Carrier 33CONNECTSTAT43 Installation Guide PDF

1 of 52
1 of 52

Summary of Content for Carrier 33CONNECTSTAT43 Installation Guide PDF

Carrier Connect Wi-Fi Thermostat 33CONNECTSTAT43

Installation Guide

CARRIER CORPORATION 2021 Catalog No. 11-808-728-01 1/22/2021

Verify that you have the most current version of this document from www.hvacpartners.com or

www.accounts.ivusystems.com or your local Carrier office.

Important changes are listed in Document revision history at the end of this document.

CARRIER CORPORATION 2021. All rights reserved throughout the world. i-Vu is a registered trademark of Carrier

Corporation. All other trademarks are the property of their respective owners.

Contents What is the Carrier Connect Wi-Fi Thermostat? ..................................................................................................... 1

Specifications ........................................................................................................................................................ 1

Wiring the Carrier Connect Wi-Fi Thermostat ..................................................................................................... 2 To wire the thermostat to equipment ................................................................................................................ 2 To wire and mount the thermostat .................................................................................................................... 4 To connect a remote input (sensor or contacts) .............................................................................................. 6 To wire for BACnet communication ................................................................................................................... 8

Registering and setting up a mobile device for enhanced access .......................................................................... 9 Using the Connect website or app .................................................................................................................. 10

Configuring the system ............................................................................................................................................. 13 To configure advanced SYSTEM SETTINGS.................................................................................................... 14

Operating your system using the Carrier Connect Wi-Fi Thermostat .............................................................. 22 Occupancy ........................................................................................................................................................... 22 Supply fan ........................................................................................................................................................... 22 Cooling ................................................................................................................................................................. 23 Econ enable ........................................................................................................................................................ 23 Heating ................................................................................................................................................................ 23 Dehumidification ............................................................................................................................................... 24 Humidification .................................................................................................................................................... 25 Filter status ......................................................................................................................................................... 25 Holidays ............................................................................................................................................................... 25 BACnet integration ............................................................................................................................................ 25

Using the Carrier Connect Wi-Fi Thermostat's screens .................................................................................... 26 HOME ................................................................................................................................................................... 26 SETPOINT ............................................................................................................................................................ 27 MODE ................................................................................................................................................................... 28 SETTINGS ............................................................................................................................................................ 28 HUMIDITY ............................................................................................................................................................ 28 FAN ....................................................................................................................................................................... 30 PROGRAM ........................................................................................................................................................... 30 HOLIDAY .............................................................................................................................................................. 31 BANNER ............................................................................................................................................................... 31 DATE and TIME ................................................................................................................................................... 31 SOFTWARE screen and BACKLIGHT screen .................................................................................................. 32 ADVANCED .......................................................................................................................................................... 32 FILTER .................................................................................................................................................................. 33 LOCKOUT ............................................................................................................................................................. 33 CLEAN .................................................................................................................................................................. 33 LOG....................................................................................................................................................................... 34 STATUS ................................................................................................................................................................ 34 SERVICE ............................................................................................................................................................... 34

Installation test .......................................................................................................................................................... 35

Troubleshooting ......................................................................................................................................................... 36 Outputs based on demand and configuration .............................................................................................. 36 Fault definitions ................................................................................................................................................. 37 Recovering from a power outage .................................................................................................................... 38 Resetting wi-fi access ....................................................................................................................................... 39 Compliance ......................................................................................................................................................... 40

FCC Compliance .................................................................................................................................. 40 BACnet Compliance ............................................................................................................................. 40

Contents

Appendix: BACnet Points List .................................................................................................................................. 41

Document revision history ........................................................................................................................................ 46

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

1

The Carrier Connect Wi-Fi Thermostat (Part #33CONNECTSTAT43) is a thermistor-based wireless thermostat

that can sense a 10K Type II OAT or a remote space or return air sensor and can control up to 4 heating and 3

cooling stages.

The Carrier Connect Wi-Fi Thermostat package includes:

Thermostat

Mounting Hardware - two screws with drywall anchors and one security screw

Quick Start Guide - Catalog No. 11-808-729-01

Some of the features:

Supporting standard air conditioning and heat pump rooftop and split units

7-day scheduling with up to 4 periods per day

Holiday scheduling

Full-color touchscreen thats easy to navigate

Remote programming and monitoring using secure Apple or Android mobile app or Web portal

Text and email service alerts

Automatic software updates via Wi-Fi

Specifications

Power requirements 24 Vac +/- 10% @ 3VA

Network Requirements Wi-Fi connectivity supports Wi-Fi: 802.11 a/b/g/n standards on 2.4 GHz networks

Environmental

operating range

32 to 104F (0 to 40C), 10 to 95% relative humidity, non condensing

Mounting Standard 4 x 2 in. electrical box using the 6-32 x 1/2 in. mounting screws provided

Overall dimensions Width:

Height:

Depth:

5.13 in. (13 cm)

3.23 in. (8.2 cm)

0.94 in. (2.4 cm)

BACnet Support Conforms to the BACnet Application Specific Controller (B-ASC) Device Profile as defined

in ANSI/ ASHRAE Standard 135-2012 (BACnet) Annex L, Protocol Revision 14

Listed by FCC Part 15, Subpart J compliant

What is the Carrier Connect Wi-Fi Thermostat?

Wiring the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

2

To wire the thermostat to equipment

Packaged Rooftop Units

Hydronic Fan Coil

Wiring the Carrier Connect Wi-Fi Thermostat

Wiring the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

3

Dual fuel systems (Furnace &heat pumps)

Furnace/AC System

Water Source Heat Pump

Air Handler or DX Fan Coil/AC Split System

Wiring the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

4

Air Handler or DX Coil/Heat Pump split system

To wire and mount the thermostat

1 Turn off 24 Vac power at the equipment circuit breaker or the system switch.

2 Place the thermostat base against your wall to mark drill holes.

3 Drill the anchor holes or use existing holes to mount the wallplate.

Drywall Drill 3/16 in. hole for the anchor.

Plaster Drill 7/32 in. hole for the anchor.

4 Pull wires through opening in base.

Wiring the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

5

5 Attach the base to the wall with the provided screws.

6 Straighten the wires and match your wire configuration to the terminals on the base.

7 Connect each wire individually by pushing down on the quick connect tab, inserting it into the connector

opening, and then releasing the tab.

Wiring the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

6

8 Attach the thermostat face by aligning it with the hinge guide on top of the back.

9 Turn on the 24 Vac power. The thermostat displays the HOME screen. See HOME (page 26) for details.

10 Configure your system as described in this document.

To connect a remote input (sensor or contacts)

NOTE Use the specified type of wire and cable for maximum signal integrity.

Power N/A

Description Stranded, twisted pair

Conductor If < 100 ft (30.5 meters) 22 AWG, unshielded

If > 100 ft (30.5 meters) 22 AWG, shielded

Maximum length 500 feet (152 meters)

Insulation Plenum rated

Thermistor 10K Type II (CP/MCI)

Wiring the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

7

Use Remote Sensor input terminals S1 and S2 for the following inputs:

OAT

T55

SAT

Occupancy contacts

Econ Fault

Wiring for space temperature sensor averaging

4 sensors

Wiring the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

8

9 sensors

To wire for BACnet communication

NOTE Use the specified type of wire and cable for maximum signal integrity.

Cable 22 or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire

Maximum length 2000 feet (610 meters) per segment

Baud rate 9600 bps, 19.2 kbps, 38.4 kpbs, or 76.8 kbps, 115.2 kbps

Connect communication wiring to terminals A+ and B-. Do not terminate shield at the thermostat.

CAUTION Maintain the same polarity.

NOTE For more networking details, see the Open Controller Network Wiring Installation Guide.

Registering and setting up a mobile device for enhanced access

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

9

Downloading the Connect App provides enhanced access to your device. The Connect App is available for

Apple IOS at App Store or at Google Play for Android devices. Search for Carrier Connect Thermostat.

NOTE Device compatibility: Apple IOS 7.0 or later or Android 4.2 or later

1 After downloading Connect App, select USER SETUP and Register New Account.

NOTE You can also register new accounts using the website connectstat.carrier.com.

2 Enter an email address that you can access on your mobile device and receive the confirmation email to

complete the registration process.

3 Select SETUP NEW THERMOSTAT and follow the Connect App instructions.

4 After registering the thermostat, enter servicing contractor's name and phone number on the SERVICE INFO

screen.

5 On the THERMOSTATS screen, select the thermostat from list and the mobile app's HOME screen appears.

Registering and setting up a mobile device for enhanced access

Registering and setting up a mobile device for enhanced access

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

10

Using the Connect website or app

After you register for an account, you can access the thermostat by using the app directly or through the Web at

connectstat.carrier.com.

You can:

Monitor the thermostat operation

Set up occupied and unoccupied (holiday) schedules

Adjust setpoints

Share thermostat access with other users

Create groups of thermostats that you have registered

Create groups of thermostats that other owners have shared with you

Get online product information

Find local dealer support

To navigate

On a touchscreen device, use any of the following:

swipe the screen

tap the arrow on the side

tap a dot on the bottom of the screen on either side of the HOME button

On a non-touchscreen device, click on the gray arrow on either the side of the screen.

You can press or click to access the following drop-down list:

My Systems

My Account

Shared Systems

Product Information

Find and Expert

Logout

1 After logging in, a list appears of thermostats that you have registered and that have been shared with you.

2 Click .

Registering and setting up a mobile device for enhanced access

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

11

3 Swipe or click to navigate to the SETTINGS screen.

NOTES

Navigate by clicking or pressing the buttons such as SETPOINTS, FAN, PROGRAM, etc..

Grayed out function buttons indicate that feature is not being used on the thermostat.

Screens Use to...

SETPOINTS Adjust the occupied and unoccupied setpoints by selecting each temperature.

FAN View and modify fan settings.

The default setting for fan operation is AUTO for both Occupied and Unoccupied periods.

When operating in AUTO MODE, the fan only runs when there is an active heating or

cooling demand.

When you select ON, the fan runs continuously, except during the Blower On Delay when

a heat cycle is starting. There is a 30-second minimum on/off timer when changing the

FAN MODE.

NOTE The following selections are not available if the thermostat has been configured for non-programmable

operation.

HUMIDITY Adjust the thermostat's humidify and dehumidify setpoints.

PROGRAM You can:

Set Occupied and Unoccupied start times, depending on the configured number of

periods and the users security level.

Select the time at the bottom of the screen to adjust the start or stop time of each

period in 15 minute increments.

Select Copy to apply that schedule to other days of the week.

Adjust the setpoints for each period.

Registering and setting up a mobile device for enhanced access

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

12

Screens Use to...

HOLIDAY Set HOLIDAY (same as unoccupied) periods with the following options:

Length of time from 1 to 365 days

Same day of each week of the month

Specific day of specific week(s) of the month

NOTE Requires advanced security level to edit these settings

Select +ADD HOLIDAY to add start month, day, and number of days.

Select ADVANCED to configure same day of each week(s) of that month.

To delete a holiday on the:

Mobile app - swipe the selected holiday to the left and select Delete

Web app - select x on right side of the holiday

SETTINGS Enter the name and location of the thermostat for the users reference. The user can enter

an email address for alerts and a mobile phone number to receive text alert messages.

NOTE Requires advanced security level to edit these settings.

ALERTS Displays a list of alerts that have been flagged in the thermostat.

SERVICE Displays the name and phone number of the service company or individual who is

responsible for servicing the system.

NOTE Requires advanced security level to edit these settings.

Configuring the system

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

13

1 On the thermostat, not a mobile device, swipe the HOME screen twice to the left to navigate to the MODE

screen and ensure the MODE is OFF.

NOTE The yellow line above a button indicates the current MODE.

2 Swipe to go to the FAN screen and then press and hold the Fan Button for 5 seconds to get to the

SYSTEM SETTINGS screen.

NOTE You can ONLY access the SYSTEM SETTINGS screens from the thermostat itself, not the app or web.

3 Enter the 3-digit security PIN code, if applicable, to open the SYSTEM SETTINGS screen.

4 Use the advanced options on the SYSTEM SETTINGS screens to configure and setup your system, change,

and view options.

NOTES

The yellow Row Indicator at the right side of the screen indicates the current location in the list of

advanced settings options. Swipe up or down to navigate through options and then tap to select one.

Swipe on any of the SYSTEM SETTINGS sub-screens to return to the SYSTEM SETTINGS main screen.

Configuring the system

Configuring the system

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

14

To configure advanced SYSTEM SETTINGS

You can only adjust the SYSTEM SETTINGS screens and parameters on the thermostat itself. You cannot access them on a

mobile device.

You can select FACTORY DEFAULTS to restore all default settings to the original values.

Parameter Name/Description Default and Range

HEAT EQUIP TYPE The equipment heating type. If you select GAS HEAT and the

COMPRESSOR TYPE for HP, then the defined DUAL FUEL thermostat operation is used

for heating.

D:

R:

GAS HEAT

GAS HEAT/ELECTRIC

HEATING EQUIP STAGES The number of gas heating stages or E- heating stages in the

equipment

NOTE If set to 2, the W2 relay output is not available for optional functions, such as

Humidifier

Humid-MiZer dehumidification

Occupancy Output

D:

R:

1

1 to 2

COMPRESSOR TYPE The type of the unit's compressors(s)

NOTE Select HP for the HEAT EQUIP TYPE to define the auxiliary heat type.

D:

R:

A/C

NONE, A/C, HP

COMPRESSOR STAGES The numbers of compressors

NOTES

If COMPRESSOR TYPE is set to HP, the number of stages also defines the number of

HP heating stages.

If set to 3, the Y3 relay output is used for the third-stage compressor and the

thermostat configuration is limited for the following:

Humidifier

Humid-MiZer dehumidification

Occupancy output

D:

R:

2

NONE, 1 to 3

AUTO ALLOWED Enables and disables the thermostat to automatically switch from

heating to cooling to maintain the temperature between the setpoints.

D:

R:

YES

YES/NO

PROG OR NON-PROG Allows the thermostat to operate as a non-programmable

(simplified) thermostat or a programmable thermostat with two or four time periods per

day.

D:

R:

PROG

PROG / NON-PROG

MAX HOLD TIME The thermostat setpoints cannot be overridden by the user. When the

SCHEDULE PAUSED button is pressed on the SETPOINTS screen (SCHEDULE IS

RUNNING), and the user changes the setpoint, the MAXIMUM TEMPORARY HOLD TIMER

is started with this value and displayed in the clock location.

D:

R:

2 hours

OFF

1 - 6 hours

FAHRENHEIT OR CELSIUS The temperature scale D:

R:

F

F/C

Configuring the system

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

15

Parameter Name/Description Default and Range

SMART RECOVERY Transitions the conditioned space from one programmable

temperature period to the next with 1F increments of the heating setpoint or with 1F

decrements of the cooling setpoint, so that by the time the next period starts, the

setpoints are at the desired temperature. The purpose of the gradual transition is to use

less energy by preventing staging up (because of a higher demand) to higher stages. The

transitions occur in a linear fashion over the smart recovery time period.

If you start a temporary hold in the middle of a smart recovery, the setpoints of the

temporary hold are used.

If a temporary hold is already active during the time that smart recovery would have

been started, a smart recovery does not start.

If the temporary hold ends in the middle of what would have been a smart recovery,

the smart recovery starts where it would have been in the linear progression at the

same time as when the temporary hold was not active.

D:

R:

30

NO, 30, 60, 90 MIN

FAN ON WITH W Supplies a fan output demand as soon as a W1 or W2 output

demand is active.

D:

R:

YES

YES/NO

REVERSING VALVE Defines whether the ON state of the reversing valve is used for

heating or cooling when COMPRESSOR TYPE is set to HP.

When the ON state of the reversing valve is used for cooling, the signal is typically

referred to as a O.

When the ON state of the reversing valve is used for heating, the signal is typically

referred to as a B demand.

If COMPRESSOR TYPE is set to HP, the thermostat configuration may be limited for

the following:

Humid-MiZer dehumidification

Humidifier operation

Occupancy output

D:

R:

COOL

COOL/HEAT

SPACE TEMP OFFSET Calibrates the internal space temperature sensor. D:

R:

0F

-5 to 5F

SPACE HUM OFFSET Calibrates the internal relative humidity sensor. D:

R:

0%

-9 to 9%

AUTO CHANGEOVER The minimum time between switching from heat-to-cool or from

cool-to-heat demands, when in AUTO MODE. The timer begins when the MINIMUM OFF

TIMER expires.

D:

R:

30 MIN

5, 10, 15, 20, 25, 30 MIN

Configuring the system

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

16

Parameter Name/Description Default and Range

REMOTE SENSOR Determines whether the remote sensor hardware input is:

NONE Not used

NONE or SPACE The outdoor temperature is acquired by Wi-Fi through the server,

based on the location of the mobile device used to connect the thermostat to a

router, or based on the ISP location, if a computer connects the thermostat to a

router.

OUTDOOR Senses the outdoor temperature

NOTE The outdoor temperature is not available if the thermostat is not connected to

Wi-Fi or if you do not select OUTDOOR.

AVERAGE Space temperature results from averaging the internal and the external

sensor

OCCUPANCY An external source is accessed to determine if the setpoints are

Occupied or Unoccupied. When Normally Open contacts close, the Occupied

setpoints are used.

NOTE When selected, NON-PROG is automatically set and is not displayed in the

Installer Settings until this parameter is changed.

FAULT INPUT An external source is used to detect a fault, as determined by the

attached Economizer.

SAT A sensor to provide a means of monitoring supply air temperature

NOTE SAT is a monitor-only point and has no effect on unit operation.

D:

R:

NONE

NONE

SPACE

OUTDOOR

AVERAGE

OCCUPANCY

FAULT INPUT

SAT

SAT TEMP OFFSET Allows temperature offsets from -5 to 5.

NOTE Only available when Remote Sensor Input > SAT is enabled.

D:

R:

0F

-5 to 5F

(1 increments)

MAX SETPOINT ERROR Allows a temperature deviation from setpoint of between 2 and

30, to determine fault conditions (ID TEMP RANGE HIGH or LOW).

NOTE This value is added to the cooling setpoint or subtracted from the heating

setpoint.

D:

R:

10F

2 to 30F

(1 increments)

ID TEMP FLT INHIBIT Allows a time delay applied to the ID TEMP fault. The range is

adjustable from 10 to 240 minutes (60 default).

NOTE Allow for recovery time when transitioning from unoccupied to occupied periods.

D:

R:

60 mins

10 to 240 mins

(10 min increments)

COOL LOCKOUT Delays the cooling equipment demands if the outdoor air temperature

is below the selected value. There is a SYSTEM EVENT warning if the mode and space

temperature dictate that there should be a cooling demand and the outdoor temperature

is preventing this demand.

D:

R:

55F

OFF

0 to 80F

(5F increments)

LOW COOL LOCKOUT (Heat pump operation only) Enables the thermostat to start all

cooling stages on a demand for cooling based on the configured value. Normal cooling

always starts with first stage compressor (Y1) and stages up to the second (Y2), when

the demand is sufficient and staging and cycle timer constraints are satisfied.

If the outdoor temperature is equal to or greater than the configured value of 80 to

110F, all stages of cooling are energized. If set to ON, all stages are energized on a call

for cooling. The outdoor temperature must also be greater than the COOL LOCKOUT

value. When a cooling cycle starts under a high cool latch, it finishes the cooling cycle on

HIGH STAGE. If the cooling equipment is energized to satisfy a dehumidify demand only

(no cooling demand), the latch is not applied.

D:

R:

OFF

OFF

80 to 110F

(5F increments)

ON

Configuring the system

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

17

Parameter Name/Description Default and Range

LOW HEAT LOCKOUT (Heat Pump operation only) Enables the thermostat to start all

compressor heating stages on a demand for heating, based on the configured value.

When the COMPRESSOR TYPE is set to HP and compressor heat is requested, it always

starts with the first compressor stage (Y1) and stages up to second stage (Y1 and Y2)

when the demand is sufficient and staging and cycle timer constraints have been

satisfied.

If the outdoor temperature is equal to or less than the configured value of 20 to 50F,

both the first and second stages of the compressor are energized to satisfy all heat

pump heating demands. If set to ON, both compressors are energized on a call for

heating. The outdoor temperature must also be greater than the HP LOCKOUT value.

When a cycle starts under a high heat latch, it finishes the heating cycle on HIGH STAGE.

D:

R:

OFF

20 to 50F

(5F increments)

ON

TIME BETWEEN FUEL TYPES The minimum time limit between switching from one fuel

type to another (other staging rules may also be in effect). Use only if the COMPRESSOR

TYPE is set for HP.

D:

R:

15 MIN

10, 15, 20, 25 MIN

CYCLE TIMER The maximum number of heat cycles per hour D:

R:

4

2, 4, 6, 8

HUMIDIFIER The output relay enables a field-installed humidifier. The humidifier is on

if there is humidity demand and any heating equipment is on. If set to YES, the

thermostat cannot be configured for Humidi-MiZer or Dehumidification. See

HUM/DEHUM OUTPUT in this table for output relay details.

D:

R:

NO

YES/NO

DEHUMIDIFIER Sets the output relay to enable a factory-installed Humidi-MiZer for

dehumidification or to use the first stage of cooling.

If HUMDIMIZER, the output relay energizes the Humidi-MiZer on the Carrier unit.

If YES, the Y1 relay is energized. A new space temp setpoint is calculated to force

cooling operation.

NOTE For details about this calculation, see HUMIDITY (page 28).

If OVRCL(2), it uses the first stage of cooling to satisfy a dehumidification demand,

but will not overcool the space by more than 2F.

If dehumidification is configured, the thermostat cannot also be configured for a

humidifier. Additional optional functions may be limited, based on the flex outputs

available.

D:

R:

NO

NO

YES

OVRCL(2)

HUMDIMIZER

MAX HEAT SETPOINT The maximum heating setpoint available on the Heat Setpoint

Wheel and the maximum heating setpoint that can be used during the occupied program

schedule

D:

R:

88F

50F to 88F

MIN COOL SETPOINT The minimum cooling setpoint that is available on the Cool

Setpoint Wheel and the minimum cooling setpoint that can be used during the occupied

program schedule

D:

R:

52F

52 to 90F

AUX HEAT LOCKOUT The outdoor temperature value that lockouts the auxiliary heat. If

the AUX HEAT LOCKOUT temperature setting is not OFF, and the outdoor air temperature

is greater than AUX HEAT LOCKOUT value, then the Aux Heat (W1 and W2) outputs are

not energized. Once the output is energized, it remains energized until the demand

algorithm no longer requires the capacity of the auxiliary heat, regardless of the value of

the outdoor air temperature.

NOTE If the MODE is emergency heat (E-HEAT), the auxiliary heat is allowed to be

energized regardless of the outdoor temperature.

D:

R:

OFF

OFF

5 to 55F

(5F increments)

Configuring the system

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

18

Parameter Name/Description Default and Range

HP LOCKOUT If you select OFF, the heating equipment cycle always starts with the heat

pump, regardless of the outdoor air temperature.

If you select a lockout temperature and the outdoor air temperature is less than the

selected temperature, the heating cycle is started with the AUX HEAT source.

If the outdoor air temperature is equal to or greater than the selected temperature,

the heating cycle is started with the heat pump.

If the outdoor temperature is not available, all heating cycles start with compressor

heat. Once the heat pump is energized, it remains energized until the heating

demand no longer requires heat pump heating, regardless of the outdoor air

temperature.

When the heat pump is not energized, but there is sufficient demand to request heat

pump heating, the heat pump lockout temperature is checked against the outdoor

air temperature, and if the outdoor air temperature is greater than the heat pump

lockout temperature, the heat pump is energized.

D:

R:

OFF

OFF

5 to 55F

(5F increments)

STAGE DELAY The minimum amount of time the current stage must be energized

before staging up to the next stage of capacity.

NOTE If the system demand is greater than 3F, then this configuration is ignored for

the current heating or cooling cycle because the staging timers are canceled to allow full

equipment capacity to meet the large demand.

D:

R:

10 MIN

2 MIN to 15 MIN

FORCED STAGE UP The amount of time another stage of heat or cool is enabled if the

space temperature conditions are not improving. If the time in a current demanded stage

reaches the selected forced stage-up time, the thermostat stages up to the next

available stage of capacity, even if DIFFERENTIAL demand is not met.

D:

R:

30 MIN

OFF

10 MIN to 120 MIN

(10 minute increments)

DIFFERENTIAL The required difference between the current space temperature and

the setpoint, before demand is initiated. This value is additive for each new stage of

equipment being demanded.

EXAMPLE A chosen DIFFERENTIAL value of 0.5F requires 0.5F difference between

setpoint and space temperature before first stage is turned on. Then, 1F of difference

between setpoint and space temperature is necessary before the second stage is turned

on.

D:

R:

1.0F

0.3 to 2.0F

(0.1F increments)

AIR FILTER REMINDER The number of hours before a SYSTEM EVENT reminds the

occupant to change the indoor air filter.

If set to OFF, a SYSTEM EVENT will not occur to remind the homeowner to change

the indoor air filter.

Decrements to the timer happen each hour of total equipment runtime.

Minutes are not stored in non-volatile memory, so a power reset clears out the

minutes within each hour of run time.

Once the number of hours is initially set or later changed, the filter timer must be

reset on the SETTINGS screen.

D:

R:

3000 HRS

OFF

500 HRS to 15000 HRS

(500 hour increments)

OCCUPANCY OUTPUT When set to ON-Y3, ON-O/B, or ON-W2, selected relay output

equals current Occupancy state. Can be used for ECON Enable.

NOTE The OCCUPANCY OUTPUT option is not displayed or available if Y3, O, and W2

relays are being used; i.e. Humidification/ Heat Pump/ 3-stage cooling/ etc..

D:

R:

OFF

OFF

ON-Y3

ON-W2

ON-O/B

Configuring the system

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

19

Parameter Name/Description Default and Range

OCCUPANCY INPUT This setting changes the current heating and cooling setpoints to

the option selected for MAX HOLD TIME. This occurs when the short is detected on the

Remote Space Sensor for the duration of 2 to 5 seconds.

D:

R:

Occupied

Occupied

Unoccupied

HUM OUTPUT Select which output to use for humidifier.

NOTE Only unassigned outputs are available.

D:

R:

OFF

ON-Y3

ON-O/B

ON-W2

DEHUM OUTPUT Select the unassigned output to use for dehumidifier (Humidi-MiZer).

NOTE Only unassigned outputs are available.

OFF

ON-Y3

ON-O/B

ON-W2

LINE FREQUENCY Used to increment operational timers within the thermostat to

ensure timing accuracy.

D:

R:

60HZ

50HZ

60HZ

DEALER NAME (Optional) This setting identifies the name of the installing contractor

and could be carried forward from the sensor if input through the local display.

DEALER PHONE (Optional) This setting identifies the phone number of the installing

contractor and can be carried forward from the sensor if input through the local display.

MSTP MAX MASTERS Used to identify max number of masters for token passing on

the MS/TP network.

D:

R:

127

1 to 127

MSTP BAUD RATE The protocol's baud rate (communication speed) on the MS/TP

network. The baud rate must be the same for all controllers on the network.

D:

R:

76800

9600

19200

38400

76800

115000

MSTP MAC ADDRESS Unique identifier for this thermostat on the MSTP network D:

R:

1

1 TO 127

BACNET UTC OFFSET Offset applied to UTC time D:

R:

5 hrs / 0 min

-13 to 13 hrs / 0 min

DEVICE ID Unique identifier for this thermostat within the system D:

R:

0

1 TO 4194302

DEVICE OBJECT NAME Assign an alpha-numeric string that is unique to the system. (Name)

DEVICE LOCATION (Optional) Use to provide details about thermostat location. (Location)

DEVICE DESCRIPTION (Optional) Use to provide additional details about this

thermostat. (Description)

Configuring the system

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

20

Parameter Name/Description Default and Range

BACNET BMS OCC Use to enable or disable BACnet occupancy control.

NOTE Occupancy is determined by 1 of 3 methods. You cannot have BACNET BMS OCC

with both PROGRAMMABLE MODE and REMOTE SENSOR set to OCCUPANCY. Setting

BACNET BMS OCC to YES forces PROG OR NON-PROG to NON-PROG and switches

REMOTE SENSOR to NONE if set to OCCUPANCY.

D:

R:

NO

YES

NO

BACNET CONFIG WRITE If YES, allows BACnet to write to GATED_WRITE points. See

Appendix BACnet Points List.

D:

R:

NO

NO

YES

NET GP OUT TIMEOUT Used to timeout Network General Purpose Outputs.

NOTES

Sets the maximum time to lapse between writes to the present_value property of the

output object before it returns to INACTIVE.

Accessible only if Y3, W2, or O/B output is available as a GP OUTPUT.

D:

R:

2 MIN

2 MIN

20 MIN

1 HR

UNLIMITED

NET GP Y3 MODE Controls the Y3 output over the BACnet network.

DISABLED sets the Present_Value of the BACnet object to INACTIVE and READ_ONLY

and the corresponding output relay will be in a de-energized state

Selecting ENERGIZE ACTIVE allows BACnet writes and energizes the output relay

when the Present_Value is ACTIVE.

Selecting ENERGIZE INACTIVE allows BACnet writes and will energize the output relay

when the Present_Value is INACTIVE.

D:

R:

DISABLED

DISABLED

ENERGIZED ACTIVE

ENERGIZED INACTIVE

NET GP W2 MODE Controls the W2 output over the BACnet network.

DISABLED sets the Present_Value of the BACnet object to inactive and read-only and

the corresponding output relay will be in a de-energized state.

ENERGIZED ACTIVE allows BACnet writes and energizes the output relay when the

Present_Value is ACTIVE.

ENERGIZED INACTIVE allows BACnet writes and energizes the output relay when the

Present_Value is INACTIVE.

D:

R:

DISABLED

DISABLED

ENERGIZED ACTIVE

ENERGIZED INACTIVE

NET GP OB MODE Controls the O/B output over the BACnet network.

DISABLED sets the Present_Value of the BACnet object to inactive and read-only and

the corresponding output relay will be in a de-energized state.

ENERGIZED ACTIVE allows BACnet writes and energizes the output relay when the

Present_Value is ACTIVE.

ENERGIZED INACTIVE allows BACnet writes and energize the output relay when the

Present_Value is INACTIVE.

D:

R:

DISABLED

DISABLED

ENERGIZED ACTIVE

ENERGIZED INACTIVE

DISCONNECT WIFI Disconnects the thermostat from the Wi-Fi network.

CAUTION Disconnecting the Wi-Fi requires setting up the Connect Thermostat

using the Connect mobile application in order to re-establish Wi-Fi connectivity.

INSTALLATION TEST See Installation Test (page 35) for detailed instructions.

Configuring the system

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

21

Parameter Name/Description Default and Range

RESTORE DEFAULTS Press and hold the 5 button for 5 seconds to initiate and restore

all system setting defaults. Press the CANCEL button to go back to SYSTEM SETTINGS

screen.

Operating your system using the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

22

The thermostat supports the following types of constant volume units:

Standard heat/cool unit types with up to 3 stages of mechanical cooling, up to 2 stages of gas or electric

heating, and up to 4 stages for non-Carrier heat pumps

Heat pump units utilizing a reversing valve output for heating and cooling control

Carrier heat pump unit with an OEM defrost control board

NOTES

Humidification or dehumidification control strategies are available for appropriately equipped units.

The following configurations have interdependencies that may preclude the use of others:

Reversing valve

Third-stage cooling

Humidification

Dehumidification

Occupancy Output

The flex outputs, Y3, O, and W2, may be available for optional functions.

EXAMPLE In a single stage heating system, the W2 output could be used as the Occupancy output to

enable the ECON during occupied periods.

Occupancy

Configure the thermostat to operate in a programmable or non-programmable mode. Non-programmable operates

continuously in occupied mode. Programmable operates as a 7-day programmable thermostat for either 2 or 4

periods per day. You can set each period as occupied or unoccupied.

If you configure Smart Recovery for 30 to 90 minutes, the occupied start time increases up to the maximum time,

in order to bring the space to the occupied setpoints at actual occupied time.

Supply fan

Configure the supply fan for ON or AUTO, in either occupied or unoccupied mode.

ON Fan runs continuously regardless of demand

AUTO Fan cycles heat or cool demand if there is a demand for humidity or dehumidification

Operating your system using the Carrier Connect Wi-Fi Thermostat

Operating your system using the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

23

Cooling

The thermostat's application and configuration determine the specific cooling sequence. It can control up to 2

stages of cooling, with an additional output for a reversing valve, for non-Carrier heat pump applications, or up to

3 stages of cooling for non-heat pump applications.

NOTE The cooling stages are controlled based on a drift algorithm and the configurable DIFFERENTIAL value

(.5F default).

The following conditions must be true for the cooling to operate:

The OAT must be above the COOL LOCKOUT (55F default), if enabled

The cooling stage 5-minute minimum off-timer has expired

The space temperature has exceeded the cooling setpoint by the DIFFERENTIAL value (.5F default)

Additional stages are added and dropped, based on demand using the DIFFERENTIAL value, STAGE DELAY timer,

and FORCED STAGE UP timer configuration values. If the LOW COOL LOCKOUT is configured for ON, or between

80 and 110F, and the OAT is equal to or greater than that value, cool stages 1 and 2 are energized on a demand

for cooling and remain on until the cooling demand is satisfied.

NOTE Once a cooling stage is energized, it remains on for a minimum of 5 minutes, regardless of demand.

Econ enable

The thermostat's application and configuration determine the specific economizer enable sequence. You can

enable an output relay in OCCUPANCY OUTPUT. The output is ON whenever the thermostat is Occupied and OFF

when Unoccupied.

NOTE The relay options may be limited by other programming options such as Humidity control, Heat Pump, etc..

The status of the economizer may be monitored using a dry contact (N.O.) on the Remote Sensor Input.

Heating

The thermostat's application and configuration determine the specific heating sequence. It can control up to 4

stages of heating when configured for non-Carrier heat pump applications, or up to 2 stages of heating for non-

heat pump applications. When applied to a Carrier commercial heat pump, HEAT TYPE must be set to GAS. HEAT

TYPE set to ELECTRIC supports the Carrier 3-stage heat operation using 2 outputs. See Outputs based on demand

and configuration (page 36).

NOTE The heating stages are controlled, based on a drift algorithm and the configurable DIFFERENTIAL value

(.5F default).

Operating your system using the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

24

The following conditions must true for heating to operate:

The OAT must be below the HEAT LOCKOUT (55F default), if enabled

The heating stage 5-minute minimum off-timer has expired

The space temperature has exceeded the heating setpoint by the DIFFERENTIAL value (.5F default)

Additional stages are added and dropped, based on demand, using the DIFFERENTIAL value, STAGE DELAY timer,

and FORCED STAGE UP timer configuration values. If the LOW HEAT LOCKOUT is configured for ON, or between

20 and 5F, and the OAT is equal to or less than that value, heat stages 1 and 2 are energized on a demand for

heating and remain on until the heating demand is satisfied.

NOTE Once a heating stage is energized, it will remain on for a minimum of 5 minutes, regardless of demand.

Dehumidification

There is occupied and unoccupied dehumidification on units that are equipped with the Carrier Humidi-MiZer

from the factory, or by energizing the first stage of cooling and over-cooling by 2F.

The following conditions must be true for dehumidification to operate:

For the Humidi-MiZer option, DEHUMIDIFY must be set to HUMIDIMIZER

For over-cooling, DEHUMIDIFY must be set to OVRCL 2F

For non-Humidi-MiZer units, DEHUMIDIFY must be set to YES and must not have an active call for heating

or cooling

Setpoint range is 35 to 65%

Humidity must be 2% greater than the dehumidify setpoint

Dehumidification ends when DEHUMIDIFY is set to:

HUMIDIMIZER and humidity drops 3% below the dehumidify setpoint

OVRCL2 and space temperature drops below the cooling setpoint by more than 2F

YES and space temperature drops below the calculated setpoint or there is a demand for heat or cool.

NOTE For details about this calculation, see HUMIDITY (page 28).

Operating your system using the Carrier Connect Wi-Fi Thermostat

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

25

Humidification

There is occupied and unoccupied humidification on units that are equipped with humidifiers.

The following conditions must be true for humidification to operate:

HUMIDIFIER must be set to YES

Must be in heating mode

Setpoint range is 15 to 50%

Humidity must be 3% less than the humidify setpoint

Humidification ends when the humidity rises 3% above the humidify setpoint or the heating demand is satisfied.

Filter status

FILTER STATUS is based on a supply fan runtime, which you can configure from 500 to 3000 hours. A filter status

alert displays when the filter timer exceeds the configured number of hours. Press to see message.

Holidays

There is a maximum of 24 holiday periods. You can program each holiday period based on a start and stop month

date, or day of the month and week, with duration up to 365 days. The holiday schedule uses the first unoccupied

period setpoints for temperature control.

BACnet integration

There are two points that act as gateways, allowing or prohibiting BACnet writes to configuration items (BACNET

CONFIG WRITE) and occupancy control (BACNET BMS OCC). These variables are only accessible via the local

screen.

See To configure advanced SYSTEM SETTINGS (page 14) for BACnet set-up and control.

A write to the Active Heat or Cool Setpoint (AV:409 or AV:410) places the thermostat into temporary override. This

override will remain in effect until the MAX Temperature Hold Time (AV:502) expires. Default is 2 hours.

Long-term setpoint adjustment is accomplished by writing to the baseline setpoints (AV:400- AV:403).

Using the Carrier Connect Wi-Fi Thermostat's screens

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

26

HOME

The HOME screen is typically what the end user sees.

Screen functions

Banner

Press the center of the scrolling Banner to switch to the screen indicated by the displayed text. You can

swipe the banner to change options, or, every 3 seconds, a different screen name scrolls across the top

that you can navigate to.

NOTE On the thermostat itself, you can select those screens on the SYSTEM SETTINGS > BANNER

screen.

Page Indicator You can tap the HOME icon at any time to go to the HOME screen. You can either swipe

or tap the dots to the left or right to navigate. The dot turns from gray to white to indicate the page you are on.

Wi-Fi Signal

The more green bars, the stronger the signal

Red indicates it is not currently connected to a router

Pressing the Wi-Fi Signal displays a screen with connectivity details

Space Temperature The center portion of the screen displays the sensed space temperature, in whole

numbers only. Fahrenheit is the default scale but you can change to Celsius in SYSTEM SETTINGS. See To

configure advanced System Settings (page 14).

Using the Carrier Connect Wi-Fi Thermostat's screens

Using the Carrier Connect Wi-Fi Thermostat's screens

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

27

Equipment Status This button is static except when equipment is being activated and then it pulses on and

off.

If you tap the Fan mode/operation icons, the screen switches to the FAN screen.

If you tap the Heat or Cool icons, the screen switches to the MODE screen.

SETPOINT

Use this screen to view, adjust, or hold heat and cool setpoints. Use the wheels to adjust setpoints. Drag a wheel

up or down or tap the top or bottom of the wheel to increase or decrease by 1 increment.

There are 2 different buttons that can appear in the center of this screen. Press to switch buttons and functions.

OCCUPIED/UNOCCUPIED button

PLAY button allows you to either play (use as is) or alter the program schedule

Text on top of the button is the current state

Text beneath the button is what will happen when you press the button

If the schedule is running, the Occupancy button and the text display whether the schedule is currently running

OCCUPIED or UNOCCUPIED setpoints. Press the button to switch heat and/or cool setpoints between Occupied

and Unoccupied settings and then the Occupancy button changes to the PLAY button.

When the schedule is not running, the text above the Play button says OCCUPIED if the heat and cool setpoints

are the same as the OCCUPIED setpoints or UNOCCUPIED if the heat and cool setpoints match the Unoccupied

setpoints. If neither is true, HOLD displays. When the schedule is paused, the remaining hold time shows in the

lower right corner.

Using the Carrier Connect Wi-Fi Thermostat's screens

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

28

MODE

Use this screen to view and change the current MODE, including:

OFF

HEAT

COOL

AUTO

E- HEAT

NOTE The horizontal yellow bar always appears above the current mode.

The thermostat does not change until the newly selected MODE has been on for at least 10 seconds.

EXAMPLE

When changing the MODE from HEAT to COOL, the thermostat must first satisfy any Minimum ON Timer

requirements and then restart the Minimum OFF Timer that must expire before the equipment IS turned on in the

new MODE. Going from any HEAT or COOL to OFF, immediately shuts off any active equipment after the 10

second delay.

SETTINGS

Use this screen to change or view the options in the thermostat. The advanced SYSTEM SETTINGS screens are

only available from the thermostat. See To configure advanced SYSTEM SETTINGS (page 14).

Press a button or scroll the vertical yellow Row Indicator to see more buttons. When you press a button, the

corresponding screen appears so you can view status and make adjustments.

HUMIDITY

To adjust the thermostat's humidify and dehumidify setpoints:

Drag the wheel up or down

Tap the top of the wheel to decrease the setpoint by 1%

Tap the bottom to increase the setpoint by 1%.

Using the Carrier Connect Wi-Fi Thermostat's screens

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

29

If cooling equipment is not available, COOL TO DEHUMIDIFY is not adjustable on the thermostat and the blue

Dehum Setpoint wheel is not adjustable.

HUMIDIFY not adjustable on the thermostat (the orange Hum Setpoint wheel is not adjustable) unless

configured to use one of the following outputs:

O/B

Y3

W2

DEHUMIDIFY = YES When humidity is above the dehumidify target, the cooling setpoint is adjusted downward,

increasing cooling demand, according to the equations in the following table, when you select YES for

DEHUMIDIFY (not true for OVERCOOL (2) or HUMIDIMIZER selections).

Cooling Setpoint Algorithm

< = 70F Use the cooling setpoint only

70.1 - 74.9F Cooling setpoint = Cooling Setpoint (Cooling Setpoint - 70F) x (Dehumidify

Error / 10) with maximum dehumidify Error of 6% (i.e. use 6% if >6%)

> = 75 Cooling setpoint = Cooling Setpoint (Dehumidify Error / 2) with maximum

dehumidify Error of 6%

When cooling to dehumidify, the minimum ON timer increases to 5 minutes and the second stage (or greater) is

not started unless there is also a cooling demand.

OVERCOOL 2 commands the system to operate the compressor, within limits, when there is a dehumidification

demand, even if there is no cooling demand. The system may overcool up to 2F and no more, when satisfying a

dehumidification demand.

Humidi-MiZer

When configured as a HUMIDIMIZER output, and the humidity level is above the dehumidify target, 24V is output

at the selected terminal. When the humidity level is below the dehumidify target, 0 Vac is output on the selected

terminal. There is a +1/-4% hysteresis around the dehumidify target to prevent rapid on/off cycling of the selected

output.

This output may be connected to compressor outputs on commercial equipment. If the selected output is

energized without any compressors being energized, the 5-minute time guard must be enforced.

Use the following table to determine values for the terminal outputs to the equipment, when specific demands are

present.

NOTES

The value of X denotes that the setting may be Off or On, depending on the state of the FAN ON WITH W set

on advanced SYSTEM SETTINGS screen.

represents Y3, W2, or O/B, based on the item available and selected in HUM/DEHUM OUTPUT

configuration. See To configure advanced System Settings (page 14).

Using the Carrier Connect Wi-Fi Thermostat's screens

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

30

Y1 Y2 W1 W2 G

Fan Off Off Off Off On Off

Cool (1) On Off Off Off On Off

Cool (2) On On Off Off On Off

Dehumidify (HUMIDIMIZER) Off Off Off Off On On

Cool (1) and Dehumidify On Off Off Off On On

Cool (2) and Dehumidify On On Off Off On On

Heat (1) Off Off On Off X Off

Heat (2) Off Off On On X Off

Heat (1) and Humidify Off Off On Off X On

Heat (2) and Humidify Off Off On On X On

FAN

Use this screen to adjust fan operation. The default setting for fan operation is AUTO for both OCCUPIED and

UNOCCUPIED periods. When operating in AUTO MODE, the fan only runs when there is an active heating or cooling

demand. When you select ON, the fan runs continuously, except during the BLOWER ON DELAY when a heat cycle

is starting. There will be a 30-second minimum on/off timer when changing the FAN MODE.

These selections are not available if the thermostat has been configured for non-programmable operation.

CAUTION The AUTO selection is a violation of the ASHRAE 90.1 and California Title 24, but is a feature of

the thermostat for building owners that mandate auto fan operation during occupied periods for energy

conservation purposes.

PROGRAM

The top center of the screen displays the program schedule day of the week. Swipe up or down to move from one

day to the next on the program schedule. The vertical yellow Row Indicator moves up and down at the same time.

The horizontal blue lines show the cool setpoints above, for each of the 4 programmable periods of the day

(up to 3 occupied periods and 1 unoccupied period, if configured).

The horizontal red lines show the heat setpoints below, for each of the 4 programmable periods of the day.

Occupied and Unoccupied appear at the top of each period.

Using the Carrier Connect Wi-Fi Thermostat's screens

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

31

The vertical dashed lines separate the program time changes throughout the day.

The times at the bottom of the dashed lines show the schedule. Click on time to edit transition time.

The vertical yellow dashed line displays the current time of day.

The yellow lines show up only when viewing the current day of the week.

HOLIDAY

This screen displays the current year's holiday schedule. On a holiday, the setpoints for the first UNOCCUPIED time

range are used for the entire day. Scroll the vertical yellow Row Indicator to see more holidays. Click on the holiday

to make edits.

BANNER

Press the center of the scrolling Banner to switch to the screen indicated by the text. You can swipe the banner to

change options, or, every 3 seconds a different screen name scrolls across the top that you can navigate to.

On the thermostat itself, you can select which screens you want on the Banner by pressing the buttons to check

the ones you want and then uncheck the ones you do not want.

The default screens are:

DATE & TIME

FAN STATUS

OUTDOOR TEMP

COOL SETPOINT

HUMIDITY

HEAT SETPOINT

DATE and TIME

On this screen, scroll or tap the Orange Hour wheel or Blue Minute wheel to adjust the date and time on the

thermostat.

Switch to the Date Adjust screen and the Time Adjust screen using the green icon button at the right side of the

screen. Scroll or tap the Orange Month wheel or Blue Day wheel.

Drag a wheel up or down or tap the top or bottom of the wheel to increase or decrease by 1 increment.

Using the Carrier Connect Wi-Fi Thermostat's screens

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

32

When the thermostat is first registered and connected to a Wi-Fi router, both the date and time are synced with

the server (based on the location of the phone/tablet used to connect the thermostat to a router or based on the

ISP location if a computer is used to connect the thermostat to a router). The time and date are synced at the top

of each hour automatically, unless the Sync Time To Server option in the SETTINGS > ADVANCED screen is set to

NO.

SOFTWARE screen and BACKLIGHT screen

SOFTWARE Displays the current software's status.

BACKLIGHT Use to change the backlight intensity in Active and Dormant modes.

The blue Active Backlight wheel adjusts the backlight intensity from 10 to 100%, (75% is the default and

recommended) when the thermostat is in an active state (being accessed or viewed by the end user).

The purple Dormant Backlight wheel adjusts backlight intensity from 0 to 25%, (25% is the default and

recommended) when the thermostat is in a dormant state (not being viewed or adjusted by the end user).

Drag a wheel up or down or tap the top or bottom of the wheel to increase or decrease by 1 increment.

ADVANCED

Use this screen to access and change more advanced settings.

Screen Name/Description Default and Range

SYNC TIME TO SERVER Sync time and date with cloud server based on thermostat

location, which is determined by your mobile app or ISP during setup

D:

R:

YES

NO/YES

SCREEN TIMEOUT The maximum amount of time the BACKLIGHT stays active when no

activity is sensed at the thermostat

D:

R:

15 SEC

5 to 30 SEC (5 second

intervals)

PROXIMITY Enable or disable proximity sensing that changes the screen backlighting

from Dormant to Active when a person is sensed in front of the thermostat

D:

R:

YES

NO/YES

PROX SENSITIVITY Change the proximity sensing feature from HIGH to MEDIUM to

LOW. Increasing the sensitivity increases the range the sensor can detect presence, but

also increases the possibility of a false presence.

D:

R:

MEDIUM

HIGH/MEDIUM/LOW

# PROGRAM DAY PARTS Number of periods per day for programming occupancy D:

R:

2

2 or 4

DST Enable or disable automatic Daylight Saving Time change in the thermostat D:

R:

ENABLED

DISABLED/ENABLED

Using the Carrier Connect Wi-Fi Thermostat's screens

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

33

Screen Name/Description Default and Range

WIRELESS Enable or disable Wi-Fi for the thermostat. If disabled, then the Wi-Fi radio in

this product is turned off and functions, such as the following, are not available:

Sync Time To Server

Outdoor Temperature via Wi-Fi Geo location

Server & Wi-Fi Errors

Remote Access Services via app or Web

CAUTION If you disable this function after the thermostat has been set up and

connected to the local Wi-Fi network, you must set it up again using the mobile App.

D:

R:

ENABLED

ENABLED/DISABLED

SOUND Adjust the sound made when touching the thermostat D:

R:

CLICK

OFF, CLICK, or BEEP

FILTER

Available on the thermostat only.

Use to reset the FILTER ALERT and see the FILTER RESET REMINDER timer information. Press the RESET button

to reset the timer to its configured value in the advanced SYSTEM SETTINGS. See To configure advanced SYSTEM

SETTINGS (page 14).

LOCKOUT

Locks out unauthorized changes made on the touchscreen. All touch interaction is locked out without the unlock

code. After 5 failed attempts, a notification (fault) is sent to the registered owner of the thermostat through Wi-Fi.

More unlock attempts are blocked for 15 minutes.

To set up a new PIN or change the current PIN, select the ENABLE button or the CHANGE PIN button, which

displays on the SET PIN screen. If the thermostat does not already have a PIN, the CHANGE PIN button cannot be

used.

On the SET PIN screen, use the 3 blue-digit PIN wheels to set the PIN. Set the 3-digit PIN and press the orange

Save button to save the PIN and return to the LOCKOUT screen. Press the DISABLE button to cancel the LOCKOUT

function and reset the PIN to 000. The default is 000 and the range is 1 to 999.

CLEAN

Stops touchscreen interaction for 10 seconds to allow cleaning the screen with a dry nonabrasive cloth. A 10-

second countdown shows on the CLEAN screen and then resumes normal operation.

Using the Carrier Connect Wi-Fi Thermostat's screens

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

34

LOG

You can use this screen to view software update history, fault history, and system events. Swipe up or down on the

vertical yellow Row Indicator to scroll through logged events.

The log includes:

STARTUP

SOFTWARE UPDATE EVENTS

POWER CYCLE EVENTS

PARAMETER OUT-OF-RANGE EVENTS

SERVER CONNECTIVITY EVENTS

NON-VOLATILE MEMORY FAULTS

TEMPERATURE FAULTS

The list displays the 5 most recent logged events, with the most recent at the top. The last line in the list includes

the RESET LOG command to clear the list. Pressing an event item displays a screen with more information. Press

the BACK button to return to the LOG screen.

STATUS

Displays the current status of

thermostat outputs

timers

stages

lockouts

Current timer status is displayed and can be cleared for testing and troubleshooting by pressing and holding the

TIMERS text for 5 seconds. Press and hold LOCKOUT TIMERS for 5 seconds to clear timer values for COOL, E-

HEAT, and HP HEAT.

Scroll the vertical yellow Row Indicator to see more options.

SERVICE

Displays the dealer/installer service contact information. This information is editable using the mobile app, LAN

mode transfer, and Wi-Fi transfer.

Installation test

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

35

Complete the following to field test the Carrier Connect Wi-Fi Thermostat's outputs.

1 Press the CHANGE button to cycle the MODE screen through the following settings:

HEATING (default) not available in a cooling-only configuration

EM HEAT not available unless a heat pump is configured

COOLING not available in a heating-only configuration

FAN

2 Press the START button.

a) The first stage of HEATING, EM HEAT, COOLING, or FAN starts running and the text reads 1ST STAGE:

180 or FAN ON and 180 seconds starts counting down.

b) The START button is replaced with a STOP button and the CHANGE button disappears.

c) Once the countdown reaches 0, if another stage exists, it starts and the text changes to 2ND STAGE:

180.

d) If no other stage exists, the cycle ends, the text disappears, and the START button reappears.

e) If a third stage exists, it starts running after the second stage countdown reaches 0.

f) While the HEATING and EM HEAT MODES are running, if a humidifier has been configured, a HUM button

appears below the STOP button. If you press the HUM button, the text HUMIDIFYING appears and turns

on the humidifier.

g) While the COOLING MODE is running, if a dehumidifier has been configured, a DEHUM button appears

below the STOP button and, if pressed, the text DEHUMIDIFYING appears and the dehumidifier turns on.

h) Pressing the STOP button turns off running equipment, the STOP button is replaced with the START

button, the CHANGE button reappears, and the second (stage running and countdown time) and third

lines (humidifying or dehumidifying), are erased.

i) When you press the CANCEL button, any equipment that is running is turned off and the SYSTEM

SETTINGS screen displays.

j) When you press the HOME icon, any equipment that is running is turned off and the HOME screen

displays.

After 15 minutes of inactivity (no button presses), the installer test stops and the HOME screen displays.

Installation test

Troubleshooting

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

36

If the display does not turn on:

1 Check terminals R and C on the thermostat base.

2 Verify power is 24 Vac +/-10%.

3 Verify that the green LED on the base is flashing at 1 Hz.

NOTE If the green LED is not flashing and you do have 24 Vac on terminals R and C, you need to replace the

thermostat.

Outputs based on demand and configuration

Demands Stages Y1 Y2 W1 W2 G Y3 *Rev Val=0 *Rev Val=B

Fan Only Off Off Off Off On Off X X

Cool 1 (A/C) On Off Off Off On Off X X

Cool 2 (A/C) On On Off Off On Off X X

Cool 3 (A/C) On On Off Off On On X X

Cool 1 (Heat Pump) On Off Off Off On X On Off

Cool 2 (Heat Pump) On On Off Off On X On Off

Dehumidify Off Off Off Off On X X X

Cool 1 and

Dehumidify

On Off Off Off On X X X

Cool 2 and

Dehumidify

On On Off Off On X X X

Heat 1 (A/C) Off Off On Off On X X X

Heat 2 (A/C) Off Off On On On X X X

Heat 1 (Heat

Pump)

On Off Off Off On X Off On

Heat 2 (Heat

Pump)

On On Off Off On X Off On

Heat 3 (HP

w/Emerg Ht)

On On On On On X Off On

Heat 4 (HP

w/Emerg Ht)

On On On On On X Off On

Heat 1 and Off Off On Off On X X X

Troubleshooting

Troubleshooting

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

37

Demands Stages Y1 Y2 W1 W2 G Y3 *Rev Val=0 *Rev Val=B

Dehumidify

Heat 2 and

Dehumidify

Off Off On On On X X X

Heat Low (Electric) Off Off On Off On X X X

Heat Med (Electric) Off Off Off On On X X X

Heat High (Electric) Off Off On On On X X X

NOTE Use this table along with the HUM/DEHUM table, if either of those functions are enabled. See HUMIDITY

(page 28).

Fault definitions

The following Fault messages are displayed and logged in the banner during the fault condition and then sent to

the Cloud server.

Faults Condition

ID TEMP SENSOR HIGH Temperature reading > 122F

ID TEMP SENSOR LOW Temperature reading = 0

Reading not available

REMOTE SENSOR HIGH Remote temperature > 122F

NOTE Displayed only if REMOTE SENSOR is set to INDOOR or AVERAGE.

REMOTE SENSOR LOW Remote temperature = 0

NOTE Displayed only if REMOTE SENSOR is set to INDOOR or AVERAGE.

HUM TEMP SENSOR HIGH Humidity sensor temperature > 122F

NOTE Displayed only if using humidity temperature as a backup source during a

fault condition with the primary temperature sensor.

HUM TEMP SENSOR LOW Humidity sensor temperature = 0

NOTE Displayed only if using humidity temperature as a backup source during

a fault condition with the primary temperature sensor.

ID TEMP RANGE HIGH Indoor Temp above cooling setpoint plus MAX SETPOINT ERROR

ID TEMP RANGE LOW Indoor Temp below heat setpoint minus MAX SETPOINT ERROR

HUM SENSOR FAILURE Any of the following:

Humidity sensor timed out

Humidity reading is > 99%

Humidity reading is 0

Troubleshooting

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

38

Faults Condition

HUMIDITY RANGE HIGH Humidity reading is > 90%

HUMIDITY RANGE LOW Humidity reading is < 10%

OUTDOOR SENSOR FAILURE OD temp > 127 or < -60

NOT CONNECTED TO SERVER Not connected to Ayla server

NOT CONNECTED TO ROUTER Router signal strength is 0 = no bars = not connected

WI-FI HARDWARE FAULT Communications error occurred with Wi-Fi module (resets after valid message

received)

ECONOMIZER FAULT Contact closure on remote sensor input, as determined by Economizer

LOCKOUT User has entered incorrect pin 5 consecutive times

Recovering from a power outage

The Carrier Connect Wi-Fi Thermostat stores the following critical information in a non-volatile flash memory:

Installer settings

Owner settings

Program schedule

Software information

Dealer information

Fault and system event information

Date and time

The Carrier Connect Wi-Fi Thermostat uses a capacitor to maintain date and time for approximately 2 hours, in

order to maintain data during short power interruptions. If the power outage is longer than 2 hours, the date and

time will automatically be updated once network connection is re-established.

Troubleshooting

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

39

Resetting wi-fi access

To assign a new Wi-Fi access point or transfer the Carrier Connect Wi-Fi Thermostat to a new account, follow

these steps.

1 On the thermostat, not a mobile device, swipe the HOME screen twice to the left to navigate to the MODE

screen and ensure the MODE is OFF.

NOTE The yellow line above a button indicates the current MODE.

2 Swipe to go to the FAN screen and then press and hold the Fan Button for 5 seconds to get to the

SYSTEM SETTINGS screen.

NOTE You can ONLY access the SYSTEM SETTINGS screens from the thermostat itself, not the app or web.

3 Enter the 3-digit security PIN code, if applicable, to open the SYSTEM SETTINGS screen.

4 Scroll down to DISCONNECT WIFI.

CAUTION Disconnecting the Wi-Fi requires setting up the Connect Thermostat using the Connect mobile

application.

5 Select YES.

6 Use the mobile app on your phone or tablet to connect the thermostat to the desired Wi-Fi Access point. See

the section of this guide titled Registering and setting up a mobile device for enhanced access (page 9).

Follow the instructions within the app.

Troubleshooting

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

40

Compliance

FCC Compliance

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

1 This device may not cause harmful interference.

2 This device must accept any interference received, including interference that may cause undesired

operation.

IMPORTANT Any changes or modifications not expressly approved by manufacturer could void the user's

authority to operate the equipment.

NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to

Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference

when the equipment is operated in a residential installation. This equipment generates, uses, and can radiate

radio frequency energy, and if it is not installed and used in accordance with this document, it may cause harmful

interference to radio communications. However, there is no guarantee that interference will not occur in a

particular installation. If this equipment does cause harmful interference to radio or television reception, which

can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference

by one or more of the following measures:

Reorient or relocate the receiving antenna.

Increase the separation between the equipment and receiver.

Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

Consult the dealer or an experienced radio/TV technician for help.

BACnet Compliance

Compliance of listed products to requirements of ASHRAE Standard 135 is the responsibility of BACnet

International. BTL is a registered trademark of BACnet International.

Appendix: BACnet Points List

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

41

Point Name Point Access Units BACnet Point Name BACnet

Object ID

Indoor Space Temperature WRITE_WHEN_OOS DEGREES_FAHRENHEIT ID_SPACE_TEMP AI:100

Indoor Space Humidity WRITE_WHEN_OOS PERCENT_RELATIVE_HUMIDITY ID_SPACE_HUM AI:101

Remote Space Temperature READ_ONLY DEGREES_FAHRENHEIT REM_SPACE_TEMP AV:100

Outdoor Temperature READ_ONLY DEGREES_FAHRENHEIT OD_TEMP AV:101

Supply Air Temperature READ_ONLY DEGREES_FAHRENHEIT SAT AV:102

Network Space Temperature READ_WRITE DEGREES_FAHRENHEIT NET_SP_TEMP AV:103

Space Temperature for

Control

READ_ONLY DEGREES_FAHRENHEIT SP_TEMP_CTRL AV:104

Network Space Humidity READ_WRITE PERCENT_RELATIVE_HUMIDITY NET_SP_HUM AV:105

Space Humidity for Control READ_ONLY PERCENT_RELATIVE_HUMIDITY SP_HUM_CTRL AV:106

Air Filter Hours Left READ_ONLY HOURS AIR_FLTR_HRS_LFT AV:300

Override Time Remaining READ_ONLY SECONDS OVRD_TIME AV:301

Occupied Heat Setpoint READ_WRITE DEGREES_FAHRENHEIT OCC_HT_SP AV:400

Occupied Cool Setpoint READ_WRITE DEGREES_FAHRENHEIT OCC_CL_SP AV:401

Unoccupied Heat Setpoint READ_WRITE DEGREES_FAHRENHEIT UNOCC_HT_SP AV:402

Unoccupied Cool Setpoint READ_WRITE DEGREES_FAHRENHEIT UNOCC_CL_SP AV:403

Dehumidification Setpoint READ_WRITE PERCENT_RELATIVE_HUMIDITY DEHUM_SP AV:406

Humidification Setpoint READ_WRITE PERCENT_RELATIVE_HUMIDITY HUM_SP AV:407

Screen Timeout READ_WRITE MINUTES SCRN_TMT AV:408

Heat Setpoint READ_WRITE DEGREES_FAHRENHEIT HEAT_SP AV:409

Cool Setpoint READ_WRITE DEGREES_FAHRENHEIT COOL_SP AV:410

Active Backlight READ_WRITE PERCENT ACTV_BCKLT AV:411

Dormant Backlight READ_WRITE PERCENT DRMNT_BCKLT AV:412

Indoor Equip Stages GATED_WRITE PERCENT_RELATIVE_HUMIDITY ID_STAGES AV:500

Outdoor Equip Stages GATED_WRITE DEGREES_FAHRENHEIT OD_STAGES AV:501

Max Temperature Hold Time GATED_WRITE HOURS MAX_HOLD_TIME AV:502

Auto Changeover Delay GATED_WRITE MINUTES AUTO_XOVR AV:503

Cool Lockout Temperature GATED_WRITE DEGREES_FAHRENHEIT COOL_LOCKOUT AV:504

High Cool Lockout (HP only) GATED_WRITE DEGREES_FAHRENHEIT HI_CL_LCKOUT AV:505

High Heat Lockout (HP only) GATED_WRITE DEGREES_FAHRENHEIT HI_HT_LCKOUT AV:506

Delay Between Fuel (HP

only)

GATED_WRITE MINUTES DLY_BW_FUEL AV:507

Cycles Per Hour GATED_WRITE CYCLES_PER_HOUR CYCLES_HR AV:508

Max Heat Setpoint GATED_WRITE DEGREES_FAHRENHEIT MAX_HT_SP AV:509

Min Cool Setpoint GATED_WRITE DEGREES_FAHRENHEIT MIN_CL_SP AV:510

Aux Heat Lockout (HP only) GATED_WRITE DEGREES_FAHRENHEIT AUX_HT_LCKOUT AV:511

Heat Pump Lockout GATED_WRITE DEGREES_FAHRENHEIT HP_LCKOUT AV:512

Stage Delay GATED_WRITE MINUTES STG_DELAY AV:513

Forced Stage Up Delay GATED_WRITE MINUTES FRCD_STG_UP AV:514

Stage Change Temp

Differential

GATED_WRITE DELTA_DEGREES_FAHRENHEIT DIFFERENTIAL AV:515

Line Frequency GATED_WRITE HERTZ LINE_FREQ AV:516

Indoor Temperature Offset GATED_WRITE DELTA_DEGREES_FAHRENHEIT ID_TEMP_OFF AV:517

Indoor Humidity Offset GATED_WRITE PERCENT_RELATIVE_HUMIDITY ID_HUM_OFF AV:518

Appendix: BACnet Points List

Appendix: BACnet Points List

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

42

Point Name Point Access Units BACnet Point Name BACnet

Object ID

SAT Temp Offset GATED_WRITE DELTA_DEGREES_FAHRENHEIT SAT_OFFSET AV:519

Air Filter Hours READ_ONLY HOURS AIR_FLT_HRS AV:520

Max Setpoint Error GATED_WRITE DELTA_DEGREES_FAHRENHEIT MAX_SP_ERR AV:521

Indoor Temp Fault Inhibit GATED_WRITE MINUTES ID_TMP_FLT_INHBT AV:522

1st Stage Cooling Out Status READ_ONLY 0=OFF

1=ON

Y1_OUT BV:200

2nd Stage Cooling Out

Status

READ_ONLY 0=OFF

1=ON

Y2_OUT BV:201

3rd Stage Cooling Out

Status

READ_ONLY 0=OFF

1=ON

Y3_OUT BV:202

1st Stage Heating Out

Status

READ_ONLY 0=OFF

1=ON

W1_OUT BV:203

2nd Stage Heating Out

Status

READ_ONLY 0=OFF

1=ON

W2_OUT BV:204

Fan Out Status READ_ONLY 0=OFF

1=ON

G_OUT BV:205

Reversing Valve Out Status READ_ONLY 0=OFF

1=ON

OB_OUT BV:206

Occupancy Out Status READ_ONLY 0=OFF

1=ON

OCC_OUT BV:208

Humidifier Out Status READ_ONLY 0=OFF

1=ON

HUM_OUT BV:209

Dehumidifier Out Status READ_ONLY 0=OFF

1=ON

DEHUM_OUT BV:210

Network General Purpose

Out Y3

READ_WRITE 0=OFF

1=ON

NET_GP_Y3_OUT BV:211

Network General Purpose

Out W2

READ_WRITE 0=OFF

1=ON

NET_GP_W2_OUT BV:212

Network General Purpose

Out OB

READ_WRITE 0=OFF

1=ON

NET_GP_OB_OUT BV:213

Wi-Fi Time Synchronization READ_WRITE 0=DISABLED

1=ENABLED

WIFI_TIME_SYNC BV:400

Proximity Sensor Enable READ_WRITE 0=DISABLED

1=ENABLED

PROXIMITY_EN BV:401

Auto DST Time Shift READ_WRITE 0=DISABLED

1=ENABLED

AUTO_DST BV:402

Wi-Fi Enable READ_WRITE 0=DISABLED

1=ENABLED

WIFI_ENABLE BV:403

Setpoint Override READ_WRITE 0=DISABLED

1=ENABLED

SETPT_OVERRIDE BV:404

BACnet BMS Occupancy GATED_WRITE 0=UNOCCUPIED

1=OCCUPIED

BMS_OCC BV:405

Filter Timer Reset READ_WRITE 0=INACTIVE

1=ACTIVE

FLTR_TMR_RST BV:406

Occupancy Input Polarity GATED_WRITE 0=OCCUPIED

1=UNOCCUPIED

OCC_IN_POL BV:500

Auto Mode Allowed GATED_WRITE 0=NO

1=YES

ALLOW_AUTO BV:501

Prog Mode Allowed GATED_WRITE 0=NO

1=YES

ALLOW_PROG BV:502

Appendix: BACnet Points List

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

43

Point Name Point Access Units BACnet Point Name BACnet

Object ID

Celsius Display GATED_WRITE 0=F

1=C

CELSIUS_DISP BV:503

Fan On with W GATED_WRITE 0=NO

1=YES

FAN_WITH_W BV:504

Rvs Vlv Energized Ht GATED_WRITE 0=ENERGIZED FOR COOL

1=ENERGIZED FOR HEAT

RVS_VLV_DIR BV:505

Humidifier Installed GATED_WRITE 0=NO

1=YES

HUM_INST BV:506

BMS Occupancy Enable GATED_WRITE 0=DISABLED

1=ENABLED

BMS_OCC_EN BV:507

BACnet Config Write Enable GATED_WRITE 0=DISABLED

1=ENABLED

CFG_WR_EN BV:511

ID TEMP SENSOR HIGH READ_ONLY 0=DISABLED

1=ENABLED

ID_TEMP_SENS_HI BV:900

ID TEMP SENSOR LOW READ_ONLY 0=INACTIVE

1=ACTIVE

ID_TEMP_SENS_LO BV:901

REMOTE SENSOR HIGH READ_ONLY 0=INACTIVE

1=ACTIVE

REM_TEMP_HI BV:902

REMOTE SENSOR LOW READ_ONLY 0=INACTIVE

1=ACTIVE

REM_TEMP_LO BV:903

HUM TEMP SENSOR HIGH READ_ONLY 0=INACTIVE

1=ACTIVE

HUM_TEMP_HI BV:904

HUM TEMP SENSOR LOW READ_ONLY 0=INACTIVE

1=ACTIVE

HUM_TEMP_LO BV:905

ID TEMP RANGE HIGH READ_ONLY 0=INACTIVE

1=ACTIVE

ID_TEMP_RNG_HI BV:906

ID TEMP RANGE LOW READ_ONLY 0=INACTIVE

1=ACTIVE

ID_TEMP_RNG_LO BV:907

HUM SENSOR FAILURE READ_ONLY 0=INACTIVE

1=ACTIVE

HUM_SENS_FAIL BV:908

HUMIDITY RANGE HIGH READ_ONLY 0=INACTIVE

1=ACTIVE

HUM_TOO_HI BV:909

HUMIDITY RANGE LOW READ_ONLY 0=INACTIVE

1=ACTIVE

HUM_TOO_LO BV:910

OUTDOOR SENSOR FAILURE READ_ONLY 0=INACTIVE

1=ACTIVE

OD_TEMP_FAIL BV:911

NOT CONNECTED TO

SERVER

READ_ONLY 0=INACTIVE

1=ACTIVE

SRVR_CONN_FAIL BV:912

NOT CONNECTED TO

ROUTER

READ_ONLY 0=INACTIVE

1=ACTIVE

RTR_CONN_FAIL BV:913

WIFI HARDWARE FAULT READ_ONLY 0=INACTIVE

1=ACTIVE

WIFI_CONF_FAIL BV:914

ECONOMIZER FAULT READ_ONLY 0=INACTIVE

1=ACTIVE

ECON_FAULT BV:915

LOCKOUT-5 BAD PIN

ENTRIES

READ_ONLY 0=INACTIVE

1=ACTIVE

LOCKOUT_FAIL BV:916

Current Mode Status READ_ONLY 1=OFF

2=HEAT

3=COOL

CURRENT_MODE MSV:300

User Mode READ_WRITE 1=OFF USER_MODE MSV:400

Appendix: BACnet Points List

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

44

Point Name Point Access Units BACnet Point Name BACnet

Object ID

2=HEAT

3=COOL

4=AUTO

5=E-HEAT

IR Proximity Sensitivity READ_WRITE 1=HIGH

2=MEDIUM

3=LOW

PROX_SENS MSV:401

Sound Effect READ_WRITE 1=OFF

2=CLICK

3=BEEP

SOUND MSV:402

Number of Parts in Schedule

Day

READ_WRITE 1=2 PARTS

2=4 PARTS

SCHED_DAY_PARTS MSV:403

Occupied Fan Mode READ_WRITE 1=AUTO

2=ON

OCC_FAN MSV:404

Unoccupied Fan Mode READ_WRITE 1=AUTO

2=ON

UNOCC_FAN MSV:405

Current Fan Mode READ_WRITE 1=AUTO

2=ON

3=OVERRIDE AUTO

4=OVERRIDE ON

FAN MODE MSV:406

Indoor Equipment Type READ_ONLY 1=NO INDOOR

2=FURNACE

3=AIR HANDLER

ID_EQUIP_TYPE MSV:500

Outdoor Equipment Type GATED_WRITE 1=NO OUTDOOR

2=A/C

3=HEAT PUMP

OD_EQUIP_TYPE MSV:501

Remote Sensor Type GATED_WRITE 1=NONE

2=OUTDOOR

3=SPACE

4=AVERAGE

5=OCCUPANCY

6=FAULT_INPUT

7=SAT

REMOTE_SENSOR MSV:502

Dehumidification Type GATED_WRITE 1=NO

2=YES

3=OVRCRL(2F)

4=HUMIDIMIZER

DEHUM_TYPE MSV:503

Occupancy Output Terminal GATED_WRITE 1=OFF

2=Y3

3=O/B

4=W2

OCC_OUTPUT MSV:504

Humidification Output

Terminal

GATED_WRITE 1=OFF

2=Y3

3=O/B

4=W2

HUM_OUTPUT MSV:505

Dehumidification Output

Terminal

GATED_WRITE 1=OFF

2=Y3

3=O/B

4=W2

DEHUM_OUTPUT MSV:506

Smart Recovery GATED_WRITE 1=NO

2=30 MIN

SMART_RECVRY MSV:507

Appendix: BACnet Points List

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

45

Point Name Point Access Units BACnet Point Name BACnet

Object ID

3=60 MIN

4=90 MIN

General Purpose Output

Timeout

GATED_WRITE 1=2 MIN

2=20 MIN

3=1 HR

4=UNLIMITED

GP_OUT_TIMEOUT MSV:508

Network GP Y3 Mode GATED_WRITE 1=DISABLED

2=ENERGIZED_ACTIVE

3=ENERGIZED_INACTIVE

NET_GP_Y3_MODE MSV:509

Network GP W2 Mode GATED_WRITE 1=DISABLED

2=ENERGIZED_ACTIVE

3=ENERGIZED_INACTIVE

NET_GP_W2_MODE MSV:510

Network GP OB Mode GATED_WRITE 1=DISABLED

2=ENERGIZED_ACTIVE

3=ENERGIZED_INACTIVE

NET_GP_OB_MODE MSV:511

Document revision history

Carrier Connect Wi-Fi

Thermostat 33CONNECTSTAT43 CARRIER CORPORATION 2021

Installation Guide All rights reserved

46

Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not

listed.

Date Topic Change description Code*

1/22/21 To wire for BACnet communication Added 115.2 kbps baud rate C-CP-E

7/17/20 BACnet Points List Corrected BACnet BMS Occupancy to GATED_WRITE from

READ_ONLY

C-CP-E

2/28/20 Entire book Updated logos C-D

1/6/20 Entire book Updated throughout for BACnet capabilities C-CP-E

9/27/19 Registering and setting up a mobile

device for enhanced access

Removed reference to a 7-day limit for mobile devices C-TS-CP-E

BACnet Integration New C-TS-CP-E

To connect a remote input ((sensor or

contacts)

Added SAT to list of inputs. C-TS-CP-E

Appendix: BACnet Points List New C-ST-CP-E

To configure advanced SYSTEM

SETTINGS

Added SAT to REMOTE SENSOR

Added BACnet parameters

C-ST-CP-E

8/28/19 Humidity Removed note limiting output use C-ST-CP-E

* For internal use only

Document revision history

Manualsnet FAQs

If you want to find out how the 33CONNECTSTAT43 Carrier works, you can view and download the Carrier 33CONNECTSTAT43 Installation Guide on the Manualsnet website.

Yes, we have the Installation Guide for Carrier 33CONNECTSTAT43 as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Installation Guide should include all the details that are needed to use a Carrier 33CONNECTSTAT43. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier 33CONNECTSTAT43 Installation Guide is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier 33CONNECTSTAT43 Installation Guide consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier 33CONNECTSTAT43 Installation Guide free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier 33CONNECTSTAT43 Installation Guide, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier 33CONNECTSTAT43 Installation Guide as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.