Installation Instructions

Table of Contents Step#1: Preparation ..........................................................................2 Step#2: Applications .........................................................................3 Step#3: Wire Connections ..................................................................4 Step#4: Test Operation & Wiring Diagrams .........................................6 Troubleshooting ..............................................................................14 Technical Specifications ...................................................................16

Follow Installation Instructions carefully. Disconnect Power to the Heater/Air Conditioner before removing the old thermostat and installing the new thermostat.

CAUTIONIMPORTANT

Copyright 2014, All Rights Reserved P/N 33CSSP3-FC

1

IMPORTANT: The Fan Coil Series Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn or protect against failure or malfunction of the thermostat controller.

Step #1 Preparation

2

Properinstallationofthethermostatwillbeaccomplishedbyfollowing these step by step instructions. If you are unsure about any of these steps, call a qualified technician for assistance.

Assembletools.

MakesureyourHeater/AirConditionerisworkingproperlybefore beginning installation of the thermostat.

Carefullyunpackthethermostat.Savethescrews,wallanchors, and instructions.

TurnoffthepowertotheHeating/AirConditioningsystematthe main fuse panel.

INSTALLATION Location Considerations Locate the Fan Coil Series Thermostat Controllers: onapartitioningwall,approximately5ft(1.5m)abovethefloorina

location of average temperature. awayfromdirectsunlight,radiantheat,outsidewalls,outsidedoors,

air discharge grills, or stairwells; and from behind doors. awayfromsteamorwaterpipes,warmairstacks,unconditionedareas (notheatedorcooled),orsourcesofelectricalinterference.

Drill with 3/16 inch Drill Bit (when not using j-box)

Flat Blade Screwdriver

Wire cutter & Stripper

Step #2 Applications

3

New Applications FollowthethermostatandE-M(Electro-Mechanical)wiringdiagrams suppliedwiththesubmittalpackage,andafixedtothefancoilunit enclosure.Gotopages6through10forinstructionstotestoperationfor the available applications.

Existing Applications Removethecoveroftheoldthermostat.Ifitdoesnotcomeoffeasilycheck

for screws. Loosenthescrewsholdingthethermostatbaseorsubbasetothewalland

lift away. Disconnectthewiresfromtheoldthermostat.Tapetheendsofthewires asyoudisconnectthemandmarkthemwiththeletteroftheterminalfor easy reconnection to the new thermostat.

Keeptheoldthermostatforreferencepurposesuntilyournewthermostat is functioning properly.

CAUTION: Risk of Electric Shock. Disconnectpowersupplybeforemakingelectricalconnectionstoavoidelectricshock.

CAUTION: Risk of Property Damage. Donotapplypowertothesystembeforecheckingallwireconnections.Shortcircuited or improperly connected wires may result in permanent damage to the equipment.

CAUTION

CAUTION

IMPORTANT:Makeallwiringconnectionsinaccordancewithlocal,national,andregional regulations.DonotexceedtheelectricalratingsoftheFanCoilSeriesThermostatControllers.

Note: This thermostat is strictly a low voltage control. A compatible relay board must be installed to isolate the 24 volt wires from the line voltage to the fan.

Step #3 Wire Connections

4

If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below.

4-Pipe Systems Wire from the Install on the old thermostat Function new thermostat terminal marked terminal marked

Y1, Y Cooling Y1

W1, W Heating W1

RH, R, M, Vr, A Power R

C Common C

G, F or LOW Low Fan Speed G

MED Medium Fan Speed G2

HIGH High Fan Speed G3

Note: Be sure to seal any opening through the wall behind the thermostat with fireproof material to prevent improper temperature sensing of the conditioned space.

5

Step #3 Wire Connections

If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below.

2-Pipe Systems Wire from the Install on the old thermostat Function new thermostat terminal marked terminal marked

Y1, Y Water Valve Y1

W1, W Strip Heater W1

RH, R, M, Vr, A Power R

C Common C

G, F or LOW Low Fan Speed G

MED Medium Fan Speed G2

HIGH High Fan Speed G3

Note: Be sure to seal any opening through the wall behind the thermostat with fireproof material to prevent improper temperature sensing of the conditioned space.

Step #4 Test Operation

6

4-PIPE SYSTEM TurnthepowerontotheFanCoilUnit.

PresstheMODEbuttonrepeatedlyuntiltheHEAT icon appears on the display.PresstheUPorDOWNbuttonsuntilthesettemperatureis10 degrees above room temperature. The hot water valve will open and the fan will be running.

PresstheMODEbuttonrepeatedlyuntiltheCOOL icon appears on the display.PresstheUPorDOWNbuttonsuntilthesettemperatureis10 degrees below room temperature. The cold water valve will open and the fan will be running.

PresstheUPbuttonuntilthesetpointisequaltotheroomtemperature. PresstheFanbuttonrepeatedlyuntilasinglebarappearsnexttotheFan icon.Confirmthefanisrunningonlowspeed.PresstheFanbuttonagain, confirmthefanisrunningonmediumspeed.Again,presstheFanbutton, confirmthefanisrunningathighspeed.PresstheFanbuttononcemore, thebarsnexttotheFaniconshoulddisappear.

PresstheMODEbuttonrepeatedlyuntiltheOFF icon appears on the display.Bothvalveswillbeclosedandthefanwillbeoff.

Step #4 Wiring Diagram

7

Sample Wiring Diagram 4-Pipe, Low Voltage Valves, Duct Temperature Sensor

& Dry Contact

COM

G3/(Y)

G2/(W)

G

R

C

S ample Wiring Diagram 4-Pipe, Low V oltage V alves, Duct T emperature Sensor & Dry Contact

COM

G

G3(Y)

G2(W)

BLACK

WHITE

Dry Contact

Duct Sensor G100-71520307

R

C

R

C

G 2

G 3

G

R S

H2O C k1

Y 1

W1 H C

Thermostat

24vac

Page 7

24 Volt Water Valves

Important Note:IfaDuct sensor is connected to this thermostat it is suggested that the fan be programmed for continuous operation (step#5,page11ofthe OwnersManual)

Step #4 Test Operation

8

2-PIPE, HEAT ONLY OR COOL ONLY TurnthepowerontotheFanCoilUnitandconfirmthatthethermostatis programmedcorrectlyinsetupsteps#3and#4onpage11oftheOwners Manual.

IfHeatOnly,presstheMODEbuttonrepeatedlyuntiltheHEAT icon appears onthedisplay.PresstheUPorDOWNbuttonsuntilthesettemperatureis 10degreesaboveroomtemperature.Thehotwatervalvewillopenandthe fan will be running.

IfCoolOnly,presstheMODEbuttonrepeatedlyuntiltheCOOL icon appears onthedisplay.PresstheUPorDOWNbuttonsuntilthesettemperatureis 10degreesbelowroomtemperature.Thecoldwatervalvewillopenand the fan will be running.

PresstheUPbuttonuntilthesetpointisequaltotheroomtemperature. PresstheFanbuttonrepeatedlyuntilasinglebarappearsnexttotheFan icon.Confirmthefanisrunningonlowspeed.PresstheFanbuttonagain, confirmthefanisrunningonmediumspeed.Again,presstheFanbutton, confirmthefanisrunningathighspeed.PresstheFanbuttononcemore, thebarsnexttotheFaniconshoulddisappear.

PresstheMODEbuttonrepeatedlyuntiltheOFF icon appears on the display.Bothvalveswillbeclosedandthefanwillbeoff.

Step #4 Wiring Diagram

9

COM

G3/(Y)

G2/(W)

G

R

C

S ample Wiring Diagram

2-Pipe, Low V oltage V alve, Heat Only or Cool Only

COM

G

G3(Y)

G2(W)

R

C

G 2

W1 G 3

G

V

Y 1

Thermostat

24vac

Page 8

24 Volt Water Valve

Sample Wiring Diagram 2-Pipe, Low Voltage Valve, Cool Only

10

Step #4 Test Operation

2-PIPE, CHANGEOVER SENSOR, NO STRIP HEAT TurnthepowerontotheFanCoilUnitandconfirmthatthethermostatis programmedcorrectlyinsetupsteps#5and#6onpage19oftheOwners Manual.

Ifhotwaterisavailable,presstheMODEbuttonrepeatedlyuntiltheHEAT iconappearsonthedisplay.PresstheUPorDOWNbuttonsuntiltheset temperatureis10degreesaboveroomtemperature.Thewatervalvewill open and the fan will be running.

Ifcoldwaterisavailable,presstheMODEbuttonrepeatedlyuntiltheCOOL iconappearsonthedisplay.PresstheUPorDOWNbuttonsuntiltheset temperatureis10degreesbelowroomtemperature.Thecoldwatervalve will open and the fan will be running.

Step #4 Wiring Diagram

11

COM

G3/(Y)

G2/(W)

G

R

C

S ample Wiring Diagram

2-Pipe, Low V oltage V alve, H2O Changeover Sensor

COM

G

G3(Y)

G2(W)

BLACK

WHITE

R

C

R

C

G 2

G 3

G

R S

H2O

V

Y 1

Thermostat

24vac

24 Volt Water Valve

H20 Changeover Sensor G100-71520306 Closed Below 60 Open Above 75

Duct Sensor G100-71520307

Sample Wiring Diagram 2-Pipe, Low Voltage Valve, H20 Changeover Sensor

Important Note:IfaDuct sensor is connected to this thermostat it is suggested that the fan be programmed for continuous operation (step#5,page11ofthe OwnersManual)

12

Step #4 Test Operation

2-PIPE, CHANGEOVER SENSOR, WITH STRIP HEAT TurnthepowerontotheFanCoilUnitandconfirmthatthethermostatis programmedcorrectlyinsetupsteps#3and#4onpage11oftheOwners Manual.

PresstheMODEbuttonrepeatedlyuntiltheHEAT icon appears on the display.PresstheUPorDOWNbuttonsuntilthesettemperatureis10 degrees above room temperature. If hot water is available, the water valve should open. If hot water is not available, the strip heater should turn on.

Ifcoldwaterisavailable,presstheMODEbuttonrepeatedlyuntiltheCOOL iconappearsonthedisplay.PresstheUPorDOWNbuttonsuntiltheset temperatureis10degreesbelowroomtemperature.Thewatervalvewill open and the fan will be running.

13

Step #4 Wiring Diagram

Sample Wiring Diagram 2-Pipe, Low Voltage Valve, Changeover Sensor

with Electric Strip Heat

COM

G3/(Y)

G2/(W)

G

R

C

S ample Wiring Diagram

2-Pipe, Low V oltage V alve, Chilled W ater with Electric Strip Heat

COM

G

G3(Y)

G2(W)

R

C

G 2

G 3

G

VR

Y 1

W1

Page 10

Thermostat

24vac

24 Volt Water Valve

24 Volt Relay to Control Strip Heater

R

H2O

Troubleshooting

14

SYMPTOM: The fan will not run in all three speeds or switches speeds in an improper order. CAUSE: Incorrect wiring between the thermostat and the relay board, or between the relay board and the fan wires. REMEDY:Recheckthewiring(G=lowspeed,G2=mediumspeed,G3=high speed).

SYMPTOM:Coldwatervalveopensforeitheracooloraheatdemandina4-pipe system. CAUSE: The thermostat has been programmed for the incorrect type of fan coil. REMEDY: Confirm that you have entered the correct programming for your type offancoilsystem(steps#5and#6,page19oftheOwnersManual).

SYMPTOM:Thewatervalvedoesnotopenatallin2-pipeconfigurations. CAUSE: The thermostat has been programmed for the incorrect type of fan coil system or the fan coil is not wired to the thermostat correctly. REMEDY:Programthethermostatfora2-pipefancoil(step#5,page19of theOwnersManual).Also,makecertainthatthewatervalveiswiredtotheY1 terminal.

SYMPTOM:Thethermostatdisplayonlyshowsclock. CAUSE: The thermostat has been programmed for a minimal display. REMEDY:ProgramthethermostatforFullDisplay(step#3,page18ofthe OwnersManual).

SYMPTOM: The thermostat displays large setpoint digits instead of the room temperature. CAUSE: The thermostat has been programmed to display Single Setpoint. REMEDY:ProgramthethermostattodisplayDualSetpoint(step #4, page 19 of the Owners Manual).

15

Troubleshooting

SYMPTOM:ThethermostatdisplayflashesOccupied1whenrunningthe program. CAUSE:ThesensorconnectedtotheDryContactterminalsofthe thermostat,isactive,forcingtheunitintoOccupied1. REMEDY: Verify proper wiring between the thermostat and the occupancy sensor and verify that the wiring is not shorted. If no sensor is connected, programtheDryContactpolarityforNormallyOpen(step#14,page21of theOwnersManual).

SYMPTOM:ThethermostatwillonlyallowHeatorOffin2-pipe installations, even though chilled water is available. CAUSE:Faulty,improperlywired,orimproperlyinstalledH2Ochangeover sensor. REMEDY:Confirmproperwiringofthechangeoversensor(betweenRand H2O).Confirmproperplacementofthesensor(goodmechanicalcoupling fortemperaturetransfer).Testthechangeoversensorasfollows: 1.Removepowerfromthefancoilsystem. 2.DisconnectthewirebetweenthesensorandtheH2Oterminal. 3.PlaceanohmmeterbetweenRandthewirejustdisconnectedfrom the sensor. 4.Agoodsensorwillshowcontinuitywheneverthewatertemperature isconfirmedtobeatorbelow65degrees.Ifthesensorisopenwhen thewatertemperatureisconfirmedtobeatorbelow65,replace the sensor.

Technical Specifications

17

XXXXX Series Thermostat Controllers Power Requirements 20 - 30 VAC 50/60 Hz, 3 VA @ 24V nominal.

Valve Outputs 0.8A max, 0.01A min, 3A inrush, 20 - 30 VAC Fan Outputs 0.4A max, 0.01A min, 3A inrush, 20 - 30 VAC

voltage free contacts, closed to signal CHILLED water supply

voltage free contacts, closed to alter setpoints

solid state temperature sensor, 10 mV / degF

16 AWG (100 ft max) to 24 AWG (36 ft max)

35 to 99 deg F (2 to 36 degC)

35 to 65 deg F +/- 3 degF, greater than 65 to less than 80 degF +/- 2 degF, 80 to 99 degF +/- 3 degF, greater than 99 to 104 degF +/- 5 degF

Adjustable 1 to 6 deg first stage, fixed 1 degree for med/hi fan speeds

35 to 104 degF (2 o 40 degC), 5 - 95% RH non-condensing, 86 degF max dew point

-22 to 122 degF (-30 to 50 degC), 5-95% RH non-condensing, 86 degF max dew point

UL/cUL listed, file E107041, NEC Class 2

3.14 H x 3.14 W x 1.1 D

0.25 kg

Output Rating

Digital Inputs H2O

CK1

Local Temperature Sensor Type

solid state temperature sensor, digital communications over two wires, 5 ft cable supplied, accurate to 1 degF

Remote Temperature Sensor Type

Temperature Adjustment Range

Accuracy

Wire Size

Deadband

Operating

Storage

Ambient Conditions

Compliance

Dimensions

Shipping Weight

This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.

United States

Canada

North American Emissions Compliance

This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numerique de la Classe (B) respecte toutes les exigences du Reglement sur le materiel brouilleur du Canada.

Manualsnet FAQs

If you want to find out how the Airstream 42V 33CSSP3-FC Carrier works, you can view and download the Carrier Airstream 42V 33CSSP3-FC Installation Instructions on the Manualsnet website.

Yes, we have the Installation Instructions for Carrier Airstream 42V 33CSSP3-FC as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Installation Instructions should include all the details that are needed to use a Carrier Airstream 42V 33CSSP3-FC. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier Airstream 42V 33CSSP3-FC Installation Instructions is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier Airstream 42V 33CSSP3-FC Installation Instructions consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier Airstream 42V 33CSSP3-FC Installation Instructions free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier Airstream 42V 33CSSP3-FC Installation Instructions, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier Airstream 42V 33CSSP3-FC Installation Instructions as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.