Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300190-01 Printed in U.S.A. Form 30/38-19SI Pg 1 1-19 Replaces: 30/38-16SI

Installation Instructions Part Number 38AP-900---022

CONTENTS

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . 1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Install Harness and Make Wire

Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Controls Configuration for EMM Options. . . . . . . . . 7

SAFETY CONSIDERATIONS

Installation of this accessory can be hazardous due to system pressures, electrical components, and equipment location (such as a roof or elevated structure). Only trained, qualified installers and service technicians should install, start up, and service this equipment. When installing this accessory, observe precautions in the liter- ature, labels attached to the equipment, and any other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling and installing this accessory.

GENERAL The energy management module (EMM) accessory (Fig. 1) package is required for additional temperature reset, demand limit, and remote set point features of the ComfortLink con- trols for 30MP, 30RAP and 38AP units. Chilled water tempera- ture reset by return water, outside air or space temperature does NOT require the addition of this accessory. The following ad- ditional features are supported by this accessory: temperature reset by 4 to 20 mA field-supplied signal. demand limit control via field-supplied two-step switch

input. demand limit control by 4 to 20 mA field-supplied signal. support of unoccupied operation for ice making through

field-supplied contacts (30MP, 30RAP only). cooling set point control by 4 to 20 mA field-supplied signal.

ACCESSORY PACKAGE CONTENTS

LEGEND

INSTALLATION

NOTE: Component arrangement drawings and wiring dia- grams show available options that may not be applicable to your unit. 1. Inspect the package contents for missing or damaged

parts. File a claim with shipping agency if parts are dam- aged. Notify your Carrier representative if any items are missing.

2. Open and tag all electrical disconnects. 3. Access control box:

a. Model 30RAP011-030, 30MP015-071 and 38AP025- 030 units: Open control box door and remove inner cover.

b. Model 30RAP035-150 and 38AP040-130 units: Open center control box door.

4. For 30RAP and 38AP units, loosen the four screws secur- ing the scrolling marquee display bracket. Lift the bracket up and slide it in the holding slots at the top of its mount- ing bracket.

For 30MP units, carefully suspend the display bracket from the wiring harness.

WARNING

Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.

ITEM PART NO. QUANTITY Energy Management Module 30GT515218 1 Harness (38APD,S025-065) 38APHLSBCE-A00 1 Harness (38APD070-130) 38APHLSLCE-A10 1 Harness, EMM to LVT (30RAP, 30MP) 38APHSCALE-A00 1

Harness, EMM to MBB/EXV (Power - 30RAP, 30MP) 38APHSCALECA10 1

Harness, EMM to MBB/EXV (Comm. - 30RAP, 30MP) 38APHSCALECA00 1

Harness, EMM to AUX (Comm. - 30MP) 38APHSCALXCA00 1

Screw, no. 6, 1-in. long AL56AU130 1 Wire Tie 4

AUX Auxiliary Board EXV Electronic Expansion Valve LVT Low Voltage Terminal MBB Main Base Board

WARNING

Before beginning installation of this equipment, be sure all power to the unit is disconnected, and that tags are properly placed to alert others. Electrical shock can cause personal injury and death.

30MP015-071, 30RAP011-150 38APD025-130, 38APS025-065

Energy Management Module (EMM) Accessory 50/60 Hz

2

5. Using the no. 6 screw provided and the existing retaining clips in the control box, mount the EMM module to the back of the control box. See Fig. 2-7 for the mounting location of each unit.

6. The board address is set through a 4-position DIP switch. All switches should be set to ON.

Fig. 1 EMM Board

LEGEND FOR FIG. 2-8 AUX Auxiliary Board CB Circuit Breaker CCB Compressor Circuit Breaker CCH Crankcase Heater Relay CHC Cooler/Pump Heater Contactor CSB Current Sensor Board CXB Compressor Expansion Board EMM Energy Management Module EQUIP Equipment EXV Electronic Expansion Valve FB Fuse Block FC Fan Contactor GND Ground LON LON Card LVT Low Voltage Terminal MBB Main Base Board MM Management Module TB Terminal Block TRAN Transformer UPC UPC Translator Board

Terminal Block Connection

CEBD430351-0396-01C

T E

S T

1

C E

P L1

30 35

1- 01

P W

R

TEST 2

J1 J2

J4 J3

J5

J6 J7

LEN

STATUS

RED LED - STATUS GREEN LED - LEN (LOCAL EQUIPMENT NETWORK)

ADDRESS DIP SWITCH

3

Fig. 2 Mounting EMM 38AP025-030 Units

Fig. 3 Mounting EMM 38AP040-060 Units

See Legend on page 2.

See Legend on page 2.

4

Fig. 4 Mounting EMM 38AP070-130 Units

Fig. 5 Mounting EMM 30RAP011-030 Units

See Legend on page 2.

See Legend on page 2.

5

Fig. 6 Mounting EMM Typical 30RAP035-060 Units Shown

Fig. 7 Mounting EMM 30MP015-071 Units

See Legend on page 2.

See Legend on page 2.

6

Fig. 8 Mounting EMM Typical 30RAP070-150 Units Shown

Install Harness and Make Wire Connections 38AP025-065 UNITS WITH AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 9 for wiring. 1. Disconnect the MBB-J3 connector and plug it into the

EMM-J3 connector. 2. Install the new harness 38APHLSBCE-A00 provided.

a. Install connector labeled MBB-J3 to MBB-J3 and other end labeled EMM-J4 to EMM-J4.

b. Install connector labeled MBB-J2 to MBB-J2 and other end labeled EMM-J1 to EMM-J1.

c. Install connectors labeled EMM-J6 and J7 to EMM- J6 and J7 and other end labeled LVT-J10 to LVT ter- minal strip.

38AP025-065 UNITS WITHOUT AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 9 for wiring.

Install the new harness 38APHLSBCE-A00 provided. 1. Install connector labeled MBB-J3 to MBB-J3 and other

end labeled EMM-J4 to EMM-J4. 2. Install connector labeled MBB-J2 to MBB-J2 and other

end labeled EMM-J1 to EMM-J1. 3. Install connectors labeled EMM-J6 and J7 to EMM-J6 and

J7 and other end labeled LVT-J10 to LVT terminal strip.

38AP070-130 UNITS WITH AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 10 for wiring. 1. Disconnect the CXB connector J4 and plug it into the

EMM connector J3. 2. Install the new harness 38APHLSLCE-A10 provided.

a. Install connector labeled CXB-J4 to CXB-J4 and other end labeled EMM-J4 to EMM-J4.

b. Install connector labeled CXB-J2 to CXB-J2 and other end labeled EMM-J1 to EMM-J1.

c. Install connectors labeled EMM-J6 and J7 to EMM- J6 and J7 and other end labeled LVT-J10 to LVT ter- minal strip.

38AP070-130 UNITS WITHOUT AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 10 for wiring.

Install the new harness 38APHLSLCE-A10 provided. 1. Install connector labeled CXB-J4 to CXB-J4 and other end

labeled EMM-J4 to EMM-J4. 2. Install connector labeled CXB-J2 to CXB-J2 and other end

labeled EMM-J1 to EMM-J1. 3. Install connectors labeled EMM-J6 and J7 to EMM-J6 and

J7 and other end labeled LVT-J10 to LVT terminal strip.

30RAP011-060 UNITS WITH AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 11 for wiring. 1. Disconnect the EXV connector J4 and plug it into the

EMM connector J4. 2. Install the new harness 38APHSCALECA00. Install con-

nector labeled EXV-J4 to EXV-J4 and other end labeled EMM-J3 to EMM-J3.

3. Install the new harness 38APHSCALECA10. Disconnect MBB connector J2 and plug it into the EMM-J2. Install connector labeled MBB/EXV-J2 to MBB-J2 and other end labeled EMM-J1 to EMM-J1.

4. Install the new harness 38APHSCALE-A00. Install con- nectors labeled EMM-J6 and J7 to EMM-J6 and J7 and other end labeled LVT-J10 to LVT terminal strip.

30RAP011-060 UNITS WITHOUT AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 11 for wiring. 1. Install the new harness 38APHSCALECA00. Install con-

nector labeled EXV-J4 to EXV-J4 and other end labeled EMM-J3 to EMM-J3.

7

2. Install the new harness 38APHSCALECA10. Install con- nector labeled MBB/EXV-J2 to MBB-J2 and other end labeled EMM-J1 to EMM-J1.

3. Install the new harness 38APHSCALE-A00. Install con- nectors labeled EMM-J6 and J7 to EMM-J6 and J7 and other end labeled LVT-J10 to LVT terminal strip.

30RAP070-150 UNITS WITH AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 12 for wiring. 1. Disconnect the CXB connector J4 and plug it into the

EMM connector J4. 2. Install the new harness 38APHSCALECA00. Install con-

nector labeled EXV-J4 to CXB-J4 and other end labeled EMM-J3 to EMM-J3.

3. Install the new harness 38APHSCALECA10. Install con- nector labeled MBB/EXV-J2 to CXB-J2 and other end labeled EMM-J1 to EMM-J1.

4. Install the new harness 38APHSCALE-A00. Install con- nectors labeled EMM-J6 and J7 to EMM-J6 and J7 and other end labeled LVT-J10 to LVT terminal strip.

30RAP070-150 UNITS WITHOUT AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 12 for wiring. 1. Install the new harness 38APHSCALECA00. Install the

connector labeled EXV-J4 to CXB-J4 and other end labeled EMM-J3 to EMM-J3.

2. Install the new harness 38APHSCALECA10. Install con- nector labeled MBB/EXV-J2 to CXB-J2 and other end labeled EMM-J1 to EMM-J1.

3. Install the new harness 38APHSCALE-A00. Install con- nectors labeled EMM-J6 and J7 to EMM-J6 and J7 and other end labeled LVT-J10 to LVT terminal strip.

30MP015-045 UNITS WITH AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 13 for wiring. 1. Remove existing harness from MBB-J3 and AUX-J9 2. Install the new harness 38APHSCALECA00. Install one

end of the harness in MBB connector J3 and the other end in EMM connector J4.

3. Install the new harness 38APHSCALECA10. Install con- nector labeled MBB/EXV-J2 to MBB-J2 and other end labeled EMM-J1 to EMM-J1.

4. Install the new harness 38APHSCALE-A00. Install con- nectors labeled EMM-J6 and J7 to EMM-J6 and J7 and the other end labeled LVT-J10 to J10 of the LVT terminal strip.

5. Install the new harness 38APHSCALXCA00 provided. Install connector labeled EMM-J3 to EMM-J3 and other end labeled AUX-J9 to AUX-J9.

30MP015-045 UNITS WITHOUT AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 13 for wiring. 1. Install the new harness 38APHSCALECA00. Install one

end of the harness in MBB connector J3 and the other end in EMM connector J4.

2. Install the new harness 38APHSCALECA10. Install con- nector labeled MBB/EXV-J2 to MBB-J2 and other end labeled EMM-J1 to EMM-J1.

3. Install the new harness 38APHSCALE-A00. Install con- nectors labeled EMM-J6 and J7 to EMM-J6 and J7 and the other end labeled LVT-J10 to J10 of the LVT terminal strip.

30MP050-071 UNITS WITH AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig. 13 for wiring. 1. Install the new harness 38APHSCALXCA00 provided.

Install connector labeled EMM-J3 and the other end labeled AUX-J9 to the open pins on AUX-J9. See Fig 13.

2. Install the new harness 38APHSCALECA10. Install the connector labeled MBB/EXV-J2 to MBB-J2 and the other end labeled EMM-J1 to EMM-J1.

3. Install the new harness 38APHSCALE-A00. Install con- nectors labeled EMM-J6 and J7 to EMM-J6 and J7 and the other end labeled LVT-J10 to J10 of the LVT terminal strip.

30MP050-071 UNITS WITHOUT AUX BOARD

Perform the following procedure to install the harness and make the wiring connections. See Fig 13 for wiring. 1. Install the new harness 38APHSCALXCA00 provided.

Install connector labeled EMM-J3 to EMM-J3 and the other end to EXV-J4.

2. Install the new harness 38APHSCALECA10. Install the connector labeled MBB/EXV-J2 to MBB-J2 and the other end labeled EMM-J1 to EMM-J1.

3. Install the new harness 38APHSCALE-A00. Install the connectors labeled EMM-J6 and J7 to EMM-J6 and J7 and the other end labeled LVT-J10 to J10 of the LVT terminal strip.

FIELD WIRING CONNECTIONS

Refer to Fig. 2-7 for field wiring interfaces with the LVT termi- nal strip.

Controls Configuration for EMM Options Refer to the 38AP controls and troubleshooting manual for split system configuration of controls. Refer to the 30RAP con- trols and troubleshooting manual for AquaSnap configuration of controls for 30RAP units. Refer to the 30MP controls and troubleshooting manual for configuration of controls for 30MP units.

LEGEND FOR FIG. 9-13 CXB Compressor Expansion Board EMM Energy Management Module FIOP Factory-Installed Option LVT Low Voltage Terminal MBB Main Base Board

Field Wiring

8

Fig. 9 Typical Wiring Connections (38AP025-065 Units)

FIOP/

ON

OFF

1 2 3 4 5 6 7 8 DARK = SWITCH LOCATION

3

2

1

3

2

1

6

5

4

3

2

1

J9

RED

WHT

BLK

12

11

10

9

8

7

6

5

4

3

2

1

12

11

10

9

8

7

J7

EMM4

3

2

1

4

3

2

1

J3

4

3

2

1

4

3

2

1

J4

RED

WHT

BLK

RED

WHT

BLK

12

11

10

9

8

7

6

5

4

3

2

1

12

11

10

9

8

7J6

14

13 14

13

ACCESSORY

LVT

1

1

2

3

4

5

6

1

2

3

4

5

6

14

15

4

3

12

13

6

5

10

11

7

8

9

8

6

7

4

5 9

2

3

10 +

-

COOLING SETPOINT 4-20mA

RED

RED

BLU

BLU

PNK

ORN

BRN

VIO

+

-

TEMP RESET 4-20mA

+

-

DEMAND LIMIT 4-20mA

DEMAND LIMIT STEP 1 OR Y3

DEMAND LIMIT STEP 2 OR Y4

DGS OR MM

FIOP

DUS

2

1

8

7

2

1

8

7

J2

J6 DTT

VIO

BRN

RED

BLK

2

1 2

1 RED

BLKJ4

CH1

-

CH11

-

CH9

-

2

1 2

1

J5 CH10

-

TO MM-A

J10

AUX

3 3

2 2

1 1

J2 BRN

VIO

2 2

1

J1

1

3 3

MBB BRN

RED

3 3

2 2

1 1

J2 2

J1

1

3

FIOP/ACCESSORY

EMM

a30-4943

A38-7212

24-V POWER CONNECTION

See Legend on page 7.

9

Fig. 10 Typical Wiring Connections (38AP070-130 Units)

FIOP/

12

11

10

9

8

7

6

5

4

3

2

1

6

5

4

3

2

1J5

CXB4

3

2

1

4

3

2

1

J3

CSB B3

2

3

1

RED

ORN

BRN

CSB A3

2

3

1

RED

ORN

BRN

4

3

2

1

4

3

2

1

J4

RED

WHT

BLK

RED

WHT

BLK

ON

OFF

1 2 3 4 5 6 7 8 DARK = SWITCH LOCATION

DUS

3

2

1

3

2

1

6

5

4

3

2

1

J9 2

1

8

7

2

1

8

7

J2

J6 DTT

RED

WHT

BLK

DGS OR MM

FIOP

12

11

10

9

8

7

6

5

4

3

2

1

12

11

10

9

8

7

J7

EMM4

3

2

1

4

3

2

1

J3

4

3

2

1

4

3

2

1

J4

RED

WHT

BLK

RED

WHT

BLK

12

11

10

9

8

7

6

5

4

3

2

1

12

11

10

9

8

7J6

14

13 14

13

ACCESSORY

LVT

1

1

2

3

4

5

6

1

2

3

4

5

6

14

15

4

3

12

13

6

5

10

11

7

8

9

8

6

7

4

5 9

2

3

10 +

-

COOLING SETPOINT 4-20mA

RED

RED

BLU

BLU

PNK

ORN

BRN

VIO

+

-

TEMP RESET 4-20mA

+

-

DEMAND LIMIT 4-20mA

DEMAND LIMIT STEP 1 OR Y3

DEMAND LIMIT STEP 2 OR Y4

VIO RED PL50-1

BRN BLK

PL50-2

RED RED PL50-3

BLK BLK

PL50-4

2

1 2

1 RED

BLKJ4

CH1

-

CH11

-

CH9

-

-

+

G

-

+

G

2

1 2

1 RED

BLKJ5 CH10

-

TO MM-A

TO MM-B

(090-130 ONLY)

J10

AUX

a30-4944

A38-7452

24-V POWER CONNECTION

See Legend on page 7.

10

Fig. 11 Typical Wiring Connections (30RAP011-060 Units)

FIOP/

12

11

10

9

8

7

6

5

4

3

2

1

12

11

10

9

8

7

J7

EMM4

3

2

1

4

3

2

1

J3

4

3

2

1

4

3

2

1

J4

RED

WHT

BLK

RED

WHT

BLK

12

11

10

9

8

7

6

5

4

3

2

1

12

11

10

9

8

7J6

14

13 14

13

ACCESSORY

1

1

2

3

4

5

6

1

2

3

4

5

6

10

7

8

9

8

6

7

4

5 9

2

3

10 +

-

COOLING SETPOINT 4-20mAPNK

ORN

BRN

VIO

+

-

TEMP RESET 4-20mA

+

-

DEMAND LIMIT 4-20mA

14

15

4

3

12

13

6

5

11

RED

RED

BLU

BLU DLS STEP 2

DLS STEP 1

LVT

16

17

2

1GRA

GRA ICE DONE

J10

A38-7212

24-V POWER CONNECTION

See Legend on page 7.

3 3

2 2

1 1

J2 BRN

VIO

2 2

1

J1

1

3 3

MBB BRN

RED

3 3

2 2

1 1

J2 2

J1

1

3

FIOP/ACCESSORY

EMM

11

Fig. 12 Typical Wiring Connections (30RAP070-150 Units)

FIOP/

12

11

10

9

8

7

6

5

4

3

2

1

12

11

10

9

8

7

J7

EMM4

3

2

1

4

3

2

1

J3

4

3

2

1

4

3

2

1

J4

RED

WHT

BLK

RED

WHT

BLK

12

11

10

9

8

7

6

5

4

3

2

1

12

11

10

9

8

7J6

14

13 14

13

ACCESSORY

1

1

2

3

4

5

6

1

2

3

4

5

6

10

7

8

9

8

6

7

4

5 9

2

3

10 +

-

COOLING SETPOINT 4-20mAPNK

ORN

BRN

VIO

+

-

TEMP RESET 4-20mA

+

-

DEMAND LIMIT 4-20mA

14

15

4

3

12

13

6

5

11

RED

RED

BLU

BLU DLS STEP 2

DLS STEP 1

LVT

16

17

2

1GRA

GRA ICE DONE

J10

24-V POWER CONNECTION a30-5546

See Legend on page 7.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300190-01 Printed in U.S.A. Form 30/38-19SI Pg 12 1-19 Replaces: 30/38-16SI

Carrier Corporation 2019

Fig. 13 Typical Wi

Manualsnet FAQs

If you want to find out how the 30RAP011-150 Carrier works, you can view and download the Carrier 30RAP011-150 v2 Installation Instructions on the Manualsnet website.

Yes, we have the Installation Instructions for Carrier 30RAP011-150 as well as other Carrier manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Installation Instructions should include all the details that are needed to use a Carrier 30RAP011-150. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Carrier 30RAP011-150 v2 Installation Instructions is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Carrier 30RAP011-150 v2 Installation Instructions consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Carrier 30RAP011-150 v2 Installation Instructions free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Carrier 30RAP011-150 v2 Installation Instructions, simply download the document to your computer. Once downloaded, open the PDF file and print the Carrier 30RAP011-150 v2 Installation Instructions as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.