SS-GAVPEC www.goodmanmfg.com 8/21 Supersedes 3/21
Contents Nomenclature ....................................... 2 Product Specifications .......................... 3 Dimensions ........................................... 4 Airflow Data ........................................... 5 Heat Kit Data .......................................... 6 Wiring Diagram ..................................... 8 Accessories ........................................... 9
AVPEC Multi-Position, Variable-Speed,
ECM-Based Air Handler with Internal EEV, ComfortBridge
and Inverter Compatible 2 to 5 Tons
* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec.
Product Features Electronic Expansion Valve (EEV) for
cooling and heat pump applications. Variable-speed ECM blower motor Suitable for operation with inverter-driven products Integrated communicating ComfortBridge Technology Commissioning and diagnostics via on board Bluetooth
with the CoolCloud phone and tablet application Provides constant CFM over a wide range of static
pressure conditions independent of duct system CFM indicator Provides adjustable low CFM
for efficient fan-only operation All-aluminum evaporator coil Fault recall of six most recent faults Improved humidity and comfort control 3 kW 25 kW electric heater kits AHRI certified; ETL listed
Cabinet air leakage less than 2.0% at 1.0 inch HO when tested in accordance with ASHRAE standard 193
Cabinet air leakage less than 1.4% at 0.5 inch HO when tested in accordance with ASHRAE standard 193
Horizontal or vertical configuration capabilities 21" depth for easier attic access DecaBDE-free thermoplastic drain pan
with secondary drain connections Screw-less sides and back helps to reduce
condensation when installed in humid locations Foil-faced insulation covers the internal
casing to reduce cabinet condensation Galvanized, leather grain-embossed finish Glue-less cabinet insulation retention Tool-less filter access
2 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 3
Nomenclature
A V P E C 25 B 1 4 AA
1 2 3 4 5 6,7 8 9 10 11,12
Brand Engineering*
A Single-Piece Air Handler Major/Minor Revisions
*Not used for inventory management
Unit Application Refrigerant Charge
R Multi Position PSC Motor 4 = R-410A
S Multi Position EEM Motor
V Multi Position Variable-Speed Electrical
Motor - Communicating 1 208/230V, 1 Phase, 60 Hz
Cabinet Finish Cabinet Width
U Unpainted B = 17"
P Painted C = 21"
D = 24"
Expansion Device
E Electronic Expansion Valve Nominal Capacity @ 13 SEER
T Expansion Device 24 = 2 Tons 31 = 2 Tons 48 = 4 Tons
V Inverter Tuned Expansion Valve 25 = 2 Tons 36 = 3 Tons 49 =3-3 Tons
29 = 2 Tons 37 = 3 Tons 59 = 4-5 Tons
Communicating 30 = 2 Tons 42 = 3 Tons 60 = 5 Tons
C = Yes 61 = 4-5 Tons
HKS X 03 X A AA
1 2 3 4 5 6,7
Unit Type Revisions
HKS Heat Kit for Engineering Revisions Air Handlers
Phase
Circuit Breaker A Single Phase 208 V E Three Phase 240 V
X No circuit breaker B Single Phase 240 V F Three Phase 208/240 V
C Circuit Breaker C Single Phase 208/240 V G Three Phase 460 V
D Three Phase 208 V
Heating Capacity @ 240 Volts H Special case 208 V*
03 3.0 kW 15 14.4 kW Cabinet Size (MAX)
05 4.5 kW 19 19.2 kW wth 150F limit C C Cabinet
06 6.0 kW 20 19.2 kW with 170F limit D D Cabinet
08 8.0 kW 25 25.0 kW X All Cabinet Sizes
10 9.6 kW
*Refer S&R Plate
2 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 3
Product Specifications
AVPEC25 B14A*
AVPEC37 C14A*
AVPEC59 D14A*
AVPEC61 D14A*
Nominal Ratings
Cooling (BTU/h) 24,000 36,000 48,000 60,000
CFM (High range) 1200/600 1700/800 1800/1350 2000/1600
Blower
Diameter 10" 10" 11" 11"
Width 6" 10" 10" 10"
Coil Drain Connection FPT " " " "
Service Valve
Liquid " " " "
Suction " " " "
Electrical Data
Voltage 208/240 208/240 208/240 208/240
Electric Heat Capacity (kW) 3, 5, 6, 8, 10 5, 6, 8, 10, 15, 19 5, 6, 8, 10, 15, 20 5, 6, 8, 10, 15, 20, 25
Min Circuit Ampacity 4.9/4.9 6.5/6.5 8.6/8.6 8.6/8.6
Max. Overcurrent Device (Amps) 15/15 15/15 15/15 15/15
Minimum VAC 197 197 197 197
Maximum VAC 253 253 253 253
Blower Motor
Full Load Amps (FLA) 3.9 5.2 6.9 6.9
Horsepower (HP) 1 1
Ship Weight (lbs.) 128 150 160 177 Note: Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental
heat installed. Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed.
4 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 5
Dimensions
AVPEC _D
IM EN
SIO N
S
9 8 7 6 5 4 3 2 1
9 8 7 6 5 4 3 2 1
F
C
D
E
B
A
F
C
D
E
B
SC
CC
1-13/16" (4.60 cm) 1-13/16" (4.60 cm)F INLET
(FRONT VIEW)
H
G
E
D
2-11/16" (6.83 cm)
1-11/16" (4.29 cm)
10-3/32" (25.88 cm)
5/8" (1.59 cm) 5/8" (1.59 cm)B
C
K J
1-15/16" (4.92 cm)
3-11/16" (9.37 cm)
7-1/8" (18.1 cm)
1" (25.4 cm) 17/3219.5" (49.53 cm) INLET
(RIGHT SIDE VIEW)
A
1-25/32" (4.52 cm)
1-13/32" (3.57 cm)
3-1/16" (7.78 cm)
5-5/32" (13.10 cm)
7-17/32" (19.13 cm)
9-5/32" (23.26 cm) 11-7/32" (28.50 cm)
21/32 (1.67 cm)
21" (55.88 cm)
1-23/32" (4.13 cm)
1-1/2" (11.43 cm)
1-11/32" (3.33 cm)
1-5/8" (4.13 cm)
2-31/32" (7.46 cm) 3-1/32" (7.70 cm)
3-25/32" (9.60 cm)
SCALE: NTS
SHEET: 1 OF 1
DWG. NO. AVPEC_DIMENSIONS
SPECIAL CHARACTERISTICS: (REFER MSP 822-01 FOR DETAILS) = CRITICAL CHARACTERISTIC REQUIRES AN INITIAL CPK OF 1.33 AND USE OF STATISTICAL PROCESS CONTROL.
= SIGNIFICANT CHARACTERISTIC REQUIRES AN INITIAL CPK OF 1.00 AND USE OF STATISTICAL PROCESS CONTROL. INABILITY TO MEET THE REQUIRED INITIAL CPK VALUE WILL REQUIRE 100% INSPECTION. CONFIDENTIAL PROPERTY OF GOODMAN MANUFACTURING COMPANY, L.P. OR ITS AFFILIATES NOT TO BE DISCLOSED TO
OTHERS, COPIED, OR USED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING. MUST BE RETURNED UPON DEMAD, ON COMPLETION OF ORDER, OR OTHER PURPOSE FOR WHICH IT WAS LENT
VERTICAL DRAIN PORT DEATIL
SEE VERTICAL DRAIN PORT DETAIL
SEE HORIZONTAL DRAIN PORT DETAIL
SUCTION TUBE LIQUID LINE
INLET TUBE
HORIZANTAL DRAIN PORT DEATIL
Model A B C D E F G H
AVPEC25B14 53 16 17 20 21 14 9 7
AVPEC37C14 53 19 21 21 18 17 10 6
AVPEC59D14 53 23 24 21 18 21 12 6
AVPEC61D14 58 23 24 26 22 21 12 25
4 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 5
Airflow Data
Model Stage Airflow CFM
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
AVPEC25B14A* High 700 690 690 685 680 670 665 660 655
Low 520 505 495 490 470 455 445 435 425
AVPEC37C14A* High 1190 1170 1165 1160 1145 1130 1120 1105 1100
Low 820 810 795 785 765 740 730 720 710
AVPEC59D14A* High 1445 1440 1430 1415 1405 1390 1380 1375 1370
Low 880 875 870 870 860 845 840 835 830
AVPEC61D14A* High 1645 1640 1640 1635 1630 1625 1620 1620 1615
Low 1080 1075 1070 1070 1060 1055 1050 1050 1045
Note: During cooling operation outdoor will determine the indoor airflow
Cooling/Heat Pump Airflow table
Model Airflow Level CFM
AVPEC25B14A* High 690
Low 495
AVPEC37C14A* High 1165
Low 795
AVPEC59D14A* High 1430
Low 870
AVPEC61D14A* High 1640
Low 1070
6 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 7
Heat Kit Data
See notes on page 7.
Model Circuit 1 Circuit 2 Single-Point Kit
Amps MCA MOP Amps MCA MOP MCA MOP
AVPEC25B14AC 0.0/0.0 4.9/4.9 15/15 --- --- --- --- ---
HKSX03XC - 208 V
No Breaker
10.8 18 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 27 30 --- --- --- --- ---
HKSX06XC - 208 V 21.7 32 35 --- --- --- --- ---
HKSX08XC - 208 V 28.9 41 45 --- --- --- --- ---
HKSX10XC - 208 V 34.7 48 50 --- --- --- --- ---
HKSC05XC - 208 V
Breaker
17.3 27 30 --- --- --- --- ---
HKSC08XC - 208 V 28.9 41 45 --- --- --- --- ---
HKSC10XC - 208 V 34.7 48 50 --- --- --- --- ---
HKSX03XC - 240 V
No Breaker
12.5 21 25 --- --- --- --- ---
HKSX05XC - 240 V 20 30 30 --- --- --- --- ---
HKSX06XC - 240 V 25 36 40 --- --- --- --- ---
HKSX08XC - 240 V 33.3 47 50 --- --- --- --- ---
HKSX10XC - 240 V 40 55 60 --- --- --- --- ---
HKSC05XC - 240 V
Breaker
20 30 30 --- --- --- --- ---
HKSC08XC - 240 V 33.3 47 50 --- --- --- --- ---
HKSC10XC - 240 V 40 55 60 --- --- --- --- ---
AVPEC37C14AC 0/0 6.5/6.5 15/15 --- --- --- --- ---
HKSX05XC - 208 V
No Breaker
17.3 28 30 --- --- --- --- ---
HKSX06XC - 208 V 21.7 34 35 --- --- --- --- ---
HKSX08XC - 208 V 28.9 43 45 --- --- --- --- ---
HKSX10XC - 208 V 34.7 50 50 --- --- --- --- ---
HKSC05XC - 208 V
Breaker
17.3 28 30 --- --- --- --- ---
HKSC08XC - 208 V 28.9 43 45 --- --- --- --- ---
HKSC10XC - 208 V 34.7 50 50 --- --- --- --- ---
HKSC15XA - 208 V 34.7 49.8 50 17.3 21.7 25 71.5 80
HKSC19CA - 208 V 34.7 49.8 50 34.7 43.3 45 93.2 100
HKSC15XF - 208 V ^ 0 6.5 15 30 38 40 --- ---
HKSX05XC - 240 V
No Breaker
20 32 35 --- --- --- --- ---
HKSX06XC - 240 V 25 38 40 --- --- --- --- ---
HKSX08XC - 240 V 33.3 48 50 --- --- --- --- ---
HKSX10XC - 240 V 40 57 60 --- --- --- --- ---
HKSC05XC - 240 V
Breaker
20 32 35 --- --- --- --- ---
HKSC08XC - 240 V 33.3 48 50 --- --- --- --- ---
HKSC10XC - 240 V 40 57 60 --- --- --- --- ---
HKSC15XB - 240 V 40 56.5 60 20 25 25 81.5 90
HKSC19CB - 240 V 40 56.5 60 40 50 50 107 110
HKSC15XF - 240 V ^ 0 6.5 15 34.6 43 45 --- ---
AVPEC59D14AC 0/0 8.6/8.6 15/15 --- --- --- --- ---
HKSX05XC - 208 V
No Breaker
17.3 30.3 35 --- --- --- --- ---
HKSX06XC - 208 V 21.7 36 40 --- --- --- --- ---
HKSX08XC - 208 V 28.9 45 45 --- --- --- --- ---
HKSX10XC - 208 V 34.7 52 60 --- --- --- --- ---
6 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 7
Heat Kit Data (cont.)
Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25 Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps 3 Notation is correct as XB because technically the 240V heater kit application can be used here
without any issues. ^ Three-phase Heater Kits (Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for Heater Kits) --- indicates Not Required Note: The 208 or 240 in the heat kit part number field is for clarification of the nominal voltage for this model.
Model Circuit 1 Circuit 2 Single-Point Kit
Amps MCA MOP Amps MCA MOP MCA MOP
HKSC05XC - 208 V
Breaker
17.3 30.3 35 --- --- --- --- ---
HKSC08XC - 208 V 28.9 45 45 --- --- --- --- ---
HKSC10XC - 208 V 34.7 52 60 --- --- --- --- ---
HKSC15XB 3 - 208 V 34.7 52 60 17.3 21.7 25 74 80
HKSC20DH - 208 V 34.7 52 60 34.7 43.3 45 95.3 100
HKSC15XF - 208 V ^ 0 8.6 15 30 38 40 --- ---
HKSX05XC - 240 V
No Breaker
20 34 35 --- --- --- --- ---
HKSX06XC - 240 V 25 40 40 --- --- --- --- ---
HKSX08XC - 240 V 33.3 50.3 60 --- --- --- --- ---
HKSX10XC - 240 V 40 59 60 --- --- --- --- ---
HKSC05XC - 240 V
Breaker
20 34 35 --- --- --- --- ---
HKSC08XC - 240 V 33.3 50.3 60 --- --- --- --- ---
HKSC10XC - 240 V 40 59 60 --- --- --- --- ---
HKSC15XB - 240 V 40 58.6 60 20 25 25 83.6 90
HKSC20DB - 240 V 40 58.6 60 40 50 50 109 110
HKSC15XF - 240 V ^ 0 8.6 15 34.6 43 45 --- ---
AVPEC61D14AC 0/0 8.6/8.6 15/15 --- --- --- --- ---
HKSX05XC - 208 V
No Breaker
17.3 30 35 --- --- --- --- ---
HKSX06XC - 208 V 21.7 36 40 --- --- --- --- ---
HKSX08XC - 208 V 28.9 45 45 --- --- --- --- ---
HKSX10XC - 208 V 34.7 52 60 --- --- --- --- ---
HKSC05XC - 208 V
Breaker
17.3 30 35 --- --- --- --- ---
HKSC08XC - 208 V 28.9 45 45 --- --- --- --- ---
HKSC10XC - 208 V 34.7 52 60 --- --- --- --- ---
HKSC15XB 3 - 208 V 34.7 52 60 17.3 21.7 25 73.6 80
HKSC20DH - 208 V 34.7 52 60 34.7 43.3 45 95.3 100
HKSC25DA - 208 V 52 73.6 80 35 43.3 45 117 125
HKSC15XF - 208 V ^ 0 8.6 15 30 38 40 --- ---
HKSC20XF - 208 V ^ 0 8.6 15 38 47 50 --- ---
HKSX05XC - 240 V
No Breaker
20 34 35 --- --- --- --- ---
HKSX06XC - 240 V 25 40 40 --- --- --- --- ---
HKSX08XC - 240 V 33.3 50.3 60 --- --- --- --- ---
HKSX10XC - 240 V 40 59 60 --- --- --- --- ---
HKSC05XC - 240 V
Breaker
20 34 35 --- --- --- --- ---
HKSC08XC - 240 V 33.3 50.3 60 --- --- --- --- ---
HKSC10XC - 240 V 40 59 60 --- --- --- --- ---
HKSC15XB - 240 V 40 58.6 60 20 25 25 83.6 90
HKSC20DB - 240 V 40 58.6 60 40.0 50 50 109 110
HKSC25DB - 240 V 60 83.6 90 40 50 50 134 150
HKSC15XF - 240 V ^ 0 8.6 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 8.6 15 43.3 54 60 --- ---
Supply Voltage 240 230 220 210 208 Correction Factor 1.00 0.92 0.84 0.77 0.75
Multiply the 240-volt heating capacity by correction factors.
Heating kW Correction Factor
8 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 9
Wiring Diagram
0140A00723-C
HEATER KIT OUTPUT
43 65 987 10 11 12
BK RD
BK RD
BL
BR
WH
BL RD PU YL
RD BK
GROUND LUG (SEE NOTE 4)
24VAC
J19
INSTALLING AUX ALARM (ALARM) (SEE NOTE 8) ~~
~~
24VAC
COM COM 208 VAC
230 VAC
208 VAC 230
VAC
TR2 (SEE NOTE 1)
TR1 (SEE NOTE 1)
FAN MOTOR
21 BKRD GY BL
ECM MOTOR
BK RD
PL1 PL2
9 78 456 3 2 1
PL3 PL4
INTEGRATED CONTROL:
POWER/HEATER CONNECTOR
PL1, PL2
COMPONENT CODES:
TL
F1U, F2U TR
THERMAL LIMIT TRANSFORMER FUSE LINK
NOTES: 1. PLACE RED WIRES ON 208 V TERMINAL OF 2-TRANSFORMER (TR1/TR2) FOR 208 VAC OPERATION.
2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.
3. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105C. USE COPPER CONDUCTORS ONLY.
4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C ANDLOCAL CODES.
5. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS FAULT RECALL BUTTON FOR MORE THAN 2 SECONDS WHILE IN STANDBY (NO THERMOSTAT INPUTS)
6. YELLOW STATUS LED PROVIDES NETWORK STATUS.GREEN RX LED INDICATES NETWORK TRAFFIC
7. DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT.
8. REMOVE SHORTING PLATE FROM THE AUX SWITCH TERMINAL WHEN INSTALLING AUX ALARM SWITCH.
9. USE N.E.C CLASS 2 WIRE.
COLOR CODES:
BL - BLUE
RD - RED
YL - YELLOW
OR - ORANGE
BK - BLACK
GY - GREY
BR - BROWN
GR - GREEN
PU - PURPLE
WH - WHITE
LOW VOLTAGE
LOW VOLTAGE FIELD
HIGH VOLTAGE
HIGH VOLTAGE FIELD
JUNCTION
TERMINAL
INTERNAL TO
RESISTOR
OVERCURRENT PROT. DEVICE
PLUG CONNECTION
EQUIPMENT GND
FIELD GROUND
THERMISTOR (HEAT EXCHANGER 1,2)
M OR
INDOOR UNIT PCB
PRESSURE SENSOR
EEV COIL
EEV
INTEGRATION
GY RD YL
BK
AUX ALARM (ALARM)
GR
(SEE NOTE 7)
OUTDOOR UNIT
RD BK
BK RD
208/230 VACTO
HEATER KIT
TRANSFORMER CONNECTOR
PL3, PL4
BL
GRND
AIR
COM
W
C
208/230 VAC
CONDENSATE SWITCH
INDOOR
L1
HEAT 1 COIL/R1
TR2
INTEGRATED CONTROL MODULE
CIRCULATOR
+VDC (1)
GRND
BLWR
BLWR
EH2
L2
40 VA
R
TO MICRO
TH2
CIRCULATOR
L1
INDOOR
DEHUM GRND (4)
2 4 V T H E R M O S T A T C O N N E C T I O N S
RX (2)
24 VAC
AIR
AUX IN
FUSE 3 A
GRND
TX (3)
G
EH1
AUX OUT
TRANSFORMER
DISCONNECT
HEAT 2 COIL/ R2
L2
S E E
N O T E 9
TYPE
RD
J6 J7 J18
TH1 TR1
Y
J19 TB1 TB2
FH1 FH2F1U VR1
C1
D1
C2
D 2TB
7 TB
4
TB 3
TB 5
TB 6
FH3 F2U
FH4
V R
2
C 63
U 2
K3
K1
K2
U6
J6 J7
J20
PB1
PB2
PB3
J8 J9 J16 J17 J18
U9
J4
U1
J1 0
B11
B 12
U 4
U 10
C 89
J1 4
J1 1
U 5
U 3 L2
L1
J13
J1 5
J1 2
U7
+ _~~
U 8
C 5
R 14
6
C4C62
R 63
R 62
R 61 L4
J1 J2
L5 J5
J3
R13 R25
R 15
R 14
R 27
R 26
RCGWYDH/ Y2 RC 2 1
THERMOSTAT
YL GR GYBKW
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
8 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 9
Accessories
Filters
Chassis Part # Size
B ALFH16201E 16.0" x 20.0"
C ALFH1912201E 19.5 x 20.0
D ALFH20231E 23.0 x 20.0
Downflow Kits
DFK-B DFK-C DFK-D
AVPEC25B14** AVPEC37C14** AVPEC59D14**
AVPEC61D14**
** (DFK-B, DFK-C, DFK-D) kits need to be broken up by cabinet size
Single Point Kit **
Model HKR-15C HKR-20C HKR-21C
SPW-01 X X X
** Must be installed along with any of the above compatible heat kits. This kit will fit any AVPEC air handler as long as a compatible heat kit is installed in the unit.
Drain Port Plug
Kit Number Description Application
DPK1 Side Drain Port Plug All Models</
Related manuals for Goodman AVPEC User's Manual
Manualsnet FAQs
If you want to find out how the AVPEC Goodman works, you can view and download the Goodman AVPEC User's Manual on the Manualsnet website.
Yes, we have the User's Manual for Goodman AVPEC as well as other Goodman manuals. All you need to do is to use our search bar and find the user manual that you are looking for.
The User's Manual should include all the details that are needed to use a Goodman AVPEC. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.
The best way to navigate the Goodman AVPEC User's Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.
This Goodman AVPEC User's Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.
You can download Goodman AVPEC User's Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.
To be able to print Goodman AVPEC User's Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Goodman AVPEC User's Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.