting for switching time segments of periodic active energy

or Rolling demand time setting, this display will be skipped.

Digital input reset

method

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu.

Setting Menu

3. Setting

46

3.12. Setting Menu 8:Special Settings (Setting Operation Time, Phase Display, IEC Mode) Set the operation time, phase display, IEC mode.

In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.

For more details about each function, refer to the corresponding pages.

Operation time page 74

Set the target for counting Operation time threshold.

When the auxiliary power (AUX) is selected for the Operation time, this display will be skipped.

1When current is set target for counting Operation time.

*:If min is selected, the Operation time will be counting when

display of current is not 0A.

2When voltage is set target for counting Operation time.

*:If min is selected, the Operation time will be counting when

display of voltage is not 0V.

Operation time

threshold

min 1 to 120%

Setting step 1%

min 20 to 120%

Setting step 1%

Set the setting menu number to 8. (as shown in the right figure)

Setting menu

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

SET RESET

Set on or off of the Operation time display that integrates the time while the target for counting is input and display it as the load Operation time.

Operation time

display oFF on

Not displayed Displayed

Select the target for counting Operation time from

the auxiliary power, current, and voltage.

Item 3-phase 4-wire 1-phase 2-wire Others

AUX AUX AUX AUX

A AAVG A AAVG

V VAVGL-N V VAVGL-L

Target for counting

Operation time setting

Auxiliary power Current Voltage

AUX A V

3. Setting

47

3.12. Setting Menu 8: Special Settings (Setting Operation Time, Phase Display, IEC Mode)

SETDISPLAY

SET

Set the phase display.

Phase display

setting 123 abc

By the setting of this mode, the following calculation methods and signs are changed.

Reactive energy counting method. (Refer to page 69)

Each measurement item display during power transmission.

(Refer to page 69)

Display of rolling demand (Refer to page 73)

Appendix : Calculation methods of ME96SS (Refer to page 106)

Set IEC mode

oFF on

(Normal mode) (IEC mode)

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu.

Setting Menu

3. Setting

48

3.13. Setting Menu CL: Present Time Settings for Data Logging Set the present clock time for data logging when installed the optional plug-in module: ME-0000BU-SS96. The present clock time should be set before operating the system.

In the operation mode, press and simultaneously for 2 seconds or more, and the following operation becomes available.

CAUTION

All logging data of ME-0000BU-SS96 are erased when you change the setting of Present time

more than 31days from the time displayed Present time display. Before changing the setting of

present clock time, output the logging data to the SD memory card and check the output data in the

PC whether the logging data are memorized properly.

Displays present time maintained in ME-0000BU-SS96. To change present time, press button. If ME96SS cannot receive the clock data from ME-0000BU-SS96, the right screen appears. Just wait there for a moment.

Present time

display

SET

SET RESET

Set the setting menu number to CL. (as shown in the right figure)

Setting menu

SET

SETDISPLAY

Set Month.

Setting range: Jan.(January) to Dec.(December) Present time setting

(Month)

SETDISPLAY

Set Day.

Setting range: 01 to 31 Present time setting

(Day)

SETDISPLAY

Set Year.

Setting range: 2016 to 2099 Present time setting

(Year)

SETDISPLAY

3. Setting

49

3.13. Setting Menu CL: Present Time Settings for Data Logging

Set Minute

Setting range of the tens place: 0 to 5

Setting range of the ones place: 0 to 9

Present time setting

(Minute)

Screen example of setting the tens place

SET

Set Hour.

Setting range: 12 AM 1 AM 2 AM 11 AM

12 PM 1 PM 2 PM 11 PM

Present time setting

(Hour)

SETDISPLAY

According to the setting flow (page 16 to 21), save the changed contents, or continue to the other setting menu.

If the E05 appears in the lower-line as the right screen, clock time setting will be incorrect. (For example, Month setting is February and Day setting is 31.) After that, please press ,review the setting value and set

it once again from Present time setting (Day) .

Setting Menu

SET

Error code

3. Setting

50

3.14. Setting Value Confirmation Menus 1-9: Confirming the Settings in the Setting Menus 1-8

and Test Mode in Setting Menu 9

Setting Value Confirmation

When is pressed for at least 2 seconds in the operation mode, the following operation becomes available.

Test Mode

Press for 2 seconds to move the set values confirmation mode.

Select setting value confirmation menu number 9. Press to move to test mode.

For more information about how to use the Test Mode, refer to page 57 or later.

SET

SET

SET

The screen transitions and operations are the same as for

Setting Menus 1 to 8 and CL.

Refer to Setting Menus 1 to 8 and CL (pages 22 to 49).

(Note: Settings cannot be changed in the Setting value

confirmation mode.)

Setting value confirmation menu

3. Setting

51

3.15. Initializing Related Items by Changing Settings When a setting value is changed, the related setting items and measurement data (maximum/minimum values) will return to the default settings. Refer to the following list.

Setting item to be changed

Initialized item

Menu 1 Menu 2 Menu 5 Menu 6 Menu 8

C h a n g e o

f o p ti o

n a l p lu

g -i n

m

o d u le

P h a s e w

ir e s

y s te

m

(* 1 )

V T

/ d

ir e c t v o lt a g e

CT current

M O

D B

U S

T

C P

D e fa

u lt

g a te

w a y e

x is

te n c e

C o m

m u n ic

a ti o

n R

e s e t

U p p e r/

lo w

e r

lim it a

la rm

i te

m

A n a lo

g o

u tp

u t

it e m

T a rg

e t fo

r c o u n ti n

g

O p e ra

ti o

n t

im e

S e tt in

g o

f IE

C m

o d e

C T

s e c o n d a ry

c u rr

e n t

C T

p ri m

a ry

c u rr

e n t

S e tt in

g i te

m

Menu 1

Phase wire system

Display pattern

VT/direct voltage

Menu2 MODBUSTCP Default gateway

Menu 3

Current scale

Voltage scale

Power scale

Reactive power scale

Menu 5 Upper/lower limit alarm item

Upper/lower limit alarm value

Menu 6

Analog output item

Maximum current scale

Maximum current demand scale

Maximum voltage scale

Maximum active power scale

Active power single deflection/

double deflection

Maximum reactive power scale

Power factor

-0.5 to 1 to 0.5-0 to 1 to 0

Menu 7

Control setting for switching Periodic

Active energy time segments

Setting of rolling demand digital input

time period

Menu 8 Threshold for counting Operation time

M e

a s u re

m e

n t d a ta

Current Maximum/minimum value

Current demand Maximum/minimum value

Voltage Maximum/minimum value

Active power Maximum/minimum value

Reactive power Maximum/minimum value

Apparent power Maximum/minimum value

Power factor Maximum/minimum value

Frequency Maximum/minimum value

Harmonic current Maximum value

Harmonic voltage Maximum value

Rolling demand(DW,Dvar,DVA) Maximum

value

Communication optional plug-in module reset (*2)

The setting value will be reset to the default value. The setting will be reset to the value corresponding to the phase wire system. *1: The settings will not return to the default values when the setting is switched only between 1N2 display and 1N3 display in the 1-phase 3-wire setting. *2: Communication optional plug-in module is reset.

3. Setting

52

3.16. Initializing All Settings

When the following operations are executed, all settings are initialized to the factory defaults. Only the settings are initialized to the defaults. The measured active energy value and operating time etc. are not initialized.

For the initializing of maximum/minimum value, refer to the section 3.15 (page 51). (For example, if the phase wire system is changed by initializing all settings, all maximum/minimum values will be initialized.)

To initialize all settings to the factory defaults, execute the following operation from the CANCEL screen in the setting mode.

For more information about how to get to the CANCEL screen, refer to 3.1.Setting flow (page16).

Setting mode Initialization completed

Press the +

for 2 seconds.

Note Before initializing all settings, output the logging data of ME-0000BU-SS96 to the SD memory card and check the output data in the PC whether the logging data are memorized properly.

RESET PHASE

CANCEL screen Measurement screen

3. Setting

53

3.17. Setting the Special Display Pattern P00

Even if there is no display pattern that you like in the display patterns P01 to P13, individual setting is available by the

display pattern P00.

This setting is made in the setting menu 1. Explanation begins with the set P00 in display pattern of the

setting menu 1 (page 22). (Others are omitted here, so refer to the setting menu 1.)

1The number of settable display is up to 4. And the number of measurement elements to be displayed is

up to 12 items.

2Explanation is made with the example of the following display pattern.

3Setting method

DISPLAY

Upper stage: item 1

Middle stage: item 2

Lower stage: item 3

Upper stage: item 4

Middle stage: item 5

Lower stage: item 6

Upper stage: item 7

Middle stage: item 8

Lower stage: item 9

Upper stage: item 10

Middle stage: item 11

Lower stage: item 12 DISPLAY DISPLAY DISPLAY

Screen 4-1 Screen 4-4 Screen 4-3 Screen 4-2

DISPLAY

Upper stage: A

Middle stage: V

Lower stage: Wh

Upper stage: PF

Middle stage: W

Lower stage:Non DISPLAY

Screen 2-1 Screen 2-2

Set the display pattern.

1Select P00 .

Select P00 by or and press .

2Set the upper stage of the display 4-1 to A.

Select A by or and press .

3Set the middle stage of the display 4-1 to V.

Select V by or and press .

4Set the lower stage of the display 4-1 to Wh.

Select Wh by or and press .

Display pattern

SET

SET

SET

SET

SET

SET

SET

SET

3. Setting

54

3.17.Setting the Special Display Pattern P00

(hereafter same as the setting menu 1)

Note

1. The following measurement items cannot be set by the display pattern P00. Set them separately in the Setting menu 3, Setting menu 7 and Setting menu 8.

Reactive energy (imported LEAD), Reactive energy (exported LAG), Reactive energy (exported LEAD), Harmonic current, Harmonic voltage, Periodic active energy, Rolling demand, Digital input, Digital output, Operation time

2. The phases of current and voltage cannot be specified. Press the button in the operation mode for switching phases.

3. For the settings other than the 3-phase 4-wire setting, the following measurement items cannot be set.

N-phase current, N-phase current demand, apparent power, apparent energy

Continued form the previous page

5Set the display of the display 4-2.

Select yES by or and press .

When you do not want to display the display 2, select no and press .

6Set the upper stage of the display 4-2 to PF.

Select PF by or and press .

7Set the upper stage of the display 4-2 to W.

Select W by or and press .

8Set the lower stage of the display 4-2 to no display.

Set the unit code of the lower stage to no display

by or and press .

9Set the display 4-3 to no display.

Select no by or and press .

Note: When the display 4-3 is set to no display, the

display 4-4 is also set to no display automatically.

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

VT / direct voltage

DISPLAY

Returns to the setting for the upper stage of the display 4-1.

PHASE

3. Setting

55

3.18. Examples of Simple Settings

The following shows a simple setting example.

Setting Example Model: ME96SSRA-MB(Not optional plug-in unit)

Phase wire system : 3-phase 4-wire

Measuring element : A, V, W, PF

Input Voltage :220/380V

CT primary current : 200A

CT Secondary current:5A

frequency :50Hz

MODBUSRTUaddress 1, baud rates 19.2kbps, parity even, stop bit 1

Setting Procedure

Items of which setting value need to be changed are indicated by .

Operation mode

Set the setting menu number to "1" and then press S E T . Setting menu

The factory default setting is "3-phase 4-wire," so just press SET. Phase wire system

Setting is "P01," so just press SET. Display pattern

The factory default setting is "No VT," so just press SET. VT/direct voltage selection

The factory default setting is "220/380V," so just press . Direct voltage

The factory default setting is "5A," so just press SET. CT secondary current

Set to "200A" and then press SET. CT primary current

The factory default setting is "50Hz," so just press SET. frequency

The factory default setting is "15min/1min," so just press SET. Time constant for rolling demand

The factory default setting is "0 second," so just press SET. Time constant for current demand

Set the setting menu number to "2" and then press SET . Setting menu

SET

Note: For more details about setting contents, refer to pages 22 to 25.

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

Press simultaneously for 2seconds RESETSET

3. Setting

56

3.18. Examples of Simple Settings

The factory default setting is "1," so just press SET. MODBUS RTU

address

The factory default setting is "19.2kbps," so just press SET. MODBUS RTU

baud rates

The factory default setting is "EVEn(even)," so just press SET. MODBUS RTU

parity

The factory default setting is "1," so just press SET. MODBUS RTU

stop bit

Set the setting menu number to "End" and then press SET. Setting menu

Press SET again. The changed setting are determined. End screen

Measurement begins according to the settings you changed. Operation mode

SET

SET

SET

SET

SET

SET

57

4. Using Test Mode

Test mode includes functions that can be used for start-up of equipment. The following table shows what can be done in the test mode.

Test menu Description

1. Communication test For models with a communication function, it is possible to monitor fixed numerical data without measurement (voltage/current) input. Use this for checking with the host system.

2. Alarm output/Digital output

operation test

For functions with alarm output, it is possible to confirm alarm output (digital point output) without measurement (voltage/current) input. Use this for confirming

connection with the contacted device.

3. Zero span adjustment for

analog output

For functions with analog output, zero span adjustment can be done for analog output.

Adjust this when matching with the receiver side and when output changes.

4. Analog output operation test For functions with analog output, it is possible to confirm analog output operation without measurement (voltage/current) input. Use this for confirming connection with

the receiver.

5. Pulse output operation test

For functions with pulse output, it is possible to confirm pulse output operation without

measurement (voltage/current) input. Use this for confirming connection with the

receiver.

Test Procedure

Press for 2 seconds to move to the set value confirmation mode.

Select setting value confirmation menu number "9" by and .

Press to move to test mode.

Execute tests using each test menu. (Refer to pages 58 to 62)

Test Mode Flow

(Note) The screen momentarily turns off.

Note When moving the test mode, ME-0000BU-SS96 becomes power outage state not to be logging the test data.

Therefore, the system log of Power failure occurred is recorded in ME-0000BU-SS96 and COM of the LCD is

blinking.

Test menu 2 (Alarm output /Digital output operation test)

)

Test menu 3 (Zero span adjustment

for analog test)

Test menu 4 (Analog output operation test)

Test menu 5 (Pulse output operation test)

Operation

mode

Test mode

SET

SET

SET

SET

Setting value

Confirmation

menu "9"

Test menu

End

Note

Test menu 1

(Communication test)

4. Using Test Mode

58

4.1. Test Menu 1: Communication Test

In the setting value confirmation mode, when the menu number is set to "9", you will enter the test mode.

Select other test menu number and then press .

Select "End" as the test menu number and then press .

You will return to the operation mode.

Test menu

SET

SET

SET

SET

Set the test menu number to "1". (as shown in the right figure)

Test menu

Execute communication test operation. (Values other than zero can be monitored even when the voltage and current are not input.)

Monitor value by communication

Values displayed on the screen,can be monitored. Measurement elements not displayed on the screen are zero.

(only power factor is 1.000). If you set the Alarm item with Setting Menu 5, the display will be the same as

the alarm is generating.

If you are using the ME-4210-SS96, alarm contact will remain open.

It is possible to monitor the digital input status. Display screen

As with the operation mode, it is displayed according to settings such as the display pattern.

The maximum/minimum value can be displayed. (Cyclic display cannot be executed.)

Button operation

Operation Function

Press Switches the display screen.

Press Switches the phase.

Press Moves or returns to the maximum/minimum

value screen.

Press or

Switches the analog bar graph element.

Switches the harmonic degree (when

harmonics screen is displayed).

Press and together for at least 2 seconds.

Change the unit of Wh, varh and VAh.

Press Return to the test menu.

Note: When executing a communication test, please read the following manual

in addition to this instruction manual. (For more information refer to page 102.)

Electronic Multi-Measuring Instrument ME Series MODBUS Interface specifications

Electronic Multi-Measuring Instrument Programming Manual (CC-Link communication)

Communication test

DISPLAY

SET

PHASE

MAX/MIN

4. Using Test Mode

59

4.2. Test Menu 2: Alarm Output/Digital Output Operation Test

The following operations are available in the test mode.

When the ME-4210-SS96 or ME-0052-SS96 optional plug-in module is not installed, this test menu will be skipped.

When Pulse/Alarm output 1(Setting Menu 5) and Pulse/Alarm output 2(Setting Menu 5) is not set to "AL",

this test menu will be skipped.(ME-4210-SS96)

Select other test menu number and then press .

Select "End" as the test menu number and then press .

You will return to the operation mode.

Test menu

SET

SET

Execute the alarm output/digital output CH2 operation test.

The test method is the same as

Alarm output/Digital output CH1 operation test . Alarm output/Digital

output CH2 operation test

Note1: When Pulse/Alarm output 2(Setting Menu 5) is not set to "AL",

this display will be skipped.(ME-4210-SS96)

Execute the alarm output/digital output CH1 operation test. When is pressed for 2 seconds, digital output is switched back.

Alarm output/Digital

output CH1 operation test oFF on

(Open) (Close) Note1: To return to the test menu,

turn digital output OFF (open).

RESET

RESET Press for 2 seconds

Note2: When Pulse/Alarm output 1(Setting Menu 5) is not set to "AL",

this display will be skipped.(ME-4210-SS96)

The current output status is displayed.

Set the test menu number to "2".

Test menu

SETDISPLAY

SETDISPLAY

SET

4. Using Test Mode

60

4.3. Test Menu 3: Zero Span Adjustment for Analog Output

The following operations are available in the test mode.

When the ME-4210-SS96 optional plug-in module is not installed, this test menu will be skipped.

Select other test menu number and then press .

Select "End" as the test menu number and then press .

You will return to the operation mode.

Test menu

SET

SET

Execute span adjustment for analog output CH2 to CH4.

The adjustment method is the same as Analog Output CH1 Span Adjustment .

Analog output CH2 to

CH4 span adjustment

Execute zero adjustment for analog output CH2 to CH4.

The adjustment method is the same as Analog Output CH1 Zero Adjustment .

Analog output CH2 to

CH4 zero adjustment

Execute span adjustment for analog output CH1.

Possible setting range : -50 to 0 to +50

Adjustment is possible up to about 0.3mA

Span adjustment movement

Analog output CH1

span adjustment

Note: For span adjustment, measurement input is necessary.

mA

4

20

Input 0

Span adjustment value

mA

4

12

20

Input

0

Span adjustment value

Execute zero adjustment for analog output CH1.

Possible setting range : -50 to 0 to +50

Adjustment is possible up to about 0.3mA

Zero adjustment movement

Analog output CH1

zero adjustment

Note: For zero adjustment, set the measurement input to zero.

mA

4

20

Input 0

Zero adjustment value

Set the test menu number to "3".

Test menu

SET

SETDISPLAY

SETDISPLAY

SETDISPLAY

SETDISPLAY

4. Using Test Mode

61

4.4. Test Menu 4: Analog Output Operation Test

The following operations are available in the test mode.

When the ME-4210-SS96 optional plug-in module is not installed, this test menu will be skipped.

Select other test menu number and then press .

Select "End" as the test menu number and then press .

You will return to the operation mode.

Test menu

SET

SET

Execute the operation test for analog output CH2 to CH4.

The test method is the same as Analog output CH1 operation test .

Analog output CH2 to

CH4 operation test

Execute the operation test for analog output CH1. (Input is not necessary.)

Output Output Specification

4-20mA

0% 4mA

25% 8mA

50% 12mA

75% 16mA

100% 20mA

Analog output CH1 operation test

0%

25%

50%

75%

100%

Note: The analog output item set up with Setting the Analog Output(Setting Menu 6) is displayed.

Upper :Analog output 1 Middle :% value Lower :Setting analog output item

and the measurement value equivalent to the % value

Set the test menu number to "4".

Test menu

SETDISPLAY

SET

SETDISPLAY

4. Using Test Mode

62

4.5. Test Menu 5: Pulse Output Operation Test

The following operations are available in the test mode.

When the ME-4210-SS96 optional plug-in module is not installed, this test menu will be skipped.

When Pulse/Alarm output 1(Setting Menu 5) and Pulse/Alarm output 2(Setting Menu 5) is not set to "PULSE",

this test menu will be skipped.(ME-4210-SS96)

Select other test menu number and then press .

Select "End" as the test menu number and then press .

You will return to the operation mode.

Test menu

SET

SET

Set the test menu number to "5".

Test menu

SETDISPLAY

SET

SETDISPLAY

Execute the operation test for pulse output CH1. (Input is not necessary.) When is pressed, 1 pulse is output.

Pulse output CH1

operation test

0 1 2 49 50pulse

RESET

RESET

Note1: When Pulse/Alarm output 1(Setting Menu 5) is not set to "PULSE",

this display will be skipped.(ME-4210-SS96) Note2: Output is executed according to the set pulse width. Note3: After reaching 50, the number of output pulses returns to 1.

Upper :Pulse output 1 Middle :Pulse Unit set up with setting menu 5.9.2. Lower

Left :The number of output pulses

Right :(Pulse Unit)(The number of output pulses)

Execute the operation test for pulse output CH2.

The test method is the same as

Pulse Output CH1 Operation Test .

Pulse output CH2 operation test

Note: When Pulse/Alarm output 2(Setting Menu 5) is not set to "PULSE",

this display will be skipped.(ME-4210-SS96)

63

5. Operation

5.1. Basic Operation

The following explains basic usages during operation.

Switch display

By pressing , the measurement display will switch over.

By pressing + , the measurement display will switch over in reverse.

Switch phase

By pressing , the current phase and

the voltage phase will switch over.

Display items and the order differ depending on the phase wire method setting display pattern settings and additional screen. For more information about detailed display patterns, refer to pages 77 and 78.

The phase cannot be switched in the following cases.

Measurement elements without phase (Frequency)

Active power, reactive power, apparent power and power factor for settings other than 3-phase 4-wire

When the setting is 1-phase 2-wire

DISPLAY

PHASE

Example of phase switching (Phase wire System: 3-phase 4-wire)

Current average Active Power (total) Voltage average (line to neutral)

PHASE PHASEPHASE

PHASE PHASEPHASE

PHASE PHASE

Current phase 1 Active Power phase 1 Voltage phase 1N

Current phase 2 Active Power phase 2 Voltage phase 2N

Current phase 3 Active Power phase 3 Voltage phase 3N

Current average Active Power (total) Voltage average (line to line)

Current phase 1 Active Power phase 1 Voltage phase 12

Current phase 2 Active Power phase 2 Voltage phase 23

Current phase 3 Active Power phase 3 Voltage phase 31

Example of display switching(Phase wire System: 3-phase 4-wire,display pattern: P01, without additional display

Upper: Current Middle: Active Power Lower: Voltage

Upper: Current Middle: Active Power Lower: Power factor

Upper: Current Middle: Power factor Lower: Voltage

When switching screens, the left screen appears momentarily. This screen indicates the number of the next screen being displayed in the total number of screens.

Screen number display

DISPLAY

DISPLAYDISPLAYDISPLAY

Upper: Current Middle: Not displayed Lower: N-phase current

DISPLAYDISPLAYDISPLAY

DISPLAY

DISPLAY

5. Operation

64

5.1. Basic Operation

Bar graph display

Bar graph displays the measurement element indicated with or .

Switching measurement factors displayed on bar graphs

Press the or button to switch.

The following example is the case of 3 measuring items of screen are different or 2 measuring items of screen are same. In the case of 3 measuring items of screen are same, the bar graph of average value or total value appear instead of (Upper), (Middle) and (Lower).

(Example) Lower element (V)

displayed on bar graph (Example) PF displayed on

bar graph

The bar graph cannot be displayed in the following cases.

When active energy / reactive energy / apparent energy are selected

When a line without measurement display is selected

Rolling Demand Display

Harmonics Display

1For 3-phase 4-wire

2For 3-phase 3-wire, 1-phase 3-wire

3For 1-phase 2-wire

(Clockwise rotation) (Counterclockwise rotation)

W

var (Lower) (Middle) PF Hz

(Upper) W

var (Lower)

(Middle)

PF Hz

(Upper) A W

var

V

(Lower)

(Middle)

PF Hz

VAVG(LL) AAVG VAVG(LN)

AAVG VAVG

(Upper)

*1 *1

*1: LN,LL does not appear.

5. Operation

65

5.1. Basic Operation

Cyclic Display

In cyclic display, display and phases automatically change at every 5 seconds.

When is pressed for about 2 seconds, the cyclic display appears.

When is pressed for about 2 seconds, the cyclic phase appears.

By pressing any other buttons except , cyclic display mode ends.

Harmonics display

Harmonic RMS value and distortion ratio can be displayed. It is necessary to set the harmonics display settings before displaying.(Refer to page 32)

Measurement items

Degree Harmonic current N-phase harmonic current Harmonic voltage RMS value

Distortion ratio

RMS value

Distortion ratio

RMS value

Distortion ratio

Harmonic total

1st

3rd,5th,7th,9th, 11th,13th,15th, 17th,19th

Example Display

Note : Harmonic total is shown by ALL.

Note 1: Before shifting to the cyclic display change screen, the display flickering 3 times.

Note 2: In the cyclic display, drawing number is not displayed.

Note 3: In the maximum value and the minimum value display, cyclic display is not available.

Upper: Degree

Middle: Distortion ratio

Lower: RMS value

Example Cyclic Display (Phase wire System: 3-phase 4-wire, Display Pattern: P01, without additional screens)

DISPLAY

Press for 2 seconds

Changes automatically

Changes automatically

Changes automatically

Changes automatically

(Displays for 5 seconds) (Displays for 5 seconds) (Displays for 5 seconds) (Displays for 5 seconds)

DISPLAY

PHASE

SET

5. Operation

66

5.1. Basic Operation

Harmonics display (Continued from previous page)

Switching degree / phase (Phase wire System: 3-phase 4-wire)

Press the or button to switch the degree.

Press to switch phases.

Note: For harmonic measurement, the following phases are not displayed.

Phase wire system Harmonic current Harmonic voltage

3-phase 3-wire 3CT 31-phase

2CT 2-phase 31-phase

1-phase 3-wire 1N2 display N-phase 12-phase

1N3 display N-phase 13-phase

PHASE

Voltage 1st phase 3N

Voltage 19th phase 3N

Current 19th phase 3

Voltage total phase 3N

Current total phase 3

Harmonic voltage

Voltage total phase 2N

Voltage total phase 1N

Voltage 1st phase 2N

Voltage 1st phase 1N

Voltage 19th phase 2N

Voltage 19th phase 1N

Appears 3rd, 5th, 7th, 9th, 11th,

13th, 15th, 17th in order.

PHASE

Harmonic current

Current total phase 2

Current total phase 1

Current 19th phase2

Current 19th phase 1

Appears 3rd, 5th, 7th, 9th, 11th,

13th, 15th, 17th in order.

PHASE

DISPLAY

Harmonic current (phase N)

Current total phase N

Current 1st phase N

Current 19th phase N

Appears 3rd, 5th, 7th, 9th, 11th,

13th, 15th, 17th in order.

DISPLAYDISPLAYDISPLAY

Previous display

Next display

Current 1st phase 3

Current 1st phase 2

Current 1st phase 1

5. Operation

67

5.1. Basic Operation

Maximum value and minimum value display

For the maximum / minimum value display screen, the maximum value, current value, and minimum value for each measurement item are displayed on one screen.

However, for harmonics only the following maximum values are displayed. Harmonic current: Total, 1st to 19th (only odd number) effective values for where the phase was largest for each phase. Harmonic voltage: Total distortion factor, 1st effective value, 3rd to 19th (only odd number) content factors for where the phase was largest for each phase

Example Display

Display of maximum value and minimum value

When is pressed, the display is changed into the maximum value and minimum value display. And when is pressed, the display changes back to the present value display.

On maximum/minimum value display, the following operation is also possible as current value display.

Button operation Function

Press

Measurement items switch according

to the following order.

However, measurement items that are not included

in the phase wire method display pattern setting

and additional screens are not displayed.

Press

3-phase 4-wire: A and DA switch as

V switches as

W, var, VA, PF switch as

AN, DAN and Hz do not have phase switching.

3-phase 3-wire, 1-phase 3-wire: Phase for A, DA and V switch.

1-phase 2-wire: No phase switch.

Press or The harmonic degree switch. (Only for harmonics display)

Press for 2 seconds Switches to measurement item cyclic display.

Press for 2 seconds Switches to phase cyclic display. Clear the maximum/minimum value

On the maximum/minimum value display screen, press the for 2 seconds to clear the maximum/minimum

value for the displayed measurement item to the present value.

On the maximum/minimum value display screen, press the and together for 2 seconds to clear all

maximum/minimum values to the present value.

When the password protection setting is enabled, maximum/minimum values are cleared after you enter the password.

Also, you can clear all maximum/minimum values by communication function. (In this case, the password is not

necessary.)

AN: N-phase current DA: Current demand DAN: N-phase current demand HI: Harmonic current HIN: N-phase harmonic current HV: Harmonic voltage

MAX/MIN

RESET

RESET

MAX/MIN

Upper: Maximum value

Middle: Current value

Lower: Minimum value

Example of current Example of current harmonics The bar graph turns on only between the maximum value and minimum value.

Harmonic degree

Harmonics wont display as bar graph.

Maximum value

Example of switching between present value display and maximum/minimum value display

Present value display Maximum value and minimum value display

MAX/MIN

Average1 Phase2 Phase3 Phase

AANDADANVWvar

HVHINHIHzPFVA

VAVG(L-N)V1NV2NV3NVAVG(L-L)V12V23V31

Total1 Phase2 Phase3 Phase

DISPLAY

PHASE

DISPLAY

PHASE

5. Operation

68

5.1. Basic Operation

Active Energy / Reactive Energy / Apparent Energy Display

Display format The following table shows the display format of active energy / reactive energy / apparent energy based on the total load.

Total load power[kW] = x (VT primary voltage) x (CT primary current)

1000 1. For the direct voltage setting, the direct voltage is used for calculation instead of

the VT primary voltage.

2. For 3-phase 4-wire or 1-phase 3-wire, the VT primary voltage and direct voltage are calculated using the line to phase voltage.

Total load [kW] Display type

Digital Display Unit Less than 10

888888

kWh (Unit can be changed from

Wh/kWh/MWh.)

10 or higher and less than 100

100 or higher and less than 1000

1000 or higher and less than 10000 MWh (Unit can be changed from

Wh/kWh/MWh.)

10000 or higher and less than 100000

100000 or higher

* For reactive energy or apparent energy, read Wh as varh or VAh.

Example Display

Expanded counting setting of menu 3 is necessary in order to appear the screen of *1. (Refer to page 32)

Active energy (Imported)

Active energy (Exported) *1

Apparent energy

Reactive energy (Imported LAG)

Reactive energy (Imported LEAD) *1

Reactive energy (Exported LAG) *1

Reactive energy (Exported LEAD) *1

How to change the unit of Wh, varh and VAh

When and are pressed simultaneously for 2 seconds, the unit of Wh, varh and VAh will be changed. This will

enable to check the upper digits or lower digits of counts.

Note1: All of Wh, varh and VAh change to same unit even if these are not shown on the screen.

Note2: When the setting value of the VT primary voltage and the CT primary current are large, the lower digits less than a measurement

range display "0".

Wh, varh and VAh zero reset

When , ,and are pressed simultaneously for 2 seconds, the measured values of Wh, varh and

VAh will be reset.

When the password protection setting is enabled, Wh, varh and VAh are reset after you enter the password.

Also, you can clear all Wh, varh and VAh values by communication function. (In this case, the password is not

necessary.) Note 1: This is effective only in the instantaneous value display. Note 2: All of Wh, varh and VAh will be reset even if these are not shown on the screen. Note 3: The periodic active energy will not be reset. Another operation is necessary. (Refer to page 72)

1 1-phase 2-wire

2 1-phase 3-wire 3 3-phase 3-wire 3 3-phase 4-wire

PHASESET RESET

Example of change: Case of active energy (imported) = 012,345,678,901,234.567Wh

UnitMega Unitnon

(Lower digit enlarged)

Unitnon Unitkilo

Press and simultaneously for 2 seconds

The metering status blinks while the active energy is being counted. When active energy is not counted, turns OFF.

Active energy measurement value

Metering status

5. Operation

69

5.1. Basic Operation

Reactive energy counting method (2 quadrant counting / 4 quadrant counting)

There are the following two types of quadrants for counting reactive energy.

Counting

method Description

4 quadrant

counting

It is counting (Imported lag), (Exported lead),(Imported lead) and (Exported lag) respectively as division of one. In general, it is

counted by this method. However, at the boundary of each division, there is a dead region. It is suitable for the counting of

equipment with the private electric generator.

2 quadrant

counting

(Imported lag) and (Exported lead) are counted as division of one. (Imported lead) and (Exported lag) are counted as division

of one. The dead region is made only nearby var=0 (power factor = 1). Therefore, because the dead region is not made

nearby power factor = 0. It is suitable for the counting of equipment without the private electric generator and the reactive

power of the capacitor load at the power factor = 0, generally.

The counting method for reactive energy (varh) is switched by Expanded counting in the Setting Menu 3.

Also, if setting of IEC mode in the Setting Menu 8 is ON, the counting method becomes 2 quadrant counting regardless of Expanded counting in the Setting Menu 3.

If setting of Expanded counting is selected for 4 quadrant counting and setting of IEC mode is ON, the screens of exported lag and exported lag appear, but these are not counting.

(Refer to page 32 about Expanded counting in the Setting Menu 3. Refer to page 47 about IEC mode in the Setting Menu 8.)

Each measurement item display during power transmission

The following table shows the symbol display () for each measurement value according to the power reception /power sending status.

(Refer to page 32 about Expanded counting in the Setting Menu 3. Refer to page 47 about IEC mode in the Setting Menu 8.)

Quadrant

Measured items

Imported Lag Imported Lead Exported Lag Exported Lead

A,DA,N-A,N-DA,V,Hz,VA

HI,N-HI,HV Unsigned

W Unsigned sign

var

Normal mode

(For 2 quadrant counting)

Unsigned

display

sign

display

sign

display

Unsigned

display

Normal mode

(For 4 quadrant counting)

Unsigned

display

sign

display

Unsigned

display

sign

display

IEC mode

(For 2 quadrant counting)

Unsigned

display

sign

display

sign

display

Unsigned

display

PF

Normal mode

(For 2 quadrant counting)

Unsigned

display

sign

display

sign

display

Unsigned

display

Normal mode

(For 4 quadrant counting)

Unsigned

display

sign

display

Unsigned

display

sign

display

IEC mode

(For 2 quadrant counting)

Unsigned

display

sign

display

Unsigned

display

sign

display

Turns on when displayed on the bar graph.

W W W

var

var

Exported lag Imported lead

Exported lead Imported lag

W W

var

var

W W

var

var

<4 quadrant counting> <2 quadrant counting>

Exported lag Imported lead

Exported lead Imported lag

Exported lag Imported lead

Exported lead Imported lag

5. Operation

70

5.1. Basic Operation

Demand time and demand value of current demand

The demand time (to) is the time until the measurement display value (Io) displays 95% of the input (I) when a

certain constant input (I) is given. To display 100% of the input (I), about three times more than the time (to) is needed.

The demand value is the measurement display value with the above time characteristics, and it shows the overall average within the demand time. The demand value changes over a relatively long time, so it is not affected by input changes within a short time. Therefore, this is good for monitoring transformer overload.

M e a s u re

m e n t d

is p la

y v

a lu

e

Time (t) 0 t0

(Time period)

0.95

5. Operation

71

5.2. Usage According to Purpose (Alarm, Periodic Active Energy, Rolling Demand, Operating

Time, Password, etc.) The following explains usage according to the purpose during operation.

Display and operation of the upper/lower limit alarm

When the value exceeds the upper or lower limit setting value set in advance, the display flickers and alarm can be output. (For more information about how to set the upper/lower limit alarm, refer to page 34 and after.)

Alarm indicator

When the measurement element with an upper/lower limit alarm is displayed on the bar graph, "" flickers on the bar graph to indicate the upper/lower limit.

Behavior During Alarm Generation

Alarm condition: When measurement value exceeds alarm value, display flicker and an alarm contact closes. Alarm cancel: When alarm is canceled, display flickers normally and alarm contact opens.

Note: When the alarm delay time is set, an alarm is generated only when the alarm value is continuously beyond the upper/lower limit alarm value for the delay time.

Alarm cancel method Measurement value Upper limit value

(or Measurement value Lower limit value) Measurement value < Upper limit alarm value

(or Measurement value > Lower limit alarm value)

Automatic

(Auto)

Display

, or or flickers

Normal display

Output (Alarm

relay contact) Closed Opened

Manual(

HoLd)

Display

, or or flickers

(Alarm generation)

, or turns ON

(Alarm retention)

Normal display

(Alarm cancellation) Output (Alarm

relay contact) Closed Closed Opened

Note 1: When the measurement element where the alarm generated exists on the display screen, the display for the digital

value, unit (A, V, W, var, PF, Hz, %, DM,THD), and phase (1, 2, 3, N) will be based on the alarm status according

to the following table. If it does not exist on the display screen, it does not flicker. Alarm status Digital value Unit Phase

Alarm generation Flickering* Flickering Flickering*

Alarm retention On Flickering Flickering*

Alarm cancellation On On On

Note 2: When the backlight flickering setting is set to ON (flicker) during alarm generation, the backlight also flickers when

an alarm is generated. Note 3: On the maximum/minimum value display screen, the present value (middle of the digital display) and , or blinks.

Monitoring phase for upper/lower limit alarm element

The phase that monitors the upper/lower limit alarm differs according to the measurement item. For more details, refer to the following table.

Upper/lower limit alarm element Monitored phase

3-phase 4-wire 3-phase 3-wire

(3CT,2CT) 1-phase 3-wire

(1N2) 1-phase 3-wire

(1N3)

Upper limit current, current demand 1, 2, 3 1, 2, 3 1, N, 2 1, N, 3

Lower limit current, current demand 1, 2, 3 1, 2, 3 1, 2 1, 3

Upper limit N-phase current, N-phase current demand N

Lower limit N-phase current, N-phase current demand N

Upper limit voltage (L-L) (Note 1) 12, 23, 31 12, 23, 31 1N, 2N, 12 1N, 3N, 13

Lower limit voltage (L-L) (Note 1) 12, 23, 31 12, 23, 31 1N, 2N, 12 1N, 3N, 13

Upper limit voltage (L-N) 1N, 2N, 3N

Lower limit voltage (L-N) 1N, 2N, 3N

Upper limit active power, reactive power, power factor Total Total Total Total

Lower limit active power, reactive power, power factor Total Total Total Total

Upper limit frequency 1N 12 1N 1N

Lower limit frequency 1N 12 1N 1N

Harmonic current total RMS value 1, 2, 3 1, 2, 3 (note 2) 1, 2 1, 3

Harmonic current total RMS value N-phase N

Harmonic voltage total distortion ratio 1N, 2N, 3N 12, 23 1N, 2N 1N, 3N

Upper limit rolling demand Total Total Total Total

Note1: For phase 12 (or phase 31) at 1-phase 3-wire, alarm monitoring is executed using a value that is two times the set upper/lower limit alarm value. Note2: Only 3-phase 3-wire (3CT) is measured for the phase 2 harmonic current.

* Does not flicker when displaying phases where no alarm occurred.

RESET

Upper/lower limit indicator

5. Operation

72

5.2 Usage According to Purpose (Alarm, Periodic Active Energy, Rolling Demand, Operating

Time, Password, etc.)

Canceling the upper/lower limit alarm

The alarm cancellation method differs depending on the setting for alarm reset. The upper and lower limit alarms can be cancelled also via communication.

Alarm cancel method Cancelation method

Automatic(Auto) When the measurement value is below the upper/lower limit set value, the alarm is automatically reset.

Manual(HoLd)

The alarm is maintained even after the measurement value is below the upper/lower limit set value. After the measurement value is below the upper/lower limit alarm value, operate the following alarm cancellation operation. (Note: However, alarms cannot be cancelled from the maximum/minimum value display screen, or the digital input/output screen.) Display the element where the alarm generated, and then press to cancel the alarm. When an element has a phase such as current and voltage, it is necessary to press for each phase when cancelling an alarm. At the current value display screen, press for 2 seconds to cancel all alarms.

Note: The difference of 0.8% between the maximum scale and alarm value is used for determining whether the measurement value is below the upper/lower limit alarm value in order to prevent chattering.

Stopping backlight flickering caused by upper/lower limit alarm generation

Press the button to stop the backlight flickering.

Upper/lower limit alarm items on the alarm contacts

Setting Alarm item for alarm output

Contact output function 1

Contact output function 2

C1A and C1B terminals C2A and C2B terminals

Alarm output Alarm output Alarm item 1 Alarm items 2-4 (output collectively with either of them)

Alarm output Pulse output Alarm items 1-4 (output collectively with either of them)

No alarm

Pulse output Alarm output No alarm Alarm items 1-4 (output collectively with either of them)

Pulse output Pulse output No alarm No alarm

Display of periodic active energy

The ability to measure the active energy divided into two time segments enables individual measurement of the active energy in a desired time segment such as peak/off-peak and day/night. The periodic active energy is counting, even if the periodic active energy display setting is OFF.

(For the setting of the Periodic active energy display, refer to page 44.)

This is displayed when the button is pressed repeatedly in the operation mode to switch the measurement displays.

Resetting periodic active energy to zero

Showing the periodic active energy 1 or 2 on the display and holding down the button for 2 seconds reset the periodic active energy to zero. (Only the displayed periodic active energy is reset.) When the password protection setting is enabled, the periodic active energy is reset to zero after the password is entered. The periodic active energy can be individually or simultaneously reset to zero via communication. (In this case, the password is not necessary)

RESET

RESET

RESET

DISPLAY

RESET

The time segments can be switched according to the setting via communication or the digital input (DI). (The time segments cannot be switched manually (button operation).)

When the selected bit is ON (1), the active energy (Imported) is

added to the periodic active energy n (where n = 1, 2).

When the selected bit is OFF (0), the active energy (Imported) is not

added to the periodic active energy n (where n = 1, 2).

When there is no digital input (DI), the active energy (Imported) is

added to the periodic active energy 1 and the active energy (Imported) is not added to the periodic active energy 2.

When there is digital input (DI), the active energy (Imported) is not

added to the periodic active energy 1 but the active energy (Imported) is added to the periodic active energy 2.

The active energy (Imported) is added to the periodic active energy 1

and periodic active energy 2. (No switching between time segments)

Periodic active energy 1 Periodic active energy 2

RESET

5. Operation

73

5.2 Usage According to Purpose (Alarm, Periodic Active Energy, Rolling Demand, Operating

Time, Password, etc.)

Display and calculation of rolling demand

The rolling demand is the value obtained by dividing the active energy/reactive energy/apparent energy (*1) in a specified time (interval) by the length of the interval. The block interval demand is to select the time width (interval) of the block used for the demand calculation. (For setting of the rolling demand display, refer to page 44.)

This is displayed when the button is pressed repeatedly in the operation mode to switch the measurement displays. *1: The energy counting used the calculation of the rolling demand are as follows.

Item Setting of IEC mode

Remarks Normal mode IEC mode

Rolling demand W (DW) Active energy(import) Active energy(import) - Active energy(export)

Rolling demand var (Dvar) {Reactive energy(Imported lag) + Reactive energy(Exported lead)}

{Reactive energy(Imported lag) + Reactive energy(Exported lead)} -{Reactive energy(Exported lag) + Reactive energy(Imported lead)}

Refer to the below picture.

Rolling demand VA (DVA) Apparent energy

DISPLAY

Rolling block

The rolling block is to select the interval and sub-interval from 1- to 60-minute intervals (by minutes) and calculate and update the rolling demand at the end of each subinterval.

Example when the interval is 15 minutes and the subinterval is 5 minutes

Fixing block

The fixing block is to select the interval from 1- to 60-minute intervals (by minutes) and calculate and update the rolling demand at the end of each interval. (For the fixing block, the interval time and subinterval time should be the same.)

Example when the interval and subinterval are 15 minutes respectively

demand> The rolling demand is calculated when the

subinterval time completes.

The displayed rolling demand is the value of the latest interval time

completed.

15 minutes

5 minutes

0 5 10 15 20 25 Time (minutes)

The rolling demand

is calculated when the subinterval time completes.

The displayed rolling demand is the value of the latest interval time

completed.

15 minutes 15 minutes

0 15 30 Time (minutes)

Note. Immediately after the adjusting rolling demand time is set, the demand time timer starts at "0 minute."

Note. Immediately after the adjusting rolling demand time is set, the demand time timer starts at "0 minute."

W W

var

var

Exported lag Imported lead

Exported lead Imported lag

5. Operation

74

5.2 Usage According to Purpose (Alarm, Periodic Active Energy, Rolling Demand, Operating

Time, Password, etc.)

Adjusting rolling demand time

Showing the rolling demand on the display and then holding down the and buttons at the same time for 2 seconds or more allows adjustment of the rolling demand time. (Even if adjustment of the demand time is set to Digital input, the demand time can be adjusted manually (by button operation).) When the password protection setting is enabled, the demand time can be adjusted after the password is entered. The rolling demand time can be adjusted also via communication although the setting item is not provided in the demand time adjustment setting. (In this case, the password is not necessary) Select whether to adjust or not the demand time.

Resetting the peak value of rolling demand

Showing the rolling demand on the display and then holding down the and buttons at the same time for 2 seconds reset the peak value of rolling demand. When the password protection setting is enabled, the peak value of rolling demand is reset after the password is entered. The rolling demand can be reset also via communication. (In this case, the password is not necessary)

Display of operation time

The measurement time is integrated according to the value set to the target for counting operation time (AUX, A, and V) and displayed as the load operation time. To display the operation time, the operation time display setting should be configured in advance. The operation time is counting, even if operation time display setting is OFF. (For setting of the operation time display, refer to page 46.)

This is displayed when the button is pressed repeatedly in the operation mode to switch the measurement displays.

Resetting the operation time to zero

Showing the operation time 1 or the operation time 2 on the display and then holding down the button for 2 seconds resets the operation time to zero. (Only the displayed operation time is reset to zero.) When the password protection setting is enabled, the operation time is reset to zero after the password is entered. All the operation times can be reset to zero also via communication. (In this case, the password is not necessary)

RESET

no yES

Not adjust Adjust SET

Display for adjustment of the demand time Operation mode Operation mode

Hold down at the same time for 2 sec.

RESET

DISPLAY

Operation time 1 Operation time 2

When the following set target for counting the operation time exceeds the threshold, the operation time 1 and operation time 2 are integrated.

For example, if you want to check both of the operation time on a monthly basis (the value which is periodically reset) and the cumulative operation time from when the system started to operate (the value which is not periodically reset), use the operation time 1 and operation time 2 accordingly. If it is unnecessary to use the operation time 1 and operation time 2 at the same time, monitor either of them.

Using the operation time 1 and operation time 2 as appropriate

Item 3-phase 4-wire 1-phase 2-wire Others

AUX (Auxiliary power)

AUX AUX AUX

A (Current) AAVG A AAVG

V (Voltage) VAVGL-N V VAVGL-L

5. Operation

75

5.2 Usage According to Purpose (Alarm, Periodic Active Energy, Rolling Demand, Operating

Time, Password, etc.)

Display and operation of digital input/output status

The digital status can be displayed by inputting the switching signal of the breaker and the alarm signal of the over current relay to the digital input (DI) terminal. The digital output (DO) terminal opens and closes the contact by communication control. To display the digital input/output status, the digital input/output status display setting should be configured in advance. (For setting of the digital input/output display, refer to page 45.)

Display examples

These are displayed when the button is pressed repeatedly in the operation mode to switch the measurement displays. Digital input reset method

The method for maintaining the digital input status differs according to the digital input reset method.

Reset method Cancelation method

Auto reset (Auto)

If the digital input turns OFF (Open), the digital input status automatically turns OFF (Open).

Latch (HoLd)

After it is detected that the digital input is ON (Closed), the digital input status is kept ON (Closed) until executing latch cancelation, even when the digital point input turns OFF (Open).

When alarm contact such as ACB are input, alarm generation status continues on this measurement instrument even when an alarm generation stops so that an alarm cannot be missed.

Digital input conditions

The following are the digital input conditions.

Input conditions Terminals DI

Rating 24VDC(19 to 30VDC),7mAor less

ON (Closed)

/ OFF (Open) time 30ms or longer for both ON and OFF

Releasing the digital input latch

Holding down the button for 2 seconds while the digital input display (DI) is displayed releases the digital input (DI) latches collectively. The digital input latches can be released also via communication.

Preventing maximum value update by motor starting current

When the motor current is monitored, use the motor starting current delay function to prevent maximum value

update and alarm generation for the current, active power, reactive power, apparent Power ,and power factor

due to the motor starting current. It is necessary to set in advance to use the motor starting current delay function.

(About settings, refer to page 36.) Movement when the motor starting current delay function is used

Note 1: Set the motor starting current value to a value lower than the lower limit value considering changes in

the load current during operation.

Note 2: When the input current is below the motor starting current value, the minimum value update stops.

DISPLAY

RESET

When the optional plug-in module ME-0052-SS96 is installed

Digital input displayDI1 to DI5 Digital output displayDO1DO2

Digital closed

Digital opened

Digital input/ output status

When the current is over the motor

starting current value, the motor

current starting current delay time

counter begins.

The maximum values for the current, active

power,reactive power and power factor are

not updated during the motor,reactive power

and power factor starting current delay time.

Also, no alarm generated even if it is over the

upper limit alarm value.

Motor starting current delay time Current

Time

Motor starting

current value

Current upper

limit alarm value

Motor starting

current

5. Operation

76

5.2 Usage According to Purpose (Alarm, Periodic Active Energy, Rolling Demand, Operating

Time, Password, etc.)

Password protection setting

In the operation mode, after pressing and simultaneously for 2 seconds or more, the password input

display will be displayed. It is possible to set the password protection if you enter the password. Default password is

0000. If you enter the wrong password, to return to the password input display (the highest digit blink).

By pressing at the highest digit, to return to the operation mode.

If you enable password protection setting, you need to input password when performing the item of the following table.

Password protection item No. Item

1 Shift to the setting mode

2 Clear the maximum/minimum value

3 Wh and varh, etc zero reset

4 Periodic Wh zero reset

5 Adjusting rolling demand time

6 Resetting the peak value of rolling demand

7 Clearing the operation time

Password protection setting (1)Set a password protection.

(2)Change the password.

Note1Select no, and go back to the operation mode.

Note2Select yES, and the current password is displayed. (3)Input a new password.

oFF on

Not protected Protected

no yES

Not change Change

Select a value of the blinking digit by pressing the or button from the highest digit.

Pressing the button moves the setting digit (blinking digit) to a lower digit.

Pressing the button moves the setting digit (blinking digit) to a higher digit.

Pressing the button at the lowest digit saves the password.

Setting is available in range from 0000 to 9999

DISPLAY

SET

SET

SET

SET

RESET PHASE

DISPLAY

Password input Select a value of the blinking digit by pressing

the or button from the highest digit.

Pressing the button moves the setting digit (blinking digit) to a lower digit.

Pressing the button moves the setting digit (blinking digit) to a higher digit.

If you enter a correct password and pressing

the in the lowest digit, password protection item is enabled.

If you enter an incorrect password and pressing

the in the lowest digit, to return to the highest digit.

DISPLAY

SETPassword input display

SET

SET

Important If You Forget Your PasswordIt is not possible to cancel the password in the field.

Please contact your supplier.

77

6. Other

6.1. Display Pattern Contents When the display pattern in the Setting menu 1 and the additional screen in the Setting menus 3, 7, and 8 are set, pressing changes the screens shown in the table below from the left to the right.

[For 3-phase 4-wire]

Display pattern

Screen set by display pattern Additional display (Set in the setting menus 3, 7, 8)

No.1 No.2 No.3 No.4 No.5 No.6 No.7 No.8 No.9

No.10 No.11 No.12 No.13 No.14 No.15 No.16 No.17 No.18 No.19 No.20 No.21 No.22 No.23 No.24 No.25 No.26 No.27 No.28

Wh Wh

Exported

varh Imported

(LAG)

varh Imported (LEAD)

varh Exported

(LAG)

varh Exported (LEAD)

VAh Periodic

Wh1 Periodic

Wh2

Rolling demand Harmonic

current

Harmonic current

N-phase

Harmonic voltage

DI status

DO status

Operation time1

Operation time2 DW Dvar DVA

P01

Upper A A A A Degree Degree Degree DI DO

Middle W W PF Periodic

Wh1 Periodic

Wh2

Peak Value

Peak Value

Peak Value

Distortion ratio

- Distortion

ratio DI No.

DO No.

hour1 hour2

Lower V PF V AN Demand

value Demand

value Demand

value RMS value

RMS value

RMS value

status status Operation

time Operation

time

P02

Upper A A A A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle V W PF Wh

Wh Exported

Lower Wh Wh Wh AN

P03

Upper A A A A A A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle PF PF PF PF PF

Lower V W var VA Hz AN

P04

Upper A A A A A A A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle V W var VA PF Hz Wh

Wh Exported

varh Imported

(LAG)

varh Imported (LEAD)

varh Exported

(LAG)

varh Exported (LEAD)

VAh

Lower Wh Wh varh VAh Wh Wh AN

P05

Upper PF Hz VA

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle W W W

Lower var var var

P06

Upper A1 V1N A A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle A2 V2N

Lower A3 V3N V AN

P07

Upper A A1 V1N A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle V A2 V2N

Lower W A3 V3N AN

P08

Upper A A A1 V1N A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle V W A2 V2N

Wh Wh

Exported

Lower Wh Wh A3 V3N AN

P09

Upper A A1 DA1 V1N A DA

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle DA A2 DA2 V2N

Lower V A3 DA3 V3N AN DAN

P10

Upper A A A1 DA1 V1N A DA

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle DA DA A2 DA2 V2N

Lower V W A3 DA3 V3N AN DAN

P11

Upper A A DA1 V1N A DA

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle DA V DA2 V2N Wh

Wh Exported

Lower Wh Wh DA3 V3N AN DAN

P12

Upper A A A DA W A DA

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle DA W V V V Wh

Wh Exported

Lower Wh Wh Wh Wh Wh AN DAN

P13

Upper A1 V1N W1 var1 VA1 PF 1 V V A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle A2 V2N W2 var2 VA2 PF 2 Hz Hz AN

Wh Wh

Exported

varh Imported

(LAG)

varh Imported (LEAD)

varh Exported

(LAG)

varh Exported (LEAD)

VAh Lower A3 V3N W3 var3 VA3 PF 3 Wh varh VAh

P00

Upper Arb itrar

y

Arb itrar

y

Arb itrar

y

Arb itrar

y

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle Arb itrar

y

Arb itrar

y

Arb itrar

y

Arb itrar

y

Wh Wh

Exported

varh Imported

(LAG)

varh Imported (LEAD)

varh Exported

(LAG)

varh Exported (LEAD)

VAh

Lower Arb itrar

y

Arb itrar

y

Arb itrar

y

Arb itrar

y

Note 1: When an additional screen is added, a screen number is added. Note 2: In the table, Wh indicates Imported active energy , and varh indicates Imported reactive energy (lag). Note 3: When Wh is selected at the screen of from No.1 to No.4, the additional display of Wh appears. varh or VAh is same, too.

DISPLAY

6. Other

78

6.1 Display Pattern Contents

[For others except 3-phase 4-wire]

Display pattern

Screen set by display pattern Additional display (Set in the setting menus 3, 7, 8)

No.1 No.2 No.3 No.4 No.5 No.6

No.7 No.8 No.9 No.10 No.11 No.12 No.13 No.14 No.15 No.16 No.17 No.18 No.19 No.20 No.21 No.22 No.23 No.24

Wh Wh

Exported

varh Imported

(LAG)

varh Imported (LEAD)

varh Exported

(LAG)

varh Exported (LEAD)

VAh Periodic

Wh1 Periodic

Wh2

Rolling demand Harmonic current

Harmonic voltage

DI status

DO status

Operation time1

Operation time2 DW Dvar VAW

P01

Upper A A A Degree Degree DI DO

Middle W W PF

Periodic Wh1

Periodic Wh2

Peak Value

Peak Value

Peak Value

Distortion ratio

Distortion ratio

DI No. DO No. hour1 hour2

Lower V PF V Demand

value Demand

value Demand

value RMS value

RMS value

RMS value

status Operation

time Operation

time

P02

Upper A A A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle V W PF Wh

Wh Exported

Lower Wh Wh Wh

P03

Upper A A A A A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle PF PF PF PF PF

Lower V W var VA Hz

P04

Upper A A A A A A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle V W var VA PF Hz Wh

Wh Exported

varh Imported

(LAG)

varh Imported (LEAD)

varh Exported

(LAG)

varh Exported (LEAD)

VAh

Lower Wh Wh varh VAh Wh Wh

P05

Upper PF Hz VA

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle W W W

Lower var var var

P06

Upper A1 V12 A

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle A2 V23

Lower A3 V31 V

P07

Upper A A1 V12

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle V A2 V23

Lower W A3 V31

P08

Upper A A A1 V12

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle V W A2 V23

Wh Wh

Exported

Lower Wh Wh A3 V31

P09

Upper A A1 DA1 V12

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle DA A2 DA2 V23

Lower V A3 DA3 V31

P10

Upper A A A1 DA1 V12

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle DA DA A2 DA2 V23

Lower V W A3 DA3 V31

P11

Upper A A DA1 V12

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle DA V DA2 V23 Wh

Wh Exported

Lower Wh Wh DA3 V31

P12

Upper A A A DA W

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle DA W V V V Wh

Wh Exported

Lower Wh Wh Wh Wh Wh

P13

Upper A1 V12 W V V V

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle A2 V23 var Hz Hz VA

Wh Wh

Exported

varh Imported

(LAG)

varh Imported (LEAD)

varh Exported

(LAG)

varh Exported (LEAD)

VAh Lower A3 V31 PF Wh varh VAh

P00

Upper Arbitra

ry Arbitra

ry Arbitra

ry Arbitra

ry

ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto ditto Middle Arbitra

ry Arbitra

ry Arbitra

ry Arbitra

ry

Wh Wh

Exported

varh Imported

(LAG)

varh Imported (LEAD)

varh Exported

(LAG)

varh Exported (LEAD)

VAh

Lower Arbitra

ry Arbitra

ry Arbitra

ry Arbitra

ry

Note 1: When an additional screen is added, a screen number is added. Note 2: When 1-phase 2-wire, only phase1 (A1, DA1) is displayed for current and only

phase12 (V12) is displayed for voltage. Other phases are not displayed even when they are set in the display pattern. Note 3: The phases displayed in the display patterns of the above table are displayed on the screen according to the phase wire system

setting shown in the table below. phase wire

Phase display in the table above

1-phase 2-wire 1-phase 3-wire

(1N2) 1-phase 3-wire

(1N3) 3-phase 3-wire

Current

1 Phase not displayed 1 1 1

2 Measurement not displayed N N 2

3 Measurement not displayed 2 3 3

Voltage

12 Phase not displayed 1N 1N 12

23 Measurement not displayed 2N 3N 23

31 Measurement not displayed 12 13 31

Note 4: In the table, Wh indicates Imported active energy , and varh indicates Imported reactive energy (lag). Note 5: When Wh or varh is selected at the screen of from No.1 to No.4, the additional display of Wh or varh appears. (P00)

6. Other

79

6.2. Maximum Scale Value

Settable primary voltage, primary current, and standard maximum scale value are shown in the tables below.

Maximum scale value of each item

Measurement element Maximum scale value

Current, Current demand

Setting of current maximum

scale SP.

CT Primary current

Voltage In the case with VT (Note 2)

1-phase 2-wire, 3-phase 3-wire VT Primary voltage150/110

3-phase 4-wire VT Primary voltage (Phase voltage)150/110

VT Primary voltage (Line voltage)3150/110

At direct input

1-phase 2-wire, 3-phase 3-wire

110V 150V

220V 300V

440V 600V

1-phase 3-wire (Phase voltage / Line voltage)

110/220V 150V/300V

220/440V 300V/600V

3-phase 4-wire (Phase voltage / Line voltage)

63.5/110V 100/150V

100/173V, 110/190V

150/300V

220/380V, 230/400V, 240/415V, 254/440V

300/600V

277/480V 400/640V

Active power, Rolling demand W (Note 1) VT ratioCT ratio

specific power(100)kW

Reactive power, Rolling demand var (Note 1) VT ratioCT ratio

specific power(100)kvar

Apparent power, Rolling demand VA (Note 1) VT ratioCT ratio

specific power(100)kVA

Note1: At direct voltage setting, VT ratio = 1. The specific power is according to the table on the right.

Note2: For convenience of scale, this is rounded off to the nearest whole number.

Specific power value for scale calculation Phase line

type CT

Secondary Rated voltage

Specific power value (100%)

1-phase 2-wire

5A

At direct input (Line voltage)

110V 0.5kW

220V 1.0kW

440V 2.0kW

In the case with VT (Line voltage)

100V, 110V 0.5kW

220V 1.0kW

1A

At direct input (Line voltage)

110V 0.1kW

220V 0.2kW

440V 0.4kW

In the case with VT (Line voltage)

100V, 110V 0.1kW

220V 0.2kW

1-phase 3-wire

5A

Without VT (Line voltage)

220V 1.0kW

440V 2.0kW

1A 220V 0.2kW

440V 0.4kW

3-phase 3-wire

5A

At direct input (Line voltage)

110V 1.0kW

220V 2.0kW

440V 4.0kW

In the case with VT (Line voltage)

100V, 110V 1.0kW

220V 2.0kW

1A

At direct input (Line voltage)

110V 0.2kW

220V 0.4kW

440V 0.8kW

In the case with VT (Line voltage)

100V, 110V 0.2kW

220V 0.4kW

3-phase 4-wire

5A

At direct input

63.5/110V 1.0kW

100/173V 110/190V

2.0kW

220/380V, 230/400V, 240/415V, 254/440V

4.0kW

277/480V 5.0kW

In the case with VT (Phase voltage)

63.5V 1.0kW

100V, 110V,

115V, 120 2.0kW

1A

At direct input

63.5/110V 0.2kW

100/173V 110/190V

0.4kW

220/380V, 230/400V, 240/415V, 254/440V

0.8kW

277/480V 1.0kW

In the case with VT (Phase voltage)

63.5V 0.2kW

100V, 110V,

115V, 120 0.4kW

Note: For reactive power or apparent power, read kW of above as kvar or kVA.

6. Other

80

6.3. Possible Setting Range for Maximum Scale The maximum scale of current can be selected from about 40% to 120% of rating, and maximum scale of voltage can be selected from about 20% to 250% of rating, and maximum scale of active power and reactive power can be selected from about 20% to 120% of rating. But for the convenience of scale conditions, the values in the following tables are applied. Also, this is same as with corresponding measured values for maximum scale of analog output.

Current maximum scale value

Possible setting range:-10 STEP to +3STEP of the rating

Example: When the rating is 100A, the value is from 45A to 160A.

Current maximum scale value (1/3) Current maximum scale value (2/3) Current maximum scale value (3/3)

STEP A unit STEP A unit kA unit STEP kA unit

1 1A 51 180A 101 25kA

2 1.2A 52 200A 102 30kA

3 1.5A 53 220A 103 32kA

4 1.6A 54 240A 104 36kA

5 1.8A 55 250A 105 40kA

6 2A 56 300A

7 2.2A 57 320A

8 2.4A 58 360A

9 2.5A 59 400A

10 3A 60 450A

11 3.2A 61 480A

12 3.6A 62 500A

13 4A 63 600A

14 4.5A 64 640A

15 4.8A 65 720A

16 5A 66 750A

17 6A 67 800A

18 6.4A 68 900A

19 7.2A 69 960A

20 7.5A 70 1000A

21 8A 71 1200A

22 9A 72 1500A

23 9.6A 73 1600A

24 10A 74 1800A

25 12A 75 2000A

26 15A 76 2200A

27 16A 77 2400A

28 18A 78 2500A

29 20A 79 3000A

30 22A 80 3200A

31 24A 81 3600A

32 25A 82 4000A

33 30A 83 4500A

34 32A 84 4800A

35 36A 85 5000A

36 40A 86 6000A

37 45A 87 6400A

38 48A 88 7200A

39 50A 89 7500A

40 60A 90 8000A

41 64A 91 9kA

42 72A 92 9.6kA

43 75A 93 10kA

44 80A 94 12kA

45 90A 95 15kA

46 96A 96 16kA

47 100A 97 18kA

48 120A 98 20kA

49 150A 99 22kA

50 160A 100 24kA

6. Other

81

6.3 Possible Setting Range for Maximum Scale

Voltage maximum scale value

Possible setting range:-18 STEP to +10STEP of the standard maximum scale value.

Example: When the standard maximum scale value is 100V, the value is from 20V to 320V.

Voltage maximum scale value (1/3) Voltage maximum scale value (2/3) Voltage maximum scale value (3/3)

STEP V unit STEP V unit kV unit STEP kV unit

1 15V 51 2200V 101 320kV

2 16V 52 2400V 102 360kV

3 18V 53 2500V 103 400kV

4 20V 54 3000V 104 450kV

5 22V 55 3200V 105 480kV

6 24V 56 3600V 106 500kV

7 25V 57 4000V 107 600kV

8 30V 58 4500V 108 640kV

9 32V 59 4800V 109 720kV

10 36V 60 5000V 110 750kV

11 40V 61 6000V 111 800kV

12 45V 62 6400V 112 900kV

13 48V 63 7.2kV 113 960kV

14 50V 64 7.5kV 114 1000kV

15 60V 65 8kV 115 1200kV

16 64V 66 9kV 116 1500kV

17 72V 67 9.6kV 117 1600kV

18 75V 68 10kV 118 1800kV

19 80V 69 12kV 119 2000kV

20 90V 70 15kV 120 2200kV

21 96V 71 16kV

22 100V 72 18kV

23 120V 73 20kV

24 150V 74 22kV

25 160V 75 24kV

26 180V 76 25kV

27 200V 77 30kV

28 220V 78 32kV

29 240V 79 36kV

30 250V 80 40kV

31 300V 81 45kV

32 320V 82 48kV

33 360V 83 50kV

34 400V 84 60kV

35 450V 85 64kV

36 480V 86 72kV

37 500V 87 75kV

38 600V 88 80kV

39 640V 89 90kV

40 720V 90 96kV

41 750V 91 100kV

42 800V 92 120kV

43 900V 93 150kV

44 960V 94 160kV

45 1000V 95 180kV

46 1200V 96 200kV

47 1500V 97 220kV

48 1600V 98 240kV

49 1800V 99 250kV

50 2000V 100 300kV

6. Other

82

6.3 Possible Setting Range for Maximum Scale

Maximum scale value for active power / reactive power

Possible setting range:-18 STEP to +3STEP of the rating

Example: When the rating is 1000W, the value is from 200W to 1600W.

Maximum scale value Maximum scale value Maximum scale value Maximum scale value Maximum scale value

of active power (1/5) of active power (2/5) of active power (3/5) of active power (4/5) of active power (5/5)

STEP W unit STEP W unit kW unit STEP kW unit MW unit STEP MW unit STEP MW unit

1 8W 51 1200W 101 200kW 151 30MW 201 4500MW

2 9W 52 1500W 102 220kW 152 32MW 202 4800MW

3 9.6W 53 1600W 103 240kW 153 36MW 203 5000MW

4 10W 54 1800W 104 250kW 154 40MW 204 6000MW

5 12W 55 2000W 105 300kW 155 45MW 205 6400MW

6 15W 56 2200W 106 320kW 156 48MW 206 7200MW

7 16W 57 2400W 107 360kW 157 50MW 207 7500MW

8 18W 58 2500W 108 400kW 158 60MW 208 8000MW

9 20W 59 3000W 109 450kW 159 64MW

10 22W 60 3200W 110 480kW 160 72MW

11 24W 61 3600W 111 500kW 161 75MW

12 25W 62 4000W 112 600kW 162 80MW

13 30W 63 4500W 113 640kW 163 90MW

14 32W 64 4800W 114 720kW 164 96MW

15 36W 65 5000W 115 750kW 165 100MW

16 40W 66 6000W 116 800kW 166 120MW

17 45W 67 6400W 117 900kW 167 150MW

18 48W 68 7200W 118 960kW 168 160MW

19 50W 69 7500W 119 1000kW 169 180MW

20 60W 70 8000W 120 1200kW 170 200MW

21 64W 71 9kW 121 1500kW 171 220MW

22 72W 72 9.6kW 122 1600kW 172 240MW

23 75W 73 10kW 123 1800kW 173 250MW

24 80W 74 12kW 124 2000kW 174 300MW

25 90W 75 15kW 125 2200kW 175 320MW

26 96W 76 16kW 126 2400kW 176 360MW

27 100W 77 18kW 127 2500kW 177 400MW

28 120W 78 20kW 128 3000kW 178 450MW

29 150W 79 22kW 129 3200kW 179 480MW

30 160W 80 24kW 130 3600kW 180 500MW

31 180W 81 25kW 131 4000kW 181 600MW

32 200W 82 30kW 132 4500kW 182 640MW

33 220W 83 32kW 133 4800kW 183 720MW

34 240W 84 36kW 134 5000kW 184 750MW

35 250W 85 40kW 135 6000kW 185 800MW

36 300W 86 45kW 136 6400kW 186 900MW

37 320W 87 48kW 137 7200kW 187 960MW

38 360W 88 50kW 138 7500kW 188 1000MW

39 400W 89 60kW 139 8000kW 189 1200MW

40 450W 90 64kW 140 9MW 190 1500MW

41 480W 91 72kW 141 9.6MW 191 1600MW

42 500W 92 75kW 142 10MW 192 1800MW

43 600W 93 80kW 143 12MW 193 2000MW

44 640W 94 90kW 144 15MW 194 2200MW

45 720W 95 96kW 145 16MW 195 2400MW

46 750W 96 100kW 146 18MW 196 2500MW

47 800W 97 120kW 147 20MW 197 3000MW

48 900W 98 150kW 148 22MW 198 3200MW

49 960W 99 160kW 149 24MW 199 3600MW

50 1000W 100 180kW 150 25MW 200 4000MW

Note: For reactive power or apparent power, read kW of above as kvar or kVA.

6. Other

83

6.4. Measurement Items and Correspondence between Display and Output The table below shows the measurement items and correspondence between display and output.

Data can be displayed or output Data cannot be displayed or output

Measurement item

Item measurement display Analog Pulse

Communi cation

3-phase 4-wire 3-phase 3-wire(3CT) 3-phase 3-wire(2CT)

1-phase 3-wire 1-phase 2-wire

3-phase 4-wire

3-phase 3-wire(3

CT)

3-phase 3-wire (2CT),

1-phase 3-wire

1-phase 2-wire

Inst Max Min Inst Max Min Inst Max Min Inst Max Min

Current

1 phase -

(Note3)

2 phase - - - - -

3 phase - - - - -

AVG - - - - -

N phase - - - - - - - - - - - - -

Current demand

1 phase -

2 phase - - - - -

3 phase - - - - -

AVG - - - - -

N phase - - - - - - - - - - - - -

Voltage

1-N phase - - - - - - - - - - - - -

2-N phase - - - - - - - - - - - - -

3-N phase - - - - - - - - - - - - -

AVG(L-N) - - - - - - - - - - - - -

1-2 phase -

2-3 phase - - - - -

3-1 phase - - - - -

AVG(L-L) - - - - - - -

Active power

1 phase - - - - - - - - - - - - -

2 phase - - - - - - - - - - - - -

3 phase - - - - - - - - - - - - -

-

Reactive power

1 phase - - - - - - - - - - - - -

2 phase - - - - - - - - - - - - -

3 phase - - - - - - - - - - - - -

-

Apparent power

1 phase - - - - - - - - - - - - -

2 phase - - - - - - - - - - - - -

3 phase - - - - - - - - - - - - -

- - - -

Power factor

1 phase - - - - - - - - - - - - -

2 phase - - - - - - - - - - - - -

3 phase - - - - - - - - - - - - -

-

Frequency -

Harmonic Current (Note 1)

RMS value

1 phase Max

Phase

- Max

Phase

- Max

Phase

- - Total Total Total Total -

2 phase - - - - - - - Total Total - - -

3 phase - - - - - - Total Total Total - -

N phase - - - - - - - - - - Total - - - -

Distortion ratio

1 phase - - - - - - - - - - - - -

2 phase - - - - - - - - - - - - - - -

3 phase - - - - - - - - - - - - - -

N phase - - - - - - - - - - - - - - - - -

Harmonic Voltage (Note 1)

RMS value

1-N phase Primary Max

Phase

- - - - - - - - - - - - - - -

2-N phase - - - - - - - - - - - - - - -

3-N phase - - - - - - - - - - - - - - -

1-2 phase - - - Primary Max

- Primary Max

- Primary - - - - - -

2-3 phase - - - - - - - - - - - - -

3-1 phase - - - - - - - - - - - - - - - - -

Distortion ratio

1-N phase Max

Phase

- - - - - - - - - - Total - - - -

2-N phase - - - - - - - - - - Total - - - -

3-N phase - - - - - - - - - - Total - - - -

1-2 phase - - - Max Phase

- Max Phase

- - - Total Total Total -

2-3 phase - - - - - - - - - Total Total - -

3-1 phase - - - - - - - - - - - - - - - - -

Active energy

2/4 quadrant counting

Imported - - - -

Exported - - - -

Active energy

Periodic 1 - - - -

2 - - - -

Reactive energy

2 quadrant counting (Note2)

Imported - - - -

Exported - - - -

4 quadrant counting

Imported lag - - - -

Imported lead - - - -

Exported lag - - - -

Exported lead - - - -

Apparent Energy Imported+ Exported

- - - -

Rolling Demand(Active power) - - - - - - - - -

Rolling Demand(Reactive power) - - - -

Rolling Demand(Apparent power) - - - -

Operation time 1 - - - - -

2 - - - - -

Note 1: RMS values of harmonics are total value and 1st to 19th (odd only). Distortion ratios of harmonics are total value and 3rd to 19th (odd only). Note 2: Imported is what Imported lag and Exported lead are counted as a single division. Exported is what Imported lead and Exported lag

are counted as a single division. Note 3: The values which can be monitored by communication are same as the values displayed. Note 4: When 1-phase 3-wire is selected, read the phase for the measurement item according to the following table.

Phase wire method 1 -phase 2 -phase 3 -phase 12 -phase 23 -phase 31 -phase

1-phase 3-wire (1N2) 1 -phase N -phase 2 -phase 1N -phase 2N -phase 12-phase

1-phase 3-wire (1N3) 1 -phase N -phase 3 -phase 1N -phase 3N -phase 13 -phase

6. Other

84

6.5. Measurement Characteristic

Metering actions in other than operation mode

Status Measurement Display Analog output Alarm contact point Pulse output

Several seconds just after turning on the auxiliary power supply (Backlight is lit, and LCD is not lit.)

No measurement No display Output over about 100% may be made until internal voltage becomes stable.

Opened No output

Setting mode, Set value confirmation mode Password protection mode

Same actions as in operation mode

No display of measured value

Same actions as in operation mode

Status before getting into setting mode and set value confirmation mode is kept.

Same actions as in operation mode

During power failure

No measurement No display No output Opened No output

Metering actions in input status

Measurement items

Actions

Current (A)

Current

demand (DA)

0A when the input current is less than 0.005A

When it is over the upper limit of the possible display range (9999), the upper limit of the possible display range (9999) is displayed.

Voltage (V) 0V when the input voltage (line voltage) is less than11V. For 3-phase 4-wire, 0V when the line to neutral voltage is less than 11V or the line to line voltage is less than 19V. For 1-phase 3-wire, 0V when the voltage between P1-P3 is less than 22V.

When it is over the upper limit of the possible display range (9999), the upper limit of the possible display range (9999) is displayed. (Note 2)

Active power (W) Reactive power (var)

Apparent power (VA)

0W, 0var and 0VA for total when the current and the voltage are 0A and 0V for all 3 phases. 0W, 0var and 0VA for each phase when the current of phase n is 0A or the voltage of phase n is 0V. (where n = 1,2 or 3)

When it is over the upper limit of the possible display range (9999), the upper limit of the possible display range (9999) is displayed.

Power factor (PF) 1.0 for total when the current and the voltage are 0A and 0V for all 3 phases. 1.0 for each phase when the current of phase n is 0A or the voltage of phase n is 0V. (where n = 1,2 or 3)

Frequency (Hz) When the input voltage of phase1 is low voltage, ---- will be displayed. Input 22V or more.

When the frequency is less than 44.5Hz or over 99.9Hz, ---- is displayed.

Harmonic current

(HI)

For effective value measurement : When the current is 0A, 0A is displayed. (Each phase) : When the voltage of phase1 is 0V or the frequency is less than 44.5Hz, ---- is displayed for all phases.

For content factor measurement : When the 1st current harmonic is 0A, 0% is

displayed. (Each phase) : When the voltage of phase1 is 0V or the frequency is

less than 44.5Hz, ---- is displayed for all phases

Harmonic Voltage

(HV)

For effective value measurement : When the current is 0V, 0V is displayed. (Each phase) : When the voltage of phase1 is 0V or the frequency is less than 44.5Hz, ---- is displayed for all phases.

For content factor measurement : When the voltage is 0V, 0% is displayed. (Each phase) : When the voltage of phase1 is 0V or the frequency is

less than 44.5Hz, ---- is displayed for all phases

Operating Time 999999 hour is displayed if it is over 999999.

Note1: Input current and input voltage means the input to the instrument. They are not to primary sides of VT, CT.

Note2: For direct measurement, it does not input upper maximum scale value.

Analog output action

Output setting Output range

Output limit setting is ON -1% to 101% of span

Output limit setting is OFF -5% to 105% of span

6. Other

85

6.6. Troubleshooting

In the case of abnormal noise, odor, smoke, or heat generation from this instrument, turn it off at once. Check the followings before you ask for repair.

Condition Possible cause Solution D

is p

la y

The display is not lit. Auxiliary power supply is not impressed on

MA and MB terminals. Impress auxiliary power supply.

When the auxiliary power supply

is impressed, display is not lit

soon.

This is not an error. For about a few seconds

after auxiliary power source is charged,

initialization of internal circuit is carried out.

Use it as it is.

The back light is not lit. The back light may be set to auto off (Auto). (If

it turns on after you press an operation button,

it means the backlight is set to auto off.)

When the auto off is enabled, it automatically

turns off in 5 minutes.

Continue using it as it is or change the setting

to HoLd (it stays on). (Refer to page 33)

The display becomes black. It may become black owing to static electricity. It goes off after a while.

End display remains.

The product is still in the setting mode. Press .

M e

a s

u re

m e

n t

e rr

o r

The current and voltage have

large errors.

The settings for VT / direct voltage and CT

primary current may be incorrect.

Please check the set values for VT / direct

voltage and CT primary current.

The current and voltage are

correct, but the active power,

reactive power, and power factor

have large errors.

The wiring for VT/CT or for the measurement

instrument may be incorrect.

Please check the wiring for VT/CT and for the

measurement instrument.

Measured values of PF are

including large error.

If the input current is smaller than the rating,

error becomes large.

(about 5% or below of rated current)

This is not an error, or uses it as it is, or if error

is troublesome, changes the CT according to

the actual current to be used.

The displayed active power is

different from the active power

that is calculated by multiplying

the displayed current, voltage,

and power factor.

If the AC of the current and voltage

deteriorate due to harmonics, it will not be the

same as the calculated value.

(For AC without harmonics, the calculated

value will match with the displayed value.)

Please continue using the instrument as it is.

The total effective harmonics

value from the harmonic current

is very different from the current

value.

The distortion factor (content factor) is way

over 100%.

(Such as measurement of the inverter

secondary side output)

Please check the measured item.

The current measured by

another measurement

instrument (such as a clamp

meter) is different from the

current measured by this

instrument. (More than the

tolerance)

If another measurement instrument uses the

average method for measuring, the

measurement instrument used will have a

larger error when the AC deteriorates due to

harmonics.

(This measurement instrument uses the RMS

value method.)

Please compare the currents using a

measurement instrument that uses the RMS

value method.

Analog output has a large error. If the wiring to the receptor is long, the error

may increase.

Perform the zero and span adjustment for

analog output. (Refer to page 60.)

Pulse output has a large error. When the pulse unit is set to the minimum

value and the pulse width is set to 0.500s or

1.000s, the pulse output cannot follow if the

load is too large, which can result in a

decrease in the pulse output number.

Review the pulse unit or pulse width setting

(refer to pages 38).

On the maximum/minimum

value display screen, a present

value that is outside of the

maximum/minimum range is

displayed.

During the starting current delay time, the

maximum value is not updated, so the

present value that is over the maximum value

may be displayed.

Please continue using the instrument as it is.

O p

e ra

ti o

n Cannot change the settings in

the setting mode.

If at the bottom of the screen is blinking,

you are in the set value confirmation mode.

Settings cannot be changed in this mode.

Please go to the setting mode to change

settings.

PASS 0000 appears when

trying to change the setting

mode.

The password protection setting is turned to

valid. Please enter the set password. Also, the

default password is 0000 (Refer to page 76)

O th

e r

Maximum value and minimum

value changed.

These are cleared if the settings for the phase

wire, VT/direct voltage, and CT primary

current are changed.

Make a note of the values before changing

the settings

The values of the setting items

that were not supposed to

change have changed.

Some setting items return to the default

values when settings for the phase wire

method, VT/direct voltage, and CT primary

current are changed.

Please refer to Initializing Related Items by

Changing Settings (page 51) and reconfigure

the setting items that returned to their default

values.

PASS 0000 appears when

trying to clear the energy or

maximum/minimum value.

The password protection setting is turned to

valid. Please enter the set password. Also, the

default password is 0000 (Refer to page 76)

SET

6. Other

86

6.6 Troubleshooting

Condition Possible cause Solution C

o m

m u

n ic

a ti

o n

o r

L o

g g

in g

COM in the LCD screen is

blinking. (Appears for 0.25sec. /

Disappears for 0.25sec.)

MODBUS RTU communication error as

follows was detected.

Communication setting(Slave address, baud

rate, stop bit and parity) was incorrect.

Function code was incorrect.

Register address was incorrect. etc.

Review the communication setting, the

function code and the register address and so

on.

If the correct query received, COM is lit.

COM in the LCD screen is

blinking. (Appears for 1sec. /

Disappears for 1sec.)

When using ME-0000MT-SS96, MODBUS

TCP communication error as follows was

detected.

MODBUS TCP application protocol header

was incorrect.

Function code was incorrect.

Register address was incorrect. etc.

Review the MODBUS TCP application

protocol header, the function code and the

register address and so on.

If the correct query received, COM is lit.

When using ME-0000BU-SS96, the error as

follows was detected.

Setting value set from the SD card was

incorrect.

SD memory card error.

The battery is low voltage. etc.

Check the LEDs of ME-0000BU-SS96.

1) LOG. LED is blink quickly.

When Setting of Logging-item pattern is LP00,

Setting data file needed to store in SD memory

card was incorrect.

Review the setting data file in SD memory card.

2) SD C. LED is blink quickly.

Check whether the SD memory card is

write-protect and SD memory card capacity is

sufficient or not.

3) BAT. LED is lit.

The voltage of the embedded lithium battery

becomes low.

It is impossible for customer to exchange the

battery. Please consider renewal.

1) LOG.

2) SD C.

3) BAT.

87

Installation 1. Dimensions

ME96SSRA-MB

Optional Plug-in Module ME-4210-SS96 ME-0040C-SS96 ME-0052-SS96

88

Installation 1. Dimensions

Optional Plug-in Module ME-0000MT-SS96

Optional Plug-in Module ME-0000BU-SS96

89

Installation 2. Mounting

1 Dimensions of mounting holes

The drilling dimensions of the panel are as shown in the right figure. The product can be installed to a panel having a thickness of 1.6 to 4.0 mm.

2 Mounting position

The contrast of the LCD changes depending on the angle at which it is viewed. Mount the product in the easy viewable position.

3 Mounting and fixing Mount the product to the panel of the main unit according to the following procedure.

4 Mounting the optional plug-in module Mount the optional plug-in module to the main unit according to the following procedure.

Remove the optional cover. Mount the optional plug-in module to the main unit.

Note

Protecting sheet The LCD part is covered with a protecting sheet to avoid scratches to the LCD during mounting of the panel. Before starting operation, remove the sheet. When removing the sheet, the LCD may illuminate due to static electricity, but this is not a product failure. After a while, the LCD goes off as it naturally discharges electricity.

Mounting position To mount the product to the edge of the panel, check the space for wiring work before determining the mounting position.

Optional plug-in module Turn off the auxiliary power before mounting the optional plug-in module. If the optional plug-in module is mounted during energization, the optional plug-in module cannot be recognized on the main unit side. In this case, turning on/restoring the auxiliary power or performing operation of restarting the instrument allows the optional plug-in module to be recognized.

Engage the convex of the optional plug-in module in the groove of the main unit.

Attach the mounting brackets to two areas

each in upper and lower parts of the main unit.

Tighten the screws of the mounting

brackets to fix them to the panel.

Screw type for mounting to the main unit: M3

Note

To avoid damage to the panel and screws, do not overtighten the screws. The recommended torque for this product is 0.3 Nm to 0.5 Nm (about half the normal torque). Tighten the upper and lower screws evenly.

90

Installation 3. Wiring

1 Applicable electric wire specifications The following table shows applicable electric wire sizes.

Section Screw type Specification of wire used Tightening

torques

Terminal of main unit. (Auxiliary power, Voltage input, Current input, MODBUSRTU communication terminal)

M3

Use crimping terminals: AWG26 to 14 (Connectable 2 wires)

Applicable crimping terminals:

0.6 to 0.8Nm

Outer Diameter

For M3 screw with an outer diameter of less than 6.0mm.

Terminal of Optional plug-in module

ME-4210-SS96

ME-0040C-SS96

ME-0052-SS96

Without screw

Single wire, Stranded wire: AWG24 to 14

Wire coating stripping length10 to 11mm (Stranded wire is bar terminal can be used in combination.)

Note: UL recognized corresponds, use according to the following conditions.

Single wire, Stranded wire: AWG24 to 18

Bar terminal can be not used in combination.

Note: When using the bar terminal for insert 2 wire, please select insertion length of 12 to 13mm.

-

2 Wiring of the main unit. Be sure to securely tighten the terminal screws to the terminal block.

CAUTION

Please do not connect three or more electric wires to one terminal. This can cause heat and fire due to imperfect contact.

If you are using bare crimped terminals, provide the insulation needed to cover exposed live parts and prevent electric shock and short circuits (e.g., use insulated tubing).

3 Connection method of terminal of optional plug-in module.

Peel the cover of the electric wire tip or crimp the bar terminal.

With the lever pressed, insert the electric wire

and then release the lever for connection.

4 Checking Check the following after connection. The electric wire is securely connected. There is no error in connection.

Electric wire

10 to 11mm

Bar terminal for inset 2wire

12 to 13mm

Insert hole Lever

91

Installation 3. Wiring

CAUTION

Do not work with live wires

Do not connect terminal and RJ-45 connector with live wires.

Do not insert and remove SD CRAD with live wires.

It may cause electric shock, burns, device burn out, or fire.

It is recommended that a protection fuse be used for VT and the auxiliary power source.

Do not open the secondary side of the CT circuit

Connect the CT secondary side signal correctly to the terminal for CT connection. If the CT is not connected properly or if the secondary side of the CT is open, it may result in high voltage on the secondary side of the CT, the insulation of the secondary winding wire may be damaged, and burnout may be caused.

Do not short the secondary side of the VT circuit

Connect the VT secondary side signal correctly to the terminal for VT connection. If the VT is not connected properly or if the secondary side of the VT shorts, over current may flow to the secondary side of the VT, which can burn out the secondary winding wire. If the secondary winding wire burns out, it can damage the insulation of the primary winding wire, resulting in a short between phases.

Make sure connections to the connection terminals are tight

Electrical wires must be properly tightened to the connection terminal.

Otherwise, heat and measurement errors may be caused.

Do not forget wiring of C1,C2 and C3 for pass.

When the L side of CT circuit is common wire, it is necessary to short-circuit C1,C2, and C3 terminal of this device.

Do not use improper electrical wires

Make sure that the electrical wires have the proper rating for current and voltage.

If inappropriate electrical wires are used, fire may be caused.

Do not pull the connection wires with force

If the terminal wiring is pulled with a strong force, the input and output portion may detach.

(Tensile load: 39.2N or less)

Do not apply an abnormal voltage.

If a pressure test is given to a high-pressure device, a ground must be used in order to avoid damaging this measurement instrument. If a high voltage of AC2000V is applied for over one minute to the measurement instrument, damage may occur.

Do not connect to Non-Connection (NC) terminal.

Do not connect to Non-Connection (NC) terminals for the purpose of relay etc.

Use the proper voltage for the auxiliary power source.

Use the proper voltage for the auxiliary power source terminal.

If an improper voltage is used, the instrument may be damaged or fire may be caused.

92

Installation 4. Wiring Diagram

Rating voltage for every phase wire system

Phase wire type Type Rating voltage Figure

3-phase 4-wire type STAR max AC277V(L-N)/480V(L-L) Figure 1

3-phase 3-wire type DELTA max AC220V(L-L) Figure 2

STAR max AC440V(L-L) Figure 3

1-phase 3-wire type max AC220V(L-N)/440V(L-L) Figure 4

1-phase 2-wire type (Note)

DELTA max AC220V(L-L) Figure 5

STAR max AC440V(L-L) Figure 6

Note. In case of a circuit which is wired from the delta connection of a 3-phase 3-wire type or a circuit of a transformer of a 1-phase 2-wire type, the maximum rating is AC220V. In case of a circuit which is wired from a 3-phase 4-wire type, the star connection of a 3-phase 3-wire type or a 1-phase 3-wire type, the maximum rating is AC440V.

93

Installation 4. Wiring Diagram

Auxiliary power supply

AC100 to 240V or DC100 to 240V.

Fuses 0.5A

Some MODBUSRTU equipment doesnt have SG. In this case, the wiring between SG is unnecessary.

Note 1: For low voltage circuits, grounding the secondary side of VT and CT is not t necessary.

Auxiliary power supply

AC100 to 240V or DC100 to 240V.

Fuses 0.5A

Some MODBUSRTU equipment doesnt have SG. In this case, the wiring between SG is unnecessary.

Note 1: For low voltage circuits, grounding the secondary side of VT and CT is not t necessary.

3-phase 4-wire type: With VT

3-phase 4-wire type: Direct input

94

Installation 4. Wiring Diagram

3-phase 3-wire(3CT) type: With VT

3-phase 3-wire(2CT) type: Direct input

Auxiliary power supply

AC100 to 240V or DC100 to 240V.

Fuses 0.5A

Some MODBUSRTU equipment doesnt have SG. In this case, the wiring between SG is unnecessary.

Note 1: For low voltage circuits, grounding the secondary side of VT and CT is not t necessary. Note 2: Do not connect to NC terminal.

Auxiliary power supply

AC100 to 240V or DC100 to 240V.

Fuses 0.5A

Some MODBUSRTU equipment doesnt have SG. In this case, the wiring between SG is unnecessary.

Note 1: For low voltage circuits, grounding the secondary side of VT and CT is not t necessary. Note 2: Do not connect to NC terminal.

95

Installation 4. Wiring Diagram

Auxiliary power supply

AC100 to 240V or DC100 to 240V.

Fuses 0.5A

Some MODBUSRTU equipment doesnt have SG. In this case, the wiring between SG is unnecessary.

Note 1: For low voltage circuits, grounding the secondary side of CT is not t necessary.

Auxiliary power supply

AC100 to 240V or DC100 to 240V.

Fuses 0.5A

Some MODBUSRTU equipment doesnt have SG. In this case, the wiring between SG is unnecessary.

Note 1: For low voltage circuits, grounding the secondary side of VT and CT is not t necessary.

1-phase 2-wire type: With VT

1-phase 3-wire type

96

Installation 4. Wiring Diagram

Optional Plug-in Module: ME-4210-SS96

Optional Plug-in Module: ME-0040C-SS96

Optional Plug-in Module: ME-0052-SS96

97

Installation 4. Wiring Diagram

Optional Plug-in Module: ME-0000MT-SS96

Optional Plug-in Module: ME-0000BU-SS96

98

Installation 4. Wiring Diagram

Note for Input

Note

1. The voltage input terminals for 3-phase 3-wire are different from those for others. 2. If the polarity for VT and CT are wrong, the measurement cannot be executed correctly. 3. Do not connect wires to the NC terminals. 4. In the case of low voltage, there is no need for grounding of the secondary sides of VT and CT. 5. Always earth the terminal to the protective earth conductor. Earth the terminal with less than

100 ohm of earth resistance. Otherwise there will be a false operation.

Note for Output

Note

1. Do not bunch pulse outputs, alarm outputs and digital inputs/outputs signal cables with the main circuit or power cables, or install them close to each other. Keep the distance between the inputs/outputs signal cables and the main circuit or power cables and high voltage lines shown below, when they run parallel to each other.

Conditions Distance

Below 600V and less than 600A power lines 30cm or more

Other power lines 60cm or more

2. Analog outputs signal cables should keep the distance from the other power cables and input signal (VT, CT and auxiliary power) cables, and should not be bunched. And use the shielded cables or twisted pair cables so that it is not affected the noise, serge, and induction. Also, the wiring cables should be as short as possible.

3. MODBUSRTU interface and analog outputs of ME-4210-SS96 do not have the insulation between them.

Note for MODBUSRTU

Note

1. Use the shielded twisted pair cable. (Recommended cables: Refer to page 102.) 2. To the units at both ends of the MODBUSRTU link, the 120-ohm resistance has to be

attached. This instrument can perform a 120-ohm termination by short-circuiting the terminal of T/R- and Ter.

3. The earthing has to be connected to earth by a thick wire of low impedance. 4. Keep the distance between MODBUSRTU link to power lines. 5. Connect to earth the SLD terminal at one end.

Note for CC-Link

Note

1. As for CC-link cable, use the designated cable. (Refer to page 102.) Ver.1.10-compatible CC-Link dedicated cables, CC-Link dedicated cables (Ver.1.00) and CC-Link dedicated high-performance cables cannot be used together. If used together, correct data transmission will not be guaranteed. Also attach the terminating resister which matches the kind of the cable.

2. Connect the shielded wire of the CC-Link dedicated cable to SLD of each module, and ground both ends of the shielded wire using grounding via FG. The SLD and FG are connected within the module.

3. Because the CC-Link transmission line is a small signal circuit, it should be separated from any strong-current circuit by 10cm or more. However, if it is laid parallel for a long distance, it must be laid at least 30cm away. The terminal must be grounded before using.

4. The CC-Link transmission line should use an exclusive line that meets the requirements for total wiring length, distance between stations, and termination resistance values according to the communication speed. If you do not use an exclusive line or observe the wiring requirements, communication may fail. (Refer to the CC-Link Cable Wiring Manual about the exclusive line and wiring requirements.)

5. Connect the supplied terminal resister to each module at both ends of the CC-Link system. Connect the terminal resistors between DA and DB.

6. CC-Link interface and MODBUSRTU do not have the insulation between them.

99

Installation 4. Wiring Diagram

Note for MODBUSTCP

Note

1. In 100Mbps communication by the 100BASE-TX connection, a communication error may occur under the influence of high frequency noise from devices other than this device in the installation environment. Take the following action to prevent the influence of high frequency noise in the construction of a network system.

(1) Wiring connection

Do not install a twisted pain cable together with the main circuit and power cables, etc.

Place the twisted pair cable in a duct.

(2) Communication system

Increase the number of communication retries if necessary.

Change the hub used for connection into a 10Mbps hub, and make communication at a

transmission speed of 10Mbps.

100

Installation 5. How to insert and eject the SD memory card (ME-0000BU-SS96)

How to insert the SD memory card

Slide the SD memory card straight into the slot until it clicks into place.

CAUTION

Make sure to use the SD memory card manufactured by Mitsubishi Electric Corporation (Model

EMU4-SD2GB). Using the other types of the SD memory card may cause the trouble such as data destruction of the memory card or system failure.

Insert the SD memory card with the write protect switch OFF. If the write protect switch is ON,

the ME-0000BU-SS96 does not communicate with an SD memory card.

How to eject the SD memory card

1) Check the SD C. LED turns off 2) Push the SD memory card in until it clicks into place. 3) The SD memory card comes out by itself.

CAUTION

During communication with the SD memory card, ejection of the memory card may cause data corruption of the memory card or failure of this unit or the memory card. Check that SD C.LED turns off to eject the SD memory card.

1) Check the SD C. LED turns off

2) Push the SD memory card in.

3) The SD memory card coes out.

101

Specifications

1. Specification

Type ME96SSRA-MB

Phase wire system 3-PHASE 4-WIRE, 3-PHASE 3-WIRE(3CT, 2CT), 1-PHASE 3-WIRE, 1-PHASE 2-WIRE (common)

Rating

Current AC5A, AC1A (common)

Voltage

3-PHASE 4-WIREmax AC277/480V

3-PHASE 3-WIRE(DELTA)max AC220V, (STAR)max AC440V

1-PHASE 3-WIREmax AC220/440V

1-PHASE 2-WIRE(DELTA)max AC220V, (STAR)max AC440V

Frequency 50-60Hz (common)

Item Measurement Item Accuracy

M e

a s u

re m

e n

t e le

m e

n ts

Current (A) A1, A2, A3, AN, AAVG

0.2% Current Demand (DA) DA1, DA2, DA3, DAN, DAAVG

Voltage (V) V12, V23, V31, VAVG(L-L), V1N, V2N, V3N, VAVG(L-N)

Active Power (W) W1, W2, W3, W

0.5% Reactive Power (var) var1, var2, var3, var

Apparent Power (VA) VA1, VA2, VA3, VA

Power Factor (PF) PF1, PF2, PF3, PF

Frequency (Hz) Hz 0.1%

Active Energy (Wh) Imported, Exported class0.5S (IEC62053-22)

Reactive Energy (varh) Imported Lag, Imported Lead, Exported Lag, Exported Lead class1S (IEC62053-24)

Apparent Energy (VAh) Imported + Exported 2.0%

Harmonic current (HI) Total, 1 to 19th(Only odd number) 1.0%

Harmonic voltage (HV) Total, 1 to 19th(Only odd number)

Rolling Demand(DW) Rolling Block, Fixing Block (Selectable by setting) 0.5%

Rolling Demand(Dvar) Rolling Block, Fixing Block (Selectable by setting) 1.0%

Rolling Demand(DVA) Rolling Block, Fixing Block (Selectable by setting)

Periodic Active Energy (Wh) Periodic Active Energy 1, Periodic Active Energy 2 class0.5S (IEC62053-22)

Operation time (h) Operation time 1, Operation time 2 (Reference)

Analog output response time 2 s or less (HI and HV10s or less)

Measuring Method

Instantaneous Value AVRMS calculation, WvarVAWhvarhVAhDigital multiplication, PFPower ratio calculation,

HzZero-cross, HIHVFFT

Demand Value DAThermal type calculation, DWRolling Demand calculation

D is

p la

y

Type LCD with backlight

Maximum Number of Display Digits or Segment Number

Number of display digits

Upper stage display6 digits, Middle stage display6 digits, Lower stage display6 digits

A, DA, V, W, var, VA, PF DW, Dvar, DVA4 digits Hz3 digits

Wh, varh, VAh9 digits(6 digits or 12 digits possible)

Harmonic total distortion ratio3 digits Harmonic RMS value4 digits Operation time6 digits

Digitalinput/outputI/O

Bar graph 21 Segment-Bar graph, 22 Segment-Indicator

Display updating time interval 0.5s, 1s

Communication Specification MODBUSRTU communication

Accessible option unit ME-4210-SS96, ME-0040C-SS96, ME-0052-SS96, ME-0000MT-SS96, ME-0000BU-SS96

Analog output Output specification DC4 to 20mA(0 to 600)

Pulse/Alarm output

The kind of switch No-voltage a contact

Contact Capacity DC35V, 0.1A

Pulse width 0.125s, 0.5s, 1.0s

Digital input(DI) Contact Capacity DC24V(DC19 to 30V), 7mA or less

Signal width 30ms or longer

Digital output(DO) The kind of switch No-voltage a contact

Contact Capacity DC35V, 0.2A

Power Failure Compensation Non volatile memory(Items Setting value, MAX/MIN value, Active/Reactive/Apparent energy,

Periodic Active Energy, Rolling Demand, Operation time)

VA Consumption

VT 0.1VA/phase (at 110VAC), 0.2VA/phase(at 220VAC) , 0.4VA/phase(at 440VAC)

CT 0.1VA/phase (at 5AAC)

Auxiliary power 7VA(AC110V), 8VA(AC220V), 5W(DC100V)

Auxiliary power AC100-240V(15%), DC100-240V(-30% +15%)

Weight 0.5kg

Dimension 96(H)96(W)90(D)

Attachment Method Embedding attachment

Operating temperature/humidity -5 to +55(average temperature35 or less per day), 0 to 85%RH, non condensing

Storage temperature/ humidity -25 to +75(average temperature35 or less per day), 0 to 85%RH, non condensing

Note1: Accuracy is specified according to the maximum scales value of rated value. Note2: Measurement of harmonics which its distortion ratio is exceeded 100% may exceed the accuracy. Note3: Harmonics cannot be measured without voltage input.

102

Specifications

2. Applicable Standards

Electromagnetic Compatibility

Emissions

Radiated Emission EN61326-1/CISPR 11 FCC Part15 Subpart B Class A

Conducted Emission EN61326-1/CISPR 11 FCC Part15 Subpart B Class A

Harmonics Measurement EN61000-3-2

Flicker Meter Measurement EN61000-3-3

Immunity

Electrostatic discharge Immunity EN61326-1/EN61000-4-2

Radio Frequency Electromagnetic field Immunity EN61326-1/EN61000-4-3

Electrical Fast Transient/Burst Immunity EN61326-1/EN61000-4-4

Surge Immunity EN61326-1/EN61000-4-5

Conducted Disturbances, Induced By Radio Frequency Fields Immunity EN61326-1/EN61000-4-6

Power Frequency Magnetic Field Immunity EN61326-1/EN61000-4-8

Voltage Dips and Short Interruptions EN61326-1/EN61000-4-11

Safety

Europe CE, as per EN61010-1

U.S. and Canada cRUus as per UL61010-1, IEC61010-1

Installation Category

Measuring Category

Pollution Degree 2

3. Specifications of MODBUS RTU Communication

Item Specifications

Physical interface RS485 2wires half duplex

Protocol RTU (Binary data)

Synchronization method Start-stop synchronization

Network topology Daisy-chain

Baud rate 2400, 4800, 9600, 19200, 38400bps

Data bit 8

Stop bit 1, 2

Parity Odd, Even, None

Slave address 1 to 255 (0For broadcast)

Distance 1200m

Maximum Number 31

Response time 1s or less (time to a response after receiving a query)

Terminate 120 1/2W

Recommended cable Shielded twisted pair, AWG24 to 14 gauge About Programming

In addition to this manual, read the following documents too. Electronic Multi-Measuring Instrument ME Series MODBUS Interface specifications ..................................... LSPM-0075

4. Specifications of CC-Link Communication

Item Specifications

CC-Link station type Remote device station (ver.1 remote device station or ver.2 remote device station)

Number of occupied stations Ver.1 remote device station (ver.1 compatible slave station) setting: 1 station Ver.2 remote device station (ver.2 compatible slave station) setting: 1 station (Expanded cyclic setting: Octuple)

CC-Link version CC-Link Ver 1.10 / 2.00

Transmission speed Can select from 156kbps / 625kbps / 2.5Mbps / 5Mbps / 10Mbps

Maximum number of connected stations

If the system is configured by only this instrument, up to 42 units can be connected. (note1)

CC-Link Dedicated Cable Use the CC-Link dedicated cables for the CC-Link system. If a cable other than the CC-Link dedicated cable is used, the performance of the CC-Link system cannot be guaranteed. For the specifications of the CC-Link dedicated cables or any other inquiries, visit the following website: CC-Link Partner Association:http://www.CC-link.org/ REMARK For details, refer to the CC-Link cable wiring manual issued by CC-Link Partner Association.

About Programming In addition to this manual, read the following documents too. Electronic Multi-Measuring Instrument programming manual (CC-Link) ............................................................ LEN080334 Electronic Multi-Measuring Instrument programming manual (CC-Link)(For ver. 2 remote device station)......... LEN130391

Note1: As for details, refer to the above manuals.

103

Specifications

5. Specifications of MODBUS TCP Communication

Item Specifications

Interface 1 port (10BASE-T/100BASE-TX)

Transmission method Base band

Number of cascade connection stages *1 Max. 4 stages (10BASE-T), Max. 2 stages (100BASE-TX)

Maximum node-to-node distance 200m (656.16ft.)

Maximum segment length *2 100m (328.08ft.)

Connector applicable for external wiring RJ45

Cable

10BASE-T Cable compliant with the IEEE802.3 10BASE-T Standard (unshielded twisted pair cable (UTP cable), Category 3 or more)

100BASE-TX Cable compliant with the IEEE802.3 100BASE-TX Standard (shielded twisted pair cable (STP cable), Category 5 or more)

Protocol MODBUS TCP (Port number 502)

Number of simultaneously connection Max. 4 connection

Functions supported Autonegotiation (10BASE-T/100BASE-TX automatically detected) Auto MDIX function (straight/crossover cable automatically detected)

*1. This is the maximum number of cascade connection stages when a repeater hub is used. For the maximum number of cascade connection stages, contact to the manufacturer for the switching hub used. *2. Length between a hub and a node.

About Programming In addition to this manual, read the following documents too. Electronic Multi-Measuring Instrument ME Series MODBUS Interface specifications ..................................... LSPM-0075

6. Specifications of Logging

Item Specifications

Logging mode Auto overwriting updating

Type of logging data (*1)

Detailed data Memorize measured data in the specified Detailed data logging cycle (1 minute, 5 minutes, 10 minutes, 15 minutes or 30 minutes). Data is output as detailed data file.

One-hour data Memorize measured data in one-hour cycle. Data is output as One-hour data file and One-day data file

The number of logging items

Detailed data Up to 6 items

One-hour data Up to 6 items

Internal memory logging period

Detailed data

Logging cycle Logging period

1minute 2 days

5minute 10 days

10minute 20 days

15minute 30 days

30minute 60 days

One-hour data 400 days (About 13 months)

Logging period with SD memory card (2GB) *2

10 years or longer

System log data 1200 records

Output format of logging data and system log data

CSV format (ASCII)

Compensation for power failure

Lithium battery (Embedded in ME-0000BU-SS96) Total time of compensation is 5 year (average daily temperature is less than +35C). (Lifetime expectancy of lithium battery is 10 year) (average daily temperature is less than +35C). It is impossible for customer to exchange the battery. Please consider renewal.

Setting values (Logging ID, Logging items, Detailed data logging cycle)

Memorized in FRAM (nonvolatile memory) The data is memorized during power failure.

Logging data, System log data

Memorized in SRAM (volatile memory) Data is erased if power failure occurs under low battery voltage condition (BAT.LED turns on).

Clock time operation Clock time operation is stopped if power failure occurs under low battery voltage condition (BAT.LED turns on). After power recovery, timing is started from Jan 1, 2016 00:00:00.

Clock accuracy Within 1 minute per month (at 25)

Memory media for data output *3 SD memory card (SD, SDHC)

Optional part SD memory card (EMU4-SD2GB) *3 *4 *1. Energy data (Wh,varh,VAh) is measuring data in ME96SS. These are not difference value calculated by logging cycle. *2. It is the period until capacity of 2GB SD memory card is filled in always-on connection. Data amount depends on the number

of characters. It is the logging period when data is output in maximum volume. *3. Make sure to use the SD memory card manufactured by Mitsubishi Electric Corporation (Model EMU4-SD2GB). Using the

other types of the SD memory card may cause the trouble such as data destruction of the memory card or system failure. *4. For purchase of optional parts, contact the shop you bought this product. In addition to this manual, read the following documents too. ME-0000BU-SS96:Logging specifications .................................................................................................... LSPM-0092

104

Specifications

7. Setting Table (Factory Settings and Customer Setting Note)

Setting menu No. Setting items Initial content Memo

1

1.1 Phase wire system 3P4(3-phase 4-wire)

1.2 Display pattern P04

1.2.1 Pattern P00

1.3 VT/direct selection no(No VT)

1.3.1 Direct voltage 220/380V

1.3.2 VT secondary voltage

1.3.3 VT primary voltage

1.4 CT secondary current 5A

1.4.1 CT primary current 5A

1.5 Frequency 50Hz

1.6 Time constant for rolling demand (Interval time constant) 15min

1.6.1 Subinterval time constant 1min

1.7 Time constant for current demand 0s

2

2.1 Communication setting selection CC or Mb.tCP

2.2 MODBUSRTU address 1

2.2.1 MODBUSRTU baud rate 19.2kbps

2.2.2 MODBUSRTU parity EVEn(even)

2.2.3 MODBUSRTU stop bit 1

2.3 CC-Link station number 1

2.3.1 CC-Link baud rate 156kbps

2.3.2 CC-Link version 1.10

2.3.3 Communication reset oFF

2.4 MODBUSTCP IP address 192.168.3.10

MODBUSTCP Subnet mask 255.255.255.0

MODBUSTCP Default gateway existence oFF(No existence)

MODBUSTCP Default gateway 127.0.0.1

Communication reset oFF

3

3.1 Current maximum scale 5A(CT primary

current)

3.1.1 Special current maximum scale

3.2 Voltage maximum scale 300V(0 STEP)

3.3 Power maximum scale 4000W(0 STEP)

3.3.1 Single / Double deflection Single deflection

3.4 Reactive power maximum scale 4000var(0 STEP)

3.5 Power factor scale 0.5(-0.5 to 1 to 0.5)

3.6 Expanded counting Combination I

3.7 Harmonics display oFF

4

4.1 Model name + option code (Model name)

4.2 Version display (Version)

4.3 Back light brightness 3

4.4 Back light auto off Auto(Auto off)

4.5 Display update time 0.5s

5

5.1 Alarm item 1 non

5.1.1 Alarm value 1

5.2 Alarm item 2 non

5.2.1 Alarm value 2

5.3 Alarm item 3 non

5.3.1 Alarm value 3

5.4 Alarm item 4 non

5.4.1 Alarm value 4

5.5 Alarm delay time

5.6 Alarm cancel method

5.7 Back light flickers during alarms

5.8 Motor start-up current masking oFF

5.8.1 Motor start-up current threshold

5.8.2 Motor start-up current delay time

5.9 Pulse / Alarm output 1 (With ME-4210-SS96) PULSE(Pulse output)

5.9.1 Pulse output 1: output item Wh

5.9.2 Pulse output 1: pulse unit 0.001kWh/pulse

5.10 Pulse / Alarm output 2 (With ME-4210-SS96) AL (Alarm output)

5.10.1 Pulse output 2: output item

5.10.2 Pulse output 2: pulse unit

5.11 Pulse width 0.125s

105

Specifications

7. Setting Table (Factory Settings and Customer Setting Note)

Setting menu No. Setting items Initial content Memo

6

6.1 Analog output CH1: output item AAVG

6.1.1 Detailed setting (1) 5A(CT primary

current)

6.1.2 Detailed setting (2)

6.2 Analog output CH2: output item VAVG(L-N)

6.2.1 Detailed setting (1) 300V(0 STEP)

6.2.2 Detailed setting (2)

6.3 Analog output CH3: output item W

6.3.1 Detailed setting (1) 4000W(0 STEP)

6.3.2 Detailed setting (2) Single deflection

6.4 Analog output CH4: output item PF

6.4.1 Detailed setting (1) 0.5(-0.5 to 1 to 0.5)

6.4.2 Detailed setting (2)

6.5 Analog output limit oFF

6

6.1 Logging ID 001

6.2 Logging data clear no (Not clear)

6.2.1 Logging data clear reconfirm no (Not clear)

6.3 Logging-item pattern LP01

6.4 Detailed data logging cycle 15min

7

7.1 Periodic Active energy display oFF(Not displayed)

7.1.1 Control setting for switching time segments of periodic

active energy non(Not switched)

7.2 Rolling demand display oFF(Not displayed)

7.2.1 Rolling demand time setting oFF(Manual)

7.3 Digital input/output status display oFF(Not displayed)

7.3.1 Digital input reset method Auto(Auto off)

8

8.1 Operating time display oFF

8.1.1 Target for counting Operation time setting AUX(Auxiliary

power)

8.1.2 Operating time threshold

8.2 Switch element information 123

8.3 Set IEC mode oFF(Normal mode)

106

Appendix

1. Calculation methods of ME96SS (for 3 phase unbalanced system with neutral)

Item Normal mode IEC mode Remark

R.m.s current for phase p

N

i

I

1N

0k

2 kp

p

==

R.m.s neutral current ( )

N

iii

I

1N

0k

2

k3k2k1

N

=

++

=

Lp-N r.m.s voltage

N

v

V

1N

0k

2 kpN

pN

==

Lp-Lg r.m.s voltage ( )

N

vv

V

1N

0k

2

kpNkgN

pg

=

=

Active power for phase p ( )

=

= 1N

0k kpkpNp iv

N

1 P

Apparent power for phase p ppNp IVS =

Reactive power for phase p

( )

=

= 1N

0k kp90kpNp iv

N

1 Q _

where i90_pk is the current waveform shifted by 90.

2 p

2 pp PSQ =

Refer to page 69 for the sign.

Power factor for phase p 2

p 2

p

p p

QP

P PF

+ =

p

p p

S

P PF =

Refer to page 69 for the sign.

Total active power 321 PPPP ++=

Total reactive power 321 QQQQ ++= Refer to page 69 for the sign.

Total apparent power 321 SSSS ++= 22 QPS +=

Total power factor 22 QP

P PF

+ =

S

P PF =

Refer to page 69 for the sign.

107

2. Optional part (Available part)

SD memory card

Item Specifications

Model EMU4-SD2GB

Amount of memory 2GB

Mass 2g

[Note] Unit: mm

IB63C45-B 20 12 New publication effective Dec.2020

Specifications are subject to change without notice.

HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

MITSUBISHI Electronic Multi-Measuring Instrument Service Network

Country/Region Corporation Name Address Telephone

Australia Mitsubishi Electric Australia Pty. Ltd. 348 Victoria Road, Rydalmere, N.S.W. 2116, Australia +61-2-9684-7777

Algeria Mec Casa Rue i N 125 Hay-Es-Salem, 02000, W-Chlef, Algeria +213-27798069

Bangladesh

PROGRESSIVE TRADING CORPORATION HAQUE TOWER,2ND FLOOR,610/11,JUBILEE ROAD, CHITTAGONG, BANGLADESH +880-31-624307

ELECTRO MECH AUTOMATION& ENGINEERING LTD.

SHATABDI CENTER, 12TH FLOOR, SUITES12-B, 292, INNER CIRCULAR ROAD,

FAKIRA POOL, MOTIJHEEL, DHAKA-1000, BANGLADESH +88-02-7192826

Belarus Tehnikon Oktyabrskaya 19, Off. 705, BY-220030 Minsk, Belarus +375 (0)17 / 210 46 26

Belgium Koning & Hartman B.V. Woluwelaan 31, BE-1800 Vilvoorde, Belgium +32 (0)2 / 2570240

Brazil Mitsubishi Electric do Brasil Comrcio e Servios Ltda.

Avenida Adelino Cardana, 293 21 andar Bethaville, Barueri SP, Brasil +55-11-4689-3000

Cambodia DHINIMEX CO.,LTD #245, St. Tep Phan, Phnom Penh, Cambodia +855-23-997-725

Central America Automation International LLC 7050 W. Palmetto Park Road Suite #15 PMB #555, Boca Raton, FL 33433 +1-561-237-5228

Chile Rhona S.A. (Main office) Vte. Agua Santa 4211 Casilla 30-D (P.O. Box) Vina del Mar, Chile +56-32-2-320-600

China

Mitsubishi Electric Automation (China) Ltd. Mitsubishi Electric Automation Building, No.1386 Hongqiao Road, Shanghai, China 200336 +86-21-2322-3030

Mitsubishi Electric Automation (China) Ltd. BeiJing

5/F,ONE INDIGO,20 Jiuxianqiao Road Chaoyang District,Beijing, China 100016 +86-10-6518-8830

Mitsubishi Electric Automation (China) Ltd. ShenZhen

Level 8, Galaxy World Tower B, 1 Yabao Road, Longgang District, Shenzhen, China 518129 +86-755-2399-8272

Mitsubishi Electric Automation (China) Ltd. GuangZhou

Rm.1006, A1 Times E-Park, No.276-282, Hanxi Road East, Zhongcun Street, Panyu Distric, Guangzhou, China 510030

+86-20-8923-6730

Mitsubishi Electric Automation (China) Ltd. ChengDu

1501-1503,15F, Guang-hua Centre Building-C, No.98 North Guang Hua 3th Rd Chengdu, China 610000

+86-28-8446-8030

Mitsubishi Electric Automation (Hong Kong) Ltd. 20/F., Cityplaza One, 1111 king's Road, Taikoo shing, Hong Kong +852-2510-0555

Colombia Proelectrico Representaciones S.A. Carrera 42 N 75 367 Bodega 109, Itagi, Medelln, Antioquia, Colombia +57-4-4441284

Czech Republic AUTOCONT CONTROL SYSTEMS S.R.O Technologick 374/6, CZ-708 00 Ostrava - Pustkovec +420 595 691 150

Denmark BEIJER ELECTRONICS A/S LYKKEGARDSVEJ 17, DK-4000 ROSKILDE, Denmark +45 (0)46/ 75 76 66

Egypt Cairo Electrical Group 9, Rostoum St. Garden City P.O. Box 165-11516 Maglis El-Shaab,Cairo - Egypt +20-2-27961337

France Mitsubishi Electric Europe B.V. French Branch FR-92741 Nanterre Cedex +33 (0)1 55 68 57 01

Germany Mitsubishi Electric Europe B.V. Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany +49 (0) 2102 4860

Greece KALAMARAKIS - SAPOUNAS S.A. IONIAS & NEROMILOU STR., CHAMOMILOS ACHARNES, ATHENS, 13678 Greece +30-2102 406000

UTECO 5, MAVROGENOUS STR., 18542 PIRAEUS, Greece +30-211-1206-900

Hungary Meltrade Ltd. Fert utca 14. HU-1107 Budapest, Hungary +36 (0)1-431-9726

India

Mitsubishi Electric India Private Limited 2nd Floor, Tower A&B, Cyber Greens, DLF Cyber City, DLF Phase-III, Gurgaon - 122 022 Haryana, India

+91-124-4630300

Mitsubishi Electric India Private Limited Pune Sales Office

ICC-Devi Gaurav Technology Park, Unit no. 402, Fourth Floor, Survey no. 191-192 (P), Opp. Vallabh Nagar Bus Depot, Pune 411018, Maharashtra, India

+91-20-68192100

Mitsubishi Electric India Private Limited FA Center

204-209, 2nd Floor, 31FIVE, Corporate Road, Prahladnagar, Ahmedabad 380015,Gujarat. India

+91-79677-77888

Indonesia PT.Mitsubishi Electric Indonesia Gedung Jaya 8th floor, JL.MH. Thamrin No.12 Jakarta Pusat 10340, Indonesia +62-21-3192-6461

P.T. Sahabat Indonesia P.O.Box 5045 Kawasan Industri Pergudangan, Jakarta, Indonesia +62-(0)21-6610651-9

Ireland Mitsubishi Electric Europe B.V. Westgate Business Park, Ballymount, IRL-Dublin 24, Ireland +353 (0)1-4198800

Israel Gino Industries Ltd. 26, Ophir Street IL-32235 Haifa, Israel +972 (0)4-867-0656

Italy Mitsubishi Electric Europe B.V. Viale Colleoni 7, I-20041 Agrate Brianza (MI), Italy +39 039-60531

Kazakhstan Kazpromavtomatika Ul. Zhambyla 28, KAZ - 100017 Karaganda +7-7212-501000

Korea Mitsubishi Electric Automation Korea Co., Ltd 9F Gangseo Hangang xi-tower A, 401 Yangcheon-ro, Gangseo-gu, Seoul 07528 Korea +82-2-3660-9573

Laos AROUNKIT CORPORATION IMPORT- EXPORT SOLE CO.,LTD

SAPHANMO VILLAGE. SAYSETHA DISTRICT, VIENTIANE CAPITAL, LAOS +856-20-415899

Lebanon Comptoir d'Electricite Generale-Liban Cebaco Center - Block A Autostrade Dora, P.O. Box 11-2597 Beirut - Lebanon +961-1-240445

Lithuania Rifas UAB Tinklu 29A, LT-5300 Panevezys, Lithuania +370 (0)45-582-728

Malaysia Mittric Sdn Bhd No. 5 Jalan Pemberita U1/49, Temasya Industrial Park, Glenmarie 40150 Shah Alam,Selangor, Malaysia

+603-5569-3748

Malta ALFATRADE LTD 99 PAOLA HILL, PAOLA PLA 1702, Malta +356 (0)21-697-816

Maroco SCHIELE MAROC KM 7,2 NOUVELLE ROUTE DE RABAT AIN SEBAA, 20600 Casablanca, Maroco +212 661 45 15 96

Myanmar Peace Myanmar Electric Co.,Ltd. NO137/139 Botahtaung Pagoda Road, Botahtaung Town Ship 11161,Yangon,Myanmar +95-(0)1-202589

Nepal Watt&Volt House KHA 2-65,Volt House Dillibazar Post Box:2108,Kathmandu,Nepal +977-1-4411330

Netherlands Imtech Marine & Offshore B.V. Sluisjesdijk 155, NL-3087 AG Rotterdam, Netherlands +31 (0)10-487-19 11

North America Mitsubishi Electric Automation, Inc. 500 Corporate Woods Parkway, Vernon Hills, IL 60061 USA +847-478-2100

Norway Scanelec AS Leirvikasen 43B, NO-5179 Godvik, Norway +47 (0)55-506000

Mexico Mitsubishi Electric Automation, Inc. Mexico Branch

Blvd. Miguel de Cervantes Saavedra 301, Torre Norte Piso 5, Col. Ampliacin Granada, Miguel Hidalgo, Ciudad de Mxico, CP 11520, Mxico

+52-55-3067-7511

Middle East Arab Countries &

Cyprus

Comptoir d'Electricite Generale-International- S.A.L.

Cebaco Center - Block A Autostrade Dora P.O. Box 11-1314 Beirut - Lebanon +961-1-240430

Pakistan Prince Electric Co. 2-P GULBERG II, LAHORE, 54600, PAKISTAN +92-42-575232, 5753373

Peru Rhona S.A. (Branch office) Avenida Argentina 2201, Cercado de Lima +51-1-464-4459

Philippines MELCO Factory Automation Philippines Inc. 128, Lopez Rizal St., Brgy. Highway Hills, Mandaluyong City, Metro Manila, Phillippines +63-(0)2-256-8042

Edison Electric Integrated, Inc. 24th Fl. Galleria Corporate Center, Edsa Cr. Ortigas Ave., Quezon City Metro Manila, Philippines +63-(0)2-634-8691

Poland Mitsubishi Electric Europe B.V. Polish Branch Krakowska 48, 32-083 Balice, Poland +48 12 347 65 00

Republic of Moldova

Intehsis SRL bld. Traian 23/1, MD-2060 Kishinev, Moldova +373 (0)22-66-4242

Romania Sirius Trading & Services SRL RO-060841 Bucuresti, Sector 6 Aleea Lacul Morii Nr. 3 +40-(0)21-430-40-06

Russia Mitsubishi Electric (Russia) LLC 2 bld.1, Letnikovskaya street, Moscow, 115114, Russia +7 495 721-2070

Saudi Arabia Center of Electrical Goods Al-Shuwayer St. Side way of Salahuddin Al-Ayoubi St. P.O. Box 15955 Riyadh 11454 - Saudi Arabia +966-1-4770149

Singapore Mitsubishi Electric Asia Pte. Ltd. 307 Alexandra Road, Mitsubishi Electric Building, Singapore 159943 +65-6473-2308

Slovakia PROCONT, Presov Kupelna 1/, SK - 08001 Presov, Slovakia +421 (0)51 - 7580 611

SIMAP Jana Derku 1671, SK - 91101 Trencin, Slovakia +421 (0)32 743 04 72

Slovenia Inea RBT d.o.o. Stegne 11, SI-1000 Ljubljana, Slovenia +386 (0)1-513-8116

South Africa CBI-electric: low voltage Private Bag 2016, ZA-1600 Isando Gauteng, South Africa +27-(0)11-9282000

Spain Mitsubishi Electric Europe B.V. Spanish Branch Carretera de Rub 76-80, E-08190 Sant Cugat del Valls (Barcelona), Spain +34 (0)93-565-3131

Sweden Mitsubishi Electric Europe B.V. (Scandinavia) Hedvig Mllers gata 6, 223 55 Lund, Sweden +46 (0)8-625-10-00

Euro Energy Components AB Jrnvgsgatan 36, S-434 24 Kungsbacka, Sweden +46 (0)300-690040

Switzerland TriElec AG Muehlentalstrasse 136, CH-8201 Schaffhausen, Switzerland +41-(0)52-6258425

Taiwan Setsuyo Enterprise Co., Ltd 5th Fl., No.105, Wu Kung 3rd, Wu-Ku Hsiang, Taipei, Taiwan, R.O.C. +886-(0)2-2298-8889

Thailand United Trading & Import Co., Ltd. 77/12 Bamrungmuang Road,Klong Mahanak Pomprab Bangkok Thailand +66-223-4220-3

Tunisia MOTRA Electric 3, Rsidence Imen, Avenue des Martyrs Mourouj III, 2074 - El Mourouj III Ben Arous, Tunisia +216-71 474 599

Turkey Mitsubishi Electric Turkey A.. erifali Mahallesi Kale Sokak No: 41, 34775 mraniye, stanbul, Turkey +90-216-969-2666

United Kingdom Mitsubishi Electric Europe B.V. Travellers Lane, UK-Hatfield, Herts. AL10 8XB, United Kingdom +44 (0)1707-276100

Uruguay Fierro Vignoli S.A. Avda. Uruguay 1274 Montevideo Uruguay +598-2-902-0808

Vietnam

Mitsubishi Electric Vietnam Co.,Ltd. Head Office 11th & 12th Floor, Viettel Tower B, 285 Cach Mang Thang 8 Street, Ward 12, District 10, Ho Chi Minh City, Vietnam

+84-28-3910-5945

Mitsubishi Electric Vietnam Co.,Ltd. Hanoi Branch

24th Floor, Handico Tower, Pham Hung Road, khu do thi moi Me Tr

Manualsnet FAQs

If you want to find out how the ME96SSRA MB Mitsubishi Electric works, you can view and download the Mitsubishi Electric ME96SSRA MB User's Manual on the Manualsnet website.

Yes, we have the User's Manual for Mitsubishi Electric ME96SSRA MB as well as other Mitsubishi Electric manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The User's Manual should include all the details that are needed to use a Mitsubishi Electric ME96SSRA MB. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Mitsubishi Electric ME96SSRA MB User's Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Mitsubishi Electric ME96SSRA MB User's Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Mitsubishi Electric ME96SSRA MB User's Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Mitsubishi Electric ME96SSRA MB User's Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Mitsubishi Electric ME96SSRA MB User's Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.