SS-GAVPEC www.goodmanmfg.com 8/21 Supersedes 3/21

Contents Nomenclature ....................................... 2 Product Specifications .......................... 3 Dimensions ........................................... 4 Airflow Data ........................................... 5 Heat Kit Data .......................................... 6 Wiring Diagram ..................................... 8 Accessories ........................................... 9

AVPEC Multi-Position, Variable-Speed,

ECM-Based Air Handler with Internal EEV, ComfortBridge

and Inverter Compatible 2 to 5 Tons

* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec.

Product Features Electronic Expansion Valve (EEV) for

cooling and heat pump applications. Variable-speed ECM blower motor Suitable for operation with inverter-driven products Integrated communicating ComfortBridge Technology Commissioning and diagnostics via on board Bluetooth

with the CoolCloud phone and tablet application Provides constant CFM over a wide range of static

pressure conditions independent of duct system CFM indicator Provides adjustable low CFM

for efficient fan-only operation All-aluminum evaporator coil Fault recall of six most recent faults Improved humidity and comfort control 3 kW 25 kW electric heater kits AHRI certified; ETL listed

Cabinet air leakage less than 2.0% at 1.0 inch HO when tested in accordance with ASHRAE standard 193

Cabinet air leakage less than 1.4% at 0.5 inch HO when tested in accordance with ASHRAE standard 193

Horizontal or vertical configuration capabilities 21" depth for easier attic access DecaBDE-free thermoplastic drain pan

with secondary drain connections Screw-less sides and back helps to reduce

condensation when installed in humid locations Foil-faced insulation covers the internal

casing to reduce cabinet condensation Galvanized, leather grain-embossed finish Glue-less cabinet insulation retention Tool-less filter access

2 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 3

Nomenclature

A V P E C 25 B 1 4 AA

1 2 3 4 5 6,7 8 9 10 11,12

Brand Engineering*

A Single-Piece Air Handler Major/Minor Revisions

*Not used for inventory management

Unit Application Refrigerant Charge

R Multi Position PSC Motor 4 = R-410A

S Multi Position EEM Motor

V Multi Position Variable-Speed Electrical

Motor - Communicating 1 208/230V, 1 Phase, 60 Hz

Cabinet Finish Cabinet Width

U Unpainted B = 17"

P Painted C = 21"

D = 24"

Expansion Device

E Electronic Expansion Valve Nominal Capacity @ 13 SEER

T Expansion Device 24 = 2 Tons 31 = 2 Tons 48 = 4 Tons

V Inverter Tuned Expansion Valve 25 = 2 Tons 36 = 3 Tons 49 =3-3 Tons

29 = 2 Tons 37 = 3 Tons 59 = 4-5 Tons

Communicating 30 = 2 Tons 42 = 3 Tons 60 = 5 Tons

C = Yes 61 = 4-5 Tons

HKS X 03 X A AA

1 2 3 4 5 6,7

Unit Type Revisions

HKS Heat Kit for Engineering Revisions Air Handlers

Phase

Circuit Breaker A Single Phase 208 V E Three Phase 240 V

X No circuit breaker B Single Phase 240 V F Three Phase 208/240 V

C Circuit Breaker C Single Phase 208/240 V G Three Phase 460 V

D Three Phase 208 V

Heating Capacity @ 240 Volts H Special case 208 V*

03 3.0 kW 15 14.4 kW Cabinet Size (MAX)

05 4.5 kW 19 19.2 kW wth 150F limit C C Cabinet

06 6.0 kW 20 19.2 kW with 170F limit D D Cabinet

08 8.0 kW 25 25.0 kW X All Cabinet Sizes

10 9.6 kW

*Refer S&R Plate

2 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 3

Product Specifications

AVPEC25 B14A*

AVPEC37 C14A*

AVPEC59 D14A*

AVPEC61 D14A*

Nominal Ratings

Cooling (BTU/h) 24,000 36,000 48,000 60,000

CFM (High range) 1200/600 1700/800 1800/1350 2000/1600

Blower

Diameter 10" 10" 11" 11"

Width 6" 10" 10" 10"

Coil Drain Connection FPT " " " "

Service Valve

Liquid " " " "

Suction " " " "

Electrical Data

Voltage 208/240 208/240 208/240 208/240

Electric Heat Capacity (kW) 3, 5, 6, 8, 10 5, 6, 8, 10, 15, 19 5, 6, 8, 10, 15, 20 5, 6, 8, 10, 15, 20, 25

Min Circuit Ampacity 4.9/4.9 6.5/6.5 8.6/8.6 8.6/8.6

Max. Overcurrent Device (Amps) 15/15 15/15 15/15 15/15

Minimum VAC 197 197 197 197

Maximum VAC 253 253 253 253

Blower Motor

Full Load Amps (FLA) 3.9 5.2 6.9 6.9

Horsepower (HP) 1 1

Ship Weight (lbs.) 128 150 160 177 Note: Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental

heat installed. Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed.

4 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 5

Dimensions

AVPEC _D

IM EN

SIO N

S

9 8 7 6 5 4 3 2 1

9 8 7 6 5 4 3 2 1

F

C

D

E

B

A

F

C

D

E

B

SC

CC

1-13/16" (4.60 cm) 1-13/16" (4.60 cm)F INLET

(FRONT VIEW)

H

G

E

D

2-11/16" (6.83 cm)

1-11/16" (4.29 cm)

10-3/32" (25.88 cm)

5/8" (1.59 cm) 5/8" (1.59 cm)B

C

K J

1-15/16" (4.92 cm)

3-11/16" (9.37 cm)

7-1/8" (18.1 cm)

1" (25.4 cm) 17/3219.5" (49.53 cm) INLET

(RIGHT SIDE VIEW)

A

1-25/32" (4.52 cm)

1-13/32" (3.57 cm)

3-1/16" (7.78 cm)

5-5/32" (13.10 cm)

7-17/32" (19.13 cm)

9-5/32" (23.26 cm) 11-7/32" (28.50 cm)

21/32 (1.67 cm)

21" (55.88 cm)

1-23/32" (4.13 cm)

1-1/2" (11.43 cm)

1-11/32" (3.33 cm)

1-5/8" (4.13 cm)

2-31/32" (7.46 cm) 3-1/32" (7.70 cm)

3-25/32" (9.60 cm)

SCALE: NTS

SHEET: 1 OF 1

DWG. NO. AVPEC_DIMENSIONS

SPECIAL CHARACTERISTICS: (REFER MSP 822-01 FOR DETAILS) = CRITICAL CHARACTERISTIC REQUIRES AN INITIAL CPK OF 1.33 AND USE OF STATISTICAL PROCESS CONTROL.

= SIGNIFICANT CHARACTERISTIC REQUIRES AN INITIAL CPK OF 1.00 AND USE OF STATISTICAL PROCESS CONTROL. INABILITY TO MEET THE REQUIRED INITIAL CPK VALUE WILL REQUIRE 100% INSPECTION. CONFIDENTIAL PROPERTY OF GOODMAN MANUFACTURING COMPANY, L.P. OR ITS AFFILIATES NOT TO BE DISCLOSED TO

OTHERS, COPIED, OR USED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING. MUST BE RETURNED UPON DEMAD, ON COMPLETION OF ORDER, OR OTHER PURPOSE FOR WHICH IT WAS LENT

VERTICAL DRAIN PORT DEATIL

SEE VERTICAL DRAIN PORT DETAIL

SEE HORIZONTAL DRAIN PORT DETAIL

SUCTION TUBE LIQUID LINE

INLET TUBE

HORIZANTAL DRAIN PORT DEATIL

Model A B C D E F G H

AVPEC25B14 53 16 17 20 21 14 9 7

AVPEC37C14 53 19 21 21 18 17 10 6

AVPEC59D14 53 23 24 21 18 21 12 6

AVPEC61D14 58 23 24 26 22 21 12 25

4 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 5

Airflow Data

Model Stage Airflow CFM

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

AVPEC25B14A* High 700 690 690 685 680 670 665 660 655

Low 520 505 495 490 470 455 445 435 425

AVPEC37C14A* High 1190 1170 1165 1160 1145 1130 1120 1105 1100

Low 820 810 795 785 765 740 730 720 710

AVPEC59D14A* High 1445 1440 1430 1415 1405 1390 1380 1375 1370

Low 880 875 870 870 860 845 840 835 830

AVPEC61D14A* High 1645 1640 1640 1635 1630 1625 1620 1620 1615

Low 1080 1075 1070 1070 1060 1055 1050 1050 1045

Note: During cooling operation outdoor will determine the indoor airflow

Cooling/Heat Pump Airflow table

Model Airflow Level CFM

AVPEC25B14A* High 690

Low 495

AVPEC37C14A* High 1165

Low 795

AVPEC59D14A* High 1430

Low 870

AVPEC61D14A* High 1640

Low 1070

6 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 7

Heat Kit Data

See notes on page 7.

Model Circuit 1 Circuit 2 Single-Point Kit

Amps MCA MOP Amps MCA MOP MCA MOP

AVPEC25B14AC 0.0/0.0 4.9/4.9 15/15 --- --- --- --- ---

HKSX03XC - 208 V

No Breaker

10.8 18 20 --- --- --- --- ---

HKSX05XC - 208 V 17.3 27 30 --- --- --- --- ---

HKSX06XC - 208 V 21.7 32 35 --- --- --- --- ---

HKSX08XC - 208 V 28.9 41 45 --- --- --- --- ---

HKSX10XC - 208 V 34.7 48 50 --- --- --- --- ---

HKSC05XC - 208 V

Breaker

17.3 27 30 --- --- --- --- ---

HKSC08XC - 208 V 28.9 41 45 --- --- --- --- ---

HKSC10XC - 208 V 34.7 48 50 --- --- --- --- ---

HKSX03XC - 240 V

No Breaker

12.5 21 25 --- --- --- --- ---

HKSX05XC - 240 V 20 30 30 --- --- --- --- ---

HKSX06XC - 240 V 25 36 40 --- --- --- --- ---

HKSX08XC - 240 V 33.3 47 50 --- --- --- --- ---

HKSX10XC - 240 V 40 55 60 --- --- --- --- ---

HKSC05XC - 240 V

Breaker

20 30 30 --- --- --- --- ---

HKSC08XC - 240 V 33.3 47 50 --- --- --- --- ---

HKSC10XC - 240 V 40 55 60 --- --- --- --- ---

AVPEC37C14AC 0/0 6.5/6.5 15/15 --- --- --- --- ---

HKSX05XC - 208 V

No Breaker

17.3 28 30 --- --- --- --- ---

HKSX06XC - 208 V 21.7 34 35 --- --- --- --- ---

HKSX08XC - 208 V 28.9 43 45 --- --- --- --- ---

HKSX10XC - 208 V 34.7 50 50 --- --- --- --- ---

HKSC05XC - 208 V

Breaker

17.3 28 30 --- --- --- --- ---

HKSC08XC - 208 V 28.9 43 45 --- --- --- --- ---

HKSC10XC - 208 V 34.7 50 50 --- --- --- --- ---

HKSC15XA - 208 V 34.7 49.8 50 17.3 21.7 25 71.5 80

HKSC19CA - 208 V 34.7 49.8 50 34.7 43.3 45 93.2 100

HKSC15XF - 208 V ^ 0 6.5 15 30 38 40 --- ---

HKSX05XC - 240 V

No Breaker

20 32 35 --- --- --- --- ---

HKSX06XC - 240 V 25 38 40 --- --- --- --- ---

HKSX08XC - 240 V 33.3 48 50 --- --- --- --- ---

HKSX10XC - 240 V 40 57 60 --- --- --- --- ---

HKSC05XC - 240 V

Breaker

20 32 35 --- --- --- --- ---

HKSC08XC - 240 V 33.3 48 50 --- --- --- --- ---

HKSC10XC - 240 V 40 57 60 --- --- --- --- ---

HKSC15XB - 240 V 40 56.5 60 20 25 25 81.5 90

HKSC19CB - 240 V 40 56.5 60 40 50 50 107 110

HKSC15XF - 240 V ^ 0 6.5 15 34.6 43 45 --- ---

AVPEC59D14AC 0/0 8.6/8.6 15/15 --- --- --- --- ---

HKSX05XC - 208 V

No Breaker

17.3 30.3 35 --- --- --- --- ---

HKSX06XC - 208 V 21.7 36 40 --- --- --- --- ---

HKSX08XC - 208 V 28.9 45 45 --- --- --- --- ---

HKSX10XC - 208 V 34.7 52 60 --- --- --- --- ---

6 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 7

Heat Kit Data (cont.)

Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25 Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps 3 Notation is correct as XB because technically the 240V heater kit application can be used here

without any issues. ^ Three-phase Heater Kits (Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for Heater Kits) --- indicates Not Required Note: The 208 or 240 in the heat kit part number field is for clarification of the nominal voltage for this model.

Model Circuit 1 Circuit 2 Single-Point Kit

Amps MCA MOP Amps MCA MOP MCA MOP

HKSC05XC - 208 V

Breaker

17.3 30.3 35 --- --- --- --- ---

HKSC08XC - 208 V 28.9 45 45 --- --- --- --- ---

HKSC10XC - 208 V 34.7 52 60 --- --- --- --- ---

HKSC15XB 3 - 208 V 34.7 52 60 17.3 21.7 25 74 80

HKSC20DH - 208 V 34.7 52 60 34.7 43.3 45 95.3 100

HKSC15XF - 208 V ^ 0 8.6 15 30 38 40 --- ---

HKSX05XC - 240 V

No Breaker

20 34 35 --- --- --- --- ---

HKSX06XC - 240 V 25 40 40 --- --- --- --- ---

HKSX08XC - 240 V 33.3 50.3 60 --- --- --- --- ---

HKSX10XC - 240 V 40 59 60 --- --- --- --- ---

HKSC05XC - 240 V

Breaker

20 34 35 --- --- --- --- ---

HKSC08XC - 240 V 33.3 50.3 60 --- --- --- --- ---

HKSC10XC - 240 V 40 59 60 --- --- --- --- ---

HKSC15XB - 240 V 40 58.6 60 20 25 25 83.6 90

HKSC20DB - 240 V 40 58.6 60 40 50 50 109 110

HKSC15XF - 240 V ^ 0 8.6 15 34.6 43 45 --- ---

AVPEC61D14AC 0/0 8.6/8.6 15/15 --- --- --- --- ---

HKSX05XC - 208 V

No Breaker

17.3 30 35 --- --- --- --- ---

HKSX06XC - 208 V 21.7 36 40 --- --- --- --- ---

HKSX08XC - 208 V 28.9 45 45 --- --- --- --- ---

HKSX10XC - 208 V 34.7 52 60 --- --- --- --- ---

HKSC05XC - 208 V

Breaker

17.3 30 35 --- --- --- --- ---

HKSC08XC - 208 V 28.9 45 45 --- --- --- --- ---

HKSC10XC - 208 V 34.7 52 60 --- --- --- --- ---

HKSC15XB 3 - 208 V 34.7 52 60 17.3 21.7 25 73.6 80

HKSC20DH - 208 V 34.7 52 60 34.7 43.3 45 95.3 100

HKSC25DA - 208 V 52 73.6 80 35 43.3 45 117 125

HKSC15XF - 208 V ^ 0 8.6 15 30 38 40 --- ---

HKSC20XF - 208 V ^ 0 8.6 15 38 47 50 --- ---

HKSX05XC - 240 V

No Breaker

20 34 35 --- --- --- --- ---

HKSX06XC - 240 V 25 40 40 --- --- --- --- ---

HKSX08XC - 240 V 33.3 50.3 60 --- --- --- --- ---

HKSX10XC - 240 V 40 59 60 --- --- --- --- ---

HKSC05XC - 240 V

Breaker

20 34 35 --- --- --- --- ---

HKSC08XC - 240 V 33.3 50.3 60 --- --- --- --- ---

HKSC10XC - 240 V 40 59 60 --- --- --- --- ---

HKSC15XB - 240 V 40 58.6 60 20 25 25 83.6 90

HKSC20DB - 240 V 40 58.6 60 40.0 50 50 109 110

HKSC25DB - 240 V 60 83.6 90 40 50 50 134 150

HKSC15XF - 240 V ^ 0 8.6 15 34.6 43 45 --- ---

HKSC20XF - 240 V ^ 0 8.6 15 43.3 54 60 --- ---

Supply Voltage 240 230 220 210 208 Correction Factor 1.00 0.92 0.84 0.77 0.75

Multiply the 240-volt heating capacity by correction factors.

Heating kW Correction Factor

8 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 9

Wiring Diagram

0140A00723-C

HEATER KIT OUTPUT

43 65 987 10 11 12

BK RD

BK RD

BL

BR

WH

BL RD PU YL

RD BK

GROUND LUG (SEE NOTE 4)

24VAC

J19

INSTALLING AUX ALARM (ALARM) (SEE NOTE 8) ~~

~~

24VAC

COM COM 208 VAC

230 VAC

208 VAC 230

VAC

TR2 (SEE NOTE 1)

TR1 (SEE NOTE 1)

FAN MOTOR

21 BKRD GY BL

ECM MOTOR

BK RD

PL1 PL2

9 78 456 3 2 1

PL3 PL4

INTEGRATED CONTROL:

POWER/HEATER CONNECTOR

PL1, PL2

COMPONENT CODES:

TL

F1U, F2U TR

THERMAL LIMIT TRANSFORMER FUSE LINK

NOTES: 1. PLACE RED WIRES ON 208 V TERMINAL OF 2-TRANSFORMER (TR1/TR2) FOR 208 VAC OPERATION.

2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.

3. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105C. USE COPPER CONDUCTORS ONLY.

4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C ANDLOCAL CODES.

5. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS FAULT RECALL BUTTON FOR MORE THAN 2 SECONDS WHILE IN STANDBY (NO THERMOSTAT INPUTS)

6. YELLOW STATUS LED PROVIDES NETWORK STATUS.GREEN RX LED INDICATES NETWORK TRAFFIC

7. DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT.

8. REMOVE SHORTING PLATE FROM THE AUX SWITCH TERMINAL WHEN INSTALLING AUX ALARM SWITCH.

9. USE N.E.C CLASS 2 WIRE.

COLOR CODES:

BL - BLUE

RD - RED

YL - YELLOW

OR - ORANGE

BK - BLACK

GY - GREY

BR - BROWN

GR - GREEN

PU - PURPLE

WH - WHITE

LOW VOLTAGE

LOW VOLTAGE FIELD

HIGH VOLTAGE

HIGH VOLTAGE FIELD

JUNCTION

TERMINAL

INTERNAL TO

RESISTOR

OVERCURRENT PROT. DEVICE

PLUG CONNECTION

EQUIPMENT GND

FIELD GROUND

THERMISTOR (HEAT EXCHANGER 1,2)

M OR

INDOOR UNIT PCB

PRESSURE SENSOR

EEV COIL

EEV

INTEGRATION

GY RD YL

BK

AUX ALARM (ALARM)

GR

(SEE NOTE 7)

OUTDOOR UNIT

RD BK

BK RD

208/230 VACTO

HEATER KIT

TRANSFORMER CONNECTOR

PL3, PL4

BL

GRND

AIR

COM

W

C

208/230 VAC

CONDENSATE SWITCH

INDOOR

L1

HEAT 1 COIL/R1

TR2

INTEGRATED CONTROL MODULE

CIRCULATOR

+VDC (1)

GRND

BLWR

BLWR

EH2

L2

40 VA

R

TO MICRO

TH2

CIRCULATOR

L1

INDOOR

DEHUM GRND (4)

2 4 V T H E R M O S T A T C O N N E C T I O N S

RX (2)

24 VAC

AIR

AUX IN

FUSE 3 A

GRND

TX (3)

G

EH1

AUX OUT

TRANSFORMER

DISCONNECT

HEAT 2 COIL/ R2

L2

S E E

N O T E 9

TYPE

RD

J6 J7 J18

TH1 TR1

Y

J19 TB1 TB2

FH1 FH2F1U VR1

C1

D1

C2

D 2TB

7 TB

4

TB 3

TB 5

TB 6

FH3 F2U

FH4

V R

2

C 63

U 2

K3

K1

K2

U6

J6 J7

J20

PB1

PB2

PB3

J8 J9 J16 J17 J18

U9

J4

U1

J1 0

B11

B 12

U 4

U 10

C 89

J1 4

J1 1

U 5

U 3 L2

L1

J13

J1 5

J1 2

U7

+ _~~

U 8

C 5

R 14

6

C4C62

R 63

R 62

R 61 L4

J1 J2

L5 J5

J3

R13 R25

R 15

R 14

R 27

R 26

RCGWYDH/ Y2 RC 2 1

THERMOSTAT

YL GR GYBKW

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.

8 www.goodmanmfg.com SS-GAVPEC SS-GAVPEC www.goodmanmfg.com 9

Accessories

Filters

Chassis Part # Size

B ALFH16201E 16.0" x 20.0"

C ALFH1912201E 19.5 x 20.0

D ALFH20231E 23.0 x 20.0

Downflow Kits

DFK-B DFK-C DFK-D

AVPEC25B14** AVPEC37C14** AVPEC59D14**

AVPEC61D14**

** (DFK-B, DFK-C, DFK-D) kits need to be broken up by cabinet size

Single Point Kit **

Model HKR-15C HKR-20C HKR-21C

SPW-01 X X X

** Must be installed along with any of the above compatible heat kits. This kit will fit any AVPEC air handler as long as a compatible heat kit is installed in the unit.

Drain Port Plug

Kit Number Description Application

DPK1 Side Drain Port Plug All Models</

Manualsnet FAQs

If you want to find out how the AVPEC Goodman works, you can view and download the Goodman AVPEC User's Manual on the Manualsnet website.

Yes, we have the User's Manual for Goodman AVPEC as well as other Goodman manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The User's Manual should include all the details that are needed to use a Goodman AVPEC. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Goodman AVPEC User's Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Goodman AVPEC User's Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Goodman AVPEC User's Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Goodman AVPEC User's Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Goodman AVPEC User's Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.