Read this manual before using the RBC- AMS54E-UL remote control.
Refer to the Installation Manual supplied with the indoor unit for any installation instructions other than operations of the remote control.
Wired Remote Control Installation Manual
+00EH97068701_EN.book Page 1 Monday, March 14, 2016 9:13 AM
1
Installation Manual
Contents
Precautions for Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Accessory Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Requirements to install the remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Install the remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wire the remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Requirements for wiring of group control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Requirements for installing two remote controls . . . . . . . . . . . . . . . . . . . . . . . . . . 7
For first use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Part Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Monitor screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Initial setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1. Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2. Name of room. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3. Screen contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4. Backlight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5. Key lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6. Header/Follower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7. Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8. Press & hold 4sec. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Field setting menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1. Test mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2. Register service info.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3. Alarm history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4. Monitor function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5. Setting louver position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6. Setting timer operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7. DN setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
+00EH97068701_EN.book Page 1 Monday, March 14, 2016 9:13 AM
2
EN
Installation Manual
Precautions for Safety Read these Precautions for Safety carefully before installation. The precautions described below include important items regarding safety. Observe them without fail.
Understand the following details (indications and symbols) before reading the body text, and follow the instructions.
Ask customer to keep this Manual at accessible place for future reference.
Indication Meaning of Indication
WARNING Text set off in this manner indicates that failure to adhere to the directions in the warning could result in serious bodily harm (*1) or loss of life if the product is handled improperly.
CAUTION Text set off in this manner indicates that failure to adhere to the directions in the caution could result in minor bodily injury (*2) or damage (*3) to property if the product is handled improperly.
*1: Serious bodily harm indicates loss of eyesight, injury, burns, electric shock, bone fracture, poisoning, and other injuries which leave aftereffect and require hospitalization or long-term treatment as an outpatient.
*2: Bodily injury indicates injury, burns, electric shock, and other injuries which do not require hospitalization or long- term treatment as an outpatient.
*3: Damage to property indicates damage extending to buildings, household effects, domestic livestock, and pets.
Symbols Meaning of Symbols
" Indicates prohibited items. The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol.
" Indicates compulsory (mandatory) items. The actual contents of the obligation indicated by a picture or text placed inside or next to the graphic symbol.
WARNING
Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in water leakage, electric shock or fire.
Perform installation work properly according to the Installation Manual. Inappropriate installation may result in water leakage, electric shock or fire.
Electrical work must be performed by a qualified electrician in accordance with this installation manual. The work must satisfy all local, national and international regulations. Inappropriate work may result in electric shock or fire.
Use predefined wire and connect them certainly. Keep the connecting terminal free from external force. Improper wire connection or clamping may result in exothermic, fire or malfunction.
+00EH97068701_EN.book Page 2 Monday, March 14, 2016 9:13 AM
3
Installation Manual
Accessory Parts No. Part name Quantity
(1) Screws 0.16" 0.79" (M420 mm)
2
(2) Wood screws 0.15" 0.63" (M3.816 mm)
2
(3) Owners Manual 1
(4) Installation Manual (This manual)
1
+00EH97068701_EN.book Page 3 Monday, March 14, 2016 9:13 AM
4
EN
Installation Manual
Installation
Requirements to install the remote control
Installation place Install the remote control at a height of 3'3" to 4'9" from the floor so that the average temperature in the room can
be detected. Do not install the remote control in a place exposed to direct sunlight or direct outside air, such as the side of a
window. Do not install the remote control in a place behind something or to the rear side of an object, where air flow is
not sufficient. Do not install the remote control in a freezing box or refrigerator, as the remote control is not waterproof. Install the remote control vertically to the wall.
Installation dimension
Room temperature sensor
4. 72
"
0.78"
4.72"
Unit : in
4-0.17"0.31" slotted hole0.94"
0.86"
1. 65
" 1.
6 5
"
+00EH97068701_EN.book Page 4 Monday, March 14, 2016 9:13 AM
5
Installation Manual
Remote control wiring and inter-unit wiring between indoor units Do not allow the wire for the remote control (communication wire) and the wire for AC208/230 V to come into contact or put them together in one electrical conduit; otherwise, the control system may have trouble due to noise. * Varies depending on the type of remote control used.
Installation of multiple remote controls To install two or more adjacent remote controls, follow the instructions in the Fig. 1 and 2.
Wiring type AWG20 to AWG14 x 2
Total length of remote control wiring and inter-wiring between indoor units (L+L1+L2+...Ln)
1 remote control 2 remote controls 2 remote controls including a wireless remote control
Up to 1640 ft (500 m) Up to 980 ft (300 m) Up to 1310 ft (400 m)
Total length of inter-wiring between indoor units (L1+L2+...Ln)
Up to 660 ft (200 m)
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Remote control wiring
L L1 L2 Ln
(Up to 8 units) Remote control
Remote control inter-units wires for group control.
Wall
1.30" or more (from a wall)
0.80" or more (when adjacent remote
controls are installed)
(Fig. 1)
1.30" or more (from a wall)
0. 8
0 "
or
m o
re Wall
(Fig. 2)
1. 9
5 "
or
m o
re
3 .4
5 "
o r
m o
re
2 .0
0 "
o r
m o
re
+00EH97068701_EN.book Page 5 Monday, March 14, 2016 9:13 AM
6
EN
Installation Manual
Install the remote control
NOTE
Wiring for the remote control should not be bundled or installed in the same conduit with a power cable.; otherwise, malfunction may result.
Install the remote control away from sources of electrical interference and electromagnetic fields.
1 Insert a flat-blade screwdriver into the groove on the back side of the remote control to remove the rear case.
2 Use the wood screws (2 pieces) supplied with the remote control to attach the rear case of the remote control to the wall. Do not use an electrical screwdriver. Do not over-tighten the screw (Tightening torque is up to 1.5 ftlbs); otherwise, the rear case may be damaged.
3 Connect the electrical wire from the indoor unit to the terminal block of remote control. (Refer to Page 7 Wire the remote control.) Check the terminal number of electrical wire from the indoor unit to avoid miswiring. (If AC 208/230 V is applied, the remote control and indoor unit will break down.)
Rear case
Remote control
Wood screw x 2
Wall
+00EH97068701_EN.book Page 6 Monday, March 14, 2016 9:13 AM
7
Installation Manual
Wire the remote control
Wiring diagram Terminal block for the remote control wiring on the indoor unit
Requirements for wiring of group control To make wiring of group control for indoor units of 4-way cassette type and other types, set the 4-way cassette type as the header unit; otherwise, some settings such as the individual louver setting are not available.
Requirements for installing two remote controls In the dual remote control system, one or more units are operated from two remote controls. (Up to two remote controls can be installed.)
Set the Follower remote control Set from 6. Header/Follower in Initial setting on the MENU screen. For details, refer to the page 17.
Install the remote controls For the dual remote control system, install the remote controls as follows:
1 Set one remote control as the Header remote control. (The remote controls are set as Header remote control as factory default.)
2 When the dual remote control system is installed by using this remote control (RBC-AMS54E-UL) with the other type of remote control, set this remote control as the Header remote control.
Remote control wiring (procured locally)
Terminal block for the remote control wiring
Remote control
* Terminals of A and B have no polarity.
* Use wire of AWG20 to AWG14. * A crimp-style terminal cannot be used.
AA
BB
+00EH97068701_EN.book Page 7 Monday, March 14, 2016 9:13 AM
8
EN
Installation Manual
Basic wiring diagram
NOTE
Terminals of A and B have no polarity.
To diverge from the indoor unit To diverge from the Header remote control
To operate a group control of multiple indoor units by two remote controls * The Header or Follower remote control can be connected to any indoor unit.
Remote control (Header)
Remote control (Follower)
(Sold separately)
Terminal block for the remote control wiring
Ground
Indoor unit
Remote control wiring (Locally procured) AWG20 to AWG14.
A B A B
A B
Remote control wiring (Locally procured) AWG20 to AWG14.
Remote control (Header)
Remote control (Follower)
(Sold separately)
Terminal block for the remote control wiring
Ground
Indoor unit
A B A B
A B
Remote control inter-unit wires for group control (Locally procured)
Remote control (Header)
Remote control (Follower)
(Sold separately)
Terminal block for the remote control wiring
Ground
Indoor unit No.1
Ground Ground Ground
Indoor unit No.2
Indoor unit No.3
Indoor unit No.8
A B
A B
A B
A BA BA B
+00EH97068701_EN.book Page 8 Monday, March 14, 2016 9:13 AM
9
Installation Manual
For first use It takes some time before the remote control becomes operable when the remote control is used for the first time. This is not a malfunction.
It takes about 5 minutes before the remote control becomes operable.
It takes about 1 minute before the remote control becomes operable.
Note For the operation of switching the room temperature sensor or the settings of the test operation, refer to the page 20.
Power on flashes disappears
Remote control becomes operable.
About 5 minutes
Power on flashes disappears
Remote control becomes operable.
About 1 minute
+00EH97068701_EN.book Page 9 Monday, March 14, 2016 9:13 AM
10
EN
Installation Manual
Part Names and Functions
Switching between the normal display and detailed display Push and hold the [ CANCEL] button and [ MONITOR] button at the same time for more than 4 seconds to switch the display mode. The normal display mode is selected as factory default setting.
Detailed display mode
1 [ MONITOR] button Displays the monitoring screen.
2 [ MENU] button Displays the menu screen.
3 [ CANCEL] button Functions as indicated on the screen, such as returning to the previous menu screen.
4 [ ] button During normal operation: adjusts the temperature. On the menu screen: selects a menu item.
5 [ ] button During normal operation: adjusts the temperature. On the menu screen: selects a menu item.
6 [ F1] button Varies its function according to the setting screen.
7 [ F2] button Varies its function according to the setting screen.
8 [ ON / OFF] button
2
6 7
4,5
3
1
8
75 Room A 12:00
Mode Fan Speed Cool
Temperature sensor
75 Room A 12:00
Mode Fan Speed Cool
Icons appear on the screen when the detailed display mode is selected.
+00EH97068701_EN.book Page 10 Monday, March 14, 2016 9:13 AM
11
Installation Manual
Monitor screen Check the current usage status.
NOTE
Total running hour The Total running hour is recorded on the remote control. The time is not recorded during Self cleaning operation or fan operation. Outdoor temp. Displays the temperature around the vent of the outdoor unit. The displayed temperature may differ from the actual outdoor temperature. Others The Header status appears during group connection. The screen returns to the previous display if no operation is performed for 60 seconds.
1 Push [ MONITOR] button. The monitor screen appears.
2 Push [ CANCEL] button to return.
(1) Displays the set temperature. (2) Displays the temperature measured by the indoor
temperature sensor of the indoor unit. If the sensor is set to that of the remote control, the temperature measured by the remote control sensor is displayed.
(3) Displays the temperature around the vent of the outdoor unit.
(4) Displays the remaining time until the filter sign lights up.
(5) Displays the accumulated operating time.
75 Room A 12:00
Mode Fan Speed Cool
Set temp. 75F 75F 95F 2500
10480
Indoor temp. Outdoor temp. Filter remaining hour Total running hour
Monitor
Return
(1) (2) (3) (4) (5)
+00EH97068701_EN.book Page 11 Monday, March 14, 2016 9:13 AM
12
EN
Installation Manual
Initial setting
1. Clock Set the Year, Month, Day, and time.
1 Push the [ MENU] button to display the menu screen.
2 Push the [ ] / [ ] button to select 10. Initial settingon the menu screen, then push the Set [ F2] button.
3 Push the [ ] / [ ] button to select an item on the Initial setting screen.
4 Push the Set [ F2] button. The selected menu setting screen will be
displayed.
5 Push the [ CANCEL] button to return. The screen returns to the Initial setting screen.
1 Push the [ ] / [ ] button to select 1. Clock on the Initial setting screen, then push the Set [ F2] button.
2 Push the [ ] / [ ] button to select the Year, Month, Day, and time. Push the - [ F1] / +
[ F2] button to set the value.
3 Push the [ MENU] button.
Initial setting(1/2) 1.Clock 2.Name of room 3.Screen contrast 4.Backlight 5.Key lock
Set Return Set
Set
Initial setting(1/2) 1.Clock 2.Name of room 3.Screen contrast 4.Backlight 5.Key lock
Set Return
Set
+
Clock Day Month Year Hour Minute
01 01
2016 00 00
+ Return Fix
+00EH97068701_EN.book Page 12 Monday, March 14, 2016 9:13 AM
13
Installation Manual
To adjust the clock
2. Name of room Set the name of the room or place where the remote control is installed. (Operations of the air conditioner are possible without this setting.)
1 Push the [ ] / [ ] button to select 1. Clock on the Initial setting screen, then push the Set [ F2] button.
2 Push the [ ] / [ ] button to select the Year, Month, Day, and time. Push the - [ F1] / +
[ F2] button to set the value.
3 Push the [ MENU] button. The screen returns to the Initial setting screen.
The clock display appears on the upper right of the screen. The clock display blinks if the clock setting has
been reset due to power failure or other cause.
NOTE
The available date range is from January 1st, 2016 to December 31st, 2099.
1 Push the [ ] / [ ] button to select 2. Name of room on the Initial setting screen, then push the Set [ F2] button.
2 Set the name of the remote control.
Enter the characters of the name in the screen (1). Move the cursor to select the character with the [ ] / [ ] button and [ F1] / [ F2] button (the selected character is highlighted), then push the [ MENU] button. Name of the remote control appears.
Up to 16 characters can be entered for Name of room.
Clock Day Month Year Hour Minute
01 01
2016 00 00
+ Return Fix
Set
+
75 Room A 12:00
Mode Fan Speed Cool
Initial setting(1/2) 1.Clock 2.Name of room 3.Screen contrast 4.Backlight 5.Key lock
Set Return
Set
Return Set Fix Del
ABCDE FGH I J KLMNO PQRST UVWXY
Z & / : abcde f g h i j k lmno p q r s t
uvwxy z+!? 12345 67890 . # ()
(1)
+00EH97068701_EN.book Page 13 Monday, March 14, 2016 9:13 AM
14
EN
Installation Manual
3. Screen contrast Adjust the contrast of the LCD.
To delete a character, highlight Del and push [ MENU] button.
To confirm the name, highlight Fix and push [ MENU] button. The screen returns to the Initial setting screen.
1 Push the [ ] / [ ] button to select 3. Screen contrast on the Initial setting screen, then push the Set [ F2] button.
2 Push the - [ F1] / + [ F2] button to adjust.
3 Push the [ MENU] button. The screen returns to the Initial setting screen.
Return Set Fix
ABCDE FGH I J KLMNO PQRST UVWXY
Z & / : abcde f g h i j k lmno p q r s t
uvwxy z+!? 12345 67890
Bedroo
Del . # ()
Return Set
Del
ABCDE FGH I J KLMNO PQRST UVWXY
Z & / : abcde f g h i j k lmno p q r s t
uvwxy z+!? 12345 67890
705A
Fix. # ()
Initial setting(1/2) 1.Clock 2.Name of room 3.Screen contrast 4.Backlight 5.Key lock
Set Return
Set
+
Screen contrast
+
+
Return Fix
+00EH97068701_EN.book Page 14 Monday, March 14, 2016 9:13 AM
15
Installation Manual
4. Backlight Turn on or off the back light of the LCD.
1 Push the [ ] / [ ] button to select 4. Backlight on the Initial setting screen, then push the Set [ F2] button.
2 Push the [ ] / [ ] button to select ON or OFF.
3 Push the [ MENU] button. When ON is selected, the back light is turned
on during operating with the remote control. When OFF is selected, the back light is not
turned on.
NOTE
The back light of the LCD is turned on as factory default.
The back light is on for a predetermined time after button operation.
Initial setting(1/2) 1.Clock 2.Name of room 3.Screen contrast 4.Backlight 5.Key lock
Set Return
Set
Backlight ON
OFF
Return Fix
+00EH97068701_EN.book Page 15 Monday, March 14, 2016 9:13 AM
16
EN
Installation Manual
5. Key lock Select whether to lock / unlock [ON / OFF], [ ], [MODE](F1) and [FAN SPEED](F2).
1 Push the [ ] / [ ] button to select 5. Key lock on the Initial setting screen, then push the Set [ F2] button.
2 Push the [ ] / [ ] button to select a key to lock / unlock.
3 Push the [ F1] button to select Lock, or [ F2] button to select Unlock.
4 Push the [ MENU] button. When "Lock" is selected, the key cannot be
used during key lock. When "Unlock" is selected, the key can be used even during key lock.
All keys are unlocked while Check is displayed.
For the key lock setting, refer to the owners manual.
The factory default is "Lock".
Initial setting(1/2) 1.Clock 2.Name of room 3.Screen contrast 4.Backlight 5.Key lock
Set Return
Set
ON/OFF
Set temp. Lock / Unlock
Lock / Unlock
Key lock(1/2)
Return Fix
Mode
Fan speed Lock / Unlock
Lock / Unlock
Key lock(2/2)
Return Fix
+00EH97068701_EN.book Page 16 Monday, March 14, 2016 9:13 AM
17
Installation Manual
6. Header/Follower Set the remote control as Header remote control or Follower remote control when the dual remote control system is used. Carry out the setting operation while the indoor unit is stopped. (Turn off the air conditioning unit before starting the setting operation.)
Note for the Header/Follower setting Set the RBC-AMS54E-UL remote control as the Header remote control when the dual remote control system is
used. The RBC-AMS54E-UL remote control can be used as the Follower remote control when the dual remote control
system is used that consists of two RBC-AMS54E-UL remote controls. The following functions are not available when the remote control is set as the Follower remote control:
Schedule timer / Off reminder timer / Night operation / Energy saving operation / Return back / Saving operation
NOTE
Some functions are not available when the remote control is set as the Follower remote control. In the dual remote control system, the latter operation overrides the former. The remote control is set as Header remote control as factory default. If the Header/Follower remote control settings are not set correctly, the E01, E03, or E09 check code is
displayed.
1 Push the [ ] / [ ] button to select 6. Header/Follower on the Initial setting screen, then push the Set [ F2] button.
2 Push the [ ] / [ ] button to select the setting.
3 Push the [ MENU] button. Setting appears on the screen, then the
screen returns to the Initial setting screen.
Initial setting(2/2) 6.Header/Follower 7.Language 8.Press & hold 4 sec.
Set Return
Set
Header/Follower Header remote controller Follower remote controller
Return Fix
Header remote control
Follower remote control
Indoor unit
Outdoor unit
+00EH97068701_EN.book Page 17 Monday, March 14, 2016 9:13 AM
18
EN
Installation Manual
7. Language Select a language for the screen text.
1 Push the [ ] / [ ] button to select 7. Language on the Initial setting screen, then push the Set [ F2] button.
2 Push the [ ] / [ ] button to select a language.
3 Push the [ MENU] button. The screen text changes to the selected language. The factory default is English.
These two screens appear for RBC-AMS54E-UL.
Initial setting(2/2) 6.Header/Follower 7.Language 8.Press & hold 4 sec.
Set Return
Set
Language(1/2)
English French German Spanish Portuguese
Franais Deutsch Espaol Portugus
Return Fix
Language(2/2)
Dutch
Return Fix
Nederlands
+00EH97068701_EN.book Page 18 Monday, March 14, 2016 9:13 AM
19
Installation Manual
8. Press & hold 4sec. Set the Press & hold 4 sec. operation for the [ ON / OFF] button.
1 Push the [ ] / [ ] button to select 8. Press & hold 4sec. on the Initial setting screen, then push the Set [ F2] button.
2 Push the [ ] / [ ] button to select ON or OFF.
3 Push the [ MENU] button. When ON is selected, the air-conditioner
starts / stops running when the [ ON / OFF] button is pressed and hold 4 seconds.
When OFF is selected, the air-conditioner starts / stops running when the [ ON / OFF] button is pressed.
Initial setting(2/2) 6.Header/Follower 7.Language 8.Press & hold 4 sec.
Set Return
Press & hold 4sec. ON
OFF
Return Fix
Set
+00EH97068701_EN.book Page 19 Monday, March 14, 2016 9:13 AM
20
EN
Installation Manual
Field setting menu
1. Test mode Set for the test operation after installation.
Before the test mode Perform the followings before turning on the power:
1) By using 500 V-megger, check that resistance of 1 M or more exists between the terminal block of the power supply and the ground (grounding). If resistance of less than 1 M is detected, do not run the unit.
2) Check all valve of the outdoor unit is opened fully.
To protect the compressor at the time of startup, leave the power on for 12 hours or more before operation. Do not press the electromagnetic contactor to forcibly perform the test mode. (It is very dangerous because the
protective device does not work.) Peel off the protective sheet affixed when the remote control was shipped before performing a test run.
Performing the test mode For the procedure of the operation, refer to the supplied Owners Manual. A forced test mode can be performed according to the following procedure when the room temperature rises / falls enough for the thermostat to turn off. In order to prevent a continuous operation, the forced test operation is released after 60 minutes have passed and returns to the normal operation.
CAUTION .
Do not perform the forced test mode for purposes other than the test mode because it applies an excessive load to the devices.
1 Push the [ MENU] button to display the menu screen.
2 Push and hold the [ MENU] button and the [ ] button at the same time to display the Field setting menu. Push and hold the buttons for more than 4
seconds.
3 Push the [ CANCEL] button to return.
Item Function
1. Test mode Settings for when performing the test operation after installation
2. Register service info Registration of information about the contact number for service, model name and serial number of the indoor unit and outdoor unit
3. Alarm history List of latest 10 alarm data: information of check code, date, time, and unit
4. Monitor function Monitoring data of sensor temperature, rotating speed of the compressor or other factor.
5. Setting louver position Change the louver indication setting to match the indoor unit type.
6. Setting timer operation mode Set whether or not the operation mode can be selected when setting the schedule timer.
7. DN setting Advanced settings using DN code
1.Test mode 2.Register service info. 3.Alarm history 4.Monitor function 5.Setting louver position
Field setting menu
Return Set
+00EH97068701_EN.book Page 20 Monday, March 14, 2016 9:13 AM
21
Installation Manual
1 Push the [ ] / [ ] button to select 1. Test mode on the Field setting menu screen, then push the Set [ F2] button. Pushing the Yes [ F1] button
sets the test mode and the screen returns to the Field setting menu screen. Push [ CANCEL] twice, the screen (2) appears.
2 Push the [ ON / OFF] button to start the test mode. The screen (1) shown in the left appears. (The screen (2) appears when the operation is stopped.) Perform the test mode in the Cool or Heat
mode. Temperature setting cannot be adjusted during
the test mode. Check codes are displayed as usual.
3 When the test mode is finished, push the [ ] / [ ] button to select 1. Test mode on the Field setting menu screen, then push the Set [ F2] button. The screen (3) appears. Pushing the Yes [ F1] button
stops the test mode screen and continues the normal operation.
NOTE
The test mode stops after 60 minutes and the screen returns to the normal / detailed display.
1.Test mode 2.Register service info. 3.Alarm history 4.Monitor function 5.Setting louver position
Field setting menu(1/2)
Return Set
Set
Yes
Return
Test mode start.
NoYes
Test mode
Test
(1) Room A 12:00
Mode Fan Speed Cool
Set
Yes
Test
(2) Room A 12:00
Return
Test mode stop.
NoYes
Test mode(3)
+00EH97068701_EN.book Page 21 Monday, March 14, 2016 9:13 AM
22
EN
Installation Manual
Using the Service monitor with the [ MONITOR] button during the test mode
2. Register service info. Register information about the contact number for service, model name and serial number of the indoor unit and outdoor unit.
Enter information manually for a Light commercial outdoor unit. Information data of Light commercial indoor unit, VRF indoor unit, and VRF outdoor unit is loaded automatically. Automatic loading is not available for some models. In this case, enter information manually.
Enter the contact number for service displayed in 2. Service information of 14. information on the menu screen.
Enter the model name and serial number displayed in 1. Model information of 14. information on the menu screen.
Push the [ MONITOR] button
Refer to 4. Monitor function (page 27) for details.
When the group control is used, select the unit to monitor in the unit selection screen before displaying the monitoring display.
Test
Room A 12:00
Mode Fan Speed Cool
Code 00
Data 0024
Return
Monitor function
+00EH97068701_EN.book Page 22 Monday, March 14, 2016 9:13 AM
23
Installation Manual
Entering information manually
Entering the contact number for service
1 Push the [ ] / [ ] button to select 2. Register service info. on the Field setting menu screen.
2 Push the Set [ F2] button. The setting screen for entering information
appears.
3 Enter the information with the [ F1] / [ F2] button and [ ] / [ ] button.
Item Function
1. Service contact tel No. Enter the contact number for service.
2. Outdoor model name Enter / reset the model name of the outdoor unit.
3. Outdoor unit serial No. Enter / reset the serial number of the outdoor unit.
4. Indoor model name Enter / reset the model name of the indoor unit.
5. Indoor unit serial No. Enter / reset the serial number of the indoor unit.
1 Push the [ ] / [ ] button to select 1. Service contact tel No., then push the Set [ F2] button.
2 Move the cursor to select the character (selected character is highlighted) with the [ F1] / [ F2] button, then enter the contact number with the [ ] / [ ] button.
3 Push the [ MENU] button.
1.Service contact tel No. 2.Outdoor model name 3.Outdoor unit serial No. 4.Indoor model name 5.Indoor unit serial No.
Register service info.
Return Set
Set
1.Service contact tel No. 2.Outdoor model name 3.Outdoor unit serial No. 4.Indoor model name 5.Indoor unit serial No.
Register service info
Return Set
Set
Input telephone number Service contact tel No.
FixReturn
- - - - - - - - - - - -
+00EH97068701_EN.book Page 23 Monday, March 14, 2016 9:13 AM
24
EN
Installation Manual
Entering the model name and serial number Enter the model name and serial number manually for a Light commercial outdoor unit. Information data is loaded automatically for Light commercial indoor units, VRF indoor units (excluding large capacity air discharge type and duct type), and VRF outdoor units. Enter the model name and serial number manually after replacing the circuit board to the service circuit board (unless entering information manually before replacement of the circuit board).
Entering the model name and serial number manually
Product Model name and serial number display
Light commercial indoor unit Information data is loaded automatically from the indoor unit and displayed.
VRF indoor unit Information data is loaded automatically from the indoor unit and displayed. Enter information manually for the indoor unit of large capacity air discharge type and duct type.
VRF outdoor unit Information data is loaded automatically from the outdoor unit and displayed.
Light commercial outdoor unit Enter information manually on the remote control.
Service circuit board Enter information manually on the remote control.
1 Push the [ ] / [ ] button to select 2. Outdoor model name on the Register service info screen, then push the Set [ F2] button. Select 3. Outdoor unit serial No. to enter the
serial number of the outdoor unit. Select 4. Indoor model name to enter the
model name of the indoor unit. Select 5. Indoor unit serial No. to enter the
serial number of the indoor unit.
Does the indoor unit / outdoor unit automatically load information data of model name and serial number to the remote control?
The model name and serial number loaded from the unit are displayed.
1. Manual entry is not needed. 2. Select Indoor unit (Outdoor unit) for the display mode
(factory default).
1. Enter the model name and serial number of the unit manually on the remote control.
2. Select Remote control for the display mode.
Yes No
1.Service contact tel No. 2.Outdoor model name 3.Outdoor unit serial No. 4.Indoor model name 5.Indoor unit serial No.
Register service info
Return Set
Set
+00EH97068701_EN.book Page 24 Monday, March 14, 2016 9:13 AM
25
Installation Manual
Selecting the model name and serial No.
2 Push the [ ] / [ ] button to select 1. Manual model name input on the Outdoor model name screen, then push the Set [ F2] button. Select 1. Manual serial No. input of 3.
Outdoor unit serial No. to enter the serial number of the outdoor unit.
Select 1. Manual model name input of 4. Indoor unit model name to enter the model name of the indoor unit.
Select 1. Manual serial No. input of 5. Indoor unit serial No. to enter the serial number of the indoor unit.
3 Enter the model name of the outdoor unit. See page 13 about how to enter the model
name and serial number.
4 Select Remote controller for the display mode of model name or serial number to display the manually entered model name or serial number. (See page 13.)
1 Push the [ ] / [ ] button to select 2. Model name selection on the Outdoor model name screen, then push the Set [ F2] button. To select the serial number of the outdoor unit,
select 2.Serial No. selection of 3. Outdoor unit serial No. .
To select the model name of the indoor unit, select 2. Model name selection of 4. Indoor unit model name.
To select the serial number of the indoor unit, select 2.Serial No. selection of 5. Indoor unit serial No..
2 Push the [ ] / [ ] button to select Remote controller or Outdoor unit. When Outdoor unit or Indoor unit is selected,
the model name or serial number received from the outdoor or indoor unit is displayed.
When Remote controller is selected, the manually entered model name or serial number is displayed.
The factory default is Outdoor unit or Indoor unit.
3 Push the [ MENU] button. The screen returns to the Outdoor model
name screen.
1.Manual model name input 2.Model name selection Outdoor model name
Outdoor model name
Return Set
Fix
Set
Return Set Fix Del
ABCDE FGH I J KLMNO PQRST UVWXY
Z & / : abcde f g h i j k lmno p q r s t . # ()
uvwxy z+!? 12345 67890
1.Manual model name input 2.Model name selection Outdoor model name RAV-SP180AT2-UL
1-1 Outdoor model name
Return Set
Fix
Set
Model name selection Remote controller
Outdoor unit
Return Fix
+00EH97068701_EN.book Page 25 Monday, March 14, 2016 9:13 AM
26
EN
Installation Manual
Checking the model name or serial number The model name or serial number to be displayed on the Outdoor (Indoor) model name or Outdoor (Indoor) unit serial No. screen is displayed.
3. Alarm history List of latest 10 alarm data: information of check code, date, time, and unit, is displayed.
Deleting the alarm history
1 Push the [ ] / [ ] button to select 3. Alarm history on the Field setting menu screen, then push the Set [ F2] button.
List of latest 10 alarm data is displayed. * The oldest data are deleted in order to record
the new ones. The date and time when the check code
occurred for the first time is displayed for the repeated alarm.
1 Push the Reset [ F2] button while the list of Alarm history is displayed.
2 Push the Yes [ F1] button after the confirmation screen is displayed. Delete the Alarm history in each remote control
when the dual remote control system is used.
1.Manual model name input 2.Model name selection Outdoor model name RAV-SP180AT2-UL
1-1 Outdoor model name
Return Set
Fix
Appears here.
1.Test mode 2.Register service info. 3.Alarm history 4.Monitor function 5.Setting louver position
Field setting menu(1/2)
Return Set
Set
Unit Code Date Time 1. 12 E04 31/12/2016 12:25 2. 3. 4.
Alarm history
Return Reset
Return
Reset all alarm data.
NoYes
Alarm history
B3
Reset
Yes
+00EH97068701_EN.book Page 26 Monday, March 14, 2016 9:13 AM
27
Installation Manual
4. Monitor function The sensor temperature or operational status of indoor unit, outdoor unit, or remote control can be monitored.
1 Push the [ ] / [ ] button to select 4. Monitor function on the Field setting menu screen, then push the Set [ F2] button. Push the [ ] / [ ] button to select
the code to check data.
2 Refer to the Installation Manual supplied with the indoor unit or outdoor unit or service manual for details about the check code and data.
3 Push the [ CANCEL] button to return to the Field setting menu screen.
Monitor function
Code 00
Data 0024
Return
Set
+00EH97068701_EN.book Page 27 Monday, March 14, 2016 9:13 AM
28
EN
Installation Manual
5. Setting louver position The louver indication setting can be changed.
1 Push the [ ] / [ ] button to select 5. Setting louver position, then push the Set [ F2] button. Impossible is displayed in the case of a model
for which the wind direction cannot be set. is displayed for the selected item.
2 Push the [ ] / [ ] button to select an item on the Field position indication screen. The highlighted item can be set. Move with the [ F1] /
[ F2] button to set the setting.
3 After setting each item, push the MENU [ MENU] button to confirm the changes to the settings.
Change the flap position indication for when swinging is cancelled in [Fixed position indicator]. When ON is selected, the louver stops and the indication becomes as shown on the right
when swinging is cancelled. (Factory default)
When OFF is selected, the stop position and indication becomes as shown on the right after swinging is cancelled.
Change the louver operation direction indication in [Operation mode]. When Up/Down is selected, the louver operation direction indication becomes as shown
on the right. (Factory default)
When Left/Right is selected, the louver operation direction indication becomes as shown on the right. This can be used with a model whose louver moves left and right.
ON / OFF
Up/Down / Left/Right
Setting louver position
Return Fix
1.Fixed position indication
2.Operation mode Set
+00EH97068701_EN.book Page 28 Monday, March 14, 2016 9:13 AM
29
Installation Manual
6. Setting timer operation mode Set the operation mode setting in the setting timer operation mode.
1 Push the [ ] / [ ] button to select 6. Setting timer operation mode, then push the Set [ F2] button. Move with the [ F1] /
[ F2] button to set the setting. is displayed for the selected item.
2 Push the MENU button to confirm the change and return to the Field setting menu screen. Push the CANCEL button to return to the Field setting menu screen without confirming the change.
Operation mode switching Setting timer operation mode
Return Fix
ON / OFF Set
+00EH97068701_EN.book Page 29 Monday, March 14, 2016 9:13 AM
30
EN
Installation Manual
7. DN setting Perform the advanced settings for the air conditioner. Carry out the setting operation while the indoor unit is stopped. (Turn off the air conditioning unit before starting the setting operation.)
NOTE
The following changes are settings to be configured by installation and service personnel. If they are set incorrectly, trouble such as the product becoming inoperable may occur.
For indoor units which do not support the functions below, the following DN code settings may not be possible. Do not perform header/follower connection for a remote control which does not support the functions below. For operation when connected to an air conditioning control system which does not support the functions below, refer
to Changing the temperature in the Owner's Manual.
1 Push the [ ] / [ ] button to select 7. DN setting on the Field setting menu screen, then push the Set [ F2] button. The fan and louver of the indoor unit operate.
When the group control is used, the fan and louver of the selected indoor unit operate.
Move the cursor to select Code(DN) with the < [ F1] button, then set Code(DN) with the [ ] / [ ] button.
Move the cursor to select Data with the > [ F2] button, then set Data with the [ ] / [ ] button.
2 Refer to the Installation Manual supplied with the indoor unit or service manual for details about the Code(DN) and Data.
3 Push the [ MENU] button to set the other Code (DN) and Data. After Continue? is displayed on the screen, push the Yes [ F1] button.
4 Push the No [ F2] button to finish the setting operation. Setting appears on the screen for a while, then the screen returns to the Field setting menu screen. Pushing the No [ F2] button
displays the unit selection screen when the group control is used. Push the [ CANCEL] button on the unit selection screen to finish the setting operation. Setting appears on the screen for a while, then the screen returns to the Field setting menu screen.
DN Item Description Factory default
77 Dual set point setting 0000: Normal automatic 0002: Dual automatic
0000
DN setting Code (DN) Data
Return
10 0000
Fix < >
Set
<
>
Yes
No
No
DN setting Code (DN) Data
Return
10 0001
Fix < >
Return
Continue?
NoYes
DN setting
+00EH97068701_EN.book Page 30 Monday, March 14, 2016 9:13 AM
Related manuals for Carrier Toshiba RBC-AMS54E-UL Installation Manual
Manualsnet FAQs
If you want to find out how the Toshiba Carrier works, you can view and download the Carrier Toshiba RBC-AMS54E-UL Installation Manual on the Manualsnet website.
Yes, we have the Installation Manual for Carrier Toshiba as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.
The Installation Manual should include all the details that are needed to use a Carrier Toshiba. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.
The best way to navigate the Carrier Toshiba RBC-AMS54E-UL Installation Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.
This Carrier Toshiba RBC-AMS54E-UL Installation Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.
You can download Carrier Toshiba RBC-AMS54E-UL Installation Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.
To be able to print Carrier Toshiba RBC-AMS54E-UL Installation Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier Toshiba RBC-AMS54E-UL Installation Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.