Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53480195-01 Printed in U.S.A. Form 48TC-1SO Rev. A Pg 1 3-2020 Replaces: OG-48TC580J-07

Users Information Manual

NOTE TO INSTALLER This manual should be left with the equipment owner.

SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, mainte- nance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extin- guisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local build- ing codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements. It is important to recognize safety information. This is the safety- alert symbol . When you see this symbol on the unit and in in- structions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.

.

WARNING ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dan- gerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, seri- ous injury, death or property damage. Before servicing, disconnect all electrical power to the

unit. When servicing controls, label all wire prior to discon-

necting. Reconnect wires correctly. Verify proper operation after servicing.

WARNING

If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal in- jury or loss of life. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch; do not use any

phone in your building. Immediately call your gas supplier from a neighbors

phone. Follow the gas suppliers instructions. If you cannot reach your gas supplier, call the fire

department. Installation and service must be performed by a qualified in- staller, service agency or the gas supplier.

AVERTISSEMENT

RISQUE DINCENDIE OU DEXPLOSION Si les consignes de scurit ne sont pas suivies la lettre, cela peut entraner la mort, de graves blessures ou des dommages matriels. Ne pas entreposer ni utiliser dessence ni autres vapeurs ou liq- uides inflammables proximit de cet appareil ou de tout autre appareil. QUE FAIRE SI UNE ODEUR DE GAZ EST DTECTE Ne mettre en marche aucun appareil. Ne toucher aucun interrupteur lectrique; ne pas

utiliser de tlphone dans le btiment. Quitter le btiment immdiatement. Appeler immdiatement le fournisseur de gaz en

utilisant le tlphone dun voisin. Suivre les instructions du fournisseur de gaz.

Si le fournisseur de gaz nest pas accessible, appeler le service dincendie.

Linstallation et lentretien doivent tre effectus par un instal- lateur ou une entreprise dentretien qualifi, ou le fournisseur de gaz.

WARNING

Do not use this furnace if any part has been under water. A flood-damaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. A qualified ser- vice agency should be contacted to inspect the furnace and to replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.

Single-Package Rooftop Gas Heating/Electric Cooling Units

with R-410A Refrigerant 3 to 27.5 Tons

2

Your combination heating/cooling rooftop unit is equipped with an automatic direct spark ignition system and induced-draft power combustion blower.

Your rooftop heating/cooling unit is equipped with an automatic, direct spark ignitor and an induced-draft, combustion blower.

IMPORTANT FACTS DO: READ AND UNDERSTAND THIS MANUAL. DO: Have your equipment and vent system inspected an-

nually by a qualified service technician. DO: Inspect your filter monthly and clean or replace when

needed. DO: Provide adequate airflow to the equipment for effi-

cient combustion and safe ventilation.

AVERTISSEMENT

Ne pas utiliser cet appareil de chauffage sil a t en partie im- merg dans leau. Un appareil de chauffage endommag par une inondation est extrmement dangereux. Sil est utilis, un incendie ou une explosion peut se produire. Il faut avoir re- cours une entreprise dentretien qualifie pour faire in- specter lappareil de chauffage et remplacer toutes les com- mandes de gaz, les pices du systme de contrle, les pices lectriques qui sont entres en contact avec leau ou lappareil de chauffage lui-mme, si cela est jug ncessaire.

WARNING Improper installation, adjustment, alteration, service or main- tenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.

WARNING Before performing recommended maintenance, be sure main power switch to unit is turned off and lockout tag is installed. Electrical shock could cause personal injury.

WARNING Burners will light automatically. Do not attempt to light by hand; personal injury may result.

WARNING

CARBON-MONOXIDE POISONING HAZARD Failure to follow instructions could result in severe personal injury or death due to carbon-monoxide poisoning, if combus- tion products infiltrate into the building. Check that all openings in the outside wall around the vent (and air intake) pipe(s) are sealed to prevent infiltration of combustion products into the building. Check that furnace vent (and air intake) terminal(s) are not ob- structed in any way during all seasons.

AVERTISSEMENT

RISQUE DINTOXICATION AU MONOXYDE DE CARBONE Si ces directives ne sont pas suivies, cela peut entraner des blessures graves ou une intoxication au monoxyde de carbone pouvant causer la mort, si des produits de combustion sinfil- trent dans le btiment. Vrifier que toutes les ouvertures pratiques dans le mur ex- trieur autour du ou des tuyaux dvent (et de la prise dair) sont scelles de manire empcher linfiltration de produits de combustion dans le btiment. Veiller ce que la ou les sorties de lvent de lappareil de chauffage (et la prise dair) ne soient, en aucune faon, ob- strues, quelle que soit la saison.

WARNING

Should overheating occur or the gas supply fail to shut off, shut off the manual gas valve to the unit before shutting off the electrical supply.

AVERTISSEMENT

En cas de temprature excessive, ou sil est impossible de couper lalimentation en gaz, fermer le robinet manuel dali- mentation en gaz du gnrateur dair chaud avant de couper lalimentation lectrique.

WARNING FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Before performing maintenance, be sure main power switch to unit is turned off and lockout tag is installed. There may be more than one power switch.

WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Do not use this equipment is any part has been under water. A flood-damaged equipment is extremely dangerous. Attempts to use the equipment can result in fire or explosion. A qualified service agency should be contacted to inspect the equipment and to replace all gas controls, control system parts, electrical parts that have been wet or the equipment if deemed necessary.

WARNING PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury. Burners will light automatically. Do not attempt to light by hand.

3

DO Make sure: 1. All flue and vent connections are clear and free of

obstructions, are leak free, and not damaged. 2. Duct connections are leak free and physically sound. 3. The unit base support is free of cracks, gaps, etc. 4. There are no signs of furnace deterioration. 5. Burners are aligned correctly. 6. Follow routine maintenance inspection.

DO NOT: Keep combustible materials, gasoline, and other flammable liquids or vapors around your equipment.

DO NOT: Cover your equipment in any manner. DO NOT: Store anything (including trash or debris) near

your equipment. DO NOT: In any way block or restrict airflow around your

equipment. DO NOT: Contaminate the air used for combustion of your

equipment with any kind of chemical or fumes. This could also cause heat exchangers, metal vent systems or compo- nents to deteriorate.

TO LIGHT UNIT

Step 1 Set room thermostat/unit controller to the lowest temperature set- ting and set the SYSTEM switch to HEAT or AUTO position. See Fig. 1.

Fig. 1 Thermostat/Unit Controller

Step 2 Turn off the gas supply by closing the gas supply shut-off valve (external to RTU unit). See Fig. 2 or 3 (depending on the size of the unit) for location and Fig. 4.

Fig. 2 Gas Supply Shut-Off Valve Location 3 to 121/2 Ton Units (Thru-the-base gas supply shown)

Fig. 3 Gas Supply Shut-Off Valve Location 15 to 271/2 Ton Units

Fig. 4 Gas Supply Shut Off Valve

Step 3 Turn off the electrical supply to the unit by switching the RTU main disconnect to OFF. Then, ensure personal safety by installing a lockout tag on the disconnect. See Fig. 5.

Fig. 5 RTU Main Disconnect Electrical Supply

WARNING FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. 1. Do not turn off the electrical power to unit without first

turning off the gas supply. 2. Before attempting to start the gas heating section,

familiarize yourself with all the procedures that must be followed.

3. Never attempt to manually light the burners on the unit with a match, lighter, or any other flame. If the electric sparking device fails to light the burners, refer to the shutdown procedures, then call your dealer as soon as possible.

CAUTION

CUT HAZARD Failure to follow this caution may result in personal injury. When removing access panels or performing maintenance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care has been taken to reduce sharp edges inside the unit, be extremely careful when handling parts or reaching into the unit.

Gas Supply Shut Off Valve (Field Supplied)

Gas Supply Shut Off Valve (Field Supplied)

LOCK-OUT TAG

ON

MAIN

OFF

4

Step 4 Remove the gas component access panel. For location of the gas component access panel, see Fig. 6 or 7 (depending on the size of the unit). See Fig. 8 for panel removal.

Fig. 6 Gas Component Access Panel and RTU Gas Valve Location

Fig. 7 Gas Component Access and Filter Access Panels 15 to 271/2 Ton Units

Fig. 8 Gas Component Access Panel Removal

Step 5 Move the RTU gas valve on/off switch to the OFF position and wait 5 minutes. See Fig. 6 or 7, depending on the type of unit, for location of RTU gas valve. See Fig. 9.

Fig. 9 Single and Two-Stage RTU Gas Valves

Step 6 Move the RTU gas valve on/off switch to the ON position.

Step 7 Replace the gas component access panel. See Fig. 10.

Fig. 10 Replacing the Gas Component Access Panel

Step 8 Remove disconnect lockout tag and restore power to the unit by switching the RTU main disconnect to ON. See Fig. 11.

Fig. 11 RTU Main Disconnect Electrical Supply

Step 9 Turn on the gas supply by opening the gas supply shut-off valve. See Fig. 12.

Fig. 12 Gas Supply Shut Off Valve

Step 10 To start unit, set room thermostat/unit controller heat setpoint to slightly above room temperature. The induced-draft combustion air fan will start. The RTU gas valve will open and main burners should ignite within 5 seconds. If the burners do not light, there is a 22 second delay. Burners will attempt to ignite within 5 seconds. Each time the burner fails to light, the 22 second time delay is re- peated. If the burner does not light within 15 minutes, the unit will lockout the gas heat. To reset after a lockout, turn off the main electrical supply to the unit by switching the RTU main disconnect to OFF for a minimum of five seconds. Repeat Steps 1-10. If burn- ers still do not light, call for service.

Step 11 Set the room thermostat/unit controller heating set point to desired temperature setting. See Fig. 13.

Fig. 13 Thermostat/Unit Controller

RTU GAS VALVE

GAS COMPONENT ACCESS PANEL

FILTER ACCESS PANEL

GAS COMPONENT ACCESS PANEL

Two-Stage RTU gas valve

300k BTU/Hr Two-Stage

RTU gas valve

On/Off Switch

OFF

ON

Single-Stage RTU gas valve

On/Off Switch

ON

MAIN

OFF

5

TO SHUT UNIT OFF

Step 1 Set room thermostat/unit controller heat set point to the lowest temperature setting and set the SYSTEM switch to OFF. See Fig. 14.

Fig. 14 Thermostat/Unit Controller

Step 2 Turn off gas supply by closing the gas supply shutoff valve (exter- nal to RTU unit). See Fig. 2 or 3 (depending on the size of the unit) for location and see Fig. 15.

Fig. 15 Gas Supply Shut Off Valve

Step 3 Turn off the electrical supply to the unit by switching the RTU main disconnect to off. Then, ensure personal safety by installing a lockout tag on the disconnect. See Fig. 16.

Fig. 16 RTU Main Disconnect Electrical Supply

Step 4 Remove the gas component access panel. For location of the gas component access panel, see Fig. 6 or 7 (depending on the size of the unit) and Fig. 17.

Fig. 17 Gas Component Access Panel Removal

Step 5 Move the RTU gas valve on/off switch to the OFF position and wait 5 minutes. See Fig. 18.

Fig. 18 Single and Two-Stage Gas Valves

Step 6 Replace the gas component access panel. See Fig. 19.

Fig. 19 Replacing the Gas Component Access Panel

Step 7 If the unit is being shut down because of a malfunction, contact your dealer as soon as possible. DO NOT proceed to Step 8.

WARNING FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death or property damage. If the main burners fail to light, or the blower fails to come on, shut down gas heating section and call your dealer for service.

WARNING FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death or property damage. 1. Turn off the gas supply by closing the gas line supply

valve. Then, turn off the electrical power supply to the unit by switching the disconnect to off. Install lockout tag before servicing or performing maintenance.

2. Do not turn off the electrical power to unit without first turning off the gas supply.

CAUTION

Ensure clearances are in accordance with local installation codes, the requirements of the gas supplier and the manufac- turer's installation instructions.

ATTENTION

Assurez-vous que les dgagements sont conformes aux codes d'installation locaux, aux exigences du fournisseur de gaz et aux instructions d'installation du fabricant.

LOCK-OUT TAG

ON

MAIN

OFF

Two-Stage RTU gas valve

300k BTU/Hr Two-Stage

RTU gas valve

On/Off Switch

OFF

ON

Single-Stage RTU gas valve

On/Off Switch

6

Step 8 If the unit is being shut down because the heating season has end- ed, remove the disconnect lockout tag and restore electrical power to the unit by switching the RTU main disconnect to ON and then set thermostat/unit controller to the COOL position to ensure oper- ation of the cooling system during the cooling season. See Fig. 20.

Fig. 20 RTU Main Disconnect Electrical Supply

ROUTINE MAINTENANCE AND CARE FOR THE EQUIPMENT OWNER

While some maintenance can be performed by laymen, most should be performed by skilled, experienced personnel. Follow the recommended service maintenance schedule, and modify it as necessary for your application/environment. For instance, dusty areas may require more frequent filter changes. After performing any maintenance or service on the unit, be sure all panels are se- curely fastened in place to prevent rain from entering unit cabinet and to prevent disruption of the correct unit airflow pattern.

To ensure proper functioning of the unit, flow of combustion and ventilating air must not be obstructed from reaching the unit. Fol- low service and performance clearances as listed in the product data. Consider the following information before maintaining or servic- ing equipment:

Compressor All compressors are factory supplied with a normal charge of the correct type refrigeration-grade oil in them and should not require additional oil.

Indoor Air Filter(s)

Indoor air filter(s) should be checked every 3 or 4 weeks (applica- tion dependent) and changed or cleaned when necessary. See Table 1 for replacement filter dimensions. See Fig. 21 or 22 (de- pending on the size of the unit) for air filter access panel location.

Table 1 Replacement Filters Size and Quantity

NOTE: Filter sizes in Table 1 are in inches. Numbers in ( ) denote filter quantity.

ON

MAIN

OFF

WARNING FIRE AND EQUIPMENT DAMAGE HAZARD Failure to follow this warning could result in personal injury and damage to equipment. Never operate unit without filters in place. The accumula- tion of dirt, dust or lint on the internal parts of your unit can cause fire or a loss of efficiency. Damage to the blower motor and/or compressors could also result.

SIZE CAPACITY (tons) 48TC/580J 48HC/581J 48KC/582J 48FC/582K 48GC/581K 48JC

04 3 N/A

16 x 25 x 2 (2) 16 x 25 x 2 (2)

16 x 25 x 2 (2) 16 x 25 x 2 (2)

16 x 16 x 2 (4)05 4 16 x 16 x 2 (4)06 5 16 x 16 x 2 (4) 16 x 16 x 2 (4)

07 6 16 x 16 x 2 (4) 16 x 20 x 2 (4) 16 x 16 x 2 (4) 08 71/2 16 x 20 x 2 (4)

20 x 20 x 2 (4) 09 81/2 20 x 20 x 2 (4) 11 10 12 10

20 x 20 x 2 (4)14 121/2 18 x 24 x 2 (6) 16 15 18 x 24 x 2 (6) 17 15

20 x 25 x 2 (6)

20 x 25 x 2 (6) N/A N/A N/A N/A 18 15 20 171/2 20 x 25 x 2 (6) 21 171/2 24 20 16 x 25 x 2 (9) 25 20

16 x 25 x 2 (9)

28 25 16 x 25 x 2 (9) 29 25

30 271/2

SIZE CAPACITY (tons) RGS Series RGH Series RGX Series RGV Series RGW Series

036 3 N/A

16 x 25 x 2 (2) 16 x 25 x 2 (2)

16 x 25 x 2 (2) 16 x 25 x 2 (2)048 4

16 x 16 x 2 (4)060 5 16 x 16 x 2 (4) 16 x 16 x 2 (4) 072 6 16 x 16 x 2 (4) 16 x 20 x 2 (4) 16 x 16 x 2 (4)

090/091 71/2 16 x 20 x 2 (4)

20 x 20 x 2 (4) 101 81/2

20 x 20 x 2 (4)110/121 10 150 121/2 N/A N/A N/A 210 171/2 20 x 25 x 2 (6)

18 x 24 x 2 (6) 240 20 20 x 25 x 2 (6) 300 25

16 x 25 x 2 (9) 16 x 25 x 2 (9)

336 27

7

Fig. 21 Air Filter Access Panel 3 to 121/2 Ton Units

Fig. 22 Air Filter Access Panel 15 to 271/2 Ton Units

1. Lift up and remove air filter access panel (3 to 121/2 ton units) or remove the screws securing the filter access panel (15 to 271/2 ton units).

2. While holding filters, tilt upper filter rack. 3. Remove filters by pulling up and out toward you from the

track. 4. Inspect filters. Clean or replace as necessary. 5. Follow direction of airflow arrows as noted on filter frame

when returning filters to rack. 6. Reinstall air filter access panel. If you have difficulty in locating your air filter or if you have ques- tions concerning proper filter maintenance, contact your dealer for instructions. When replacing your unit filters, always use the same size and type of filter that was originally supplied by the installer. Units with outdoor air capability have a cleanable filter for the out- door air. This filter should be checked semi-annually and cleaned as necessary with steam or hot water and a mild detergent. Do not use throwaway filters in place of cleanable filters.

Condenser Fan

Electrical Controls and Wiring Ensure wires do not contact refrigerant tubing or sharp edges. Electrical controls are difficult to check without proper instrumen- tation. If inadequate cooling is suspected, contact your qualified local dealer for service.

Combustion Area and Vent System The combustion area and vent system should be visually inspected before each heating season.

Proceed as follows to inspect the combustion area and power- venting system of your unit. 1. Turn off gas supply to your unit. 2. Turn off electrical power to your unit; install lockout tag. 3. Remove gas component access panel. 4. Using a flashlight, carefully inspect the burner areas for dirt,

soot, or scale.

5. When you have completed your inspection, follow the start- up procedures in this manual to restore your unit to operation.

6. Observe unit heating operation. Watch the burner flame to see if it is bright blue. If you observe a suspected malfunction or that the burner flame is not bright blue, shut down the unit and call your dealer.

7. Replace gas component access panel.

Integrated Gas Controller (IGC) The IGC board incorporates an LED that emits a flashing light to indicate an alarm code. If the furnace section will not operate and the LED is flashing a code (1 to 9 flashes in succession), contact your dealer and request service. NOTE: Make note of the flash code before powering off the unit. The alarm codes clear after power cycle.

Unit Panels After performing any maintenance or service on the unit, be sure all panels are securely fastened in place to prevent rain from enter- ing unit cabinet and to prevent disruption of the correct unit air- flow pattern.

WARNING PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury. Do not poke sticks, screwdrivers, or other objects into revolving fan blades.

AIR FILTER ACCESS PANEL

FILTER ACCESS PANEL

GAS COMPONENT ACCESS PANEL

WARNING FIRE HAZARD Failure to follow this warning could result in personal injury and damage to equipment. If your unit makes any unusual or especially loud noises during heating, shut down the heating section and call your qualified service technician.

CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in damage to equip- ment. If dirt, soot, rust or scale accumulations are found, call your service technician and do not operate your heating section.

WARNING PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury. Components in heat section may be hot after unit has started up. When observing flame, be careful not to get close to or touch heating components.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53480195-01 Printed in U.S.A. Form 48TC-1SO Rev. A Pg 8 3-2020 Replaces: OG-48TC580J-07

2019 CAC / BDP

BEFORE YOU CALL FOR SERVICE, CHECK FOR PROBLEMS THAT CAN BE EASILY SOLVED

If insufficient heating or cooling is suspected: ( ) Check for sufficient airflow. Check the air filter for dirt Check for blocked return-air or supply-air grilles. Be sure they are open and unobstructed. If these checks do not reveal the cause, call your servicing dealer. If your unit is not operating at all, check the following list for easy solutions: ( ) Check to be sure that your thermostat/unit controller tem- perature selector is set above the indoor temperature during the heating season, or below the indoor temperature during the cool- ing season. Be sure the SYSTEM switch in the proper HEAT or COOL position and not in the OFF position. ( ) Is the electrical supply switch ON? Are any fuses blown, or has the circuit breaker tripped? ( ) During the heating season, check the external manual shutoff valve. Is this lever parallel with the pipe, indicating that the valve is open? Or is the lever at the right angle, indicating that the valve is closed? If closed, has the gas been shut off for safety reasons? Otherwise, you may open the valve and follow the start-up proce- dures listed in this manual. NOTE: Before proceeding with the next check, turn OFF the elec- trical power supply to the unit. Remove the gas component access panel. ( ) During the heating season, check the control switch on the gas valve. Is it in the ON position? If it is not, be sure it has not been turned off for the purpose of safety. If no safety hazards are present, follow the start-up procedures in this manual. If your unit still fails to operate, call your servicing dealer for trou- bleshooting and repairs. Specify the model and serial numbers of your unit. (Record them in this manual in the space provided.) If the dealer knows exactly which unit you have, he may be able to offer suggestions over the phone, or save valuable time through knowledgeable preparation for the service call.

IN CASE OF TROUBLE If, after performing the above checks, unit performance is unsatis- factory, shut off the unit and call your dealer. Dealers Name ___________________________________ Telephone No. ____________________________________ Unit Model ______________________________________ Unit Serial Number ________________________________

REGULAR DEALER MAINTENANCE

Heat Exchanger NOTE: To ensure dependable and efficient heating operation, the heat exchanger should be checked by a qualified maintenance per- son before each heating season, and cleaned when necessary. AUTION

Checking and/or cleaning the heat exchanger involves removing the gas controls assembly and the flue collector box cover. When finished, the gas controls must be reinstalled for proper operation. Also, the flue collector box cover must be replaced correctly, with red RTV, so that a proper seal is maintained. Contact your dealer for the required periodic maintenance. At the beginning of each cooling/heating season and as conditions require.

Fans and Belts, and Fan Motor Check quarterly the condition of fan wheels and housings, belt tension and fan motor shaft bearings. No lubrication of condenser or evaporator fan bearings or motors is required or recommended.

Evaporator and Condenser Coils Cleaning of the coils should be done by qualified service person- nel. This procedure should be performed prior to cooling opera- tion or more frequently should conditions require. Contact you dealer for the required annual maintenance.

Condensate Drain The drain pan and condensate drain line should be checked and cleaned at the same time the cooling coils are checked by your dealer. In addition to the type of routine maintenance you might be will- ing to perform, your unit should be inspected regularly by a prop- erly trained and qualified service technician. An inspection (pref- erably each heating/cooling season, but at least every year) should include the following: Inspection of all flue product passages, including the burn-

ers, heat exchanger, and flue collector box. Inspection of all combustion and ventilation-air passages

and openings. Close inspection of all gas pipes leading to and inside your

unit. Inspection and if required, cleaning of the condenser and

evaporator coils. Inspection, and if required, cleaning of the condensate

drain pan. Inspection and cleaning of blower wheel housing and motor. Inspection of all supply and return-air ducts for leaks, ob-

structions, and insulation integrity. Any problems found should be resolved at the time of inspection.

Inspection of the unit base for cracks, gaps, etc., which may cause a hazardous condition.

Inspection of the unit casing for signs of deterioration. Inspection of all electrical wiring and components to en-

sure proper connection. Inspection for leaks in the refrigerant circuit. Pressure

check to determine appropriate refrigerant charge. Inspection of fan wheels and housings, belt tension, and

fan motor shaft bearings. Operational check of the unit to determine working condi-

tions. Repair or adjustment should be made at the time of inspection.

Your servicing dealer may offer an economical service contract that covers seasonal inspections. Ask for further details. Complete service instructions can be found in the units Service and Maintenance Instructions.

CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in damage to equip- ment. This checkout should not be attempted by anyone not having the required expertise and equipment to do the job prop

Manualsnet FAQs

If you want to find out how the 48GC Carrier works, you can view and download the Carrier 48GC User's Manual on the Manualsnet website.

Yes, we have the User's Manual for Carrier 48GC as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The User's Manual should include all the details that are needed to use a Carrier 48GC. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier 48GC User's Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier 48GC User's Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier 48GC User's Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier 48GC User's Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier 48GC User's Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.