Remote Temperature Probes Installation and Operation

Specifications subject to change without notice.

1 of 3 Catalog No. 11-808-634-01

#20910 10/26/20

Overview

The Remote Probe with Plenum-Rated Cable is a small stainless steel temperature sensor used for single point temperature measurement with PVC plenum rated cable. It is ideal for bracket mounting for chamber, duct, thermowell or L-bracket applications. Part #s NSB-10K-2-RPP-6 (6 probe) NSB-10K-2-RPP-5 (5 probe) NSB-10K-2-RPP-10 (10 probe) NSB-10K-2-RPP-15 (15 probe) NSB-10K-2-RPP-25 (25 probe) NSB-50K-RPP-5-C (5 probe)

The Remote Probe with FEP-Jacketed Cable is a small stainless steel temperature sensor used for single point temperature measurement with FEP plenum cable. It is ideal for bracket mounting in harsh environments for chamber, duct, thermowell or L- bracket applications. Part #s NSB-10K-2-RPFEP-18 (18 probe) NSB-10K-2-RPFEP-5 (5 probe)

The Remote Probe with FEP-Jacketed Cable for submersion is a small stainless steel temperature sensor used for sin gle point temperature measurement with submersion FEP plenum cable. It is ideal for bracket mounting in wet or water submersion environments for chamber, duct, immersion or L-bracket applications. Part #s NSB-10K-2-RPFEP2-5 (5 probe) NSB-10K-2-RPFEP2-25 (25 probe) NSB-50K-RPFEP2-5-C (5 probe)

Figure 1: Remote Probe

Specifications Sensor Passive, NTC, 2 wire

Thermistor Thermal resistor Temp. Output Resistance, 10k Type 2 Accuracy (Std) 0.36F, (0.2C) Stability < 0.036F/Year, (<0.02C/Year) Heat dissipation 2.7 mW/C Temp. Drift <0.02C per year Probe range -40 to 221F (-40 to 105C)

Lead wire 22AWG stranded

Wire Insulation -RPP Flame Retardant PVC plenum cable -RPFEP FEP jacketed plenum rated cable -RPFEP2 FEP jacketed plenum and

submersion rated cable

Probe

-RPP, RPFEP Rigid, 304 Stainless Steel, 0.25 OD

Probe Length -RPP, RPFEP 1.75 (44.5mm)

Mounting External Probe Bracket required Probe Vented polycarbonate shield, OD

Probe Length 1.2 with NPT threads Agency RoHS, CE

Specifications subject to change without notice.

2 of 3 Catalog No. 11-808-634-01

Remote Temperature Probes Installation and Operation

#20910 10/26/20

Mounting

1. Strap sensor so that it has good contact with bare pipe.

2. To increase the accuracy of the sensor, use an insulating material to insulate the sensor and pipe from ambient temperature influences. Foamback insulation is available in 1/4 thickness (p/n NSB- Foamback-.250) and in 1/8 thickness (p/n NSB- Foamback-.125). NOTES Insulation should be installed a minimum of 4

pipe diameters on each side of the strap-on sensor. Example: pipe x 4 = 2.

Insulation should be 2 on each side of the sensor wrapped all the way around the pipe.

Figure 2: Stainless Steel Remote Probe Strapped to Pipe

Figure 3A: Break-Off Tab from a Flexible Figure 3B: Break-Off Tab Used to

Probe Bracket (P/N NSB-PB-50)Mount a Stainless Steel Remote Probe

Wiring and Termination Carrier recommends using twisted pair of at least 22 AWG for runs under 100 feet, and sealant filled connectors for all wire connections. Runs from 100 to 500 feet should use shielded 22 AWG. All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this devices wiring in the same conduit as high or low voltage AC power wiring. Tests show that inaccurate signal levels are possible when AC power wiring is present in the same conduit as the sensor wires.

Step 1 Step 2

To Controller Analog Input (AI) (No Polarity)

To Controller Analog Input (AI) (No Polarity)

Figure 4: 2 Wire Lead Wire Termination for Thermistor

Sensor

Specifications subject to change without notice.

3 of 3 Catalog No. 11-808-634-01

Remote Temperature Probes Installation and Operation

#20910 10/26/20

Diagnostics Possible Problem: Controller reports higher or lower than actual temperature

Possible Solutions: - Confirm the input is set up correctly in the controller

Manualsnet FAQs

If you want to find out how the NSB-10K-2-RPP Carrier works, you can view and download the Carrier NSB-10K-2-RPP Installation and Operation Manual on the Manualsnet website.

Yes, we have the Installation and Operation Manual for Carrier NSB-10K-2-RPP as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Installation and Operation Manual should include all the details that are needed to use a Carrier NSB-10K-2-RPP. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier NSB-10K-2-RPP Installation and Operation Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier NSB-10K-2-RPP Installation and Operation Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier NSB-10K-2-RPP Installation and Operation Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier NSB-10K-2-RPP Installation and Operation Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier NSB-10K-2-RPP Installation and Operation Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.