Dell VMAX3 and VMAX All Flash Power Off and Power On Procedures

Power Off and Power On Procedures Rev. 12.0 September 2022

Under normal circumstances, only Dell personnel or certified partners should power off and power on a VMAX3 or VMAX All Flash array.

This document describes how to power off and power on a VMAX3 or VMAX All Flash array. The array is designed to stay powered up in all situations. Call the Dell Service Support Center for assistance before performing a power-off procedure. If the array needs repair, only qualified Dell personnel or partners familiar with the array and their safety procedures for electrical equipment should access components inside the cabinet.

CAUTION: If eNAS is implemented on the system, there is no access to the NAS File Services while the system is

powered off.

Power off and power on procedures for VMAX3, VMAX 450F, VMAX 850F, VMAX 950F................................................................ 2

Power off and power on procedures for VMAX 250F....................................................................................................................................4

Power off and power on procedures for VMAX3, VMAX 450F, VMAX 850F, VMAX 950F

Power Distribution Unit (PDU)

The figure below displays the system bay location of the PDUs (one per zone) and the power tee breakers with corresponding on (in) and off (out) positions.

2

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

PDU PDU

System Bay (rear view)

Z o

n e

B

Z o

n e

A

1 2

3 4

5 6

1 2

3 4

5 6

Power zone B

Left side

Power zone A

Right side

1 2

3 4

5 6

1 2

3 4

5 6

Zone A

Right side

Zone B

Left side

Power zone B

Left side

Power zone A

Right side

(W it h

r e

a r

d o

o r

re m

o ve

d )

(W it h

r e

a r

d o

o r

)

ON OFF

1 2

3 4

5 6

1 2

3 4

5 6

Figure 1. System bay power tee breakers

Power off procedure

Unless it is an emergency situation, Dell Customer Engineers (CEs) should perform a routine shutdown using the Simplified SymmWin Shutdown script.

CEs should check with the customer to determine if the system is part of an SRDF/Metro vWitness environment before running the script. If it is, the customer must ensure that Bias is applied to the system that is not being powered off before the CE runs the script. See SalesForce KB 520304: VMAX3, VMAX AFA & PowerMax: SRDF/Metro vWitness Best Practices:

https://www.dell.com/support/kbdoc/en-us/000021348

See the Solutions Enabler SRDF Family User Guide for your version of Solutions Enabler: 1. Go to https://www.dell.com/support/home/en-us. 2. In the Search Support box, enter Solutions Enabler SRDF Family User Guide.

From the rear of the system, pull power tee breakers 1-6 for Zone A PDU and then 1-6 for Zone B PDU. The system begins the automated power off process.

NOTE: Do not pull the two blue arrow shaped tabs that are located between the power tee breakers. Pulling the blue

arrows unlatches the PDU locking mechanism and allows the PDU to be removed.

2

2

1

Figure 2. Power tee breaker ON (1) and OFF (2) positions

Figure legend:

1. ON position 2. OFF position

NOTE: If the system will be powered off for more than three months, turn the SPS color wheel from green to yellow to

disengage the SPS batteries from the SPS tray.

Power on procedure

Before you begin, in the front of the rack verify that the SPS color wheels are in the green (engaged) position. If the batteries are not engaged, you must engage them first. Press the color wheel and fully insert the batteries.

Power on the bay with Engine 1 first. When powering on the system, ensure that all remaining bays are powered on within 10 minutes of the first bay being

powered on. You can power on the remaining bays in any order.

On the rear door of each bay, push in the power tee breakers (1-6) for Zone A to the ON position. Immediately after, push in the power tee breakers (1-6) of Zone B.

The array starts the initialization procedure. The procedure time varies depending on the size and configuration type. At the end of the power on procedure, all directors are online to the host and the port online or offline state is returned to the state it was in when the power off process was initiated.

To bring an offline system online, run the Simplified SymmWin script Bring VMAX Online.

3

2

1

Figure 3. Power tee breaker ON (1) and OFF (2) positions

Figure legend:

1. ON position 2. OFF position

Power off and power on procedures for VMAX 250F

Power switches

Before proceeding, identify the locations of the switches.

The figure below displays the system bay location of the power switches. If the system is installed in a customer rack the switches may be in different locations.

4

System bay rear

Power zone B

Left side

Power zone A

Right side

Power

switch

O N I

O FF

O

Figure 4. System bay power switches

Power off procedure

Unless it is an emergency situation, Dell Customer Engineers (CEs) should perform a routine shutdown using the Simplified SymmWin Shutdown script.

CEs should check with the customer to determine if the system is part of an SRDF/Metro vWitness environment before running the script. If it is, the customer must ensure that Bias is applied to the system that is not being powered off before the CE runs the script. See SalesForce KB 520304: VMAX3, VMAX AFA & PowerMax: SRDF/Metro vWitness Best Practices:

https://www.dell.com/support/kbdoc/en-us/000021348

See the Solutions Enabler SRDF Family User Guide for your version of Solutions Enabler: 1. Go to https://www.dell.com/support/home/en-us. 2. In the Search Support box, enter Solutions Enabler SRDF Family User Guide.

Power off the system bay by pressing the Zone A and Zone B power distribution panel (PDP) power switches to the OFF position. The system begins the automated power down process.

Power on procedure

Power on the system bay by pressing the Zone A and Zone B power distribution panel (PDP) power switches to the ON position.

Upon power on, the array starts the initialization procedure. The procedure time varies depending on the size and configuration type. At the end of the power up procedure, all directors are online to the host and the port online or offline state is returned to the state it was in when the power off process was initiated.

To bring an offline system online, run the Simplified SymmWin script Bring VMAX Online.

5

Notes, cautions, and warnings

NOTE: A NOTE indicates important information that helps you make better use of your product.

CAUTION: A CAUTION indicates either potential damage to hardware or loss of data and tells you how to avoid the

problem.

WARNING: A WARNING indicates a potential for property damage, personal injury, or death.

2015 - 2022 Dell Inc. or its subsidiaries. All rights reserved. Dell Technologies, Dell, and other trademarks are trademarks of Dell Inc. or its subsidiaries. Other tradem

Manualsnet FAQs

If you want to find out how the 100K Dell works, you can view and download the Dell Symmetrix VMAX3 100K Storage Power Off and Power On Procedures on the Manualsnet website.

Yes, we have the Power Off And Power On Procedures for Dell 100K as well as other Dell manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Power Off And Power On Procedures should include all the details that are needed to use a Dell 100K. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Dell Symmetrix VMAX3 100K Storage Power Off and Power On Procedures is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Dell Symmetrix VMAX3 100K Storage Power Off and Power On Procedures consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Dell Symmetrix VMAX3 100K Storage Power Off and Power On Procedures free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Dell Symmetrix VMAX3 100K Storage Power Off and Power On Procedures, simply download the document to your computer. Once downloaded, open the PDF file and print the Dell Symmetrix VMAX3 100K Storage Power Off and Power On Procedures as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.