Averaging Duct Temperature Sensors

Installation and Operation

1 of 3 Catalog No. 11-808-631-01

Specifications subject to change without notice.

#20903 2/15/18

Overview

The Averaging Sensor is for duct mounting and temperature measurement of stratified air across the duct to give the average

temperature along the length of the sensor. The flexible probe is made of aluminum and made in different lengths for a custom duct fit.

Enclosure mounting styles come in plastic or metal for both NEMA 1 and NEMA 4 applications and are all plenum rated.

Figure1: Duct Unit with J-Box (Standard)

Part #s NSB-10K-2-A-8 (8 probe) NSB-10K-2-A-12 (12 probe) NSB-10K-2-A-24 (24 probe)

Figure 2: BB2 Enclosure Duct Unit

Part #s NSB-10K-2-A-8-BB2 (8 probe) NSB-10K-2-A-12-BB2 (12 probe) NSB-10K-2-A-24-BB2 (24 probe)

Figure 3: BB4 EnclosureDuct Unit

Part #s NSB-10K-2-A-8-BB4 (8 probe) NSB-10K-2-A-12-BB4 (12 probe) NSB-10K-2-A-24-BB4 (24 probe)

A Pierceable Knockout Plug (Part # NSB-PKP-100) is available for the open port in the BB4.

Specifications

Sensor Passive Thermistor 4 sensors in < 24 probes

9 sensors in > 24 probes Thermistor Thermal resistor (NTC) Temp. output Resistance, 10k Type 2 Accuracy (std) 0.36F, (0.2C) Stability < 0.036F/Year, (<0.02C/Year) Heat dissipation 2.7 mW/C Temp. drift <0.02C per year Probe range -40 to 221F (-40 to 105C)

Lead Wire 22AWG stranded, Etched Teflon, Plenum rated

Probe Flexible Aluminum tube, 0.19 OD Probe Length 8, 12, 24 per order Duct Gasket 1/4 Closed cell foam (impervious to mold) Mounting Extension tabs (ears), 3/16 holes

Enclosure Types J-Box With eight knockouts BB2 Box Withthree NPSM and three 1/2 drillouts BB4 Box With three drill-outs, one open port

Enclosure Ratings J-Box NEMA 1 BB2 Box NEMA 4X, IP66 BB4 Box IP10 (IP44 with Knockout Plug installed)

Enclosure Materials J-Box Galvanized steel, UL94H-B BB2 Box Polycarbonate, UL94V-0, UV rated BB4 Box Polycarbonate and Nylon, UL94V-0

Ambient (Enclosure) 0 to 100% RH, Non-condensing J-Box -40F to 212F, (-40 to 100C) BB2, BB4-40F to 185F, (-40 to 85C)

Agency RoHS, CE

Specifications subject to change without notice.

2 of 3 Catalog No. 11-808-631-01

Averaging Duct Temperature Sensors

Installation and Operation

Figure 7: BB2 Enclosure Mounting

Holes and installation.

#20903 2/15/18

Mounting

1. Place the sensor in the middle or top of the duct as shown in Figure 4 or Figure 5 so the flexible probe can enter the duct in a convenient place. Drill the probe and mounting holes as depicted for the enclosure being used.

2. Insert the probe by unrolling the sensor into the duct carefully to avoid kinking

the sensor. Serpentine the duct with the sensor at least twice across the stratified air in the duct to achieve the best average temperature reading.

At the sensor reversing points a turning bracket can be used to support the sensor and to avoid kinking the sensor.

3. Mount the enclosure to the duct using #8 screws through a minimum of two

opposing mounting tabs provided.

4. Snug up the sensors so that the foam backing is depressed to prevent air leakage but do not overtighten or strip the screw threads.

NOTES

Be sure to use caulk or Teflon tape for your conduit entries to maintain the appropriate NEMA or IP rating for your application.

Conduit entry for outdoor or wet applications should be from the bottom of the enclosure.

Figure 6: Junction Box

Mounting Holes and installation

Figure 4: Flexible Sensor Horizontal Mount (Best for Vertical Stratification)

Figure 5: Flexible Sensor Vertical Mount (Best for Horizontal Stratification)

Figure 8: BB4 Enclosure Mounting Holes and Installation

Specifications subject to change without notice.

3 of 3 Catalog No. 11-808-631-01

Averaging Duct Temperature Sensors

Installation and Operation

#20903 2/15/18

Wiring and Termination

Carrier recommends using twisted pair of at least 22AWG for all wire connections. Larger gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this devices wiring in the same conduit as high or low voltage AC power wiring. Tests show that inaccurate signal levels are possible when AC power wiring is present in the same conduit as the sensor wires.

Diagnostics Problems: Controller reports higher or lower than actual temperature.

Possible Solutions: - Confirm the input is set up correctly in the front end software - Check wiring for proper termination and continuity. (shorted or open) - Disconnect wires and measure sensor resistance and verify the Sensor output is correct.

Manualsnet FAQs

If you want to find out how the NSB-10K-2-A-24 Carrier works, you can view and download the Carrier NSB-10K-2-A-24 Installation and Operation Manual on the Manualsnet website.

Yes, we have the Installation and Operation Manual for Carrier NSB-10K-2-A-24 as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Installation and Operation Manual should include all the details that are needed to use a Carrier NSB-10K-2-A-24. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier NSB-10K-2-A-24 Installation and Operation Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier NSB-10K-2-A-24 Installation and Operation Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier NSB-10K-2-A-24 Installation and Operation Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier NSB-10K-2-A-24 Installation and Operation Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier NSB-10K-2-A-24 Installation and Operation Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.