Summary of Content for Mitsubishi Electric F800 FR F862 Instruction Manual PDF

IN VER

TER F800

FR

-F862 IN STR

U C

TIO N

M A

N U

A L (H

A R

D W

A R

E)

B

HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

IB(NA)-0600689ENG-B(1903)MEE Printed in Japan Specifications subject to change without notice.

INVERTER

INTRODUCTION 1

F800 FR-F862 (SEPARATED CONVERTER TYPE) INSTRUCTION MANUAL (HARDWARE)

FR-F862-05450 to 08500 Inverter for fans and pumps

INSTALLATION AND WIRING 2

PRECAUTIONS FOR USE OF THE INVERTER 3

PROTECTIVE FUNCTIONS 4

PRECAUTIONS FOR MAINTENANCE AND

INSPECTION 5

SPECIFICATIONS 6

Thank you for choosing this Mitsubishi Electric inverter. This Instruction Manual describes handling and cautions about the hardware, such as installation and wiring, for the FR-F862 (separated converter type) that are different from the FR-F860. Information about the software, such as basic operations and parameters, is described in the FR-F860 Instruction Manual (Detailed) in the CD-ROM enclosed with the product. In addition to this manual, please read the manuals in the enclosed CD-ROM carefully. Do not use this product until you have a full knowledge of the equipment, safety information and instructions. Please forward this Instruction Manual to the end user.

Electric Shock Prevention

Fire Prevention

Injury Prevention

Additional Instructions The following instructions must be also followed. If the product is handled incorrectly, it may cause unexpected fault, an injury, or an electric shock.

Safety Instructions Do not attempt to install, operate, maintain or inspect the product until you have read through this Instruction Manual and appended documents carefully and can use the equipment correctly. Do not use this product until you have a full knowledge of the equipment, safety information and instructions. Installation, operation, maintenance and inspection must be performed by qualified personnel. Here, an expert means a person who meets all the conditions below. A person who took a proper engineering training. Such training may be available at your local Mitsubishi Electric office. Contact your local sales office for schedules and locations. A person who can access operating manuals for the protective devices (e.g. light curtain) connected to the safety control system. A person who has read and familiarized himself/herself with the manuals.

In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION"

Incorrect handling may cause hazardous conditions, resulting in death or severe injury. Incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause only material damage.

Note that even the level may even lead to a serious consequence according to conditions. Be sure to follow the instructions of both levels as they are critical to personal safety.

WARNING While the inverter power is ON, do not remove the front cover or

the wiring cover. Do not run the inverter with the front cover or the wiring cover removed, as accidental contact with exposed high-voltage terminals and internal components may occur, resulting in an electrical shock. Even if power is OFF, do not remove the front cover except for

wiring or periodic inspection. You may accidentally touch the charged inverter circuits and get an electric shock. Before wiring or inspection, power lamp must be switched OFF.

Any person who is involved in wiring or inspection shall wait for at least 10 minutes after the power supply has been switched OFF and check that there are no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous. This inverter must be earthed (grounded). Earthing (grounding)

must conform to the requirements of national and local safety regulations and electrical code (NEC section 250, IEC 61140 class 1 and other applicable standards). Any person who is involved in wiring or inspection of this

equipment shall be fully competent to do the work. The inverter must be installed before wiring. Otherwise you may

get an electric shock or be injured. Setting dial and key operations must be performed with dry

hands to prevent an electric shock. Otherwise you may get an electric shock. Do not subject the cables to scratches, excessive stress, heavy

loads or pinching. Doing so may cause an electric shock. Do not change the cooling fan while power is ON. It is dangerous

to change the cooling fan while power is ON. Do not touch the printed circuit board or handle the cables with

wet hands. Doing so may cause an electric shock. A PM motor is a synchronous motor with high-performance

magnets embedded in the rotor. Motor terminals holds high- voltage while the motor is running even after the inverter power is turned OFF. Before wiring or inspection, the motor must be confirmed to be stopped. In an application, such as fan and blower, where the motor is driven by the load, a low-voltage manual motor starter must be connected at the inverter's output side, and wiring and inspection must be performed while the motor starter is open. Otherwise you may get an electric shock.

WARNING

CAUTION

CAUTION

CAUTION Inverter must be installed on a nonflammable wall without holes

(so that nobody touches the inverter heat sink on the rear side, etc.). Mounting it to or near flammable material may cause a fire. If the inverter has become faulty, the inverter power must be

switched OFF. A continuous flow of large current may cause a fire. Be sure to perform daily and periodic inspections as specified in

the Instruction Manual. If a product is used without any inspection, a burst, breakage, or a fire may occur.

CAUTION The voltage applied to each terminal must be the ones specified

in the Instruction Manual. Otherwise an explosion or damage may occur. The cables must be connected to the correct terminals.

Otherwise an explosion or damage may occur. The polarity (+ and -) must be correct. Otherwise burst, damage,

etc. may occur. While power is ON or for some time after power-OFF, do not

touch the inverter as it will be extremely hot. Touching these devices may cause a burn.

CAUTION Transportation and installation Any person who is opening a package using a sharp object,

such as a knife and cutter, must wear gloves to prevent injuries caused by the edge of the sharp object. The product must be transported in correct method that

corresponds to the weight. Failure to do so may lead to injuries. Do not stand or rest heavy objects on the product. Do not stack the boxes containing inverters higher than the

number recommended. When carrying the inverter, do not hold it by the front cover; it

may fall off or fail. During installation, caution must be taken not to drop the inverter

as doing so may cause injuries. The product must be installed on the surface that withstands the

weight of the inverter. Do not install the product on a hot surface. The mounting orientation of the inverter must be correct. The inverter must be installed on a strong surface securely with

screws so that it will not drop. Do not install or operate the inverter if it is damaged or has parts

missing. Foreign conductive objects must be prevented from entering the

inverter. That includes screws and metal fragments or other flammable substance such as oil. As the inverter is a precision instrument, do not drop or subject it

to impact. The surrounding air temperature for LD models must be

between -10 and +50C (non-freezing). The surrounding air temperature for SLD (initial setting) models must be between -10 and +40C (non-freezing). Otherwise the inverter may be damaged. The ambient humidity must be 95%RH or less (non-

condensing). Otherwise the inverter may be damaged. (Refer to page 17 for details.)

Safety Instructions 1

CAUTION Transportation and installation The storage temperature (applicable for a short time, e.g. during

transit) must be between -20 and +65C. Otherwise the inverter may be damaged. The inverter must be used indoors (without corrosive gas,

flammable gas, oil mist, dust and dirt etc.) Otherwise the inverter may be damaged. This product must be used at an altitude of 2500 m or less, with

2.9 m/s2 or less vibration at 10 to 55 Hz (directions of X, Y, Z axes). Otherwise the product may be damaged. (For installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.) If halogen-based materials (fluorine, chlorine, bromine, iodine,

etc.) infiltrate into a Mitsubishi Electric product, the product will be damaged. Halogen-based materials are often included in fumigant, which is used to sterilize or disinfest wooden packages. When packaging, prevent residual fumigant components from being infiltrated into Mitsubishi Electric products, or use an alternative sterilization or disinfection method (heat disinfection, etc.) for packaging. Sterilization of disinfection of wooden package should also be performed before packaging the product.

Wiring Do not install a power factor correction capacitor or surge

suppressor/capacitor type filter on the inverter output side. These devices on the inverter output side may be overheated or burn out. The output side terminals (terminals U, V, and W) must be

connected correctly. Otherwise the motor will rotate inversely. PM motor terminals (U, V, W) hold high-voltage while the PM

motor is running even after the power is turned OFF. Before wiring, the PM motor must be confirmed to be stopped. Otherwise you may get an electric shock. Never connect a PM motor to the commercial power supply.

Applying the commercial power supply to input terminals (U, V, W) of a PM motor will burn the PM motor. The PM motor must be connected with the output terminals (U, V, W) of the inverter.

Trial run Before starting operation, each parameter must be confirmed

and adjusted. A failure to do so may cause some machines to make unexpected motions.

WARNING Usage Everyone must stay away from the equipment when the retry

function is set as it will restart suddenly after a trip. Since pressing the STOP/RESET key may not stop output

depending on the function setting status, separate circuit and switch that make an emergency stop (power OFF, mechanical brake operation for emergency stop, etc.) must be provided. OFF status of the start signal must be confirmed before resetting

the inverter fault. Resetting inverter fault with the start signal ON restarts the motor suddenly. Do not use a PM motor for an application where the PM motor is

driven by its load and runs at a speed higher than the maximum motor speed. Use this inverter only with three-phase induction motors or with a

PM motor. Connection of any other electrical equipment to the inverter output may damage the equipment. Do not modify the equipment. Do not perform parts removal which is not instructed in this

manual. Doing so may lead to fault or damage of the product.

CAUTION Usage The electronic thermal relay function does not guarantee

protection of the motor from overheating. It is recommended to install both an external thermal and PTC thermistor for overheat protection. Do not use a magnetic contactor on the inverter input for

frequent starting/stopping of the inverter. Doing so may shorten the life of this product. The effect of electromagnetic interference must be reduced by

using a noise filter or by other means. Otherwise nearby electronic equipment may be affected. Appropriate measures must be taken to suppress harmonics.

Otherwise power supply harmonics from the inverter may heat/ damage the power factor correction capacitor and generator. When driving a 600V class motor by the inverter, the motor must

be an insulation-enhanced motor or measures must be taken to suppress surge voltage. Surge voltage attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor. When parameter clear or all parameter clear is performed, the

required parameters must be set again before starting operations because all parameters return to their initial values. The inverter can be easily set for high-speed operation. Before

changing its setting, the performances of the motor and machine must be fully examined. Stop status cannot be hold by the inverter's brake function. In

addition to the inverters brake function, a holding device must be installed to ensure safety. Before running an inverter which had been stored for a long

period, inspection and test operation must be performed. Static electricity in your body must be discharged before you

touch the product. Only one PM motor can be connected to an inverter. A PM motor must be used under PM motor control. Do not use a

synchronous motor, induction motor, or synchronous induction motor. Do not connect a PM motor in the induction motor control

settings (initial settings). Do not use an induction motor in the PM motor control settings. It will cause a failure. In the system with a PM motor, the inverter power must be

turned ON before closing the contacts of the contactor at the output side.

Emergency stop A safety backup such as an emergency brake must be provided

for devices or equipment in a system to prevent hazardous conditions in case of failure of this product or an external device controlling this product. When the breaker on the inverter input side trips, the wiring must

be checked for fault (short circuit), and internal parts of the inverter for a damage, etc. The cause of the trip must be identified and removed before turning ON the power of the breaker. When a protective function activates, take an appropriate

corrective action, then reset the inverter, and resume the operation.

Maintenance, inspection and parts replacement Do not carry out a megger (insulation resistance) test on the

control circuit of the inverter. It will cause a failure. Disposal The inverter must be treated as industrial waste.

2 Safety Instructions

Application of caution labels Caution labels are used to ensure safety during use of the Mitsubishi Electric inverters. Apply the following labels to the inverter if the "retry function" and/ or "automatic restart after instantaneous power failure" have been enabled. For the retry function

For automatic restart after instantaneous power failure

Application of motor control labels Apply the following labels to the inverter to avoid connecting motors not intended for a particular motor control setting.

General instruction For clarity, illustrations in this Instruction Manual may be drawn

with covers or safety guards removed. Ensure all covers and safety guards are properly installed prior to starting operation. For details on the PM motor, refer to the Instruction Manual of the PM motor.

CAUTION Retry Function Has Been Selected

Stay away from the motor and machine. They will start suddenly (after given time has elapsed) when alarm occurs.

CAUTION Automatic Restart after Instantaneous Power Failure Has Been Selected

Stay away from the motor and machine. They will start suddenly (after reset time has elapsed) when instantaneous power failure occurs.

Induction motor setting

The inverter is set for the induction motor control. Do not connect a PM motor.

PM motor control setting

The inverter is set for the PM motor control. Do not connect an induction motor.

Safety Instructions 3

CONTENTS

1 INTRODUCTION 7 1.1 Product checking 8

1.2 Inverter component names 9

1.3 About the related manuals 10

2 INSTALLATION AND WIRING 11 2.1 Peripheral devices 12

2.1.1 Inverter and peripheral devices ...................................................................................................................... 12

2.1.2 Peripheral devices.......................................................................................................................................... 14

2.2 Removal and reinstallation of the front covers 15

2.3 Installation of the inverter and enclosure design 17 2.3.1 Inverter installation environment .................................................................................................................... 17

2.3.2 Amount of heat generated by the inverter ...................................................................................................... 19

2.3.3 Cooling system types for inverter enclosure .................................................................................................. 20

2.3.4 Inverter installation ......................................................................................................................................... 21

2.3.5 Protruding the heat sink through a panel ....................................................................................................... 23

2.4 Terminal connection diagrams 25

2.5 Main circuit terminals 27 2.5.1 Details on the main circuit terminals of the inverter........................................................................................ 27

2.5.2 Details on the main circuit terminals of the converter unit (FR-CC2-C) ......................................................... 27

2.5.3 Terminal layout of the main circuit terminals, wiring of power supply and the motor ..................................... 28

2.5.4 Applicable cables and wiring length ............................................................................................................... 29

2.5.5 Earthing (grounding) precautions ................................................................................................................... 31

2.6 Control circuit 32 2.6.1 Details on the control circuit terminals of the inverter..................................................................................... 32

2.6.2 Details on the control circuit terminals of the converter unit (FR-CC2-C) ...................................................... 35

2.6.3 Control logic (sink/source) change ................................................................................................................. 36

2.6.4 Wiring of inverter control circuit ...................................................................................................................... 38

2.6.5 Wiring precautions.......................................................................................................................................... 40

2.6.6 When using separate power supplies for the control circuit and the main circuit........................................... 41

2.6.7 When supplying 24 V external power to the control circuit............................................................................. 42

2.7 Communication connectors and terminals 44 2.7.1 PU connector.................................................................................................................................................. 44

2.7.2 USB connector ............................................................................................................................................... 45

2.7.3 RS-485 terminal block .................................................................................................................................... 46

3 PRECAUTIONS FOR USE OF THE INVERTER 47 3.1 Electro-magnetic interference (EMI) and leakage currents 48

3.1.1 Leakage currents and precautions ................................................................................................................. 48

3.1.2 Precautions against inverter-generated EMI .................................................................................................. 49

4 CONTENTS

3.2 Power supply harmonics 51 3.2.1 Power supply harmonics.................................................................................................................................51

3.3 Installation of a reactor 51

3.4 Power-OFF and magnetic contactor (MC) 52

3.5 Precautions against deterioration of the 600 V class motor insulation 53

3.6 Checklist before starting operation 54

3.7 Failsafe system which uses the inverter 57

4 PROTECTIVE FUNCTIONS 59 4.1 Inverter fault and indications 60

4.2 Reset method for the protective functions 60

4.3 List of fault displays 61

5 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 63

5.1 Inspection item 64 5.1.1 Daily inspection...............................................................................................................................................64

5.1.2 Periodic inspection..........................................................................................................................................64

5.1.3 Daily and periodic inspection ..........................................................................................................................65

5.1.4 Checking the inverter and converter modules ................................................................................................66

5.1.5 Cleaning..........................................................................................................................................................67

5.1.6 Replacement of parts......................................................................................................................................67

5.1.7 Removal and reinstallation of the control circuit terminal block ......................................................................69

5.2 Measurement of main circuit voltages, currents and powers 71 5.2.1 Measurement of powers .................................................................................................................................73

5.2.2 Measurement of voltages ...............................................................................................................................73

5.2.3 Measurement of currents................................................................................................................................73

5.2.4 Example of measuring converter unit (FR-CC2-C) input power factor ...........................................................73

5.2.5 Measurement of converter output voltage (across terminals P and N)...........................................................73

5.2.6 Measurement of inverter output frequency .....................................................................................................73

5.2.7 Insulation resistance test using megger .........................................................................................................74

5.2.8 Withstand voltage test ....................................................................................................................................74

6 SPECIFICATIONS 75 6.1 Inverter rating 76

6.2 Common specifications 77

6.3 Outline dimension drawings 79

CONTENTS 5

APPENDIX 81 Appendix 1 Comparison with FR-F860 ...................................................................................................... 82 Appendix 2 Instructions for UL and cUL ................................................................................................... 83 Appendix 3 Restricted Use of Hazardous Substances in Electronic and Electrical Products ............. 85

6 CONTENTS

1

INTRODUCTION 7

1 INTRODUCTION

The contents described in this chapter must be read before using this product. Always read the instructions before use.

1.1 Product checking......................................................................8 1.2 Inverter component names......................................................9 1.3 About the related manuals.......................................................10

DU ............................................................. Operation panel (FR-LU08) (option) Operation panel ........................................ Operation panel (FR-LU08) (option) Parameter unit .......................................... Parameter unit (FR-PU07) PU ............................................................. Operation panel and parameter unit Inverter ...................................................... Mitsubishi Electric inverter FR-F860 series Pr. ............................................................. Parameter number (Number assigned to function) PU operation ............................................. Operation using the PU (operation panel/parameter unit) External operation ..................................... Operation using the control circuit signals Combined operation ................................. Combined operation using the PU (operation panel/parameter unit)

and External operation

Connection diagrams in this Instruction Manual suppose that the control logic of the input terminal is the sink

logic, unless otherwise specified. (For the control logic, refer to page 36.)

Product checking

1.1 Product checking Unpack the product and check the rating plate and the capacity plate of the inverter to ensure that the model agrees with the

order and the product is intact.

Inverter model

How to read the SERIAL number Rating plate example The SERIAL consists of one symbol, two characters indicating the production

year and month, and six characters indicating the control number.

The last digit of the production year is indicated as the Year, and the Month is

indicated by 1 to 9, X (October), Y (November), or Z (December).

Symbol Year Month Control number

SERIAL

FR-F862-05450-3-60

Rating plate

Input rating

Output rating

SERIAL

Inverter model

Country of origin

F R - F 8 6 2 - 05450 - 3 - 60

600 V class Symbol Voltage class

6

Symbol Circuit board coating (conforming to IEC60721-3-3 3C2/3S2)

With With

Plated conductor

With Without

06 60

Symbol Description 05450 to 08500 Inverter SLD rated current (A)

Symbol Structure, functionality Separated converter type2

8 INTRODUCTION

Inverter component names

1

1.2 Inverter component names Component names are as follows.

Refer to the Instruction Manual (Detailed) of the FR-F860.

Symbol Name Description Refer to page

(a) RS-485 terminals Enables RS-485 and MODBUS RTU, and BACnet communication. 46 (b) Plug-in option connector 1

Connects a plug-in option or a communication option. Instruction Manual of the option

(c) Plug-in option connector 2

(d) Plug-in option connector 3

(e) Voltage/current input switch Selects between voltage and current for the input via terminals 2 and 4.

(f) Control circuit terminal block Connects cables for the control circuit. 32

(g) PU connector Connects the operation panel or the parameter unit. This connector also enables the RS-485 communication.

44

(h) USB A connector Connects a USB memory device. 45

(i) USB mini B connector Connects a personal computer and enables communication with FR Configurator2.

45

(j) Front cover (upper side) Needs to be removed for control circuit wiring, installation of a plug-in (communication) option, RS-485 terminal wiring, changing of the voltage/ current input switch setting, etc.

15

(k) Power lamp Stays ON while the power is supplied to the control circuit (R1/L11, S1/L21). 28 (l) Alarm lamp Turns ON when the protective function of the inverter is activated. 59 (m) Charge lamp Stays ON while the power is supplied to the main circuit. 28 (n) Accessory cover Remove this cover for using the PU connector.

(o) Front cover (lower side) Remove this cover for wiring. 15 (p) Main circuit terminal block Connects cables for the main circuit. 27 (q) Cooling fan Cools the inverter. 68

(r) Switches for manufacturer setting (SW3 and SW4) Do not change the initial setting (OFF ).

(r)

(g)

(f)

(e)

(p)

(m)

(a)

(d)

(b)

(c)

(n)

(k) (l)

(j)

(o)

(h) (i)

(q)

OFF ON

INTRODUCTION 9

About the related manuals

1.3 About the related manuals The manuals related to the FR-F862 are as follows.

Manual name Manual number FR-F860 Instruction Manual (Detailed) IB-0600688ENG

FR-CC2-C (Converter unit) Instruction Manual IB-0600572ENG

FR Configurator2 Instruction Manual IB-0600516ENG

PLC Function Programming Manual IB-0600492ENG

10 INTRODUCTION

2

INSTALLATION AND WIRING 11

2 INSTALLATION AND WIRING

This chapter explains the installation and the wiring of this product. Always read the instructions before use.

2.1 Peripheral devices ....................................................................12 2.2 Removal and reinstallation of the front covers......................15 2.3 Installation of the inverter and enclosure design..................17 2.4 Terminal connection diagrams................................................25 2.5 Main circuit terminals ...............................................................27 2.6 Control circuit ...........................................................................32 2.7 Communication connectors and terminals ............................44

Peripheral devices

2.1 Peripheral devices

2.1.1 Inverter and peripheral devices

NOTE To prevent an electric shock, always earth (ground) the motor, the inverter, and the converter unit. Do not install a power factor correction capacitor, surge suppressor, or capacitor type filter on the inverter's output side. Doing so

will cause the inverter shut off or damage the capacitor or surge suppressor. If any of the above devices is connected, immediately remove it. When installing a molded case circuit breaker on the output side of the inverter, contact the manufacturer of the molded case circuit breaker.

Electromagnetic wave interference The input/output (main circuit) of the inverter or the converter unit includes high frequency components, which may interfere with the communication devices (such as AM radios) used near the inverter or the converter unit. Refer to page 49 for countermeasures.

For details of options and peripheral devices, refer to the respective Instruction Manual. A PM motor cannot be driven by the commercial power supply. A PM motor is a motor with permanent magnets embedded inside. High voltage is generated at the motor terminals while the

motor is running. Before closing the contactor at the output side, make sure that the inverter power is ON and the motor is stopped.

Earth (Ground)

R/L1 S/L2 T/L3 N/-N/- P/+P/+

: Install these options as required.

U V W U

Earth (Ground)

V W

(d) Molded case circuit breaker (MCCB) or earth leakage current breaker (ELB), fuse

(i) Noise filter

(k) Contactor Example) No-fuse switch (DSN type)

(l) PM motor

(g) Noise filter

(e) Magnetic contactor (MC)

(a) Inverter (FR-F862)

(b) Converter unit (FR-CC2-C)

(c) Three-phase AC power supply

(h) USB connector

Personal computer (FR Configurator2)

USB

USB host (A connector)

USB device (Mini B connector)

Communication status indicator (LED)(USB host)

Earth (Ground)

(j) Induction motor

(f) AC reactor

IM connection PM connection Earth

(Ground)

12 INSTALLATION AND WIRING

Peripheral devices

2

Symbol Name Overview Refer

to page

(a) Inverter (FR-F862)

The life of the inverter and the converter unit is influenced by the surrounding air temperature. The surrounding air temperature should be as low as possible within the permissible range. This must be noted especially when the inverter and the converter unit installed in an enclosure. Incorrect wiring may lead to damage of the inverter and the converter unit. The control signal lines must be kept fully away from the main circuit lines to protect them from noise.

17 25

(b) Converter unit (FR-CC2-C)

(c) Three-phase AC power supply Must be within the permissible power supply specifications of the converter unit.

76

(d) Molded case circuit breaker (MCCB), earth leakage circuit breaker (ELB), or fuse

Must be selected carefully since an inrush current flows in the converter unit at power ON.

14

(e) Magnetic contactor (MC) Install this to ensure safety. Do not use this to start and stop the inverter. Doing so will shorten the life of the inverter and the converter unit.

52

(f) AC reactor

Install this to suppress harmonics and to improve the power factor. An AC reactor is required when installing the inverter near a large power supply system (1000 kVA or more). Under such condition, the inverter and the converter unit may be damaged if you do not use a reactor. Select a reactor according to the applied motor capacity.

51

(g) Noise filter Suppresses the noise radiated from the power supply side of the converter unit.

49

(h) USB connection

Connect between the inverter and a personal computer with a USB (ver. 1.1) cable. Use a USB memory device to copy parameter settings or use the trace function.

45

(i) Noise filter Install this to reduce the electromagnetic noise generated from the inverter and the converter unit. The noise filter is effective in the range from about 0.5 to 5 MHz.

49

(j) Induction motor Connect a squirrel-cage induction motor.

(k) Contactor Example) No-fuse switch (DSN type)

Connect this for an application where a PM motor is driven by the load even while the inverter power is OFF. Do not open or close the contactor while the inverter is running (outputting).

(l) PM motor A PM motor can be used. A PM motor cannot be driven by the commercial power supply.

INSTALLATION AND WIRING 13

Peripheral devices

2.1.2 Peripheral devices Selecting the converter unit (FR-CC2-C) Select the capacity of the FR-CC2-C converter unit according to the connected motor capacity.

The motor capacity indicated is the maximum capacity applicable for use of the 4-pole standard motor.

Selecting the breaker/magnetic contactor Check the model of the inverter and the converter unit you purchased. Appropriate peripheral devices must be selected

according to the capacity.

Refer to the following table to prepare appropriate peripheral devices.

NOTE When the converter unit capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to

the converter unit model, and select cables and reactors according to the motor output.

When the breaker on the converter unit's input side trips, check for the wiring fault (short circuit), damage to internal parts of

the inverter and the converter unit, etc. The cause of the trip must be identified and removed before turning ON the power of

the breaker.

Converter unit FR-CC2-[ ]

Inverter Model

FR-F862-[ ] Rated current

(A) Motor capacity

(kW)

C355K 05450 SLD 545 400

LD 496 355

C400K 06470 SLD 647 450

LD 589 400

C560K 08500 SLD 850 630

LD 773 560

Motor output (kW)

Applicable converter model

Applicable inverter model

Molded case circuit breaker (MCCB) or

earth leakage circuit breaker (ELB) (NF, NV type)

Input-side magnetic

contactor

SLD LD SLD LD 400 FR-CC2-C355K FR-F862-05450 700 A 700 A 475 A 469 A

450 FR-CC2-C400K FR-F862-06470 900 A 800 A 592 A 589 A

630 FR-CC2-C560K FR-F862-08500 1200 A 1000 A 776 A 773 A

Assumes the use of a Mitsubishi Electric 4-pole standard motor with the power supply voltage of 575 VAC 50 Hz.

Select an MCCB according to the power supply capacity.

Install one MCCB per converter.

(For the use in the United States or Canada, refer to page 83 to select the appropriate fuse.)

The magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the

magnetic contactor is used for emergency stops during motor driving, the electrical durability is 25 times.

If using an MC for emergency stop during driving the motor, select an MC regarding the converter unit input side current as JEM 1038-AC-3

class rated current. When using an MC on the inverter output side for commercial-power supply operation switching using a general-purpose

motor, select an MC regarding the rated motor current as JEM 1038-AC-3 class rated current.

MCCB Converter unit

MCCB Converter unit

M

M

INV

INV

14 INSTALLATION AND WIRING

Removal and reinstallation of the front covers

2

2.2 Removal and reinstallation of the front covers

Removal of the front cover (lower side)

(a) When the mounting screws are removed, the front cover (lower side) can be removed. (The number of the mounting screws differs by the capacity.)

(b) With the front cover (lower side) removed, wiring of the main circuit terminals can be performed.

Removal of the front cover (upper side)

(a) With the front cover (lower side) removed, loosen the mounting screws on the front cover (upper side). These screws cannot be removed.

(b) While holding the areas around the installation hooks on the sides of the front cover (upper side), pull out the front cover using its upper side as a support.

(c) With the front cover (upper side) removed, wiring of the control circuit and the RS-485 terminals, and installation of the plug-in option can be performed.

(a) (b)

(a) (b) (c)

Loosen

INSTALLATION AND WIRING 15

Removal and reinstallation of the front covers

Reinstallation of the front covers

(a) Insert the upper hooks of the front cover (upper side) into the sockets of the inverter. Securely install the front cover (upper side) to the inverter by fixing the hooks on the sides of the cover into place.

(b) Tighten the mounting screws at the lower part of the front cover (upper side). (c) Fasten the front cover (lower side) with the mounting screws. (The number of the mounting screws differs by the capacity.)

NOTE When installing the front cover (upper side), fit the connector of the operation panel securely along the guides of the PU

connector.

Fully make sure that the front cover has been reinstalled securely. Always tighten the installation screws of the front cover.

(b) (c)(a)

Fasten Fasten

16 INSTALLATION AND WIRING

Installation of the inverter and enclosure design

2

2.3 Installation of the inverter and enclosure design When designing or manufacturing an inverter enclosure, determine the structure, size, and device layout of the enclosure by

fully considering the conditions such as heat generation of the contained devices and the operating environment. An inverter

uses many semiconductor devices. To ensure higher reliability and long period of operation, operate the inverter in the

ambient environment that completely satisfies the equipment specifications.

2.3.1 Inverter installation environment The following table lists the standard specifications of the inverter installation environment. Using the inverter in an

environment that does not satisfy the conditions deteriorates the performance, shortens the life, and causes a failure. Refer to

the following points, and take adequate measures.

Standard environmental specifications of the inverter

Temperature applicable for a short time, for example, in transit.

For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.

Surrounding Air Temperature is a temperature measured at a measurement position in an enclosure.

Ambient Temperature is a temperature outside an enclosure.

Temperature The permissible surrounding air temperature of the inverter is between -10C and +40C (-10C and +50C at the LD ratings).

Always operate the inverter within this temperature range. Operation outside this range will considerably shorten the service

lives of the semiconductors, parts, capacitors and others. Take the following measures to keep the surrounding air

temperature of the inverter within the specified range.

(a) Measures against high temperature

Use a forced ventilation system or similar cooling system. (Refer to page 20.)

Install the enclosure in an air-conditioned electric chamber.

Block direct sunlight.

Provide a shield or similar plate to avoid direct exposure to the radiated heat and wind of a heat source.

Ventilate the area around the enclosure well.

(b) Measures against low temperature

Provide a space heater in the enclosure.

Do not power OFF the inverter. (Keep the start signal of the inverter OFF.)

(c) Sudden temperature changes

Select an installation place where temperature does not change suddenly.

Avoid installing the inverter near the air outlet of an air conditioner.

If temperature changes are caused by opening/closing of a door, install the inverter away from the door.

NOTE For the amount of heat generated by the inverter unit, refer to page 19.

Item Description

Surrounding air temperature

LD -10 to +50C (non-freezing)

SLD (initial setting) -10 to +40C (non-freezing)

Ambient humidity 95% RH or less (non-condensing)

Storage temperature -20 to + 65C

Atmosphere Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)

Altitude Maximum 2500 m

Vibration 2.9 m/s2 or less at 10 to 55 Hz (directions of X, Y, Z axes)

Measurement position

Measurement position

Inverter 5 cm 5 cm

5 cm

Enclosure

INSTALLATION AND WIRING 17

Installation of the inverter and enclosure design

Humidity Operate the inverter within the ambient air humidity of usually 45 to 95%. Too high humidity will pose problems of reduced

insulation and metal corrosion. On the other hand, too low humidity may cause a spatial electrical breakdown. The humidity

conditions for the insulation distance defined in JEM 1103 standard "Insulation Distance from Control Equipment" is 45 to

85%.

(a) Measures against high humidity

Make the enclosure enclosed, and provide it with a hygroscopic agent.

Provide dry air into the enclosure from outside.

Provide a space heater in the enclosure.

(b) Measures against low humidity

Air with proper humidity can be blown into the enclosure from outside. Also when installing or inspecting the unit, discharge

your body (static electricity) beforehand, and keep your body away from the parts and patterns.

(c) Measures against condensation

Condensation may occur if frequent operation stops change the in-enclosure temperature suddenly or if the outside air

temperature changes suddenly.

Condensation causes such faults as reduced insulation and corrosion.

Take the measures against high humidity in (a).

Do not power OFF the inverter. (Keep the start signal of the inverter OFF.)

Dust, dirt, oil mist Dust and dirt will cause such faults as poor contacts, reduced insulation and cooling effect due to the moisture-absorbed

accumulated dust and dirt, and in-enclosure temperature rise due to a clogged filter. In an atmosphere where conductive

powder floats, dust and dirt will cause such faults as malfunction, deteriorated insulation and short circuit in a short time.

Since oil mist will cause similar conditions, it is necessary to take adequate measures.

Precautions

Place the inverter in a totally enclosed enclosure.

Take measures if the in-enclosure temperature rises. (Refer to page 20.)

Purge air.

Pump clean air from outside to make the in-enclosure air pressure higher than the outside air pressure.

Corrosive gas, salt damage If the inverter is exposed to corrosive gas or to salt near a beach, the printed board patterns and parts will corrode or the

relays and switches will result in poor contact.

In such places, take the measures given above.

Explosive, flammable gases As the inverter is non-explosion proof, it must be contained in an explosion-proof enclosure. In places where explosion may

be caused by explosive gas, dust or dirt, an enclosure cannot be used unless it structurally complies with the guidelines and

has passed the specified tests. This makes the enclosure itself expensive (including the test charges). The best way is to

avoid installation in such places and install the inverter in a non-hazardous place.

High altitude Use the inverter at an altitude of within 2500 m. For use at an altitude above 1000 m, consider a 3% reduction in the rated

current per 500 m increase in altitude.

If it is used at a higher place, it is likely that thin air will reduce the cooling effect and low air pressure will deteriorate dielectric

strength.

18 INSTALLATION AND WIRING

Installation of the inverter and enclosure design

2

Vibration, impact The vibration resistance of the inverter is up to 2.9 m/s2 at 10 to 55 Hz frequency and 1 mm amplitude for the directions of X,

Y, Z axes. Applying vibration and impacts for a long time may loosen the structures and cause poor contacts of connectors,

even if those vibration and impacts are within the specified values.

Especially when impacts are applied repeatedly, caution must be taken because such impacts may break the installation feet.

Precautions

Provide the enclosure with rubber vibration isolators.

Strengthen the structure to prevent the enclosure from resonance.

Install the enclosure away from the sources of the vibration.

2.3.2 Amount of heat generated by the inverter Regarding the amount of heat generated in the FR-F860 series inverter The amount of heat generated by the inverter unit and converter unit is shown in the following tables.

NOTE The amount of heat generated shown assumes that the output current is inverter rated current, and carrier frequency is 2

kHz.

Inverter model Amount of heat generated (W)

SLD LD FR-CC2-C355K 2500

7300 2300

6600 FR-F862-05450 4800 4300

FR-CC2-C400K 3000 8600

2600 7700

FR-F862-06470 5600 5100

FR-CC2-C560K 3700 11400

3200 10200

FR-F862-08500 7700 7000

INSTALLATION AND WIRING 19

Installation of the inverter and enclosure design

2.3.3 Cooling system types for inverter enclosure From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformers, lamps, resistors,

etc.) and the incoming heat such as direct sunlight must be dissipated to keep the in-enclosure temperature lower than the

permissible temperatures of the in-enclosure equipment including the inverter.

The cooling systems are classified as follows in terms of the cooling calculation method.

(a) Cooling by natural heat dissipation from the enclosure surface (totally enclosed type)

(b) Cooling by heat sink (aluminum fin, etc.)

(c) Cooling by ventilation (forced ventilation type, pipe ventilation type)

(d) Cooling by heat exchanger or cooler (heat pipe, cooler, etc.)

Cooling system Enclosure structure Comment

Natural

Natural ventilation (enclosed type / open type)

This system is low in cost and generally used, but the enclosure size increases as the inverter capacity increases. This system is for relatively small capacities.

Natural ventilation (totally enclosed type)

Being a totally enclosed type, this system is the most appropriate for hostile environment having dust, dirt, oil mist, etc. The enclosure size increases depending on the inverter capacity.

Forced air

Heat sink cooling This system has restrictions on the heat sink mounting position and area. This system is for relatively small capacities.

Forced ventilation This system is for general indoor installation. This is appropriate for enclosure downsizing and cost reduction, and often used.

Heat pipe This is a totally enclosed for enclosure downsizing.

INV

INV

INV Heat sink

INV

INV

Heat pipe

20 INSTALLATION AND WIRING

Installation of the inverter and enclosure design

2

2.3.4 Inverter installation Inverter placement

Install the inverter on a strong surface securely with screws.

Leave enough clearances and take cooling measures.

Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.

Install the inverter on a nonflammable wall surface.

When encasing multiple inverters in an enclosure, install them in parallel as a cooling measure.

For heat dissipation and maintenance, keep clearance between the inverter and the other devices or enclosure surface.

The clearance below the inverter is required as a wiring space, and the clearance above the inverter is required as a heat

dissipation space.

When designing or building an enclosure for the inverter, carefully consider influencing factors such as heat generation of

the contained devices and the operating environment.

For replacing the cooling fan, 30 cm or more of space is necessary in front of the inverter. Refer to page 68 for fan replacement.

Installation orientation of the inverter Install the inverter on a wall as specified. Do not mount it horizontally or in any other way.

Above the inverter Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter should be

heat resistant.

Vertical

Allow clearance.

Clearances (side)Clearances (front)

Inverter

5 cm or more 1

10 cm or more

10 cm or more

20 cm or more

20 cm or more

INSTALLATION AND WIRING 21

Installation of the inverter and enclosure design

Arrangement of multiple inverters and converter units

Arrangement of the ventilation fan and inverter

When multiple inverters and converter units are placed in the

same enclosure, generally arrange them horizontally as shown

in the figure on the right.

Do not place multiple products vertically. The exhaust air

temperature of the inverter and the converter unit may be

increased.

When mounting multiple inverters and converter units, fully take

caution not to make the surrounding air temperature of the

inverter and the converter unit higher than the permissible value

by providing ventilation and increasing the enclosure size. Arrangement of multiple inverters and converter units

Heat generated in the inverter is blown up from the bottom of

the unit as warm air by the cooling fan. When installing a

ventilation fan for that heat, determine the place of ventilation

fan installation after fully considering an air flow. (Air passes

through areas of low resistance. Make an airway and airflow

plates to expose the inverter to cool air.)

Arrangement of the ventilation fan and inverter

Enclosure

InverterConverter unit

InverterConverter unit

InverterConverter unit

Inverter Inverter

22 INSTALLATION AND WIRING

Installation of the inverter and enclosure design

2

2.3.5 Protruding the heat sink through a panel When encasing an inverter to an enclosure, the heat generated in the enclosure can be greatly reduced by protruding the

heat sink of the inverter.

When installing the inverter in a compact enclosure, etc., this installation method is recommended.

Panel cutting Cut the panel of the enclosure according to the inverter capacity.

FR-F862-05450

(Unit: mm)

FR-F862-06470

FR-F862-08500

(Unit: mm)

6-M10 screw520

Hole

200

15 15

12 70

13 00

200 660

Hole

240 240 6-M10 screw

15 15

20 15

15 50

INSTALLATION AND WIRING 23

Installation of the inverter and enclosure design

Removal of the rear installation frame

Installation of the inverter in enclosure Place the inverter in an enclosure so that the inverter's heat sink section protrudes from the hole through the panel of the

enclosure. Fasten the inverter to the panel with screws through holes in the upper and lower installation frames.

NOTE As the heat sink section protruded through the panel includes a cooling fan, this type of installation is not suitable for

environment in which the inverter may be exposed to drops of water, oil mist, dust, etc.

Make sure that screws, debris etc. do not get into the inverter and cooling fan.

Two installation frames are attached to each of the upper and lower

parts of the inverter. Remove the rear side installation frame on the top

and bottom of the inverter as shown on the right. Upper installation frame (rear side)

Lower installation frame (rear side)

185 mm

Exhaust air

To avoid interference with small protrusions (finger guard protective cooling fan covers) on top of the heat sink, the thickness of the panel of the enclosure should not exceed 10 mm (marked with *1 in the figure below) and the space around the covers (fans) should be cleared.

140 mm

6 m

m Inverter

Inside of enclosure

Enclosure

Installation frame

Depth dimension of the inverter's heat sink section protruded through the panelCooling

air

Panel of enclosure Finger guard protective cooling fan cover10 mm1

24 INSTALLATION AND WIRING

Terminal connection diagrams

2

2.4 Terminal connection diagrams

R1/L11 S1/L21

PC

Frequency setting signals (Analog) 10E(+10V)

10(+5V)

2

(Analog common)

2 3

1

Auxiliary input

Terminal 4 input (Current input)

1

4

Frequency setting potentiometer 1/2W1k

Running

Up to frequency

Overload

Frequency detection

Open collector output common Sink/source common

Motor

Relay output 1 (Fault output)

C1

B1

A1

U V W

Earth (Ground)

0 to 5VDC selectable 0 to 10VDC

Open collector output

Main circuit terminal

Control circuit terminal

0 to 5VDC 0 to 10VDC

C2

B2

A2 Relay output 2

Relay output

M

0 to 20mADC

0 to 5VDC 0 to 10VDC

selectable

4 to 20mADC TXD+

TXD-

RXD+ RXD- GND (SG)

Data transmission

GND

RS-485 terminals

S IN

K

S O

U R

C E

Connector for plug-in option connection

STF

STR

STP(STOP)

RH

RM

RL

JOG

RT

MRS X10

RES

AU

CS

SD

RUN

SU

IPF

OL

FU

SE

Data reception

(+) (-)

5

VCC

(+) (-)

5V

Sink logic

Earth (Ground)

N/-

P/+

Initial value

ON OFF

42

For manufacturer

So (SO)

SOC

Shorting wire

S1

S2

PC

SD SIC

+24 SD

Jumper

(Permissible load current 100mA)

Connector 1 Connector 2

Connector 3

24V external power supply input

Common terminal

24VDC power supply (Common for external power supply transistor)

Forward rotation start Reverse rotation start

Start self-holding selection

Middle speed

High speed

Low speed

Jog operation

Second function selection

Reset

Terminal 4 input selection

Control input signals (No voltage input allowed)

Multi-speed selection

Contact input common

Main circuit

Control circuit

PU connector

USB A connector

USB mini B connector

Voltage/current input switch

selectable

Terminating resistor

Initial value

Initial value

Output stop RDA

RDI

Converter unit

RSO

SE

N/-

P/+

IPF

RDB

FAN

R/L1 S/L2 T/L3

OH

RES SD

PC

+24 C1

B1

A1

(-)

(+) Analog signal output (0 to 10VDC)

(-)

(+) Analog current output (0 to 20mADC)

AM

5

F/C (CA)

24V

INSTALLATION AND WIRING 25

Terminal connection diagrams

A jumper is installed across terminal R1/L11 and terminal P/+, and across terminal S1/L21 and terminal N/-. When using a separate power

supply for the control circuit, remove the jumpers.

The function of these terminals can be changed with the input terminal assignment (Pr.178 to Pr.189). Terminal JOG is also used as the pulse train input terminal. Use Pr.291 to choose JOG or pulse.

The X10 signal (NC contact input specification) is assigned to the terminal MRS in the initial setting. Set Pr.599 = "0" to change the input

specification of the X10 signal to NO contact.

No function is assigned in the initial setting. Use Pr.186 for function assignment.

Terminal input specifications can be changed by analog input specification switchover (Pr.73, Pr.267). To input a voltage (0 to 5 V/0 to 10 V), set

the voltage/current input switch OFF. To input a current (4 to 20 mA), set the voltage/current input switch ON. Terminals 10 and 2 are also used

as a PTC input terminal (Pr.561). It is recommended to use 2 W 1 k when the frequency setting signal is changed frequently.

The function of these terminals can be changed with the output terminal assignment (Pr.195, Pr.196). The function of these terminals can be changed with the output terminal assignment (Pr.190 to Pr.194). No function is assigned in the initial setting. Use Pr.192 for function assignment.

NOTE To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, keep the

cables of the main circuit for input and output separated.

After wiring, wire offcuts must not be left in the inverter.

Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.

When drilling mounting holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the

inverter.

Set the voltage/current input switch correctly. Incorrect setting may cause a fault, failure or malfunction.

Terminals S1, S2, SIC, So (SO), and SOC are for manufacturer setting. Do not remove the shorting wires across terminals S1

and PC, terminals S2 and PC, and terminals SIC and SD. When the shorting wires are removed, the inverter does not

operate.

Connection between the converter unit and the inverter Perform wiring so that the commands sent from the converter unit are transmitted to the inverter without fail. Incorrect

connection may damage the converter unit and the inverter.

For the wiring length, refer to the table below.

For the cable gauge of the cable across the main circuit terminals P/+ and N/- (P and P, N and N), refer to page 29.

Do not install an MCCB across terminals P/+ and N/- (across terminals P and P/+ or across N and N/-). Connecting the opposite polarity of

terminals N/- and P/+ will damage the inverter.

For the terminal used for the X10 signal input, set "10" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function.

(The X10 signal is assigned to terminal MRS in the initial setting.)

For the X10 signal, NC contact input specification is selected in the initial setting. Set Pr.599 = "0" to change the input specification to NO

contact.

For the terminal used for the X11 signal input, set "11" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function. For

RS-485 or any other communication where the start command is only transmitted once, use the X11 signal to save the operation mode at the

time of an instantaneous power failure.

Always connect terminal RDA of the converter unit and terminal MRS (X10) of the inverter, and terminal SE of the converter unit and terminal SD

(sink logic) of the inverter. Not connecting these terminals may damage the converter unit.

Total wiring length Across terminals P and P and terminals N and N 50 m or less

Other control signal cables 30 m or less

Inverter Converter unit (FR-CC2-C)

M R1/L11 S1/L21

R/L1

S/L2

T/L3

Power supply

MCCB MC U V W

R1/L11 S1/L21

P/+P/+ N/-N/-

X11

RES

SD

IPF

RSO

SE

MRS(X10)

RDA

RDB

26 INSTALLATION AND WIRING

Main circuit terminals

2

2.5 Main circuit terminals

2.5.1 Details on the main circuit terminals of the inverter

2.5.2 Details on the main circuit terminals of the converter unit (FR-CC2-C)

Terminal symbol Terminal name Terminal function description Refer

to page

U, V, W Inverter output Connect these terminals to a three-phase squirrel cage motor or an PM motor.

-

R1/L11, S1/L21

Power supply for the control circuit

Connected to terminals P/+ and N/-. To retain the fault display and fault output, or to use the converter unit (FR-CC2-C), remove the jumpers installed across terminals R1/L11 and S1/L21, and supply external power to these terminals. The power capacity necessary when separate power is supplied from terminals R1/L11 and S1/L21 is 80 VA.

41

P/+, N/- Converter unit connection Connect the converter unit (FR-CC2-C). 25

Earth (ground) For earthing (grounding) the inverter chassis. Be sure to earth (ground) the inverter.

31

Terminal symbol Terminal name Terminal function description Refer

to page R/L1, S/L2, T/L3

AC power input Connect these terminals to the commercial power supply. -

R1/L11, S1/L21

Power supply for the control circuit

Connected to the AC power supply terminals R/L1 and S/L2. To retain the fault display and fault output, remove the jumpers across terminals R/L1 and R1/L11 and across S/L2 and S1/L21, and supply external power to these terminals. When using a separate power supply from R1/L11 and S1/L21, the necessary power capacity of the separate power supply is 80 VA.

41

P/+, N/- Inverter connection Connect to terminals P/+ and N/- of the inverter. 25

Earth (ground) For earthing (grounding) the converter unit chassis. Be sure to earth (ground) the converter.

31

INSTALLATION AND WIRING 27

Main circuit terminals

2.5.3 Terminal layout of the main circuit terminals, wiring of power supply and the motor

NOTE Make sure the power cables are connected to terminals R/L1, S/L2, and T/L3 of the converter unit. (Phase need not be

matched.) Never connect the power cable to terminals U, V, and W of the inverter. Doing so will damage the inverter.

Connect the motor to terminals U, V, and W of the inverter. (The phases must be matched.)

When wiring the main circuit conductor, tighten a nut from the right side of the conductor.

When wiring two wires, place wires on both sides of the conductor. (Refer to the diagram below.)

For wiring, use bolts (nuts) provided with the inverter.

When wiring the main circuit conductor (terminals R/L1, S/L2, T/L3) of the converter unit (FR-CC2-C), use the bolts (nuts) for

main circuit wiring, which are provided on the front side of the conductor.

FR-CC2-C355K to FR-CC2-C560K FR-F862-05450 to FR-F862-08500

Jumper

Charge lamp

P/+N/-

To inverter

R1/L11 S1/L21

R/L1 S/L2 T/L3

Power supply

Charge lamp

Jumper

M Motor

N/-

P/+

To converter unit

R1/L11 S1/L21

FR-CC2-C355K FR-CC2-C400K, C560K

Connect the cables here. Connect the cables here.

28 INSTALLATION AND WIRING

Main circuit terminals

2

2.5.4 Applicable cables and wiring length Select a recommended cable size to ensure that the voltage drop ratio is within 2%.

If the wiring distance is long between the inverter and motor, the voltage drop in the main circuit will cause the motor torque to

decrease especially at a low speed.

The following table shows a selection example for the wiring length of 20 m (575 V input power supply).

SLD rating (Pr.570 Multiple rating setting = "0") Converter unit (FR-CC2-C)

Inverter

It is the gauge of the cable with the continuous maximum permissible temperature of 90C or higher (LMFC (heat resistant flexible cross-linked

polyethylene insulated cable), etc.). It assumes a surrounding air temperature of 50C or lower and in-enclosure wiring.

It is the gauge of the cable with continuous maximum permissible temperature of 90C (THHN cable). It assumes a surrounding air temperature

of 40C or lower and in-enclosure wiring.

(For the use in the United States or Canada, refer to page 83.)

The terminal screw size indicates the size of a terminal screw for R/L1, S/L2, T/L3, U, V, W, P/+, N/-, and a screw for earthing (grounding).

The screw size for earthing (grounding) terminal is indicated in parentheses.

LD rating (Pr.570 Multiple rating setting = "1") Converter unit (FR-CC2-C)

Inverter

It is the gauge of the cable with the continuous maximum permissible temperature of 90C or higher (LMFC (heat resistant flexible cross-linked

polyethylene insulated cable), etc.). It assumes a surrounding air temperature of 50C or lower and in-enclosure wiring.

It is the gauge of the cable with continuous maximum permissible temperature of 90C (THHN cable). It assumes a surrounding air temperature

of 40C or lower and in-enclosure wiring.

(For the use in the United States or Canada, refer to page 83.)

The terminal screw size indicates the size of a terminal screw for R/L1, S/L2, T/L3, U, V, W, P/+, N/-, and a screw for earthing (grounding).

The screw size for earthing (grounding) terminal is indicated in parentheses.

Converter model

FR-CC2-[ ]

Terminal screw size

Tightening torque

Nm

Crimp terminal Cable gauge

HIV cables, etc. (mm2) AWG/MCM

R/L1, S/L2, T/L3

P/+, N/- Earthing

(grounding) cable

R/L1, S/L2, T/L3

P/+, N/-

Earthing (grounding)

cable

R/L1, S/L2, T/L3

P/+, N/-

Earthing (grounding)

cable C355K M12 (M10) 46 2100-12 2100-12 100-10 2100 2100 100 2300 2300 4/0 C450K M12 (M10) 46 2150-12 2200-12 100-10 2150 2200 100 2350 2400 300 C560K M12 (M10) 46 2200-12 2250-12 100-10 2200 2250 100 2400 2500 300

Inverter model

FR-F862-[ ]

Terminal screw size

Tightening torque

Nm

Crimp terminal Cable gauge

HIV cables, etc. (mm2) AWG/MCM

U, V, W P/+, N/- Earthing

(grounding) cable

U, V, W

P/+, N/-

Earthing (grounding)

cable

U, V, W

P/+, N/-

Earthing (grounding)

cable 05450 M12 (M10) 46 2125-12 2100-12 100-10 2125 2100 100 2350 2300 4/0 06470 M12 (M10) 46 2150-12 2200-12 100-10 2150 2200 100 2350 2400 300 08500 M12 (M10) 46 2250-12 2250-12 100-10 2250 2250 100 2500 2500 300

Converter model

FR-CC2-[ ]

Terminal screw size

Tightening torque

Nm

Crimp terminal Cable gauge

HIV cables, etc. (mm2) AWG/MCM

R/L1, S/L2, T/L3

P/+, N/- Earthing

(grounding) cable

R/L1, S/L2, T/L3

P/+, N/-

Earthing (grounding)

cable

R/L1, S/L2, T/L3

P/+, N/-

Earthing (grounding)

cable C355K M12 (M10) 46 2100-12 2100-12 100-10 2100 2100 100 2300 2300 4/0 C450K M12 (M10) 46 2150-12 2200-12 100-10 2150 2200 100 2350 2400 300 C560K M12 (M10) 46 2200-12 2250-12 100-10 2200 2250 100 2400 2500 300

Inverter model

FR-F862-[ ]

Terminal screw size

Tightening torque

Nm

Crimp terminal Cable gauge

HIV cables, etc. (mm2) AWG/MCM

U, V, W P/+, N/- Earthing

(grounding) cable

U, V, W

P/+, N/-

Earthing (grounding)

cable

U, V, W

P/+, N/-

Earthing (grounding)

cable 05450 M12 (M10) 46 2125-12 2100-12 100-10 2125 2100 100 2300 2300 4/0 06470 M12 (M10) 46 2150-12 2200-12 100-10 2150 2200 100 2350 2400 300 08500 M12 (M10) 46 2200-12 2250-12 100-10 2200 2250 100 2400 2500 300

INSTALLATION AND WIRING 29

Main circuit terminals

The line voltage drop can be calculated by the following formula:

Line voltage drop [V]=

Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque

reduction) in the low speed range.

NOTE Tighten the terminal screw to the specified torque.

A screw that has been tightened too loosely can cause a short circuit or malfunction.

A screw that has been tightened too tightly can cause a short circuit or malfunction due to the unit breakage.

Use crimp terminals with insulation sleeves to wire the power supply and motor.

Total wiring length With induction motor Connect one or more general-purpose motors within the total wiring length 500 m.

With PM motor Use the wiring length of 100 m or shorter when connecting a PM motor.

Use one PM motor for one inverter. Multiple PM motors cannot be connected to an inverter.

NOTE Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray capacitances of the

wiring, leading to a malfunction of the overcurrent protective function or fast response current limit function or a malfunction or

fault of the equipment connected on the inverter output side. If the fast-response current limit function malfunctions, disable

this function. (For the details of Pr.156 Stall prevention operation selection, refer to the Instruction Manual (Detailed) of the

FR-F860.)

For the details of Pr.72 PWM frequency selection, refer to the Instruction Manual (Detailed) of the FR-F860.

Total wiring length

wire resistance [m/m] wiring distance [m] current [A] 1000

500 m or less

300 m

300 m

300 m+300 m=600 m

30 INSTALLATION AND WIRING

Main circuit terminals

2

2.5.5 Earthing (grounding) precautions Always earth (ground) the motor, the inverter, and the converter unit.

Purpose of earthing (grounding) Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to the ground before use.

An electrical circuit is usually insulated by an insulating material and encased. However, it is impossible to manufacture an

insulating material that can shut off a leakage current completely, and actually, a slight current flows into the case. The

purpose of earthing (grounding) the case of an electrical apparatus is to prevent operators from getting an electric shock from

this leakage current when touching it.

To avoid the influence of external noises, the earthing (grounding) is important to EMI-sensitive equipment that handle low-

level signals or operate very fast such as audio equipment, sensors, computers.

Earthing (grounding) system to be established As described previously, the purpose of earthing (grounding) is roughly classified into the electrical shock prevention and the

prevention of malfunction due to the influence of electromagnetic noise. These two purposes should be clearly distinguished,

and the appropriate earth (ground) system must be established to prevent the leakage current having the inverter's high

frequency components from reversing through another earth (ground) point for malfunction prevention by following these

instructions.

Make the separate earth (ground) connection (I) for high frequency products such as the inverter from any other devices

(EMI-sensitive devices described above) wherever possible.

Establishing adequate common (single-point) earth (ground) system (II) shown in the following figure is allowed only in

cases where the separate earth (ground) system (I) is not feasible. Do not make inadequate common (single-point) earth

(ground) connection (III).

As leakage currents containing many high frequency components flows into the earthing (grounding) cables of the inverter

and peripheral devices the inverter must also be earthed (grounded) separately from the EMI-sensitive devices described

above.

In a high building, it may be effective to use its iron structure frames as earthing (grounding) electrode for EMI prevention in

order to separate from the earth (ground) system for electric shock prevention.

Earthing (Grounding) must conform to the requirements of national and local safety regulations and electrical codes

(NEC section 250, IEC 61140 class 1 and other applicable standards).

A neutral-point earthed (grounded) power supply in compliance with EN standard must be used.

Use the thickest possible earthing (grounding) cable. The earthing (grounding) cable should be equal to the size

indicated in the table on page 29.

The earthing (grounding) point should be as close as possible to the inverter, and the earth (ground) cable length should

be as short as possible.

Run the earthing (grounding) cable as far away as possible from the I/O wiring of the EMI-sensitive devices and run

them in parallel in the minimum distance.

Inverter/ converter

unit EMI-sensitive

devices

(I) Separate earthing (grounding): Good

EMI-sensitive devices

(II) Common (single-point) earthing (grounding): OK

Inverter/ converter

unit

Inverter/ converter

unit

EMI-sensitive devices

(III) Inadequate common (single-point) earthing (grounding): Bad

INSTALLATION AND WIRING 31

Control circuit

2.6 Control circuit

2.6.1 Details on the control circuit terminals of the inverter

The input signal function of the terminals in can be selected by setting Pr.178 to Pr.196 (I/O terminal function selection). For the parameter details, refer to the Instruction Manual (Detailed) of the FR-F860.

Input signal

Ty pe Terminal

symbol Terminal name Terminal function description Rated specification

C on

ta ct

in pu

t

STF Forward rotation start Turn ON the STF signal to start forward rotation and turn it OFF to stop.

When the STF and STR signals are turned ON simultaneously, the stop command is given.

Input resistance: 4.7 k Voltage when contacts are open: 21 to 27 VDC Current when contacts are short- circuited: 4 to 6 mADC

STR Reverse rotation start Turn ON the STR signal to start reverse rotation and turn it OFF to stop.

STP (STOP) Start self-holding selection

Turn ON the STP (STOP) signal to self-hold the start signal.

RH RM RL

Multi-speed selection Multi-speed can be selected according to the combination of the RH, RM and RL signals.

JOG

Jog mode selection Turn ON the JOG signal to enable JOG operation (initial setting) and turn ON the start signal (STF or STR) to start JOG operation.

Pulse train input Terminal JOG is also used as the pulse train input terminal. To use as a pulse train input terminal, change the Pr.291 setting. (maximum input pulse: 100k pulses/s)

Input resistance: 2 k Current when contacts are short- circuited: 8 to 13 mADC

RT Second function selection

Turn ON the RT signal to enable the second function. When the second function such as "second torque boost" and "second V/F (base frequency)" is set, turning ON the RT signal enables the selected function.

Input resistance: 4.7 k Voltage when contacts are open: 21 to 27 VDC Current when contacts are short- circuited: 4 to 6 mADC

MRS (X10)

Output stop (Inverter operation enable)

Connect to terminal RDA of the converter unit (FR-CC2-C). When the RDA signal is turned OFF, the inverter output is shut off. The X10 signal (NC contact) is assigned to terminal MRS in the initial setting. Use Pr.599 to change the specification to NO contact.

RES Reset

Use this signal to reset a fault output provided when a protective function is activated. Turn ON the RES signal for 0.1 second or longer, then turn it OFF. In the initial setting, reset is always enabled. By setting Pr.75, reset can be enabled only at an inverter fault occurrence. The inverter recovers about 1 second after the reset is released.

AU Terminal 4 input selection

The terminal 4 function is available only when the AU signal is ON Turning ON the AU signal disables the terminal 2 function.

CS No function Use Pr.186 CS terminal function selection for function assignment.

SD

Contact input common (sink)

Common terminal for the contact input terminal (sink logic).

External transistor common (source)

Connect this terminal to the power supply common terminal of a transistor output (open collector output) device, such as a programmable controller, in the source logic to avoid malfunction by undesirable current.

24 VDC power supply common

Common terminal for the 24 VDC power supply (terminal PC, terminal +24) Isolated from terminals 5 and SE.

PC

External transistor common (sink)

Connect this terminal to the power supply common terminal of a transistor output (open collector output) device, such as a programmable controller, in the source logic to avoid malfunction by undesirable current.

Power supply voltage range: 19.2 to 28.8 VDC Permissible load current: 100 mA

Contact input common (source)

Common terminal for contact input terminal (source logic).

24 VDC power supply common

Can be used as a 24 VDC 0.1 A power supply.

32 INSTALLATION AND WIRING

Control circuit

2

Set Pr.73, Pr.267, and the voltage/current input switch correctly, then input an analog signal in accordance with the setting. Applying a voltage with the voltage/current input switch ON (current input is selected) or a current with the switch OFF (voltage input is selected)

could cause component damage of the inverter or analog circuits of output devices. (For the details, refer to the Instruction Manual (Detailed) of

the FR-F860.)

Sink logic is initially set.

Output signal

F re

qu en

cy s

et tin

g

10E Frequency setting power supply

When connecting the frequency setting potentiometer at an initial status, connect it to terminal 10. Change the input specifications of terminal 2 using Pr.73 when connecting it to terminal 10E.

10 0.4 VDC. Permissible load current: 10 mA

10 50.5 VDC. Permissible load current: 10 mA

2 Frequency setting (voltage)

Inputting 0 to 5 VDC (or 0 to 10 V, 0 to 20 mA) provides the maximum output frequency at 5 V (10 V, 20 mA) and makes input and output proportional. Use Pr.73 to switch among input 0 to 5 VDC (initial setting), 0 to 10 VDC, and 0 to 20 mA. Set the voltage/current input switch in the ON position to select current input (0 to 20 mA).

For voltage input, Input resistance: 10 1 k Maximum permissible voltage: 20 VDC For current input, Input resistance: 245 5 Permissible maximum current: 30 mA

4 Frequency setting (current)

Inputting 4 to 20 mADC (or 0 to 5 V, 0 to 10 V) provides the maximum output frequency at 20 mA and makes input and output proportional. This input signal is valid only when the AU signal is ON (terminal 2 input is invalid). Use Pr.267 to switch among input 4 to 20 mA (initial setting), 0 to 5 VDC, and 0 to 10 VDC. Set the voltage/current input switch in the OFF position to select voltage input (0 to 5 V/0 to 10 V). Use Pr.858 to switch terminal functions.

1 Frequency setting auxiliary

Input 0 to 5 VDC or 0 to 10 VDC to add this signal to the frequency setting signal input via terminal 2 or 4. Use Pr.73 to switch between input 0 to 5 VDC and 0 to 10 VDC (initial setting). Use Pr.868 to switch terminal functions.

Input resistance: 10 1 k Permissible maximum voltage: 20 VDC

5 Frequency setting common

Common terminal for the frequency setting signal input via terminal 2 or 4 frequency setting signal (via terminal 2, 1 or 4) and for the analog output terminals AM and CA. Do not earth (ground).

T he

rm is

to r

10 2

PTC thermistor input For receiving PTC thermistor outputs. When PTC thermistor is valid (Pr.561 "9999"), terminal 2 is not available for frequency setting.

Applicable PTC thermistor specification, Overheat detection, resistance: 0.5 to 30 k (Set by Pr.561)

E xt

er na

l p ow

er s

u pp

ly in

pu t

+24 24 V external power supply input

For connecting a 24 V external power supply. If a 24 V external power supply is connected, power is supplied to the control circuit while the main power circuit is OFF.

Input voltage: 23 to 25.5 VDC Input current: 1.4 A or less

Ty pe Terminal

symbol Terminal name Terminal function description Rated specification

R el

ay

A1, B1, C1

Relay output 1 (fault output)

1 changeover contact output that indicates that an inverter's protective function has been activated and the outputs are stopped. Fault: discontinuity across B and C (continuity across A and C), Normal: continuity across B and C (discontinuity across A and C)

Contact capacity: 230 VAC 0.3 A (power factor = 0.4) 30 VDC 0.3 AA2,

B2, C2

Relay output 2 1 changeover contact output

Ty pe Terminal

symbol Terminal name Terminal function description Rated specification

Voltage/current input switch

2 4

switch1 switch2

INSTALLATION AND WIRING 33

Control circuit

Communication

Terminals for manufacturer setting

O pe

n co

lle ct

or

RUN Inverter running The output is in LOW state when the inverter output frequency is equal to or higher than the starting frequency (initial value: 0.5 Hz). The output is in HIGH state during stop or DC injection brake operation.

Permissible load: 24 VDC (maximum 27 VDC) 0.1 A (The voltage drop is 2.8 V at maximum while the signal is ON.) The open collector transistor is ON (conductive) in LOW state. The transistor is OFF (not conductive) in HIGH state.

SU Up to frequency

The output is in LOW state when the output frequency is within the set frequency range 10% (initial value). The output is in HIGH state during acceleration/deceleration and at a stop.

Fault code (4 bits) output.

OL Overload alarm

The output is in LOW state when stall prevention is activated by the stall prevention function. The output is in HIGH state when stall prevention is canceled.

IPF Open collector output No function is assigned in the initial setting. The function can be assigned by setting Pr.192.

FU Frequency detection

The output is in LOW state when the inverter output frequency is equal to or higher than the preset detection frequency, and is in HIGH state when it is less than the preset detection frequency.

SE Open collector output common

Common terminal for terminals RUN, SU, OL, IPF, FU

A na

lo g

AM Analog voltage output

Among several monitor items such as output frequency, select one to output it via these terminals. The signal is not output during an inverter reset. The size of output signal is proportional to the magnitude of the corresponding monitoring item. Use Pr.55, Pr.56, and Pr.866 to set full scales for the monitored output frequency, output current, and torque.

Output item: Output frequency (initial setting)

Output signal: 0 to 10 VDC, Permissible load current: 1 mA (load impedance 10 k or more) Resolution: 8 bits

CA Analog current output

Load impedance: 200 to 450 Output signal: 0 to 20 mADC

Ty pe Terminal

symbol Terminal name Terminal function description

R S

-4 8

5

PU connector

With the PU connector, communication can be made through RS-485. (For connection on a 1:1 basis only) Conforming standard: EIA-485 (RS-485) Transmission format: Multidrop link Communication speed: 4800 to 115200 bps Wiring length: 500 m

R S

-4 85

te rm

in a

ls

TXD+ Inverter transmission terminal

The RS-485 terminals support the RS-485 communication. Conforming standard: EIA-485 (RS-485) Transmission format: Multidrop link Communication speed: 300 to 115200 bps Overall length: 500 m

TXD-

RXD+ Inverter reception terminalRXD-

GND (SG)

Earthing (grounding)

U S

B

USB A connector A connector (receptacle). Plug a USB memory device into this connector to copy parameter settings or use the trace function. Interface: Conforms to USB 1.1

(USB 2.0 full speed compatible) Transmission speed: 12 Mbps

USB B connector

Mini B connector (receptacle). By connecting an inverter to the personal computer through USB, FR Configurator2 can be used for setting the inverter, monitoring, and testing the operation.

Terminal symbol Terminal function description

S1, S2, SIC, So (SO), SOC

Terminals S1, S2, SIC, So (SO), and SOC are for manufacturer setting. Do not connect anything to there. Doing so may cause an inverter failure. Do not remove the shorting wires across terminals S1 and PC, terminals S2 and PC, and terminals SIC and SD. Removing either shorting wire disables the inverter operation.

Ty pe Terminal

symbol Terminal name Terminal function description Rated specification

34 INSTALLATION AND WIRING

Control circuit

2

2.6.2 Details on the control circuit terminals of the converter unit (FR-CC2-C)

The input signal function of the terminals in can be selected by setting Pr.178, Pr.187, Pr.189 to Pr.195 (I/O terminal function selection). For the parameter details, refer to the Instruction Manual of the FR-CC2-C.

Input signal

Ty pe Terminal

symbol Terminal name Terminal function description Rated specification

C on

ta ct

in pu

t

RES Reset

Use this signal to reset a fault output provided when a protective function is activated. Turn ON the RES signal for 0.1 second or longer, then turn it OFF. In the initial setting, reset is always enabled. By setting Pr.75, reset can be set enabled only at fault occurrence of the converter unit. The inverter recovers about 1 second after the reset is released.

Input resistance: 4.7 k Voltage when contacts are open: 21 to 27 VDC Current when contacts are short- circuited: 4 to 6 mADC

OH External thermal relay input

The External thermal relay input (OH) signal is used when using an external thermal relay or a thermal protector built into the motor to protect the motor from overheating. When the thermal relay is activated, the inverter is shut off due to the fault occurrence of the external thermal relay operation (E.OHT).

RDI Contact input The function can be assigned by setting Pr.178.

SD

Contact input common (sink)

Common terminal for contact input terminal (sink logic)

External transistor common (source)

Connect this terminal to the power supply common terminal of a transistor output (open collector output) device, such as a programmable controller, in the source logic to avoid malfunction by undesirable current.

24 VDC power supply common

Common terminal for the 24 VDC power supply (terminal PC, terminal +24) Isolated from terminals 5 and SE.

PC

External transistor common (sink)

Connect this terminal to the power supply common terminal of a transistor output (open collector output) device, such as a programmable controller, in the source logic to avoid malfunction by undesirable current.

Power supply voltage range: 19.2 to 28.8 VDC Permissible load current: 100 mA

Contact input common (source)

Common terminal for contact input terminal (source logic).

24 VDC power supply common

Can be used as a 24 VDC 0.1 A power supply.

P ow

er s

up pl

y in

pu t

+24 24 V external power supply input

For connecting a 24 V external power supply. If a 24 V external power supply is connected, power is supplied to the control circuit while the main power circuit is OFF.

Input voltage: 23 to 25.5 VDC Input current: 1.4 A or less

INSTALLATION AND WIRING 35

Control circuit

Output signal

2.6.3 Control logic (sink/source) change Switch the control logic of input signals as necessary.

To change the control logic, change the jumper connector position on the control circuit board.

Connect the jumper connector to the connector pin of the desired control logic.

The control logic of input signals is initially set to the sink logic (SINK).

(The output signals may be used in either the sink or source logic independently of the jumper connector position.)

NOTE Make sure that the jumper connector is installed correctly.

Never change the control logic while power is ON.

Ty pe Terminal

symbol Terminal name Terminal function description Rated specification

R el

a y

A1, B1, C1

Relay output 1 (fault output)

1 changeover contact output that indicates that the protective function of the converter unit has been activated and the outputs are stopped. Fault: discontinuity across B and C (continuity across A and C), Normal: continuity across Band C (discontinuity across A and C)

Contact capacity: 230 VAC 0.3 A (power factor = 0.4) 30 VDC 0.3 A

88R, 88S

For manufacturer setting. Do not use.

O pe

n co

lle ct

or

RDA Inverter operation enable (NO contact)

The output is in LOW state when the converter unit operation is ready. Assign the signal to terminal MRS (X10) of the inverter. The inverter can be started when the RDA status is LOW.

Permissible load: 24 VDC (27 VDC at maximum) 0.1 A (The voltage drop is 2.8 V at maximum while the signal is ON.) The open collector transistor is ON (conductive) in LOW state. The transistor is OFF (not conductive) in HIGH state.

RDB Inverter operation enable (NC contact)

The output is in LOW state when a converter unit fault occurs or the converter is reset. The inverter can be started when the RDB status is HIGH.

RSO Inverter reset The output is in LOW state when the converter is reset (RES-ON). Assign the signal to the terminal RES of the inverter. The inverter is reset when it is connected with the RSO status LOW.

IPF Instantaneous power failure

The output is in LOW state when an instantaneous power failure is detected.

FAN Cooling fan fault The output is in LOW state when a cooling fan fault occurs.

SE Open collector output common

Common terminal for terminals RDA, RDB, RSO, IPF, FAN Connect this terminal to the terminal SD (sink logic) or PC (source logic) of the inverter.

CAUTION Do not use the empty terminals (NCs) of the control circuit. Doing so may lead to damage of the converter unit

and the inverter. Always connect between terminal RDA of the converter unit and terminal MRS (X10) of the inverter, and between

terminal SE of the converter unit and terminal SD (terminal PC in the source logic) of the inverter. Failure to do so may lead to damage of the converter unit.

Jumper connector For sink logic

SOURCE

SINK

36 INSTALLATION AND WIRING

Control circuit

2

Sink logic and source logic In the sink logic, a signal turns ON when a current exits from the corresponding signal input terminal.

Terminal SD is common to the contact input signals. Terminal SE is common to the open collector output signals.

In the source logic, a signal turns ON when a current enters into the corresponding signal input terminal.

Terminal PC is common to the contact input signals. Terminal SE is common to the open collector output signals.

When using an external power supply for transistor output

Sink logic

Use terminal PC as a common terminal, and perform

wiring as follows. (Do not connect terminal SD on the

inverter with terminal 0 V for the external power supply.

When using terminals PC-SD as a 24 VDC power supply,

do not install an external power supply in parallel with the

inverter. Doing so may cause a malfunction in the inverter

due to undesirable currents.)

Source logic

Use terminal SD as a common terminal, and perform

wiring as follows. (Do not connect terminal PC on the

inverter with terminal +24 V for the external power supply.

When using terminals PC-SD as a 24 VDC power supply,

do not install an external power supply in parallel with the

inverter. Doing so may cause a malfunction in the inverter

due to undesirable currents.)

Current

PC

STF R

STR R

Source logic

Source connector

Current

SD

STF R

STR R

Sink connector

Sink logic

Current flow concerning the input/output signal when sink logic is selected

Current flow concerning the input/output signal when source logic is selected

DC input (source type)

24 VDC

RUN

SE

TB1

TB18

R

Inverter

R

Current flow

+ -+-

DC input (sink type)

Inverter

24 VDC

RUN

SE

TB1

TB17

R

R

Current flow

QY40P type transistor output unit

TB1

TB2

TB17

TB18

24 VDC SD

PC

STR

STF

Inverter

24 VDC (SD)

Current flow

Constant voltage circuit

QY80 type transistor output unit

Constant voltage circuit

PC

TB1

TB2

TB17Fuse

TB18

STF

STR

SD

Inverter

24 VDC (SD)

24 V

D C

Current flow

INSTALLATION AND WIRING 37

Control circuit

2.6.4 Wiring of inverter control circuit Control circuit terminal layout

This terminal functions operates as terminal CA.

The X10 signal is assigned in the initial setting.

No signal is assigned in the initial setting.

Wiring method Wire insertion

Use crimp terminals and stripped wire for the control circuit wiring. For single wire, the stripped wire can be used without crimp

terminal.

Connect the end of wires (crimp terminal or stranded wire) to the terminal block.

(1) Strip the signal wires as shown below. If too much of the wire is stripped, a short circuit may occur with neighboring wires.

If not enough of the wire is stripped, wires may become loose and fall out.

Twist the stripped end of wires to prevent them from fraying. Do not solder it.

(2) Use appropriate crimp terminals (ferrules, blade terminals, etc.).

Insert wires to the crimp terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.

Check the condition of the crimp terminals after crimping. Do not use the crimp terminals of which the crimping is

inappropriate, or the face is damaged.

Crimp terminals commercially available (as of January 2017)

Phoenix Contact Co., Ltd.

Wire strip length

Wire gauge (mm2)

Ferrule part No. Crimping tool model No.With insulation sleeve Without insulation sleeve For UL wire

0.3 AI 0,34-10TQ - -

CRIMPFOX 6

0.5 AI 0,5-10WH - AI 0,5-10WH-GB

0.75 AI 0,75-10GY A 0,75-10 AI 0,75-10GY-GB

1 AI 1-10RD A 1-10 AI 1-10RD/1000GB

1.25, 1.5 AI 1,5-10BK A 1,5-10 AI 1,5-10BK/1000GB

0.75 (for two wires) AI-TWIN 2 0,75-10GY - -

A ferrule with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.

Applicable for terminals A1, B1, C1, A2, B2, and C2 only.

AM

2 5 4 1 F/C +24 SD SD S1 S2 PC A1 B1 C1 A2 B2 C2SICSo SOC

5 10E 10 SE SE SURUN IPF OL FU PC RL RM RH RT AU SD SD CSSTP MRS (X10)2

RES STF STR JOG

1

3 3

10 mm

Crumpled tip Wires are not inserted into the sleeve

Unstranded wires

Damaged

Wire

Sleeve

0 to 0.5 mm

38 INSTALLATION AND WIRING

Control circuit

2

NICHIFU Co., Ltd.

NOTE When using stranded wires without a crimp terminal, twist enough to avoid short circuit with neighboring terminals or wires.

Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause an inverter damage

or injury.

Wire removal

Common terminals of the control circuit (SD, PC, 5, SE) Terminals SD (sink logic), PC (source logic), 5, and SE are common terminals (0 V) for I/O signals. (All common terminals

are isolated from each other.) Do not earth (ground) these terminals. Avoid connecting terminal SD (sink logic) with terminal

5, terminal PC (source logic) with terminal 5, and terminal SE with terminal 5.

In the sink logic, terminal SD is a common terminal for the contact input terminals (STF, STR, STP (STOP), RH, RM, RL,

JOG, RT, MRS, RES, AU, and CS). The open collector circuit is isolated from the internal control circuit by photocoupler.

In the source logic, terminal PC is a common terminal for the contact input terminals (STF, STR, STP (STOP), RH, RM, RL,

JOG, RT, MRS, RES, AU, and CS). The open collector circuit is isolated from the internal control circuit by photocoupler.

Terminal 5 is a common terminal for the frequency setting terminals (1, 2, and 4) and the analog output terminals (AM and

CA). It should be protected from external noise using a shielded or twisted cable.

Terminal SE is a common terminal for the open collector output terminals (RUN, SU, OL, IPF, and FU). The contact input

circuit is isolated from the internal control circuit by photocoupler.

Wire gauge (mm2) Blade terminal

part No. Insulation cap

part No. Crimping tool

model No. 0.3 to 0.75 BT 0.75-11 VC 0.75 NH 69

(3) Insert each wire into the terminal. When using single wire or stranded wires without a crimp terminal, push the

open/close button all the way down with a flathead screwdriver, and insert the

wire.

Pull the wire while pushing the open/close button all

the way down firmly with a flathead screwdriver.

Flathead screwdriver

Open/close button

Flathead screwdriver

Open/close button

NOTE Pulling out the wire forcefully without pushing the open/close

button all the way down may damage the terminal block.

Use a small flathead screwdriver (tip thickness: 0.4 mm/tip

width: 2.5 mm).

If a flathead screwdriver with a narrow tip is used, terminal

block may be damaged.

Commercially available products (as of February 2016)

Place the flathead screwdriver vertical to the open/close

button. In case the blade tip slips, it may cause an inverter

damage or injury.

Name Model Manufacturer

Screwdriver SZF 0- 0,4 2,5

Phoenix Contact Co., Ltd.

INSTALLATION AND WIRING 39

Control circuit

Signal inputs by contactless switches The contact input terminals of the inverter (STF, STR, STP (STOP), RH, RM, RL, JOG, RT, MRS, RES, AU, CS) can be

controlled using a transistor instead of a contact switch as shown below.

2.6.5 Wiring precautions It is recommended to use a cable of 0.75 mm2 for the connection to the control circuit terminals.

The wiring length should be 30 m at the maximum.

Use two or more parallel micro-signal contacts or twin contacts to prevent

contact faults when using contact inputs since the control circuit input signals

are micro-currents.

To suppress EMI, use shielded or twisted cables for the control circuit

terminals and run them away from the main and power circuits (including the

200V relay sequence circuit). For the cables connected to the control circuit terminals, connect their shields to the common

terminal of the connected control circuit terminal. When connecting an external power supply to the terminal PC, however,

connect the shield of the power supply cable to the negative side of the external power supply. Do not directly earth

(ground) the shield to the enclosure, etc.

Always apply a voltage to the fault output terminals (A1, B1, C1, A2, B2, C2) via a relay coil, lamp, etc.

Separate the wiring of the control circuit away from the wiring of the main circuit.

Make cuts in rubber bush of the inverter side and lead the wires through.

+24 V

STF, etc.

SD Inverter

External signal input using transistor (sink logic)

PC

RSTF, etc.

+24 V

Inverter

External signal input using transistor (source logic)

Micro signal contacts Twin contacts

Rubber bush (viewed from inside)

Make cuts along the lines on the inside with a cutter knife

40 INSTALLATION AND WIRING

Control circuit

2

2.6.6 When using separate power supplies for the control circuit and the main circuit

Cable size for the control circuit power supply (terminals R1/L11 and S1/ L21)

Terminal screw size: M4

Cable gauge: 0.75 mm2 to 2 mm2

Tightening torque: 1.5 Nm

Connection method When a fault occurs, opening of the electromagnetic contactor (MC) on the inverter power supply side results in power loss in

the control circuit, disabling the fault output signal retention. Terminals R1/L11 and S1/L21 are provided to hold a fault signal.

In this case, connect the power supply terminals R1/L11 and S1/L21 of the control circuit to the input side of the MC.

The terminals R1/L11 and S1/L21 are connected to the terminals P/+ and N/- with a jumper respectively. Do not connect the

power cable to incorrect terminals. Doing so may damage the inverter.

(a) Remove the upper screws. (b) Remove the lower screws. (c) Pull the jumper toward you to remove. (d) Connect the separate power supply cable for the control circuit to the upper terminals (R1/L11, S1/L21).

NOTE When using separate power supplies, always remove the jumpers from terminals R1/L11 and S1/L21. The inverter may be

damaged if the jumpers are not removed.

The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than

the input side of the MC.

When using a separate power supply from R1/L11 and S1/L21, the necessary power capacity of the separate power supply is

80 VA.

If the main circuit power is switched OFF (for 0.1 s or more) then ON again, the inverter is reset and a fault output will not be

held.

InverterConverter unitMC R/L1

S/L2

P/+

N/-

T/L3

R1/L11

S1/L21

P/+

N/-

Remove the jumper

R1/L11 S1/L21

Power supply terminal block for the control circuit

(c)

(d)

(a) (b)

Power supply terminal block for the control circuit

INSTALLATION AND WIRING 41

Control circuit

2.6.7 When supplying 24 V external power to the control circuit

Connect a 24 V external power supply across terminals +24 and SD. Connecting a 24 V external power supply enables I/O terminal ON/OFF operation, operation panel displays, control functions, and communication during communication operation even during power-OFF of inverter's main circuit power supply. When the main circuit power supply is turned ON, the power supply changes from the 24 V external power supply to the main circuit power supply.

Specification of the applied 24 V external power supply

Commercially available products (as of February 2015)

Starting and stopping the 24 V external power supply operation Supplying 24 V external power while the main circuit power is OFF starts the 24 V external power supply operation.

Likewise, turning OFF the main circuit power while supplying 24 V external power starts the 24 V external power supply

operation.

Turning ON the main circuit power stops the 24 V external power supply operation and enables the normal operation.

NOTE When the 24 V external power is supplied while the main circuit power supply is OFF, the inverter operation is disabled.

In the initial setting, when the main power supply is turned ON during the 24 V external power supply operation, a reset is

performed in the inverter, then the power supply changes to the main circuit power supply. (The reset can be disabled using

Pr.30.)

Confirming the 24 V external power supply input During the 24 V external power supply operation, the alarm lamp blinks.

During the 24 V external power supply operation, the 24 V external power supply operation signal (EV) is output. To use the

EV signal, set "68 (positive logic) or 168 (negative logic)" in one of Pr.190 to Pr.196 (Output terminal function selection) to assign function to an output terminal.

Item Rate Specification Input voltage 23 to 25.5 VDC

Input current 1.4 A or lower

Model Manufacturer S8JX-N05024C Specifications: Capacity 50 W, output voltage 24 VDC, output current 2.1 A Installation method: Front installation with cover

or

S8VS-06024 Specifications: Capacity 60 W, output voltage 24 VDC, output current 2.5 A Installation method: DIN rail installation

For the latest information about OMRON power supply, contact OMRON corporation.

OMRON Corporation

42 INSTALLATION AND WIRING

Control circuit

2

Operation while the 24 V external power is supplied Fault records and parameters can be read and parameters can be written (when the parameter write from the operation

panel is enabled) using the operation panel keys.

The safety stop function is disabled during the 24 V external power supply operation.

During the 24 V external power supply operation, monitored items related to inputs to main circuit power supply, such as

output current and converter output voltage, are invalid.

The alarms, which have occurred when the main circuit power supply is ON, continue to be output after the power supply is

changed to the 24 V external power supply. Perform the inverter reset or turn OFF then ON the power to reset the faults.

The output data is retained when "1 or 11" is set in Pr.495 Remote output selection.

NOTE Inrush current equal to or higher than the 24 V external power supply specification may flow at power-ON. Confirm that the

power supply and other devices are not affected by the inrush current and the voltage drop caused by it. Depending on the

power supply, the inrush current protection may be activated to disable the power supply. Select the power supply and

capacity carefully.

When the wiring length between the external power supply and the inverter is long, the voltage often drops. Select the

appropriate wiring size and length to keep the voltage in the rated input voltage range.

In a serial connection of several inverters, the current increases when it flows through the inverter wiring near the power

supply. The increase of the current causes voltage to drop further. Use the inverter after confirming that the input voltage of

each converter unit is within the rated input voltage range. Depending on the power supply, the inrush current protection may

be activated to disable the power supply. Select the power supply and capacity carefully.

"E.SAF" or "E.P24" may appear when the start-up time of the 24 V power supply is too long (less than 1.5 V/s) in the 24 V

external power supply operation.

"E.P24" may appear when the 24 V external power supply input voltage is low. Check the external power supply input.

Do not touch the control circuit terminal block (circuit board) during the 24 V power supply operation (when conducted).

Otherwise you may get an electric shock or burn.

INSTALLATION AND WIRING 43

Communication connectors and terminals

2.7 Communication connectors and terminals

2.7.1 PU connector Removal and reinstallation of the accessory cover

Mounting the operation panel (FR-LU08) or parameter unit (FR-PU07) on the enclosure surface

The operation panel can be used for setting the inverter parameters, monitoring various items, and checking fault

indications.

Having an operation panel (FR-LU08) or a parameter unit (FR-PU07) on the enclosure surface is convenient. With a

connection cable, the operation panel (FR-LU08) or the parameter unit (FR-PU07) can be mounted to the enclosure

surface and connected to the inverter.

Use the option FR-CB2[ ], or connectors and cables available on the market.

(To install the operation panel (FR-LU08), the optional connector (FR-ADP) is required.)

Securely insert one end of the connection cable until the stoppers are fixed.

NOTE Refer to the following table when fabricating the cable on the user side. Keep the total cable length within 20 m.

Commercially available products (as of February 2015)

For the details of the FR-LU08, refer to the FR-LU08 Instruction Manual.

Loosen the two screws on the accessory cover.

(These screws cannot be removed.)

Push the upper part of the accessory cover and pull the

accessory cover to remove.

To install the accessory cover, fit it securely and tighten the screws. (Tightening torque: 0.40 to 0.45 Nm)

Name Model Manufacturer Communication cable SGLPEV-T (Cat5e/300 m) 24AWG 4P Mitsubishi Cable Industries, Ltd.

RJ-45 connector 5-554720-3 Tyco Electronics

Parameter unit connection cable (FR-CB2[ ]) (option)

Operation panel connection connector (FR-ADP) (option)

STF FWD PU

Operation panel (FR-LU08) (option)

Parameter unit (FR-PU07) (option)

44 INSTALLATION AND WIRING

Communication connectors and terminals

2

Communication operation Using the PU connector enables communication operation from a personal computer, etc. When the PU connector is

connected with a personal, FA or other computer by a communication cable, a user program can run to monitor the inverter

or read and write parameters.

Communication can be performed with the Mitsubishi inverter protocol (computer link operation).

(For details, refer to the Instruction Manual (Detailed) of the FR-F860.)

2.7.2 USB connector

USB host communication

Different inverter data can be saved in a USB memory device.

The USB host communication enables the following functions.

The operating status of the USB host can be checked on the LED display of the inverter.

When a device such as a USB battery charger is connected to the USB connector and an excessive current (500 mA or

more) flows, USB host error (UF warning) is displayed on the operation panel.

If a UF warning occurs, disconnect the USB device and set Pr.1049 = "1" to cancel the USB error. (The UF warning can

also be canceled by resetting the inverter power or resetting with the RES signal.)

Interface Conforms to USB 1.1

Transmission speed 12 Mbps

Wiring length Maximum 5 m

Connector USB A connector (receptacle)

Compatible USB memory

(Format) FAT32

Capacity 1 GB or more (used in the recorder mode of the trace function)

Encryption function Not available

Function Description

Parameter copy

Copies the parameter setting from the inverter to the USB memory device. A maximum of 99 parameter setting files can be saved in a USB memory device.

The parameter setting data copied in the USB memory device can be copied to other inverters. This function is useful in backing up the parameter setting or for sharing the parameter setting among multiple inverters.

The parameter setting file can be copied onto a personal computer from the USB memory device and edited using FR Configurator2.

Trace The monitored data and output status of the signals can be saved in a USB memory device. The saved data can be imported to FR Configurator2 to diagnose the operating status of the inverter.

PLC function data copy

This function copies the PLC function project data to a USB memory device when the PLC function is used. The PLC function project data copied in the USB memory device can be copied to other inverters. This function is useful in backing up the parameter setting and for allowing multiple inverters to operate by the same sequence programs.

LED display status Operating status

OFF No USB connection.

ON The communication is established between the inverter and the USB device.

Fast blinking The USB memory device is being accessed. (Do not remove the USB memory device.)

Slow blinking Error in the USB connection.

Place a flathead screwdriver, etc. in a slot and push up the cover to open.

USB host (A connector)

USB device (Mini B connector)

Communication status indicator (LED)

Personal computer (FR Configurator2)

USB

INSTALLATION AND WIRING 45

Communication connectors and terminals

NOTE Do not connect devices other than a USB memory device to the inverter.

If a USB device is connected to the inverter via a USB hub, the inverter cannot recognize the USB memory device properly.

For the details of usage, refer to the Instruction Manual (Detailed) of the FR-F860.

USB device communication A USB (Ver. 1.1) cable connects the inverter with a personal computer.

Parameter setting and monitoring can be performed by FR Configurator 2.

NOTE For the details of FR Configurator2, refer to the Instruction Manual of FR Configurator2.

2.7.3 RS-485 terminal block Communication operation

The RS-485 terminals enables communication operation from a personal computer, etc. When the PU connector is connected

with a personal, FA or other computer by a communication cable, a user program can run to monitor the inverter or read and

write parameters.

Communication can be performed with the Mitsubishi inverter protocol (computer link operation) and MODBUS RTU protocol.

(For details, refer to the Instruction Manual (Detailed) of the FR-F860.)

NOTE To avoid malfunction, keep the RS-485 terminal wires away from the control circuit board.

For wiring of the RS-485 terminals used with a plug-in option, lead the wires on the left side of the plug-in option.

Interface Conforms to USB 1.1

Transmission speed 12 Mbps

Wiring length Maximum 5 m

Connector USB mini B connector (receptacle)

Power supply Self-powered

Conforming standard EIA-485 (RS-485)

Transmission format Multidrop link

Communication speed 115200 bps maximum

Overall length 500 m

Connection cable Twisted pair cable (4 pairs)

Terminating resistor switch Initially-set to "OPEN". Set only the terminating resistor switch of the remotest inverter to the "100" position.

OPEN

100

+ -+ TXD RXD-VCC GND

+ -+ TXD RXD-VCC GND

RDA1 (RXD1+)

RDB1 (RXD1-)

RDA2 (RXD2+)

RDB2 (RXD2-)

SDA1 (TXD1+)

SDB1 (TXD1-)

SDA2 (TXD2+)

SDB2 (TXD2-)

P5S (VCC)

SG (GND)

P5S (VCC)

SG (GND)

46 INSTALLATION AND WIRING

3

PRECAUTIONS FOR USE OF THE INVERTER 47

3 PRECAUTIONS FOR USE OF THE INVERTER

This chapter explains the precautions for use of this product. Always read the instructions before using the equipment.

3.1 Electro-magnetic interference (EMI) and leakage currents ..48 3.2 Power supply harmonics .........................................................51 3.3 Installation of a reactor ............................................................51 3.4 Power-OFF and magnetic contactor (MC) ..............................52 3.5 Precautions against deterioration of the 600 V class motor

insulation...................................................................................53 3.6 Checklist before starting operation ........................................54 3.7 Failsafe system which uses the inverter ................................57

Electro-magnetic interference (EMI) and leakage currents

3.1 Electro-magnetic interference (EMI) and leakage currents

3.1.1 Leakage currents and precautions Capacitances exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current

flows. Since its value depends on the static capacitances, carrier frequency, etc., low acoustic noise operation at the

increased carrier frequency of the inverter will increase the leakage current. Therefore, take the following precautions. Select

the earth leakage current breaker according to its rated sensitivity current, independently of the carrier frequency setting.

To-earth (ground) leakage currents Leakage currents may flow not only into the inverter's own line but also into the other lines through the earthing (grounding)

cable, etc. These leakage currents may operate earth leakage circuit breakers and earth leakage relays unnecessarily.

Precautions

If the carrier frequency setting is high, decrease the Pr.72 PWM frequency selection setting.

Note that motor noise increases. Selecting Pr.240 Soft-PWM operation selection makes the sound inoffensive.

By using earth leakage circuit breakers designed for harmonic and surge suppression in the inverter's own line and other

line, operation can be performed with the carrier frequency kept high (with low noise).

To-earth (ground) leakage currents

Take caution as long wiring will increase the leakage current. Decreasing the carrier frequency of the inverter reduces the

leakage current.

Increasing the motor capacity increases the leakage current.

Line-to-line leakage currents Harmonics of leakage currents flowing in static capacitances between the inverter output cables may operate the external

thermal relay unnecessarily.

Precautions

Use Pr.9 Electronic thermal O/L relay.

If the carrier frequency setting is high, decrease the Pr.72 PWM frequency selection setting.

Note that motor noise increases. Selecting Pr.240 Soft-PWM operation selection makes the sound inoffensive.

To ensure that the motor is protected against line-to-line leakage currents, it is recommended to use a temperature sensor

to directly detect motor temperature.

Installation and selection of the molded case circuit breaker

Install a molded case circuit breaker (MCCB) on the power receiving side to protect the wiring at the inverter input side.

Select an MCCB according to the inverter input side power factor, which depends on the power supply voltage, output

frequency and load. Especially for a completely electromagnetic MCCB, a slightly large capacity must be selected since its

operation characteristic varies with harmonic currents. (Check it in the data of the corresponding breaker.)

Power supply

Thermal relay

Line-to-line static capacitances

MCCB MC

Line-to-line leakage currents path

Motor

Inverter M

48 PRECAUTIONS FOR USE OF THE INVERTER

Electro-magnetic interference (EMI) and leakage currents

3

3.1.2 Precautions against inverter-generated EMI Some electromagnetic noises enter the inverter or the converter unit to cause its malfunction, and others are radiated by the

inverter or the converter unit to cause the peripheral devices to malfunction. Though the inverter or the converter unit is

designed to have high immunity performance, it handles low-level signals, so it requires the following basic techniques. Also,

since the inverter chops outputs at high carrier frequency, that could generate electromagnetic noises. To prevent peripheral

devices from malfunctioning due to electromagnetic noise, take precautions to suppress EMI. These techniques differ slightly

depending on EMI paths.

Basic techniques

- Do not run the power cables (I/O cables) and signal cables of the inverter or the converter unit in parallel with each other

and do not bundle them.

- Use shielded twisted pair cables for the detector connecting and control signal cables and connect the sheathes of the

shielded cables to terminal SD.

- Ground (Earth) the inverter or the converter unit, motor, etc. at one point.

Techniques to reduce electromagnetic noises that enter and cause a malfunction of the inverter or the converter unit (EMI

precautions)

When devices that generate many electromagnetic noises (which use magnetic contactors, electromagnetic brakes, many

relays, for example) are installed near the inverter or the converter unit and it may malfunction due to electromagnetic

noises, the following precautions must be taken:

- Provide surge suppressors for devices that generate many electromagnetic noises to suppress electromagnetic noises.

- Install data line filters (page 50) to signal cables.

- Ground (Earth) the shields of the detector connection and control signal cables with cable clamp metal.

Techniques to reduce electromagnetic noises that are radiated by the inverter or converter unit to cause the peripheral

devices to malfunction (EMI precautions)

Noises generated from the inverter or the converter unit are largely classified into those radiated by the cables connected to

the inverter or the converter unit and its main circuits (I/O), those electromagnetically and electrostatically induced to the

signal cables of the peripheral devices close to the main circuit power supply, and those transmitted through the power

supply cables.

Noise directly radiated from the inverter or the converter unit

Inverter generated electromagnetic noise

Air propagated noise

Electrical path propagated noise

Electromagnetic induction noise

Electrostatic induction noise

Path (c)

Path (b)

Path (a)

Path (h)

Path (g)

Path (d), (e)

Path (f)

Noise propagated through power supply cable

Noise radiated from power supply cable

Noise radiated from motor connection cable

Noise from earthing (grounding) cable due to leakage current

M

(a)

(b)

(c)

(c)

(h)

(g)

(e)

(g)

(d) (f)

Converter unit

Inverter (a)

Motor

Telephone

Sensor

Instrument Receiver

Sensor power supply

PRECAUTIONS FOR USE OF THE INVERTER 49

Electro-magnetic interference (EMI) and leakage currents

Data line filter Data line filter is effective as an EMI precaution. Provide a data line filter for the detector cable, etc.

EMI precautions example

Noise propagation path Precautions

(a)(b)(c)

When devices that handle low-level signals and are liable to malfunction due to electromagnetic noises, e.g. instruments, receivers and sensors, are contained in the enclosure that contains the inverter or the converter unit, or when their signal cables are run near the inverter, the devices may malfunction due to by air-propagated electromagnetic noises. The following precautions must be taken: Install easily affected devices as far away as possible from the inverter or the converter unit. Run easily affected signal cables as far away as possible from the inverter or the converter unit, and its I/O cables.

Do not run the signal cables and power cables (inverter or converter unit I/O cables) in parallel with each other and do not bundle them.

Inserting a line noise filter into the output suppresses the radiated noise from the cables. Use shielded cables as signal cables and power cables and run them in individual metal conduits to produce further effects.

(d)(e)(f)

When the signal cables are run in parallel with or bundled with the power cables, magnetic and static induction noises may be propagated to the signal cables to cause malfunction of the devices and the following precautions must be taken: Install easily affected devices as far away as possible from the inverter or the converter unit. Run easily affected signal cables as far away as possible from the inverter or the converter unit, and its I/O cables.

Do not run the signal cables and power cables (inverter or converter unit I/O cables) in parallel with each other and do not bundle them.

Use shielded cables as signal cables and power cables and run them in individual metal conduits to produce further effects.

(g)

When the power supplies of the peripheral devices are connected to the power supply of the inverter or the converter unit in the same line, its generated noises may flow back through the power supply cables to cause malfunction of the devices and the following precautions must be taken: Install the line noise filter to the power cables (output cables) of the inverter.

(h)

When a closed loop circuit is formed by connecting the peripheral device wiring to the inverter or the converter unit, leakage currents may flow through the earthing (grounding) cable of the inverter or the converter unit to cause the device to malfunction. In that case, disconnecting the earthing (grounding) cable from the device may stop the malfunction of the device.

Converter unit

Line noise filter

Install filter on inverter output side.Install filter on converter unit input side.

Inverter

Sensor Use a twisted pair shielded cable

Enclosure Decrease carrier frequency

Motor Inverter power supply

Separate inverter, converter unit and power line by more than 30 cm (at least 10 cm) from sensor circuit.

Control power supply

Do not earth (ground) enclosure directly. Do not earth (ground) control cable.

Use 4-core cable for motor power cable and use one cable as earth (ground) cable.

Do not earth (ground) shield but connect it to signal common cable.

Line noise filter M

Power supply for

sensor

50 PRECAUTIONS FOR USE OF THE INVERTER

Power supply harmonics

3

3.2 Power supply harmonics

3.2.1 Power supply harmonics The inverter may generate power supply harmonics from its converter circuit to affect the power generator, power factor

correction capacitor etc. Power supply harmonics are different from noise and leakage currents in source, frequency band and

transmission path. Take the following precaution suppression techniques.

The differences between harmonics and noises

Precautions

NOTE The power factor improving capacitor and surge suppressor on the inverter output side may be overheated or damaged by

the harmonic components of the inverter output. Also, since an excessive current flows in the inverter to activate overcurrent

protection, do not provide a capacitor and surge suppressor on the inverter output side when the motor is driven by the

inverter. For power factor improvement, install a reactor on the inverter input side or in the DC circuit.

3.3 Installation of a reactor When the inverter is connected near a large-capacity power transformer (1000 kVA or more) or when a power factor

correction capacitor is to be switched over, an excessive peak current may flow in the power input circuit, damaging the

converter circuit. To prevent this, always install an AC reactor.

Item Harmonics Noise

Frequency Normally 40th to 50th degrees or less (3 kHz or less).

High frequency (several 10 kHz to 1 GHz order).

Environment To-electric channel, power impedance. To-space, distance, wiring path,

Quantitative understanding Theoretical calculation possible. Random occurrence, quantitative grasping difficult.

Generated amount Nearly proportional to the load capacity. Changes with the current variation ratio. (Gets larger as switching speed increases.)

Affected equipment immunity Specified by standards per equipment. Different depending on maker's equipment specifications.

Precaution Provide a reactor. Increase distance.

The harmonic current generated from the inverter

to the input side differs according to various

conditions such as the wiring impedance,

whether a reactor is used or not, and output

frequency and output current on the load side.

For the output frequency and output current, we

understand that this should be calculated in the

conditions under the rated load at the maximum

operating frequency.

The converter unit (FR-CC2-C) is equipped with the DC reactor.

DC reactor 1

Inverter with converter unit

R

S

T Z

Y

X U

V

W

R/L1

S/L2

T/L3

M

AC reactor Do not insert power factor improving capacitor.

MCCB MC

P ow

er s

up pl

y

MCCB MC

Inverter with converter unit

R

S

T Z

Y

X U

V

W

R/L1

S/L2

T/L3

M

5000 5300

4000

3000

2000

1000

110 165 247 330 420 550 kVA

AC reactor

Power supply

Capacities requiring installation of AC reactor

Inverter capacity

P ow

er s

up pl

y sy

st em

ca

pa ci

ty (k

V A

)

PRECAUTIONS FOR USE OF THE INVERTER 51

Power-OFF and magnetic contactor (MC)

3.4 Power-OFF and magnetic contactor (MC)

Converter unit input side magnetic contactor (MC) On the converter unit input side, it is recommended to provide an MC for the following purposes:

(Refer to page 14 for selection.)

To disconnect the inverter from the power supply at activation of a protective function or at malfunctioning of the driving

system (emergency stop, etc.).

To prevent any accident due to an automatic restart at power restoration after an inverter stop made by a power failure.

To separate the inverter from the power supply to ensure safe maintenance and inspection work.

If using an MC for emergency stop during operation, select an MC regarding the converter unit input side current as JEM

1038-AC-3 class rated current.

NOTE Since repeated inrush currents at power ON will shorten the life of the converter circuit (switching life is about 1,000,000

times), frequent starts and stops of the magnetic contactor must be avoided. Turn ON/OFF the inverter start controlling

terminals (STF, STR) to run/stop the inverter.

Inverter start/stop circuit example

As shown below, always use the start signal (ON or OFF of STF(STR) signal) to make a start or stop.

Install a stepdown transformer.

Connect the power supply terminals R1/L11, S1/L21 of the control circuit to the input side of the MC to hold an alarm signal when the inverter's

protective circuit is activated. At this time, remove jumpers across terminals R1/L11 and S1/L21. (Refer to page 41 for removal of the jumper.)

Handling of the magnetic contactor on the inverter's output side Switch the magnetic contactor between the inverter and motor only when both the inverter and motor are at a stop. When the

magnetic contactor is turned ON while the inverter is operating, overcurrent protection of the inverter and such will activate.

When an MC is provided to switch to a commercial power supply, for example, it is recommended to use the electronic bypass

function Pr.135 to Pr.139. (The commercial power supply operation is not available with PM motors.)

Handling of the manual contactor on the inverter's output side A PM motor is a synchronous motor with high-performance magnets embedded inside. High-voltage is generated at the motor

terminals while the motor is running even after the inverter power is turned OFF. In an application where the PM motor is

driven by the load even after the inverter is powered OFF, a low-voltage manual contactor must be connected at the inverter's

output side.

MCCB

Converter unit

Power supply

To the motor

Inverter

Stop

Start

Operation preparation

Start/Stop

P/+

N/-

P/+

N/-

A1

B1

C1

RDA

MC R/L1

S/L2

T/L3 R1/L11

S1/L21

OFF ON

MC

RA

MC RA

MC

RA

U

V

A1

B1

C1

W

SD STF/STR

R1/L11

S1/L21

X10

SE SD

T 1

2 2

52 PRECAUTIONS FOR USE OF THE INVERTER

Precautions against deterioration of the 600 V class motor insulation

3

NOTE Before wiring or inspection for a PM motor, confirm that the PM motor is stopped. In an application, such as fan and blower,

where the motor is driven by the load, a low-voltage manual contactor must be connected at the inverter's output side, and

wiring and inspection must be performed while the contactor is open. Otherwise you may get an electric shock.

Do not open or close the contactor while the inverter is running (outputting).

3.5 Precautions against deterioration of the 600 V class motor insulation

In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals. Especially for a 600V class motor, the surge voltage may deteriorate the insulation.

Surge voltage at a motor terminal by motor wiring length (reference)

When the 600V class motor is driven by the inverter, consider the following measures:

Measures Inverter duty motor

Select an inverter duty motor. Many motor manufacturers sell motors with insulation systems designed to withstand the

stress imposed by PWM inverters

AC reactor

For added protection, install an AC reactor on the inverter output

100%

0

200

150

Vo lta

ge a

t a m

ot or

te rm

in al

(% )

10 20 30 40 50 60 70 80 90 100 Motor wiring length (m)

PRECAUTIONS FOR USE OF THE INVERTER 53

Checklist before starting operation

3.6 Checklist before starting operation The FR-F860 series inverter and FR-CC2-C converter unit are highly reliable products, but incorrect peripheral circuit making

or operation/handling method may shorten the product life or damage the products.

Before starting operation, always recheck the following points.

Point to be checked Action Refer

to page

Check by user

Crimp terminals are insulated. Use crimp terminals with insulation sleeves to wire the power supply and the motor.

-

The wiring between the power supply (R/L1, S/L2, T/L3) and the motor (U, V, W) is correct.

Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform such wiring.

28

No wire offcuts are left from the time of wiring.

Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter and the converter unit clean. When drilling mounting holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the inverter and the converter unit.

-

The main circuit cable gauge is correctly selected.

Use an appropriate cable gauge to suppress the voltage drop to 2% or less. If the wiring distance is long between the inverter and motor, the voltage drop in the main circuit will cause the motor torque to decrease especially during the output of a low frequency.

29

The total wiring length is within the specified length.

Keep the total wiring length is within the specified length. In long distance wiring, charging currents due to stray capacitance in the wiring may degrade the fast-response current limit operation or cause the equipment on the inverter's output side to malfunction. Pay attention to the total wiring length.

29

Precautions are taken against EMI.

The input/output (main circuit) of the inverter and the converter unit includes high frequency components, which may interfere with the communication devices (such as AM radios) used near the inverter and the converter unit. In such case, enable the built-in EMC filter of the converter unit (connect two of the EMC filter ON/OFF female connectors to the ON male connectors) to minimize interference.

49

Countermeasures are taken against electrical corrosion on the motor bearing.

When a motor is driven by the inverter, axial voltage is generated on the motor shaft, which may cause electrical corrosion of the bearing in rare cases depending on the wiring, load, operating conditions of the motor or a specific inverter setting (high carrier frequency). Contact your sales representative to take appropriate countermeasures for the motor. The following shows examples of countermeasures for the inverter. Decrease the carrier frequency. Provide a common mode choke on the output side of the inverter.

Recommended common mode choke: FT-3KM F series FINEMET

common mode choke cores manufactured by Hitachi Metals, Ltd.

FINEMET is a registered trademark of Hitachi Metals, Ltd.

-

On the inverter's output side, there is no power factor correction capacitor, surge suppressor, or radio noise filter installed.

Doing so will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices is connected, immediately remove it.

-

When performing an inspection or rewiring on the product that has been energized, the operator has waited long enough after shutting off the power supply.

For a short time after the power-OFF, a high voltage remains in the smoothing capacitor, and it is dangerous. Before performing an inspection or rewiring, wait 10 minutes or longer after the power supply turns OFF, then confirm that the voltage across the main circuit terminals P/+ and N/- of the inverter is low enough using a tester, etc.

-

The inverter's output side has no short circuit or ground fault occurring.

A short circuit or earth (ground) fault on the inverter's output side may damage the inverter module.

Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused by peripheral circuit inadequacy or an earth (ground) fault caused by wiring inadequacy or reduced motor insulation resistance may damage the inverter module.

Fully check the to-earth (ground) insulation and phase-to-phase insulation of the inverter's output side before power-ON. Especially for an old motor or use in hostile atmosphere, securely check the motor insulation resistance, etc.

-

The circuit is not configured to use the converter unit's input-side magnetic contactor to start/stop the inverter frequently.

Since repeated inrush currents at power ON will shorten the life of the inverter and the converter unit, frequent starts and stops of the magnetic contactor must be avoided. Turn ON/OFF the inverter's start signals (STF, STR) to run/ stop the inverter.

52

54 PRECAUTIONS FOR USE OF THE INVERTER

Checklist before starting operation

3

The voltage applied to the I/O signal circuits of the inverter and the converter unit is within the specifications.

Application of a voltage higher than the permissible voltage to the I/O signal circuits of the inverter and the converter unit or opposite polarity may damage the I/O devices. Especially check the wiring to prevent the speed setting potentiometer from being connected incorrectly to short circuit the terminals 10E and 5.

32

The converter unit and the inverter are correctly connected.

Make sure that terminal P/+ of the converter unit and terminal P/+ of the inverter, and terminal N/- of the converter unit and terminal N- of the inverter are correctly connected. Connecting the opposite polarity of terminals N/- and P/+ will damage the inverter. Also, do not install an MCCB across terminals P/+ and N/- (across terminals P and P/+ or across N and N/-).

Always connect terminal RDA of the converter unit and terminal MRS (X10) of the inverter, and terminal SE of the converter unit and terminal SD (terminal PC for source logic) of the inverter. Not connecting these terminals may damage the converter unit.

26

When using the electronic bypass operation, electrical and mechanical interlocks are provided between the electronic bypass contactors MC1 and MC2.

When using a switching circuit as shown below, chattering due to mis- configured sequence or arc generated at switching may allow undesirable current to flow in and damage the inverter. Mis-wiring may also damage the inverter. (The commercial power supply operation is not available with PM motors.)

If switching to the commercial power supply operation while a failure such as an output short circuit has occurred between the magnetic contactor MC2 and the motor, the damage may further spread. If a failure has occurred between the MC2 and the motor, a protection circuit such as using the OH signal input must be provided.

-

Precautions are taken for power restoration after a power failure.

If the machine must not be restarted when power is restored after a power failure, provide an MC in the converter unit's input side and also make up a sequence which will not switch ON the start signal. If the start signal (start switch) remains ON after a power failure, the inverter will automatically restart as soon as the power is restored.

-

A magnetic contactor (MC) is installed on the converter unit's input side.

On the converter unit's input side, connect an MC for the following purposes: To disconnect the inverter and the converter unit from the power supply at activation of a protective function or at malfunctioning of the driving system (emergency stop, etc.).

To prevent any accident due to an automatic restart at power restoration after an inverter stop made by a power failure.

To separate the inverter and the converter unit from the power supply to ensure safe maintenance and inspection work.

If using an MC for emergency stop during operation, select an MC regarding the converter unit input side current as JEM 1038-AC-3 class rated current.

52

The magnetic contactor on the inverter's output side is properly handled.

Switch the magnetic contactor between the inverter and motor only when both the inverter and motor are at a stop.

52

When using a PM motor, a low- voltage manual contactor is installed on the inverter's output side.

A PM motor is a synchronous motor with high-performance magnets embedded inside. High-voltage is generated at the motor terminals while the motor is running even after the inverter power is turned OFF. In an application, such as fan and blower, where the motor is driven by the load, a low-voltage manual contactor must be connected at the inverter's output side, and wiring and inspection must be performed while the contactor is open. Otherwise you may get an electric shock.

52

EMC precautions are taken for the frequency setting signals.

If electromagnetic noise generated from the inverter and the converter unit causes frequency setting signal to fluctuate and the motor rotation speed to be unstable when changing the motor speed with analog signals, the following precautions are effective: Do not run the signal cables and power cables (inverter and converter unit I/O cables) in parallel with each other and do not bundle them.

Run signal cables as far away as possible from power cables (inverter and converter I/O cables).

Use shielded cables. Install a ferrite core on the signal cable.

-

Point to be checked Action Refer

to page

Check by user

Inverter with converter unit

MC2

MC1

U V W

R/L1 S/L2 T/L3

IM Power supply

Undesirable current

Interlock

PRECAUTIONS FOR USE OF THE INVERTER 55

Checklist before starting operation

A countermeasure is provided for an overload operation.

When performing frequent starts/stops by the inverter, rise/fall in the temperature of the transistor element of the inverter will repeat due to a repeated flow of large current, shortening the life from thermal fatigue. Since thermal fatigue is related to the amount of current, the life can be increased by reducing current at locked condition, starting current, etc. Reducing current may extend the service life but may also cause torque shortage, which leads to a start failure. Adding a margin to the current can eliminate such a condition. For an induction motor, use the inverter and the converter unit of a higher capacity (up to two ranks). For a PM motor, use the inverter and the converter unit, and PM motor of higher capacities.

-

The specifications and rating match the system requirements.

Make sure that the specifications and rating match the system requirements. -

Point to be checked Action Refer

to page

Check by user

56 PRECAUTIONS FOR USE OF THE INVERTER

Failsafe system which uses the inverter

3

3.7 Failsafe system which uses the inverter When a fault is detected by the protective function, the protective function is activated to output a fault signal. However, a fault

signal may not be output at an inverter's fault occurrence when the detection circuit or output circuit fails, etc. Although

Mitsubishi Electric assures the best quality products, provide an interlock which uses inverter status output signals to prevent

accidents such as damage to the machine when the inverter fails for some reason. Also at the same time consider the system

configuration where a failsafe from outside the inverter, without using the inverter, is enabled even if the inverter fails.

Interlock method which uses the inverter status output signals By combining the inverter output signals to provide an interlock as shown below, an inverter failure can be detected.

No. Interlock method Check method Used signals

a Inverter protective function operation

Operation check of an alarm contact. Circuit error detection by negative logic.

Fault (ALM) signal

b Inverter operating status Operation ready signal check. Inverter operation ready (RY) signal

c Inverter running status Logic check of the start signal and running signal. Start (STF/STR) signal Inverter running (RUN) signal

d Inverter running status Logic check of the start signal and output current. Start (STF/STR) signal Output current detection (Y12) signal

(a) Checking by the output of the inverter fault signal

When the inverter's protective function is activated and

the inverter trips, the Fault (ALM) signal is output. (The

ALM signal is assigned to terminal A1B1C1 in the initial

setting).

With this signal, check that the inverter operates

properly.

In addition, negative logic can be set. (ON when the

inverter is normal, OFF when the fault occurs.)

(b) Checking the inverter operating status by the inverter

operation ready completion signal

The Inverter operation ready (RY) signal is output when

the inverter power is ON and the inverter becomes

operative.

Check if the RY signal is output after powering ON the

inverter.

(c) Checking the inverter operating status by the start signal

input to the inverter and inverter running signal

The Inverter running (RUN) signal is output when the

inverter is running. (The RUN signal is assigned to

terminal RUN in the initial setting.)

Check if the Y12 signal is being output while inputting a

start signal to the inverter. (The STF signal is a forward

rotation signal, and the STR signal is a reverse rotation

signal.) Even after the start signal is turned OFF, the

RUN signal is kept output until the inverter makes the

motor to decelerate and to stop. For the logic check,

configure a sequence considering the inverter's

deceleration time.

ON

OFF RES

OFF

ON

Reset ON

O ut

pu t f

re qu

en cy

ALM (when output

at NC contact)

Inverter fault occurrence (trip)

Time

(about 1 s) Reset processing

STF

RH

RY

ON OFF

ON OFF

ON OFF

ON

RUN ON OFF

Time

Power supply

O ut

pu t f

re qu

en cy

Pr. 13 Starting frequency

DC injection brake operation point

DC injection brake operation

Reset processing

PRECAUTIONS FOR USE OF THE INVERTER 57

Failsafe system which uses the inverter

NOTE Changing the terminal assignment using Pr.190 and Pr.196 (Output terminal function selection) may affect the other

functions. Set parameters after confirming the function of each terminal.

For the details of the parameters and signals, refer to the Instruction Manual (Detailed) of the FR-F860.

Backup method outside the inverter Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure status of

the inverter itself. For example, if an inverter CPU fails in a system interlocked with the inverter's fault, STF/STR, and RUN

signals, no fault signal will be output and the RUN signal will be kept ON because the inverter CPU is down.

Provide a speed detector to detect the motor speed and current detector to detect the motor current and consider the backup

system such as performing a check as below according to the level of importance of the system.

(a) Start signal and actual operation check

Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to

the inverter and detected speed of the speed detector or detected current of the current detector. Note that the current

is flowing through the motor while the motor coasts to stop, even after the inverter's start signal is turned OFF. For the

logic check, configure a sequence considering the inverter's deceleration time. In addition, it is recommended to check

the three-phase current when using the current detector.

(b) Command speed and actual operation check

Check for a gap between the actual speed and commanded speed by comparing the inverter's speed command and

the speed detected by the speed detector.

(d) Checking the motor operating status by the start signal input to the inverter and inverter output current detection signal

The Output current detection (Y12) signal is output when the inverter operates and current flows into the motor.

Check if the Y12 signal is being output while inputting a start signal to the inverter. (The STF signal is a forward rotation

signal, and the STR signal is a reverse rotation signal.) The Y12 signal is initially set to be output at 110% rated inverter

current. Adjust the level to around 20% using no load current of the motor as reference with Pr.150 Output current detection level. Like the Inverter running (RUN) signal, even after the start signal is turned OFF, the Y12 signal is kept output until the

inverter stops the output to a decelerating motor. For the logic check, configure a sequence considering the inverter's

deceleration time.

When using various signals, assign the functions to Pr.190 and Pr.196 (Output terminal function selection) referring to the

table on the left.

Output signal

Pr.190 to Pr.196 setting Positive logic Negative logic

ALM 99 199

RY 11 111

RUN 0 100

Y12 12 112

Inverter

Controller

System failure

To the alarm detection sensor

Sensor (speed, temperature,

air volume, etc.)

58 PRECAUTIONS FOR USE OF THE INVERTER

4

PROTECTIVE FUNCTIONS 59

4 PROTECTIVE FUNCTIONS

This chapter explains the PROTECTIVE FUNCTIONS that operates in

this product.

Always read the instructions before using the equipment.

4.1 Inverter fault and indications...................................................60 4.2 Reset method for the protective functions.............................60 4.3 List of fault displays .................................................................61

Inverter fault and indications

60 PROTECTIVE FUNCTIONS

4.1 Inverter fault and indications When a fault occurs in the inverter, a protective function is automatically activated to shut off the inverter output and show

an indication on the operation panel of the inverter.

When any fault occurs, take an appropriate corrective action, then reset the inverter, and resume the operation. Restarting

the operation without a reset may break or damage the inverter.

When a protective function is activated, note the following points.

Inverter fault or alarm indications are categorized as below.

NOTE For the details of fault displays and other malfunctions, refer to the Instruction Manual (Detailed) of the FR-F860.

The past eight faults can be displayed on the operation panel. (Fault history) (For the operation, refer to the operation panel

or the parameter unit Instruction Manual.)

4.2 Reset method for the protective functions Reset the inverter by performing any of the following operations. Note that the accumulated heat value of the electronic

thermal relay function and the number of retries are cleared (erased) by resetting the inverter.

The inverter recovers about 1 s after the reset is released.

NOTE OFF status of the start signal must be confirmed before resetting the inverter fault. Resetting an inverter fault with the start

signal ON restarts the motor suddenly.

Item Description

Fault output signal Opening the magnetic contactor (MC) provided on the input side of the inverter at a fault occurrence shuts off the control power to the inverter, therefore, the fault output will not be retained.

Fault or alarm indication When a protective function is activated, the operation panel displays a fault indication.

Operation restart method While a protective function is activated, the inverter output is kept shutoff. Reset the inverter to restart the operation.

Displayed item Description

Error message A message regarding an operational fault and setting fault by the operation panel and parameter unit is displayed. The inverter output is not shut off.

Warning The inverter output is not shut off even when a warning is displayed. However, failure to take appropriate measures will lead to a fault.

Alarm The inverter output is not shut off. An Alarm (LF) signal can also be output with a parameter setting.

Fault A protective function is activated to shut off the inverter output and output a Fault (ALM) signal.

On the operation panel, press the STOP/RESET key to reset the

inverter.

(This may only be performed when a fault occurs.)

Switch power OFF once, then switch it ON again.

Turn ON the Inverter reset (RES) signal for 0.1 s or more. (If the

RES signal is kept ON, "Err" appears (blinks) to indicate that the

inverter is in a reset status.)

ON

OFF

SD

Inverter

RES

List of fault displays

PROTECTIVE FUNCTIONS 61

4

4.3 List of fault displays For details, refer to the Instruction Manual (Detailed) of the FR-F860.

If faults other than the above appear, contact your sales

representative.

Abbreviation Name

E rr

or m

es sa

ge

HOLD Operation panel lock LOCD Password locked Er1 to Er4 Er8

Parameter write error

rE1 to rE4 rE6 to rE8

Copy operation error

Err. RES signal ON or communication circuit fault

W ar

ni ng

OL Stall prevention (overcurrent) oL Stall prevention (overvoltage) TH Electronic thermal relay function pre-alarm PS PU stop CP Parameter copy SA SA MT1 to MT3 Maintenance timer 1 to 3 UF USB host error

CF Continuous operation during communication fault

LDF Load fault warning

A la

rm FN Fan alarm

F au

lt

E.OC1 Overcurrent trip during acceleration E.OC2 Overcurrent trip during constant speed E.OC3 Overcurrent trip during deceleration or stop

E.OV1 Regenerative overvoltage trip during acceleration

E.OV2 Regenerative overvoltage trip during constant speed

E.OV3 Regenerative overvoltage trip during deceleration or stop

E.THT Inverter overload trip (electronic thermal relay function)

E.THM Motor overload trip (electronic thermal relay function)

E.FIN Heat sink overheat

F au

lt

E.OLT Stall prevention stop E.SOT Loss of synchronism detection E.LUP Upper limit fault detection E.LDN Lower limit fault detection E.GF Output side earth (ground) fault overcurrent E.LF Output phase loss E.OHT External thermal relay operation E.PTC PTC thermistor operation E.OPT Option fault E.OP1 Communication option fault E.16 to E.20 User definition error by the PLC function E.PE Parameter storage device fault E.PUE PU disconnection E.RET Retry count excess E.PE2 Parameter storage device fault E.CPU E.5 to E.7

CPU fault

E.CTE Operation panel power supply short circuit RS-485 terminals power supply short circuit

E.P24 24 VDC power fault E.CDO Abnormal output current detection E.SER Communication fault (inverter) E.AIE Analog input fault E.USB USB communication fault E.SAF Safety circuit fault E.PBT E.13

Internal circuit fault

E.OS Overspeed occurrence E.LCI 4 mA input fault E.PCH Pre-charge fault E.PID PID signal fault E.1 to E.3 Option fault

O th

er s E.0 No fault records

RD Backup in progress

WR Restoration in progress

Abbreviation Name

MEMO

62

5

PRECAUTIONS FOR MAINTENANCE AND INSPECTION 63

5 PRECAUTIONS FOR MAINTENANCE AND INSPECTION

This chapter explains the PRECAUTIONS FOR MAINTENANCE AND

INSPECTION for this product.

Always read the instructions before using the equipment.

5.1 Inspection item..........................................................................64 5.2 Measurement of main circuit voltages, currents and

powers .......................................................................................71

Inspection item

The inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any

fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and

vibration, changes in the parts with time, service life, and other factors.

Precautions for maintenance and inspection When accessing the inverter for inspection, wait for at least 10 minutes after the power supply has been switched OFF, and

then make sure that the voltage across the main circuit terminals P/+ and N/- of the inverter is not more than 30 VDC using a

tester, etc.

5.1 Inspection item

5.1.1 Daily inspection Basically, check for the following faults during operation.

Motor operation fault

Improper installation environment

Cooling system fault

Abnormal vibration, abnormal noise

Abnormal overheat, discoloration

5.1.2 Periodic inspection Check the areas inaccessible during operation and requiring periodic inspection.

Consult us for periodic inspection.

Check and clean the cooling system. .......... Clean the air filter, etc.

Check the tightening and retighten.............. The screws and bolts may become loose due to vibration, temperature

changes, etc. Check and tighten them.

Tighten them according to the specified tightening torque. (Refer to page 29.)

Check the conductors and insulating materials for corrosion and damage.

Measure the insulation resistance.

Check and change the cooling fan and relay.

64 PRECAUTIONS FOR MAINTENANCE AND INSPECTION

Inspection item

5

5.1.3 Daily and periodic inspection

Oil component of the heat dissipation grease used inside the inverter may leak out. The oil component, however, is not flammable, corrosive, nor

conductive and is not harmful to humans. Wipe off such oil component.

It is recommended to install a voltage monitoring device for checking the voltage of the power supplied to the inverter.

One to two years of periodic inspection cycle is recommended. However, it differs according to the installation environment.

Consult us for periodic inspection.

NOTE Continuous use of a leaked, deformed, or degraded smoothing aluminum electrolytic capacitor (as shown in the table above)

may lead to a burst, breakage or fire. Replace such capacitor without delay.

Area of inspection Inspection item Description

Inspection interval Corrective action at

fault occurrence

Check by the userDaily Periodic

General

Surrounding environment

Check the surrounding air temperature, humidity, dirt, corrosive gas, oil mist, etc.

Improve the environment.

Overall unit Check for unusual vibration and noise.

Check fault location and retighten.

Check for dirt, oil, and other foreign material. Clean.

Power supply voltage

Check that the main circuit voltages and control voltages are normal.

Inspect the power supply.

Main circuit

General

(1) Check with megger (across main circuit terminals and earth (ground) terminal).

Contact the manufacturer.

(2) Check for loose screws and bolts. Retighten.

(3) Check for overheat traces on the parts. Contact the manufacturer.

(4) Check for stain. Clean.

Conductors, cables (1) Check conductors for distortion. (2) Check cable sheaths for breakage and

deterioration (crack, discoloration, etc.).

Contact the manufacturer.

Contact the manufacturer.

Transformer/ reactor

Check for unusual odor and abnormal increase of whining sound.

Stop the equipment and contact the manufacturer.

Terminal block Check for a damage. Stop the equipment and contact the manufacturer.

Smoothing aluminum electrolytic capacitor

(1) Check for liquid leakage. Contact the manufacturer.

(2) Check for safety valve projection and bulge. Contact the manufacturer.

(3) Judge by visual check

Relay/contactor Check that the operation is normal and no chattering sound is heard.

Contact the manufacturer.

Control circuit, protective circuit

Operation check

(1) Check that the output voltages across phases are balanced while operating the inverter alone.

Contact the manufacturer.

(2) Check that no fault is found in protective and display circuits in a sequence protective operation test.

Contact the manufacturer.

C om

po ne

nt s

ch ec

k

Overall (1) Check for unusual odor and discoloration.

Stop the equipment and contact the manufacturer.

(2) Check for serious rust development. Contact the manufacturer.

Aluminum electrolytic capacitor

(1) Check for liquid leakage in a capacitor and deformation trace.

Contact the manufacturer.

(2) Visual check and judge by the life check of the control circuit capacitor. (Refer to the Instruction Manual (Detailed) of the FR-F860).

Cooling system

Cooling fan

(1) Check for unusual vibration and noise. Replace the fan.

(2) Check for loose screws and bolts. Fix with the fan cover fixing screws

(3) Check for stain. Clean.

Heat sink (1) Check for clogging. Clean.

(2) Check for stain. Clean.

Display Indication

(1) Check that indications are correct. Contact the manufacturer.

(2) Check for stain. Clean.

Meter/counter Check that readouts are correct. Stop the equipment and contact the manufacturer.

Load motor

Operation check Check for vibration and abnormal increase in operation noise.

Stop the equipment and contact the manufacturer.

PRECAUTIONS FOR MAINTENANCE AND INSPECTION 65

Inspection item

5.1.4 Checking the inverter and converter modules Preparation Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W). (The inverter and the converter

unit (FR-CC2-C) can be measured with those cables connected.)

Prepare a continuity tester. (For the resistance measurement, use the 100 range.)

Checking method Change the polarity of the tester alternately at a semiconductor device (transistor) on an electrical path between two terminals

among the inverter main circuit terminals R/L1, S/L2, T/L3, U, V, W, P/+, and N/- to check the electric continuity.

NOTE Before measurement, check that the smoothing capacitor is discharged.

At the time of electric discontinuity, the measured value is almost . When there is an instantaneous electric continuity, due to

the smoothing capacitor, the tester may not indicate . At the time of electric continuity, the measured value is several to

several tens of . When all measured values are almost the same (although values may not be constant depending on the

tester type), it shows that there are no electrical paths with problems.

Device number and target terminal

(Assuming that an analog meter is used.)

Tester polarity Continuity

Tester polarity Continuity

C on

ve rt

er

m od

ul e

D1 R/L1 P/+ No

D4 R/L1 N/- Yes

P/+ R/L1 Yes N/- R/L1 No

D2 S/L2 P/+ No

D5 S/L2 N/- Yes

P/+ S/L2 Yes N/- S/L2 No

D3 T/L3 P/+ No

D6 T/L3 N/- Yes

P/+ T/L3 Yes N/- T/L3 No

In ve

rt er

m od

u le

TR1 U P/+ No

TR4 U N/- Yes

P/+ U Yes N/- U No

TR3 V P/+ No

TR6 V N/- Yes

P/+ V Yes N/- V No

TR5 W P/+ No

TR2 W N/- Yes

P/+ W Yes N/- W No

Converter module Inverter module

D1 D2 D3

D4 D5 D6

TR1 TR3 TR5

TR4 TR6 TR2

U

V

W

R/L1

S/L2

T/L3

C C

P/+

N/-

P/+

N/-

66 PRECAUTIONS FOR MAINTENANCE AND INSPECTION

Inspection item

5

5.1.5 Cleaning Always run the inverter in a clean status.

When cleaning the inverter, gently wipe dirty areas with a soft cloth immersed in neutral detergent or ethanol.

NOTE Do not use solvent, such as acetone, benzene, toluene and alcohol, as these will cause the inverter surface paint to peel off.

The display, etc. of the operation panel and parameter unit are vulnerable to detergent and alcohol. Therefore, avoid using

them for cleaning.

5.1.6 Replacement of parts The inverter consists of many electronic parts such as semiconductor devices.

The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced

performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically.

Use the life check function as a guidance of parts replacement.

Estimated lifespan for when the yearly average surrounding air temperature is 40C.

(without corrosive gas, flammable gas, oil mist, dust and dirt etc.)

Output current (80% of the inverter rating)

NOTE For parts replacement, contact the nearest Mitsubishi Electric FA center.

Inverter parts life display The inverter diagnoses the control circuit capacitor and the cooling fan by itself, and estimates their lives.

The self-diagnostic warning is output when the life span of each part is near its end. It gives an indication of replacement time.

The life warning output can be used as a guideline for life judgment.

NOTE Refer to the Instruction Manual (Detailed) of the FR-F860 to perform the life check of the inverter parts.

Part name Estimated lifespan Description Cooling fan 10 years Replace (as required)

Main circuit smoothing capacitor 10 years Replace (as required)

On-board smoothing capacitor 10 years Replace the board (as required)

Relays As required

Main circuit fuse 10 years Replace (as required)

Parts Judgment level Control circuit capacitor Estimated remaining life 10%

Cooling fan Not more than the specified speed

PRECAUTIONS FOR MAINTENANCE AND INSPECTION 67

Inspection item

Replacement procedure of the cooling fan The replacement interval of the cooling fan used for cooling the parts generating heat such as the main circuit semiconductor

is greatly affected by the surrounding air temperature. When unusual noise and/or vibration are noticed during inspection, the

cooling fan must be replaced immediately.

Removal 1) Remove the fan cover fixing screws, and remove the fan cover.

2) Disconnect the fan connector and remove the fan block.

3) Remove the fan fixing screws, and remove the fan.

The number of cooling fans differs according to the inverter capacity.

Reinstallation 1) Before installing the new fan, check the orientation of the fan to be sure that the "AIR FLOW" arrow printed on the side

of the fan points upward.

2) For reconnection of the fan, refer to the above figure.

NOTE Installing the fan in the opposite direction of air flow can cause the inverter life to be shorter.

Prevent the cable from being caught when installing a fan.

Switch the power OFF before replacing fans. Since the inverter circuits are charged with voltage even after power OFF,

replace fans only when the inverter cover is on the inverter to prevent an electric shock accident.

1)

2)

3)

Fan

Fan connection connector

Fan cover

Fan block

AIR FLOW

68 PRECAUTIONS FOR MAINTENANCE AND INSPECTION

Inspection item

5

Smoothing capacitors A large-capacity aluminum electrolytic capacitor is used for smoothing in the DC section of the main circuit, and an aluminum

electrolytic capacitor is used for stabilizing the control power in the control circuit. Adverse effects from ripple currents

deteriorate capacitors. Replacement intervals of capacitors vary greatly with surrounding temperatures and operating

conditions. Replace them roughly every 10 years when used in normal air-conditioned environments.

Inspecting the product visually:

Case: Check that the sides and bottom of the capacitor have not ruptured.

Rubber seal: Check for any noticeable bulging or severe cracks.

Check for external cracks, discoloration, leakage, etc. It is assumed that the capacitor has reached the end of its life when

its capacity has dropped below 80% of its rated capacity.

NOTE The inverter diagnoses the control circuit capacitor by itself and can estimate its remaining life. (Refer to the FR-F860

Instruction Manual (Detailed).)

Relay output terminals The contacts of relays deteriorate over time. To prevent faults from occurring, relays must be replaced when they have

reached the maximum of switching operations (switching life).

The control terminal block must be replaced (refer to page 69) in case of failure of either relay connected to the relay output

terminals A1, B1, and C1, or A2, B2, and C2. (After replacing the control terminal block, connect the jumper connector to

the correct position in accordance with the control logic of input signals. (Refer to page 36.))

Main circuit fuse A fuse is used inside the inverter. Replacement intervals of fuses vary with surrounding temperatures and operating

conditions. Replace them roughly every 10 years when used in normal air-conditioned environments.

5.1.7 Removal and reinstallation of the control circuit terminal block

The FR-F800 series inverter has a removable control circuit terminal block, which can be replaced with a new one or a control

terminal option.

Removal and reinstallation 1) Loosen the two mounting screws at the both side of the control circuit terminal block. (These screws cannot be removed.)

Slide down the control circuit terminal block to remove it.

Loosen the screws

PRECAUTIONS FOR MAINTENANCE AND INSPECTION 69

Inspection item

2) Be careful not to bend the pins of the inverter's control circuit connector, reinstall the control circuit terminal block and fix it

with the mounting screws.

NOTE Before starting inverter replacement, switch power OFF, wait for at least 10 minutes, and then check the voltage with a tester

and such to ensure safety.

Removal and reinstallation precautions Precautions to be taken when removing or reinstalling the control circuit terminal block are shown below.

Observe the following precautions and handle the inverter properly to avoid malfunctions or failures.

To remove or reinstall the control circuit terminal block, keep it upright so that it is parallel with the inverter.

To install the control circuit terminal block, slide it upward so that the tongues on the inverter slot into the grooves on the

terminal block.

Check that the terminal block is parallel to the inverter and the pins on the inverter control circuit connector are not bent.

After checking proper connection, fix the terminal block in place with two screws.

NOTE Do not tilt the terminal block while tightening the screws or removing it from the inverter. (Otherwise, stress applied to the

control circuit terminal block or the control circuit connector may damage the pins.)

After replacing the control terminal block, connect the jumper connector to the correct position in accordance with the control

logic of input signals. (Refer to page 36.)

Fasten the screws.

Control circuit terminal blockInverter's control circuit connector

A

Slot the tongue into the groove.

Insert the terminal block parallel to the

inverter.

View from side A

Control circuit terminal blockInverter's control circuit connector

70 PRECAUTIONS FOR MAINTENANCE AND INSPECTION

Measurement of main circuit voltages, currents and powers

5

5.2 Measurement of main circuit voltages, currents and powers

Since the voltages and currents on the inverter power supply and output sides include harmonics, measurement data

depends on the instruments used and circuits measured.

When instruments for commercial frequency are used for measurement, measure the following circuits with the instruments

given on the next page.

NOTE When installing meters etc. on the inverter output side

When the wiring length between the inverter and the motor is large, the meters and CTs may generate heat due to line-to-line

leakage current. Therefore, choose the equipment which has enough allowance for the current rating.

To measure and display the output voltage and output current of the inverter, it is recommended to use terminal AM and CA

output functions of the inverter.

Ar

As

At

Vr

Vs

Vt

Au

Av

Aw

Vu

Vv

Vw

W21

V

U

V

W

Inverter/ converter unit

Three-phase power supply To the motor

Input voltage

Input current

Output voltage

Output current

R/L1

S/L2

T/L3

P/+ N/-

W11

W12

W13 W22

+ -

PRECAUTIONS FOR MAINTENANCE AND INSPECTION 71

Measurement of main circuit voltages, currents and powers

Measuring points and instruments

Use an FFT to measure the output voltage accurately. A tester or general measuring instrument cannot measure accurately.

When the carrier frequency exceeds 5 kHz, do not use this instrument since using it may increase eddy current losses produced in metal parts

inside the instrument, leading to burnout. In this case, use an approximate-effective value type.

When the setting of Pr.195 ABC1 terminal function selection is the positive logic

Item Measuring point Measuring instrument Remarks (reference measured value)

C on

ve rt

er u

n it

(F R

-C C

2- C

)

Power supply voltage V1

Across R/L1 and S/L2, S/L2 and T/L3, T/L3 and R/L1

Digital power meter (for inverter)

Commercial power supply Within permissible AC voltage fluctuation (Refer to page 76.)

Power supply side current I1

R/L1, S/L2, T/L3 line current

Power supply side power P1

R/L1, S/L2, T/L3 and Across R/L1 and S/L2, S/L2 and T/L3, T/L3 and R/L1

P1 = W11 + W12 + W13 (3-wattmeter method)

Power supply side power factor Pf1

Calculate after measuring power supply voltage, power supply side current and power supply side power.

Converter output Across P/+ and N/- Such as tester Inverter LED is lit. 1.35 V1

Operation enable signal External thermal relay signal Reset signal

Across RDI, OH, RES(+) and SD (for sink logic)

Digital multimeter or other tester, or moving-coil type instrument (internal resistance 50 k or more)

When open 20 to 30 VDC ON voltage: 1 V or less

"SD" is common.

Alarm signal Across A1 and C1 Across B1 and C1

Digital multimeter or other tester

Continuity check [Normal] [Fault]

Across A1 and C1 Discontinuity Continuity Across B1 and C1 Continuity Discontinuity

In ve

rt er

Output side voltage V2

Across U and V, V and W, and W and U

Digital power meter (for inverter)

Difference between the phases is within 1% of the maximum output voltage.

Output side current I2

U, V and W line currents

Difference between the phases is 10% or lower of the rated inverter current.

Output side power P2

U, V, W and across U and V, V and W

Digital power meter (for inverter) P2 = W21 + W22 2-wattmeter method (or 3-wattmeter method)

Output side power factor Pf2

Calculate in similar manner to power supply side power factor.

Frequency setting signal

Across 2, 4(+) and 5

Digital multimeter or other tester, or moving-coil type instrument (internal resistance 50 k or more)

0 to 10 VDC, 4 to 20 mA

"5" is common.

Across 1(+) and 5 0 to 5 VDC and 0 to 10 VDC

Frequency setting power supply

Across 10(+) and 5 5.2 VDC

Across 10E(+) and 5 10 VDC

Frequency meter signal Start signal Select signal Reset signal Output stop signal

Across AM(+) and 5 Approximately 10 VDC at maximum frequency (without frequency meter)

Across CA(+) and 5 Approximately 20 mADC at maximum frequency

Across STF, STR, RH, RM, RL, JOG, RT, AU, STP (STOP), CS, RES, MRS(+) and SD (for sink logic)

When open 20 to 30 VDC ON voltage: 1 V or less

"SD" is common.

Fault signal Across A1 and C1 Across B1 and C1

Digital multimeter or other tester

Continuity check [Normal] [Fault]

Across A1 and C1 Discontinuity Continuity Across B1 and C1 Continuity Discontinuity

Pf1 P1

3V1 I 1

----------------------- 100= %

Pf2 P2

3V2 I2 ------------------------ 100= %

72 PRECAUTIONS FOR MAINTENANCE AND INSPECTION

Measurement of main circuit voltages, currents and powers

5

5.2.1 Measurement of powers Use a digital power meter (for inverter) for the input side of the converter unit (FR-CC2-C) and the output side of the inverter.

5.2.2 Measurement of voltages Converter unit (FR-CC2-C) input side Use a digital power meter for inverters for the input side voltage.

Inverter output side Always use a digital power meter for inverter for measurement as the output side voltage has a PWM-controlled rectangular

wave. The value monitored on the operation panel is the inverter-controlled voltage itself. Hence, that value is accurate and it

is recommended to monitor values (analog output) using the operation panel.

5.2.3 Measurement of currents Use digital power meters (for converter) for the both of inverter input and output side.

Since current on the converter unit input side tends to be unbalanced, measurement of three phases is recommended.

Correct value cannot be obtained by measuring only one or two phases. On the other hand, the unbalanced ratio of each

phase of the output side current should be within 10%.

The inverter output current can be monitored on the operation panel. The value monitored on the operation panel is accurate

if the output frequency varies, and it is recommended to monitor values (provide analog output) using the operation panel.

Examples of measured value differences produced by different measuring meters are shown below.

5.2.4 Example of measuring converter unit (FR-CC2-C) input power factor

Calculate using effective power and apparent power. A power-factor meter cannot indicate an exact value.

5.2.5 Measurement of converter output voltage (across terminals P and N)

The output voltage of the converter is output across terminals P and N, and can be measured with a voltmeter such as a

digital multimeter. Although the voltage varies according to the power supply voltage, approximately 800 to 900 V is output

when no load is connected and voltage decreases during driving load operation.

When energy is regenerated from the motor during deceleration, for example, the converter output voltage rises to nearly

1100 to 1300 V maximum.

5.2.6 Measurement of inverter output frequency In the initial setting, a pulse train proportional to the output frequency is output across the analog current output terminals CA

and 5 of the inverter. Measure the current using a tester.

For detailed specifications of the analog current output terminal CA, refer to the Instruction Manual (Detailed) of the FR-F860.

Total power factor of the converter unit = Effective power

Apparent power

= Three-phase input power found by the 3-wattmeter method

V (power supply voltage) I (input current effective value)3

PRECAUTIONS FOR MAINTENANCE AND INSPECTION 73

Measurement of main circuit voltages, currents and powers

5.2.7 Insulation resistance test using megger For the inverter and the converter unit (FR-CC2-C), conduct the insulation resistance test on the main circuit only as shown

below and do not perform the test on the control circuit. (Use a 500 VDC megger.)

NOTE Before performing the insulation resistance test on the external circuit, disconnect the cables from all terminals of the inverter

and the converter unit so that the test voltage is not applied to the inverter and the converter unit.

For the continuity test of the control circuit, use a tester (high resistance range) and do not use the megger or buzzer.

5.2.8 Withstand voltage test Do not conduct a withstand voltage test. Deterioration may occur.

500 VDC megger

Power supply

Motor P/+ N/-Converter

unit U V W

Inverter IM R/L1 S/L2 T/L3

P/+ N/-

Earth (ground) terminal Earth (ground) terminal

500 VDC megger

74 PRECAUTIONS FOR MAINTENANCE AND INSPECTION

6

SPECIFICATIONS 75

6 SPECIFICATIONS

This chapter explains the SPECIFICATIONS of this product.

Always read the instructions before using the equipment.

6.1 Inverter rating............................................................................76 6.2 Common specifications ...........................................................77 6.3 Outline dimension drawings....................................................79

Inverter rating

6.1 Inverter rating Inverter

The applicable motor capacity indicated is the maximum capacity applicable for use of the 4-pole standard motor.

The rated output capacity indicated assumes that the output voltage is 575 V.

When an operation is performed with the carrier frequency set to 3 kHz or more, and the inverter output current reaches the value indicated in

the parenthesis, the carries frequency is automatically lowered. The motor noise becomes louder accordingly.

The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,

allow time for the inverter and motor to return to or below the temperatures under 100% load.

The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.

However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about .

Model FR-F862-[ ] 05450 06470 08500 Inverter capacity (kW) 315 400 500

Applicable motor capacity (kW) SLD (initial setting)

400 450 630

LD 355 400 560

O ut

pu t

Rated capacity (kVA) SLD (initial setting)

543 645 847

LD 494 587 770

Rated current (A) SLD (initial setting)

545 (463) 647 (549) 850 (722)

LD 496 (421) 589 (500) 773 (657)

Overload current rating

SLD (initial setting)

110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature of 40C

LD 120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature of 50C

Rated voltage Three-phase 525 to 600 V

In pu

t p ow

er DC power supply voltage 618 to 933 VDC

Control power supply auxiliary input Single phase 525 to 600 V 50 Hz/60 Hz

Permissible control power supply auxiliary input fluctuation

Frequency 5%, voltage 10%

Protective structure (IEC 60529) Open type (IP00)

Cooling system Forced air cooling

Approx. mass (kg) 163 243 243

76 SPECIFICATIONS

Common specifications

6

6.2 Common specifications C

on tr

ol s

pe ci

fic at

io ns

Control method Soft-PWM control / high carrier frequency PWM control (Selectable among V/F control (Optimum excitation control), Advanced magnetic flux vector control (Advanced optimum excitation control) and PM motor control)

Output frequency range 0.2 to 590 Hz (The upper-limit frequency is 400 Hz under Advanced magnetic flux vector control, and PM motor control.)

Frequency setting resolution

Analog input

0.015 Hz/60 Hz (terminal 2, 4: 0 to 10 V/12 bits) 0.03 Hz/60 Hz (0 to 5 V/11 bits or 0 to 20 mA/approx. 11 bits for terminals 2 and 4, 0 to 10 V/12 bits for terminal 1) 0.06 Hz/60 Hz (0 to 5 V/11 bits for terminal 1)

Digital input 0.01 Hz

Frequency accuracy

Analog input Within 0.2% of the max. output frequency (25C 10C)

Digital input Within 0.01% of the set output frequency

Voltage/frequency characteristics

Base frequency can be set from 0 to 590 Hz. Constant-torque/variable-torque pattern or adjustable 5 points V/F can be selected.

Starting torque

induction motor 120% 0.5 Hz (Advanced magnetic flux vector control)

IPM motor 50%

Torque boost Manual torque boost

Acceleration/deceleration time setting

0 to 3600 s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/ deceleration mode, backlash countermeasures acceleration/deceleration can be selected.

DC injection brake (induction motor) Operation frequency (0 to 120 Hz), operation time (0 to 10 s), operation voltage (0 to 30%) variable

Stall prevention operation level

Activation range of stall prevention operation (SLD rating: 0 to 120%, LD rating: 0 to 150%). Whether to use the stall prevention or not can be selected. (V/F control, Advanced magnetic flux vector control)

O pe

ra tio

n sp

ec ifi

ca tio

ns

Frequency setting signal

Analog input Terminals 2 and 4: 0 to 10 V, 0 to 5 V, 4 to 20 mA (0 to 20 mA) are available. Terminal 1: -10 to +10 V, -5 to 5 V are available.

Digital input Input using the setting dial of the operation panel or parameter unit Four-digit BCD or 16-bit binary (when used with option FR-A8AX)

Start signal Forward and reverse rotation or start signal automatic self-holding input (3-wire input) can be selected.

Input signals (twelve terminals)

Low-speed operation command, Middle-speed operation command, High-speed operation command, Second function selection, Terminal 4 input selection, Jog operation selection, Output stop, Start self- holding selection, Forward rotation command, Reverse rotation command, Inverter reset The input signal can be changed using Pr.178 to Pr.189 (Input terminal function selection).

Pulse train input 100k pulses/s

Operational functions

Maximum and minimum frequency settings, multi-speed operation, acceleration/deceleration pattern, thermal protection, DC injection brake, starting frequency, JOG operation, output stop (MRS), stall prevention, regeneration avoidance, increased magnetic excitation deceleration, frequency jump, rotation display, automatic restart after instantaneous power failure, electronic bypass sequence, remote setting, automatic acceleration/deceleration, retry function, carrier frequency selection, fast-response current limit, forward/reverse rotation prevention, operation mode selection, slip compensation, speed smoothing control, traverse, auto tuning, applied motor selection, RS-485 communication, PID control, PID pre- charge function, cooling fan operation selection, stop selection (deceleration stop/coasting), power failure time deceleration-to-stop function, PLC function, life diagnosis, maintenance timer, current average monitor, multiple rating, test run, 24 V power supply input for control circuit, self power management, BACnet communication, PID gain tuning, cleaning, load characteristics storage

Output signal Open collector output (five terminals) Relay output (two terminals)

Inverter running, Up to frequency, Overload warning, Output frequency detection, Fault The output signal can be changed using Pr.190 to Pr.196 (Output terminal function selection). Fault codes of the inverter can be output (4 bits) from the open collector.

Pulse train output 50k pulses/s

In di

ca tio

n

For meter

Current output

Max. 20 mADC: one terminal (output frequency) The monitored item can be changed using Pr.54 CA terminal function selection.

Voltage output

Max. 10 VDC: one terminal (output frequency) The monitored item can be changed using Pr.158 AM terminal function selection.

SPECIFICATIONS 77

Common specifications

Temperature applicable for a short time, e.g. in transit.

This protective function is not available in the initial status.

Protective/ warning function

Protective function

Overcurrent trip during acceleration, Overcurrent trip during constant speed, Overcurrent trip during deceleration or stop, Regenerative overvoltage trip during acceleration, Regenerative overvoltage trip during constant speed, Regenerative overvoltage trip during deceleration or stop, Inverter overload trip (electronic thermal relay function), Motor overload trip (electronic thermal relay function), Heat sink overheat, Stall prevention stop, Loss of synchronism detection, Upper limit fault detection, Lower limit fault detection, Output side earth (ground) fault overcurrent, Output short circuit, Output phase loss, External thermal relay operation, PTC thermistor operation, Option fault, Communication option fault, Parameter storage device fault, PU disconnection, Retry count excess, CPU fault, Operation panel power supply short circuit/RS-485 terminals power supply short circuit, 24 VDC power fault, Abnormal output current detection, Communication fault (inverter), Analog input fault, USB communication fault, Overspeed occurrence, 4 mA input fault, Pre-charge fault, PID signal fault, Internal circuit fault

Warning function

Fan alarm, Stall prevention (overcurrent), Stall prevention (overvoltage), Electronic thermal relay function pre-alarm, PU stop, Parameter copy, Maintenance timer 1 to 3, USB host error, Operation panel lock, Password locked, Parameter write error, Copy operation error, 24 V external power supply operation, Continuous operation during communication fault, Load fault warning

En vi

ro nm

en t

Surrounding air temperature

-10C to +50C (non-freezing) (LD ratings) -10C to +40C (non-freezing) (SLD ratings)

Surrounding air humidity With circuit board coating (conforming to IEC 60721-3-3 3C2/3S2): 95% RH or less (non-condensing)

Storage temperature -20C to +65C

Atmosphere Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt, etc.)

Altitude/vibration Maximum 2500 m (For installation at an altitude above 1000 m, consider a 3% reduction in the rated

current per 500 m increase in altitude.), 2.9 m/s2 or less at 10 to 55 Hz (directions of X, Y, Z axes)

78 SPECIFICATIONS

Outline dimension drawings

6

6.3 Outline dimension drawings FR-F862-05450

FR-F862-06470, FR-F862-08500

(Unit: mm)

(Unit: mm)

185

185

23

12 70 200

540 440

4.5 4.5 200 (70)

(1 5)

13 00

(1 7)

17 12

96

15 13

30

3-12 hole 8-25 hole

185

185

23

12 100 240

680 440

4.5 4.5 240 (100)

(1 5)

15 50

(1 7)

17 15

46

15 15

80

3-12 hole 8-25 hole

SPECIFICATIONS 79

MEMO

80

APPENDIX 81

APPENDIX

APPENDIX provides the reference information for use of this product. Refer to APPENDIX as required.

Appendix 1 Comparison with FR-F860............................................82 Appendix 2 Instructions for UL and cUL.........................................83 Appendix 3 Restricted Use of Hazardous Substances in

Electronic and Electrical Products..............................85

Appendix 1 Comparison with FR-F860

Item FR-F862 Remarks (FR-F860)

Pr.30 Regenerative function selection

Setting ranges "2, 10, 11, 102, 110, 111" Initial value "10"

Setting ranges "0 to 2, 10, 11, 20, 21, 100 to 102, 110, 111, 120, 121" Initial value "0"

Monitor function (Pr.52, Pr.54, Pr.158, Pr.774 to Pr.776, Pr.1027 to Pr.1034)

Emergency drive status Without (Unacceptable)

Input terminal function selection (Pr.178 to Pr.189)

DC feeding operation permission (X70), DC feeding cancel (X71), Emergency drive execution command (X84) Without (Unacceptable)

Pr.187 MRS terminal function selection Initial value "10" (X10) Initial value "24" (MRS)

Output terminal function assignment selection (Pr.190 to Pr.196, Pr.313 to Pr.322)

Instantaneous power failure/undervoltage (IPF), Emergency drive in operation (Y65), Fault output during Emergency drive (Y66), DC current feeding (Y85), Main circuit capacitor life (Y87), Inrush current limit circuit life (Y89) Without (Unacceptable)

Pr.192 IPF terminal function selection Initial value "9999" (No function) Initial value "2" (IPF)

Inrush current limit circuit life display, Main circuit capacitor life display (Pr.256, Pr.258, Pr.259)

Without the parameter

Emergency drive function (Pr.514, Pr.515, Pr.523, Pr.524, Pr.1013)

Without the parameter

Pr.599 X10 terminal input selection Initial value "1" (NC contact specification) Initial value "0" (NO contact specification)

Pr.872 Input phase loss protection selection Without the parameter

Warning, protective functions

Emergency drive in operation (ED), Instantaneous power failure (E.IPF), Undervoltage (E.UVT), Input phase loss (E.ILF), Inrush current limit circuit fault (E.IOH) Not available

82 APPENDIX

Appendix 2 Instructions for UL and cUL (Standard to comply with: UL 508C, CSA C22.2 No.274-13)

General Precaution CAUTION - Risk of Electric Shock -

The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10

minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.

ATTENTION - Risque de choc lectrique -

La dure de dcharge du condensateur de bus est de 10 minutes. Avant de commencer le cblage ou linspection, mettez

lappareil hors tension et attendez plus de 10 minutes.

Installation The FR-F862 inverters with the below types of converter unit have been approved as products for use in enclosure.

Design the enclosure so that the surrounding air temperature, humidity and ambience of the inverter will satisfy the

specifications. (Refer to page 17.)

Wiring protection For installation in the United States, Class T, Class J, Class CC, or Class L fuse must be provided, in accordance with the

National Electrical Code and any applicable local codes.

For installation in Canada, Class T, Class J, Class CC, or Class L fuse must be provided, in accordance with the Canadian

Electrical Code and any applicable local codes.

Wiring to the power supply and the motor Refer to the National Electrical Code (Article 310) regarding the allowable current of the cable. Select the cable size for 125%

of the rated current according to the National Electrical Code (Article 430).

For wiring the input (R/L1, S/L2, T/L3) terminals of the converter unit and output (U, V, W) terminals of the inverter, use the UL

listed copper, stranded wires (rated at 75C) and round crimp terminals. Crimp the terminals with the crimping tool

recommended by the terminal maker.

Short circuit ratings Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 600 V Maximum.

Motor overload protection When using the electronic thermal relay function as motor overload protection, set the rated motor current in Pr.9 Electronic thermal O/L relay.

FR-CC2-[ ] C355K C400K C560K Rated fuse voltage (V) 575 V or more

Fuse allowable rating (A) 700 800 1000

Operation characteristics of electronic thermal relay function This function detects the overload (overheat) of the motor

and trips the inverter by stopping the operation of the

transistor at the inverter output side. (The operation

characteristic is shown on the left.)

When a value 50% of the inverter rated output current

(current value) is set in Pr.9 The % value denotes the percentage to the rated inverter

current. It is not the percentage to the rated motor current.

Transistor protection is activated depending on the

temperature of the heat sink. The protection may be

activated even with less than 150% depending on the

operating conditions.230

52.5% 105%

50 100 150

60

120

180

240

50

60

70

Pr.9 = 50% setting of inverter rating1, 2

Pr.9 = 100% setting of inverter rating2

6 Hz

20 Hz 10 Hz

6 Hz

0.5 Hz

30 Hz or more30 Hz

or more 20 Hz 10 Hz

0.5 Hz

Range for the transistor protection3

S ec

on d

di sp

la y

in th

is re

gi on

M in

ut e

di sp

la y

in

th is

re gi

on

O pe

ra tio

n tim

e (m

in )

O pe

ra tio

n tim

e (s

)

Characteristic when electronic thermal relay function for motor protection is turned off (When Pr.9 setting is 0(A))

Inverter output power (%) (% to the inverter rated current)

Operation region Region on the right of characteristic curve Non-operation region Region on the left of characteristic curve

APPENDIX 83

NOTE The internal accumulated heat value of the electronic thermal relay function is reset by inverter power reset and reset signal

input. Avoid unnecessary reset and power-OFF.

Install an external thermal relay (OCR) between the inverter and motors to operate several motors, a multi-pole motor or a

dedicated motor with one inverter. Note that the current indicated on the motor rating plate is affected by the line-to-line

leakage current (refer to the FR-F860 Instruction Manual (Detailed)) when selecting the setting for an external thermal relay.

The cooling effect of the motor drops during low-speed operation. Use a thermal protector or a motor with built-in thermistor.

When the difference between the inverter and motor capacities is large and the setting is small, the protective characteristics

of the electronic thermal relay function will be deteriorated. In such case, use an external thermal relay.

A dedicated motor cannot be protected by an electronic thermal O/L relay. Use an external thermal relay.

Motor over temperature sensing is not provided by the drive.

84 APPENDIX

APPENDIX 85

Appendix 3 Restricted Use of Hazardous Substances in Electronic and Electrical Products

The mark of restricted use of hazardous substances in electronic and electrical products is applied to the product as follows

based on the Management Methods for the Restriction of the Use of Hazardous Substances in Electrical and Electronic

Products of the People's Republic of China.

SJ/T11364 GB/T26572

GB/T26572

(Pb)

(Hg)

(Cd)

(Cr(VI))

(PBB)

(PBDE)

86

WARRANTY

When using this product, make sure to understand the warranty described below.

1. Warranty period and coverage We will repair any failure or defect (hereinafter referred to as "failure") in our FA equipment (hereinafter referred to as the "Product") arisen during warranty period at no charge due to causes for which we are responsible through the distributor from which you purchased the Product or our service provider. However, we will charge the actual cost of dispatching our engineer for an on-site repair work on request by customer in Japan or overseas countries. We are not responsible for any on-site readjustment and/or trial run that may be required after a defective unit are repaired or replaced.

[Term] The term of warranty for Product is twelve months after your purchase or delivery of the Product to a place designated by you or eighteen months from the date of manufacture whichever comes first ("Warranty Period"). Warranty period for repaired Product cannot exceed beyond the original warranty period before any repair work.

[Limitations] (1) You are requested to conduct an initial failure diagnosis by yourself, as a general rule. It can also be carried out by us or our service company upon your

request and the actual cost will be charged. However, it will not be charged if we are responsible for the cause of the failure.

(2) This limited warranty applies only when the condition, method, environment, etc. of use are in compliance with the terms and conditions and instructions that are set forth in the instruction manual and user manual for the Product and the caution label affixed to the Product.

(3) Even during the term of warranty, the repair cost will be charged on you in the following cases; a failure caused by your improper storing or handling, carelessness or negligence, etc., and a failure caused by your hardware or software problem a failure caused by any alteration, etc. to the Product made on your side without our approval a failure which may be regarded as avoidable, if your equipment in which the Product is incorporated is equipped with a safety device required by

applicable laws and has any function or structure considered to be indispensable according to a common sense in the industry a failure which may be regarded as avoidable if consumable parts designated in the instruction manual, etc. are duly maintained and replaced any replacement of consumable parts (condenser, cooling fan, etc.) a failure caused by external factors such as inevitable accidents, including without limitation fire and abnormal fluctuation of voltage, and acts of

God, including without limitation earthquake, lightning and natural disasters a failure generated by an unforeseeable cause with a scientific technology that was not available at the time of the shipment of the Product from our

company any other failures which we are not responsible for or which you acknowledge we are not responsible for

2. Term of warranty after the stop of production (1) We may accept the repair at charge for another seven (7) years after the production of the product is discontinued. The announcement of the stop of

production for each model can be seen in our Sales and Service, etc. (2) Please note that the Product (including its spare parts) cannot be ordered after its stop of production.

3. Service in overseas Our regional FA Center in overseas countries will accept the repair work of the Product; however, the terms and conditions of the repair work may differ depending on each FA Center. Please ask your local FA center for details.

4. Exclusion of loss in opportunity and secondary loss from warranty liability Regardless of the gratis warranty term, Mitsubishi Electric shall not be liable for compensation to: (1) Damages caused by any cause found not to be the responsibility of Mitsubishi Electric. (2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi Electric products. (3) Special damages and secondary damages whether foreseeable or not, compensation for accidents, and compensation for damages to products other

than Mitsubishi Electric products. (4) Replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.

5. Change of Product specifications Specifications listed in our catalogs, manuals or technical documents may be changed without notice.

6. Application and use of the Product (1) For the use of our product, its applications should be those that may not result in a serious damage even if any failure or malfunction occurs in product,

and a backup or fail-safe function should operate on an external system to product when any failure or malfunction occurs. (2) Our product is designed and manufactured as a general purpose product for use at general industries.

Therefore, applications substantially influential on the public interest for such as atomic power plants and other power plants of electric power companies, and also which require a special quality assurance system, including applications for railway companies and government or public offices are not recommended, and we assume no responsibility for any failure caused by these applications when used. In addition, applications which may be substantially influential to human lives or properties for such as airlines, medical treatments, railway service, incineration and fuel systems, man-operated material handling equipment, entertainment machines, safety machines, etc. are not recommended, and we assume no responsibility for any failure caused by these applications when used. We will review the acceptability of the abovementioned applications, if you agree not to require a specific quality for a specific application. Please contact us for consultation.

87

About the enclosed CD-ROM The enclosed CD-ROM contains PDF copies of the manuals related to this product.

Before using the enclosed CD-ROM The copyright and other rights of the enclosed CD-ROM all belong to Mitsubishi Electric Corporation.

No part of the enclosed CD-ROM may be copied or reproduced without the permission of Mitsubishi Electric Corporation.

Specifications of the enclosed CD-ROM are subject to change for modification without notice.

We are not responsible for any damages and lost earnings, etc. from use of the enclosed CD-ROM.

Trademarks

Microsoft, Windows, and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation in the

United States and/or other countries.

Windows Vista is either registered trademarks or trademark of Microsoft Corporation in the United States and/or other

countries.

Adobe and Acrobat Reader are either registered trademarks or trademarks of Adobe Systems Incorporated in the United

States and/or other countries.

Intel and Pentium are trademarks of Intel Corporation in the United States and/or other countries.

Any trade names and product names of companies herein are all trademarks or registered trademarks of those respective

companies.

Warranty

We do not provide a warranty against defects in the enclosed CD-ROM and related documents.

NOTE This is a personal computer dedicated CD-ROM. Do not attempt to play it on ordinary audio devices. The loud volume may

damage hearing and speakers.

System requirements for the enclosed CD-ROM The following system is required to read instruction manuals contained in the enclosed CD-ROM.

Operating method of the enclosed CD-ROM How to read instruction manuals

Step 1. Start a personal computer and place the enclosed CD-ROM in the CD-ROM drive.

Step 2. The main window automatically opens by the web browser.

Step 3. Click a manual you want to read in the "INSTRUCTION MANUAL" list.

Step 4. PDF manual you clicked opens.

Manual opening of the enclosed CD-ROM

Step 1. Start a personal computer and place the enclosed CD-ROM in the CD-ROM drive.

Step 2. Open "index.html" file in the enclosed CD-ROM.

Step 3. The main window opens by the web browser. Follow the instructions from Step 3 of "How to read instruction

manuals".

PDF data of the instruction manual are stored in "MANUAL" folder on the enclosed CD-ROM.

Item Specifications OS Microsoft Windows 10, Windows 8.1, Windows 8, Windows 7, Windows Vista

CPU Intel Pentium or better processor

Memory 128 MB of RAM

Hard disk 90 MB of available hard-disk space

CD-ROM drive Double speed or more (more than quadruple speed is recommended)

Monitor 800600 dots or more

Application Adobe Reader 7.0 or higher

Internet Explorer 6.0 or higher

88

REVISIONS

*The manual number is given on the bottom left of the back cover.

Revision Date *Manual Number Revision Oct. 2016 IB(NA)-0600689ENG-A First edition

Mar. 2019 IB(NA)-0600689ENG-B Addition Application of caution labels

Removal and reinstallation of the control circuit terminal block

IB(NA)-0600689ENG-B

FR-F800 Series Instruction Manual Supplement

1 Support for CC-Link IE TSN

Using the plug-in option FR-A8NCG enables CC-Link IE TSN communication.

For the details, refer to the FR-A8NCG Instruction Manual.

2 Main circuit capacitor residual-life estimation function

Even when the power supply cannot be turned OFF, the remaining life of the main circuit capacitor can be estimated

without stopping the operation. Note that the remaining life of the main circuit capacitor estimated by this function is

theoretical, and should be used as a guideline only.

*1 Valid values (read only) for separated converter type inverters are "0, 1, 4, and 5". The setting range (reading only) for IP55 compatible

modes is "0 to 63".

*2 The setting is available only for standard models and IP55 compatible models.

Display estimated main circuit capacitor residual life (Pr.506) The estimated residual life of the main circuit capacitor is displayed in Pr.506.

The remaining life of the main circuit capacitor is calculated from the energization time and the inverter output power (100% =

Start of service life). When the remaining life of the main circuit capacitor falls below 10%, bit 5 of Pr.255 Life alarm status

display turns ON and a warning is output by the Y90 signal.

Life alarm display and signal output (Y90 signal, Pr.255)

Power no longer needs to be turned OFF for the warning signal (Y90) to be output when using the main circuit

residual-life estimation function.

Whether or not the parts of the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit circuit or internal

air circulation fans have reached the life alarm output level can be checked with Pr.255 Life alarm status display and the Life

alarm (Y90) signal. (Internal air circulation fans are equipped with IP55 compatible models.)

Pr. Name Initial value Setting range Description

255 E700

Life alarm status display 0 (0 to 15, 32 to 47)

Displays whether or not the parts of the control circuit capacitor, main circuit capacitor, cooling fan, and inrush current limit circuit have reached the life alarm output level. Read-only.

506 E705

Display estimated main circuit capacitor residual life

100% (0 to 100%) Displays the estimated residual life of the main circuit capacitor. Read-only.

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

bit0 Control circuit capacitor life

1 15bit 7 0

bit1 Main circuit capacitor life (Standard models and IP55 compatible models only)

bit2 Cooling fan life

bit3 Inrush current limit circuit life (Standard models and IP55 compatible models only)

Pr.255 read Pr.255 setting read

Bit image is displayed in decimal

bit4 Life of internal air circulation fans (IP55 compatible models only)

bit5 Estimated residual-life of main circuit capacitor (Standard models and IP55 compatible models only)

1 BCN-C22005-895

The Life alarm (Y90) signal turns ON when either the control circuit capacitor life, main circuit capacitor life, cooling fan life,

inrush current limit circuit life, internal air circulation fan life or the estimated residual life of the main circuit capacitor reaches

the level set to output the life alarm.

For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) in any of Pr.190 to Pr.196 (Output

terminal function selection).

NOTE When using an option (FR-A8AY, FR-A8AR, FR-A8NC, FR-A8NCE), the life alarm for the Control circuit capacitor

life (Y86 signal), Main circuit capacitor life (Y87 signal), Cooling fan life (Y88 signal), Inrush current limit circuit life

(Y89 signal), and the estimated residual-life of the Main circuit capacitor (Y248 signal) can be output individually.

Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the

other functions. Set parameters after confirming the function of each terminal.

3 Reset selection after inverter faults are cleared (Pr.349, N241)

When the communication option is specified for the command source in Network operation mode, it is possible to select

whether the inverter is reset after the "Fault reset" command is executed. (Only when the HMS network option is installed.)

*1 When 24 V external power is available for control circuit or power is input only to control circuit.

*2 Available when the HMS network option is installed.

Setting Description

Pr.349 N010 N240 N241 Communication reset selection Ready bit status selection

Reset selection after inverter faults are

cleared

NET operation mode

Other than NET operation mode

Main circuit: power-ON

Main circuit: power-OFF*1 Reset

0 0 0 0 Reset enabled Reset enabled Ready bit: ON Ready bit: ON Enabled

1 1 0 0 Reset enabled Reset disabled Ready bit: ON Ready bit: ON Enabled

100 0 1 0 Reset enabled Reset enabled Ready bit: ON Ready bit: OFF Enabled

101 1 1 0 Reset enabled Reset disabled Ready bit: ON Ready bit: OFF Enabled

1000 0 0 1 Reset enabled Reset enabled Ready bit: ON Ready bit: ON Disabled*2

1001 1 0 1 Reset enabled Reset disabled Ready bit: ON Ready bit: ON Disabled*2

1100 0 1 1 Reset enabled Reset enabled Ready bit: ON Ready bit: OFF Disabled*2

1101 1 1 1 Reset enabled Reset disabled Ready bit: ON Ready bit: OFF Disabled*2

2 BCN-C22005-895

4 Compliance with the latest BACnet standard

Properties have been added for comply with the latest BACnet standard.

Supported property of BACnet standard object type R: Read only

ANNEX A - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE)

(This annex is part of this Standard and is required for its use.)

BACnet Protocol Implementation Conformance Statement

Date: 1st Jul 2014

Vendor Name: Mitsubishi Electric Corporation

Product Name: Inverter

Product Model Number: FR-F820-1, FR-F820-2, FR-F840-1, FR-F840-2, FR-F842-1, FR-F842-2, FR-F846-1, FR-

F846-2, FR-F820-E1, FR-F820-E2, FR-F840-E1, FR-F840-E2, FR-F842-E1, FR-F842-E2,

FR-F846-E1, FR-F846-E2

Application Software Version: XXXX* (Four-digit number followed by a letter)

Firmware Revision: 1.00

BACnet Protocol Revision: 4

Product Description:

BACnet Standardized Device Profile (Annex L):

BACnet Cross-Domain Advanced Operator Workstation (B-XAWS)

BACnet Advanced Operator Workstation (B-AWS)

BACnet Operator Workstation (B-OWS)

BACnet Operator Display (B-OD)

BACnet Advanced Life Safety Workstation (B-ALSWS)

BACnet Life Safety Workstation (B-LSWS)

BACnet Life Safety Annunciator Panel (B-LSAP)

BACnet Advanced Access Control Workstation (B-AACWS)

BACnet Access Control Workstation (B-ACWS)

BACnet Access Control Security Display (B-ACSD)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

Properties Object support condition

Analog Input

Analog Output

Analog Value

Binary Input

Binary Output

Binary Value

Device

Property List R R R R R R R

Current Command Priority R R

3 BCN-C22005-895

BACnet Advanced Life Safety Controller (B-ALSC)

BACnet Life Safety Controller (B-LSC)

BACnet Advanced Access Control Controller (B-AACC)

BACnet Access Control Controller (B-ACC)

BACnet Router (B-RTR)

BACnet Gateway (B-GW)

BACnet Broadcast Management Device (B-BBMD)

BACnet Access Control Door Controller (B-ACDC)

BACnet Access Control Credential Reader (B-ACCR)

BACnet General (B-GENERAL)

List all BACnet Interoperability Building Blocks Supported (Annex K):

DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B, DM-DCC-B , DM-RD-B

Segmentation Capability:

Standard Object Types Supported:

An object type is supported if it may be present in the device. For each standard Object Type supported provide the

following data:

1. Whether objects of this type are dynamically creatable using the CreateObject service

2. Whether objects of this type are dynamically deletable using the DeleteObject service

3. List of the optional properties supported

4. List of all properties that are writable where not otherwise required by this standard

5. List of all properties that are conditionally writable where not otherwise required by this standard

6. List of proprietary properties and for each its property identifier, datatype, and meaning

7. List of any property range restrictions

Dynamic object creation and deletion is not supported.

To check the object types supported by the FR-F800 series, refer to the Instruction Manual (Detailed).

Able to transmit segmented messages Window Size

Able to receive segmented messages Window Size

4 BCN-C22005-895

Data Link Layer Options:

Device Address Binding:

Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and

certain other devices.) Yes No

Networking Options:

Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.

Annex H, BACnet Tunneling Router over IP

Character Sets Supported:

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

ISO 10646 (UTF-8) IBMTM/MicrosoftTM DBCS ISO 8859-1

ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208

Gateway Options:

If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that

the gateway supports:

If this product is a communication gateway which presents a network of virtual BACnet devices, a separate PICS shall

be provided that describes the functionality of the virtual BACnet devices. That PICS shall describe a superset of the

functionality of all types of virtual BACnet devices that can be presented by the gateway.

Network Security Options:

Non-secure Device - is capable of operating without BACnet Network Security

Secure Device - is capable of using BACnet Network Security (NS-SD BIBB)

Multiple Application-Specific Keys

Supports encryption (NS-ED BIBB)

Key Server (NS-KS BIBB)

ARCNET (ATA 878.1), 2.5 Mb. (Clause 8)

ARCNET (ATA 878.1), EIA-485 (Clause 8), baud rate(s)

BACnet IP, (Annex J)

BACnet IP, (Annex J), BACnet Broadcast Management Device (BBMD)

BACnet IP, (Annex J), Network Address Translation (NAT Traversal)

BACnet IPv6, (Annex U)

BACnet IPv6, (Annex U), BACnet Broadcast Management Device (BBMD)

BACnet/ZigBee (Annex O)

ISO 8802-3, Ethernet (Clause 7)

MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 57600, 76800, 115200

MS/TP slave (Clause 9), baud rate(s):

Point-To-Point, EIA 232 (Clause 10), baud rate(s):

Point-To-Point, modem, (Clause 10), baud rate(s):

Other:

5 BCN-C22005-895

1 BCN-C22005-914

FR-F800 Series Instruction Manual Supplement

1 Direct multi-speed operation

When the RLF (RLR) signal is input, the operation is the same as the one when the STF (STR) signal and RL signal

are input.

Input terminal function assignment Use Pr.178 to Pr.189 to set the functions of the input terminals.

Refer to the following table and set the parameters.

Direct multi-speed setting While the RLF or RLR signal is input, the operation is according to Pr.6 Multi-speed setting (low-speed). The rotation is

forward while the RLF signal is input, and the rotation is reverse while the RLR signal is input.

NOTE The Pr.6 setting should be equal to or higher than the Pr.13 Starting frequency setting.

To assign the RLF and RLR signals to input terminals, set "128 (RLF)" and "129 (RLR)" in any two parameters from

Pr.178 to Pr.189 (Input terminal function selection).

The direct multi-speed operation is enabled only when the inverter operates in External operation mode.

When the RLR or STR signal is input while the RLF signal is input, the motor is decelerated to stop.

When the RLF or STF signal is input while the RLR signal is input, the motor is decelerated to stop.

When Pr.59 Remote function selection "0", the RLF signal is used as the STF signal, and the RLR signal is used

as the STR signal.

When the stop-on-contact function is enabled, the RLF signal is used as the STF signal, and the RLR signal is used

as the STR signal.

When the RLF or RLR signal is turned ON to enable the direct multi-speed operation, the setting of Pr.250 Stop

selection and the STP (STOP) signal are disabled.

Setting Signal name Function Related parameter

128 RLF Low-speed forward rotation command Pr.6

129 RLR Low-speed reverse rotation command Pr.6

Low-speed forward rotation command Low-speed reverse rotation command

RLF ON

Time

RLF RLR SD

Inverter

Output frequency

RLR ON

Forward rotation

Reverse rotation

Pr.6

Pr.6

BCN-C22005-914_ENG.book 1

2 BCN-C22005-914

2 Checking of current input on analog input terminal

A terminal for current input check can be selected.

Selection terminal for current input check (Pr.573) Use Pr.573 to select which terminal's current input is checked.

3 Input terminal status monitor

The input states of terminals S1 and S2 can be monitored.

Monitor item list (Pr.52, Pr.774 to Pr.776, Pr.992) Use Pr.52, Pr.774 to Pr.776, or Pr.992 to select the item to monitor on the operation panel or the parameter unit.

Refer to the following table to find the setting value for each monitoring. The value in the Pr. setting column is set in each of the

parameters for monitoring (Pr.52, Pr.774 to Pr.776, and Pr.992) to determine the monitor item. The value in the RS-485 column

is used for the RS-485 communication special monitor selection. The value in the MODBUS RTU column is used for the

MODBUS RTU real time monitor.

*1 The details of bits for the input terminal status are as follows. (1: ON state, 0: OFF state of a terminal on the inverter. "" denotes an

indefinite (null) value.)

*2 Parameter setting is not available for setting the item as the main monitor item on the LCD operation panel (FR-LU08) or the

parameter unit (FR-PU07). Use the monitor function of the FR-LU08 or the FR-PU07 for setting.

Pr. Name Initial value

Setting range Description

573 T052

4 mA input check selection 9999

1, 11, 21 Operation continues with output frequency before the current input loss.

2, 12, 22 4 mA input fault (E.LCI) is activated when the current input loss is detected.

3, 13, 23 The inverter output decelerates the motor to a stop when the current input loss is detected. After the motor is stopped, 4 mA input fault (E.LCI) is activated.

4, 14, 24 Operation continues at the frequency set in Pr.777.

9999 No current input check.

Pr.573 setting Terminal to be checked

1 to 4 Terminals 2 and 4

11 to 14 Terminals 4

21 to 24 Terminals 2

Monitor item Increment and unit

Pr. setting

RS-485 MODBUS RTU Description

Input terminal status 55 H0F 40215 The ON/OFF state of the input terminals on the inverter is displayed. (Refer to page 3 for details of indication on the DU.)

b15 b0

CS--S2 RES STP (STOP) MRS RHJOG RM RL RT AU STR STFS1

BCN-C22005-914_ENG.book 2

3 BCN-C22005-914

Monitoring I/O terminals on the operation panel (FR-DU08) (Pr.52, Pr.774 to Pr.776, Pr.992)

When Pr.52 (Pr.774 to Pr.776, Pr.992) = "55", the I/O terminal state can be monitored on the operation panel (FR-DU08).

When a terminal is ON, the corresponding LED segment is ON. The center LED segments are always ON.

On the I/O terminal monitor, the upper LEDs indicate the input terminal status, and the lower LEDs indicate the output terminal

status.

4 Main circuit capacitor life measuring

The measurement of the main circuit capacitor life can start whenever the power supply is turned OFF without setting

the parameter every time.

*1 The setting is available only for standard models and IP55 compatible models.

Life display of the main circuit capacitor (Pr.258, Pr.259) (Standard models and IP55 compatible models)

For accurate life measurement of the main circuit capacitor, wait three hours or longer after turning OFF. The

temperature left in the main circuit capacitor affects measurement.

Pr.52, Pr.774 to Pr.776, Pr.992 setting

Monitor item Monitor description

55 I/O terminal status Displays the I/O terminal ON/OFF state of the inverter.

Pr. Name Initial value

Setting range Description

259 E704

Main circuit capacitor life measuring

0

0 No measurement

1 (2, 3, 8, 9)

Setting "1" and turning the power supply OFF starts the measurement of the main circuit capacitor life. (Only once) If the setting value of Pr.259 becomes "3" after turning the power supply ON again, it means that the measurement is completed. The deterioration degree is read to Pr.258.

11 (12, 13, 18, 19)

When "11" is set, turning OFF the power supply starts the measurement of the main circuit capacitor life. If the setting value of Pr.259 becomes "13" after turning the power supply ON again, it means that the measurement is completed. The deterioration degree is read to Pr.258.

The center LED segments are always ON.

Segments corresponding to input terminals - Display example -

When signals STF, RH and RUN are on

Segments corresponding to output terminals

A

RL RH

RT MRS

RUNABC1

STP (STOP) RM AU

ABC2 OL

SU IPF FU

STR STFRES CSJOG

So (SO)

S1 S2

BCN-C22005-914_ENG.book 3

4 BCN-C22005-914

The deterioration degree of the main circuit capacitor is displayed in Pr.258.

With the main circuit capacitor capacity at factory shipment as 100%, the capacitor life is displayed in Pr.258 every time

measurement is made. When the measured value falls to 85% or lower, bit 1 of Pr.255 is turned ON (set to 1) and the Y90

signal is also output as an alert.

Measure the capacitor capacity according to the following procedure and check the deterioration degree of the capacitor

capacity.

1. Check that the motor is connected and at a stop.

2. Set "1, 11" (measuring start) in Pr.259.

3. Switch the power OFF. The inverter applies DC voltage to the motor to measure the capacitor capacity

while the inverter is OFF.

4. After confirming that the power lamp is OFF, turn ON the power again.

5. Check that "3, 13" (measurement complete) is set in Pr.259, read Pr.258, and check the deterioration

degree of the main circuit capacitor.

NOTE When the main circuit capacitor life is measured under the following conditions, "forced end" (Pr.259 = "8, 18"), or

"measurement error" (Pr.259 = "9, 19") may occur, or the status may remain in "measurement start" (Pr.259 = "1,

11"). To perform measurement, first eliminate the following conditions. Under the following conditions, even if

"measurement complete" (Pr.259 = "3, 13") is reached, measurement cannot be performed correctly.

Operation environment: Surrounding air temperature (annual average of 40C (free from corrosive gas, flammable

gas, oil mist, dust and dirt)).

Output current: 80% of the inverter rating

Since repeated inrush currents at power ON will shorten the life of the converter circuit, frequent starts and stops of

the magnetic contactor must be avoided.

Pr.259 Description Remarks

0 No measurement Initial value

1, 11 Start measurement

Measurement starts when the power supply is switched OFF. (Only once when Pr.259 = "1") When Pr.259 = "11", the measurement starts every time the power supply is turned OFF.

2, 12 During measurement Only displayed and cannot be set. (When "11" is set in Pr.259, "12, 13, 18, or 19" is displayed.)

3, 13 Measurement complete

8, 18 Forced end

9, 19 Measurement error

- FR-HC2, FR-CV, MT-RC, or a sine wave filter (MT-BSL/BSC) is connected.

- Terminals R1/L11, S1/L21 or DC power supply is connected to terminals P/+ and N/-.

- The power supply is switched ON during measurement.

- The motor is not connected to the inverter.

- The motor is running (coasting).

- The motor capacity is smaller than the inverter capacity by two ranks or more.

- The inverter output is shut off or a fault occurred while the power was OFF.

- The inverter output is shut off with the MRS signal.

- The start command is given while measuring.

- The applied motor setting is incorrect.

WARNING When measuring the main circuit capacitor capacity (Pr.259 = "1, 11"), the DC voltage is applied to the motor for about 1

second at power OFF. Never touch the motor terminal, etc. right after powering OFF to prevent an electric shock.

BCN-C22005-914_ENG.book 4

5 BCN-C22005-914

5 Load characteristics fault detection

This section describes how to set the load characteristics reference for the existing load characteristics fault detection

function. The following shows the procedure to set the load characteristics reference manually.

Setting the load characteristics reference manually (Pr.1481 to Pr.1485)

Set Pr.1480 Load characteristics measurement mode = "0" (initial value).

Set Pr.1486 and Pr.1487 to specify the frequency band for the measurement, and calculate the frequency as the load

characteristics reference (f2 to f4) using the following table.

Start the inverter operation, and set Pr.1481 = "8888" during operation at the frequency of the load characteristics reference 1

(f1). The load status at that point is set in Pr.1481 (only when the set frequency is within 2 Hz of the frequency of the

measurement point, and the SU signal is ON).

Set load references in Pr.1482 to Pr.1485 in the same way as Pr.1481.

NOTE When inputting values in Pr.1481 to Pr.1485 directly, input the load meter monitored values at the frequency of each

load characteristics reference.

6 PLC function

This section describes the CC-Link I/O specifications for the PLC function. For details, refer to the PLC function

programming manual.

The signal name of the PLC function device No. Y34 differs depending on the setting of Pr.192 IPF terminal function selection

as follows.

The signal name of the PLC function device No. Y35 differs depending on the setting of Pr.193 OL terminal function selection

as follows.

Pr. Name Initial value

Setting range

Description

1481 H521

Load characteristics load reference 1 9999

0 to 400% Set the reference value of normal load characteristics. 8888: The present load status is written as reference status. 9999: The load reference is invalid.

1482 H522

Load characteristics load reference 2 9999

1483 H523

Load characteristics load reference 3 9999

1484 H524

Load characteristics load reference 4 9999

1485 H525

Load characteristics load reference 5 9999

Reference Frequency Load reference

Load characteristics reference 1 f1: Load characteristics minimum frequency (Pr.1487) Pr.1481

Load characteristics reference 2 f2 = (f5-f1)/4+f1 Pr.1482

Load characteristics reference 3 f3 = (f5-f1)/2+f1 Pr.1483

Load characteristics reference 4 f4 = (f5-f1)3/4+f1 Pr.1484

Load characteristics reference 5 f5: Load characteristics maximum frequency (Pr.1486) Pr.1485

Pr.192 setting Signal name

9999 Instantaneous power failure (Terminal IPF function)

Other than 9999 Overload alarm (Terminal OL function)

Pr.193 setting Signal name

9999 Overload alarm (Terminal OL function)

Other than 9999 Instantaneous power failure (Terminal IPF function)

BCN-C22005-914_ENG.book 5

FR-F800 Series Instruction Manual Supplement

1 Cooling fan operation selection during the test operation

The cooling fan can be stopped during PM motor test operation.

Cooling fan operation selection during the test operation (P.H106) When P.H106 = "1" or Pr.244 = "1000, 1001, or 1101 to 1105", the cooling fan can be set to always OFF during PM motor test

operation.

Pr. Name Initial value

Setting range Description

244 Cooling fan operation selection 1

0 Cooling fan ON/OFF control is disabled. (The cooling fan is always ON at power ON) The cooling fan operates at power ON.

1

Cooling fan ON/OFF control is enabled. The fan is always ON while the inverter is running. During a stop, the inverter status is monitored and the fan switches ON/OFF according to the temperature.

101 to 105 Cooling fan ON/OFF control is enabled. Set the cooling fan stop waiting time within 1 to 5 seconds.

1000

Cooling fan ON/OFF control is disabled. (The cooling fan is always ON at power ON) The cooling fan operates at power ON.

The cooling fan can be set to always OFF during PM motor test operation.

1001

Cooling fan ON/OFF control is enabled. The fan is always ON while the inverter is running. During a stop, the inverter status is monitored and the fan switches ON/OFF according to the temperature.

1101 to 1105

Cooling fan ON/OFF control is enabled. Set the cooling fan stop waiting time within 1 to 5 seconds.

H100 Cooling fan operation selection 1

0 Cooling fan ON/OFF control is disabled. (The cooling fan is always ON at power ON) The cooling fan operates at power ON.

1

Cooling fan ON/OFF control is enabled. The fan is always ON while the inverter is running. During a stop, the inverter status is monitored and the fan switches ON/OFF according to the temperature.

101 to 105 Cooling fan ON/OFF control is enabled. Set the cooling fan stop waiting time within 1 to 5 seconds.

H106

Cooling fan operation selection during the test operation

0 0 The cooling fan operates according to the H100 setting during PM

motor test operation.

1 The cooling fan can be set to always OFF during PM motor test operation.

1 BCN-C22005-931

2 Inverter parts life display The degree of deterioration of the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit circuit, and relay contacts of terminals A, B, and C can be diagnosed on the monitor. When the life span of each part is near its end, the self-diagnostic warning is output to prevent a fault. (Use the life check of this function as a guideline only, since the life span of each part except for the main circuit capacitor is calculated theoretically.)

*1 The setting range (read-only) differs depending on the inverter model (standard model, separate converter type, or IP55 compatible model).

Life alarm display and signal output (Y90 signal, Pr.255)

In the life diagnosis of the main circuit capacitor, the alarm signal (Y90) is not output unless measurement by turning OFF the power supply is performed.

Pr.255 Life alarm status display and the Life alarm (Y90) signal can be used to check whether or not the life alarm output level is reached for the following parts: the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit circuit, relay contacts of terminals A, B, and C, and internal air circulation fan. (Internal air circulation fans are equipped with IP55 compatible models.)

When the parts have reached the life alarm output level, the corresponding bits of Pr.255 turns ON. The ON/OFF state of the bits can be checked with Pr.255. The following table shows examples.

: Parts reaching alarm output level : Parts not reaching alarm output level

Pr. Name Initial value Setting range Description

255 E700 Life alarm status display 0 (0 to 255)*1

Displays whether or not the life alarm output level is reached for the following parts: the control circuit capacitor, main circuit capacitor, cooling fan, inrush current limit circuit, and relay contacts of terminals A, B, and C. Read-only.

507 E706

Display/reset ABC1 relay contact life 100% (0 to 100%) Displays the degree of deterioration of the relay

contacts of terminals A1, B1, and C1. 508 E707

Display/reset ABC2 relay contact life 100% (0 to 100%) Displays the degree of deterioration of the relay

contacts of terminals A2, B2, and C2.

Pr.255 bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0 Remarks

Decimal Binary

239 11101111 All parts have reached alarm output level for standard structure models.

5 101 Control circuit capacitor and cooling fan have reached alarm output level.

0 0 No parts have reached alarm output level.

0 0 0 0 0 0 0 0 0 0 0 0 1 0 0

bit0 Control circuit capacitor life

1 15bit 7 0

bit1 Main circuit capacitor life (Standard models and IP55 compatible models only)

bit2 Cooling fan life bit3 Inrush current limit circuit life (Standard models and IP55 compatible models only)

Pr.255 read Pr.255 setting read

Bit image is displayed in decimal

bit4 Life of internal air circulation fans (IP55 compatible models only) bit5 Estimated residual-life of main circuit capacitor (Standard models and IP55 compatible models only)

bit6 ABC1 relay contact life bit7 ABC2 relay contact life

2 BCN-C22005-931

The Life alarm (Y90) signal turns ON when the life alarm output level is reached for either of the following: the control circuit capacitor life, main circuit capacitor life, cooling fan life, inrush current limit circuit life, internal air circulation fan life, estimated residual-life of the main circuit capacitor, ABC1 relay contact life, or ABC2 relay contact life.

For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) in any of Pr.190 to Pr.196 (Output terminal function selection).

NOTE When using an option (FR-A8AY, FR-A8AR, FR-A8NC, FR-A8NCE, or FR-A8NCG), warning signals can be output

individually: Control circuit capacitor life (Y86) signal, Main circuit capacitor life (Y87) signal, Cooling fan life (Y88) signal, Inrush current limit circuit life (Y89) signal, Estimated residual-life of main circuit capacitor (Y248) signal, ABC1 relay contact life (Y249) signal, and ABC2 relay contact life (Y250) signal.

Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other functions. Set parameters after confirming the function of each terminal.

Life display of the relay contacts of terminals A, B, and C (Pr.507, Pr.508)

The degree of deterioration of the relay contacts of terminals A1, B1, and C1 is displayed in Pr.507, and that for terminals A2, B2, and C2 is displayed in Pr.508.

The number of times the contacts of relay turn ON is counted down from 100% (0 time) by 1% (500 times). When the counter reaches 10% (45,000 times), bit 6 or bit 7 of Pr.255 turns ON and a warning is output by the Y90 signal.

Any value can be set in Pr.507 and Pr.508. After replacement of the control circuit terminal block or installation of a control terminal option, set Pr.507 and Pr.508 again.

3 For customers using communication options manufactured by HMS

DriveControl writing restriction selection The command source to change the DriveControl settings (including Netctrl bit and Netref bit) can be selected.

Pr. Name Initial value Setting range Description

349 Communication reset selection/Ready bit status selection

0

0, 1, 100, 101, 1000, 1001, 1100, 1101, 10000, 10001, 10100, 10101, 11000, 11001, 11100, 11101

Use this parameter to select the error reset operation, Ready bit status, inverter reset operation when a fault is cleared, and DriveControl writing restriction.

N010 Communication reset selection 0

0 Error reset is enabled in any operation mode. 1 Error reset is enabled in the Network operation mode.

N240 Ready bit status selection 0 0 The status of Ready bit in communication data can be

changed when an HMS network option is installed.1

N241 Reset selection after inverter faults are cleared 0

0 The inverter is reset when a fault is cleared. 1 The inverter is not reset when a fault is cleared.

N242 DriveControl writing restriction selection 0

0 DriveControl writing is not restricted. 1 DriveControl writing is restricted.

3 BCN-C22005-931

DriveControl writing restriction selection (P.N242) The command source to change the DriveControl settings can be restricted to only the command source selected

by Pr.550 NET mode operation command source selection.

*1 The operation mode affects the availability of communication reset. *2 The ON/OFF state of the power supply affects the ON/OFF state of Ready bit. *3 When 24 V external power is available for control circuit or power is input only to control circuit. *4 Available when the HMS network option is installed.

Setting value Description

Pr.349 N010 N240 N241 N242

Communication reset selection*1 Ready bit status selection*2

Reset selection after inverter faults

are cleared

DriveControl writing

restriction selection

NET operation

mode

Other than NET

operation mode

Main circuit: power-ON

Main circuit: power-OFF*3

0 0 0 0 0 Reset enabled

Reset enabled

Ready bit: ON

Ready bit: ON Reset enabled Not restricted

1 1 0 0 0 Reset enabled

Reset disabled

Ready bit: ON

Ready bit: ON Reset enabled Not restricted

100 0 1 0 0 Reset enabled

Reset enabled

Ready bit: ON

Ready bit: OFF Reset enabled Not restricted

101 1 1 0 0 Reset enabled

Reset disabled

Ready bit: ON

Ready bit: OFF Reset enabled Not restricted

1000 0 0 1 0 Reset enabled

Reset enabled

Ready bit: ON

Ready bit: ON

Reset disabled*4 Not restricted

1001 1 0 1 0 Reset enabled

Reset disabled

Ready bit: ON

Ready bit: ON

Reset disabled*4 Not restricted

1100 0 1 1 0 Reset enabled

Reset enabled

Ready bit: ON

Ready bit: OFF

Reset disabled*4 Not restricted

1101 1 1 1 0 Reset enabled

Reset disabled

Ready bit: ON

Ready bit: OFF

Reset disabled*4 Not restricted

10000 0 0 0 1 Reset enabled

Reset enabled

Ready bit: ON

Ready bit: ON Reset enabled Restricted*4

10001 1 0 0 1 Reset enabled

Reset disabled

Ready bit: ON

Ready bit: ON Reset enabled Restricted*4

10100 0 1 0 1 Reset enabled

Reset enabled

Ready bit: ON

Ready bit: OFF Reset enabled Restricted*4

10101 1 1 0 1 Reset enabled

Reset disabled

Ready bit: ON

Ready bit: OFF Reset enabled Restricted*4

11000 0 0 1 1 Reset enabled

Reset enabled

Ready bit: ON

Ready bit: ON

Reset disabled*4 Restricted*4

11001 1 0 1 1 Reset enabled

Reset disabled

Ready bit: ON

Ready bit: ON

Reset disabled*4 Restricted*4

11100 0 1 1 1 Reset enabled

Reset enabled

Ready bit: ON

Ready bit: OFF

Reset disabled*4 Restricted*4

11101 1 1 1 1 Reset enabled

Reset disabled

Ready bit: ON

Ready bit: OFF

Reset disabled*4 Restricted*4

4 BCN-C22005-931

4 BACnet network port

Supported property of BACnet standard object type The BACnet network port is added.

R: Read only, W: Read/Write (Commandable values not supported), C: Read/Write (Commandable values supported)

*1 This property is commandable for some instances of this object. Otherwise it is read/write. *2 This property is supported only for instances of this object where the Present Value property is commandable. *3 Writing is possible when the network type is not PTP.

Property Object support condition

Analog Input

Analog Output

Analog Value

Binary Input

Binary Output

Binary Value Device Network

Port APDU Timeout R Application Software Version (Application Software Version) R

Database Revision R Device Address Binding (Device Address Binding) R

Event State R R R R R R Firmware Revision R Max APDU Length Accepted R Max Info Frames W W Max Master W W Model Name R Number of APDU Retries R Object Identifier R R R R R R R R Object List R Object Name R R R R R R R R Object Type R R R R R R R R Out Of Service R R R R R R R Polarity R R Present Value R C C*1 R C C*1

Priority Array R R*2 R R*2

Protocol Object Types Supported (Protocol Object Types Supported) R

Protocol Revision R Protocol Services Supported (Protocol Services Supported) R

Protocol Version R Relinquish Default R R*2 R R*2

Segmentation Supported R Status Flags R R R R R R R System Status R Unit R R R Vendor Identifier R Vendor Name R Property List R R R R R R R R Current Command Priority R R Reliability R Network Type R Protocol Level R Network Number R*3

Network Number Quality R Changes Pending R APDU Length R Link Speed R MAC Address R IP Address R IP Subnet_Mask R IP Default Gateway R IP DNS Server R

5 BCN-C22005-931

Details of the supported properties The details of the properties supported by the network port are as follows.

Property Details

BACnet MS/TP BACnet/IP

Max Info Frames

Shows the maximum number of frames that the inverter can transmit while it owns the token. When a value is written, it is reflected to the Pr.727 setting.

A rejection code (0) is displayed when the property is read/written.

Max Master Shows the maximum address for master node When a value is written, it is reflected to the Pr.726 setting.

A rejection code (0) is displayed when the property is read/written.

Object Identifier Shows the unique numeric code to identify the object. Object Name Shows the object name. Object Type Network Port: NETWORK_PORT (56) Out Of Service FALSE (0) Status Flags Always 0. Property List Shows the property identifier list.

Reliability Shows the reliability of the network port. Fixed to no-fault-detected (0) for the FR-F800(-E).

Network Type Shows the communication method of the network. Fixed to MSTP (2) for the FR-F800.

Shows the communication method of the network. Fixed to IPV4 (5) for the FR-F800-E.

Protocol Level Shows the protocol level. Fixed to BACNET_APPLICATION (2) for the FR-F800(-E).

Network Number Shows the network number. Fixed to 0 for the FR-F800(-E). If a value other than "0" is written, an error code VALUE_OUT_OF_RANGE (37) will be returned.

Network Number Quality Shows the quality of the network port number. Fixed to UNKNOWN (0) for the FR-F800(-E).

Changes Pending If the property value whose change is to be reflected at a reset is changed, TRUE is returned. FALSE is returned after the status is initialized by a reset.

APDU Length Shows the maximum number of octets. Fixed to 50 octets for the FR-F800.

Shows the maximum number of octets. Fixed to 1024 octets for the FR-F800-E.

Link Speed

Shows the communication speed in the unit of bit/s. The Pr.332 setting value 100 equals the communication speed.

Shows the communication speed in the unit of bit/s. The Pr.1426 setting value is used for the communication speed.

MAC Address

Shows the MAC address of the network port. The Pr.331 setting value is used for the MAC address. For example, the MAC address is 7F when Pr.331 = "127".

A rejection code (0) is displayed when the property is read/written.

IP Address A rejection code (0) is displayed when the property is read.

Shows the octet string of the IP address assigned to the inverter. For example, C0A83200 is displayed when the IP address is 192.168.50.0.

IP Subnet Mask A rejection code (0) is displayed when the property is read.

Shows the octet string of the subnet mask assigned to the inverter. For example, FFFFFF00 is displayed when the subnet mask is 255.255.255.0.

IP Default Gateway A rejection code (0) is displayed when the property is read. Fixed to "00000000" for the FR-F800-E.

IP DNS Server A rejection code (0) is displayed when the property is read. Fixed to "00000000" for the FR-F800-E.

6 BCN-C22005-931

1 BCN-C22005-976

FR-F800 Series Instruction Manual Supplement

1 Internal storage device fault (E.PE6) The operation of the storage device in the inverter can be checked. If a data fault occurs in the storage device in the inverter, the protective function (E.PE6) is activated. When the read value of Pr.890 is "7" or smaller, an inverter reset after All parameter clear can return the operation to normal. (The parameters that had been changed before All parameter clear must be set again.)

*1 For example, when parameter clear, All parameter clear, Parameter copy, or offline auto tuning is performed in the inverter, or when parameter batch write is performed in FR Configurator2.

NOTE "E.PE6" does not activate the retry function. "E.PE6" outputs the Fault output 3 (Y91) signal. "E.PE6" turns OFF the Safety monitor output (SAFE) signal. "E.PE6" is not cleared by turning ON the Fault clear (X51) signal. "E.PE6" is not activated during emergency drive operation. The communication data code for "E.PE6" is 172 (HAC).

Checking faulty area in the internal storage device When E.PE6 occurs, faulty area in the internal storage device can be checked by reading Pr.890.

Use the read value of Pr.890 to check the faulty area. The following table shows faulty areas indicated by the read value of Pr.890. Some read values indicate that there are multiple

faulty areas. (For example, the read value "7" indicates that all the areas described in No. 1 to No. 3 are faulty.)

Operation panel indication E.PE6 FR-LU08

indication Fault

Name Internal storage device fault

Description This protective function is activated by an inverter reset if writing data fails due to power-OFF or a data fault occurs in the storage device during parameter operations*1.

Check point Check if the power was turned OFF during parameter operations.

Corrective action

Check the power supply or the devices on the power system to check that the devices have no fault. When E.PE6 occurs due to power-OFF during parameter operations:

Check the read value of Pr.890. When the value is "7" or smaller, perform All parameter clear and then an inverter reset. The parameters that had been changed before All parameter clear must be set again.

When E.PE6 occurs due to other reason (such as turning OFF/ON the power or an inverter reset): Contact your sales representative.

Pr. Name Initial value Setting range Description 890 H325

Internal storage device status indication 0 (0 to 9999) A faulty area detected by self-check function can be

indicated in the internal storage device.

No. Read value Description

1 1, 3, 5, 7 Storage area other than the area for parameter settings is faulty (such as area for the set frequency). (When All parameter clear is performed, the set frequency, remotely-set frequency, host name for Ethernet communication, and offline auto tuning data are cleared.)

2 2, 3, 6, 7 Storage area for standard parameter settings is faulty. 3 4, 5, 6, 7 Storage area for communication parameter settings is faulty. 4 8 to 9999 Area for manufacturer setting

Pr.890 read Pr.890 setting read

BCN-C22005-976_ENG.fm 1

2 BCN-C22005-976

2 PID upper/lower limit pre-warning (Pr.1346, Pr.1370 to Pr.1373)

Pr.1346 PID lower limit operation detection time is added. Detection time for PID upper/lower limit pre-warning can be set separately.

The set point can be changed to suppress increases of the measured value before PID upper limit (FUP) or PID lower limit (FDN) is detected.

When the measured value reaches and remains at the pre-warning level set in Pr.1371 PID upper/lower limit pre-warning level range for the time set in Pr.1370 Detection time for PID limiting operation, the PID upper/ lower limit pre-warning (Y219) signal or the Second PID upper/lower limit pre-warning (Y220) signal is output. Also, the set point is changed by the amount set in Pr.1372 PID measured value control set point change amount.

To set the detection time for upper and lower limits separately, set Pr.1346 PID lower limit operation detection time.

Set the rate (%/s) in Pr.1373 PID measured value control set point change rate for changing the set point by the Pr.1372 setting value. When the measured value falls within the normal range, the set point returns to its original value.

For the Y219 and Y220 signals, assign the functions to output terminals using the Pr.190 to Pr.196 (Output terminal function selection).

Pr. Name Initial value

Setting range Description

1346 A457

PID lower limit operation detection time 9999

0 to 900 s Set the time from when the measured value reaches the lower limit pre-warning level (Pr.1371) until the set point change is started.

9999 The Pr.1370 setting is applied to the operation. 1370 A442

Detection time for PID limiting operation 0 s 0 to 900 s Set the time from when the measured value reaches the pre-

warning level (Pr.1371) until the set point change is started.

1371 A443

PID upper/lower limit pre- warning level range 9999

0% to 50% Set the operation range for the PID upper/lower limit pre- warning function.

9999 The PID upper/lower limit pre-warning function is disabled. 1372 A444

PID measured value control set point change amount 5% 0% to 50% Set the set point change amount for the PID upper/lower limit

pre-warning operation. 1373 A445

PID measured value control set point change rate 0% 0% to 100% Set the set point change rate for the PID upper/lower limit pre-

warning operation.

Output signal Pr.190 to Pr.196 setting

Positive logic Negative logic Y219 219 319 Y220 220 320

BCN-C22005-976_ENG.fm 2

3 BCN-C22005-976

Measured value

Measured value

Lower limit level Pr.132 (Pr.1144)

Time

FUP

FDN

Upper limit level Pr.131 (Pr.1143)

Set point

Upper limit pre-warning level

Lower limit pre-warning level

Normal set point Pr.1372

Pr.1373

Pr.1373

Y219(Y220)

Pr.1371

Pr.1370Pr.1370 or

Pr.1346

Pr.1370

ON

Pr.1372

Pr.1370 or

Pr.1346

Pr.1370 Pr.1370

Pr.1371

Pr.1373

ON ON ON

BCN-C22005-976_ENG.fm 3

INVERTER

IN VER

TER F800

FR

-F862 IN STR

U C

TIO N

M A

N U

A L (H

A R

D W

A R

E)

B

INTRODUCTION 1

INSTALLATION AND WIRING 2

PRECAUTIONS FOR USE OF THE INVERTER 3

PROTECTIVE FUNCTIONS 4

PRECAUTIONS FOR MAINTENANCE AND

INSPECTION 5

SPECIFICATIONS 6

HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

IB(NA)-0600689ENG-B(1903)MEE Printed in Japan Specifications subject to change without notice.

F800 FR-F862 (SEPARATED CONVERTER TYPE) INSTRUCTION MANUAL (HARDWARE)

FR-F862-05450 to 08500 Inverter for fans and pumps

Manualsnet FAQs

If you want to find out how the F800 Mitsubishi Electric works, you can view and download the Mitsubishi Electric F800 FR F862 Instruction Manual on the Manualsnet website.

Yes, we have the Instruction Manual for Mitsubishi Electric F800 as well as other Mitsubishi Electric manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Instruction Manual should include all the details that are needed to use a Mitsubishi Electric F800. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Mitsubishi Electric F800 FR F862 Instruction Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Mitsubishi Electric F800 FR F862 Instruction Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Mitsubishi Electric F800 FR F862 Instruction Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Mitsubishi Electric F800 FR F862 Instruction Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Mitsubishi Electric F800 FR F862 Instruction Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.