Flir Extech 382357 Tester User Manual PDF

1 of 13
1 of 13

Summary of Content for Flir Extech 382357 Tester User Manual PDF

USER MANUAL 

Ground Resistance ClampOn Tester 

MODEL 382357 

382357EUEN V2.4   2/13 2

Introduction  Congratulations on your purchase of Extechs 382357 Ground Resistance Tester. This Clampon  device allows the user to measure ground resistance without the use of auxiliary ground rods.  This device can only be used on multigrounded systems. It is not necessary to disconnect the  ground under test. This meter is shipped fully tested and calibrated and, with proper use, will  provide years of reliable service. Please visit our website (www.extech.com) to check for the  latest version of this User Guide, Product Updates, and Customer Support. 

Safety 

Only qualified technicians should operate this meter. 

Use extreme caution when operating the meter near energized electrical equipment. 

Do not attempt to use this meter to twist or pry the ground electrode or ground wire away  from grounded equipment. 

All metal objects or wires connected to the electrical system under test should be assumed  to be lethal until tested. Grounded systems are no exception. 

Ensure that the batteries are inserted correctly in the battery compartment.  

Remove the batteries from the meter if the meter is to be stored for long periods. 

WARNING: If the meter is used in a manner not specified by the manufacturer, the built in  protections provided by the meter may be impaired. 

International Safety Symbols 

This symbol, adjacent to another symbol or terminal, indicates the user must  refer to the manual for further information. 

This symbol, adjacent to a terminal, indicates that, under normal use, hazardous  voltages may be present 

382357EUEN V2.4   2/13 3

Description 

1. Jaw Assembly 

2. Hold Button 

3. Rotary Selector Switch 

4. LCD Display 

5. Record Button 

6. (decrement) Button 

7. (increment) Button 

8. Function Button 

9. Measurement Trigger 

Display Symbols 

1. REC: Indicates data logging in progress 

2. NO. Indicates the READ function 

3.     :  Clamp jaws are not fully closed

4. NOISE: Excessive noise on the ground  conductor or rod 

5. ))): Hi Lo alarm position 

6. Function or Record display 

7. : Ohms (resistance measurement) 

8. mA: milliamperes, Amperes (current measurements) 

9. H:  Hold function activated 

10. Main display 

11.          : Low Battery 

12. Auto Power Off 

1

2

3

4

5

678

9

382357EUEN V2.4   2/13 4

Operation 

Note: Ensure that the jaws are fully closed before testing. 

Note: DO NOT clamp on to any conductor or open the clamp jaws during the startup self calibration (selfcal is identified by the LCD counting down from CAL7 to CAL1). 

Ground Resistance Measurements 

1. Open the clamp jaws and check that all surfaces are  clean and free of dust, dirt, or any foreign  substances. Clean if necessary. 

2. Forcefully snap the clamp jaws open and closed  several times. 

3. Turn the meter on by moving the rotary switch to  the ohms  position. DO NOT interrupt the start up  procedure by opening the clamp jaws or clamping  around a conductor. During selfcalibration, the  meter will display CAL5, CAL4, CAL3, CAL2 and  CAL1. 

4. Once the startup calibration procedure is completed, the meter will sound a beep. Clamp  on to an electrode or ground rod and read the value of ground resistance on the display. 

Ground / Leakage Current Measurement 

1. Turn the meter on by moving the rotary switch to the  mA or A position. 

2. Clamp on to the electrode or conductor 

3. Read the value of leakage current displayed on the  LCD. 

HOLD 

Press the HOLD button to freeze the reading in the display. H will appear in the display. Press  HOLD again to exit the function.  

382357EUEN V2.4   2/13 5

High and Low Alarm 

1. Turn the meter on by moving the rotary switch to the ))) position.

2. Press the FUNC button to view and adjust the HI alarm value.

3. Press  or the  button to increase or decrease the value. Hold down the button to  increase the speed of adjustment. The value can be incremented from 0 to 1500 ohms and  then OL (overload). The value will roll over to 0 after OL is displayed.

4. Once the desired value is set, press the FUNC button a second time to view and adjust the  LO alarm value.

5. Press the FUNC button three more times to exit the setting mode.

6. The meter will now compare the measured resistance value with the high and low limits 

when the meter is set to the ))) position. If the reading is larger than the HI value, the  meter will beep and display HI on the LCD. If the reading is lower than the LO value, the  meter will beep and display LO on the LCD.

Data Logging 

Setting the Sampling Time 

1. Press the FUNC button three times until the SEC symbol appears in the LCD display.

2. The sampling rate is now displayed in seconds.

3. Press the or the  button to increase or decrease the value. The value can be  incremented from 0 to 255 seconds.

4. Once the desired value is set, press the FUNC button several times until the characters in  the upper row of the LCD disappear.

Recording Data 

1. Press the REC button to start recording data at the specified sampling rate. The REC  symbol will appear on the top of the LCD display. To stop recording, press the REC button.  The REC symbol will no longer be displayed on the LCD.

NOTE: Data logging will automatically stop if the memory is filled (116 records), or if the meter  detects a low battery condition. 

NOTE: If the sampling interval is set to 0, only one sample will be recorded. To record another  sample, press REC again. 

382357EUEN V2.4   2/13 6

Recalling Stored Data 

1. Press the FUNC button four times until the NO. symbol is displayed on the LCD. The  current record number will be displayed in the top row and the data will be displayed below  it.

2. Press the  or the  button to step through and read the data in the next memory  location. Holding down the button will increase the speed of the incrementing value.

Clearing Data Memory 

1. With the meter powered off, press and hold down the REC button while turning the meter  on. The CL symbol will appear on the display indicating that memory has been cleared. 

382357EUEN V2.4   2/13 7

Measurement Principles 

Typical multigrounded distribution system 

If the parallel ground resistances,  R1, R2, R3,etc, up to Rn are combined  as Req, then only Rg and Req are   left in the circuit 

If a constant voltage is applied to the circuit, the following equation applies: 

eqg RR I

V           where:    ni

R

R

i

eq ,...2,1, 1

1

 

If Rg and R1, R2, R3Rn, are approximately the same, and n is large (200, for example), then Req  will be much less then Rg and may possibly approach zero.  

Example: 

If Rg and R1, R2, R3Rn are all 10 respectively and n = 200, then Req by calculation equals: 

05.0

10

1 ...

10

1

10

1 1

eqR  

geqg RRR I

V 05.1005.010  

V

I

Req

Rg

382357EUEN V2.4   2/13 8

Applications 

TelephoneElectrical Ground Rods 

1. Remove any protective covering from the ground conductor 

2. Turn the meter switch to the Ohm  function. 

3. Once the startup calibration procedure is completed clamp on to an electrode or ground  rod. 

4. Allow several seconds for the meter to settle and then note the reading. 

Cellular Transmission Towers 

WARNING: Use extreme care when making measurements around transmission towers; High  Voltage may be present. 

The ground conductor should be located at the base of the tower, but your configuration may  be different. 

1. Locate the ground conductor 

2. Clamp around the ground conductor. You should place the clamp before any splices, bonds  or other splits in the ground system. 

3. Read the measured reading. 

Transmission

Tower

Primary Ground Conductor

Branch Ground Conductors

Cement Pad

382357EUEN V2.4   2/13 9

Service Entrance 

Note: Multiple ground rods, multiple grounds i.e. ground rod(s) and water pipe grounds, or a  combination may be present depending on the particular situation. In these situations it is  necessary to make your measurements between the serviceentrance neutral and all  subsequent ground points. 

Troubleshooting 

1. Snap the jaws open and closed two or three times before turning the meter on 

2. Do not clamp on to any device during the powerup initialization sequence.  

3. Snap the jaws two or three times after clamping on to the ground electrode or rod. 

4. Slight amounts of drift may occur at high resistance measurements; this is normal and  should not be cause for concern. 

Blank display or any failure mode 

Replace the battery before proceeding. 

Startup Initialization Failure 

The startup calibration will continue indefinitely if the jaws are open or dirty. Check that the  jaws mating surfaces are clean. Do not open the jaws while the initialization sequence is  running. 

Noise on the Ground Electrode or Rod 

If noise is present (over 3A or 30V) on the ground electrode or rod, the word NOISE will  appear on the display and readings can no longer be considered accurate. Before the meter can  be used accurately, the noise problem must be addressed. 

Distribution Panel

Ground Rod

Water Pipe

382357EUEN V2.4   2/13 10

Reference Test Loop 

The reference test loop is a set of resistors that provides a means to check the performance of  the meter. 

1. Open the measurement jaws and check that the mating surfaces are clean and free of dust,  dirt, or any foreign substances. Clean if necessary. 

2. Clamp the meter around the reference loop as shown in the diagram. 

3. Give the meter a few seconds to settle and read the measurement. The meter should  display approximately the same value as marked on the reference loop, taking into  consideration the accuracy listed in the specification chart. If the readings are not similar to  what is marked on the reference loop, consult the Trouble Shooting and Maintenance  sections of this manual. 

382357EUEN V2.4   2/13 11

Maintenance 

General Care 

Store the ground resistance tester and reference loop in its case when not in use.  A damp  cloth may be used to clean any surface dirt from the meter. Never use harsh detergents,  abrasives, solvents, or cleaners on the meter.   

Battery Replacement 

When the low battery symbol appears on the display, replace the meters 9V battery.  Use a  high quality alkaline battery whenever replacement becomes necessary. 

1. Remove the two rear screws and open the meter housing. 

2. Replace the battery, close the meter housing, and affix the two rear screws. 

Never dispose of used batteries or rechargeable batteries in household waste.  As consumers, users are legally required to take used batteries to appropriate  collection sites, the retail store where the batteries were purchased, or wherever  batteries are sold. 

Disposal: Do not dispose of this instrument in household waste. The user is  obligated to take endoflife devices to a designated collection point for the disposal  of electrical and electronic equipment.    

Other Battery Safety Reminders 

o Never dispose of batteries in a fire. Batteries may explode or leak.

o Never mix battery types. Always install new batteries of the same type.

Clamp Jaw Maintenance 

The jaws may be brushed clean with a toothbrush or similar softbristled brush.  Care must be  taken to ensure that the contact fins are not bent or deformed, as this will affect the operation  of the meter. 

382357EUEN V2.4   2/13 12

Specifications 

General Specifications 

Resistance Test Frequency:   3.333 kHz (15mV rms approx.) 

Max Conductor size  23mm (0.9)

Display  4digit (9999 count) display 

Sampling rate  0.5 seconds 

Memory  116 records 

Datalogging sample rate  1 to 255 seconds 

Power supply  One (1) 9V battery 

Power consumption  40mADC 

Battery Life  3000 measurements 

Temp. Coefficient   0.15 times the specified accuracy per  oC from 4 to 18oC (39 to 

64F) and 28 to 50 oC (82 to 122F)

Current Overload   Protected to 100A Continuous; 200A for less than 5 seconds  (50/60Hz)

Range selection  Automatic ranging 

Safety  Meets the requirements for IEC10101 Category III 300V and  Category II 600 V 

Operating conditions  0  to 50oC (32 to 122oF) with < 85% RH

Storage conditions  20  to 60oC (4 to 140oF) with < 75% RH

Dimensions  257 x 100 x 47mm (10.1 x 3.9 x 1.9) 

Weight  1.4lbs (640g) 

Accessories  Resistance check plate, 9V battery, & carrying case 

382357EUEN V2.4   2/13 13

Ground Resistance (Autorange) Specifications 

Range  Resolution  Accuracy (of reading) 

0.025 to 0.250  0.002   (1.5% + 0.05 

0.250 to 1.000  0.02   (1.5% + 0.05

1.001 to 9.999  0.02   (1.5% + 0.1

10.00 to 50.00  0.04   (2.0% + 0.3

50.01 to 99.99  0.04   (2.0% + 0.5

100.0 to 200.0  0.4   (3.0% + 1.0

200.1 to 400.0  2   (5.0% + 5

400.0 to 600.0  5   (10% + 10

600.1 to 1500  20    20%

Accuracy Note: Loop resistance noninductive, external field < 50A/m, external electrical field  <1 V/m, conductor centered 

Ground / Leakage Current Specifications 

Range  Accuracy (% of reading) 

0.300 to 1.000mA   (2.0%  0.05mA) 

1.00 to 10.00mA   (2.0%  0.03mA)

10.0 to 100.0mA   (2.0%  0.3mA)

100 to 1000mA   (2.0%  0.3mA) 

Autoranging 

0.20 to 4.00A   (2.0%  0.03A) 

4.00 to 30.00A   (3.0%  0.03A) Manual range 

Notes: 50/60Hz bandwidth, True RMS sensing, Crest Factor < 3.0   

High and Low Alarm (programmable

Range  Resolution 

Manualsnet FAQs

If you want to find out how the Extech Flir works, you can view and download the Flir Extech 382357 Tester User Manual on the Manualsnet website.

Yes, we have the User Manual for Flir Extech as well as other Flir manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The User Manual should include all the details that are needed to use a Flir Extech. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Flir Extech 382357 Tester User Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Flir Extech 382357 Tester User Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Flir Extech 382357 Tester User Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Flir Extech 382357 Tester User Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Flir Extech 382357 Tester User Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.