Remote controller installation requirements

Accessory parts

Installation place

Remote controller installation dimension

No.

1

2

1

2

3 2

Part Name Q'ty No.

4

5

1

1

Part Name Q'ty

Wood screws

Installation Manual

Owner's Manual

EH99677801 (EN)

Remote controller

Screw 0.16" x 0.79" (M4 x 20 mm)

Connection diagram

How to select the room temperature sensor

(Fig. 1)

To installation personnel - Electrical work and ServiceINSTALLATION MANUAL Remote controller with weekly timer Model: RBC-AMS41UL

Install the remote controller 3'3" to 4'11" (1 m - 1.5 m) above floor level (average room temperature area).

Do not install the remote controller in a place exposed to direct sunlight or outside air (such as a window, etc.).

Do not install the remote controller where ventilation is poor. Do not install the remote controller in a freezing or refrigerated area - the

remote controller is not water or splash-proof. Install the remote controller in a vertical position.

Be sure to follow the installation dimension as shown in the figure 1 when you install the remote controller on the wall.

Two room temperature sensors are installed: one in the indoor unit; the other in the remote controller. Only one sensor (usually the indoor units) can be active at any one time. To select the sensor in the remote controller, perform the following steps. 1.Push + temperature setup button for 4 seconds or more. NOTE:The unit number displayed the first time is the indoor unit address of

the master unit in the group control. NOTE:Do not press the button. 2.Using the temperature setup buttons / , specify the item code . 3.Using the timer buttons / , change the setting from to . 4.Push the button. (The display should stop flashing and become

constantly lit.) 5.Push the button. The status returns to the operation stop status and is displayed in the

LCD. NOTE 1:When using two remote controllers, the room temperature sensor

selection can be set either from the header/follower remote controller. Only the header remote controller can act as a remote control sensor. When using two remote controllers, the temperature can be set from either the header or follower remote controller.

NOTE 2:In group control, the remote control sensor does not work if the group address is not set to the indoor unit of the master unit.

NOTE 3:When using the remote sensor and the remote controller together, do not use the remote control sensor of the remote controller.

In a dual remote controller system, one or more units are operated by multiple remote controllers. (A maximum of two remote controllers can be set.)

How to install For a dual remote controller system, install the remote controllers in the following way. 1.Set one of remote controllers as the header remote controller. (The default

setting is Header.) 2.Set the DIP switch on all other remote controller P.C. boards to Sub (to enable

them as follower remote controllers).

1.For removal of the remote controllers lower case (rear case), insert the tip of a straight blade screwdriver, etc., into the two openings at the bottom of the remote controller to open the lower case.

2.Fix the remote controllers rear case by wood screws (2 pcs.). Do not over tighten, as it may damage the rear case.

3.Connect the wires from the indoor unit to the remote controller terminal block. (Refer to How to wire the remote controller.)

Connect the wires of the remote controller following the terminal numbering convention of the indoor unit to prevent miswiring. (Do not apply AC 208-230V mains voltage to the remote controller as it will be damaged).

NOTE 1:The remote controller wire should not be bundled with other wires (mains, etc.), or installed with other wires in the same conduit, as malfunction may result.

NOTE 2:Install the remote controller away from sources of electrical interference and electromagnetic fields.

NOTE 3:If electrical interference is unavoidable, countermeasures such as appropriate filtering should be employed.

Operating a group control of multiple indoor units from remote controllers installed in two different locations. * Header and Follower remote controllers are operable even if they are

connected to any indoor unit.

How to install the remote controller

How to wire the remote controller

Multiple remote controller installation requirements

Terminal block for remote controller wiring in indoor unit

*AWG20 (Use 0.5 mm2 wire) *Can not use the closed end

wire joint. *Use UL wires rated 300 V.

SET

UNIT

1.Push and hold the button for 4 seconds or more until TEST appears in the LCD, then press the button. TEST appears in LCD during the test run. Temperature adjustment is not possible while TEST is displayed. The test

run applies considerable load on the machine; therefore, it is recommended not to use the test mode beyond necessity.

2.The test mode should be used in either HEAT or COOL mode. NOTE:The outdoor unit will not operate for approx. 3 minutes after power up,

or the operation will stop. 3.Be sure the TEST indication in the LCD has disappeared by pushing the button again after exiting the test mode. (The remote controller has a

60-minute off timer function to prevent continuous test run).

Remote controller test run setup

Follow the steps below to select and set the operation status of the air conditioner when power is restored after a power outage has occurred during a scheduled operation. 1.Hold down the + buttons for at least 4 seconds. (This step can be

performed whether the air conditioner is running or shut down.) 2. Press the TEMP. / buttons, and set code No.14. 3. Press the TIME / buttons, and set the setting data to (factory

setting) or . 4. Press the button. The setting data is entered successfully if the display

stops blinking and lights up. 5. Press the button. * (factory setting): No settings are sent when the power is restored, and the scheduled

operation is resumed as soon as the program time is reached after the power has been restored.

* :If there was a program which was to have run during the power outage, it is resumed in accordance with what was programmed. If there is no program, operation resumes in accordance with what was being performed prior to the power outage.

Selecting the operation when the power is restored after a power outage

ON/OFF

Operating one indoor unit from remote controllers installed in two different locations.

Paper size: A4 297x210

4.7" (120) 2.4" (62)

in (mm)

3. 3"

(8 4)

0. 7"

(1 8)

4. 7"

(1 20

)

Wood screws

Remote controller

Cover

Lower case (Rear case)

Wiring slot

Remote controller (inside, rear)

Indoor unit No.1

Indoor unit No.2

Indoor unit No.3

Indoor unit No.8

Remote controller inter-unit wires for group control

Terminal block for remote controller wire

(Field procurement)

Remote controller (Header)

Indoor unit

Ground

GroundGroundGroundGround

Terminal block for remote controller wiring

(sold separately)

Remote controller (Follower)

Remote controller (Header)

(Sold separately)

Remote controller (Follower)

Remote controller

Remote controller wiring (Field procurement)

Remote

Manualsnet FAQs

If you want to find out how the RBC-AMS41UL Carrier works, you can view and download the Carrier Toshiba RBC-AMS41UL Installation Manual on the Manualsnet website.

Yes, we have the Installation Manual for Carrier RBC-AMS41UL as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Installation Manual should include all the details that are needed to use a Carrier RBC-AMS41UL. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier Toshiba RBC-AMS41UL Installation Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier Toshiba RBC-AMS41UL Installation Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier Toshiba RBC-AMS41UL Installation Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier Toshiba RBC-AMS41UL Installation Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier Toshiba RBC-AMS41UL Installation Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.