USER MANUAL
FLIR MODEL TA72 and TA74 UNIVERSAL FLEX CURRENT PROBE ACCESSORIES
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 2
Table of Contents
1. DISCLAIMERS 3
1.1 Copyright 3
1.2 Quality Assurance 3
1.3 Documentation 3
1.4 Disposal of Electronic Waste 3
2. SAFETY 4
3. INTRODUCTION 6
3.1 Key Features 6
4. DESCRIPTIONS 7
4.1 Meter Description 7
4.2 Control buttons and Indicators 8
5. OPERATION 9
5.1 Powering the Meter 9
5.2 Work Lights 9
5.3 AC Current Measurements 10
6. MAINTENANCE 13
6.1 Cleaning and Storage 13
6.2 Battery Replacement 13
7. SPECIFICATIONS 14
7.1 General specifications 14
7.2 AC Current Electrical specifications 15
8. TECHNICAL SUPPORT 16
9. WARRANTY 16
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 3
1. Disclaimers
1.1 Copyright
20152016, FLIR Systems, Inc. All rights reserved worldwide. No parts of the software including source code may be reproduced, transmitted, transcribed or translated into any language or computer language in any form or by any means, electronic, magnetic, optical, manual or otherwise, without the prior written permission of FLIR Systems.
The documentation must not, in whole or part, be copied, photocopied, reproduced, translated or transmitted to any electronic medium or machine readable form without prior consent, in writing, from FLIR Systems.
Names and marks appearing on the products herein are either registered trademarks or trademarks of FLIR Systems and/or its subsidiaries. All other trademarks, trade names or company names referenced herein are used for identification only and are the property of their respective owners.
1.2 Quality Assurance
The Quality Management System under which these products are developed and manufactured has been certified in accordance with the ISO 9001 standard.
FLIR Systems is committed to a policy of continuous development; therefore we reserve the right to make changes and improvements on any of the products without prior notice.
1.3 Documentation
To access the user manuals, extended warranty registration and notifications go to the Download tab at: http://support.flir.com. In the download area you will also find the latest releases of manuals for our other products, as well as manuals for our historical and obsolete products. The extended warranty page can also be found at www.Flir.com/testwarranty.
1.4 Disposal of Electronic Waste
As with most electronic products, this equipment must be disposed of in an environmentally friendly way, and in accordance with existing regulations for electronic waste.
Please contact your FLIR Systems representative for more details.
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 4
2. Safety
Safety Notes
Before operating the device, you must read, understand, and follow all instructions, dangers,
warnings, cautions, and notes.
FLIR Systems reserves the right to discontinue models, parts or accessories, and other items,
or to change specifications at any time without prior notice.
Remove the batteries if the device is not used for an extended period of time.
Warning Statements
To ensure the safe operation and service of the meter, follow these instructions closely. Failure to observe warnings can result in severe injury.
WARNINGS identify hazardous conditions and actions that could cause BODILY HARM or DEATH.
Individual protective equipment should be used if HAZARDOUS LIVE parts in the installation where measurements are to be carried out could be accessible.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Always use proper terminals, switch position, and range for measurements.
To reduce the risk of fire or electric shock, do not expose this product to rain or moisture.
Verify the meter operation by measuring a known current. If in doubt, have the meter serviced.
Do not apply more than the rated voltage/current as marked on the meter.
To avoid false readings that can lead to electric shock and injury, replace battery as soon as the low battery indicator appears.
Do not use the meter in or around explosive gas or vapor.
Do not use a flexible current sensor if the inner copper wire of the flexible cord is visible.
Deenergize the installation under test or wear suitable protective clothing when placing or removing the flexible current probe from a test setup.
Do not apply/remove the flexible current probe to/from UNINSULATED HAZARDOUS LIVE conductors which may cause electric shock, electric burn, or arc flash.
Agency Approvals:
MSIP-REI-FS5-TA74
UL listing is not an indication or a verification of the accuracy of the meter
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 5
CAUTIONS
CAUTIONS identify conditions and actions that could cause DAMAGE to the meter or equipment under test. Do not expose the meter to extremes in temperature or high humidity.
Safety Symbols that are typically marked on meters and instructions
This symbol, adjacent to another symbol, indicates the user must refer to the manual for further information.
Do not apply or remove clamp from HAZARDOUS LIVE conductors
Equipment protected by double or reinforced insulation
Battery symbol
Conforms to EU directives
Do not discard this product in household trash.
AC measurement
Earth ground
PER IEC1010 OVERVOLTAGE INSTALLATION CATEGORY
OVERVOLTAGE CATEGORY I Equipment of OVERVOLTAGE CATEGORY I is equipment for connection to circuits in which measures are taken to limit the transient overvoltages to an appropriate low level. Note Examples include protected electronic circuits.
OVERVOLTAGE CATEGORY II Equipment of OVERVOLTAGE CATEGORY II is energyconsuming equipment to be supplied from the fixed installation. Note Examples include household, office, and laboratory appliances.
OVERVOLTAGE CATEGORY III Equipment of OVERVOLTAGE CATEGORY III is equipment in fixed installations. Note Examples include switches in the fixed installation and some equipment for industrial use with permanent connection to the fixed installation.
OVERVOLTAGE CATEGORY IV Equipment of OVERVOLTAGE CATEGORY IV is for use at the origin of the installation. Note Examples include electricity meters and primary overcurrent protection equipment
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 6
3. Introduction Thank you for choosing the FLIR TA72 or TA7 4 UNIVERSAL FLEX CURRENT PROBE ACCESSORY that can measure up to 3000A AC. A standard Digital MultiMeter (DMM) in VAC mode can be used to display the current measurement when the current probe is connected to the DMM.
The TA74 is the 18 (45.7cm) clamp version and the TA72 is the 10 (25.4cm) clamp version, otherwise both meters are the same. These devices are professional CAT IV 600V CAT III 1000V instruments with high power Work Lights. This meter is shipped fully tested and calibrated and, with proper use, will provide years of reliable service.
3.1 Key Features
3000A AC Current Measurements displayed on connected DMM
Convenient Flexible Clamp with locking mechanism
0.3 (7.5mm) coil diameter for measuring in tight spaces
Supplied banana plug cables
Power button
Battery status LED indicator
Current AC Range select switch 30A, 300A, 3000A
Battery powered
High power work lights
Register for Extended Warranty www.Flir.com/testwarranty
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 7
Fig. 41 Description
1
2 3
4
5
6 7
8
9
4. Descriptions
4.1 Meter Description
1. Flexible Current Clamp Coil
2. Work Lights
3. Coil tip (inserts into lock mechanism)
4. Clamp lock mechanism
5. Range indicators
6. RANGE select button
7. Power and Work Lights button
8. Test lead cable connection
9. Test leads connect to DMM
Note that battery compartment is located on the back of the meter
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 8
4.2 Control buttons and Indicators
Momentary presses step through the ranges manually
When powered, press to activate/deactivate work lights
Press and hold to switch power ON/OFF
Illuminates when the 30A ranges is selected
Illuminates when the 300A ranges is selected
Illuminates when the 3000A ranges is selected
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 9
5. Operation Note: Before operating the device, please read and understand all Warning and Caution statements and follow all instructions and notes.
Note: Models TA72 and TA74 are not designed for use with VFD (Variable Frequency Drive) equipment, as erroneous readings may result. Using with VFD equipment does not pose a safety hazard to personnel and will not damage equipment. Please contact FLIR for additional information.
5.1 Powering the Meter
The meter is powered by two (2) AAA 1.5V batteries (located in the compartment on the back of the meter). Press and hold the Power button for > 2 seconds to switch the device ON or OFF.
The meter will beep as it switches ON and one of the Range indicator lamps will be lit. Use the Range button to select a range manually.
If the meter does not switch ON please check the batteries located in the rear battery compartment. Refer to the battery replacement section of this User Guide.
5.1.1 Auto Power OFF (APO)
The meter switches OFF automatically after an approximately 10minute period of inactivity. Several seconds before the meter automatically switches OFF the meter beeps several times to alert the user.
To disable the APO feature, press both the RANGE and POWER buttons simultaneously (with the meter OFF). The three range indicator LEDs will flash three times. To reenable APO, turn the meter OFF then ON.
The meter reenables APO each time the meter is powered OFF.
5.2 Work Lights
With the unit powered up, press the Work Light button to switch the high power Work Lights
ON or OFF. Note that excessive use of the Work Lights will shorten battery life.
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 10
V AC
Fig. 51 Connect to DMM
1
2
Fig. 52 Clamp Jaw Lock
5.3 AC Current Measurements
WARNING: Ensure that power to the device under test is OFF before starting this procedure. Switch power to the device under test ON only after the clamp has been safely attached to the device under test.
CAUTION: Do not move fingers above the range lamps at any time during a test.
Note: Models TA72 and TA74 are not designed for use with VFD (Variable Frequency Drive) equipment, as erroneous readings may result. Using with VFD equipment does not pose a safety hazard to personnel and will not damage equipment. Please contact FLIR for additional information.
1. Switch OFF the Clamp Adaptor, the DMM, and
the device under test.
2. Connect the Clamp Adaptor to the DMM input
jacks using the supplied banana plugs (Fig. 51).
3. Switch ON the DMM and set the DMM to the AC
V mode.
4. Use the RANGE button to set the measurement
range of the Clamp Adaptor to the expected
current range measurement.
5. Turn the clamp lock (1) counterclockwise to release the
clamp (2). See Fig. 52.
6. Fully enclose the conductor under test with the flexible
clamp probe (see Fig. 53). Do not measure current higher
than the specified current limit.
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 11
Fig. 53 Clamp around one conductor
7. Attach the flexible clamp coil tip (2) to the lock (1) and lock it in place by turning the clamp
lock clockwise. See Fig. 52.
8. Switch the Clamp Adaptor ON (press and hold the Power button) and then switch the
device under test ON. Never move fingers higher than the range indicator lights when
testing. Keep hands and fingers away from the clamp coil while testing.
9. Read the current value in the DMM display. Refer to Sections 5.3.1 to 5.3.3 for tips on
determining the magnitude of current measured by the TA7x based on the DMM reading.
10. Remove power to the device under test before removing the Clamp connection.
5.3.1 Manual Range Selection For the best results, with regard to output signal, select the correct range using the RANGE button, according to expected current measurement. See Table below:
Range Selection Best Performance
30A (100mV/1A) 30.00A max.
300A (10mv/1A) 30.0 to 300.0 A
3000A (1mV/1A) 300.0 to 3000A
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 12
5.3.2 DMM Reading Multiplier Table The Table below uses FLIR DM93 and CM83 DMMs as examples; However, most standard DMMs set to the AC Voltage mode will respond similarly.
Note: Do not set the DMM to VFD mode when testing.
TA7x Range1
Current Measured by TA7x
in Amperes (A)
DMM Displayed Readings
Multiplier2 FLIR DM93 V AC mode
FLIR CM83 V AC mode
30A
5.0 0.500 0.50 Current = 10 x LCD
reading 15.0 1.500 1.50
25.0 2.500 2.50
300A
55.0 0.550 0.55 Current = 100 x LCD reading
150.0 1.500 1.50
250.0 2.500 2.50
3000A
500.0 0.500 0.50 Current = 1000 x LCD reading
1500A 1.500 1.50
2500A 2.500 2.50 1 Range is determined by the lit LED lamp on the TA7x
2 Multiplier used to determine current measured, based on DMM reading (with DMM in ACV mode)
5.3.3 Measurement Examples
Example 1: 30A Current Measurement
With the DMM set to the AC voltage mode:
Clamp set to the 30A range: the clamp output will be 3000mV (3.0 VAC)
DMM will display 3.000 in the V AC mode (x10 = 30A)
Clamp set to the 300A range: the clamp output will be 300mV (0.3VAC)
DMM will display 0.300 in the V AC mode (x100 = 30A)
Example 2: 60A Current Measurement
With the DMM set to the AC Voltage mode:
Clamp set to the 300A range: the clamp output will be 600mV (0.6VAC);
DMM will display 0.600 in the V AC mode (x100 = 60A)
Clamp set to the 3000A range: the clamp output will be 60mV (0.06VAC)
DMM will display 0.060 in the V AC mode (x1000 = 60A)
Example 3: 600A Current Measurement
With the DMM set to the AC Voltage mode:
Clamp set to the 300A range: the clamp output will reach 4500mV (4.5 VAC); this is an over range (overload) condition. Select the higher 3000A range: the clamp output will be 600mV (0.6VAC); DMM will display 0.600 in the V AC mode (x1000 = 600A)
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 13
6. Maintenance
6.1 Cleaning and Storage
Clean the meter with a damp cloth and mild detergent; do not use abrasives or solvents.
If the meter is not to be used for an extended period, remove the batteries and store them separately.
6.2 Battery Replacement
CAUTION: Disconnect the meter from the conductor under test and switch the meter OFF before opening the battery compartment.
1. Remove the battery compartment Phillips head screw from the back of the meter.
2. Remove the battery compartment cover.
3. Replace the 2 AAA 1.5V batteries observing correct polarity.
4. Reattach the battery compartment cover.
5. Secure the compartment cover with the Phillips head screw.
6.2.1 Disposal of Electronic Waste As with most electronic products, this equipment must be disposed of in an environmentally friendly way, and in accordance with existing regulations for electronic waste.
Please contact your FLIR Systems representative for more details.
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 14
7. Specifications
7.1 General specifications
Clamp Jaw Flexible type with locking mechanism
Coil diameter 0.3 (7.5mm); Coil tip (item 3 in Fig. 41): 0.5 (13mm)
Bend radius 1.5 (38mm) for TA72 and 3.1 (80mm) for TA74
Flexible Conductor length 10 (25.4 cm) for TA72 and 18 (45.7cm) for TA74
Work lights Two White LEDs
AC bandwidth 45 to 500Hz (sine wave)
Measurement rate 1.5 samples per second, nominal
Operating Temperature 32~122F (0~50C)
Operating Humidity Max 80% up to 95F (35C) decreasing linearly to 60% at 113F (45C)
Storage Temperature 4~140F (20~60C) without batteries
Storage Humidity 80% RH maximum
Temperature Coefficient 0.2 x specified accuracy / C, < 64.5F (18C), > 82.4F (28C)
Altitude Maximum operating altitude 6562 (2000m)
Battery Two AAA 1.5V batteries
Battery life 160 hours with alkaline batteries
Auto Power OFF (APO) After 10 minutes of inactivity with disable
Dimensions (W x H x D) TA72: 4.7 x 11.0 x 1.0 (120 x 280 x 25 mm)
TA74: 5.1 x 13.8 x 1.0 (130 x 350 x 25 mm)
Weight TA72: 6.0 oz. (170g) with batteries
TA74: 7.1 oz. (200g) with batteries
Drop test 9.8 ft. (3m)
Agency Approvals UL, CE, RCM, and KC
Safety Standards IP54
For indoor use and in accordance with the requirements for double insulation to EN610101, EN610102032, EN613261; CAT IV 600V, CAT III 1000V, Pollution Degree 2
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 15
7.2 AC Current Electrical specifications
Function Range Output Voltage Accuracy
AC Current
30.00 A AC 100mV/1A AC (3.0% of Full Scale)
for frequency range: 45~500Hz 300.0A AC 10mV/1A AC
3000 A AC 1mV/1A AC
Notes:
Accuracy is given as (% of reading + least significant counts) at 73.4F 9F (23C 5C) with relative humidity lower than 80%. Accuracy is specified for a period of one year after calibration.
Max. Output Voltage: 4.5V peak
Output Noise: < 5mV for each range
Position Error of Clamp: Accuracy and position error assumes centralized primary conductor at optimum position (center of clamp jaw), no external electrical or magnetic field, and within operating temperature range.
Distance from optimum position
TA72 TA72 Error TA74 TA74 Error Position*
0.6 (15mm) 2.0% 1.4 (35mm) 1.0% A
1.0 (25mm) 2.5% 2.0 (50mm) 1.5% B
1.4 (35mm) 3.0% 2.4 (60mm) 2.0% C
*See position examples in diagram below:
A B C
Fig. 71 Positioning Conductor in Clamp Jaw center
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 16
8. Technical Support
Main Website http://www.flir.com/test
Technical Support Website http://support.flir.com
Technical support Email TMSupport@flir.com
Service/Repair Support Email Repair@flir.com
Support Telephone number +1 8554993662 option 3 (tollfree)
9. Warranty
9.1 FLIR Global Limited Lifetime Warranty A qualifying FLIR Test and Measurement product (the Product) purchased either directly from FLIR Commercial Systems Inc and affiliates (FLIR) or from an authorized FLIR distributor or reseller that Purchaser registers online with FLIR is eligible for coverage under FLIRs Limited Lifetime Warranty, subject to the terms and conditions in this document. This warranty only applies to purchases of Qualifying Products (see below) purchased and manufactured after April 1, 2013.
PLEASE READ THIS DOCUMENT CAREFULLY; IT CONTAINS IMPORTANT INFORMATION ABOUT THE PRODUCTS THAT QUALIFY FOR COVERAGE UNDER THE LIMITED LIFETIME WARRANTY, PURCHASERS OBLIGATIONS, HOW TO ACTIVATE THE WARRANTY, WARRANTY COVERAGE, AND OTHER IMPORTANT TERMS, CONDITIONS, EXCLUSIONS AND DISCLAIMERS.
1. PRODUCT REGISTRATION. To qualify for FLIRs Limited Lifetime Warranty, Purchaser must fully register the Product directly with FLIR online at http://www.flir.com within Sixty (60) DAYS of the date the Product was purchased by the first retail customer (the Purchase Date). Qualifying PRODUCTS THAT ARE NOT REGISTERED ONLINE WITHIN SIXTY (60) DAYS OF THE PURCHASE DATE WILL HAVE A LIMITED ONE YEAR WARRANTY FROM DATE OF PURCHASE.
2. QUALIFYING PRODUCTS. Upon registration, Test and Measurement products that qualify for coverage under FLIRs Limited Lifetime Warranty are: CM7x, CM8x, DMxx, MR7x, TA7x, VP5x not including accessories which may have their own warranty.
3. WARRANTY PERIODS. For purposes of the The Limited Lifetime Warranty, Lifetime is defined as seven years (7) after the product is no longer manufactured, or ten years (10) from date of purchase, whichever is greater. This Warranty is only applicable to the original owner of the Products.
Any Product that is repaired or replaced under warranty is covered under this Limited Lifetime Warranty for one hundred eighty days (180) days from the date of return shipment by FLIR or for the remaining duration of the applicable Warranty Period, whichever is longer.
4. LIMITED WARRANTY. In accordance with the terms and conditions of this Limited Lifetime Warranty, and except as excluded or disclaimed in this document, FLIR warrants, from the Purchase Date, that all fully registered Products will conform to FLIRs published Product specifications and be free from defects in materials and workmanship during the applicable Warranty Period. PURCHASERS SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY, AT FLIRS SOLE DISCRETION, IS THE REPAIR OR REPLACEMENT OF DEFECTIVE PRODUCTS IN A MANNER, AND BY A SERVICE CENTER, AUTHORIZED BY FLIR. IF THIS REMEDY IS ADJUDICATED TO BE INSUFFICIENT, FLIR SHALL REFUND PURCHASERS PAID PURCHASE PRICE AND HAVE NO OTHER OBLIGATION OR LIABILITY TO BUYER WHATSOEVER.
5. WARRANTY EXCLUSIONS AND DISCLAIMERS. FLIR MAKES NO OTHER WARRANTY OF ANY KIND WITH RESPECT TO THE PRODUCTS. ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE (EVEN IF PURCHASER HAS NOTIFIED FLIR OF ITS INTENDED USE FOR THE PRODUCTS), AND NONINFRINGEMENT ARE EXPRESSLY EXCLUDED FROM THIS AGREEMENT.
FLIR TA72_TA74 USER MANUAL Document Identifier: TA72_TA74 enUS_AC 17
THIS WARRANTY EXPRESSLY EXCLUDES ROUTINE PRODUCT MAINTENANCE, SOFTWARE UPDATES, AND REPLACEMENT OF MANUALS, FUSES, OR DISPOSABLE BATTERIES. FLIR FURTHER EXPRESSLY DISCLAIMS ANY WARRANTY COVERAGE WHERE THE ALLEGED NONCONFORMITY IS DUE TO NORMAL WEAR AND TEAR, OTHER ALTERATION, MODIFICATION, REPAIR, ATTEMPTED REPAIR, IMPROPER USE, IMPROPER MAINTENANCE, NEGLECT, ABUSE, IMPROPER STORAGE, FAILURE TO FOLLOW ANY PRODUCT INSTRUCTIONS, DAMAGE (WHETHER CAUSED BY ACCIDENT OR OTHERWISE), OR ANY OTHER IMPROPER CARE OR HANDING OF THE PRODUCTS CAUSED BY ANYONE OTHER THAN FLIR OR FLIRS EXPRESSLY AUTHORIZED DESIGNEE.
THIS DOCUMENT CONTAINS THE ENTIRE WARRANTY AGREEMENT BETWEEN PURCHASER AND FLIR AND SUPERSEDES ALL PRIOR WARRANTY NEGOTIATIONS, AGREEMENTS, PROMISES AND UNDERSTANDINGS BETWEEN PURCHASER AND FLIR. THIS WARRANTY MAY NOT BE ALTERED WITHOUT THE EXPRESS WRITTEN CONSENT OF FLIR.
6. WARRANTY RETURN, REPAIR AND REPLACEMENT. To be eligible for warranty repair or replacement, Purchaser must notify FLIR within thirty (30) days of discovering of any apparent defect in materials or workmanship. Before Purchaser may return a Product for warranty service or repair, Purchaser must first obtain a returned material authorization (RMA) number from FLIR. To obtain the RMA number Owner must provide an original proof of purchase. For additional information, to notify FLIR of an apparent defect in materials or workmanship, or to request an RMA number, visit http://www.flir.com. Purchaser is solely responsible for complying with all RMA instructions provided by FLIR including but not limited to adequately packaging the Product for shipment to FLIR and for all packaging and shipping costs. FLIR will pay for returning to Purchaser any Product that FLIR repairs or replaces under warranty.
FLIR reserves the right to determine, in its sole discretion, whether a returned Product is covered under Warranty. If FLIR determines that any returned Product is not covered under Warranty or is otherwise excluded from Warranty coverage, FLIR may charge Purchaser a reasonable handling fee and return the Product to Purchaser, at Purchasers expense, or offer Purchaser the option of handling the Product as a nonwarranty return.
7. NONWARRANTY RETURN. Purchaser may request that FLIR evaluate and service or repair a Product not covered under warranty, which FLIR may agree to do in its sole discretion. Before Purchaser returns a Product for nonwarranty evaluation and repair, Purchaser must contact FLIR by visiting http://www.flir.com to request an evaluation and obtain an RMA. Purchaser is solely responsible for complying with all RMA instructions provided by FLIR including but not limited to adequately packaging the Product for shipment to FLIR and for all packaging and shipping costs. Upon receipt of an authorized nonwarranty return, FLIR will evaluate the Product and contact Purchaser regarding the feasibility of and the costs and fees associated with Purchasers request. Purchaser shall be responsible for the reasonable cost of FLIRs evaluation, for the cost of any repairs or services authorized by Purchaser, and for the cost of repackaging and returning the Product to Purchaser.
Any nonwarranty repair of a Product is warranted for one hundred eighty days (180) days from the date of return shipment by FLIR to be free from defects in materials and workmanship only, subject to all of the limitations, exclusions and disclaimers in this document.
Corporate Headquarters
FLIR Systems, Inc.
2770 SW Parkway Avenue
Wilsonville, OR 97070
USA
Telephone: +1 5034983547
Customer Support
Technical Support Website http://support.flir.com
Technical Support Email TMSupport@flir.com
Service and Repair Email Repair@flir.com
Customer Support Telephone +1 8554993662 option 3 (toll free)
Related manuals for Flir TA74 Current Probe User Manual
Manualsnet FAQs
If you want to find out how the TA74 Flir works, you can view and download the Flir TA74 Current Probe User Manual on the Manualsnet website.
Yes, we have the User Manual for Flir TA74 as well as other Flir manuals. All you need to do is to use our search bar and find the user manual that you are looking for.
The User Manual should include all the details that are needed to use a Flir TA74. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.
The best way to navigate the Flir TA74 Current Probe User Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.
This Flir TA74 Current Probe User Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.
You can download Flir TA74 Current Probe User Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.
To be able to print Flir TA74 Current Probe User Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Flir TA74 Current Probe User Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.