Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

By Greg Henderson, Riyad Moe, Chris Kitten and Jose L. Flores

Dell Datacenter Infrastructure Engineering

June 2010

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page ii

THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL

ERRORS AND TECHNICAL INACCURACIES. THE CONTENT IS PROVIDED AS IS, WITHOUT EXPRESS

OR IMPLIED WARRANTIES OF ANY KIND.

2010 Dell Inc. All rights reserved. Reproduction of this material in any manner whatsoever without

the express written permission of Dell Inc. is strictly forbidden. For more information, contact Dell.

Dell, the DELL logo, the DELL badge, and PowerEdge are trademarks of Dell Inc.

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page 1

Contents Introduction ........................................................................................................................................................... 2

Section 1: Cabling a Dell PowerEdge R310 or R410 With a Cable Management Arm (CMA) .......... 2

1.1 Connecting the CMA Cables to the System ....................................................................................... 2

1.2 Installing the Inner CMA Attachment Bracket .................................................................................... 3

1.3 Routing the Power Cables Through the Strain Reliefs ...................................................................... 3

1.4 Routing the Cables Through the CMA ................................................................................................. 3

1.5 Left-Side Mounting Instructions ........................................................................................................... 4

1.6 Right-Side Mounting Instructions ......................................................................................................... 6

Section 2: Cabling a Dell PowerEdge R310 or R410 System Without a CMA ...................................... 7

2.1 Routing the Cables ................................................................................................................................... 7

2.2 Removing the CMA Brackets for Shallow Racks ................................................................................. 7

Section 3: Replacing a Power Supply on a PowerEdge R310 or R410 System With a CMA ................ 8

Section 4: Cabling a PowerEdge R310 or R410 System Installed in Static Rails .................................... 9

Table of Figures

Figure 1: System with Cables Installed ................................................................................................................... 2 Figure 2: Attaching the Inner CMA Attachment Bracket ..................................................................................... 3 Figure 3: Routing Power Cables Through the Strain Reliefs .............................................................................. 3 Figure 4: Routing the Cables Through the CMA .................................................................................................. 4 Figure 5: Attaching the KVM Dongle to the CMA Basket .................................................................................... 5 Figure 6: Left-Side Mounted CMA Installation ...................................................................................................... 6 Figure 7: Right-Side Mounted CMA Installation ................................................................................................... 6 Figure 8: Cable Routing Without a CMA ................................................................................................................ 7 Figure 9: Removing the CMA Brackets for Shallow Racks .................................................................................. 8 Figure 10: Disconnecting the Inner CMA Attachment Bracket .......................................................................... 9 Figure 11: Replacing the Outer Power Supply ...................................................................................................... 9 Figure 12: Cabling a System Installed in Static Rails .......................................................................................... 10

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page 2

Introduction This white paper covers recommended cable routing procedures for Dell PowerEdge R310 & R410

systems in the following racks:

PowerEdge 4210/2410

PowerEdge 4820/4220/2420

If you are using the optional CMA, following these procedures will allow you to extend the system

from the rack for service without powering down or disconnecting the cables. If you are not using the

CMA, following these procedures will ensure secure attachment and strain relief of the cables behind

the system. For guidelines on how to route cables within the rack, refer to the Dell Best Practices Guide for Rack Enclosure white paper.

Section 1: Cabling a Dell PowerEdge R310 or R410 With a Cable Management Arm (CMA) This section details how to cable a PowerEdge R310 or R410 system using a CMA. If you are cabling

the system without the optional CMA, refer to Section 2.

Follow the instructions contained in the Rack Installation Guide in the rail kit to install the server into

the rack. Once installed, use these instructions to install the cables. All illustrations in the following

sections were created using a PowerEdge R410 system.

NOTE: PowerEdge R310 & R410 systems are not compatible with previous generation rails and

CMAs.

1.1Connecting the CMA Cables to the System Attach the CMA tray to the back of the rails as described in the CMA Installation Instructions provided in the CMA kit. Connect all applicable cables to the rear of the system and verify that all connections are secure. See Figure 1. Figure 1: System with Cables Installed

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page 3

1.2Installing the Inner CMA Attachment Bracket As described in the Rack Installation Instructions, locate and attach the appropriate inner CMA

attachment bracket based on which side you wish to mount the CMA. Use the bracket marked A for

mounting the CMA on the left side, and the bracket marked B for mounting on the right side. See

Figure 2.

Figure 2: Attaching the Inner CMA Attachment Bracket

1.3Routing the Power Cables Through the Strain Reliefs After you have installed the tray and cables, route the power cables through the strain reliefs located

on the power supply handles as shown in Figure 3.

Figure 3: Routing Power Cables Through the Strain Reliefs

1.4Routing the Cables Through the CMA

You can install the CMA on either the rear right or rear left side of the rails. Mounting the CMA on the

side that is opposite of the power supplies (left-side mount) is recommended; otherwise, the CMA

must be disconnected, to some extent, in order to remove the power supplies. Refer to Section 3 for

details on power supply replacement.

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page 4

NOTE: For guidelines on how to route cables within the rack, refer to the Dell Best Practices Guide for Rack Enclosures white paper.

1.5Left-Side Mounting Instructions 1. Install the CMA on the rear left side of the rails by attaching both CMA housings to the attachment

brackets on the rails.

2. Route the cables through the CMA while avoiding twisting the cables. Use the hook and loop

straps on the CMA to secure the cables. See Figure 4.

Figure 4: Routing the Cables Through the CMA

3. If the cable bundle includes a keyboard, video, and mouse (KVM) dongle, place the dongle inside

the CMA basket for light to medium cable loads. If the KVM dongle does not fit inside the basket

with the other cables, attach the dongle to the exterior of the front basket as shown in Figure 5.

Cables entering the CMA should have

a small amount of slack to avoid cable

strain when the CMA is extended.

NOTE: Do not store excess cable

slack inside the CMA. The cable may

protrude through the CMA, thus

causing binding and potentially

damaging the cable.

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page 5

Figure 5: Attaching the KVM Dongle to the CMA Basket

4. Once you have routed all the cables through the CMA, dress the cable slack between the back of

the system and the entrance of the CMA using the tie wraps (shown in yellow in all illustrations)

provided in the CMA kit.

5. Clip off the excess length of material from the tie wraps. Make sure that the heads of the tie wraps

are positioned so as to avoid interference with adjacent systems. Return the CMA to the closed

(retracted) position.

6. Extend the system out of the rack to verify that there is sufficient slack in the cables on both ends

of the CMA.

See Figure 6 for an example of a completed left-side mounted CMA installation.

Use the hook and loop straps on the

CMA basket to secure the KVM dongle.

KVM Dongle

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page 6

Figure 6: Left-Side Mounted CMA Installation

1.6Right-Side Mounting Instructions Install the CMA on the rear right side of the rails by attaching both CMA housings to the attachment

brackets on the rails. Follow steps 2-6 from the left-side mounting instructions in section 1.5. See

Figure 7 for an example of a completed right-side mounted CMA installation.

Figure 7: Right-Side Mounted CMA Installation

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page 7

Section 2: Cabling a Dell PowerEdge R310 or R410 System Without a CMA NOTE: The CMA on Dell PowerEdge R310 & R410 systems is optional. Without the CMA installed,

the system must be powered down and all cables disconnected before it can be removed from the

rack.

2.1Routing the Cables 1. Connect all applicable cables to the rear of the system and verify that all connections are secure.

2. Using the hook and loop straps supplied with the rail kit, bundle the cables and secure them to

either the left or right CMA attachment brackets as described in the Rack Installation Instructions.

See Figure 8 for an example of data cables secured to the left CMA bracket and power cables

secured to the right CMA bracket.

3. It is recommended that the cables be secured to the outer brackets, but cables may be secured to

the inner brackets as well if desired.

Figure 8: Cable Routing Without a CMA

2.2Removing the CMA Brackets for Shallow Racks If you are installing the system into a shallow rack (less than 1 meter deep) and you will not be

installing a CMA, the outer CMA brackets may be removed if necessary in order to allow the rails to fit

properly into the rack. Remove the brackets by using a #2 Phillips screwdriver to remove the screws

used to attach them to the rails as shown in Figure 9.

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page 8

Figure 9: Removing the CMA Brackets for Shallow Racks

Section 3: Replacing a Power Supply on a PowerEdge R310 or R410 System With a CMA

1. Remove the tray from underneath the CMA as described in the CMA Installation Instructions provided with the CMA kit.

2. Swing the CMA into the service position.

3. Disconnect the power cord from the power supply and disengage the strain relief.

4. If the CMA is attached to the left side, both power supplies can be removed without

disconnecting the CMA.

5. If the CMA is attached to the right side and the inner power supply needs to be replaced, the

CMA does not need to be disconnected.

6. If the CMA is attached to the right side and the outer power supply needs to be replaced:

a. Disconnect the inner CMA bracket from the rail as shown in Figure 10.

b. While supporting the CMA with one hand, remove and replace the power supply with

the other hand as shown in Figure 11.

c. Reinstall the inner CMA bracket to reconnect the CMA.

7. After the power supply has been replaced, plug in the power cord, re-engage the strain relief,

replace the CMA support tray, and return the CMA to the closed (retracted) position.

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page 9

Figure 10: Disconnecting the Inner CMA Attachment Bracket

Figure 11: Replacing the Outer Power Supply

Section 4: Cabling a PowerEdge R310 or R410 System Installed in Static Rails NOTE: The CMA is compatible with the sliding rails only, not the static rails.

1. Follow the instructions contained in the Rack Installation Instructions found in the static rail kit

to install the server into a two-post or four-post rack.

2. Install the hook and loop straps provided in the rail kit through the slots in the rear brackets of

the rails as described in the Rack Installation Instructions.

Disconnected inner

CMA bracket

Cable Routing Procedures for Dell PowerEdge R310 & R410 Systems

Page 10

3. Connect all applicable cables to the rear of the system and verify that all connections are

secure.

4. Using the hook and loop straps, bundle the cables and secure them to either the left rail or

right rail as described in the Rack Installation Instructions. See Figure 12 for an example of

data cables that are secured to the left rail and power cables that are secured to the right rail

(

Manualsnet FAQs

If you want to find out how the PowerEdge Dell works, you can view and download the Dell PowerEdge 2410 R310 Rack Infrastructure Cable Routing Guide on the Manualsnet website.

Yes, we have the Cable Routing Guide for Dell PowerEdge as well as other Dell manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Cable Routing Guide should include all the details that are needed to use a Dell PowerEdge. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Dell PowerEdge 2410 R310 Rack Infrastructure Cable Routing Guide is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Dell PowerEdge 2410 R310 Rack Infrastructure Cable Routing Guide consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Dell PowerEdge 2410 R310 Rack Infrastructure Cable Routing Guide free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Dell PowerEdge 2410 R310 Rack Infrastructure Cable Routing Guide, simply download the document to your computer. Once downloaded, open the PDF file and print the Dell PowerEdge 2410 R310 Rack Infrastructure Cable Routing Guide as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.