- Manuals
- Brands
- Carrier
- Heat Pump
- Aquazone 50PSW
- Installation Guide
Carrier Aquazone 50PSW Installation Guide PDF
Summary of Content for Carrier Aquazone 50PSW Installation Guide PDF
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide i All rights reserved
Source Water Loop Control for UC Open XP
Installation and Start-up Guide
CARRIER CORPORATION 2021 Catalog No. 11-808-541-01 6/16/2021
Verify that you have the most current version of this document from www.hvacpartners.com or
www.accounts.ivusystems.com or your local Carrier office.
Important changes are listed in Document revision history at the end of this document.
CARRIER CORPORATION 2021. All rights reserved throughout the world. i-Vu is a registered trademark of Carrier
Corporation. All other trademarks are the property of their respective owners.
Contents Source Water Loop Control for UC Open XP overview and specifications .............................................................. 1
What is the Loop Control application? .............................................................................................................. 1 UC Open XP specifications .................................................................................................................................. 1 Safety considerations........................................................................................................................................... 3
Installing the UC Open XP ........................................................................................................................................... 4 Mounting the UC Open XP ................................................................................................................................... 4 Wiring the UC Open XP for power....................................................................................................................... 4
To wire for power ................................................................................................................................... 5 Addressing the UC Open XP ................................................................................................................................ 5 Wiring for communications ................................................................................................................................. 6
Wiring specifications for BACnet MS/TP and ARC156 ........................................................................ 6 To wire the controller to the network ................................................................................................... 6
Wiring inputs and outputs ................................................................................................................................... 7 Inputs and outputs table ...................................................................................................................... 7 Input wiring specifications .................................................................................................................... 8 Inputs ..................................................................................................................................................... 9 Binary outputs ....................................................................................................................................... 9 Analog outputs .................................................................................................................................... 10 To wire inputs and outputs on the UC Open XP ................................................................................. 11
Installing the UC Open XP IO expander .................................................................................................................... 14 To mount and attach the UC Open XP IO ....................................................................................................... 14 To wire for power ............................................................................................................................................... 15 Wiring inputs and outputs ................................................................................................................................ 15
Input wiring specifications .................................................................................................................. 16 Inputs on the UC Open XP IO .............................................................................................................. 16 Binary outputs ..................................................................................................................................... 16 To wire inputs and outputs on UC Open XP IO ................................................................................... 17
Wiring an Equipment Touch to the UC Open XP's Rnet port ....................................................................... 18 Wiring Specifications ........................................................................................................................... 18 To wire an Equipment Touch to the UC Open XP ............................................................................... 19
Start-up ....................................................................................................................................................................... 21 Select the Loop Control control program and graphic ................................................................................. 21 Configure the points and properties ............................................................................................................... 21
Sequence of Operation ............................................................................................................................................. 23 Scheduling without Condenser Water Linkage ............................................................................................. 23 Scheduling with Condenser Water Linkage................................................................................................... 24 Constant flow pump control ............................................................................................................................. 24 Loop pump(s) constant flow ............................................................................................................................ 25 Loop Pump(s) with bypass valve differential pressure control ................................................................... 25 Loop Pump(s) with VFD loop differential pressure control ......................................................................... 26 Two loop pumps with VFDs, lead/lag operation for loop differential pressure control .......................... 27 Pump rotation .................................................................................................................................................... 27 Tower fan control ............................................................................................................................................... 28 Analog (2-stage modulating) tower fan control ............................................................................................ 28 Staged tower fan control .................................................................................................................................. 29 Boiler control ...................................................................................................................................................... 29 Analog (2-stage modulating) boiler/valve control ........................................................................................ 30 Staged boiler control ......................................................................................................................................... 30 Condenser Water Linkage ................................................................................................................................ 31 Loop optimization .............................................................................................................................................. 31 WSHP compressor enable command output ................................................................................................ 32
Contents
Alarm lamp output ............................................................................................................................................ 32
Troubleshooting ......................................................................................................................................................... 33 UC Open XP LED's .............................................................................................................................................. 33 Expander LED's .................................................................................................................................................. 34 To get the serial number .................................................................................................................................. 35 To restore defaults ............................................................................................................................................. 35 To replace the UC Open XP's battery .............................................................................................................. 36
Compliance ................................................................................................................................................................ 37 FCC Compliance ................................................................................................................................................. 37 CE Compliance ................................................................................................................................................... 37 BACnet Compliance........................................................................................................................................... 37
Appendix A: UC Open XP and UC Open XP IO wire lists ......................................................................................... 38 UC Open XP wire list .......................................................................................................................................... 38 UC Open XP IO wire list ..................................................................................................................................... 40
Appendix B: Loop Control Points/Properties .......................................................................................................... 42 Status................................................................................................................................................................... 42 Unit Configuration .............................................................................................................................................. 43 Setpoints ............................................................................................................................................................. 45 Alarm Configuration .......................................................................................................................................... 46 Service Configuration ........................................................................................................................................ 47 Maintenance ....................................................................................................................................................... 54 Alarms ................................................................................................................................................................. 55 Linkage ................................................................................................................................................................ 56 I/O Points ............................................................................................................................................................ 57
Appendix C: Loop Control Points/Properties on the Equipment Touch .............................................................. 60 Navigation screens ............................................................................................................................................ 60 Startup Wizard ................................................................................................................................................... 62
Document revision history ........................................................................................................................................ 65
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 1 All rights reserved
What is the Loop Control application?
The Loop Control application is designed to maintain the source supply water temperature at the control setpoint
and provide source water flow as required. The Loop Control application supports up to 4 stages of boiler capacity
and up to 4 cooling tower stages. The controller also provides the option to use 2 cascaded Analog Outputs for
either, or both, the tower staging or boiler capacity staging. The Loop Control can control 1 or 2 pumps in a
constant-flow application, or up to 2 pumps in a variable-flow source water application, maintaining the loop
pressure differential setpoint. The internal application programming provides loop pump operation based on heat
pump demand and/or scheduling. This controller can be used in stand-alone mode, communicate to an i-Vu
Control System, or a BACnet Third Party Building Automation System (BAS).
It can also be used in conjunction with Carrier WSHP Open controller as a complete system that utilizes Linkage to
operate the loop pumps. The Linked system protects against individual heat pump lockouts by sending the loop
status and loop temperature to each heat pump to insure proper operation. The Loop Control, when used with
Carrier WSHP and Linkage, can optimize the water loop temperature for greater system energy savings over a
simple fixed two-setpoint control system.
You can connect a Carrier Equipment Touch user interface with the UC Open XP, using the 5-pin Local Access port.
The Equipment Touch is a touchscreen device with a 4.3 in. color LCD display that you can view or change
property values, schedule equipment, view trends and alarms, and more, without having to access the system's
server.
For more details about the Equipment Touch, see the Equipment Touch Installation and Setup Guide.
The Loop Control application supports detailed color graphics, status, properties, alarms, trends, performance,
configuration, and Help on the Equipment Touch. In addition, the Startup Wizard facilitates configuring installation
configuration. For details, see Loop Control Points/Properties on the Equipment Touch (page 60).
UC Open XP specifications
Power 24 Vac 10%, 5060 Hz
20 VA power consumption
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
BACnet MS/TP Port For communication with the controller network using MS/TP (9600 bps, 19.2
kbps, 38.4 kbps, or 76.8 kbps)
BACnet ARC156 Port For communication with the controller network using ARC156
Source Water Loop Control for UC Open XP overview and specifications
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 2 All rights reserved
Rnet port Supports one Equipment Touch per Rnet.
NOTES
Equipment Touch requires 24 Vac and cannot be powered by Rnet's 12 Vdc.
For more details, see the Equipment Touch Installation and Setup Guide.
The Loop Control application does not support the ZS or Wireless sensor. Only
the Equipment Touch can be connected to the Rnet port.
Local Access port For system start-up and troubleshooting using Field Assistant
Xnet Remote Expansion port For communication with the UC Open XP IO expander.
Inputs 12 inputs configurable for 0-10 V, RTD Therm Dry, or 0-20mA. Inputs 1 and 2 may
be used for pulse counting.
Input pulse frequency 10 pulses per second. Minimum pulse width (on or off time) required for each
pulse is 50 msec.
Input resolution 12 bit A/D
Aux Power Output 5 Vdc or 24 Vdc input sensor power. Jumper selectable, limited to 200 mA.
Available on input terminal 1.
Binary outputs 6 binary outputs, configured as dry contact, normally open or normally closed,
must be powered from a Class 2 power source.
Analog outputs 6 analog outputs:
1 and 2 are configurable for 0-10 V or 0-20 mA
3 - 6 are 0-10 V only
Output resolution 8 bit D/A
Real time clock Battery-backed real time clock keeps track of time in the event of a power failure
Battery 10-year Lithium CR2032 battery retains the following data for a maximum of
10,000 hours during power outages: control programs, editable properties,
schedules, and trends.
Protection Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that
causes a fault returns to normal.
The power, network, input, and output connections are also protected against
transient excess voltage/surge events lasting no more than 10 msec.
CAUTION To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
Status indicators LEDs indicate status of communications, running, errors, and power. LED
indicators for transmit/receive for the BACnet MS/TP and ARC156 ports and for
each of the 12 outputs.
Environmental operating
range
0 to 140 F (-18 to 60C), 0 to 90% relative humidity, non-condensing
Storage temperature range -24 to 140F (-30 to 60C), 0 to 90% relative humidity, non-condensing
Physical Rugged aluminum housing with removable screw terminals
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 3 All rights reserved
Overall dimensions A:
B:
11-13/16 in. (30 cm)
5 in. (12.7 cm)
Mounting dimensions C:
D:
E:
4 in. (10.2 cm)
1/2 in. (1.3 cm)
13/64 in. (.5 cm)
Panel depth 2 in. (5.1 cm)
Weight 1.1lb. (0.5 kg)
BACnet support Conforms to the BACnet Advanced Application Controller (B-AAC) Standard Device
Profile as defined in ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L,
Protocol Revision 9
Listed by UL-916, (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15-Subpart B-Class
A
Safety considerations
WARNING Disconnect electrical power to the UC Open XP before wiring it. Failure to follow this warning
could cause electrical shock, personal injury, or damage to the controller.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 4 All rights reserved
To install the UC Open XP:
1 Mount the controller (page 4).
2 Wire the controller for power (page 4).
3 Set the controller's address (page 5).
4 Wire the controller to the BACnet MS/TP or BACnet ARC156 network (page 6).
5 Wire inputs and outputs (page 7).
6 Wire expanders to the controller (page 14).
7 Wire devices to the Rnet port (page 18).
Mounting the UC Open XP
WARNING
When you handle the UC Open XP:
Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
Do not touch components or leads.
Handle the board by its edges.
Isolate from high voltage or electrostatic discharge.
Ensure that you are properly grounded.
Screw the UC Open XP into an enclosed panel using the mounting slots on the cover plate. Leave about 2 in. (5
cm) on each side of the controller for wiring. See mounting dimensions in Specifications.
If using expanders, see Installing an expander (page 14) before mounting the controller.
Wiring the UC Open XP for power
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
CAUTIONS
The UC Open XP is powered by a Class 2 power source. Take appropriate isolation measures when mounting
it in a control panel where non-Class 2 circuits are present.
Carrier controllers can share a power supply as long as you:
Maintain the same polarity.
Use the power supply only for Carrier controllers.
Installing the UC Open XP
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 5 All rights reserved
To wire for power
1 Turn off the UC Open XP's power switch to prevent it from powering up before you can verify the correct
voltage.
2 Remove primary power from the 24 Vac transformer.
3 Pull the screw terminal connector from the controller's power terminals labeled Gnd and 24 Vac.
4 Connect the transformer wires to the screw terminal connector.
5 Apply primary power to the transformer.
6 Measure the voltage at the UC Open XP's power screw terminal connector to verify that the voltage is within
the operating range of 21.6 - 26.4 Vac.
7 Insert the screw terminal connector into the UC Open XP's power terminals.
8 Turn on the UC Open XP's power switch.
9 Verify that the Power LED is on and the Run LED is blinking.
Addressing the UC Open XP
The UC Open XP's two rotary switches determine its MAC address when it is placed on a BACnet MS/TP network.
The rotary switches define the MAC address portion of the device's BACnet address, which is composed of the
network address and the MAC address.
1 Turn on the controller's power.
2 Using the rotary switches, set the controller's address. Set the Tens (10's) switch to the tens digit of the
address, and set the Ones (1's) switch to the ones digit.
EXAMPLE If the controllers address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
10's
1's
1
3
45
2
7 8
9
6
0
1
3
45
2
7 8
9
6
0
3 Turn on the controller's power.
NOTE The controller reads the address each time you apply power to it.
CAUTION The factory default setting is 00 and must be changed to successfully install your UC Open XP.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 6 All rights reserved
Wiring for communications
The UC Open XP communicates using BACnet on the following types of network segments:
MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
ARC156 communicating at 156 kbps
NOTE For more networking details, see the Open Controller Network Wiring Installation Guide.
Wiring specifications for BACnet MS/TP and ARC156
Cable: 22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
Maximum length: 2000 feet (610 meters)
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
To wire the controller to the network
1 Pull the screw terminal connector from the controller's power terminals labeled Gnd and 24 Vac.
2 Check the communications wiring for shorts and grounds.
3 Connect the communications wiring to the BACnet MS/TP or to the BACnet ARC156 port.
NOTE Use the same polarity throughout the network segment.
4 For MS/TP, verify the jumpers are set to 485-2w and EIA-485. They are not used for ARC156.
5 Set the communication type and baud rate.
For...
Set Communications
Selection jumper to...
Set DIP switches 1 and 2
to...
Set DIP switches 3 and 4
to...
MS/TP MS/TP The appropriate baud rate.
See the MS/TP Baud
diagram on the controller.
Off/Off
ARC156 ARC156 N/A. Baud rate will be 156
kbps regardless of the DIP
switch settings.
On/On
NOTE Use the same baud rate for all controllers on the network segment.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 7 All rights reserved
6 Wire the controllers on an MS/TP or ARC156 network segment in a daisy-chain configuration.
7 If the UC Open XP is at either end of a network segment, connect a BT485 to the UC Open XP.
8 Insert the power screw terminal connector into the UC Open XP's power terminals.
9 Verify communication with the network by viewing a Module Status report in the i-Vu interface.
Wiring inputs and outputs
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
See Appendix A (page 38) to print a blank wire list.
Inputs and outputs table
Depending on the configuration of the Loop Control application, the I/O points change. For variable flow
applications,such as the bypass valve control or VFD pump control, the function of Channel AO2 changes.
I/O Type Channel Input Type Object Name
Source Supply Water Temp BAI IN-1 10K Thermistor sswt_sensor
Source Return Water Temp BAI IN-2 10K Thermistor srwt_sensor
OAT sensor BAI IN-3 10K Thermistor oatsens
RH sensor BAI IN-4 0-10 Vdc rh_sensor
Source Water Diff. Pressure BAI IN-5 0-10 Vdc src_diff_press
SW Pump 1 Amp sensor BAI IN-6 0-10 Vdc swp1_amp_sensor
SW Pump 1 Status BBI IN-6 Dry Contact sw_p1_status
SW Pump 2 Amp sensor BAI IN-7 0-10 Vdc swp2_amp_sensor
SW Pump 2 Status BBI IN-7 Dry Contact sw_p2_status
Remote
Contact Input
BBI IN-8 Dry Contact rem_con
Source Water Flow BBI IN-9 Dry Contact sw_flow
High Wtr Level BBI IN-10 Dry Contact high_sump_lvl
Low Wtr Level BBI IN-11 Dry Contact low_sump_lvl
Pump 1 VFD Output BAO AO-1 0-10 Vdc pump1_vfd_output
Bypass Valve/Pump 2 VFD Output BAO AO-2 0-10 Vdc chw_bypass_valve_vfd
Boiler Output 1 BAO AO-3 0-10 Vdc boiler_output1
Boiler Output 2 BAO AO-4 0-10 Vdc boiler_output2
Tower Output 1 BAO AO-5 0-10 Vdc tower_output1
Tower Output 2 BAO AO-6 0-10 Vdc tower_output2
CW Pump1 S/S BBO BO-1 cw_pump1
CW Pump2 S/S BBO BO-2 cw_pump2
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 8 All rights reserved
I/O Type Channel Input Type Object Name
WSHP Comp Command BBO BO-3 wshp_ok
Alarm BBO BO-4 alm
Makeup Valve BBO BO-5 makeup
Boiler Output Stage 1 BBO EXP BO-1 m1128
Boiler Output Stage 2 BBO EXP BO-2 m1141
Boiler Output Stage 3 BBO EXP BO-3 m1142
Boiler Output Stage 4 BBO EXP BO-4 m1143
Tower Output Stage 1 BBO EXP BO-5 m1144
Tower Output Stage 2 BBO EXP BO-6 m1145
Tower Output Stage 3 BBO EXP BO-7 m1146
Tower Output Stage 4 BBO EXP BO-8 m1147
Legend
AI - Analog Input
BI - Binary Input
AO - Analog Output
BO - Binary Output
*Channel use is determined by specific application configuration.
Input wiring specifications
Input Maximum length Minimum gauge Shielding
05 Vdc 500 feet
(152 meters)
22 AWG 100 feet
(30.4 meters) unshielded
100 - 500 feet shielded
Thermistor
Dry contact
Pulse counter TLO
500 feet
(152 meters)
22 AWG 100 feet
(30.4 meters) unshielded
100 - 500 feet shielded
Equipment Touch
device
500 feet
(152 meters)
22 AWG (7x0096) bare
copper
If shielded, Aluminum/Mylar shield
(100% coverage) with TC drain wire
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 9 All rights reserved
Inputs
The UC Open XP has inputs that accept the following signal types.
Signal Type Description
Thermistor Precon type 2 (10 kOhm at 77F). Input voltages should be from 0.489 Vdc
to 3.825 Vdc for thermistors.
Dry contact A 5 Vdc wetting voltage detects contact position, resulting in a 1 mA
maximum sense current when the contacts are closed.
05 Vdc
010 Vdc
The input impedance of the UC Open XP is approximately 20 kOhm.
020 mA
The input resistance on the positive (+) terminal is 250 Ohms. The Aux
Power Out connector is capable of supplying 24 Vdc to multiple 420 mA
transducers, but the total current demanded must not exceed 200 mA. If the
voltage measured from the Aux Power Out connector to Gnd is less than 18
Vdc, you need to use an external power supply.
RTD Platinum - 1 kOhm at 32F (0C)
Nickel/Iron - 1 kOhm at 70F (21C)
Balco TS8000 - 1 kOhm at 70F (21C)
Input voltages should be from 0.61.2 V
Pulse counter* UI-1 and UI-2 only:
Maximum of pulses per second. Minimum pulse width required for each
pulse:
ON to OFF time (half cycle) is msec
ON to OFF to ON time (full cycle) is msec
* The UC Open XP can perform pulse counting for dry contact or voltage inputs if you assign the input to a Pulse
to Analog Input microblock.
Binary outputs
The UC Open XP has 6 binary outputs. Each output is a dry contact that must be powered from a Class 2 power
source.
To size output wiring, consider the following:
Total loop distance from the power supply to the controller, and then to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
Acceptable voltage drop in the wire from the controller to the controlled device
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 10 All rights reserved
Analog outputs
The UC Open XP has analog outputs:
1 and 2 are configurable for 0-10 Vdc or 0-20 mA
3, 4, 5, and 6 are 0-10 V only
The controlled device must and have the following input impedance:
If output controls a... Resistance to ground must be...
010 Vdc device 500 Ohms minimum
020 mA device 800 Ohms maximum
NOTES
The device must share the same ground as the UC Open XP
The total output current from all outputs and the Aux Power Out connector must not exceed 200 mA at 86F
(30C).
200 mA at 115F
122.5 mA at 140F
For temperatures above 86F (30C), use the following equation to calculate the total current at 3.1 mA per
degree:
200 mA - ((max. expected temp. - 86F) * 3.1 mA/F)
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 11 All rights reserved
To wire inputs and outputs on the UC Open XP
1 Turn off the UC Open XP's power.
2 Connect the input wiring to the screw terminals on the UC Open XP.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 12 All rights reserved
NOTES
If using shielded wire, connect the shield to the GND terminal with the ground wire. Tape off the shield
wire at the sensor end.
Connect the shield wire to the GND terminal with the ground wire.
Use only UI-1 or UI-2 for pulse counter or timed local override.
For an internally-powered 4-20 mA sensor, wire the sensor's positive terminal to the + terminal on the UC
Open XP's Aux Power Out port. Wire the sensor's negative terminal to an input's + terminal.
3 Set the appropriate jumpers on the UC Open XP.
To use... For...
Any input Thermistor
Dry contract
05 Vdc
0-10 Vdc
020 mA
RTD
Set each input's
Universal Input
Mode Select
jumper to the
type of signal the
input will receive.
Aux Power
Out port
Internally-powered
4-20 mA
Set the Select jumper to +5V or +24V as
required by the sensor.
4 Connect the binary output wiring to the screw terminals on the UC Open XP and to the controlled device.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 13 All rights reserved
5 Connect the analog output wiring to the screw terminals on the UC Open XP and to the controlled device.
6 Set the AO Mode Select jumper to the type of device you are wiring the output to.
7 Turn on the UC Open XP's power.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 14 All rights reserved
1 Mount the expander. (page 14)
2 Wire the expander for power. (page 15)
3 Wire inputs and outputs. (page 17)
CAUTION Do not change the rotary switch address from the default setting of 1.
To mount and attach the UC Open XP IO
WARNING
When you handle the UC Open XP IO:
Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
Do not touch components or leads.
Handle the board by its edges.
Isolate from high voltage or electrostatic discharge.
Ensure that you are properly grounded.
Wiring restrictions for connecting the UC Open XP IO to the UC Open XP
Maximum length: 100 feet (30 meters)
22 or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
You can mount the UC Open XP IO in one of the following locations:
On top of a UC Open XP, using the two allen cap screws provided. Connect Gnd to Gnd, Xnet- to Xnet-, Xnet+
to Xnet+.
Installing the UC Open XP IO expander
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 15 All rights reserved
Beside the UC Open XP, by screwing the UC Open XP IO into an enclosed panel using the mounting slots on
the cover plate. Leave about 2 in. (5 cm) on each side of the expander for wiring. Mounting hole dimensions
1.5" from the left (width) by 10.2" (height). Connect Gnd to Gnd, Xnet- to Xnet-, Xnet+ to Xnet+. You can
mount the UC Open XP IO up to 100 ft away from the UC Open XP.
To wire for power
Older models of the UC Open XP IO have a power jumper that you must set to turn the expander on and off.
CAUTIONS
The UC Open XP IO expander is powered by a Class 2 power source. Take appropriate isolation measures
when mounting it in a control panel where non-Class 2 circuits are present.
For the UC Open XP to recognize an attached expander, you must turn on the expander before you turn on the
UC Open XP.
1 Pull the screw terminal connector from the controller's power terminals labeled Gnd and 24 Vac.
2 Ground shielded wire to the UC Open XP IO's ground terminal.
3 Set the configuration jumpers for inputs 9 through 16 for thermistor/dry contact or 0-5 Vdc.
4 Insert the power screw terminal connector into the UC Open XP's power terminals.
5 Verify that the Power LED is on and the Run LED is blinking.
Wiring inputs and outputs
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
See Appendix A (page 38) to print a blank wire list.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 16 All rights reserved
Input wiring specifications
Input Maximum length Minimum gauge Shielding
05 Vdc 500 feet
(152 meters)
22 AWG 100 feet Unshielded
100 - 500 feet Shielded
Thermistor
Dry contact
Pulse counter
TLO
500 feet
(152 meters)
22 AWG 100 feet Unshielded
100 - 500 feet Shielded
Inputs on the UC Open XP IO
The UC Open XP IO has 16 inputs that accept the following signal types:
Signal Type Description
Thermistor Precon type 2 (10 kOhm at 77F). Input voltages should be from 0.489 Vdc to 3.825 Vdc
for thermistors.
Dry contact A 5 Vdc wetting voltage detects contact position, resulting in a 1 mA maximum sense
current when the contacts are closed.
05 Vdc
The input impedance of the UC Open XP IO is approximately 20 kOhm.
Pulse counter 10 pulses per second. Minimum pulse width (on or off time) required for each pulse is 50
msec.
Binary outputs
The UC Open XP IO has 8 binary outputs. Each output is a dry contact that must be powered from a Class 2 power
source.
To size output wiring, consider the following:
Total loop distance from the power supply to the controller, and then to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
Acceptable voltage drop in the wire from the controller to the controlled device
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 17 All rights reserved
To wire inputs and outputs on UC Open XP IO
1 Verify that the UC Open XP IO's power and communications connections work properly.
2 Pull the screw terminal connector from the controller's power terminals labeled Gnd and 24 Vac.
3 Connect the input wiring to the screw terminals on the UC Open XP IO.
NOTE Connect the shield wire to the GND terminal with the ground wire.
4 Set each input's Universal Input Mode Select jumper to indicate the type of input.
WARNING Do not apply 24 Vac to these universal inputs.
5 Connect binary output wiring to the BO screw terminals on the UC Open XP IO and to the controlled device.
6 Wire GND for each binary output to its even-numbered terminal.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 18 All rights reserved
7 Insert the power screw terminal connector into the UC Open XP's power terminals.
Wiring an Equipment Touch to the UC Open XP's Rnet port
Only the Equipment Touch can be connected to the Rnet port. The Loop Control application does not support the
SPT sensor, ZS sensor, or Wireless Adapter for wireless sensor.
The Rnet communicates at a rate of 115 kbps.
CAUTION The Equipment Touch requires a 24 Vac power supply. It is not powered by the Rnet.
Wiring Specifications
NOTE If you wire the Equipment Touch directly to the controller's Rnet port, you can use a 2-conductor cable
instead of the standard 4-conductor Rnet cable.
Description 4-conductor, shielded or unshielded, CMP, plenum rated cable
Conductor 22 AWG (7x0096) bare copper
Maximum length 500 feet (152 meters)
Insulation Low-smoke PVC (or equivalent)
Color Code Black, white, green, red
Shielding If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire
UL temperature rating 32167F (075C)
Voltage 300 Vac, power limited
Listing UL: NEC CL2P, or better
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 19 All rights reserved
To wire an Equipment Touch to the UC Open XP
Power wiring
2-conductor wire 18 AWG for distances up to 100 feet. All transformer secondaries must be grounded. Wiring
connections must be in accordance with NEC and local codes.
The Equipment Touch cannot be powered by the Rnet. It requires a 24 Vac (15%), 5 VA, 5060 Hz, Class 2
external power supply.
Rnet wiring
NOTE If you wire the Equipment Touch directly to the controller's Rnet port, you can use a 2-conductor cable
instead of the standard 4-conductor Rnet cable.
Description 4-conductor, shielded or unshielded, CMP, plenum rated cable
Conductor 22 AWG (7x0096) bare copper
Maximum length 500 feet (152 meters)
Insulation Low-smoke PVC (or equivalent)
Color Code Black, white, green, red
Shielding If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire
UL temperature rating 32167F (075C)
Voltage 300 Vac, power limited
Listing UL: NEC CL2P, or better
CAUTION The UC Open XP can share a power supply with the Carrier controller as long as:
The power supply is AC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.
1 Turn off the UC Open XP's power.
2 Partially cut, then bend and pull off the outer jacket of the cable. Do not nick the inner insulation.
3 Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 20 All rights reserved
4 Wire the UC Open XP's Rnet+ and Rnet- terminals to the terminals of the same name on the Equipment
Touch's connector.
NOTE If using shielded wire, connect the shield wire and the ground wire to the Gnd terminal.
5 Turn on the UC Open XP's power.
6 Turn on the Equipment Touch.
For complete Equipment Touch installation instructions including wiring diagrams, see the Equipment Touch
Installation and Setup Guide.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 21 All rights reserved
Use one of the following interfaces to start up, access information, read sensor values, and test the controller.
This interface... Provides a...
Field Assistant application -
Runs on a laptop that connects to controller's Local Access port 1
Temporary interface
Equipment Touch device -
Connects to controller's Rnet port 2
Temporary or permanent
interface
i-Vu application
Available for BACnet systems only
Permanent interface
System Touch device
Available only for BACnet MS/TP systems.
Wire to a BACnet MS/TP network connector and a 24 Vac power supply 3
Temporary or permanent
interface
1 Requires a USB Link (Part #USB-L). 2 See the Equipment Touch Installation and Setup Guide for detailed instructions. 3 See the System Touch Installation and Setup Guide for detailed instructions.
CAUTION If multiple controllers share power but polarity was not maintained when they were wired, the
difference between the controller's ground and the computer's AC power ground could damage the USB Link and
the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB
Link. Purchase a USB isolator online from a third-party manufacturer.
Select the Loop Control control program and graphic
The field-installed UC Open XP does not come from the factory with a control program or graphic. You must load a
control program and graphic as part of the installation and commissioning. You can select the Loop Control control
program and graphic from EquipmentBuilder. All the configurations that are currently available for the Loop
Control are included in a single download file for both the equipment and graphic.
After selecting the control program and graphic files, save and download them to the controller. If desired, you can
create a custom graphic using ViewBuilder. See ViewBuilder Help for details.
Configure the points and properties
You must configure certain points and properties.
Appendix B (page 42) is a complete list of all the points and properties, with descriptions, defaults, and ranges.
These properties affect the unit operation and/or control. Review and understand the meaning and purpose of
each property before changing it.
Start-up
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 22 All rights reserved
Appendix C (page 60) show the points and properties you can configure using the Equipment Touch.
To start up the controller, configure your necessary points/properties in the following:
Unit Configuration (page 43)
Setpoints (page 45)
Service Configuration (page 47)
Examples of some settings that you need to configure for start-up are the Number of Pumps, Pump Control, and
Pump Staging, found in the Service Configuration (page 47) section of Appendix B (page 42).
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 23 All rights reserved
The Loop Control Source Loop Control is an application that is designed to control the pumps, towers, and boiler
operation in a heat pump system. The pumps provide water loop circulation, while the towers and boilers supply or
remove energy from the source water loop for the heat pumps. The Loop Control can control one or two pumps in
a constant-flow application, or up to 2 pumps in a variable-flow source water application, maintaining the loop
pressure differential setpoint
The Loop Control supports Carrier Condenser Water Linkage between Carrier Open WSHP units and the loop
controller. When Linkage is active, the loop controller responds to the demands for heating or cooling from the
Open WSHPs and will operate the pump(s) when required. The system provides closed loop feedback to the
individual WSHPs by confirming source water availability prior to operating any compressors in the Carrier Open
WSHPs. Also, the Loop Control receives the acceptable range of the source water temperature from the Carrier
Open WSHPs and verifies that the water provided is within the required operating temperature range.
The Loop Control may be used as a standalone loop control without Carrier Linkage and utilize a third party
BACnet system for control, or operate in a standalone mode providing a hardwired binary input to command the
loop pump operation and a hardwired binary output (WSHP Comp Command) to confirm successful loop
operation.
The following sections describe the Loop Control's functionality. All points in this sequence of operation refer to
the Equipment Touch, Field Assistant, or i-Vu interface.
Scheduling without Condenser Water Linkage
Scheduling
The Loop Control MUST be occupied for loop pump operation. The occupied time periods define when the pump(s)
operate. The Loop Control operates the pumps continuously during the occupied period.
You must provide a source for occupancy by:
configuring a Time Schedule
mapping System Occupancy to a BACnet point
utilizing the Remote Contact Input
using a third party control system that Enables/Disables the BAS On/Off point
setting the local time and date for the schedule to function and operate properly
You can change the occupancy source to one of the following:
Occupancy Schedules
The controller is occupied 24/7 until you configure a time schedule using the Equipment Touch, Field
Assistant, the i-Vu application, or until a third party control system Enables/Disables the BAS On/Off point.
You can disable the local occupancy default operation by going to Configuration > Unit Configuration >
Occupancy Schedules and changing the point from Enable to Disable and clicking OK.
NOTE You must Enable this point in order for the Equipment Touch, Field Assistant, or the i-Vu application
to assign a time schedule to the controller.
Sequence of Operation
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 24 All rights reserved
Schedule
The unit operates according to the schedule configured and stored in the unit. The schedule is accessible in
the Equipment Touch, Field Assistant, or the i-Vu application. The daily schedule consists of a start and stop
time (standard or 24-hour mode) and 7 days of the week, starting with Monday and ending on Sunday.
Enable the Occupancy Schedules to use the occupancy scheduling.
Occupancy Input Contact (optional)
If configured for remote occupancy control (default), the controller can use an external dry contact closure to
determine the occupancy status of the Loop Control. Disable the Occupancy Schedules to use the occupancy
contact input.
NOTE Scheduling can only be controlled from one source.
BAS (Building Automation System) On/Off
For use with a Building Automation System that supports network scheduling, you must disable the
Occupancy Schedules so the BAS can control the unit through a network communication and the BAS
scheduling function.
NOTE Scheduling can either be controlled from the unit or the BAS, but not both.
System Occupancy
Uses the network to obtain an occupancy status value from another controller, which is read over the network
and used by this controller. Occupancy Schedules MUST be set to Disable to use this function. See Device
Address Binding to configure the System Occupancy point.
NOTE Scheduling can only be controlled from one source.
Scheduling with Condenser Water Linkage
When the Loop Control is part of a Carrier Open WSHP system and Condenser Water Linkage is active, you can
configure how the loop pumps operate. The system can be configured to start the pumps only on a heating or
cooling demand from any of the Carrier WSHPs linked to the Loop Control by setting the Pump Start to Demand.
You can configure it to operate the loop pumps on any demand and/or continuously during the occupied period,
as defined by the Open WSHPs' schedules that are connected through Linkage. No local occupancy scheduling is
available when Linkage is active.
Constant flow pump control
You can configure the Loop Control to operate 1 or 2 constant speed loop pumps.
When power is reapplied after a power outage, there is a user-configurable delay of 5 - 600 seconds (default 5)
before starting any pump. You must configure Power Fail Restart Delay to define the delay time (0 - 600 seconds,
default 5) before the pump begins to operate after power has been restored to the controller.
If the Shutdown input is active, the pump is shut down after the Pump Stop Delay expires, regardless of
occupancy state. Otherwise, the pump will operate whenever the occupancy state is determined to be occupied.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 25 All rights reserved
Pump Status (Option) - An optional hardware input is available for each pump. You can configure it as either an
analog input to detect pump status by measuring the pump current or as a binary input to measure pump state
as a discrete input (on/off). Configure each pump separately. Also, there is a Network Status input to read the
pump status, if available (See Device Address Binding).
Pump status options include:
Switch
Amperage
Network
None
If the pump status is not configured as None, the controller compares the status of the pump to the desired
commanded state. When the pump is commanded to run (ON), the pump status is checked and verified to match
the commanded state. If the pump status is not on, then a Pump n Fail Alarm (n indicates the pump number) is
generated after 30 seconds. When the pump is commanded OFF, if the pump status is still on, then a Pump n in
Hand Alarm is generated after 30 seconds.
Loop pump(s) constant flow
The Loop Control operates one or two pumps in constant flow mode to provide source water for the water source
heat pumps. For a single pump application, the pump operates as a lead pump whenever the Loop Control is in an
occupied mode. For two-pump systems, the Loop Control is automatically configured to operate the pumps as
lead/standby, where the second pump is available as a spare if the lead pump fails.
The following conditions must be true in order for the cooling algorithm to run:
Loop Control is occupied (standalone) or a pump requirement is received from Linkage
The Shutdown input is not active
If the above conditions are met, the pump is energized, otherwise it is disabled. After the pump output is enabled,
if a pump status type is configured, then the pump status will be checked to verify that the actual pump operation
matches the commanded state. For two-pump systems, if a pump failure is detected, the Loop Control energizes
the standby pump and verifies its operation if a pump status type has been selected. An alarm is generated for
any pump that has failed.
Loop Pump(s) with bypass valve differential pressure control
The Loop Control operates 1 or 2 constant speed pumps in variable flow mode using a bypass valve to control the
loop differential pressure and provide source water for the water source heat pumps. For a single pump
application, the pump operates as a lead pump whenever the Loop Control is in an occupied mode. For 2-pump
systems, the Loop Control is automatically configured to operate the pumps as lead/standby, where the second
pump is available as a spare if the lead pump fails. When the pumps are required to operate, the Loop Control
monitors the differential loop pressure input and adjusts the bypass valve position to maintain the required loop
pressure to meet the desired setpoint.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 26 All rights reserved
The following conditions must be true in order for the cooling algorithm to run:
Loop Control is occupied (standalone) or a pump requirement is received from Linkage.
The Shutdown input is not active
The loop differential pressure input is valid
If the above conditions are met, the pump is energized, otherwise it is disabled. After the pump output is enabled,
if a pump status type is configured, then the pump status will be checked to verify that the actual pump operation
matches the commanded state. For 2-pump systems, if a pump failure is detected, the Loop Control will energize
the standby pump and verify its operation if a pump status type has been selected. An alarm is generated for any
pump that has failed.
After enabling the pump, the bypass is commanded to the full bypass position. The loop differential pressure is
then compared to the desired loop pressure setpoint and a PID calculates the bypass valve position required to
meet the loop pressure setpoint.
Loop Pump(s) with VFD loop differential pressure control
The Loop Control operates 1 or 2 pumps in variable flow mode using a VFD to control pump speed and provide
source water for the water source heat pumps. For a single pump application, the pump operates as a lead pump
whenever the Loop Control is in an occupied mode. For 2-pump systems, when the Loop Control is configured to
operate the pumps as lead/standby, the second pump is available as a spare if the lead pump fails. When the
pumps are required to operate, the Loop Control monitors the differential loop pressure input and adjusts the
speed of the lead pump to provide the required loop pressure to meet the desired setpoint.
The following conditions must be true in order for the cooling algorithm to run:
Loop Control is occupied (standalone) or a pump requirement is received from Linkage
The Shutdown input is not active
The loop differential pressure input is valid
If the above conditions are met, the pump is energized. Otherwise, it is disabled. After the pump output is enabled,
if a pump status type is configured, then the pump status is checked to verify that the actual pump operation
matches the commanded state. For 2-pump systems, if a pump failure is detected, the Loop Control energizes the
standby pump and verifies its operation, if a pump status type has been selected. An alarm is generated for any
pump that has failed.
After enabling the pump, the VFD is commanded to the user-configured Min VFD Output speed. The loop
differential pressure is then compared to the desired loop pressure setpoint and a PID calculates the required
pump speed to meet the setpoint.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 27 All rights reserved
Two loop pumps with VFDs, lead/lag operation for loop differential
pressure control
The Loop Control operates 2-staged pumps in variable flow mode using a VFD to control pump speed and provide
source water for the water source heat pumps. For staged operation, the Loop Control Pump Staging must be set
to lead/lag, which uses the second pump as a lag pump for additional flow capacity. When the pumps are
required to operate, the Loop Control monitors the differential loop pressure input and adjusts the number of
operating pumps and the speed of the pumps to provide the required loop pressure to meet the desired setpoint.
The following conditions must be true in order for the cooling algorithm to run:
Loop Control is occupied (standalone) or a pump requirement is received from Linkage
The Shutdown input is not active
The loop differential pressure input is valid
If the above conditions are met, the lead pump is energized, otherwise all pumps are disabled. After the lead
pump output is enabled, if a pump status type is configured, then the pump status will be checked to verify the
actual pump operation matches the commanded state. If a pump failure is detected, the Loop Control will
energize the lag pump and verify its operation if a pump status type has been selected. An alarm is generated for
any pump that has failed.
After enabling the lead pump, the VFD is commanded to the user-configured Min VFD Output speed. The loop
differential pressure is then compared to the desired loop pressure setpoint and a PID calculates the required
pump speed to meet the setpoint. If the lead pump speed increases above the user-configured setpoint to enable
the lag pump (90% default), then the lag pump starts and slowly begins to ramp up to the current VFD
commanded output speed. The PID monitors the loop pressure and, as the lag pump increases speed and the
loop pressure increases, the PID output is reduced, as necessary, until both pumps achieve the same operating
speed.
If the loop flow requirement is reduced, and if both pumps are operating and the VFD speed drops below 65% (the
user-configured setpoint minus the configured hysteresis), then the lag pump is disabled.
Pump rotation
The ability to rotate pumps is available for any application with 2 pumps. Pump rotation is user-configured. The
following options are available:
Daily
Weekly
Monthly
Manual Rotation
Runtime
Never Rotate
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 28 All rights reserved
If you select daily, weekly, or monthly, the lead and standby or lag pump rotates as scheduled and on the
configured day and time. If you select manual rotation, you must rotate the pumps manually by selecting Rotate
from the drop-down menu. If you select Runtime, the pumps automatically rotate after the lead pump operating
hours reach the configured number of hours.
Tower fan control
The Loop Control has the ability to directly control up to 2 stages of variable speed (VFD-controlled) tower fans
through 2 cascade, staged, analog outputs or up to 4 stages of tower fans (on/off) using 4 binary outputs. The
first stage analog out may also be used alone or in conjunction with an external field-supplied staging controller to
convert the analog signal to the desired number of staged binary outputs.
Whenever the pumps are commanded to run, flow has been proven, and if the source water temperature is
greater than the loops configured Maximum Source Water Temp Setpoint minus 5F, or if Linkage is active,
above the Max Allowable Loop Temperature minus 5F (loop cooling setpoint), a PID loop calculates the desired
tower fan output.
See Loop Optimization (page 31) for details on loop setpoint optimization when Linkage is used and Loop
Optimization is set to Enable.
Analog (2-stage modulating) tower fan control
When configured for Modulating, the Loop Control provides 2 analog outputs to directly control up to 2 stages of
variable speed (VFD-controlled) tower fans. 2 binary outputs are also provided to control the tower dampers or
diverting valve, if required.
If the PID output is greater than 0, the binary output Tower Output Stage 1 is energized to allow for tower
operation and the analog output Tower Ouput 1 is set to the PID output value.
If the PID output exceeds the user-configurable lag tower enable setpoint, the second binary output Tower
Output Stage 2, is energized to allow for the second tower operation and the second analog output Tower
Output 2 is set to the PID output value.
If the tower fan's speed decreases below the user-configured lag tower enable setpoint, minus the hysteresis
value, the second tower is disabled.
The following conditions must be true for the cooling algorithm to run:
Loop Control is occupied (standalone) or a pump requirement is received from Linkage
The Shutdown input is not active
The loop flow must be proven
CAUTION The source water temp must be greater than the loop cooling setpoint to start and stay above the
setpoint minus the hysteresis value.
If the above conditions are met, the PID is activated and calculates a value required to maintain the loop cooling
setpoint. If the PID output value is greater than 0, the first stage binary tower output is enabled and the first stage
tower fan operates at the calculated output speed.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 29 All rights reserved
After enabling the lead tower, if the tower fan speed increases above the user-configured setpoint, to enable the
lag tower output (71% default), then the lag tower is empowered by enabling the Tower Output Stage 2, while
slowly ramping up Tower Output 2 VFD-commanded output speed until both achieve the same operating speed.
If the tower fan speed decreases below the user-configured setpoint, minus the hysteresis (default 50%), the lag
tower output Tower Output Stage 2 is disabled and the Tower Output 2 VFD is commanded to 0%.
Staged tower fan control
The Loop Control provides the capability to control from 1 to 4 stages of tower fans. When configured for staged
control, the user must select the number of tower stages. The Loop Control provides 4 dedicated binary outputs
that can directly control up to 4 stages of tower fans.
The following conditions must be true for the cooling algorithm to run:
Loop Control is occupied (standalone) or a pump requirement is received from Linkage
The Shutdown input is not active
The loop flow must be proven
CAUTION The source water temp must be greater than the loop cooling setpoint to start and stay above the
setpoint minus the hysteresis value.
If the above conditions are met, the PID is activated and calculates a value required to maintain the desired
setpoint. The PID output value is compared to the calculated Enable % based on the number of tower stages
configured and, if it is greater than that value, the appropriate stages are energized.
The formula below determines the stage enable point:
Enable % = 100 / [Number of stages +1]
Each stage number is multiplied by the Enable % to determine when that stage is enabled.
EXAMPLE In a 3 stage application, the Enable % equals 100 / 3+1 or 25%.
Therefore, Stage 1 is energized when the PID output > 25%, Stage 2 at > 50%, and stage 3 at > 75%.
Once a stage is energized, a user-configurable hysteresis prevents short cycling (defaults: Stage 1 hysteresis is
10%, all others are 20%). As the loop temperature is satisfied and falls below the setpoint, the PID output
decreases and stages are disabled in sequential order from highest to lowest.
Boiler control
The Loop Control can directly control up to 2 stages of variable fire boilers using 2 cascade, staged, analog
outputs, or up to 4 stages of boilers (on/off) using 4 binary outputs.
The first stage analog output may be used alone, or in conjunction with an external field-supplied staging
controller, to convert the analog signal to the desired number of staged binary outputs.
Whenever the pumps are commanded to run, flow has been proven, and if the source water temperature is less
than the loops configured Minimum Source Water Temp Setpoint plus 5F, or if Linkage is active, below the Min
Allowable Loop Temperature plus 5F (loop heating setpoint), a PID loop calculates the desired tower fan output.
See Loop Optimization (page 31) for details on loop setpoint optimization when Linkage is used and Loop
Optimization is set to Enable.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 30 All rights reserved
Analog (2-stage modulating) boiler/valve control
When configured for Modulating, the Loop Control provides 2 analog outputs to directly control up to 2 stages of
variable fire boilers or a hot water mixing valve.
If the PID output is greater than 0, the analog output, Boiler Output 1, is set to the PID output value.
If the PID output exceeds the user configurable lag boiler enable setpoint, the second analog output, Boiler
Output 2, will ramp up to the PID output value.
If the PID output decreases below the user-configured lag boiler enable setpoint, minus the hysteresis value,
the second boiler is disabled.
The following conditions must be true for the boiler algorithm to run:
Loop Control is occupied (standalone) or a pump requirement is received from Linkage
The Shutdown input is not active
The loop flow must be proven
CAUTION The source water temp must be less than the loop heating setpoint to start and stay below the
setpoint plus the hysteresis value
If the above conditions are met, the PID is activated and calculates a value required to maintain the loop heating
setpoint. If the PID output value is greater than 0, the first stage boiler output is set to the PID value.
If the PID output increases above the user-configured setpoint to enable the lag boiler (99% default), then the lag
boiler is enabled and slowly ramps Boiler Output 2, until both achieve the same output value.
If the boiler output PID decreases below the user-configured setpoint, minus the hysteresis (default 5%), the lag
boiler output Boiler Output 2, is commanded to 0%.
Staged boiler control
The Loop Control provides the capability to control from 1 to 4 stages of boilers. When configured for staged
control, the user must select the number of boiler stages. The Loop Control provides 4 dedicated binary outputs
that can directly control up to 4 stages.
The following conditions must be true for the cooling algorithm to run:
Loop Control is occupied (standalone) or a pump requirement is received from Linkage
The Shutdown input is not active
The loop flow must be proven
CAUTION The source water temp must be less than the loop heating setpoint to start and stay below the
setpoint plus the hysteresis value.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 31 All rights reserved
If the above conditions are met, the PID is activated and calculates a value required to maintain the desired
setpoint. The PID output value is compared to the calculated Enable % based on the number of boiler stages
configured and, if it is greater than that value, the appropriate stages are energized.
The formula below determines the stage enable point:
Enable % = 100 / [Number of stages +1]
Each stage number is multiplied by the Enable % to determine when that stage is enabled.
EXAMPLE In a 3 stage application, the Enable % equals 100 / 3+1 or 25%.
Therefore, Stage 1 is energized when the PID output > 25%, Stage 2 at > 50%, and stage 3 at > 75%.
Once a stage is energized, a user-configurable hysteresis prevents short cycling (defaults: Stage 1 hysteresis is
10%, all others are 20%). As the loop temperature is satisfied and falls below the setpoint, the PID output
decreases and stages are disabled in sequential order from highest to lowest.
Condenser Water Linkage
The Loop Control receives and sends information from any linked Carrier WSHP Open controllers through
Condenser Water Linkage. When required to operate, the source water loop pumps supply water for all the
connected water source heat pumps. The Loop Control receives the composite heat pumps operating water
temperature limits, occupancy status, and the total demand for both heating and cooling from all the connected
WSHP Open equipment. In return, the Loop Control sends the loop pump status and loop temperature to each
heat pump so each WSHP Open can verify it is capable to operate its compressors safely without causing a
lockout condition to occur.
NOTE The minimum and maximum loop temperatures for heating and cooling are configured separately in each
WSHP Open controller. Refer to the specific requirements for acceptable loop temperatures in the Product Data
for each individual heat pump.
Loop optimization
The UC Open XP has the ability to provide loop optimization for system utilizing WSHP Open controllers and
Linkage. Loop optimization provides a more efficient operating system by adjusting the loop temperature up or
down, based on the number of heat pumps operating in the heating or cooling mode. Loop Optimization must be
set to Enable to use this feature.
Loop optimization provides two optimization methods. If Loop Calculation Type is set to 15 day average (default),
the calculation takes into effect 15 days of rolling data to determine the optimum loop temperature. This
seasonally adjusts to building operating conditions and filters out one-day event occurrences. If Loop Calculation
Type is set to Daily, only the last 24 hours of data is used. All data is accumulated every hour to record how many
heat pumps were operating in heating mode and how many were operating in cooling mode.
Loop Calculation determines how the data is used to determine the optimum loop temperature. If it is set to
Weighted Average (default), the actual number of heat pumps operating each hour, in each mode, are taken into
account to ensure the loop is optimized for the largest heat pump energy usage. If it is set to Equally Weighted,
then each hour is treated the same, regardless of the total number of heat pumps operating during that hour.
Finally, Loop differential ensures sufficient hysteresis between the setpoint used for loop heating control and the
setpoint used for loop cooling control. The individual setpoints are determined from the calculated ideal loop
setpoint and the position of that setpoint between the allowable minimum and maximum loop temperatures.
The default Loop differential is set to 10F but is user-adjustable and must be set to at least 5F or higher.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 32 All rights reserved
WSHP compressor enable command output
The Loop Control has a binary output and a network-accessible BACnet BV that can be used to interlock the
operation of the connected WSHP equipment in standalone application without Linkage. The output determines
when the individual WSHP units can safely operate.
The output is activated whenever the pumps are commanded to run and flow has been detected via the Source
Water Flow binary input or the Network Flow input and the loop temperature is between the configured Min
Source Water Temp Alarm Limit and Max Source Water Temp Alarm Limit.
Alarm lamp output
The UC Open XP has a binary output that can be connected to a local alarm lamp to indicate a problem with loop
flow, the loop pumps, or the source water supply temperature.
If Linkage is inactive, the alarm output is activated whenever the source water supply temperature exceeds the
configured Maximum Source Water Temp or drops below the configured Minimum Source Water Temp. It will
also be activated whenever the pumps are commanded to operate and loop flow is not detected or if any pump
fails.
If Linkage is active, the alarm output is activated using the same criteria as above, except the source water supply
temperature is compared to the minimum and maximum allowable source water temperature limits received from
the Open WSHPs through Linkage, rather than the configured values.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 33 All rights reserved
If you have problems mounting, wiring, or addressing the UC Open XP or the UC Open XP IO, contact Carrier
Control Systems Support.
NOTE To help you troubleshoot, obtain a Module Status (Modstat) from the controller and review the System Error
and Warning details.
UC Open XP LED's
The LEDs indicate if the controller is speaking to the devices on the network. The LEDs should reflect
communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs become.
Verify the LED patterns by cycling power to the controller and noting the lights and flashes.
LEDs Status
Power Lights when power is being supplied to the controller.
NOTE The UC Open XP is protected by internal solid state Polyswitches on the incoming power and
network connections. These Polyswitches are not replaceable, but they will reset themselves if the
condition that caused the fault returns to normal.
Rx Lights when the controller receives data from the network segment; there is an Rx LED for Ports 1
and 2.
Tx Lights when the controller transmits data from the network segment; there is an Rx LED for Ports 1
and 2.
Run Lights based on controller health.
Error Lights based on controller health.
The Run and Error LED's indicate controller and network status.
If Run LED shows... And Error LED shows... Status is...
1 flash per second 1 flash per second, alternating
with the Run LED
The controller files are archiving. Archive is
complete when Error LED stops flashing.
2 flashes per second Off Normal
2 flashes per second 2 flashes,
alternating with Run LED
Five minute auto-restart delay after system error
2 flashes per second 3 flashes,
then off
The controller has just been formatted
2 flashes per second 4 flashes, then pause Two or more devices on this network have the
same network address
2 flashes per second 1 flash per second The controller is alone on the network
Troubleshooting
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 34 All rights reserved
If Run LED shows... And Error LED shows... Status is...
2 flashes per second On Exec halted after frequent system errors, due to:
Controller halted
Program memory corrupted
One or more programs stopped
5 flashes per second On Exec start-up aborted, Boot is running
5 flashes per second Off Firmware transfer in progress, Boot is running
7 flashes per second 7 flashes per second,
alternating with Run LED
Ten second recovery period after brownout
14 flashes per second 14 flashes per second,
alternating with Run LED
Brownout
On On Failure. Try the following solutions:
Turn the UC Open XP off, then on.
Download memory to the UC Open XP.
Replace the UC Open XP.
NOTE If you resolve the issue but the Error LED does not turn off, cycle power to the controller.
Expander LED's
The LEDs indicate if the controller is speaking to the devices on the network. The LEDs should reflect
communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs become.
LEDs Status
Power Lights when power is being supplied to the controller.
NOTE The UC Open XP is protected by internal solid state Polyswitches on the
incoming power and network connections. These Polyswitches are not replaceable
and will reset themselves if the condition that caused the fault returns to normal.
Rx Lights when the controller receives data from the network segment; there is an Rx
LED for Ports 1 and 2.
Tx Lights when the controller transmits data from the network segment; there is an Rx
LED for Ports 1 and 2.
Run Lights based on controller health. See table below.
Error Lights based on controller health. See table below.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 35 All rights reserved
The Run and Error LED's indicate expander and network status.
If Run LED shows... And Error LED shows... Status is..
2 flashes per second Off Normal
5 flashes per second 2 flashes per second Boot is running or driver is updating
5 flashes per second On Fatal error. Replace expander or return
for repair.
To get the serial number
If you need the UC Open XP's serial number when troubleshooting, the number is on:
A laser-etched number and QR code on the inside circuit board
a sticker on the back of the main controller board (prior to 2019)
a Module Status report (Modstat) under Core (or Main) board hardware
To obtain a modstat in the i-Vu interface:
1 Select the UC Open XP in the navigation tree.
2 Right-click and select Module Status.
To restore defaults
WARNING This erases all archived information and user-configuration settings. You will have to reconfigure
all custom settings. It is recommended to restore the factory defaults only under the guidance of Carrier Control
Systems Support.
To erase volatile memory data and restore factory default configuration settings:
1 Turn off the UC Open XP's power switch.
2 Put the Factory Defaults jumper on.
3 Turn on the UC Open XP's power switch.
4 Remove the Factory Defaults jumper.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 36 All rights reserved
To replace the UC Open XP's battery
To determine when to replace the battery, remove power and measure the voltage. If the voltage is below 2.9
volts, you need to replace the battery.
CAUTION Power must be ON to the UC Open XP when replacing the battery, or your date, time, and trend
data will be lost.
1 Remove the battery from the controller, making note of the battery's polarity.
2 Insert the new battery, matching the battery's polarity with the polarity indicated on the UC Open XP.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 37 All rights reserved
FCC Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense.
CAUTION Changes or modifications not expressly approved by the responsible party for compliance could
void the users authority to operate the equipment.
CE Compliance
WARNING This is a Class A product. In a domestic environment, this product may cause radio interference
in which case the user may be required to take adequate measures.
BACnet Compliance
Compliance of listed products to requirements of ASHRAE Standard 135 is the responsibility of BACnet
International. BTL is a registered trademark of BACnet International.
Compliance
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 38 All rights reserved
These wire lists represent all the possible points for this application. The points that are actually used in your
application depend on the equipment options you select in EquipmentBuilder.
UC Open XP wire list
Open System Network
UC Open XP Universal Controller
Project Name:
Location:
Controller:
Network Number:
MAC Address:
Aux
power
1 5V Jumper right 2
1 24V Jumper left 2
2 GND
Point/
Cable#
Inputs
(+)
(G) Input
Type
Jumper
Position
of Pins
I/O Sensor
code
Equipment
Name
Point
Name
3 5 0-10 Upper UI-1
3 5 Pulse/Other Middle
3 5 4-20 Lower
4 5 0-10 Upper UI-2
4 5 Pulse/Other Middle
4 5 4-20 Lower
6 8 0-10 Upper UI-3
6 8 Other Middle
6 8 4-20 Lower
7 8 0-10 Upper UI-4
7 8 Other Middle
7 8 4-20 Lower
9 11 0-10 Upper UI-5
9 11 Other Middle
9 11 4-20 Lower
10 11 0-10 Upper UI-6
10 11 Other Middle
10 11 4-20 Lower
12 14 0-10 Upper UI-7
12 14 Other Middle
12 14 4-20 Lower
13 14 0-10 Upper UI-8
13 14 Other Middle
Appendix A: UC Open XP and UC Open XP IO wire lists
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 39 All rights reserved
13 14 4-20 Lower
15 17 0-10 Upper UI-9
15 17 Other Middle
15 17 4-20 Lower
16 17 0-10 Upper UI-10
16 17 Other Middle
16 17 4-20 Lower
18 20 0-10 Upper UI-11
18 20 Other Middle
18 20 4-20 Lower
19 20 0-10 Upper UI-12
19 20 Other Middle
19 20 4-20 Lower
Point/
Cable#
Analog
Outs
(+)
(G) A-Output
Type
Jumper Position
of Pins
I/O Sensor
code
Equipment
Name
Point
Name
1 2 mA Left 2 pins AO-1
Volt Right 2 pins
3 4 mA Left 2 pins AO-2
Volt Right 2 pins
5 6 0-10 N/A AO-3
7 8 0-10 N/A AO-4
9 10 0-10 N/A AO-5
11 12 0-10 N/A AO-6
Point/
Cable#
Binary
Outs
(+)
(G) B-Output
Type
Jumper Position
of Pins
I/O Sensor
code
Equipment
Name
Point
Name
1 2 N.C. N/A
BO-1
3 2 N.O.
4 5 N.C. N/A BO-2
6 5 N.O.
7 8 N.C. N/A BO-3
9 8 N.O.
10 11 N.C. N/A BO-4
12 11 N.O.
13 14 N.C. N/A BO-5
15 14 N.O.
16 17 N.C. N/A BO-6
18 17 N.O.
NOTE Only UI-1 and UI-2 have Pulse Count Ability (meter).
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 40 All rights reserved
UC Open XP IO wire list
Open System Network
UC Open XP IO Universal Controller Expander
Project Name:
Location:
Controller:
Network Number:
MAC Address:
Point/
Cable#
Inputs
(+)
(G) Input
Type
Jumper
Position
of Pins
Sensor
code
Equipment
Name
Point
Name
1 2 BI BI-1
3 4 BI BI-2
5 6 BI BI-3
7 8 BI BI-4
9 10 BI BI-5
11 12 BI BI-6
13 14 BI BI-7
15 16 BI BI-8
1 2 0-5V No Jumper UI-9
1 2 Therm/Dry
Contact Jumper
3 4 0-5V No Jumper UI-10
3 4 Therm/Dry
Contact Jumper
5 6 0-5V No Jumper UI-11
5 6 Therm/Dry
Contact Jumper
7 8 0-5V No Jumper UI-12
7 8 Therm/Dry
Contact Jumper
9 10 0-5V No Jumper UI-13
9 10 Therm/Dry
Contact Jumper
11 12 0-5V No Jumper UI-14
11 12 Therm/Dry
Contact Jumper
13 14 0-5V No Jumper UI-15
13 14 Therm/Dry
Contact Jumper
15 16 0-5V No Jumper UI-16
15 16 Therm/Dry
Contact Jumper
Point/
Cable#
Binary
Outs
(+)
(G) B-Output
Type
Jumper
Position
of Pins
Sensor
code
Equipment
Name
Point
Name
1 2 N.O. N/A BO-1
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 41 All rights reserved
3 4 N.O N/A BO-2
5 6 N.O. N/A BO-3
7 8 N.O. N/A BO-4
9 10 N.O. N/A BO-5
11 12 N.O. N/A BO-6
13 14 N.O. N/A BO-7
15 16 N.O. N/A BO-8
NOTE All inputs can be pulse inputs.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 42 All rights reserved
The following tables describe all of the possible settings for your controller on the i-Vu or Field Assistant Properties tab.
See Loop Control Points/Properties on the Equipment Touch for the points and properties available on the Equipment
Touch interface.
Status
Navigation: i-Vu / Field Assistant: Properties > Control Program > Status
Point Name/Description Range
Run Status The current operational status of the loop control system. R: Off/Running
Source Water Supply Temp The water temperature being supplied to the WSHPs. R: -56 to 245F
Source Water Return Temp The water temperature returning from the WSHPs. R: -56 to 245F
Pump 1 Operation Status Pump 1's status. R: Off - OK to Run
On as Lead
Waiting in Standby
On as Replacement
Running as Lag
Failed
Pump 1 VFD Speed The current commanded speed of the VFD. R: 0 to 100%
Pump 2 Operation Status Pump 2's status. R: Off - OK to Run
On as Lead
Waiting in Standby
On as Replacement
Running as Lag
Failed
Pump 2 VFD Speed The current commanded speed of the VFD. R: 0 to 100%
Delta Pressure The differential pressure between the supply and return source water. R: -45 to 145 psi
Bypass Valve Percent The percent the bypass value is open or closed. R: 0 to 100%
Boiler Output 1 The Boiler Output 1 analog output's current commanded state. R: 0 to 100%
Boiler Output 2 The Boiler Output 2 analog output's current commanded state. R: 0 to 100%
Tower Output 1 The Tower Output 1 analog output's current commanded state. R: 0 to 100%
Tower Output 2 The Tower Output 2 analog output's current commanded state. R: 0 to 100%
Loop Optimization The status of the Loop Optimization routine. R: Disabled/Enabled
Current Tower Setpoint The current tower setpoint. R: 40 to 120F
Current Loop Setpoint The current loop setpoint. R: 40 to 120F
Appendix B: Loop Control Points/Properties
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 43 All rights reserved
Point Name/Description Range
Current Boiler Setpoint The current boiler's setpoint. R: 45 to 140F
Outdoor Air Temperature The outdoor air temperature used for control. R: -56 to 245F
OA Relative Humidity The outdoor air relative humidity sensor's current value. R: 0 to 100%
Wet Bulb Temperature The calculated wet bulb's current value. R: -56 to 245F
Shutdown When Active, provides a means to stop heating and cooling in an orderly
manner. All alarms are reset and current active alarms are displayed.
R: Inactive/Active
Unit Configuration
Navigation: i-Vu / Field Assistant: Properties > Control Program > Configuration > Unit Configuration
Point Name/Description Range
On Off Auto HOA switch
Auto The pumps cycle on and off based on demand or occupancy
Locked Unit is locked on or off
D:
R:
Auto
Auto
Locked (ON/OFF)
Pump Start Enables or disables the pumps based on demand only or on occupancy-
or-demand.
D:
R:
Demand Only
Demand Only
Occ or Demand
Minimum Heat Pump Demand Number of requests required to start the loop pumps
when the pumps are being controlled by heat pump demand.
D:
R:
0
0 - 100
Power Fail Restart Delay How long the controller delays normal operation after the
power is restored. Typically used to prevent excessive demand when recovering from a
power failure.
D:
R:
60 seconds
0 to 600 seconds
Pump Stop Delay How long the pump continues to run after the application no longer
requires pump operation.
D:
R:
15 minutes
0 to 9999 minutes
Occupancy Schedules If enabled, the unit follows the occupancy schedule as
configured.
D:
R:
Disable
Disable/Enable
Rotation Method
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 44 All rights reserved
Point Name/Description Range
Rotation Method
Daily Rotates the pumps daily at a specified time.
Weekly Rotates the pumps weekly on a specified day and time.
Monthly Rotates the pumps monthly on a specified day and time.
Manual Rotation Manually rotates the pumps when the operator commands it.
Runtime Rotates the pumps after the lead pump reaches a specified number of
runtime hours.
Never Rotate Does not allow the pumps to rotate.
D:
R:
Daily
Daily
Weekly
Monthly
Manual Rotation
Runtime
Never Rotate
Rotation Method Parameters Specify further details of the selected method.
Method Enter...
Daily time of the day to rotate the lead pump
NOTE Enter the time of day in Defined
Time for Rotation. The time of day you
specify is used during a weekly or monthly
rotation.
D:
R:
13:00
00:00 to 23:59
Weekly day of the week to rotate the lead pump
performed at the time of day specified in
Defined Time for Rotation
D:
R:
3 (Wednesday)
1 to 7 (Monday to Sunday)
Monthly day of the month to rotate the lead pump
performed at the time of day specified in
Defined Time for Rotation
D:
R:
1
1 to 31
Manual
Rotation
manually rotate the lead pump D:
R:
Do not Rotate
Rotate
Do Not Rotate
Runtime number of runtime hours before rotating
the lead pump
D:
R:
360 hrs
24 - 9999 hrs
Runtime since last rotation:
- Pump 1
- Pump 2
R:
R:
0 - 360 hrs
0 - 360 hrs
Defined Time for Rotation Specify the time of day (24 hour format) for automatic
rotation based on the method and schedule you selected.
(Not applicable to Runtime Equalization.)
D:
R:
13:00
00:01 to 23:99
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 45 All rights reserved
Setpoints
Navigation: i-Vu / Field Assistant: Properties > Control Program > Configuration > Setpoints
Point Name/Description Range
Maximum Source Water Temp Setpoint The maximum allowable source water
temperature. This is the upper limit setpoint when Linkage is not active.
D:
R:
90F
55 to 115F
Max Source Water Temp Alarm Limit The source water temperature must exceed this
value to generate a High Source Water Temperature alarm. This is the lower limit
setpoint when Linkage is not active.
D:
R:
125F
75 to 140F
Minimum Source Water Temp Setpoint The minimum allowable source water
temperature.
D:
R:
60F
20 to 70F
Min Source Water Temp Alarm Limit The source water temperature must be lower
than this value to generate a Low Source Water Temperature alarm.
D:
R:
40F
15 to 70F
Tower Approach The temperature in degrees above the outdoor air's wet bulb
temperature that is used to limit the lowest loop setpoint, when Loop Optimization is
active.
D:
R:
12F
5 to 25F
Source Loop Diff Press. Setpoint The differential pressure setpoint maintained by the
loop system.
D:
R:
15 psi
5 to 50 psi
Lag Pump Enables lag pump if PID control output is greater than XX%, hyst X%. D:
R:
90%, 25%
50 to 99%
5 to 75%
Lag Boiler Enables lag boiler if PID control output is greater than XX%, hyst X%. D:
R:
99%, 50%
50 to 99%
5 to 75%
Lag Tower Enables lag tower if PID control output is greater than XX%, hyst XX. D:
R:
71%, 21%
50 to 99%
5 to 50%
Loop Setpoint Optimization*
Enable Loop Optimization Determines if loop optimization is enabled or disabled. D:
R:
Enable
Disable/Enable
Loop Calculation Type You can choose between 15 Day Average (generally a better
choice for larger buildings which are less subject to weather changes) and a Daily
Average.
D:
R:
15 day Average
15 day Average
Daily
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 46 All rights reserved
Point Name/Description Range
Loop Calculation When using the 15 day rolling average loop calculation type
(described above), the:
Weighted Average - weights the actual number of heat pumps in heating or cooling mode every day when
calculating the average setpoint
Equally Weighted - gives equal weight to the daily averages (percentage of heat pumps in heating or cooling
mode) when calculating the average setpoint
D:
R:
Weighted Average
Weighted Average
Equally Weighted
Loop Differential The difference between the heating (boiler) and cooling (tower)
setpoints.
D:
R:
10F
5 to 50F
* Loop Optimization requires Linkage to Carrier Open WSHPs.
Alarm Configuration
Navigation: i-Vu / Field Assistant: Properties > Control Program > Configuration > Alarm Configuration
Point Name/Description Range
Differential Pressure Alarm Hysteresis The value that the differential pressure must
change from the alarm setpoint to release a High or Low Differential Pressure Alarm.
D:
R:
5 psi
2 to 25 psi
Pump 1 Status Alarm(s) Generates a Pump Fail Alarm if the feedback status of
pump 1 has not turned on after it has been enabled. If the status is on, and the pump
has not been enabled, it will enable the Pump in Hand Alarm.
D:
R:
30 seconds
0 to 9999 seconds
Pump 1 Runtime Alarm The value that the runtime must exceed to generate a
Runtime Alarm.
D:
R:
10000 hr
0 to 99999 hr
Pump 2 Status Alarm(s) Generates a Pump Fail Alarm if the feedback status of
pump 2 has not turned on after it has been enabled. If the status is on and the pump
has not been enabled, it will enable the Pump in Hand Alarm.
D:
R:
30 seconds
0 to 9999 seconds
Pump 2 Runtime Alarm The value that the runtime must exceed to generate a
Runtime Alarm.
D:
R:
10000 hr
0 to 99999 hr
Pump Lockout on Catastrophic Loss of Water
Main Loop Flow Status Alarm(s) Generates a Main Loop Flow Status Alarm if the
feedback status of loop pumps has not turned on after it has been enabled.
D:
R:
180 seconds
0 to 9999 seconds
Catastrophic Pump Lockout Shows status of pumps. R: OK
Locked Out
Disable pumps should the loop lose main CW Flow Disables all pumps if there is no
flow. Bypasses any lead/standby routines. You must manually reset the system.
D:
R:
No
No/Yes
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 47 All rights reserved
Service Configuration
Navigation: i-Vu / Field Assistant: Properties > Control Program > Configuration > Service Configuration
Point Name/Description Range
Number Of Pumps The number of pumps in the system. D:
R:
One
One
Two
Pump Status Type The type of status that the pumps deliver to the loop controller to
indicate they are on.
D:
R:
Switch
Switch
Amperage
Network
None
Pump Control This is the type of pump/water loop system being controlled.
Constant Volume Turns the pump on and leaves it on until scheduled to turn off
or the demand has been satisfied.
Constant Vol w/Bypass Turns the pump on and then maintains a differential
pressure with the bypass valve.
Vfd Turns the pump on and maintains a differential pressure by modulating the
speed of the Vfd.
D:
R:
Constant Volume
Constant Volume
Constant Vol w/Bypass
Vfd
Pump Staging If there are 2 pumps controlled by a Vfd, this setting is adjustable. For
other combinations, it defaults to Lead/Standby.
It determines the type of pump sequencing.
Lead/Standby - One pump runs as the lead pump and the other pump waits in
standby.
Lead/Lag One pump runs as the lead pump and, if the additional capacity is
required, brings the second pump on as the lag pump. (Only available if Pump
Control is set to Vfd.)
D:
R:
Lead/Standby
Lead/Standby
Lead/Lag
Cooling Type The cooling tower /_fan control configuration. D:
R:
Modulating
Modulating
1 - Stage
2 - Stage
3 - Stage
4 - Stage
Heat Type The boiler output control configuration. D:
R:
Modulating
Modulating
1 - Stage
2 - Stage
3 - Stage
4 - Stage
Sump Level Control Enable or disable sump level control. D:
R:
Disable
Disable/Enable
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 48 All rights reserved
Point Name/Description Range
Remote Contact Unocc Logic State Sets the remote contact's normal logic state. D:
R:
Open
Open/Closed
Flow Type Sets the Source Water Flow switch's flow type. When set to Normal, the
flow switch contact closes when water flow is detected.
D:
R:
Normal
Normal
Inverted
Outdoor Air Sensor Type The location of the source of the OAT input value. D:
R:
Local OAT Sensor
None
Local OAT Sensor
Network OAT
Outdoor Air Temp Calibration A calibration offset value allows the local outdoor air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
D:
R:
0.00
-9.9 to 10F
Outdoor Air Temperature The outdoor air temperature value being used for control. R: -56 to 245F
OA Relative Humidity Sensor Type - The location of the source of the Outdoor Air
Relative Humidity input value.
D:
R:
Local RH Sensor
None
Local RH Sensor
Network RH
OA Relative Humidity Calibration A calibration offset value allows the local relative
humidity sensor to be adjusted to match a calibrated standard measuring the space
relative humidity in the same location.
D:
R:
0%rh
-15 to 15%rh
OA Relative Humidity The current value of the local relative humidity sensor. R: 0 to 100%rh
Differential Pressure Sensor Type The location of the source of the differential
pressure input value.
D:
R:
Local DP Sensor
Local DP Sensor
Network DP
Pump 1 Trip Point Determines when Pump 1 is on.
Configuration > Service Configuration > Pump Status Type must be set to Amperage.
D:
R:
3.00 A
0 to 9999.00 A
Pump 2 Trip Point Determines when Pump 2 is on.
Configuration > Service Configuration > Pump Status Type must be set to Amperage.
D:
R:
3.00 A
0 to 9999.00 A
System Outdoor Air Temperature Allows the controller to use an outdoor air
temperature value from the network. The remote controller must have a network-
accessible outdoor air temperature sensor value.
R: N/A
System Outdoor Air RH Allows the controller to use an outdoor air relative humidity
value from the network. The remote controller must have a network-accessible OA
relative humidity sensor value.
R: N/A
Source Water Diff. Pressure Allows using another controller's differential pressure
sensor from the network. The remote controller must have a network-accessible
differential pressure sensor value.
R: N/A
System Occupancy Allows reading and using another controller's occupancy status
value over the network. The remote controller must have a network-accessible
Occupancy Status point.
R: Unoccupied/Occupied
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 49 All rights reserved
Point Name/Description Range
Network Flow Input Allows using another controller's flow sensor value over the
network. The remote controller must have a network-accessible flow sensor value.
R: No Flow/Flow
SW Pump 1 Network Status Allows the ability to get SW Pump 1 status over the
network. The remote point must be a network-accessible value.
R: Off/On
SW Pump 2 Network Status Allows the ability to get SW Pump 2 status over the
network. The remote point must be network-accessible.
R: Off/On
Pump1 Network S/S Allows starting Pump 1 over the network. The remote Start/Stop
point must be network-accessible.
R: Off/On
Pump2 Network S/S Allows starting Pump 2 over the network. The remote Start/Stop
point must be network-accessible.
R: Off/On
Pump 1 VFD Network Output Allows managing the Pump 1 VFD speed over the
network. The remote device must have a network-accessible VFD control point.
R: 0 to 100%
Pump 2 VFD Network Output Allows managing the Pump 2 VFD speed over the
network. The remote device must have a network-accessible VFD control point.
R: 0 to 100%
CHW Byp Vlv Network Output Allows managing the bypass valve position over the
network. The remote device must have a network-accessible Bypass Valve control point.
R: 0 to 100%
Boiler Output 1 Allows managing the Boiler 1 output over the network. The remote
point must be network-accessible.
R: 0 to 100%
Boiler Output 2 Allows managing the Boiler 2 output over the network. The remote
point must be network-accessible.
R: 0 to 100%
Tower Output 1 Allows managing the Tower 1 output over the network. The remote
point must be network-accessible.
R: 0 to 100%
Tower Output 2 Allows managing the Tower 2 output over the network. The remote
point must be network-accessible.
R: 0 to 100%
Lockout
Lockout If disabled, allows pumps to continue to cycle until either pump status is
attained. If enabled it will lockout out the pumps after they have failed 3 (default value)
consecutive times
D:
R:
Disabled
Disabled/Enabled
Lock out both pumps if both have failed "#" consecutive times. - Set the number of
pump failures.
D:
R:
3
1 to 5
Manually release lockout? If the pump lockout is enabled and the pumps are locked
out, you can manually release the lockout.
D:
R:
Off
Off/Release
Pump Control
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 50 All rights reserved
Lockout
Loop Bypass Valve VFD PID (BPID) This Bacnet Object determines what the variable
frequency drive output should be.
NOTE The following default values should be changed only by a technician trained in PID
Loop algorithms
Action reverse
Update Interval 1:00 (mm:ss)
Proportional 10
Integral 2.0
Derivative 0
Deadband 0
Bias 30
Bypass Valve Type Defines the normal position of the Bypass valve with no signal. D:
R:
Normally Closed
Normally Closed
Normally Open
VFD PID (BPID) This Bacnet Object determines what the variable frequency drive target
output should be.
NOTE The following default values should be changed only by a technician trained in PID
Loop algorithms
Action reverse
Update Interval 1:00 (mm:ss)
Proportional 10
Integral 5.0
Derivative 0
Deadband 0
Bias 30
Minimum VFD Output The minimum output signal the control supplies to the VFD as a
percentage of its range. The balancer can set this to adjust the units minimum flow.
D:
R:
20%
10 to 50%
The following values for Boiler Control are factory defaults or typical values.
Boiler Control
Enable Boiler if Source Water Temp xx deg < Minimum Source Temp Setpoint xx deg + __
deg,
D:
R:
5 deg
2 to 15F
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 51 All rights reserved
Lockout
hysterisis __. Unless Loop Optimization is enabled. D:
R:
3 deg
1 to 10F
Boiler Setpoint is ___ deg. D:
R:
60F
40 to 80F
Heat stage 1 is __.
R:
On/Off
Heating Stage 1:
Enable Heating Stage 1 if Heating output > _.__%.
NOTE This value is automatically calculated based on number of stages configured.
R: 20 to 50%
hysterisis __. D: 10%
Min heating stage #1 on time is _:__ (mm:ss) R: 3:00 mm:ss
Min heating stage #1 off time is _:__ (mm:ss) D: 0:00 mm:ss
Once disabled, delay Heating Stage 1 for _:__ (mm:ss) after Heating Stage 2 is off. D: 2:00 mm:ss
Heat stage 2 is __.
R:
On/Off
Heating Stage 2:
Enable Heating Stage 2 _:__ (mm:ss) after Heating Stage 1 is enabled D: 5:00 mm:ss
and if Heating output >__._%.
NOTE This value is automatically calculated if number of stages configured > 1.
R: 40 to 66%
hysterisis __. D: 20%
Min heating stage #2 on time is _:__ (mm:ss) D: 3:00 mm:ss
Min heating stage #2 off time is _:__ (mm:ss) D: 0:00 mm:ss
Once disabled, delay Heating Stage 2 for _:__ (mm:ss) after Heating Stage 3 is off. D: 2:00 mm:ss
Heat stage 3 is __.
R:
On/Off
Heating Stage 3:
Enable Heating Stage 3 _:__ (mm:ss) after Heating Stage 2 is enabled D: 5:00 mm:ss
and if Heating output > __%,
NOTE This value is automatically calculated if number of stages configured > 2.
R: 60 to 75%
hysterisis __% D: 20%
Min heating stage #3 on time is _:__ (mm:ss) D: 3:00 mm:ss
Min heating stage #3 off time is _:__ (mm:ss) D: 0:00 mm:ss
Once disabled, delay Heating Stage 3 for _:__ (mm:ss) after Heating Stage 4 is off. D: 2:00 mm:ss
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 52 All rights reserved
Lockout
Heat stage 4 is __.
R:
On/Off
Heating Stage 4:
Enable Heating Stage 4 _:__ (mm:ss) after Heating Stage 3 is enabled and D: 5:00 mm:ss
if Heating output > __%,
NOTE This value is automatically calculated if the number of stages configured > 3.
D: 80%
hysterisis __. D: 20%
Min heating stage #4 on time is _:__ (mm:ss) D: 3:00 mm:ss
Min heating stage #4 off time is _:__ (mm:ss) D: 0:00 mm:ss
The following values for Tower Control are factory defaults or typical values.
Tower Control
Enable Tower if Source Water Temp xx deg > Minimum Source Temp Setpoint xx deg - __
deg,
D:
R:
5 deg
2 to 15F
hysterisis __. Unless Loop Optimization is enabled. D:
R:
3 deg
1 to 10F
Tower setpoint is __ deg. D:
R:
90F
75 to 110F
Cooling Stage 1 is __.
R:
On/Off
Cooling Stage 1:
Enable Cooling Stage 1 if Cooling output > __%
NOTE This value is automatically calculated based on number of stages configured.
R: 20 to 50%
hysterisis __. D: 10%
Once disabled, delay Cooling Stage 1 for _:__ mm:ss after Cooling Stage 2 is off. D: 5:00 mm:ss
Cooling Stage 2 is __.
R:
On/Off
Cooling Stage 2:
Enable Cooling Stage 2 _:__ mm:ss D: 5:00 mm:ss
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 53 All rights reserved
Lockout
after Cooling Stage 1 is enabled and if Cooling output > __.__%,
NOTE This value is automatically calculated if number of stages configured > 1.
R: 40 to 66%
hysterisis __. D: 20%
Once disabled, delay Cooling Stage 2 for _:__ mm:ss after Cooling Stage 3 is off. D: 5:00 mm:ss
Cooling Stage 3 is __.
R:
On/Off
Cooling Stage 3:
Enable Cooling Stage 3 _:__ mm:ss D: 5:00 mm:ss
after Cooling Stage 2 is enabled and if Cooling output > __.__%,
NOTE This value is automatically calculated if number of stages configured > 2.
R: 60 to 75%
hysterisis __. D: 20%
Once disabled, delay Cooling Stage 3 for _:__ mm:ss after Cooling Stage 4 is off. D: 5:00 mm:ss
Cooling Stage 4 is __.
R:
On/Off
Cooling Stage 4:
Enable Cooling Stage 4 _:__ mm:ss D: 5:00 mm:ss
after Cooling Stage 3 is enabled and if Cooling output > __.__%,
NOTE This value is automatically calculated if number of stages configured > 3.
D: 80%
hysterisis __. D: 20%
Low Sump Water Level:
Open makeup valve if switch is On for _:__ mm:ss. D: 0:05 mm:ss
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 54 All rights reserved
Maintenance
Navigation: i-Vu / Field Assistant: Properties > Control Program > Maintenance
Point Name/Description Default/Range
Unit
Source Water Pump 1 Status Pump 1's status. R: On/Off
Source Water Pump 2 Status Pump 2's status. R: On/Off
Source Water Pump 1 Amps The amps from pump 1. R: 0.1 to 10 A
Source Water Pump 2 Amps The amps from pump 2. R: 0.1 to 10 A
WSHP Loop Conditions Loop conditions are OK to run or Not OK to run, based on
condenser water flow and temperature status.
R: OK to run
Not OK
Outdoor Air Temperature
Outdoor Air Temperature Source The source of the OAT value.
States:
N/A No sensor value associated with this device
Local A physical sensor is wired and connected to the appropriate input channel
of this controller
Network A network sensor value provided to this controller
Linkage The sensor value from an active Linkage connection, such as Airside
Linkage.
Locked Value The controller's sensor input is manually locked to a specific value
R: N/A
Local
Network
Linkage
Locked Value
System Outdoor Air Temperature Allows the outdoor air temperature value to be
received when enabled.
D:
R:
-999.00F
N/A
Outdoor Air Temp Displays the outdoor air temperature value from your designated
source.
R: -56 to 245F
Outdoor Air Relative Humidity
OA Relative Humidity Source The source of the outdoor air relative humidity value.
States:
N/A - No sensor value associated with this device
Local - A physical sensor is wired and connected to the appropriate input channel of
this controller
Network - A network sensor value provided to this controller
Linkage - The sensor value from a linked device, obtained through air or water
linkage
Locked Value - The controllers sensor input is manually locked to a specific value
R: N/A
Local
Network
Linkage
Locked Value
System Outdoor Air RH Allows the OA relative humidity value to be received from
another Network device when enabled.
D:
R:
-999.00%rh
N/A
OA Relative Humidity The outdoor air relative humidity value used for control. R: 0 to 100%rh
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 55 All rights reserved
Point Name/Description Default/Range
Occupancy
Remote Contact Input The status of the physical Remote Contact BI point. R: Open/Closed
BAS On/Off Determines the controller's occupancy state and can be set over the
network by another device or third party BAS.
Options:
Inactive Occupancy is determined by a configured schedule
Occupied The controller is always in the occupied mode
Unoccupied The controller is always in the unoccupied mode
D:
R:
Inactive
Inactive
Occupied
Unoccupied
System Occupancy The status of the System Occupancy network point. R: Inactive
Occupied
Unoccupied
Occupancy Contact The Remote Occupancy Contact input's current status. R: Inactive
Active Occupied
Schedules The controller's occupancy status based on the local schedule. R: Unoccupied/Occupied
Alarms
Navigation: i-Vu / Field Assistant: Properties > Control Program > Alarms
Point Name/Description Default/Range
Pump 1 in Hand Pump 1's status on, but the commanded state is off. R: Normal/Hand
Pump 1 Fail Pump 1's commanded state is on, but the status is off and has exceeded
the feedback delay timer.
R: Normal/Alarm
Pump 1 Runtime The status of Pump 1's runtime. R: Accumulating
Exceeds Limit
Pump 2 in Hand Pump 2's status is on, but the commanded state is off. R: Normal/Hand
Pump 2 Fail Pump 2's commanded state is on, but the status is off and has exceeded
the feedback delay timer.
R: Normal/Alarm
Pump 2 Runtime The status of Pump 2's runtime. R: Accumulating
Exceeds Limit
Pump 1 and 2 Failed Pump 1 and 2 have been locked out by exceeding the attempts
to start the pumps. You must manually reset them.
R: Normal/Alarm
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 56 All rights reserved
Point Name/Description Default/Range
Leaving Source Water Temp Sensor Status of the leaving source water temperature
sensor.
R: Normal/Alarm
High Source Water Temperature Source water temperature has exceeded the high
limit.
R: Normal/Alarm
Low Source Water Temperature Source water temperature has dropped below the
low limit.
R: Normal/Alarm
No Water Flow Indicates there is no water flow detected in the system. R: Normal/Alarm
High Differential Pressure Differential pressure has exceeded the high limit. R: Normal/Alarm
Low Differential Pressure Differential pressure has dropped below the low limit. R: Normal/Alarm
Outdoor Air Temp Sensor Indicates if the controller is receiving a valid outdoor air
temperature value.
R: Normal/Alarm
OA Relative Humidity Indicates if the controller is receiving a valid outdoor air relative
humidity value.
R: Normal/Alarm
Condenser Water Linkage Indicates if Condenser Water Linkage is not updated from
the Loop controller, after is a 5 minute alarm delay.
NOTE Reset this alarm by re-establishing Linkage and correcting the condition that
caused the Linkage failure, or by momentarily setting the Shutdown point to Active.
R: Normal/Alarm
SUMP_HI The status of the sump high water level switch. R: Normal/Alarm
SUMP_LO The status of the sump low water level switch. R: Normal/Alarm
Linkage
Navigation: i-Vu / Field Assistant: Properties > Control Program > Linkage
Point Name/Description Range
Linkage
Linkage Equip (Collector) Shows the linkage information that is being sent from the
WSHP to the Loop Controller.
D: Application Instance = 1
Number of Providers = 0
Condenser Water Linkage If Active, the controller is part of a linked system. If Not
Active, the controller is a stand-alone device.
R: Not Active/Active
Min Allowable Loop Temperature Used for setpoint optimization, the minimum
allowable loop temperature.
R: 0.0 to 999.0F
Max Allowable Loop Temperature Used for setpoint optimization, the maximum
allowable loop temperature.
R: 0.0 to 999.0F
Water Loop Temp The source water supply temperature of the loop. R: 0.0 to 999.0F
Loop Pump Status The actual state of the source water loop pump(s). R: Off/On
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 57 All rights reserved
Point Name/Description Range
Heat Pumps in Cool Mode The number of WSHP's that are currently calling for cooling
operation.
R: 0 to 999
Heat Pumps in Heat Mode The number of WSHP's that are currently calling for
heating operation.
R: 0 to 999
I/O Points
The values shown on the I/O Points Properties page are the raw values at the I/O objects and may not match values
shown on status displays that are affected by control program logic.
We strongly recommend that you leave these parameters at their defaults. I/O can only be used for the purpose designed
in the equipment control program. Modifying these parameters may result in unpredictable equipment control.
The following Point List table shows the point names, point types, object ID's, and Object names for every input and output
point. The default point addressing is designed to be used with the UC Open XP controller and UC Open XP IO expander.
Navigation: i-Vu / Field Assistant: Properties > I/O Points
Point List
Name Type Channel Input Type Object Name
OAT sensor BAI IN-3 Therm oatsens
Outdoor Air RH Sensor BAI IN-4 0-10 vdc oarh_sensor
Source Return Water Temp BAI IN-2 Therm srwt_sensor
Source Supply Water Temp BAI IN-1 Therm sswt_sensor
Source Water Diff. Pressure BAI IN-5 0-10 vdc src_diff_press
SW Pump 1 Amp Sensor BAI IN-6 0-10 vdc swp1_amp_sensor
SW Pump 1 Status BBI IN-6 Dry Contact sw_p1_status
SW Pump 2 Amp Sensor BAI IN-7 0-10 vdc swp2_amp_sensor
SW Pump 2 Status BBI IN-7 Dry Contact sw_p2_status
High Wtr Level BBI IN-10 Dry Contact high_sump_lvl
Low Wtr Level BBI IN-11 Dry Contact low_sump_lvl
Remote Contact Input BBI IN-8 Dry Contact rem_con
Source Water Flow BBI IN-9 Dry Contact sw_flow
Boiler Output 1 BAO AO-3 boiler_output1
Boiler Output 2 BAO AO-4 boiler_output2
Bypass Valve/Pump 2 VFD Output BAO AO-2 chw_bypass_valve_vfd
Pump 1 VFD Output BAO AO-1 pump1_vfd_output
Tower Output 1 BAO AO-5 tower_output1
Tower Output 2 BAO AO-6 tower_output2
Alarm BBO BO-4 alm
Boiler Output Stage 1 BBO EXP BO-1 m1128
Boiler Output Stage 2 BBO EXP BO-2 m1141
Boiler Output Stage 3 BBO EXP BO-3 m1142
Boiler Output Stage 4 BBO EXP BO-4 m1143
CW Pump1 S/S BBO BO-1 cw_pump1
CW Pump2 S/S BBO BO-2 cw_pump2
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 58 All rights reserved
Point List
Name Type Channel Input Type Object Name
Makeup Valve BBO BO-5 makeup
Tower Output Stage 1 BBO EXP BO-5 m1144
Tower Output Stage 2 BBO EXP BO-6 m1145
Tower Output Stage 3 BBO EXP BO-7 m1146
Tower Output Stage 4 BBO EXP BO-8 m1147
WSHP Comp Command BBO BO-3 wshp_ok
WARNINGS
Do not change the Value, Offset/Polarity, Exp:Num, I/O Type, Sensor/Actuator Type, Min/Max, or Resolution I/O
configuration parameter for the points listed below. Changing these parameters could cause improper control and/or
equipment damage.
Use extreme caution if locking a point as this may also cause improper control and/or equipment damage.
Point Name/Description
Source Supply Water Temp The value of the controller's leaving source supply water
temperature sensor input, prior to configuring Calibration Offset.
R: -56 to 245F
Source Return Water Temp The value of the controller's source return water
temperature sensor input, prior to configuring Calibration Offset.
R: -56 to 245F
OAT Sensor The value of the controller's outdoor air temperature sensor input, prior to
any operator-configured Calibration Offset.
R: -56 to 245F
Outdoor Air RH Sensor The value of the controller's outdoor air relative humidity sensor
input, prior to any operator-configured Calibration Offset.
R: 0 to 100%rh
Source Water Diff. Pressure The current reading of the controller's differential
pressure input.
R: 0 to 10 psi
SW Pump 1 Amp Sensor The current voltage of the controller's pump 1 amp input. R: 10 to 50 Amps
SW Pump 2 Amp Sensor The current voltage of the controller's pump 2 amp input. R: 0 to 5 Volt
SW Pump 1 Status The current state of pump 1's status input. R: Off/On
SW Pump 2 Status The current state of pump 2's status input. R: Off/On
Remote Contact Input The current state of the input connected to the remote contact
input.
R: Off/On
Source Water Flow The current state of the flow input. R: No Flow/Flow
High Wtr Level The current state of the high water level switch's status input. R: Off/On
Low Wtr Level The current state of the low water level switch's status input. R: Off/On
Pump 1 VFD Ouput The current commanded output to the pump 1 VFD. R: 0 to 100%
Bypass Valve / Pump 2 VFD Output The current commanded output to the bypass
valve or Pump 2 VFD.
R: 0 to 100%
Boiler Output 1 The current commanded output to the Boiler Output 1. R: 0 to 100%
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 59 All rights reserved
Boiler Output 2 The current commanded output to the Boiler Output 2. R: 0 to 100%
Tower Output 1 The current commanded output to the Tower Output 1. R: Off/On
Tower Output 2 The current commanded output to the Tower Output 2. R: Off/On
CW Pump1 S/S The current commanded output to start or stop pump 1. R: Off/On
CW Pump2 S/S The current commanded output to start or stop pump 2. R: Off/On
WSHP Comp Command The WSHP Compressor Command is enabled if the loop
controller is running and has flow.
R: Off/On
Alarm If an alarm is present in the loop controller, the alarm output is turned on. R: Normal/Alarm
Makeup Valve The current commanded output to the makeup valve. R: Off/On
Boiler Output Stage 1 The current commanded output to start or stop boiler output 1. R: Off/On
Boiler Output Stage 2 The current commanded output to start or stop boiler output 2. R: Off/On
Boiler Output Stage 3 The current commanded output to start or stop boiler output 3. R: Off/On
Boiler Output Stage 4 The current commanded output to start or stop boiler output 4. R: Off/On
Tower Output Stage 1 The current commanded output to start or stop tower output 1. R: Off/On
Tower Output Stage 2 The current commanded output to start or stop tower output 2. R: Off/On
Tower Output Stage 3 The current commanded output to start or stop tower output 3. R: Off/On
Tower Output Stage 4 The current commanded output to start or stop tower output 4. R: Off/On
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 60 All rights reserved
NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You must enter an integer only.
Navigation screens
Screen Names Display Details
Standby
Not an interactive screen. Touch anywhere to advance to
Home screen.
Screen displays after the Inactivity
Timer expires (default is 5 minutes).
Displays:
Source water supply temperature
Mode - Heating or Cooling
Occupancy
Home
Click on the right to navigate to Snapshot screen.
Displays:
Source water supply temperature
Mode - Heating or Cooling
Occupancy
Appendix C: Loop Control Points/Properties on the Equipment Touch
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 61 All rights reserved
Screen Names Display Details
Snapshot
Back to the Home screen - click on the left
Forward to Loop Control Properties Menu screen - click
on the right
Navigates to:
Equipment alarm indicator
SWS Temp, SWR Temp, Bypass
Valve Status, Loop Diff Pressure,
Boiler Status, and Tower Status, if
applicable
Source pump status
OAT, if available and allowed
Alarms, if present
Navigates to:
Alarm status
Schedules
Trends
Loop Control
Properties
Navigates to Property pages
Login with one of the following
passwords:
User level - type user
Admin level - type admin
Factory level - type Touch
NOTE Only the buttons that are
authorized for a specific password
level are visible.
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 62 All rights reserved
Screen Names Display Details
Show/Hide
Configuration
Configure Show/Hide conditions for
values on the following screens:
Standby
Home
Snapshot
NOTE Only displayed for the Factory
or Admin password. (See above.)
Startup Wizard
Navigation: Equipment Touch: Startup Wizard
Point Name/Description Range
Number Of Pumps The number of pumps in the system. D:
R:
One
One
Two
Pump Status Type The type of status that the pumps deliver to the loop controller to
indicate they are on.
D:
R:
Switch
Switch
Amperage
Network
None
Pump 1 Control Pump control type for single pump system. D:
R:
Constant Volume
Constant Volume
Constant Vol w/Bypass
Single Vfd
Pump 2 Control Pump control type for two-pump system. D:
R:
Constant Volume
Constant Volume
Constant Vol w/Bypass
Single Vfd
Two VFDs
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 63 All rights reserved
Point Name/Description Range
Pump Staging If there are 2 pumps, this type of staging enables or disables the
pumps, based on Demand Only or Occ or Demand (set in Unit Configuration).
Lead/Standby - One pump runs as the lead pump and the other pump waits in
standby.
Lead/Lag One pump runs as the lead pump and, if the pressure is not maintained, brings the second pump on
as the lag pump. (Only available if Pump Control is set to Two VFDs)
D:
R:
Lead/Standby
Lead/Standby
Lead/Lag
Cooling Type The cooling tower /_fan control configuration. D:
R:
Modulating
Modulating
1 - Stage
2 - Stage
3 - Stage
4 - Stage
Heat Type The boiler output control configuration. D:
R:
Modulating
Modulating
1 - Stage
2 - Stage
3 - Stage
4 - Stage
Sump Level Control Enable or disable sump level control. D:
R:
Disable
Disable/Enable
Remote Contact Unocc Logic State Sets the remote contact's normal logic state. D:
R:
Open
Open/Closed
Flow Type Sets the Source Water Flow switch's flow type. When set to Normal, the flow
switch contact closes when water flow is detected.
D:
R:
Normal
Normal
Inverted
Outdoor Air Sensor Type The location of the source of the OAT input value. D:
R:
Local OAT Sensor
None
Local OAT Sensor
Network OAT
Outdoor Air Temp Calibration A calibration offset value allows the outdoor air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
D:
R:
0.00
-9.9 to 10F
OA Relative Humidity Sensor Type - The location of the source of the Outdoor Air Relative
Humidity input value.
D:
R:
Local RH Sensor
None
Local OAT Sensor
Network OAT
Relative Humidity Calibration A calibration offset value allows the local relative
humidity sensor to be adjusted to match a calibrated standard measuring the space
relative humidity in the same location.
D:
R:
0%rh
-15 to 15%rh
Differential Pressure Sensor Type The location of the source of the differential
pressure input value.
D:
R:
Local DP Sensor
Local DP Sensor
Network DP
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 64 All rights reserved
Point Name/Description Range
Pump 1 Trip Point Determines when Pump 1 is on. D:
R:
3.00 A
0 to 9999.00 A
Pump 2 Trip Point Determines when Pump 2 is on. D:
R:
3.00 A
0 to 9999.00 A
Lockout If disabled, allows pumps to continue to cycle until either pump status is
attained. If enabled it will lockout out the pumps after they have failed 3 (default value)
consecutive times
D:
R:
Disabled
Disabled/Enabled
Lock out both pumps if both have failed "#" consecutive times. - Set the number of
pump failures.
D:
R:
3
1 to 5
Manually release lockout? If the pump lockout is enabled and the pumps are locked
out, you can manually release the lockout.
D:
R:
Off
Off/Running
Source Water Loop Control for UC Open XP CARRIER CORPORATION 2021
Installation and Start-up Guide 65 All rights reserved
Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not
listed.
Date Topic Change description Code*
6/16/21 Specifications Reworded Rnet port specification and added power supplied by
Rnet port.
Reworded Protection specification and added first paragraph.
X-H-JS-O
1/25/19 Specifications Added surge CAUTION to Protection specification. X-TS-AK-E-CC
* For internal use only
Document revision history
<
Related manuals for Carrier Aquazone 50PSW Installation Guide
Manualsnet FAQs
If you want to find out how the Aquazone 50PSW Carrier works, you can view and download the Carrier Aquazone 50PSW Installation Guide on the Manualsnet website.
Yes, we have the Installation Guide for Carrier Aquazone 50PSW as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.
The Installation Guide should include all the details that are needed to use a Carrier Aquazone 50PSW. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.
The best way to navigate the Carrier Aquazone 50PSW Installation Guide is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.
This Carrier Aquazone 50PSW Installation Guide consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.
You can download Carrier Aquazone 50PSW Installation Guide free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.
To be able to print Carrier Aquazone 50PSW Installation Guide, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier Aquazone 50PSW Installation Guide as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.