Carrier Aquazone 50PSW Installation Instructions PDF

1 of 28
1 of 28

Summary of Content for Carrier Aquazone 50PSW Installation Instructions PDF

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500103-01 Printed in U.S.A. Form 50PSW-3SI Pg 1 419 8-14 Replaces: NEW

Installation, Start-Up, and Service Instructions

CONTENTS Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Step 1 Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2 Step 2 Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 STORAGE PROTECTION INSPECT UNIT Step 3 Locate Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Step 4 Mount Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Step 5 Connect Piping. . . . . . . . . . . . . . . . . . . . . . . . . 8 WATER SUPPLY AND QUALITY COOLING TOWER/BOILER APPLICATION WELL WATER SYSTEMS EARTH COUPLED GEOTHERMAL SYSTEMS Step 6 Wire Electrical Connections . . . . . . . . . . . 13 PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . . . . 18 Safety Devices and the Complete C Controller . . 18 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Unit Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 21 Cleaning and Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 22 Ground Coupled, Closed Loop and Plateframe

Heat Exchanger Well Systems . . . . . . . . . . . . . . . . 22 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Units with Aquazone Complete C Control . . . . . . . 22 Off Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Heating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Water Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Refrigerant System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 24 Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 50PSW START-UP CHECKLIST . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can

be hazardous due to system pressure and electrical compo- nents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func- tion of cleaning coils. All other operations should be performed by trained service personnel. When working on air-condition- ing equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Improper installation, adjustment, alteration, service, main- tenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individ- ual instructions packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special installation requirements.

Understand the signal words DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARN- ING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.

Recognize safety information. This is the safety alert symbol ( ). When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.

IMPORTANT: Read the entire instruction manual before starting installation.

WARNING

Electrical shock can cause personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable. Install lock- out tag.

Aquazone 50PSW025-420

Water-to-Water Source Heat Pump with Puron Refrigerant (R-410A)

2

GENERAL The Aquazone 50PSW water source heat pump (WSHP)

is a single-package vertically mounted unit with electronic con- trols designed for year-round cooling and heating.

INSTALLATION

Step 1 Check Jobsite Installation, operation and maintenance instructions are provided with each unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed

below to prepare a unit for installation. See Tables 1 and 2 for unit physical data.

Units are designed for indoor installation only. Be sure to al- low adequate space around the unit for servicing. See Fig. 1-4 for overall unit dimensions.

These units are not approved for outdoor installation and must be installed indoors in the structure being conditioned. Do not locate in areas where ambient conditions are not main- tained within 40 to 100 F.

Step 2 Check Unit Upon receipt of shipment at the jobsite, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the car- ton or crating of each unit, and inspect each unit for damage. Ensure the shipping company makes proper notation of any shortages or damage on all copies of the freight bill. Concealed damage not discovered during unloading must be reported to the shipping company within 15 days of receipt of shipment. NOTE: It is the responsibility of the purchaser to file all necessary claims with the shipping company. 1. Verify unit is correct model for entering water tempera-

ture of job. 2. Be sure the location chosen for unit installation provides

ambient temperatures maintained above freezing. Well water applications are especially susceptible to freezing.

3. Be sure the installation location is isolated from sleeping areas, private offices and other acoustically sensitive spaces. NOTE: A sound control accessory package may be used to help eliminate sound in sensitive spaces.

4. Provide sufficient access to allow maintenance and servicing of the compressor and coils.

5. Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of unit if necessary.

6. Provide ready access to water valves and fittings, and screwdriver access to unit side panels.

7. Where access to side panels is limited, pre-removal of the control box side mounting screws may be necessary for future servicing.

STORAGE If the equipment is not needed for immediate installation upon its arrival at the jobsite, it should be left in its shipping carton and stored in a clean, dry area of the building or in a warehouse. Units must be stored in an upright position at all times. If carton stacking is necessary, stack units a maxi- mum of 3 cartons high. Do not remove any equipment from its shipping package until it is needed for installation.

Table 1 50PSW 025-071 Unit Physical Data

WARNING

DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective gloves and gog- gles and proceed as follows: a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from sys-

tem using both high-pressure and low pressure ports. c. Traces of vapor should be displaced with nitrogen

and the work area should be well ventilated. Refrig- erant in contact with an open flame produces toxic gases.

d. Cut component connection tubing with tubing cutter and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system.

e. Carefully unsweat remaining tubing stubs when nec- essary. Oil can ignite when exposed to torch flame.

Failure to follow these procedures may result in personal injury or death.

CAUTION

DO NOT re-use compressor oil or any oil that has been exposed to the atmosphere. Dispose of oil per local codes and regulations. DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed. Failure to follow these proce- dures may result in damage to equipment.

IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsi- bility of the installing contractor to determine and comply with ALL applicable codes and regulations.

CAUTION

To avoid equipment damage, do not use these units as a source of heating or cooling during the construction pro- cess. The mechanical components used in these units can quickly become clogged with construction dirt and debris which may cause system damage.

50PSW UNIT SIZE 025 035 049 061 071 Compressor Type Scroll Scroll Scroll Scroll Scroll Quantity 1 1 1 1 1 Maximum Water Working Pressure (psig/kPa)

400/3100 400/3100 400/3100 400/3100 400/3100

Water Connection Size (in.) FPT 3/4 3/4 1 1 1 Refrigeration Charge (oz/ckt) 48 59 62 72 90 Operating Weight (lb) 240 250 280 310 430 Shipping Weight (lb) 260 270 300 330 450

3

Table 2 50PSW 122-420 Unit Physical Data

50PSW UNIT SIZE 122 180 210 240 360 420 Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Quantity 2 1 1 2 2 2 Maximum Water Working Pressure (psig/kPa) 400/3100 400/3100 400/3100 400/3100 400/3100 400/3100

Water Connection Size (in.) FPT 11/4 11/2 11/2 2 2 2 Refrigeration Charge (oz/ckt) 85 210 220 140 210 220 Operating Weight (lb) 720 850 890 1230 1550 1700 Shipping Weight (lb) 740 870 910 1260 1580 1730

Fig. 1 50PSW025-071 Unit

T

Q R S

24.0

LEFT SIDEUNIT FRONT

L

K

H

J 32.5

E

D

F

24.0

G

P

M N

LEGEND

*Refers to both load and source fluid connections. NOTES:All dimensions are within 0.125 in. Specifications subject to change without notice.

UNIT SIZE

DIMENSIONS (INCHES) FIELD CONN.*

HRP CONN.D E F G H J K L M N P Q R S T

025 2.70 2.50 13.70 2.50 3.25 1.95 14.25 1.95 7.15 11.00 4.25 6.55 8.05 9.55 1.25 3/4 1/2 035 2.30 2.30 14.30 2.50 3.70 2.55 15.70 2.55 7.15 11.00 4.25 6.55 8.05 9.55 1.25 3/4 1/2 049 2.30 2.60 14.30 2.65 3.70 2.65 15.70 2.65 7.15 11.00 4.25 6.55 8.05 9.55 1.25 1 1/2 061 2.30 2.60 14.30 2.65 3.20 2.65 15.20 2.65 7.15 11.00 4.25 6.55 8.05 9.55 1.25 1 1/2 071 2.50 2.60 21.75 4.45 2.50 2.45 21.75 2.65 7.15 11.00 4.25 6.55 8.05 9.55 1.25 1 1/2

HRP Heat Recovery Package

4

Fig. 2 50PSW122-210 Unit

K

L

A

LEFT SIDE

C

B

D H

F

E

G

M

J

SOURCE OUT

SOURCE IN

LOAD OUT

LOAD IN

UNIT REAR

ELECTRICAL CONNECTIONS

FRONTLEFT SIDE

UNIT SIZE

DIMENSIONS (INCHES) WATER CONN. (FPT)A B C D E F G H J K L M

122 37.50 27.62 7.00 8.38 9.25 33.50 20.75 13.50 17.50 3.50 46.00 28.00 11/4 180 37.50 19.75 4.50 8.38 9.25 33.50 24.00 13.50 17.50 3.50 46.00 28.00 11/2 210 37.50 19.75 4.50 8.38 9.25 33.50 23.50 13.50 17.50 3.50 46.00 28.00 11/2

5

Fig. 3 50PSW240-420 Unit

UNIT SIZE

DIMENSIONS (INCHES) WATER CONN. (FPT)A B C D E F G H J K L M

240 70.00 44.00 8.50 24.50 10.50 49.00 17.50 30.00 20.50 3.50 46.00 28.00 2 360 70.00 44.00 4.50 24.50 10.50 49.00 17.50 30.00 23.50 3.50 46.00 28.00 2 420 70.00 44.00 4.50 24.50 10.50 49.00 17.50 30.00 23.50 3.50 46.00 28.00 2

K

L

LOAD OUT

SOURCE OUT

SOURCE IN

LOAD IN

C

B

D H

F

E J

M G

UNIT REAR

A

LEFT SIDE

ELECTRICAL CONNECTIONS

FRONTLEFT SIDE

6

Fig. 4 Service Clearances

Sizes 025 thru 071 (Top View)

No access panels are located on this side.

Load Side Source Side pot - XH laixaoC pot - XH laixaoC

and bottom and bottom

No access is required on this side.

Rev. Valves - top and bottom

Compressor

ecruoS daoL lortnoC Box - top

Service Clearance Water Connections - Qty 2 for the source and qty 2 for the load

24" Minimum 36" Optimum

Access on this side of the unit is required for piping and insulation.

No access is required on this side.

Sizes 122 thru 210 (Top View)

Access on this side of the unit is required for piping and insulation. No access panels are located on this side.

Water Connections - Qty 2 for the source and qty 2 for the load daoL ecruoS

Source Side Load Side pot - XH laixaoC pot - XH laixaoC

and bottom and bottom

No access is required on this

si ssecca oN .edis required on this side.

Rev. Valves - top and bottom

Compressor

Control Box - top Service Clearance

24" Minimum 36" Optimum

419

7

Fig. 4 Service Clearances (cont) PROTECTION Once the units are properly positioned on the jobsite, they must be covered with either a shipping carton, vinyl film, or an equivalent protective covering. Open ends of pipes stored on the jobsite must be capped. This precaution is especially important in areas where painting, plastering, or spraying of fireproof material, etc., is not yet complete. Foreign material that is allowed to accumulate within the units can pre- vent proper start-up and necessitate costly clean-up operations.

Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components.

INSPECT UNIT To prepare the unit for installation, com- plete the procedures listed below: 1. Compare the electrical data on the unit nameplate with

ordering and shipping information to verify that the correct unit has been shipped.

2. Verify that the unit is the correct model for the entering water temperature of the job.

3. Wait to remove the packaging until the unit is ready for installation.

4. Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.

5. Inspect all electrical connections. Be sure connections are clean and tight at the terminals.

6. Loosen bolts and remove shipping clamps on compres- sors equipped with external spring vibration isolators. Compressors are internally spring-mounted.

7. Locate and verify any accessory kit located in compressor section.

8. Remove any access panel screws that may be difficult to remove once unit is installed.

Step 3 Locate Unit The following guidelines should be considered when choosing a location for the WSHP: Units are for indoor use only. Provide sufficient space for water and electrical

connections. Locate unit in an area that allows for easy access and

removal of access panels. Allow enough space for service personnel to perform

maintenance.

Step 4 Mount Unit Rod attachments must be able to support the weight of the unit. See Tables 1 and 2 for unit op- erating weight.

Sizes 240 thru 420 (Top View)

Access on this side of the unit is required for piping and insulation. No access panels are located on this side.

Water Connections - Qty 2 for the source daol eht rof 2 ytq dna daoL ecruoS

Source Side Load Side pot - XH laixaoC pot - XH laixaoC

and bottom and bottom

No access is required on this

si ssecca oN .edis required on this side.

Rev. Valves - top and bottom

Dual Compressors - top and bottom

Control Box - top Service Clearance

24" Minimum 36" Optimum

CAUTION

DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.

419

8

Step 5 Connect Piping Supply and return piping must be as large as the unit connections on the heat pump (larg- er on long runs). Never use flexible hoses of a smaller inside diameter than that of the water connections on the unit. The water-to-water series units are supplied with either a copper or optional cupro-nickel condenser. Should your well driller ex- press concern regarding the quality of the well water available or should any known hazards exist in your area, Carrier recom- mends proper testing to assure the well water quality is suitable for use with water source equipment. In conditions anticipating moderate scale formation or in brackish water a cupro-nickel heat exchanger is recommended.

Both the supply and discharge water lines will sweat if sub- ject to low water temperature. These lines should be insulated to prevent damage from condensation.

All manual flow valves used in the system must be ball valves. Globe and gate valves must not be used due to high pressure drop and poor throttling characteristics.

Never exceed the recommended water flow rates. Serious damage or erosion of the water to refrigerant heat exchanger could occur.

Always check carefully for water leaks and repair appropri- ately. Units are equipped with female pipe thread fittings. Con- sult the specification sheets for sizes. Thread sealant should be used when connecting water piping connections to the units to insure against leaks and possible heat exchanger fouling. Do not overtighten the connections. Flexible hoses should be used between the unit and the rigid system to avoid possible vibra- tion. Ball valves should be installed in the supply and return lines for unit isolation and unit flow balancing. WATER SUPPLY AND QUALITY Check water supply. Water supply should be plentiful and of good quality. See Table 3 for water quality guidelines.

In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the Water Quality Guidelines table. Consult a local water treat- ment firm, independent testing facility, or local water authority for specific recommendations to maintain water quality within the published limits.

COOLING TOWER/BOILER APPLICATION (Fig. 5) To assure adequate cooling and heating performance, the cool- ing tower and boiler fluid loop temperature should be main- tained between 50 F and 100 F. In the cooling mode, heat is rejected from the unit into the condenser water loop. A cooling tower provides evaporative cooling to the loop water; thus, maintaining a constant supply temperature to the unit. When utilizing an open cooling tower, chemical water treatment is mandatory to ensure the water is free of corrosive materials. A secondary heat exchanger (plate frame between the unit and the open cooling tower) may also be used. It is imperative that all air is eliminated from the closed loop side of the heat exchanger to prevent condenser fouling.

In the heating mode, heat is absorbed from the condenser water loop to the unit. A boiler can be utilized to maintain the loop within the proper temperature range. In milder climates a flooded tower concept is often used. This concept involves adding make-up water to the cooling tower sump to maintain the desired loop temperature. No unit should be connected to the supply or return piping until the water system has been completely cleaned and flushed to remove any dirt, piping chips or other foreign material. Supply and return hoses should be connected together during this process to ensure the entire system is properly flushed. After the cleaning and flushing has taken place, the unit may be connected to the water loop and should have all valves wide open.

Pressure/temperature ports are recommended in both the supply and return lines for systen flow balancing. Water flow can be accurately set by measuring the refrigerant-to-water heat exchangers water side pressure drop. WELL WATER SYSTEMS (Fig. 6) Water quantity should be plentiful, between 1.5 and 2.5 gpm per ton of cooling, and of good quality. To avoid the possibility of freezing the well water should be above 50 F.

Water pressure must always be maintained in the heat ex- changer by placing a water control valve on the outlet of the water-to-water unit. A bladder type expansion tank may be used to maintain pressure on the system.

Avoid using low voltage (24 volt) solenoids, using them may overload the unit transformer or interfere with the lock-out circuit. Line voltage solenoids connected across the load side (T1, T2) of the compressor contactor are preferred.

Pilot operated or slow closing valves are recommended to reduce water hammer.

The discharge water from the water-to-water unit is not con- taminated in any manner and can be disposed of in various ways depending on the local codes (i.e. discharge well, dry well, storm sewer, drain field, stream, pond, etc.) EARTH COUPLED GEOTHERMAL SYSTEMS (Fig. 7) Closed loop and pond applications require special- ized design knowledge. No attempt at these installations should be made unless the dealer has received specialized training.

Utilizing the Ground Loop Pumping Package (GLP), makes the installation easy. Anti-freeze solutions are utilized when en- tering loop temperatures drop below 40 F or where piping will be routed through areas subject to freezing. A flow rate be- tween 2.5 to 3.0 gpm per nominal ton of cooling is recom- mended for this application.

CAUTION

Galvanized pipe or fittings are not recommended for use with these units due to the possible galvanic corrosion.

CAUTION

Improper heat exchanger fluid flow due to piping, valving or improper pump operation is hazardous to the unit and constitutes abuse which will void the heat exchanger and compressor warranty.

IMPORTANT: Failure to comply with the above required water quality and quantity limitations and the closed- system application design requirements may cause damage to the tube-in-tube heat exchanger that is not the responsi- bility of the manufacturer.

9

Fig. 5 Typical Tower/Boiler Application (Source Side)

NOTE: Water and electrical connection locations vary depending on model. Connect as required per unit labels.

1 Ball Valves 2 Hose Kits 3 P/T Plugs 4 Load Side Connections* 5 Low Voltage Control Connection* 6 Vibration Pad 7 Line Voltage Disconnect 8 Supply and Return Lines of Central System

10

WATER OUT

WATER IN

2

3

8

Fig. 6 Typical Well Water Application (Source Side)

NOTE: Water and electrical connection locations vary depending on model. Connect as required per unit labels.

1 Pressure Tank 2 Ball Valves 3 Solenoid Valve (Slow Closing) 4 Hose Kit 5 P/T Kit 6 Load Side Connections* 7 Low Voltage Control Connection* 8 Vibration Pad 9 Line Voltage Disconnect

11

Fig. 7 Typical Earth Coupled Application (Source Side)

NOTE: Water and electrical connection locations vary depending on model. Connect as required per unit labels.

1 Polybutylene or Polyethelene with Insulation 2 Ground Loop Pumping Package (GLP) 3 Ground Loop Connection Kit 4 P/T Plugs 5 Load Side Connections* 6 Low Voltage Control Connection* 7 Vibration Pad 8 Line Voltage Disconnect

12

Table 3 Water Quality Guidelines

LEGEND

*Heat exchanger materials considered are copper, cupronickel, 304 SS (stainless steel), 316 SS, titanium.

Closed recirculating system is identified by a closed pressurized piping system.

**Recirculating open wells should observe the open recirculating design considerations.

If the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion problems exists. Sulfides in the water quickly oxidize when exposed to air, requir- ing that no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause system problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0. To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.

CONDITION HX MATERIAL*

CLOSED RECIRCULATING OPEN LOOP AND RECIRCULATING WELL**

Scaling Potential Primary Measurement Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.

pH/Calcium Hardness Method All N/A pH < 7.5 and Ca Hardness, <100 ppm

Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.) Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be implemented.

Ryznar Stability Index All N/A 6.0 - 7.5 If >7.5 minimize steel pipe use.

Langelier Saturation Index All N/A

0.5 to +0.5 If <0.5 minimize steel pipe use.

Based upon 150 F HWG and direct well, 85 F indirect well HX. Iron Fouling

Iron Fe2+ (Ferrous) (Bacterial Iron Potential) All N/A

<0.2 ppm (Ferrous) If Fe2+ (ferrous) >0.2 ppm with pH 6 - 8, O2<5 ppm check for

iron bacteria. Iron Fouling All N/A <0.5 ppm of Oxygen

Above this level deposition will occur. Corrosion Prevention

pH All 6 - 8.5 Monitor/treat as needed.

6 - 8.5 Minimize steel pipe below 7 and no open tanks with pH <8.

Hydrogen Sulfide (H2S)

All N/A

<0.5 ppm At H2S>0.2 ppm, avoid use of copper and cupronickel piping of HXs.

Rotten egg smell appears at 0.5 ppm level. Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.

Ammonia Ion as Hydrox- ide, Chloride, Nitrate and Sulfate Compounds

All N/A <0.5 ppm

Maximum Chloride Levels Maximum allowable at maximum water temperature. 50 F (10 C) 75 F (24 C) 100 F (38 C)

Copper N/A <20 ppm NR NR Cupronickel N/A <150 ppm NR NR

304 SS N/A <400 ppm <250 ppm <150 ppm 316 SS N/A <1000 ppm <550 ppm <375 ppm

Titanium N/A >1000 ppm >550 ppm >375 ppm Erosion and Clogging

Particulate Size and Erosion

All

<10 ppm of particles and a maximum velocity of

6 fps. Filtered for maximum

800 micron size.

<10 ppm (<1 ppm sandfree for reinjection) of particles and a maxi- mum velocity of 6 fps. Filtered for maximum 800 micron size. Any par- ticulate that is not removed can potentially clog components.

HWG Hot Water Generator HX Heat Exchanger

N/A Design Limits Not Applicable Consid- ering Recirculating Potable Water

NR Application Not Recommended SS Stainless Steel

13

Step 6 Wire Electrical Connections All field wiring must comply with local and national fire, safety and electrical codes. Power to the unit must be within the operating voltage range indicated on the units nameplate. On three phase units, phases must be balanced within 2%.

Properly sized fuse or HACR (heating, air-conditioning, and refrigeration) circuit breakers must be installed for branch circuit protection. See equipment rating plate for maximum size.

The unit is supplied with an opening for attaching conduit. Be certain to connect the ground lead to the ground lug in the control box. Connect the power leads as indicated on the unit wiring diagram. See Table 4 and Fig. 8-11.

Table 4 50PSW Electrical Data

LEGEND

WARNING

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation. Install lockout tag.

CAUTION

Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors. Failure to heed this warning could result in equipment damage.

50PSW UNIT SIZE

VOLTAGE (V-Ph-Hz)

COMPRESSOR MCA MAX FUSE

QTY RLA LRA

025 208/230-1-60 1 11.7 58.3 14.6 25

265-1-60 1 9.1 54.0 11.4 20 208/230-3-60 1 6.5 55.4 8.1 15

035

208/230-1-60 1 15.3 83.0 19.1 30 265-1-60 1 13.0 72.0 16.3 25

208/230-3-60 1 11.6 73.0 11.6 25 460-3-60 1 5.7 38.0 7.1 15

049 208/230-1-60 1 21.2 104.0 26.5 45 208/230-3-60 1 14.0 83.1 17.5 30

460-3-60 1 6.4 41.0 8.0 15

061 208/230-1-60 1 27.1 152.9 33.9 60 208/230-3-60 1 16.5 110.0 20.6 35

460-3-60 1 7.2 52.0 9.0 15

071 208/230-1-60 1 29.7 179.2 37.1 60 208/230-3-60 1 17.6 136.0 22.0 35

460-3-60 1 8.5 66.1 10.6 15

122 208/230-1-60 2 28.3 178.0 63.7 90 208/230-3-60 2 19.2 136.0 43.2 60

460-3-60 2 8.7 66.1 19.6 25

180 208/230-3-60 1 48.1 245.0 60.1 100

460-3-60 1 18.6 125.0 23.3 40 575-3-60 1 14.7 100.0 18.4 30

210 208/230-3-60 1 55.8 340.0 69.8 125

460-3-60 1 26.9 173.0 33.6 60 575-3-60 1 23.7 132.0 29.6 50

240 208/230-3-60 2 33.3 239.0 74.9 100

460-3-60 2 17.9 125.0 40.3 50 575-3-60 2 12.8 80.0 28.8 40

360 208/230-3-60 2 48.1 245.0 108.2 150

460-3-60 2 18.6 125.0 41.9 60 575-3-60 2 14.7 100.0 33.1 45

420 208/230-3-60 2 55.8 340.0 125.6 175

460-3-60 2 26.9 173.0 60.5 80 575-3-60 2 23.7 132.0 53.3 70

LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps

14

C O

M P

LE TE

C IN

C LU

D E

S B

U IL

T IN

: 2 70

-3 00

S E

C O

N D

R A

N D

O M

S TA

R T

30 0

S E

C O

N D

D E

LA Y

O N

B R

E A

K

12

0 S

E C

O N

D L

O W

P R

E S

S U

R E

B Y

PA S

S

D E

FA U

LT S

E TT

IN G

S F

O R

C O

M P

LE TE

C B

O A

R D

F R

O M

F A

C TO

R Y

S H

O W

N

F ig

. 8

U n

it S

iz es

0 25

-0 71

, S in

g le

-P h

as e

C o

m p

le te

C C

o n

tr o

l B o

ar d

15

C O

M P

LE TE

C IN

C LU

D E

S B

U IL

T IN

: 2 70

-3 00

S E

C O

N D

R A

N D

O M

S TA

R T

30 0

S E

C O

N D

D E

LA Y

O N

B R

E A

K

12

0 S

E C

O N

D L

O W

P R

E S

S U

R E

B Y

PA S

S

D E

FA U

LT S

E TT

IN G

S F

O R

C O

M P

LE TE

C B

O A

R D

F R

O M

F A

C TO

R Y

S H

O W

N

F ig

. 9

U n

it S

iz e

12 2,

S in

g le

-P h

as e

C o

m p

le te

C C

o n

tr o

l B o

ar d

16

C O

M P

LE TE

C IN

C LU

D E

S B

U IL

T IN

: 2 70

-3 00

S E

C O

N D

R A

N D

O M

S TA

R T

30 0

S E

C O

N D

D E

LA Y

O N

B R

E A

K

12

0 S

E C

O N

D L

O W

P R

E S

S U

R E

B Y

PA S

S

D E

FA U

LT S

E TT

IN G

S F

O R

C O

M P

LE TE

C B

O A

R D

F R

O M

F A

C TO

R Y

S H

O W

N

F ig

. 1 0

U

n it

S iz

es 0

25 -0

71 , 1

80 , a

n d

2 10

, 3 -P

h as

e C

o m

p le

te C

C o

n tr

o l B

o ar

d

17

C O

M P

LE TE

C IN

C LU

D E

S B

U IL

T IN

: 2 70

-3 00

S E

C O

N D

R A

N D

O M

S TA

R T

30 0

S E

C O

N D

D E

LA Y

O N

B R

E A

K

12

0 S

E C

O N

D L

O W

P R

E S

S U

R E

B Y

PA S

S

D E

FA U

LT S

E TT

IN G

S F

O R

C O

M P

LE TE

C B

O A

R D

F R

O M

F A

C TO

R Y

S H

O W

N .

F ig

. 1 1

U

n it

S iz

es 1

22 a

n d

2 40

-4 20

, 3 -P

h as

e C

o m

p le

te C

C o

n tr

o l B

o ar

d

18

PRE-START-UP

System Checkout When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure: 1. Voltage is within the utilization range specifications of the

unit compressor and fan motor, and voltage is balanced for 3-phase units.

2. Fuses, breakers and wire are correct size. 3. Low voltage wiring is complete. 4. Piping and system flushing is complete. 5. Air is purged from closed loop system. 6. System is balanced as required. Monitor if necessary. 7. Isolation valves are open. 8. Water control valves or loop pumps are wired. 9. Transformer switched to lower voltage tap if necessary.

10. Service/access panels are in place. 11. Control field-selected settings are correct.

FIELD SELECTABLE INPUTS Jumpers and DIP (dual in-line package) switches on the

control board are used to customize unit operation and can be configured in the field.

Safety Devices and the Complete C Control- ler Each unit is factory provided with a Complete C con- troller that controls the compressor operation and monitors the safety controls that protect the unit. See Fig. 12 for Complete C sequence of operation.

Safety controls include the following: For single compressor models (025-071, 180 and 210),

Fig. 8 and Fig. 10 - High-pressure switch inputs are wired across the HPC ter-

minals on the control board - Low-pressure switch inputs are wired across the LPC ter-

minals on the control board - The standard source side freeze thermistor is wired across

the FREEZE 1 terminals on the control board. Cutting the FREEZE 1 diode will change the freeze setting to 15 F for the source sensor.

- The standard load side freeze thermistor is wired across the FREEZE 2 terminals on the control board. Cutting the FREEZE 2 diode will change the freeze setting to 15 F for the load sensor.

For dual compressor models (122, 240-420), Fig. 9 and Fig. 11 - High-pressure switch inputs are wired across the HP1 and

HP2 terminals on the control board - Low-pressure switch inputs are wired across the LP1 and

LP2 terminals on the control board - The standard source side freeze thermister is wired across

the FREEZE 1 terminals on the control board. Cutting the JP 1 diode will change the freeze setting to 15 F for the source sensor.

- The standard load side freeze thermister is wired across the FREEZE 2 terminals on the control board. Cutting the JP 2 diode will change the freeze setting to 15 F for the load sensor.

Optional freeze protection sensor, mounted close to con- densing water coil, monitors refrigerant temperature between condensing water coil and thermal expansion valve. If temperature drops below or remains at freeze limit trip for 30 seconds, the controller will shut down the compressor and enter into a soft lockout condition. The default freeze limit trip is 30 F, however this can be changed to 15 F by cutting the R-42 resistor located on top of DIP switch SW1.

The optional condensate overflow protection sensor is located in the drain pan of the unit and connected to the COND terminal on the Complete C board.

NOTE: If freeze protection sensor is not installed, a jumper between freeze contacts must be installed on the Complete C board otherwise unit will not start.

The Complete C controller includes the following features: ANTI-SHORT CYCLE TIMER A 5-minute delay on break timer prevents compressor short cycling. RANDOM START Each controller has a unique random start delay ranging from 270 to 300 seconds to reduce the chances of multiple units simultaneously starting after initial power up or after a power interruption, creating a large electri- cal spike. LOW PRESSURE BYPASS TIMER If the compressor is running and the low-pressure switch opens, then the control will keep the compressor on for 120 seconds. After 2 minutes if the low-pressure switch remains open, the control will shut down the compressor and enter a soft lockout. The compressor will not be energized until the low-pressure switch closes and the anti-short cycle time delay expires. If the low-pressure switch opens 2 to 4 times in 1 hour, the unit will enter a hard lockout and need to be reset. BROWNOUT/SURGE/POWER INTERRUPTION PRO- TECTION The brownout protection in the Complete C board will shut down the compressor if the incoming power falls below 18 VAC. The compressor will remain off till the voltage goes above 18 VAC and the anti-short cycle timer (300 seconds) times out. The unit will not go into a hard lockout. MALFUNCTION OUTPUT Alarm output is Normally Open (NO) dry contact. If 24 VAC output is needed R must be wired to the ALR-COM terminal; 24 VAC will be available on the ALR-OUT terminal when the unit is in alarm condition. If pulse is selected the alarm output will be pulsed. The fault out- put will depend on the dip switch setting for ALARM. If it set to CONST, a constant signal will be produced to indicate a fault has occurred and the unit requires inspection to deter- mine the type of fault. If it is set to PULSE, a pulse signal is produced and a fault code is detected by a remote device indi- cating the fault. See LED Fault Indication below for blink code explanations. The remote device must have a malfunction de- tection capability when the Complete C board is set to PULSE. TEST DIP SWITCH A test DIP switch is provided to re- duce all time delay settings to 10 seconds during troubleshoot- ing or verification of unit operation. Note that operation of the unit while in test mode can lead to accelerated wear and prema- ture failure of the unit. The TEST switch must be set back to NO for normal operation. FREEZE SENSOR The freeze sensor input is active all the time, if a freeze option is not selected the freeze terminals will need a jumper. There are 2 configurable freeze points, 30 F and 15 F. The unit will enter a soft lockout until the temperature climbs above the set point and the anti-short cycle time delay has expired. The freeze sensor will shut the compressor output down after 90 seconds of water flow loss and report a freeze condition. It is recommended to have a flow switch to prevent the unit from running if water flow is lost. See Fig. 13.

IMPORTANT: Jumpers and DIP switches should only be clipped when power to control board has been turned off.

19

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES YES

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

Y1=1

V > 18VAC

HPC = 1

LPC = 1

FRZ > TEMP LIM

CON > 0

INITIAL POWER UP T > ASC OR

RS SEC

TIME > 30 SEC

TIME > 120 SEC

COUNT = 2

Start Timer

Start Timer

CC Output = On

CC Output = Off

Blink Code On Status LED Report Alarm Fault

Hard Lockout ALR Output = On/Pulse

Blink Code On Status LED Soft Lockout

Record Alarm Start Counter (If Applicable)

Start Anti Short Cycle

Start Random Start Up

Lockout Can Be Set To 4 Via Dip Switch

Power/Switchs/Sensor Status Check

Fig. 12 Complete C Controller Sequence of Operation

20

NOTE: If unit is employing a fresh water system (no anti- freeze protection), it is extremely important to have the Freeze jumper R-42 resistor set to 30 F in order to shut down the unit at the appropriate leaving water temperature and pro- tect the heat pump from freezing if a freeze sensor is included.

LED FAULT INDICATION Two LED indicators are pro- vided: Green: Power LED indicates 18 to 30 VAC present at the board. Red: Fault indicator with blink codes as follows: One blinkHigh pressure lockout Two blinksLow pressure lockout Three blinksFreeze sensor lockout Four blinksCondensate overflow Five blinksBrownout INTELLIGENT RESET If a fault condition is initiated, the 5-minute delay on break time period is initiated and the unit will restart after these delays expire. During this period the fault LED will indicate the cause of the fault. If the fault condi- tion still exists or occurs 2 or 4 times (depending on 2 or 4 set- ting for Lockout DIP switch) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout reset. A

single condensate overflow fault will cause the unit to go into a hard lockout immediately, and will require a manual lockout reset. LOCKOUT RESET A hard lockout can be reset by turning the unit thermostat off and then back on when the RESET DIP switch is set to Y or by shutting off unit power at the cir- cuit breaker when the RESET DIP switch is set to R. NOTE: The blower motor will remain active during a lockout condition. COMPLETE C BOARD DEFAULT SETTINGS The Complete C board will come from the factory with the follow- ing default settings:

FreezeTerminals not jumped on all the time Temp30F Lockout2 ResetY AlarmPULSE TestNO Dry ContactNormally Open (NO)

CONSIDERATIONS 1. Always check incoming line voltage power supply and

secondary control voltage for adequacy. Transformer pri- maries are dual tapped for 208 and 230 volts. Connect the appropriate tap to ensure a minimum of 18 volts second- ary control voltage. 24 volts is ideal for best operation.

2. Long length thermostat and control wiring leads may cre- ate voltage drop. Increase wire gage or up-size transform- ers may be required to ensure minimum secondary volt- age supply.

3. Carrier recommends the following guidelines for wiring between a thermostat and the unit: 18 GA up to 60 ft, 16 GA up to 100 ft and 14 GA up to 140 ft.

4. Do not apply additional control devices to the control cir- cuit power supply without consulting the factory. Doing so may void equipment warranties.

5. Check with all code authorities on requirements involv- ing condensate disposal/over flow protection criteria.

Table 5 Cooling Mode Operating Pressure (psig)

Table 6 Heating Mode Operating Pressure (psig)

Freeze Protection Sensor

Fig. 13 Freeze Protection Sensor

ENTERING LOAD/EVAP TEMP (F)

ENTERING SOURCE CONDENSER TEMPERATURE (F) 75 F 85 F 95 F

Suction Pressure

Discharge Pressure

Suction Pressure

Discharge Pressure

Suction Pressure

Discharge Pressure

65 99-116 290-320 107-123 325-358 107-123 370-400 55 91-107 265-311 91-107 303-350 99-116 370-400 45 76- 91 265-311 76- 91 295-345 83- 99 358-390

ENTERING LOAD TEMP (F)

ENTERING SOURCE CONDENSER TEMPERATURE (F) 40 F 60 F 80 F

Suction Pressure

Discharge Pressure

Suction Pressure

Discharge Pressure

Suction Pressure

Discharge Pressure

70 68-83 255-290 99-116 270-305 130-145 290-325 90 76-91 350-380 99-116 358-390 130-165 370-400

110 76-91 455-480 99-116 470-500 139-165 480-575

21

START-UP Use the procedure outlined below to initiate proper unit

start-up. NOTE: This equipment is designed for indoor installation only.

Operating Limits (See Table 7) ENVIRONMENT This equipment is designed for indoor installation ONLY. Extreme variations in temperature, humidi- ty and corrosive water or air will adversely affect the unit per- formance, reliability and service life. POWER SUPPLY A voltage variation of 10% of name- plate utilization voltage is acceptable. NOTE: These operating conditions are not normal or continu- ous operating conditions. It is assumed that start-up is for the purpose of bringing the building space up to occupancy temperature.

Table 7 50PSW Unit Operating Limits

Unit Start-Up 1. Set the primary controller to the highest setting. 2. Set the primary controller system switch to COOL. The

reversing valve solenoid should energize. The compres- sor should not run.

3. Reduce the primary controller setting approximately 5 degrees below return fluid temperature.

4. Verify the heat pump is operating in the cooling mode. 5. Check the cooling refrigerant pressures against the values

listed in Table 5. 6. Turn the primary controller system switch to the OFF

position. The unit should stop running and the reversing valve should de-energize.

7. Leave the unit off for approximately (5) minutes to allow for system equalization.

8. Turn the primary controller to the lowest setting. 9. Set the primary controller switch to HEAT.

10. Increase the primary controller setting approximately 5 degrees above the return fluid temperature.

11. Verify the heat pump is operating in the heating mode. 12. Check the heating refrigerant pressures against the values

listed in Table 6. 13. Set the primary controller to maintain the desired return

fluid temperature. 14. Check for vibrations, leaks, etc. 15. Instruct the owner on the unit and control operation.

Scroll Compressor Rotation It is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction: 1. Connect service gages to suction and discharge pressure

fittings. 2. Energize the compressor. 3. The suction pressure should drop and the discharge

pressure should rise, as is normal on any start-up. If the suction pressure does not drop and the discharge

pressure does not rise to normal levels: 1. Turn off power to the unit. Install disconnect tag. 2. Reverse any two of the unit power leads. 3. Reapply power to the unit and verify pressures are cor-

rect. The suction and discharge pressure levels should now move to their normal start-up levels.

After a few minutes of reverse operation, the scroll com- pressor internal overload protection will open, thus activating the unit lockout. This requires a manual reset. To reset, turn the thermostat on and then off. NOTE: There is a 5-minute time delay before the compressor will start.

Cleaning and Flushing Cleaning and flushing of the piping system is the single most important step to ensure proper start-up and continued efficient operation of the system.

Follow the instructions below to properly clean and flush the system: 1. Verify electrical power to the unit is disconnected and

lockout tag installed. 2. Install the system with the supply hose connected directly

to the return riser valve. Use a single length of flexible hose.

3. Open all air vents. Fill the system with the water. DO NOT allow system to overflow. Bleed all air from the system. Pressurize and check the system for leaks and re- pair appropriately.

4. Verify all strainers are in place. Start the pumps, and sys- tematically check each vent to ensure all air is bled from the system.

5. Verify make-up water is available. Adjust make-up water appropriately to replace the air which was bled from the system. Check and adjust the water/air level in the expan- sion tank.

6. Raise the loop temperature to approximately 85F. Open the drain at the lowest point in the system. Adjust the make-up water replacement rate to equal the rate of bleed.

7. Refill the system and add trisodium phosphate in a pro- portion of approximately one pound per 150 gal. of water (or other equivalent approved cleaning agent).

WARNING

When the disconnect switch is closed, high voltage is pres- ent in some areas of the electrical panel. Exercise caution when working with the energized equipment.

WATER LIMITS COOLING (F)

HEATING (F)

SOURCE COIL Min Entering Water 50 20 Normal Entering Water 85 60 Max Entering Water 110 70

LOAD COIL Min Entering Water 50 60 Normal Entering Water 60 100 Max Entering Water 90 120

CAUTION

When the compressor is rotating in the wrong direction, the unit makes an elevated level of noise and does not provide cooling. Damage to compressor will occur if allowed to operate in this manner.

WARNING

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position before flushing system. Install lockout tag.

22

Raise the loop temperature to 100F. Circulate the solu- tion for a minimum of 8 to 24 hours. At the end of this period, shut off the circulating pump and drain the solu- tion. Repeat system cleaning if desired.

8. When the cleaning process is complete, remove the short- circuited hose. Reconnect the hoses to the proper supply, and return the connections to each of the units. Refill the system and bleed off all air.

9. Test the system pH with litmus paper. The system water should be slightly alkaline (pH of 7.5 to 8.5). Add chemi- cals, as appropriate, to maintain acidity levels.

10. When the system is successfully cleaned, flushed, refilled and bled, restore power.

11. Check the main system panels, safety cutouts and alarms. Set the controls to properly maintain loop temperatures.

Antifreeze In areas where entering loop temperatures drop below 40 F or where piping will be routed through areas subject to freezing, antifreeze is needed.

Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 15 F below the lowest expected entering loop temperature. For example, if the lowest expected entering loop temperature is 30 F, the leav- ing loop temperature would be 22 to 25 F. Therefore, the freeze protection should be at 15 F (30 F 15 F = 15 F).

Calculate the total volume of fluid in the piping system. See Table 8. Use the percentage by volume in Table 9 to determine the amount of antifreeze to use. Antifreeze concentration should be checked from a well mixed sample using a hydrome- ter to measure specific gravity. FREEZE PROTECTION SELECTION The freeze sensor input is active all the time, if a freeze option is not selected the freeze terminals will need a jumper. There are 2 configurable freeze points, 30 F and 15 F. The unit will enter a soft lockout until the temperature climbs above the set point and the anti- short cycle time delay has expired. The freeze sensor will shut the compressor output down after 90 seconds of water flow loss and report a freeze condition. It is recommended to have a flow switch to prevent the unit from running if water flow is lost.

Table 8 Approximate Fluid Volume (gal.) per 100 Ft of Pipe

LEGEND

NOTE: Volume of heat exchanger is approximately 1.0 gallon.

Table 9 Antifreeze Percentages by Volume

Cooling Tower/Boiler Systems These systems typically use a common loop maintained at 60 to 90 F. The use of a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop is recom- mended. If an open type cooling tower is used continuously, chemical treatment and filtering will be necessary.

Ground Coupled, Closed Loop and Plateframe Heat Exchanger Well Systems These systems al- low water temperatures from 30 to 110 F. The external loop field is divided up into 2 in. polyethylene supply and return lines. Each line has valves connected in such a way that upon system start-up, each line can be isolated for flushing using only the system pumps. Air separation should be located in the piping system prior to the fluid re-entering the loop field.

OPERATION

Power Up Mode The unit will not operate until all the inputs, terminals and safety controls are checked for normal operation. NOTE: The compressor will have a 5-minute anti-short cycle upon power up.

Units with Aquazone Complete C Con- trol The controller will memorize the last mode used be- fore power is removed and will run in that mode after it is turned on. In all modes the control will display temperature de- gree differential setting for 5 seconds once it is powered and this setting may be adjusted during this time. Thereafter the display will switch to the monitored water temperature. When switching from one mode to another the set point (the decimal point is used to distinguish it from water temperature) for the new mode is displayed for 5 seconds and then monitored water temperature. During this time the set point may be adjusted.

Off Mode In the OFF mode all outputs are disabled and mode indication LEDs will be off.

The control will first display temperature differential setting with the ability for the user to adjust it and then will display OFF and finally water temperature.

CAUTION

To avoid possible damage to a plastic (PVC) piping sys- tem, do not allow temperatures to exceed 110 F.

CAUTION

DO NOT use Stop Leak or any similar chemical agent in this system. Addition of these chemicals to the loop water will foul the system and inhibit unit operation.

IMPORTANT: All alcohols should be pre-mixed and pumped from a reservoir outside of the building or introduced under water level to prevent alcohols from fuming.

PIPE DIAMETER (in.) VOLUME (gal.) Copper 1 4.1

1.25 6.4 1.5 9.2

Rubber Hose 1 3.9 Polyethylene 3/4 IPS SDR11 2.8

1 IPS SDR11 4.5 11/4 IPS SDR11 8.0 1/2 IPS SDR11 10.9 2 IPS SDR11 18.0 11/4 IPS SCH40 8.3 11/2 IPS SCH40 10.9 2 IPS SCH40 17.0

IPS Internal Pipe Size SCH Schedule SDR Standard Dimensional Ratio

ANTIFREEZE MINIMUM TEMPERATURE FOR

FREEZE PROTECTION (F) 10 15 20 25

Methanol (%) 25 21 16 10 100% USP Food Grade Propylene Glycol (%) 38 30 22 15

23

Heating Mode When the unit is operated in the heating mode and the controlled water temperature is below the set point minus the differential setting, terminal Y1 will close and the unit will operate (first stage compressor in a two stage unit). When the set point is satisfied the compressor is turned off.

In a two-stage unit after the first stage activation if the water temperature drops an additional 2 degrees below the set point, the second stage (terminal Y2) will be activated (if control is configured for both compressors). Both stages will be on until the set point is satisfied.

When the unit runs after power is applied or the mode is changed from cooling to heating, if the fluid temperature is be- low set point and does not change for 3 minutes, the second stage of heating will be activated. This only applies for a two- stage machine.

There will be 5 minutes delay on break after the unit cycles off on temperature, a power interruption or because of a fault condition. See Table 10.

At any point in time the control will ignore a low pressure switch condition for 120 seconds before turning off the com- pressor.

Table 10 Fault Codes

Cooling Mode When the unit is operated in the cool- ing mode and the leaving water temperature is above the tem- perature set point plus the differential setting, terminals Y1 will close (first-stage compressor of a two-stage unit) and the unit will operate in the cooling mode. When the set point is satisfied the compressor is turned off. The reversing valve is always ac- tivated when the unit is in the cooling mode.

On two-stage units, after first stage activation if water tem- perature increases 2 degrees above the set point, the second stage (terminal Y2) will be activated (if control is configured for both compressors). Both stages will remain on until the set point is satisfied.

When the unit runs after power is applied or the mode is changed from heating to cooling, if the fluid temperature is above cooling point and does not change for 3 minutes, the sec- ond stage will be activated. This only applies for a two-stage machine.

There will be 5 minutes delay on break after the unit cycles off on temperature, a power interruption or because of a fault condition.

Retry Mode In Retry mode, the staus LED will flash the code for the corresponding fault. If the fault clears and the

thermostat call (Y) is still present the Complete C or Deluxe D control will run the compressor once the ASC (anti-short cycle) timer has expired and will try to satisfy the call. If the call is satisfied, the unit will resume its normal operation.

If 2 or 4 consecutive faults occur (depending on the DIP switch setting) within 1 hour, the controller will lock the com- pressor operation out and will flash the alarm code on the status LED as well as alarm dry contact output. When the Complete C or Deluxe D control enters lockout mode, the alarm will also be shown on the panel mounted LED.

SERVICE Perform the procedures outlined below periodically, as

indicated.

Water Coil Keep all air out of the water coil. Check open loop systems to be sure the well head is not allowing air to infiltrate the water line. Always keep lines airtight.

Inspect heat exchangers regularly, and clean more frequent- ly if the unit is located in a dirty environment. The heat exchanger should be kept full of water at all times. Open loop systems should have an inverted P trap placed in the discharge line to keep water in the heat exchanger during off cycles. Closed loop systems must have a minimum of 15 psig during the summer and 40 psig during the winter.

Check P trap frequently for proper operation.

Refrigerant System Verify air and water flow rates are at proper levels before servicing. To maintain sealed circuit- ry integrity, do not install service gages unless unit operation appears abnormal.

BLINK CODE

SINGLE COMPRESSOR

SIZES 025-071, 180, AND 210

DUAL COMPRESSOR

SIZES 122, 240-420

One Blink High Pressure High Pressure 1 Two Blinks Low Pressure Low Pressure 1 Three Blinks Source Side Freeze High Pressure 2 Four Blinks Not Used on PSW Low Pressure 2 Five Blinks Brown Out Freeze (Load or

Source) Six Blinks Load Side Freeze Not Used on

These Sizes Seven Blinks Not Used on

These Sizes Brown Out

IMPORTANT: When a compressor is removed from this unit, system refrigerant circuit oil will remain in the com- pressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed.

IMPORTANT: To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must only be serviced by technicians which meet local, state and federal proficiency requirements.

IMPORTANT: All refrigerant discharged from this unit must be recovered without exception. Technicians must fol- low industry accepted guidelines and all local, state and fed- eral statutes for the recovery and disposal of refrigerants.

WARNING

To prevent injury or death due to electrical shock or contact with moving parts, open unit disconnect switch before ser- vicing unit.

CAUTION

To avoid fouled machinery and extensive unit clean-up, DO NOT operate units without filters in place. DO NOT use equipment as a temporary heat source during construction.

24

Condenser Cleaning Water-cooled condensers may require cleaning of scale (water deposits) due to improperly maintained closed-loop water systems. Sludge build-up may need to be cleaned in an open water tower system due to induced contaminants.

Local water conditions may cause excessive fouling or pitting of tubes. Condenser tubes should therefore be cleaned at least once a year, or more often if the water is contaminated.

Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment analysis is recommended. Refer to the Carrier System Design Manual, Part 5, for general water conditioning information.

Clean condensers with an inhibited hydrochloric acid solu- tion. The acid can stain hands and clothing, damage concrete, and, without inhibitor, damage steel. Cover surroundings to guard against splashing. Vapors from vent pipe are not harmful, but take care to prevent liquid from being carried over by the gases.

Warm solution acts faster, but cold solution is just as effec- tive if applied for a longer period.

GRAVITY FLOW METHOD Do not add solution faster than vent can exhaust the generated gases.

When condenser is full, allow solution to remain overnight, then drain condenser and flush with clean water. Follow acid manufacturers instructions. See Fig. 14.

FORCED CIRCULATION METHOD Fully open vent pipe when filling condenser. The vent may be closed when condenser is full and pump is operating. See Fig. 15.

Regulate flow to condenser with a supply line valve. If pump is a nonoverloading type, the valve may be fully closed while pump is running.

For average scale deposit, allow solution to remain in con- denser overnight. For heavy scale deposit, allow 24 hours. Drain condenser and flush with clean water. Follow acid manu- facturers instructions.

Checking System Charge Units are shipped with full operating charge. If recharging is necessary: 1. Insert thermometer bulb in insulating rubber sleeve on

liquid line near filter drier. Use a digital thermometer for all temperature measurements. DO NOT use a mercury or dial-type thermometer.

2. Connect pressure gage to discharge line near compressor. 3. After unit conditions have stabilized, read head pressure

on discharge line gage. NOTE: Operate unit a minimum of 15 minutes before checking charge. From standard field-supplied Pressure- Temperature chart for R-410A, find equivalent saturated condensing temperature.

4. Read liquid line temperature on thermometer; then subtract from saturated condensing temperature. The dif- ference equals subcooling temperature.

Refrigerant Charging

NOTE: Do not vent or depressurize unit refrigerant to atmo- sphere. Remove and recover refrigerant following accepted practices.

TROUBLESHOOTING When troubleshooting problems with a WSHP, refer to

Table 11.

CAUTION

Follow all safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution. Observe and follow acid manufacturers instructions.

Fig. 14 Gravity Flow Method

FILL CONDENSER WITH CLEANING SOLUTION. DO NOT ADD SOLUTION MORE RAPIDLY THAN VENT CAN EXHAUST GASES CAUSED BY CHEMICAL ACTION.

PAIL

FUNNEL

CONDENSER

PAIL

3 TO 4

VENT PIPE 5 APPROX

1 PIPE

WARNING

To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system this can cause compressor flooding.

SUCTION

PUMP SUPPORT

TANK

FINE MESH SCREEN

RETURN

GAS VENTPUMP PRIMING CONN.

GLOBE VALVES

SUPPLY

1 PIPE

CONDENSER

REMOVE WATER REGULATING VALVE

Fig. 15 Forced Circulation Method

25

Table 11 Troubleshooting

FAULT POSSIBLE CAUSE SOLUTION

COMPRESSOR DOES NOT OPERATE

Power supply off Apply power, close disconnect. Blown fuse Replace fuse or reset circuit breaker. Check for correct fuses. Broken or loose wires Replace or tighten the wires. Check for loose or broken wires at compressor, capacitor, or contactor. Voltage supply low If voltage is below minimum voltage specified on unit data plate, contact local power company. Controller Set controller to COOL and lowest temperature setting, the unit should run in the cooling mode

(reversing valve energized). Set unit to HEAT and the highest temperature setting, the unit should run in the heating mode. If the compressor does not run in all cases, the controller could be miswired or faulty.To ensure miswired or faulty thermostat verify 24 volts is available on the unit section low voltage terminal strip between R and C, Y and C, and O and C. Replace the controller if defective.

Safety controls Reset the controller to OFF. After a few minutes turn to COOL or HEAT. If the compressor runs, unit was off on one of the safety controls. (See problem for possible causes)

Compressor overload open If the compressor is cool and the overload will not reset, replace compressor. Compressor motor grounded Internal winding grounded to the compressor shell. Replace compressor. If compressor burnout, install

suction filter drier. Compressor windings open After compressor has cooled, check continuity of the compressor windings. If the windings

are open, replace the compressor.

UNIT OFF ON HIGH-PRESSURE SWITCH

Discharge pressure too high In COOLING mode: SOURCE COIL - Lack of or inadequate water flow. Entering water temperature too warm. Scaled or plugged condenser. In HEATING mode: LOAD COIL - Lack of or inadequate water flow. Entering water temperature too warm. Scaled or plugged load coil.

Refrigerant charge The unit is overcharged with refrigerant. Recover refrigerant, evacuate and recharge with factory recommended charge.

High-pressure switch Check for defective or improperly calibrated high-pressure switch.

UNIT OFF ON LOW-PRESSURE SWITCH

Suction pressure too low In COOLING mode: LOAD COIL - Lack of or inadequate fluid flow. Entering water temperature too cold. Scaled or plugged load coil. In HEATING mode: SOURCE COIL - Lack of or inadequate fluid flow. Entering water temperature too cold. Scaled or plugged source coil.

Refrigerant charge The unit is low on refrigerant. Check for refrigerant leak, repair, evacuate and recharge with factory recommended charge.

Low-pressure switch Check for defective or improperly calibrated low-pressure switch.

UNIT SHORT CYCLES

Unit oversized Recalculate heating and or cooling loads. Wiring and controls Loose connections in the wiring or a defective compressor contactor. Fluid Volume Inadequate load side fluid volume.

INSUFFICIENT COOLING OR HEATING

Unit undersized Recalculate heating and or cooling loads. If excessive, possibly adding insulation and shading will rec- tify the problem. Unit may be short of refrigerant.

Refrigerant charge Unit may be short on refrigerant charge. Compressor Check for defective compressor. If discharge is too low and suction pressure is too high, compressor is

not pumping properly. Replace compressor. Reversing valve Defective reversing valve creating bypass of refrigerant from discharge to suction side of compressor.

Replace reversing valve. Operating pressures Compare unit operating pressures to the pressure / temperature chart for the unit. TXV Check TXV (thermostatic expansion valve) for possible restriction or defect. Replace if necessary. Moisture, noncondensables The refrigerant system may be contaminated with moisture or noncondensables. Recover refrigerant,

evacuate and recharge with factory recommended charge. Note: a liquid line drier may be required.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500103-01 Printed in U.S.A. Form 50PSW-3SI Pg 26 419 8-14 Replaces: NEW

Carrier Corporation 2014 8-733-954-209

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500103-01 Printed in U.S.A. Form 50PSW-3SI CL-1 419 8-14 Replaces: NEW

50PSW START-UP CHECKLIST

CUSTOMER:___________________________ JOB NAME:

MODEL NO.:___________________________ SERIAL NO.: _____________ DATE:

LOOP TYPE: ___________________________ ANTIFREEZE TYPE AND %:______________________

I. PRE-START-UP

DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE? (Y/N)

HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS TIGHT? (Y/N)

HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER? (Y/N)

HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN? (Y/N)

HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED? (Y/N)

IS AN AIR FILTER INSTALLED? (Y/N)

II. START-UP

IS FAN OPERATING WHEN COMPRESSOR OPERATES? (Y/N)

IF 3-PHASE SCROLL COMPRESSOR IS PRESENT, VERIFY PROPER ROTATION PER INSTRUCTIONS. (Y/N)

UNIT VOLTAGE COOLING OPERATION

PHASE AB VOLTS PHASE BC VOLTS PHASE CA VOLTS (if 3 phase) (if 3 phase)

PHASE AB AMPS PHASE BC AMPS PHASE CA AMPS (if 3 phase) (if 3 phase)

CONTROL VOLTAGE

IS CONTROL VOLTAGE ABOVE 21.6 VOLTS? (Y/N) . IF NOT, CHECK FOR PROPER TRANSFORMER CONNECTION.

TEMPERATURES

FILL IN THE ANALYSIS CHART ATTACHED.

COAXIAL HEAT EXCHANGER

COOLING CYCLE: FLUID IN F FLUID OUT F PSI FLOW

HEATING CYCLE: FLUID IN F FLUID OUT F PSI FLOW

AIR COIL COOLING CYCLE: AIR IN F AIR OUT F

HEATING CYCLE: AIR IN F AIR OUT F

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500103-01 Printed in U.S.A. Form 50PSW-3SI CL-2 419 8-14 Replaces: NEW

Carrier Corporation 2014

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- -

- --

- -

- -

- -

- -

- -

- -

- -

- -

- -

-

C U

T A

LO N

G D

O T

T E

D L

IN E

C U

T A

LO N

G D

O T

T E

D L

IN E

8-733-954-209

HEATING AND COOLING CYCLE ANALYSIS

HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =

FLOW RATE (GPM) x TEMP. DIFF. (DEG. F) x FLUID FACTOR* = (Btu/hr)

SUPERHEAT = SUCTION TEMPERATURE SUCTION SATURATION TEMPERATURE = (DEG F)

SUBCOOLING = DISCHARGE SATURATION TEMPERATURE LIQUID LINE TEMPERATURE = (DEG F)

*Use 500 for water, 485 for antifreeze.

DESCRIPTION HEATING COOLING NOTES Voltage Compressor Amp

1 Suction Temperature 2 Suction Pressure

2a Saturation Temperature 2b Superheat 3 Discharge Temperature 4 Discharge Pressure

4a Saturation Temperature 4b Subcooling 5 Liquid Line Temperature 6 Source Water In Temperature 7 Source Water Out Temperature Temperature Difference 8 Source Water In Pressure 9 Source Water Out Pressure

9a Pressure Drop 9b Flow Rate (gpm) 10 Load Water In Temperature 11 Load Water Out Temperature Temperature Difference 12 Load Water In Pressure 13 Load Water Out Pressure

13a Pressure Drop 13b Flow Rate (gpm)

COMPRESSOR

DISCHARGE

SUCTION

HWG*

EXPANSION VALVE FILTER

DRIER

REVERSING VALVE

HEATING POSITION COOLING POSITION

1

COAX

C O

AX

5

1210

1311

9

7

8

6

4

3

2

FP2: HEATING LIQUID LINE

5 FP1: COOLING LIQUID LINE

CONDENSER (HTG) EVAPORATOR (CLG)

CONDENSER (COOLING) EVAPORATOR (HEATING)

WATER-TO-WATER UNITS REFRIG FLOW - HEATING REFRIG FLOW - COOLING

Source

Load

LEGEND

*Turn off HWG (hot water generator) before troubleshooting.

CLG Cooling HTG Heating

a5

Manualsnet FAQs

If you want to find out how the Aquazone 50PSW Carrier works, you can view and download the Carrier Aquazone 50PSW Installation Instructions on the Manualsnet website.

Yes, we have the Installation Instructions for Carrier Aquazone 50PSW as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Installation Instructions should include all the details that are needed to use a Carrier Aquazone 50PSW. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier Aquazone 50PSW Installation Instructions is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier Aquazone 50PSW Installation Instructions consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier Aquazone 50PSW Installation Instructions free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier Aquazone 50PSW Installation Instructions, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier Aquazone 50PSW Installation Instructions as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.