Installation Instructions
Table of Contents Step#1: Preparation ..........................................................................2 Step#2: Applications .........................................................................3 Step#3: Wire Connections ..................................................................4 Step#4: Test Operation & Wiring Diagrams .........................................6 Troubleshooting ..............................................................................14 Technical Specifications ...................................................................16
Follow Installation Instructions carefully. Disconnect Power to the Heater/Air Conditioner before removing the old thermostat and installing the new thermostat.
CAUTIONIMPORTANT
Copyright 2014, All Rights Reserved P/N 33CSSN3-FC
1
IMPORTANT: The Fan Coil Series Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn or protect against failure or malfunction of the thermostat controller.
Step #1 Preparation
2
Properinstallationofthethermostatwillbeaccomplishedbyfollowing these step by step instructions. If you are unsure about any of these steps, call a qualified technician for assistance.
Assembletools.
MakesureyourHeater/AirConditionerisworkingproperlybefore beginning installation of the thermostat.
Carefullyunpackthethermostat.Savethescrews,wallanchors, and instructions.
TurnoffthepowertotheHeating/AirConditioningsystematthe main fuse panel.
INSTALLATION Location Considerations Locate the Fan Coil Series Thermostat Controllers: onapartitioningwall,approximately5ft(1.5m)abovethefloorina
location of average temperature. awayfromdirectsunlight,radiantheat,outsidewalls,outsidedoors,
air discharge grills, or stairwells; and from behind doors. awayfromsteamorwaterpipes,warmairstacks,unconditionedareas (notheatedorcooled),orsourcesofelectricalinterference.
Drill with 3/16 inch Drill Bit (when not using j-box)
Flat Blade Screwdriver
Wire cutter & Stripper
Step #2 Applications
3
New Applications FollowthethermostatandE-M(Electro-Mechanical)wiringdiagrams suppliedwiththesubmittalpackage,andafixedtothefancoilunit enclosure.Gotopages6through10forinstructionstotestoperationfor the available applications.
Existing Applications Removethecoveroftheoldthermostat.Ifitdoesnotcomeoffeasilycheck
for screws. Loosenthescrewsholdingthethermostatbaseorsubbasetothewalland
lift away. Disconnectthewiresfromtheoldthermostat.Tapetheendsofthewires asyoudisconnectthemandmarkthemwiththeletteroftheterminalfor easy reconnection to the new thermostat.
Keeptheoldthermostatforreferencepurposesuntilyournewthermostat is functioning properly.
CAUTION: Risk of Electric Shock. Disconnectpowersupplybeforemakingelectricalconnectionstoavoidelectricshock.
CAUTION: Risk of Property Damage. Donotapplypowertothesystembeforecheckingallwireconnections.Shortcircuited or improperly connected wires may result in permanent damage to the equipment.
CAUTION
CAUTION
IMPORTANT:Makeallwiringconnectionsinaccordancewithlocal,national,andregional regulations.DonotexceedtheelectricalratingsoftheFanCoilSeriesThermostatControllers.
Note: This thermostat is strictly a low voltage control. A compatible relay board must be installed to isolate the 24 volt wires from the line voltage to the fan.
Step #3 Wire Connections
4
If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below.
4-Pipe Systems Wire from the Install on the old thermostat Function new thermostat terminal marked terminal marked
Y1, Y Cooling Y1
W1, W Heating W1
RH, R, M, Vr, A Power R
C Common C
G, F or LOW Low Fan Speed G
MED Medium Fan Speed G2
HIGH High Fan Speed G3
Note: Be sure to seal any opening through the wall behind the thermostat with fireproof material to prevent improper temperature sensing of the conditioned space.
5
Step #3 Wire Connections
If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below.
2-Pipe Systems Wire from the Install on the old thermostat Function new thermostat terminal marked terminal marked
Y1, Y Water Valve Y1
W1, W Strip Heater W1
RH, R, M, Vr, A Power R
C Common C
G, F or LOW Low Fan Speed G
MED Medium Fan Speed G2
HIGH High Fan Speed G3
Note: Be sure to seal any opening through the wall behind the thermostat with fireproof material to prevent improper temperature sensing of the conditioned space.
Step #4 Test Operation
6
4-PIPE SYSTEM TurnthepowerontotheFanCoilUnit.
PresstheMODEbuttonrepeatedlyuntiltheHEAT icon appears on the display.PresstheUPorDOWNbuttonsuntilthesettemperatureis10 degrees above room temperature. The hot water valve will open and the fan will be running.
PresstheMODEbuttonrepeatedlyuntiltheCOOL icon appears on the display.PresstheUPorDOWNbuttonsuntilthesettemperatureis10 degrees below room temperature. The cold water valve will open and the fan will be running.
PresstheUPbuttonuntilthesetpointisequaltotheroomtemperature. PresstheFanbuttonrepeatedlyuntilasinglebarappearsnexttotheFan icon.Confirmthefanisrunningonlowspeed.PresstheFanbuttonagain, confirmthefanisrunningonmediumspeed.Again,presstheFanbutton, confirmthefanisrunningathighspeed.PresstheFanbuttononcemore, thebarsnexttotheFaniconshoulddisappear.
PresstheMODEbuttonrepeatedlyuntiltheOFF icon appears on the display.Bothvalveswillbeclosedandthefanwillbeoff.
Step #4 Wiring Diagram
7
Sample Wiring Diagram 4-Pipe, Low Voltage Valves, Duct Temperature Sensor
& Dry Contact
COM
G3/(Y)
G2/(W)
G
R
C
S ample Wiring Diagram 4-Pipe, Low V oltage V alves, Duct T emperature Sensor & Dry Contact
COM
G
G3(Y)
G2(W)
BLACK
WHITE
Dry Contact
Duct Sensor G100-71520307
R
C
R
C
G 2
G 3
G
R S
H2O C k1
Y 1
W1 H C
Thermostat
24vac
Page 7
24 Volt Water Valves
Important Note:IfaDuct sensor is connected to this thermostat it is suggested that the fan be programmed for continuous operation (step#5,page11ofthe OwnersManual)
8
Step #4 Test Operation
2-PIPE, HEAT ONLY OR COOL ONLY TurnthepowerontotheFanCoilUnitandconfirmthatthethermostatis programmedcorrectlyinsetupsteps#3and#4onpage11oftheOwners Manual.
IfHeatOnly,presstheMODEbuttonrepeatedlyuntiltheHEAT icon appears onthedisplay.PresstheUPorDOWNbuttonsuntilthesettemperatureis 10degreesaboveroomtemperature.Thehotwatervalvewillopenandthe fan will be running.
IfCoolOnly,presstheMODEbuttonrepeatedlyuntiltheCOOL icon appears onthedisplay.PresstheUPorDOWNbuttonsuntilthesettemperatureis 10degreesbelowroomtemperature.Thecoldwatervalvewillopenand the fan will be running.
PresstheUPbuttonuntilthesetpointisequaltotheroomtemperature. PresstheFanbuttonrepeatedlyuntilasinglebarappearsnexttotheFan icon.Confirmthefanisrunningonlowspeed.PresstheFanbuttonagain, confirmthefanisrunningonmediumspeed.Again,presstheFanbutton, confirmthefanisrunningathighspeed.PresstheFanbuttononcemore, thebarsnexttotheFaniconshoulddisappear.
PresstheMODEbuttonrepeatedlyuntiltheOFF icon appears on the display.Bothvalveswillbeclosedandthefanwillbeoff.
Step #4 Wiring Diagram
9
COM
G3/(Y)
G2/(W)
G
R
C
S ample Wiring Diagram
2-Pipe, Low V oltage V alve, Heat Only or Cool Only
COM
G
G3(Y)
G2(W)
R
C
G 2
W1 G 3
G
V
Y 1
Thermostat
24vac
Page 8
24 Volt Water Valve
Sample Wiring Diagram 2-Pipe, Low Voltage Valve, Cool Only
10
Step #4 Test Operation
2-PIPE, CHANGEOVER SENSOR, NO STRIP HEAT TurnthepowerontotheFanCoilUnitandconfirmthatthethermostatis programmedcorrectlyinsetupsteps#5and#6onpage19oftheOwners Manual.
Ifhotwaterisavailable,presstheMODEbuttonrepeatedlyuntiltheHEAT iconappearsonthedisplay.PresstheUPorDOWNbuttonsuntiltheset temperatureis10degreesaboveroomtemperature.Thewatervalvewill open and the fan will be running.
Ifcoldwaterisavailable,presstheMODEbuttonrepeatedlyuntiltheCOOL iconappearsonthedisplay.PresstheUPorDOWNbuttonsuntiltheset temperatureis10degreesbelowroomtemperature.Thecoldwatervalve will open and the fan will be running.
Step #4 Wiring Diagram
11
COM
G3/(Y)
G2/(W)
G
R
C
S ample Wiring Diagram
2-Pipe, Low V oltage V alve, H2O Changeover Sensor
COM
G
G3(Y)
G2(W)
BLACK
WHITE
R
C
R
C
G 2
G 3
G
R S
H2O
V
Y 1
Thermostat
24vac
24 Volt Water Valve
H20 Changeover Sensor G100-71520306 Closed Below 60 Open Above 75
Duct Sensor G100-71520307
Sample Wiring Diagram 2-Pipe, Low Voltage Valve, H20 Changeover Sensor
Important Note:IfaDuct sensor is connected to this thermostat it is suggested that the fan be programmed for continuous operation (step#5,page11ofthe OwnersManual)
12
Step #4 Test Operation
2-PIPE, CHANGEOVER SENSOR, WITH STRIP HEAT TurnthepowerontotheFanCoilUnitandconfirmthatthethermostatis programmedcorrectlyinsetupsteps#3and#4onpage11oftheOwners Manual.
PresstheMODEbuttonrepeatedlyuntiltheHEAT icon appears on the display.PresstheUPorDOWNbuttonsuntilthesettemperatureis10 degrees above room temperature. If hot water is available, the water valve should open. If hot water is not available, the strip heater should turn on.
Ifcoldwaterisavailable,presstheMODEbuttonrepeatedlyuntiltheCOOL iconappearsonthedisplay.PresstheUPorDOWNbuttonsuntiltheset temperatureis10degreesbelowroomtemperature.Thewatervalvewill open and the fan will be running.
13
Step #4 Wiring Diagram
Sample Wiring Diagram 2-Pipe, Low Voltage Valve, Changeover Sensor
with Electric Strip Heat
COM
G3/(Y)
G2/(W)
G
R
C
S ample Wiring Diagram
2-Pipe, Low V oltage V alve, Chilled W ater with Electric Strip Heat
COM
G
G3(Y)
G2(W)
R
C
G 2
G 3
G
VR
Y 1
W1
Page 10
Thermostat
24vac
24 Volt Water Valve
24 Volt Relay to Control Strip Heater
R
H2O
Troubleshooting
14
SYMPTOM: The fan will not run in all three speeds or switches speeds in an improper order. CAUSE: Incorrect wiring between the thermostat and the relay board, or between the relay board and the fan wires. REMEDY:Recheckthewiring(G=lowspeed,G2=mediumspeed,G3=high speed).
SYMPTOM:Coldwatervalveopensforeitheracooloraheatdemandina4-pipe system. CAUSE: The thermostat has been programmed for the incorrect type of fan coil. REMEDY: Confirm that you have entered the correct programming for your type offancoilsystem(steps#3and#4,page11oftheOwnersManual).
SYMPTOM:Thewatervalvedoesnotopenatallin2-pipeconfigurations. CAUSE: The thermostat has been programmed for the incorrect type of fan coil system or the fan coil is not wired to the thermostat correctly. REMEDY:Programthethermostatfora2-pipefancoil(step#3,page11of theOwnersManual).Also,makecertainthatthewatervalveiswiredtotheY1 terminal.
SYMPTOM:Partsofthethermostatdisplayaremissing. CAUSE: The thermostat has been programmed for a minimal display. REMEDY:ProgramthethermostatforFullDisplay(step#1,page10ofthe OwnersManual).
SYMPTOM: The thermostat displays large setpoint digits instead of the room temperature. CAUSE: The thermostat has been programmed to display Single Setpoint. REMEDY:ProgramthethermostattodisplayDualSetpoint(step #2, page 10 of the Owners Manual).
15
Troubleshooting
SYMPTOM:ThethermostatdisplayisstuckinUnoccupied. CAUSE:ThesensorconnectedtotheDryContactterminalsofthethermostat,is active,forcingtheunitintoUnoccupied. REMEDY: Verify proper wiring between the thermostat and the occupancy sensor and verify that the wiring is not shorted. If no sensor is connected, program the DryContactpolarityforNormallyOpen(step #11, page 13 of the Owners Manual).
SYMPTOM:ThethermostatwillonlyallowHeatorOffin2-pipeinstallations, even though chilled water is available. CAUSE:Faulty,improperlywired,orimproperlyinstalledH2Ochangeoversensor. REMEDY:Confirmproperwiringofthechange-oversensor(betweenRand H2O).Confirmproperplacementofthesensor(goodmechanicalcouplingfor temperaturetransfer). Test the changeover sensor as follows: 1.Removepowerfromthefancoilsystem. 2.DisconnectthewirebetweenthesensorandtheH2Oterminal. 3.PlaceanohmmeterbetweenRandthewirejustdisconnectedfromthesensor. 4.Agoodsensorwillshowcontinuitywheneverthewatertemperatureis confirmedtobeatorbelow65degrees.Ifthesensorisopenwhenthewater temperatureisconfirmedtobeatorbelow65,replacethesensor.
Technical Specifications
16
XXXXX Series Thermostat Controllers Power Requirements 20 - 30 VAC 50/60 Hz, 3 VA @ 24V nominal.
Valve Outputs 0.8A max, 0.01A min, 3A inrush, 20 - 30 VAC Fan Outputs 0.4A max, 0.01A min, 3A inrush, 20 - 30 VAC
voltage free contacts, closed to signal CHILLED water supply
voltage free contacts, closed to alter setpoints
solid state temperature sensor, 10 mV / degF
16 AWG (100 ft max) to 24 AWG (36 ft max)
35 to 99 deg F (2 to 36 degC)
35 to 65 deg F +/- 3 degF, greater than 65 to less than 80 degF +/- 2 degF, 80 to 99 degF +/- 3 degF, greater than 99 to 104 degF +/- 5 degF
Adjustable 1 to 6 deg first stage, fixed 1 degree for med/hi fan speeds
35 to 104 degF (2 o 40 degC), 5 - 95% RH non-condensing, 86 degF max dew point
-22 to 122 degF (-30 to 50 degC), 5-95% RH non-condensing, 86 degF max dew point
UL/cUL listed, file E107041, NEC Class 2
3.14 H x 3.14 W x 1.1 D
0.25 kg
Output Rating
Digital Inputs H2O
CK1
Local Temperature Sensor Type
Temperature Adjustment Range
Accuracy
Wire Size
Deadband
Operating
Storage
Ambient Conditions
Compliance
Dimensions
Shipping Weight
This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.
United States
Canada
North American Emissions Compliance
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numerique de la Classe (B) respecte toutes les exigences du Reglement sur le materiel brouilleur du Canada.
Fan Coil Series Thermostat Controllers
Printed on recycle
Related manuals for Carrier Airstream 42C 33CSSN3 FC Installation Instructions
Manualsnet FAQs
If you want to find out how the Airstream 42C 33CSSN3 FC Carrier works, you can view and download the Carrier Airstream 42C 33CSSN3 FC Installation Instructions on the Manualsnet website.
Yes, we have the Installation Instructions for Carrier Airstream 42C 33CSSN3 FC as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.
The Installation Instructions should include all the details that are needed to use a Carrier Airstream 42C 33CSSN3 FC. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.
The best way to navigate the Carrier Airstream 42C 33CSSN3 FC Installation Instructions is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.
This Carrier Airstream 42C 33CSSN3 FC Installation Instructions consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.
You can download Carrier Airstream 42C 33CSSN3 FC Installation Instructions free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.
To be able to print Carrier Airstream 42C 33CSSN3 FC Installation Instructions, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier Airstream 42C 33CSSN3 FC Installation Instructions as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.