Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53480046-01 Printed in U.S.A. Form 48A-4SO Pg 1 7-07 Replaces: 48A-2SOBook 1

Tab 1a

Users Information Manual NOTE TO INSTALLER

This manual should be left with the equipment owner.

Your combination heating/cooling unit is equipped with direct spark ignition and induced draft power combustion blower.

TO LIGHT UNIT

See Fig. 1 and 2 for location of gas valve. Refer to Fig. 3 while performing the following steps.

1. Turn off the unit demand for cooling or heating by using the scrolling marquee. The scrolling marquee is located in the control box at the compressor end of the unit. a. Push the ESCAPE key unit a blank display screen

is shown. b. Push the DOWN arrow key until the SERVICE

TEST LED is lit. c. Push the ENTER key. The display will show

STOP. d. Push the ENTER key again. The NO/YES display

will flash. e. Push the UP or DOWN key to toggle the display to

YES and then push ENTER. The unit will be locked off from heat, cooling or any operation. The controls will still function and the display will still operate.

2. Close the field-installed manual gas shutoff valve. 3. Turn off the electrical power to the unit using the optional

disconnect or the field-installed disconnect and lock off using proper lockout and tag-out procedures.

4. Remove the gas section panels. 5. Move the switch on the gas valve to the OFF position and

wait 5 minutes. NOTE: If this is the first installation of the unit, the gas flue hoods must be installed before operating unit. These must be installed for the unit to run properly.

6. Move the switch on the gas valve to the ON position. 7. Replace the gas section access panels. 8. Turn on the electrical supply to the units. 9. Open the field-installed manual gas valve.

WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch;

do not use any phone in your building.

Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions.

If you cannot reach your gas sup- plier, call the fire department.

Installation and service must be per- formed by a qualified installer, service agency or the gas supplier.

Improper installation, adjustment, alteration, ser- vice or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.

Before performing recommended maintenance, be sure main power switch to unit is turned off and lockout tag is installed. Electrical shock could cause personal injury.

Burners will light automatically. Do not attempt to light by hand; personal injury may result.

1. Do not turn off the electrical power to unit without first turning off the gas supply.

2. Before attempting to start the gas heating section, familiarize yourself with all the procedures that must be followed.

3. Never attempt to manually light the burners on the unit with a match, lighter, or any other flame. If the electric sparking device fails to light the burners, refer to the shutdown procedures, then call your dealer as soon as possible.

If you do not follow these instructions exactly, a fire or explosion may result, causing property damage, injury, or loss of life.

48AJ,AK,AW,AY020-060 Single-Package Rooftop Gas Heating Units

with COMFORTLINK Controls and Scroll Compressors

2

Fig. 1 Typical Gas Section Location (48AK020 Shown)

Fig. 2 Typical Gas Valve Location (48AJ,AK,AW,AY020-050 Shown)

3

STEP 1

Fig. 3 To Light Unit

STEP 5STEP 4

STEP 3

STEP 2

STEP 7STEP 6

STEP 10STEP 8 STEP 9

Run Status

Service Test

Temperature

Pressures

Setpoints

Inputs

Outputs

Configuration

Time Clock

Operating Modes

Alarms

Alarm Status

ENTER

MODE

ESCAPE

Run Status

Service Test

Temperature

Pressures

Setpoints

Inputs

Outputs

Configuration

Time Clock

Operating Modes

Alarms

Alarm Status

ENTER

MODE

ESCAPE

4

10. Using the scrolling marquee, enable the unit to run using the following procedure: a. Push the ESCAPE key unit a blank display screen

is shown. b. Push the DOWN key until the SERVICE TEST

LED is lit. c. Push the ENTER key. The display will show

STOP. d. Push the ENTER key again. The NO/YES display

will flash. e. Push the UP or DOWN key to toggle the display to

NO and then push ENTER. The unit will return to normal operation and exit SERVICE TEST mode.

11. To test the operation of the gas section, use the scrolling marquee Service Test routine to energize the gas outputs and to turn on the gas. Refer to unit Controls, Start-Up, Operation, Service and Troubleshooting literature for more information.

12. For normal operation, make sure that units with a conven- tional thermostat are set to heating control temperature. On VAV (variable air volume) and CV (constant volume) units with a space temperature sensor, make sure that the set points are at the normal heat set points.

TO SHUT UNIT OFF

Refer to Fig. 4 while performing the following steps: 1. Turn off the unit demand for cooling or heating by using

the scrolling marquee. The scrolling marquee is located in the control box at the compressor end of the unit. a. Push the ESCAPE key unit a blank display screen

is shown. b. Push the DOWN arrow key until the SERVICE

TEST LED is lit. c. Push the ENTER key. The display will show

STOP. d. Push the ENTER key again. The NO/YES display

will flash. e. Push the UP or DOWN key to toggle the display to

YES and then push ENTER. The unit will be locked off from heat, cooling or any operation. The controls will still function and the display will still operate.

2. Close the field-installed manual gas shutoff valve. 3. Turn off the electrical power to the unit using the optional

disconnect or the field-installed disconnect and lock off using proper lockout and tag-out procedures.

4. Remove the gas section panels. 5. Move the switch on the gas valve to the OFF position and

wait 5 minutes before doing any service in the section or on the piping.

6. Replace gas section access panels. 7. If unit is being shut down because of a malfunction, call

your dealer as soon as possible. If unit is being shut down because the heating season has ended, restore electrical power to the unit and reset the scrolling marquee to run mode to ensure operation of the cooling system during the cooling season.

Do not use this unit if any part has been under water. Imme- diately call a qualified service technician to inspect the unit and to replace any part of the control system and gas control that has been under water.

MAINTAINING YOUR UNIT All maintenance should be handled by skilled, experienced

personnel. Your dealer can help you establish a standard procedure.

For your safety, keep the area around the unit clear and free of combustible materials, gasoline, and other flammable liquids and vapors.

To ensure proper functioning of the unit, the flow of com- bustion and ventilating air must not be obstructed from reach- ing the unit. Clearance of at least 4 ft on flue and condenser sides and 6 in. on all other sides is required.

ROUTINE MAINTENANCE AND CARE FOR THE EQUIPMENT OWNER

Consider the following information before maintaining or servicing equipment:

Air Filter(s) Air filter(s) should be checked at least every 3 or 4 weeks and changed or cleaned when necessary. Replace the air filters with 20 x 24 x 2-in. size filters. The filter access panel is located at the end of the unit opposite of the condenser section. The access door is labeled to indicate that it is the filter access door. To replace or inspect filters:

1. Loosen the 3 latches securing the filter access door and open door.

2. Remove the bolt securing the inner access panel, located behind the filter access door, using care not to lose the bolt.

3. Remove the inner access panel.

If the main burners fail to light or the blower fails to start, shut down gas heating section and call your dealer for ser- vice. Failure to follow these requirements could result in serious personal injury.

1. Do not turn off the electrical power to unit without first turning off the gas supply.

2. Never attempt to manually light the main burners on unit with a match, lighter, or any other flame. If the electric sparking device fails to light the main burners, refer to the following shutdown procedures. Call your dealer as soon as possible.

Failure to follow these procedures can result in serious fire or personal injury.

IMPORTANT: Should overheating occur or the gas supply fail to shut off, shut off the manual gas valve to the unit before shutting off the electrical supply.

1. TURN OFF GAS SUPPLY AND THEN ELECTRI- CAL POWER TO YOUR UNIT BEFORE SERVIC- ING OR PERFORMING MAINTENANCE.

2. Do not turn off electrical power to this unit without first turning off the gas supply.

3. When removing access panels or performing mainte- nance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care has been taken to reduce sharp edges inside the unit, be extremely careful when handling parts or reaching into the unit.

Failure to follow these procedures can result in serious fire or personal injury.

5

STEP 1

Fig. 4 To Shut Unit Off

STEP 5

STEP 4

STEP 3

STEP 2

STEP 6

Run Status

Service Test

Temperature

Pressures

Setpoints

Inputs

Outputs

Configuration

Time Clock

Operating Modes

Alarms

Alarm Status

ENTER

MODE

ESCAPE

6

4. Slide the black plastic filter retainer towards you and remove.

5. Remove filters by pulling toward you and away from the filter track.

6. A filter removal rod is shipped taped to the partition located near the bottom filter track. The filter removal rod will aid in the removal of filters beyond the reach of the service person.

7. Inspect or replace filters. 8. Return filters to filter tracks. Note direction of airflow

arrows on filter frame. 9. Reinstall the black plastic filter retainer.

10. Place the filter removal rod back on the partition for future use.

11. Reinstall inner panel. 12. Reinstall bolt securing the inner panel. 13. Close filter access panel and tighten latches.

If you have difficulty in locating your air filter or if you have questions concerning proper filter maintenance, contact your dealer for instructions. When replacing your unit filters, always use the same size and type of filter that was originally supplied by the installer.

Units with outdoor air capability have a cleanable filter for the outdoor air. This filter should be checked annually and cleaned as necessary with steam or hot water and a mild deter- gent. Do not use throwaway filters in place of cleanable filters.

Heat Exchanger To ensure dependable and efficient heating operation, the heat exchanger should be checked by a qualified maintenance person before each heating season and cleaned when necessary. This checkout should not be attempt- ed by anyone not having the required expertise and equipment to do the job properly. Checking and/or cleaning the heat exchanger involves removing the gas controls assembly, the flue collector box, and the flue collector box cover. When finished, the gas controls assembly must be reinstalled for proper operation. Also, the flue collector box cover must be replaced correctly so that a proper seal is maintained. Refer to unit installation instructions for correct procedure. Contact your dealer for the required periodic maintenance.

Fans and Belts Periodically check the condition of the fan wheels and housings, and belt tension. When service is necessary, call your dealer.

Indoor-Fan Motor, Outdoor-Fan Motor, and Combustion Fan Motor Lubrication is not recom- mended. Bearings will not require lubrication for at least 5 years of normal operation. After 5 years, motor life can be extended by having the motors serviced at an authorized motor service shop.

Fan Shaft Bearings The bearings should be greased with Shell Alvania no. 2 grease or equivalent. The bearings will need to be greased annually, dependent on fan usage. Do not grease more than once a year.

Evaporator and Condenser Coils Cleaning of the coils should be done by qualified service personnel. Contact your dealer for the required annual maintenance.

Condensate Drain The drain pan and condensate drain line should be checked and cleaned at the same time the cooling coils are checked by your dealer.

Compressor All compressors are factory supplied with a normal charge of the correct type of refrigeration-grade oil in them and should not require additional oil.

Condenser Fan

The fan must be kept free of all obstructions to ensure prop- er cooling. Contact your dealer for any required service.

Electrical Controls and Wiring Electrical con- trols are difficult to check without proper instrumentation. If there are any discrepancies in the operating cycle, contact your dealer and request service.

Refrigerant Circuit The refrigerant circuit is difficult to check for leaks without the proper equipment. If inadequate cooling is suspected, contact your local dealer for service.

Combustion Area and Vent System The com- bustion area and vent system should be visually inspected be- fore each heating season. The normal accumulation of dirt, soot, rust, and scale can result in loss of efficiency and im- proper performance if allowed to build up.

See Fig. 1 and 2 and proceed as follows to inspect the com- bustion area and power-venting system of your unit.

1. Turn off gas supply to your unit. 2. Turn off electrical power to your unit. 3. Remove gas section access panels. 4. Using a flashlight, carefully inspect the burner areas for

dirt, soot, rust, or scale.

5. When you have completed your inspection, follow the To Light Unit section in this manual to restore your unit to operation.

6. Observe unit heating operation. Watch the burner flame to see if it is bright blue. If you observe a suspected mal- function or if the flame is not bright blue, call your dealer.

7. Replace gas section access panels.

Unit Panels After performing any maintenance or service on the unit, be sure all panels are securely fastened in place to prevent rain from entering unit cabinet and to prevent disruption of the correct unit airflow pattern.

Never operate your unit without filters in place. Failure to heed this warning may result in damage to the blower motor and/or compressor. An accumulation of dust and lint on internal parts of your unit can cause loss of efficiency and, in some cases, fire.

Do not poke sticks, screwdrivers, or any other object into revolving fan blades. Severe bodily injury may result.

If your unit makes any unusual or especially loud noises during heating, shut down the heating section and call your dealer.

If dirt, soot, rust, or scale accumulations are found, call your dealer and do not operate your heating section.

Components in heat section may be hot after unit has been started. When observing flame, be careful not to get close to or touch heating components. Serious personal injury may result.

7

REGULAR DEALER MAINTENANCE In addition to the type of routine maintenance you might be

willing to perform, your unit should be inspected regularly by a properly trained service technician. An inspection (preferably each year, but at least every other year) should include the following:

1. Inspection of all flue product passages including the burners, heat exchanger, and flue collector box.

2. Inspection of all combustion and ventilation-air passages and openings.

3. Close inspection of all gas pipes leading to and inside your unit.

4. Inspection and if required, cleaning of the condenser and evaporator coils.

5. Inspection and if required, cleaning of the condensate drain pan.

6. Inspection and cleaning of blower wheel housing and motor.

7. Inspection of all supply and return-air ducts for leaks, ob- structions, and insulation integrity. Any problems found should be resolved at the time of inspection.

8. Inspection of the unit base for cracks, gaps, etc., which may cause a hazardous condition.

9. Inspection of the unit casing for signs of deterioration. 10. Inspection of all electrical wiring and components to

ensure proper connection. 11. Inspection for leaks in the refrigerant circuit. Pressure-

check to determine appropriate refrigerant charge. 12. Inspection of fan wheels and housings, belt tension, and

fan motor shaft bearings. 13. Operational check of the unit to determine working

conditions. Repair or adjustment should be made at the time of inspection.

Your servicing dealer may offer an economical service con- tract that covers seasonal inspections. Ask for further details.

Complete service instructions can be found in the unit Controls, Start-Up, Operation, Service and Troubleshooting literature.

BEFORE YOU CALL FOR SERVICE, CHECK FOR PROBLEMS

THAT CAN BE EASILY SOLVED If insufficient heating or cooling is suspected: ( ) Check for sufficient airflow. Check the air filter for dirt. Check for blocked return or supply-air grilles. Be sure they are open and unobstructed. If these checks do not reveal the cause, call your servicing dealer.

If your unit is not operating at all, check the following list for easy solutions: ( ) If using a thermostat, check to be sure that your thermo- stat temperature set point is above the indoor temperature dur- ing the heating season, or below the indoor temperature during the cooling season. Be sure the thermostat mode is in the proper AUTO, HEAT, or COOL mode and not in the OFF mode. ( ) Check scrolling marquee to be sure unit is not in SERVICE TEST mode. Check set points are properly set. ( ) Is the electrical supply switch ON? Are any fuses blown or has the circuit breaker tripped? ( ) During the heating season, check the external manual shutoff valve. Is this lever parallel with the pipe, indicating that the valve is open? Or is the lever at the right angle, indicating that the valve is closed? If closed, has the gas been shut off for safety reasons? Otherwise, you may open the valve and follow the start-up procedures listed in this manual. NOTE: Before proceeding with the next check, turn OFF the electrical power supply to the unit. Remove the gas section access panels. ( ) During the heating season, check the switch on the gas valve. Is it in the ON position? If it is not, be sure it has not been turned off for the purpose of safety. If no safety hazards are present, follow the start-up procedures in this manual. ( ) If your unit still fails to operate, call your servicing dealer for troubleshooting and repairs. Specify the model and serial numbers of your unit. (Record them in this manual in the space provided.) If the dealer knows exactly which unit you have, he may be able to offer suggestions over the phone, or save valuable time through knowledgeable preparation for the service call.

IN CASE OF TROUBLE If, after performing the above checks, unit performance is

unsatisfactory, shut off the unit and call your dealer. Dealers Name _____________________________________ Telephone No _____________________________________ Unit Model _______________________________________ Unit Serial Number _________________________________

<

Manualsnet FAQs

If you want to find out how the 48AJ Carrier works, you can view and download the Carrier 48AJ User's Manual on the Manualsnet website.

Yes, we have the User's Manual for Carrier 48AJ as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The User's Manual should include all the details that are needed to use a Carrier 48AJ. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier 48AJ User's Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier 48AJ User's Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier 48AJ User's Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier 48AJ User's Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier 48AJ User's Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.