Catalog No. 11-808-622-01

1 of 2

Specifications subject to change without notice.

#8588 2/15/18

Overview

Figure 1: Wall Plate with Temperature Sensor Part # NSB-10K-2-SP

Specifications

Material Aluminum or Stainless Steel

Sensing element 10k Type 2 Thermistor

Environmental Operation Range -40 to 212F (-40 to 100C) -4 to 158F(-20 to 70C) with transmitter

Humidity 0 to 95%, non-condensing

Wiring

Carrier recommends using twisted pair of at least 22 AWG for all wire connections. Larger gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes.

Do NOT run this devices wiring in the same conduit as AC power wiring of NEC class 1, NEC class 2, NEC class 3 or with wiring used to supply highly inductive loads such as motors, contactors and relays. Tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines.

Wall Plate Temperature Sensors

Installation and Operation

Carrier recommends wiring the product with power disconnected. Proper supply voltage, polarity, and wiring connections are important to a successful installation. Not observing these recommendations may damage the product and will void the warranty.

Catalog No. 11-808-622-01

2 of 2

Specifications subject to change without notice.

#8588 2/15/18

Termination

Terminate the sensor wires to your controller wires using sealant filled connectors to ensure a moisture tight connection.

The wallplates foam back insulates the temperature sensor from the wall temperature and/or conduit drafts.

Mounting

Mounting hardware is provided for both junction box and drywall installation.

Junction Box

1. Pull the wire through the wall and out of the junction box, leaving about six inches free.

2. Terminate the unit according to the guidelines in Termination on page 1.

NOTE Make sure the foam gasket on the back plate is compressed about 50% and the metal plate does not touch the wall.

Drywall Mounting

1. Place the plate against the wall where you want to mount the sensor.

2. Use a pencil to mark the two mounting holes.

3. Drill two 3/16 holes in the center of each marked mounting hole. Insert a drywall anchor into each hole.

4. Cut hole between the mounting holes that clears the apparatus mounted on plate.

5. Pull the wire through the wall hole cut in step 4, leaving about six inches free.

6. Terminate the unit according to the guidelines in Termination on page 1.

7. Secure the plate to the drywall anchors using the #6 x 1 inch mounting screws provided.

NOTE Make sure the foam gasket on the back plate is compressed about 0% and the metal plate doesnt touch the wall.

Diagnostics

Possible Problems:

Controller reports

higher than actual

temperature

Controller reports

lower than actual

temperature

Possible Solutions:

- Confirm that the input is set up correctly in the controller software.

- Verify that the wires are not electrically shorted.

- Check wiring for proper termination.

- Disconnect the controller wires from the sensor. Measure the temperature sensors resistance with an ohmmeter. Verify the sensors output is correct.

- Confirm that the input is set up correctly in the controller software.

- Verify that the wires are not electrically open.

- Che

Manualsnet FAQs

If you want to find out how the NSB-MISC Carrier works, you can view and download the Carrier NSB-MISC v3 Installation and Operation Manual on the Manualsnet website.

Yes, we have the Installation and Operation Manual for Carrier NSB-MISC as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Installation and Operation Manual should include all the details that are needed to use a Carrier NSB-MISC. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier NSB-MISC v3 Installation and Operation Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier NSB-MISC v3 Installation and Operation Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier NSB-MISC v3 Installation and Operation Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier NSB-MISC v3 Installation and Operation Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier NSB-MISC v3 Installation and Operation Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.