Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53330008-01 Printed in U.S.A. Form 33CS-64SI Pg 1 6-07 Replaces: 33CS-54SIBook 1 4
Tab 11a 13a
Mounting Instructions Part Number 33CSPREMLK
GENERAL The PremierLink controller is a field retrofit rooftop control
compatible with the Carrier Comfort Network (CCN) sys- tem. This control is designed to allow users the access and abil- ity to change factory-defined settings, thus expanding the func- tion of the standard unit control board. The complete Premier- Link package (part number 33CSPREMLK) consists of a rooftop control circuit board with plastic cover and label, wire harness, spade connectors, wire nuts and 4 mounting screws.
Carriers diagnostic standard tier display tools such as System Pilot or Touch Pilot device can be used with the PremierLink controller. Access is available via an RJ-14 con- nection or a 3-wire connection to the communication bus. User interfaces available for use with the CCN system are PCs equipped with Carrier interface software such as Service Tool, ComfortVIEW, or ComfortWORKS software. When used as part of the CCN, other devices such as the CCN data transfer or Comfort Controller can read data from or write data to the PremierLink retrofit controller.
TOOLS REQUIRED Phillips head mechanical screwdriver or battery operated
drill with Phillips head bit.
INSTALLATION
Location The PremierLink controller should be located inside one of the available service access panels of the unit. Be sure the location selected prevents moisture and rain from coming into contact with the circuit board.
Select a location which will be safe from water damage and allow sufficient access for service and wiring. For service access, there should be at least 6 in. of clearance between the front of the PremierLink controller and adjacent surfaces. Be sure to leave 1/2 in. clearance in front of RJ-14 connector for attaching RJ-14 cable from a CCN device. A field-supplied right angle 6-pin RJ-14 connector can be attached if necessary. NOTE: If the PremierLink controller must be installed in a location where there is not easy access to CCN connectors, a remote connection kit (part number 33CSREMCCN) can be ordered.
Mounting Perform the following steps to mount the PremierLink controller:
1. Remove plastic cover by gently squeezing the middle of longer sides of the cover and pull away from the board. This will release the locking tabs inside cover.
2. Holding the controller upright, align the holes in each top corner of the controller to predrilled holes on unit surface. See Fig. 1.
NOTE: If replacing an existing Apollo control, two holes on the board will line up with two holes where the Apollo con- trol base plate was mounted.
3. Hold the controller firmly in place. Be sure all standoffs are in contact with mounting surface for stability. This keeps the circuit board from bending and provides for grounding.
4. Align controller to existing holes on unit and drill remain- ing holes.
5. Using four no. 6x1-in. self-drilling Phillips pan head screws (provided), attach controller to unit through standoffs ensuring a secure grip to unit surface and proper electrical grounding.
6. Replace plastic cover to protect circuit board. The cover also provides product identification.
NOTE: The plastic cover is UL (Underwriters Laboratories) 94-V0/5VB approved. If installing the controller in the air- stream, be sure to check with local codes department. As an alternative, the controller can be mounted without the cover.
For further instructions regarding sensors, options, start-up, configuration, and troubleshooting of the controller, refer to the Installation, Start-Up, and Configuration Instructions.
IMPORTANT: This document contains Premier- Link controller mounting information only. Refer to the Installation, Start-Up, and Configuration manual for PremierLink controller wiring and installation configuration procedures.
IMPORTANT: To prevent malfunctioning of the circuit board, any wires not being used in the wire harness should be removed or capped. To remove wires from Molex connector, depress the metal latching tab with a small screwdriver and gently pull the wire out.
PREMIERLINK Retrofit Rooftop Controller
Version 2.0