Outdoor Air Static Pressure Pickup Port

Termination and Troubleshooting

rev. 5/30/07 #14358 2/5/18

1 of 2 Catalog No. 11-808-626-01

How It Works

Building static pressure is the pressure difference between the inside and the outside of a building. The outdoor static

pressure is the atmospheric pressure at the building site. The building may have positive, neutral, or negative pressure

with respect to the outside atmosphere. Differences in pressure are due to powered supply or exhaust fans and are usually

less than 0.1 inches of water.

Measuring building static pressure is complicated by the dynamic action of the wind. A breeze of 10 MPH provides a

pressure of 0.048 inches of water, a gale of 40 MPH is 0.772 inches, and a hurricane of 75 MPH is 2.716 inches. Clearly,

the winds pressure may be more than the desired building static pressure. Measuring the winds pressure instead of the

true outdoor static pressure will radically alter the actual static pressure reading.

Mounting the unit with the plate parallel to the earths surface, as shown in Figure 2, allows the predominantly horizontal

flow of the wind an omni-directional entry between the plate and the housing. The plate forces the wind to move perpendicu-

larly to the pressure orifice in the housing, irrespective of the winds direction, greatly minimizing the dynamic air pressure.

Mounting the unit vertically, as on the side of a rooftop air conditioning unit (RTU), will only provide a true static pressure

reading if the wind is blowing within 15 to 20 degrees of the direction of the opening. If the wind is blowing at a vertically-

mounted Outdoor Air Static Pressure Pickup Port, it will pile up, providing a higher than correct static pressure reading.

If the wind is blowing away from the sensor it will be in the wake of the RTU, providing a lower than correct static pressure

reading.

Figure 1: Outdoor Air Static

Pressure Pickup Port

Part # NSB-ZPS-ACC10

Mounting

The Outdoor Air Static Pressure Pickup Port should be mounted at least 12 inches above surrounding obstacles so that

you get the true static pressure reading. Carrier supplies a brass bulkhead fitting to get your pressure signal inside the

building envelope, the user supplies all necessary pressure tubing and the 1/2 inch EMT conduit mounting support.

Mount the unit so that other equipment on the building cannot physically or mechanically obstruct it. Do not mount under

awnings or other projections within 15 feet. If the unit cannot be roof mounted with an unobstructed view of the horizon,

then do not mount near economizers, intake or exhaust fans, or barometric dampers. Do not mount near building corners.

Mount near the center of the building away from balconies and opening windows. Mount at least 24 inches from the wall.

.

2 of 2

Outdoor Air Static Pressure Pickup Port

Termination and Troubleshooting

rev. 5/30/07 #14358 2/5/18

Catalog No. 11-808-626-01

Figure 2: Preferred Mounting,

1/2 EMT Conduit Mounting Support

Figure 3: Wall Mounting,

1/2 EMT Conduit Mounting Support

Preferred Mounting

Figure 2 shows the Outdoor Air Static Pressure Pickup Port mounted on an RTU or air handler. A mounting support is

field-fabricated from a piece of 1/2-inch EMT conduit bent to 90 degrees as shown. A short leg mounts the Static

Pressure Pickup Port. A long leg mounts the assembly to the side of the mechanical equipment. The length of the long

leg is dependent on your installation site; just be sure that the Static Pressure Sensor is at least 12 inches above the top

of the equipment. If you are mounting on mechanical equipment with a condenser fan or a building air discharge, mount

the Static Pressure Pickup Port on the opposite end of the equipment. It is best to mount it to the compartment that

contains the controls; usually there is a hole in the compartment into the building envelope for control wiring.

Drill two holes in the sheet metal for the EMT conduit support brackets. Bolt the EMT conduit mounting support to the

side of the equipment. Place enough tubing on the Outdoor Air Static Pressure Pickup Ports barbed fitting to reach

beyond the end of the EMT conduit mounting support. Slide the tubing down the inside of the EMT conduit and slide the

Static Pressure Pickup Ports conduit fitting onto the EMT conduit. Position the Static Pressure Pickup Port with the plate

down and parallel to the earths surface. Tighten the Static Pressure Pickup Ports conduit fittings screw until the unit is

secure on the EMT mounting support.

Drill a 5/16-inch hole in the sheet metal near the bottom of the EMT conduit mounting support for the bulkhead fitting.

Place the fitting through the sheet metal from the outside so that the nut is on the inside, and then tighten the nut

securely but do not over tighten. Place the tubing coming out the bottom on the EMT conduit mounting support onto the

bulkhead fitting. Place up to 150 feet of tubing on the bulkhead fittings inside port and run the tubing into the building to

Manualsnet FAQs

If you want to find out how the NSB-ACC Carrier works, you can view and download the Carrier NSB-ACC v2 Termination and Troubleshooting Manual on the Manualsnet website.

Yes, we have the Termination and Troubleshooting Manual for Carrier NSB-ACC as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Termination and Troubleshooting Manual should include all the details that are needed to use a Carrier NSB-ACC. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier NSB-ACC v2 Termination and Troubleshooting Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier NSB-ACC v2 Termination and Troubleshooting Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier NSB-ACC v2 Termination and Troubleshooting Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier NSB-ACC v2 Termination and Troubleshooting Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier NSB-ACC v2 Termination and Troubleshooting Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.