USER GUIDE 

3000A AC Flexible Clamp Adaptors 

Models CA3010 and CA3018

CA3010_CA3018 enGB_V1.0   1/15 2

Introduction 

Thank you for choosing the Extech AC Flexible Clamp Adaptor that can measure up to 3000A AC.   A standard Digital MultiMeter (DMM) in mV AC mode can be used to display the current  measurement when the CA series Adaptor is connected to the DMM. 

The CA3018 is the 18 (45.7cm) clamp version and the CA3010 is the 10 (25.4cm) clamp version,  otherwise both meters are the same. These devices are professional CAT IV 600V CAT III 1000V  instruments. This meter is shipped fully tested and calibrated and, with proper use, will provide  years of reliable service. 

Features 

3000A AC Current Measurements displayed on connected DMM 

Convenient Flexible Clamp with locking mechanism 

7.5mm (0.3) coil diameter for measuring in tight spaces 

Supplied banana plug cables 

Power button 

Battery status LED indicator 

Current AC Range select switch 30A, 300A, 3000A 

Battery powered 

CA3010_CA3018 enGB_V1.0   1/15 3

Safety Information 

To ensure the safe operation and service of the meter, follow these instructions closely. Failure to  observe warnings can result in severe injury. 

WARNINGS 

WARNINGS identify hazardous conditions and actions that could cause BODILY HARM or DEATH. 

Individual protective equipment should be used if HAZARDOUS LIVE parts in the installation  where measurements are to be carried out could be accessible. 

If the equipment is used in a manner not specified by the manufacturer, the protection  provided by the equipment may be impaired. 

Always use proper terminals, switch position, and range for measurements. 

To reduce the risk of fire or electric shock, do not expose this product to rain or moisture. 

Verify the meter operation by measuring a known current. If in doubt, have the meter  serviced. 

Do not apply more than the rated voltage/current as marked on the meter. 

To avoid false readings that can lead to electric shock and injury, replace battery as soon as  the low battery indicator appears. 

Do not use the meter in or around explosive gas or vapor. 

Do not use a flexible current sensor if the inner copper wire of the flexible cord is visible. 

Deenergize the installation under test or wear suitable protective clothing when placing or  removing the flexible current probe from a test setup. 

Do not apply/remove the flexible current probe to/from UNINSULATED HAZARDOUS LIVE  conductors which may cause electric shock, electric burn, or arc flash. 

CA3010_CA3018 enGB_V1.0   1/15 4

CAUTIONS 

CAUTIONS identify conditions and actions that could cause DAMAGE to the meter or equipment  under test. Do not expose the meter to extremes in temperature or high humidity. 

Safety Symbols that are typically marked on meters and instructions 

This symbol, adjacent to another symbol, indicates the user must refer to the  manual for further information. 

  Do not apply or remove clamp from HAZARDOUS LIVE conductors 

Equipment protected by double or reinforced insulation 

Battery symbol 

Conforms to EU directives 

Do not discard this product in household trash. 

AC measurement 

Earth ground 

PER IEC1010 OVERVOLTAGE INSTALLATION CATEGORY 

OVERVOLTAGE CATEGORY I  Equipment of OVERVOLTAGE CATEGORY I is equipment for connection to circuits in which  measures are taken to limit the transient overvoltages to an appropriate low level.  Note  Examples include protected electronic circuits. 

OVERVOLTAGE CATEGORY II  Equipment of OVERVOLTAGE CATEGORY II is energyconsuming equipment to be supplied from  the fixed installation.  Note  Examples include household, office, and laboratory appliances. 

OVERVOLTAGE CATEGORY III  Equipment of OVERVOLTAGE CATEGORY III is equipment in fixed installations.  Note  Examples include switches in the fixed installation and some equipment for industrial use  with permanent connection to the fixed installation. 

OVERVOLTAGE CATEGORY IV  Equipment of OVERVOLTAGE CATEGORY IV is for use at the origin of the installation.  Note  Examples include electricity meters and primary overcurrent protection equipment

CA3010_CA3018 enGB_V1.0   1/15 5

1

2

3

4 5

6

7

8

Description 

Meter Description 

1. Flexible Current Clamp 

2. Range selector 

3. Power button 

4. Banana Plug cable 

5. Battery Compartment 

6. Battery status indicator 

7. Clamp Lock mechanism 

8. Test Lead Banana Plugs 

Operation 

NOTES: Read and understand all Warning and Caution statements in this operation manual  prior to using this meter. 

Meter Power 

The meter is powered by two (2) AAA 1.5V batteries (located in compartment on bottom of meter  handle). Press the Power button momentarily to switch the device ON or OFF. 

Battery status indication 

The battery status indicator blinks slowly when the battery is fresh (> 2.5V). The indicator blinks  quickly when the battery is weakening (< 2.5V) and requires changing. Refer to the Maintenance  section for details on battery replacement. 

CA3010_CA3018 enGB_V1.0   1/15 6

AC Current Measurements  

WARNING: Ensure that power to the device under test is OFF before starting this procedure.  Switch power to the device under test ON only after the clamp has been safely attached to the  device under test. 

CAUTION:  Do not move fingers above the LCD at any time during a test. 

1. Switch OFF the Clamp Adaptor, the DMM, and the device under test. 

2. Connect the Clamp Adaptor to the DMM banana jacks using the supplied banana plugs. 

3. Switch ON the DMM and set the DMM to the AC V mode. 

4. Set the Range Select switch on the Clamp Adaptor to the expected current range  measurement. 

5. Turn the knurled clamp lock mechanism on the Clamp Adaptor counterclockwise to release  the flexible clamp. 

6. Fully enclose only one conductor of the device under test with the flexible clamp probe (see  accompanying diagrams). Do not attempt to measure current higher than the specified  current limit. 

7. Switch the Clamp Adaptor ON (press Power button) and then switch the device under test  ON. Never move fingers above the LCD when running a test. 

8. Read the current value in the DMM display. 

9. Remove power to the device under test before removing the Flexible Clamp connection and  disconnecting the application setup.  

Range Selection Guide 

For the best results, with regard to output signal, select the correct range according to expected  current measurement. See Table below. 

Range Select Switch  Best Performance 

30A (100mV/1A)  30.00A max. 

300A (10mv/1A)  30.0 to 300.0 A 

3000A (1mV/1A)  300.0 to 3000A 

CA3010_CA3018 enGB_V1.0   1/15 7

Maintenance 

WARNING: To avoid electrical shock, disconnect the meter from any circuit and turn OFF the  meter before opening the case. Do not operate the meter with an open case. 

Cleaning and Storage  Periodically wipe the case with a damp cloth and mild detergent; do not use abrasives or   solvents. If the meter is not to be used for 60 days or more, remove the batteries and store them  separately. 

Battery Replacement 

CAUTION: Remove the meter from the conductor under test and switch the meter OFF  before opening the battery compartment.

1. With a flat blade screwdriver or coin, rotate the battery compartment cover to the unlock  position. 

2. Remove the battery compartment cover. 

3. Replace the 2 AAA 1.5V batteries observing correct polarity. Positive side of both batteries  insert first. 

4. Reattach the battery compartment cover. 

5. Rotate the battery compartment cover to the lock position. 

You, as the end user, are legally bound (EU Battery ordinance) to return all used  batteries, disposal in the household garbage is prohibited! You can hand over  your used batteries / accumulators at collection points in your community or  wherever batteries accumulators are sold! 

Disposal: Follow the valid legal stipulations in respect of the disposal of the device  at the end of its lifecycle 

CA3010_CA3018 enGB_V1.0   1/15 8

Specifications 

Function  Range  Output Voltage  Accuracy 

AC Current   

30.00 A AC  100mV/1A AC   (3.0% of Full Scale) 

for frequency range: 45~500Hz  300.0A AC  10mV/1A AC 

3000 A AC  1mV/1A AC 

Notes: 

Accuracy is given as  (% of reading + least significant counts) at 23C 5C with relative humidity  lower than 80%. Accuracy is specified for a period of one year after calibration. 

Max. Output Voltage: 4.5V peak 

Output Noise: < 5mV for each range 

Position Error of Clamp: Accuracy and position error assumes centralized primary conductor at  optimum position, no external electrical or magnetic field, and within operating temperature  range. 

CA3010   CA3010 Error*  CA3018  CA3018 Error* 

Distance from  optimum position  

15mm (0.6)  +2.0%  35mm (1.4)  +1.0% 

25mm (1.0)  +2.5%  50mm (2.0)  +1.5% 

35mm (1.4)  +3.0%  60mm (2.4)  +2.0% 

 *Add this error to the AC Current accuracy specification listed earlier in this section. 

CA3010_CA3018 enGB_V1.0   1/15 9

GENERAL SPECIFICATIONS 

Clamp Jaw  Flexible type with locking mechanism and 7.5mm (0.3) coil  diameter  

Battery status indication  LED indicator blinks slowly (battery power > 2.5V) or quickly  (battery power < 2.5V) 

AC bandwidth  45 to 500Hz (sine wave) 

Operating Temperature and Humidity 

  0~30C (32~86F); 80%RH maximum  

  30~40C (86~104F); 75%RH maximum 

  40~50C (104~122F); 45%RH maximum   

Storage Temperature and Humidity 

  20~60C (4~140F); 80%RH maximum 

Temperature Coefficient  0.2 x specified accuracy / C, < 18C (64.5F), > 28C (82.4F) 

Altitude  Maximum operating altitude 2000m (6562) 

Battery  Two AAA 1.5V batteries 

Battery life  160 hours with alkaline batteries 

Dimensions (W x H x D)  CA3010: 120 x 280 x 25 mm (4.7 x 11.0 x 1.0) 

  CA3018: 130 x 350 x 25 mm (5.1 x 13.8 x 1.0)   

Weight  CA3010: 170 g (6.0 oz.) 

CA3018: 200 g (7.1 oz.) 

Safety Standards  For indoor use and in accordance with the requirements for double  insulation to EN610101, EN610102032, EN613261; CAT IV 600V,  CAT III 1000V, Pollution Degree 2 

Shock Vibration  Sinusoidal vibration MILPRF28800F (555 Hz, 3g max.) 

Drop Protection  1.2m (4) drop onto hard wood or concrete floor 

Copyright  2015 FLIR Systems, Inc.  Reservados

Manualsnet FAQs

If you want to find out how the CA3018 Flir works, you can view and download the Flir CA3018 Clamp Adaptor User Guide on the Manualsnet website.

Yes, we have the User Guide for Flir CA3018 as well as other Flir manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The User Guide should include all the details that are needed to use a Flir CA3018. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Flir CA3018 Clamp Adaptor User Guide is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Flir CA3018 Clamp Adaptor User Guide consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Flir CA3018 Clamp Adaptor User Guide free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Flir CA3018 Clamp Adaptor User Guide, simply download the document to your computer. Once downloaded, open the PDF file and print the Flir CA3018 Clamp Adaptor User Guide as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.