073-0668 Rev. B

Xserve

Power Supply

Replacement Instructions

Follow the instructions in this sheet carefully. Failure to follow these instructions could damage your equipment and void its warranty.

Note:

Online instructions covering customer-installable parts are available at http://www.info.apple.com/installparts/.

Tools Required

No tools are required for this procedure. You may, however, nd a Phillips screwdriver useful in releasing the thumbscrews at the front of the server.

Opening the Server

The server slides open from the front of the rack. The top cover remains in place in the rack while the bottom housing (containing all internal components) should be placed on a sturdy, at surface.

Note:

Two people are required to slide the server open: one to depress the chassis levers and one to pull the bottom housing out of the rack.

1. Alert users that the server will be unavailable for a period of time.

2. Shut down the server.

Warning: To avoid damaging internal components or causing injury, always shut down the server before opening it. After you shut down the server, internal components can be very hot. Let the server cool down before continuing.

3. Write down the servers serial number, which is located on the back panel. If it is necessary to set up the servers software after you replace the power supply, you will be asked for the serial number at login.

Xserve Power Supply -

2

4. If the hard drives are in the locked position (the yellow security LED on the front panel is on), use the Allen key that came with the server to unlock them.

5. If the cable management arm is not in use, unplug all external cables except the power cord.

6. Touch the servers metal case to discharge any static electricity.

Important:

Always ground yourself by touching the servers case before you touch any parts or install any components inside the server. To avoid static electricity building back up in your body, do not walk around the room until you have completed your work and closed the computer.

7. Unplug the power cord.

8. Release the two thumb screws at the front of the server.

(Figure 1)

Note:

The thumbscrews are captive and do not separate from the bottom housing.

Figure 1

Xserve Power Supply -

3

9. Grasp the thumbscrews and slide the bottom housing forward part way to expose the two chassis levers.

(Figure 2)

10. While depressing both levers, pull the bottom housing all the way forward and remove it from the rack.

Figure 2

11. Place the bottom housing on a sturdy, at surface and ESD mat.

12. Put on the ESD wrist strap.

Xserve Power Supply -

4

Removing the Installed Power Supply

Warning: The power supply is a high-voltage component and should not be opened for any reason, even when the server is off.

Note:

There are two versions of Xserve. If your version does not include a plastic duct over the heatsink, skip to step 3.

1. Release the latch on the heatsink duct from its slot, slide the cover away from the blower, and lift the end of the duct as shown.

(Figure 3)

2. Remove the duct from the server.

Figure 3

Xserve Power Supply -

5

3. Release the locking latch on the power supply cable connector and disconnect the cable from the drive interconnect board.

(Figure 4)

4. Release the thumbscrew that secures the power supply to the chassis.

Note:

The thumbscrew is captive; you cannot remove it.

5. Grasp the metal ange of the power supplys connector (on the left side) and lift up to disconnect the power supply from the logic board.

Note:

You may need to loosen the left side of the power supply and then lift at another point near the front to disengage it. Do not lift the small lip that contains the thumbscrew.

6. Holding the power supply in both hands, remove it from the server.

Figure 4

Installing the Replacement Power Supply

1. Angle the replacement power supply into the bottom housing, so that the back end of the power supply ts against the inside back wall of the housing.

2. Press straight down to connect the power supply to the logic board.

3. Tighten the thumbscrew that secures the power supply to the chassis.

4. Connect the power supply cable to the drive interconnect board.

5. If necessary, replace the heatsink duct.

Xserve Power Supply -

6

Closing the Server

1. Carefully slide the bottom housing back into the rack.

2. Tighten the front thumb screws to secure it.

Warning: Never turn on the server unless all of its internal and external parts are in place and it is closed. Operating the server when it is open or missing parts can damage it or cause injury.

Apple Computer, Inc.

2003 Apple Computer, Inc. All rights reserved.

This document is protected under U.S. Copyright Law and International Treaties, and no part of this document may be reproduced in any form without written permission from Apple.

Apple is not responsible for typographical, printing, or inadvertent errors.

Apple Computer, Inc. 1 Innite Loop Cupertino, CA 95014-2084 USA + 1 408 996 1010 http://www.apple.com

Apple, the Apple logo, Mac, Macintosh, a

Manualsnet FAQs

If you want to find out how the Xserve Apple works, you can view and download the Apple Xserve v24 Replacement Instructions on the Manualsnet website.

Yes, we have the Replacement Instructions for Apple Xserve as well as other Apple manuals. All you need to do is to use our search bar and find the user manual that you are looking for.

The Replacement Instructions should include all the details that are needed to use a Apple Xserve. Full manuals and user guide PDFs can be downloaded from Manualsnet.com.

The best way to navigate the Apple Xserve v24 Replacement Instructions is by checking the Table of Contents at the top of the page where available. This allows you to navigate a manual by jumping to the section you are looking for.

This Apple Xserve v24 Replacement Instructions consists of sections like Table of Contents, to name a few. For easier navigation, use the Table of Contents in the upper left corner.

You can download Apple Xserve v24 Replacement Instructions free of charge simply by clicking the “download” button in the upper right corner of any manuals page. This feature allows you to download any manual in a couple of seconds and is generally in PDF format. You can also save a manual for later by adding it to your saved documents in the user profile.

To be able to print Apple Xserve v24 Replacement Instructions, simply download the document to your computer. Once downloaded, open the PDF file and print the Apple Xserve v24 Replacement Instructions as you would any other document. This can usually be achieved by clicking on “File” and then “Print” from the menu bar.