PS100 and CH100 Power Supply and Charging Regulators,

A100 Null Modem Adapter, and A105 Additional

12 V Terminals Adapter Revision: 4/09

C o p y r i g h t 2 0 0 0 - 2 0 0 9 C a m p b e l l S c i e n t i f i c , I n c .

Warranty and Assistance The PS100 AND CH100 POWER SUPPLY AND CHARGING REGULATORS, A100 NULL MODEM ADAPTER, AND A105 ADDITIONAL 12 V TERMINALS ADAPTER are warranted by CAMPBELL SCIENTIFIC, INC. to be free from defects in materials and workmanship under normal use and service for twelve (12) months from date of shipment unless specified otherwise. Batteries have no warranty. CAMPBELL SCIENTIFIC, INC.'s obligation under this warranty is limited to repairing or replacing (at CAMPBELL SCIENTIFIC, INC.'s option) defective products. The customer shall assume all costs of removing, reinstalling, and shipping defective products to CAMPBELL SCIENTIFIC, INC. CAMPBELL SCIENTIFIC, INC. will return such products by surface carrier prepaid. This warranty shall not apply to any CAMPBELL SCIENTIFIC, INC. products which have been subjected to modification, misuse, neglect, accidents of nature, or shipping damage. This warranty is in lieu of all other warranties, expressed or implied, including warranties of merchantability or fitness for a particular purpose. CAMPBELL SCIENTIFIC, INC. is not liable for special, indirect, incidental, or consequential damages.

Products may not be returned without prior authorization. The following contact information is for US and International customers residing in countries served by Campbell Scientific, Inc. directly. Affiliate companies handle repairs for customers within their territories. Please visit www.campbellsci.com to determine which Campbell Scientific company serves your country.

To obtain a Returned Materials Authorization (RMA), contact CAMPBELL SCIENTIFIC, INC., phone (435) 753-2342. After an applications engineer determines the nature of the problem, an RMA number will be issued. Please write this number clearly on the outside of the shipping container. CAMPBELL SCIENTIFIC's shipping address is:

CAMPBELL SCIENTIFIC, INC. RMA#_____ 815 West 1800 North Logan, Utah 84321-1784

For all returns, the customer must fill out a Declaration of Hazardous Material and Decontamination form and comply with the requirements specified in it. The form is available from our website at www.campbellsci.com/repair. A completed form must be either emailed to shanna@campbellsci.com or faxed to 435-750-9579. Campbell Scientific will not process any returns until we receive this form. If the form is not received within three days of product receipt or is incomplete, the product will be returned to the customer at the customers expense. Campbell Scientific reserves the right to refuse service on products that were exposed to contaminants that may cause health or safety concerns for our employees.

CAMPBELL SCIENTIFIC, INC. does not accept collect calls.

PS100 Table of Contents PDF viewers note: These page numbers refer to the printed version of this document. Use the Adobe Acrobat bookmarks tab for links to specific sections.

1. General Description.....................................................1

2. Specifications ..............................................................1

3. Wiring............................................................................2

4. A100 Null Modem Adapter ..........................................4

5. A105 12V Terminal Expansion Adapter .....................5

Figures 1. Wiring to Charger.......................................................................................3 2. Simplified Charging Circuit Schematic ......................................................4 3. Null Modem Connections...........................................................................5 4. A105 Adapter .............................................................................................5

i

PS100 and CH100 Power Supply and Charging Regulators, A100 Null Modem Adapter, and A105 Additional 12 V Terminals Adapter

1. General Description The PS100 is a 12-volt power supply that includes a charging regulator and a 7 amp hour battery. The CH100 is a charging regulator that is used with a Campbell Scientific battery pack such as the BP12 or BP24 or with a user- supplied battery. Charging power is typically supplied by an AC transformer or an unregulated solar panel.

The PS100 and CH100 each have one adapter connector that will allow connecting one of the following adapters.

The A100 Null Modem Adapter has two 9-pin connectors that provide a null modem for use in a site, without a datalogger. The A100 connects and powers two Campbell Scientific peripherals that would normally be connected to a datalogger. These peripherals are typically modems linking different communications technologies; e.g., telephone to radio.

The A105 Additional 12 V Terminals Adapter may be used to provide additional 12 V and ground terminals where the power supply is used to power several devices.

To prevent people from getting burned, an ABS plastic cover [CSI #18688] sits on the heatsink of a PS100 or CH100. The cover is fastened to the heatsink via a #4-40 x .250 Pan Phillips screw [#395]. The cover must be removed to attach an A100 or A105 adapter. Some early models of the PS100 and CH100 did not include the cover and do not have a place to attach it.

NOTE

2. Specifications Input Voltage (CHG terminals) 15 to 28 VDC or 18 VAC RMS Battery Connections Charging Output Voltage: Temperature compensated float

charge for 12 V Battery Temperature Compensation Range: -40 to +60C Charging Current Limit: 1.2 Amps typical

1

PS100 and CH100 Power Supply and Charging Regulators

Power Out (+12 terminals) Voltage: Unregulated 12 V from Battery Current Limited w / 3 A Thermal Fuse: > 3 A @ < 20C 3 A @ 20C 2.1A @ 50C 1.8 A @ 60C

Battery Packs Operating Temperature Range: -40 to +60C Capacity: PS100 7 Amp hours BP12 12 Amp hours BP24 24 Amp hours

These batteries are designed to be float charged. Permanent damage occurs and battery life is shortened if the battery is allowed to discharge below 10.5 volts.

WARNING

AC Transformer: CSI Model No. 9591 Input Voltage: 120 VAC Output Voltage: 18 VAC RMS Output Current (max): 1.2 Amps RMS Protection (automatic reset): 85C thermal reset breaker UL Approval: UL-1950

AC Transformer: CSI Model No. 14014 Input Voltage: 90 - 264 VAC; 47 - 63 Hz Output Voltage: 18 VDC Output Current (max): 1.3 Amps UL Approved, File No.: E137895

PS100 Physical Specifications: 10.5 cm tall, 19 cm long,

7 cm wide

3. Wiring An internal or external battery is connected to the charger by means of the INT (Internal) or EXT (External) connectors, as shown in Figure 1. An external battery cable is available for the charger. This cable connects another battery with the charger to provide power if the main battery is removed. The red lead connects to the positive battery terminal and the black lead connects to the negative terminal.

Reversal of polarity of external battery will damage the PS100 or CH100.

WARNING

2

PS100 and CH100 Power Supply and Charging Regulators

It is possible to leave two batteries connected. The battery connections are diode isolated (Figure 2); however, if one of the batteries fail, it could draw all the charging current and the other battery will be discharged.

A battery must be attached for the charger to function correctly as a power supply.

CAUTION

The leads from the transformer or solar panel are connected to the CHG terminals. Polarity does not matter; either lead can be connected to either terminal.

The wires that connect power to the datalogger and/or peripherals are connected to the +12 and ground ( ) terminals.

To Battery

From Transformer or Solar Panel

To Datalogger or Peripherals

FIGURE 1. Wiring to Charger

3

PS100 and CH100 Power Supply and Charging Regulators

INT

EXT

B A

T T

CHG

O F

F

O N

CHG

CHG

+12

+12

Charging

Regulator IN

OUT 3 A Thermal

Fuse

These look identical when unplugged

FIGURE 2. Simplified Charging Circuit Schematic

4. A100 Null Modem Adapter The A100 has two 9-pin CS I/O ports with a null modem between them. The ports are used to connect two 9-pin devices that would normally be connected to the CS I/O port on a Campbell datalogger. The charger supplies 12 volts and 5 volts to the appropriate pins on the connector for powering the connected devices.

This cannot be used as a null modem between two RS- 232 devices.

CAUTION

4

PS100 and CH100 Power Supply and Charging Regulators

1 1

2 7 3 8 4 9 5

+5 V

GND HS

Ring +12 V

RX TX ME

Ring

RX TX ME

2

3

4

5

6

7

8

9

+12 V+5 V

1.85 A Thermal

Fuse

FIGURE 3. Null Modem Connections

5. A105 12V Terminal Expansion Adapter The A105 adapter adds four 12-V terminals and four ground terminals to a CH100 or PS100 (see Figure 4). The extra terminals make it easier to wire multiple continuously powered 12-Vdc devices to the power supply.

FIGURE 4. A105 Adapter

5

PS100 and CH100 Power Supply and Charging Regulators

6

Campbell Scientific Companies

Campbell Scientific, Inc. (CSI) 815 West 1800 North Logan, Utah 84321 UNITED STATES

www.campbellsci.com info@campbellsci.com

Campbell Scientific Africa Pty. Ltd. (CSAf) PO Box 2450

Somerset West 7129 SOUTH AFRICA

www.csafrica.co.za cleroux@csafrica.co.za

Campbell Scientific Australia Pty. Ltd. (CSA) PO Box 444

Thuringowa Central QLD 4812 AUSTRALIA

www.campbellsci.com.au info@campbellsci.com.au

Campbell Scientific do Brazil Ltda. (CSB) Rua Luisa Crapsi Orsi, 15 Butant

CEP: 005543-000 So Paulo SP BRAZIL www.campbellsci.com.br suporte@campbellsci.com.br

Campbell Scientific Canada Corp. (CSC)

11564 - 149th Street NW Edmonton, Alberta T5M 1W7

CANADA www.campbellsci.ca dataloggers@campbellsci.ca

Campbell Scientific Centro Caribe S.A. (CSCC)

300 N Cementerio, Edificio Breller Santo Domingo, Heredia 40305

COSTA RICA www.campbellsci.cc info@campbellsci.cc

Campbell Scientific Ltd. (CSL)

Campbell Park 80 Hathern Road

Shepshed, Loughborough LE12 9GX UNITED KINGDOM

www.campbellsci.co.uk sales@campbellsci.co.uk

Campbell Scientific Ltd. (France) Miniparc du Verger - Bat. H

1, rue de Terre Neuve - Les Ulis 91967 COURTABOEUF CEDEX

FRANCE www.campbellsci.fr info@campbellsci.fr

Campbell Scientific Spain, S. L.

Psg. Font 14, local 8 08013 Barcelona

SPAIN w

Manualsnet FAQs

If you want to find out how the PS12LA Campbell Scientific works, you can view and download the Campbell Scientific PS12LA Power Supply Instruction Manual on the Manualsnet website.

Yes, we have the Instruction Manual for Campbell Scientific PS12LA as well as other Campbell Scientific manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Instruction Manual should include all the details that are needed to use a Campbell Scientific PS12LA. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Campbell Scientific PS12LA Power Supply Instruction Manual is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Campbell Scientific PS12LA Power Supply Instruction Manual consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Campbell Scientific PS12LA Power Supply Instruction Manual free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Campbell Scientific PS12LA Power Supply Instruction Manual, simply download the document to your computer. Once downloaded, open the PDF file and print the Campbell Scientific PS12LA Power Supply Instruction Manual as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.